XWEB500
XWEB500
XWEB500
Ver 1.0
WARNING: TO PREVENT FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS APPLIANCE TO RAIN OR MOISTURE.
CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER (OR BACK). NO USER-SERVICEABLE PARTS INSIDE, REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. THE LIGHTNING FLASH WITH ARROWHEAD SYMBOL, WITHIN AN EQUILATERAL TRIANGLE, IS INTENDED TO ALERT THE USER TO THE PRESENCE OF UNINSULATED DANGEROUS VOLTAGE WITHIN THE PRODUCTS ENCLOSURE THAT MAY BE OF SUFFICIENT MAGNITUDE TO CONSTITUTE A RISK OF ELECTRIC SHOCK TO PERSONS. THE EXCLAMATION POINT WITHIN AN EQUILATERAL TRIANGLE IS INTENDED TO ALERT THE USER TO THE PRESENCE OF IMPORTANT OPERATING AND MAINTENANCE (SERVICING) INSTRUCTIONS IN THE LITERATURE ACCOMPANYING THE APPLIANCE.
WARNING: Use only modems supported by this monitoring unit. Dixell S.p.a can accept no responsibility for possible damage due the usage of not supported modems.
WARNING: Dixell S.p.a. reserves itself the right to alter this manual without notice. The last version available can be downloaded from the website.
WARNING: This controlling and monitoring unit is compliant with standard EN 12830 if it is used together with probes that are compliant with standard EN 13485
INDEX
INTRODUCTION................................................................................................................ 6 PACKAGING..................................................................................................................... 7 MINIMUM SYSTEM REQUIREMENTS FOR THE PC-CLIENT........................................ 8 1 GENERAL INFORMATION.............................................................................................. 9 2 INSTALLATION............................................................................................................... 9
2.1 HARDWARE............................................................................................................................. 9
2.1.1 RS485.............................................................................................................................................. 2.1.2 SERIAL ADDRESS................................................................................................................................. 2.1.3 THE TTL OUTPUT................................................................................................................................ 2.1.4 SERIAL ADDRESS OF THE INSTRUMENTS...................................................................................................... 2.1.5 TERMINATION RESISTOR.......................................................................................................................... 2.1.6 COMPATIBLE INSTRUMENTS .................................................................................................................... 10 11 12 12 12 12
3.3.3 SCHEDULER........................................................................................................................................ 31
3.3.3.1 PRINTING EVENTS........................................................................................................................................................ 36 3.3.3.2 USING THE SCHEDULER.............................................................................................................................................. 38
3.3.4 ALARMS............................................................................................................................................. 40
3.3.4.1 ALARM TYPOLOGY AND ALARM LEVELS.................................................................................................................... 40 3.3.4.2 DESTINATION OF THE ALARM MESSAGES................................................................................................................ 41
3.3.4.3 ALARM LEVELS.............................................................................................................................................................. 41 3.3.4.4 ALARM TYPOLOGY MANAGEMENT .................................................................................................................................................................................................... 42 3.3.4.5 QUEUED MESSAGES.................................................................................................................................................... 43
3.8 PERMISSIONS....................................................................................................................... 85
3.8.1 MANAGING THE USERS............................................................................................................................ 86
5 APPENDIX.................................................................................................................... 91 APPENDIX A: DEVICE ADVANCED SECTION............................................................... 92 APPENDIX 0: GLOSSARY............................................................................................... 94 APPENDIX 0: SUPPORTED INSTRUMENTS.................................................................. 96 APPENDIX 0: ACCESSORIES....................................................................................... 100
INTRODUCTION
Congratulations! This manual will teach you everything about XWEB 500 server, the most powerful and configurable tool for Controlling and Monitoring. This manual is a comprehensive guide to your XWEB 500. You will find all the information you need to work with the unit. The XWEB 500 is based on the latest technology of the Internet world to display the WEB pages contained into the unit itself. The Linux operative system guarantees maximum efficiency and stability support for this kind of product. All future software releases developed by Dixell will be available via internet connection. The Hardware inside the unit, based on high performance electronic boards, does not require any maintenance.
6/103
10/01/2006 - 1592010900
PACKAGING
Unpack the unit carefully and make sure that all accessories are put aside so they will not be lost. Examine the unit for any possibility of shipping damage. If your unit is damaged or fails to operate, notify your dealer immediately. If your unit was shipped to you directly, notify the shipping company without delay. Only the consignee (the person or company receiving the unit) can file a claim against the carrier for shipping damage. We recommend that you retain the original carton and packing materials for use should you transport or ship the unit in the future. Inside the box you must find these articles: The XWEB 500 server unit [1]. One CD Rom containing the Operative manual and software [2]. USB and power supply [3] Quick setup manual (Fast installation) [4].
If one of the above items is damaged, do not hesitate to contact your supplier.
MODEM (not included) When working with the modem connection always check the kind of modem you are going to install by verifying, with Dixell, the complete compatibility with the XWEB 500 unit. Dixell is not responsible for bad functioning of unknown or untested devices.
10/01/2006- 1592010900
Pag. 7 / 103
8/103
10/01/2006 - 1592010900
1 GENERAL INFORMATION
XWEB 500 is a Controlling and Monitoring system based on WEB server technology. It is capable to communicate data to one external Client with the same kind of procedure used by the Internet Web Sites. Client need only a standard Browser such as Microsoft Explorer or Netscape. The Web Pages with all the information are contained into the server itself; Linux operative system ensures maximum efficiency and security. The server reads, logs and checks the data coming from the Dixell instruments connected to a RS485 line. The communication protocol is the Modbus-Rtu. The XWEB 500 is capable of recognising also most of the Modbus-Rtu compatible instruments not manufactured by Dixell. ATTENTION: Always check the proper RS485 connections (see 2.1.1 rs485) ATTENTION: Dixell S.p.a. reserves itself the right to analyse the Modbus-RTU compatibility of other manufacturers devices before ensuring their integration into XWEB 500 system. Clients to Server connection possibility: Modem: point to point through local and remote modem devices (Creating a Remote Access under Windows); Local USB cable: Before pluging-in the USB cable, please install the connection software provided with the cd-rom. You can plug the provided USB cable into labelled USB socket of XWEB 500 and on the other side into your PC USB port. Intranet / Internet: where available a static IP, using the standard socket 10 Base-T with RJ45 connector. Cross over ethernet cable: You can plug a bridge network cable into RJ45 socket of XWEB 500 and on the other side into your PC network adapter. Ask your network administrator to properly setup your PC to be able to access XWEB 500 web pages.
The User interface is defined by the Browser program and it is the same for all kind of connections. The PC-client needs only a standard Browser, there is no need to install any kind of software Some pages created by the web server rely on Java and they need the Java Virtual Machine program that is normally installed in the latest Browsers and operative systems. Check the different connection under 2.1.8 Local connectivity. Features and functions included into the XWEB 500 management: Data monitoring and recording, alarm detection and recording of the instrument connected. Alarm management defined by the User with visible signals (onboard led), or relay switching or remote transmission via Fax, E-mail or sms. Interactive commands to manage the connected instruments. Parameter table programming. Graphic or table viewing and printing of the recorded data.
2 INSTALLATION
2.1 HARDWARE
ATTENTION: to protect both yourself and the server from electrical hazards the XWEB 500 should remain
10/01/2006- 1592010900
Pag. 9 / 103
turned off until you are finished connecting all electrical devices to the unit. To avoid accidental start of the unit, remember to plug in electrical cable only when you have finished setting up all other connection.
1 2 3 4 5 6 7 8 9 10 11 12 (+) 13 (-) 14 ()
: USB socket for PC connection : System Alarm :5-6 No Alarm :5-7 At least one alarm : modem reset relay : digital input : USB socket for devices connection : External modem socket : Internal modem line connector : RJ45 Ethernet connector : RS 485 socket
2.1.1 RS485
To be connected to the serial line all the Dixell Modbus instruments must be provided with direct RS485 terminals or the TTL-RS485 interface (XJRS485 or XJ485). Check the instrument manuals for more information. The RS485 line is mainly based on two polarised terminals. Please beware to respect the right sequence for all the devices connected to the serial line.
Follow these important advises: The RS485 serial line must reach all the instruments where they are installed. Beware to the wire polarities when screwing them into the instrument terminals.
10/103
10/01/2006 - 1592010900
Wrong connection
Always keep the usb cable away from power cables. Always keep the usb cable away from electro-magnetic or frequency sources. Do not connect shield to ground. Do not connect the Gnd terminal. Remember to draw a map of the line. This will help you to find an error if something is wrong. The instrument with RS485 have + and - terminals, respect the polarity. To keep the line balanced it is necessary a 100 Ohm resistor at the end of the line (you ca use the RS 485+ and RS 485- terminals of the last instrument connected).
10/01/2006- 1592010900
Pag. 11 / 103
All controllers equipped with 2 serial addresses (XC400/600/800/900, XH200/300/400 etc.) must be used with both addresses equal. iCHILLs need to activate a particular value in the Advanced section. User must check Force Device On status. Remember to stop-start acquisition after this operation. To use non Dixell, but modBus compatible controllers (such as Energy Analyzer by Carlo Gavazzi) follow this instructions: a) Go to Configuration then Devices. b) On the drop down menu Actions select New.... c) A new pop-up window will appear: fill in the blank with the name of the controller and the ADR. d) Choose the proper device model (e.g. ENERGY_800000000000000). e) Press Create
12/103
10/01/2006 - 1592010900
It represents the most common method where the LAN (intranet / Ethernet / internet) is not available. It is strongly advised to use a dedicated telephone line. IMPORTANT: Use exclusively modem devices approved by Dixell. Remember that many modems are not compatible with Linux. The list of compatible models can be found under the menu: Configuration System - Modem. In appendix E, you can find the complete list of accessories together with their commercial name. Dixell can provide you these modems. You can decide to buy them in your country, but do not use different models from the ones stated here. Dixell is not responsible for any action depending on a modem that is not present in the official list of supported accessories. External Modem. Connect the modem to the COM Port on the back side using the modem cable commonly included into the modem packaging itself. The reset of XWEB modem is directly controlled by the XWEB 500 Server through the COM port, but if you use a GSM modem remember to use the external relay to cut the modem power supply to reset it. Connect the modem to the telephone line with the phone cable included into the modem packaging. Remember to check if there is a switching machine (add the prefix digit). The connection procedure is divided in two parts: In the first part it is necessary to create the Remote Access, in your remote PC, set with the telephone number of the line where the XWEB 500 is connected to. You have to use Dixell as Username and Password. The second is the procedure you will ever use: after launching the new Remote Access that will engage the line via the modem, start the Browser from your PC and insert the address http://192.168.0.150 into Explorer/Netscape address bar. Proper information about setting up a dial-up connection for the client PC, can be found inside the INSTALLATION MANUAL on 4.3. 2.1.7.2 INTRANET / ETHERNET CONNECTION
The Intranet or Ethernet connection should be initially managed by the net administrator which will assign one free IP address to reach the Server. This number is an example of what you should expect: http://192.168.000.111. After receiving the address from your network Administrator the XWEB 500 must be set with this number. Use a standard RJ45 network cable to connect the unit to your existing LAN. The Intranet method allows the connection to interact with XWEB 500 from all the PC Clients. Insert the net address assigned by the administrator into the Browser address bar. Bookmark the address with personalised name for the future connections.
10/01/2006- 1592010900
Pag. 13 / 103
2.1.7.3 INTERNET CONNECTION It is necessary a STATIC IP address for the XWEB 500 which is normally assigned by the Provider of your internet services. The Internet connection allows XWEB 500 to be reached from all PC-clients. Insert the net address assigned by the administrator into the Browser address bar. Bookmark the address with personalised name for the future connections. Ask your provider for more details about the rent of a static IP. This the internet system requirements for the best result: Wide band connection. At least 1 static IP addresses for the XWEB 500.
The internet connection is established through a device called Router that receives and sends the data as interface between an Intranet and Internet. The Provider also assigns the address of the router that is called IP WAN. Remember that the default value of the IP of the XWEB 500 is: 192.168.0.150. Depending on the contract the Provider can also supply the router, otherwise the user can buy it separately. REMEMBER: ask qualified personnel for the router installation by using this information: Used ports that are mapped to the LAN side: 22 (used for SSH connection) 80 (used for the http:// access) 42 (tcp and udp) towards the name server you choose 53 (tcp and udp) towards the name server you choose The above ports are all related to the XWEB 500 IP address 192.168.0.150. While the ports on the WAN side are: Telnet (to configure the router from a remote, also via Internet) http (To access the XWEB 500)
14/103
10/01/2006 - 1592010900
configuration is it possible to remove the local connection and work only via the on-board keyboard and display. For complete information on how to connect to the unit, please refer to the Installation Guide. In the cd-rom is available a software to automatically setup the PC for the USB connection.
10/01/2006- 1592010900
Pag. 15 / 103
16/103
10/01/2006 - 1592010900
2. From the TAB Privacy, apply the Default settings and press the button Settings on the bottom right corner.
10/01/2006- 1592010900
Pag. 17 / 103
18/103
10/01/2006 - 1592010900
Please remember to add each IP address you will use to this list.
far as firewall is concerned, add port 80 and port 22 to the allowed ports forwarding, of course all the TCP/IP requests coming from the IP address of XWEB 500 must be allowed.
10/01/2006- 1592010900
Pag. 21 / 103
22/103
10/01/2006 - 1592010900
PRIMARY/SECONDARY DNS: In the internet world you can reach a web server using its name, for example www.dixell.com, digiting the name into your web-browser address bar. Due to the protocol used to guarantee performance and security, all names are converted into IP numbers. This operation is made by a DNS server. Usually your ISP or your network administrator can provide you a valid DNS number. DNSs are also mandatory to use e-mail and the internet upgrade procedure.
24/103
10/01/2006 - 1592010900
already been done, you can send a test e-mail/SMS/Fax by pressing the proper button.
26/103
10/01/2006 - 1592010900
These items represent the name of server and its description. Time
Server Status
3.2.4 ALARMS
This area immediately on the right hand side shows the currently active alarms of the instrument. The alarm list is repetitively updated in a short time interval. To manually force the alarm updating: click on the Active Alarms
Adjust the address range and push Start. During the RS485 polling Tx/Rx led blinks and this windows will appear:
When the search is complete a new window will appear. To use the new controllers, under Operation column check the box Insert, then push Add.
3.3.2 CATEGORIES
28/103
10/01/2006 - 1592010900
This function allows you to define the functioning attributes and the working features of the instruments themselves. The user is required to preventively decide the list of these features. Lately, when working with the Device configuration, each device can be easily configured with these appropriate attributes. Some categories can be defined also with Default. In this case the category is initially proposed as default during the instrument configuration. Click on Configuration Category roll-down menu.
3.3.2.1 DEVICE TIPOLOGY This category defines the application at which the instruments belong to. Up to 5 different category can be defined. Eg: Display cabinets Frozen food, Meat Room, Air Conditioning, etc. To insert a new item Click News and then into the field Name. Insert the word or the words that more represents the application; . The most common category should be set as Default by clicking into its box; Only one Default can be selected for each category; Click Insert do include the new item into the list. Wait the screen refresh. To modify an existing item Click on the name-field and modify it, then press Modify; Click the Set as Default if necessary; To delete one of the item of the list Click on Cancel; Confirm the operation if necessary. Wait the screen refresh. To reset all the items of the list Click on new; Wait the screen refresh.
3.3.2.2 RECORDING INTERVAL Define the recording intervals of the instruments to log the data into the archive. Eg: Standard = 15min., Fast = 3min.. XWEB 500 can define different log intervals for different instruments when the log frequency is not the same for all the instruments. To insert a new item Click News and then into the field Name. Insert the word or the words that more represents the application;. To modify an existing item Click on the name-field and modify it, then press Modify; Click the Set as Default if necessary; To delete one of the item of the list Click on Cancel; Confirm the operation if necessary. Wait the screen refresh.
10/01/2006- 1592010900
Pag. 29 / 103
3.3.2.3 RTC SYNCRONIZATION In this section user can decide how often to synchronise the controller equipped with a real time clock. Interval is expressed in hh:mm. The maximum value accepted is 12:00. It means that every 12 hours a synchronise-command is sent to the controller. To enable a controller, the user has to go to the Devices page and check the RTC Sync checkbox.
30/103
10/01/2006 - 1592010900
3.3.3 SCHEDULER
This is a powerful tool for managing category and repetitive commands. Now it is possible to send command to a set of controllers and have a visual chart. This feature, for instance, is very useful to avoid command time-overlap. To start the Scheduler, use the drop-down menu Configuration, then Scheduler. This window will appear (Java is required):
On the bottom there is a timeline (00:00 to 24:00), each hour is marked with a vertical line. This main window is very useful to build a complete time table in a very easy and fast way.
File Submenu:
SAVE
This function allow you to save the changes done till now. Beware that the system can not go back to a previous save, only the last one is available.
EXIT
Class Submenu:
CREATE CLASS
By using this menu it is possible to create a new class.
10/01/2006- 1592010900
Pag. 31 / 103
Fill in Class Name field, then pick up a Category. Wait for the complete list of the controller. Check all the controllers you want to send a command and push Add Command event. If you want to manage a timescheduled printout, please choose Add printing Event.
Choose a command, then fill in Activation Time. Choose a marker and its colour. Push Confirm to add this event to the Scheduler. After having selected Add Printing Event, use the drop-down menu Fast Selection, or if you prefer you can also select all the analog values manually. Insert the time schedule Activation Time and the Marker Colour. Press Confirm
32/103
10/01/2006 - 1592010900
For instance the The fast selection set to H.A.C.C.P Probe 1 produces the following output:
It is shown Site name XWEB 500, printout name H.A.C.C.P. printout, date and time, address of the controllers, name of the controllers and analog values.
EDIT CLASS
10/01/2006- 1592010900
Pag. 33 / 103
choose the class you want to modify then press Edit. If you want to delete a class, choose it and press Delete.
Event submenu:
ADD EVENT
To add an event to an existing class.
Choose a class then select a command. Fill in Activation Time. Choose a marker and its colour. Push Confirm to add this event to the Scheduler.
The system loads the same menu already discussed at point D).
34/103
10/01/2006 - 1592010900
Choose a Name and a colour. Mark Yearly option if you want this day definition applied to all available years.
When you defines a new day, please note that the system automatically uses the command chart present in that moment in your PC screen. This means that the first time you start working with the scheduler the default day is displayed. Point a day, then with left mouse button click on it. A menu with all the available day definitions will appear.
DELETE DAY
Windows submenu:
SHOW LEGEND SHOW CALENDAR SHOW LOGS
10/01/2006- 1592010900 Pag. 35 / 103 This menu shows all the command marker used.
It is possible to filter all the command sent using From, To and Class.
This menu filters only the commands. This menu filters only the printing events.
Days submenu:
DAYS
It allows to switch between different days definition. 3.3.3.1 PRINTING EVENTS If you want to manage a time-scheduled printout, please choose Add printing Event.
36/103
10/01/2006 - 1592010900
Choose a command, then fill in Activation Time. Choose a marker and its colour. Push Confirm to add this event to the Scheduler. After having selected Add Printing Event, use the drop-down menu Fast Selection, or if you prefer you can also select all the analog values manually. Insert the time schedule Activation Time and the Marker Colour. Press Confirm
For instance the The fast selection set to H.A.C.C.P Probe 1 produces the following output:
10/01/2006- 1592010900
Pag. 37 / 103
It is shown Site name XWEB 500, printout name H.A.C.C.P. printout, date and time, address of the controllers, name of the controllers and analog values.
3.3.3.2 USING THE SCHEDULER Once you have created a schedule it is possible to check or modify an existing event in a very simple way. Use left mouse button and click on it. If there is a marker overlapping (this means that 2 or more events start at the same time), the applet will show you a brief list of all the event available. With left mouse button you can select the one you want to modify or delete.
38/103
10/01/2006 - 1592010900
10/01/2006- 1592010900
Pag. 39 / 103
3.3.4 ALARMS
3.3.4.1 ALARM TYPOLOGY AND ALARM LEVELS
The alarm typology is a list of alarm events designed by the user to describe the possible alarms that the instruments can generate. In this way similar alarm events can be grouped together under a unique identification label, so high and low temperature alarms can be defined as Temperature alarms or the high and low pressure alarms belong to Pressure alarm identification. The Alarm Level list is also designed and named by the user. Each alarm level can be assigned with one or many alarm typologies. The alarm level starts the appropriate action in case of alarm event and depending on the level of alert it transfers the information via fax or e-mail with appropriate messages or turn on relais etc.
40/103
10/01/2006 - 1592010900
3.3.4.2
The list of the destinations contains the users (directors, maintenance personnel, assistance etc.) enabled to receive the alarm notification. The XWEB 500 is capable of transferring the alarm message through Fax or e-mail. To insert a new item Click into the field Name and insert the appropriate word or words. Click on Insert to add the new value.
To change the setting Click into Selection and find the desired item from the list. Click into the desired fields and change them with the appropriate values. Click on Modify. To delete an item Select the user to delete. Click on Cancel. To delete all the items of the list Click on Cancel All; Confirm the operation if necessary. Wait for the screen refresh. To reset the form Click on new.
For each receiver the calendar function is also suitable to enable the alarm sending procedure only during certain period of time. See Calendar chapter. 3.3.4.3 ALARM LEVELS
The alarm levels are organised as a list of items. Each named level provides to execute the right procedure to transfer the alarm notification to the receiver or receivers. They act just like a filter. E.g: an alarm belonging to the Temperature alarm typology can be differently treated from the no-link alarm so as the destination and the kind of message is suitable to a proper information about the alarm event itself. The alarm level also assigns the number of receivers and the transmission mode (Fax and E-mail). It is also possible to switch on/off the status of the onboard relay. Check/uncheck AUX1 or AUX2 in the proper page. In the back of the unit you can find the relay outputs.
WARNING:
Terminal blocks for relays AUX1 and AUX2 can not be used for switching high voltage loads (24V or higher). Use a low voltage circuit to manage your loads.
The easiest method to work with levels is to define three kinds of alarms corresponding to Severe alarm, Standard alarm, Warning. Each alarm typology, depending on its importance, can be linked to one of this three alarm level to alert different personnel. It is also allowed to define as many alarm levels as the existing alarm typology in order to transfer complete information about each alarm origin. Under the device configuration paragraph you will learn how to assign the designed alarm typologies and alarm levels to each instrument. This multilevel structure gives the maximum flexibility and it comes to solve every kind of alarm management problem.
10/01/2006- 1592010900
Pag. 41 / 103
Insert a new Alarm Level and the attributes Click into Name and insert the word(s) that better represents the alarm e.g.: Severe Alarm.
To insert the Receiver Select the Receiver. Click the kind of procedure to send the alarm (Fax, E-mail). Click on Insert to add the new item. To modify an item Select the item from the Selection roll down menu. Modify the appropriate fields. Click on Modify. To delete an item Select the user to delete. Click on Cancel. To delete all the items of the list Click on Cancel All; Confirm the operation if necessary. Wait the screen refresh. To reset the form Click on new To use the on-board buzzer Click on Buzzer. If the option is unchecked, during an alarm the buzzer will not be activated. ALARM TYPOLOGY MANAGEMENT
3.3.4.4
The alarm typology list, designed by the user, groups the common alarm features of the instrument into an
42/103
10/01/2006 - 1592010900
unique definition. For instance all the temperature alarms that are not important can be defined by a typology named as Normal Alarm while the temperature alarms of the frozen food can be identified by the typology Severe Alarm. The user can assign a typology name for the desired alarm event such as: High temperature, low temperature, High or pressure, open door, compressor oil, Frozen food, etc The user can define the accuracy of the alarm description Each typology can define the following: One of the alarm level previously defined to send the alarm. The Delay time that defines the minimum duration of alarm. The alarm must be longer to be computed, otherwise the system will only record the event in the alarm historical list. The accumulation time that defines the time when the alarm will be sent. This time will be counted only if the alarm lasts more than its delay time. For each alarm the user can insert the appropriate word(s) that represent(s) the alarm transmission.
Click into the Name and insert the appropriate word(s) to describe the alarm typology. Assign the alarm level procedure under Level. Define the Accumulation time and the minimum activation time or Delay of the alarm. Insert the appropriate message header into the corresponding fields. To modify the item From Selection find the desired item. Change the wrong description. Click on Modify. To delete an item Select the item to delete. Click on Cancel. To delete all the items of the list Click on Cancel All; Confirm the operation if necessary. Wait the screen refresh. To reset the form Click on new
3.3.4.5 QUEUED MESSAGES The fax message can be sent to a back-up number (Second fax number). If the first number is engaged or the line is unavailable, the system tries to send the message to the second fax number.
The XWEB 500 use the Calendar as filter before activating the resource itself, if the resource is not Enabled in that period nothing happens. The alarm procedure to inform an Assistance Centre or the light on function can be override by their appropriate Calendar programming. The number of Calendars is not limited and each Calendar can manage more than one resource. The Calendar is based on a weekly list extended for all the month, the tile colour shows the function related to that day The day is divided in: Enabled Partly Enabled Disabled Green colour; Yellow colour; Grey colour.
Disabled day represent the 24 ore where the resource is not active (eg holiday). Enabled and Partly Enabled days can accept the period of activity of the resource.
Setting the daily period activity for all the week (Eg: define Saturday and Sunday as Disabled, Wednesday as Partly Enabled). Select the appropriate month: Point the mouse arrow on the rose tile Saturday. Click with the left button and then set the value as Weekly not Enabled. The tiles become Grey.
44/103
10/01/2006 - 1592010900
Repeat the operation for Sunday. The tiles become grey. Click with the left button of the mouse on the rose tile Wednesday and select Set As Weekly Partly Enabled. The tiles become yellow.
Define the period of activity of a day (Eg: from 08:00 to 20:00 for Enabled day and from 08:00 to 13:00 for Partly Enabled). Under the Individual Day Time Band click into From and set 08:00 then click into To and set 20:00. Click on the button Set for All Enabled to active the new period for the Enabled day.
10/01/2006- 1592010900
Pag. 45 / 103
All the working days (Enabled) will follow the new times. Repeat the same operation to define the new period for the Partly Enabled days but clicking on Set for All Partly Enabled DAY ATTRIBUTE To verify the day attribute point the mouse arrow into the appropriate day and click the right button.
Single day setting The attribute of a single day can be defined as follow: Point the mouse arrow into the appropriate day; Click on the left mouse button and select from the list the new attribute: Set As Enabled Only that day as Enabled. Set As Not Enabled Only that day as Not Enabled. Set As Yearly Not Enabled Only that day as Enabled for all the years. Set As Partly Enabled Only that day as Partly Enabled. Set As Yearly Partly Enabled Only that day as Enabled for all the years.
46/103
10/01/2006 - 1592010900
Select a limited period of days To define a common attribute only to some days. This allows to set a holiday period for one or more desired months of the year. Point the mouse on the first day desired, click the left button. Keeping the left button pushed move the pointer slightly through the next days to be included. Release the mouse button and select the proper attribute, all the selected tiles will change into the new corresponding colour.
Calendar Management Under this section the three button allows to save a new calendar format, load or delete it.
to create a new calendar. As default Sunday and Saturday are not enabled. to save the new or modified calendar structure. to delete the displayed calendar. to save the displayed calendar with a new appropriate name.
10/01/2006- 1592010900
Pag. 47 / 103
Please go to Configuration -> Devices roll-down menu. This window will appear:
By using Device drop-down menu you can select which controllers to show.
48/103
10/01/2006 - 1592010900
If the instrument has not been already renamed the identification name is: New_Model-name where: New means that the name has been assigned automatically by the system; Model-name define the instrument model.
Instead of xxx_New_Model the user can insert the new appropriate name for this instrument. 3.3.6.2 ASSIGN THE NAME OF THE CONTROLLER
After selecting the device, click into the Name field. Insert the new name such as Frozen food_001. Assign the proper sampling Interval, decide if you want to read and record data from this instrument by checking/unchecking Data Reading and Recording boxes. Data Buffer is an useful function that stores with the maximum speed available lots of data values (regardless of sampling interval) when an alarm occurs. Ten minutes of data values before and 5 after the alarm are recorded at maximum speed if Data Buffer box is checked. Finally if you need to synchronize the on-board RTC of the controller, select RTC. Click Modify now or at the end of the whole configuration.
10/01/2006- 1592010900
Pag. 49 / 103
3.3.6.3
Be sure of having selected the right instrument under the Device menu. Depending on the instrument model there are different available categories to define the attributes of the instrument itself. If you do not find the right one maybe it is not defined or it is not available for that instrument. By itself XWEB 500, after the recognising procedure, assigns the default categories (if you checked the box in category window) to the devices connected to the RS 485. To change the category click inside the field and select the appropriate item. Click Modify now or at the end of the whole configuration. 3.3.6.4 ASSIGN THE ALARM TYPOLOGY
Be sure of having selected the right instrument under the Device menu. ALARM ORIGIN: depending on the instrument model there are different available alarms, if you do not find the right one it means that it is not available for that instrument. NAME: each alarm can be assigned with an appropriate label defined by the user, this label is also used when it is displayed by the system. Click inside the Name and modify it. TIPOLOGY: links alarm type to the proper Alarm typology. If you do not find the proper action in it, step back to the Alarms definition to insert the new features into a new alarm typology. SH (Show): when it is enabled th alarm is showed in main page. SND (Send): when it is enabled the alarm is sent by XWEB 500. REC (Recording): when it is enabled the corresponding alarm is logged. Click Modify now or at the end of the whole configuration.
3.3.6.5
The middle area is dedicated to the analogue inputs (probe), setpoint, digital inputs, devices status, and commands assignments.
50/103
10/01/2006 - 1592010900
NAME: The first time each name is displayed by following the internal XWEB 500 archive of standard feature of the instruments. Each definition can be renamed when necessary to give the proper meaning. Beware of the difference between integer and decimal value. Instruments are factory preset to decimal point, so if you change this value to integer you need to make the same change inside XWEB 500. All default labels are intended as decimal, when you change to integer a postfix -I is shown. It may happen that you move to integer using advanced properties (see Appendix A), then coming back to label name and changing it without using -I you completely loose the information you are displaying integer. This may be a problem because when you come back to advanced section there is no more difference between decimal and integer. To change a name simply click inside its field and modify it. Unit: The analogue input is followed by the proper unit of measurement, change the unit by clicking in it then insert the new value. Beware that in this window you can change only the label of the unit of measurement. In Advanced section you can change the behaviour of the instrument (e.g. Celsius or Fahrenheit degree) Click Confirm now or at the end of the whole configuration. Delete one device from the list Stop acquisitions. Select the instrument to delete. Click on Cancel in Action menu. Advanced function The Advanced key allows to reach another configuration area dedicated to the instrument setup. This area is very dangerous because this configuration defines important features that can badly affect the unit if not properly set. Take care of this advice and ask authorised personnel before trying any kind of setting. You can find more complete information in Appendix A. 3.3.6.6 CLONE FUNCTION This function is intended to let the user save a lot of time during the first setup of the XWEB 500. By using this function the system will broadcast the current instrument setup to all the other that are compatible. The compatible instruments are only the ones who belong to the same model. In this situation the user is requested to made only one setup, then using clone button in few seconds (depending on the total number of instruments) the configuration will be applied to all the other controllers. In the first step you are required to make a complete setup regarding both standard and advanced section. When you are ready, please go to Configuration -> Devices roll-down menu. This window will appear:
10/01/2006- 1592010900
Pag. 51 / 103
In the upper part you can see information concerning the name of the instrument that the system will use as base model (Source device). In our example we have a XJP60D whose name is Acq. module 1. It is possible to change the name of the Target device by clicking in the field Name. By clicking Clone button XWEB 500 begins to broadcast this setup to all the compatible instruments. Once it has finished a summarising window will appear. It is also possible to decide to clone both the typology and the recording interval by ticking the corresponding columns.
Check/uncheck the proper action and push Apply. Data reading: XWEB 500 will only read data coming from RS 485.
52/103
10/01/2006 - 1592010900
XWEB 500 will record data coming from RS 485. XWEB 500 will send alarms coming from controllers.
The devices can be selected using the Device filter in order to reduce the number of items of the search. From the Device filter roll down menu select the category to which the instruments belong to. Then, under the Select a device menu select the instrument you are interested in. After some seconds the whole situation of the instrument will be loaded and displayed. The information is divided in horizontal rows such as analogue inputs, Set points, digital inputs, device status, outputs status, alarms and commands. A grey label means a function not active at that moment, on the contrary a blue label means an activated function.
10/01/2006- 1592010900
Pag. 53 / 103
Remember that you are looking at a still page therefore the instrument information is loaded and displayed then there is no more data coming from the server. The screen refresh with the new data can be executed automatically by selecting the Auto box and decide the updating interval by clicking into the time box on the right side. Click on Update button to update the window with manual procedure. Change set point function You can change on the fly the set point value by clicking inside the box:
A window will appear, asking you the new value, confirm the new set point by clicking OK button.
54/103
10/01/2006 - 1592010900
Commands The last stripe of information contains the available commands for that instrument. Use them to operate on the instrument. Take care of the operations you make with commands. Click on the interested function button, after sending the command the information of the new status will be automatically updated and displayed.
10/01/2006- 1592010900
Pag. 55 / 103
Each device is represented by an horizontal row that includes as many rows as many information are available from the instrument. For each row, the blue bar contains the address and the instrument name followed by the typology to which the instrument belongs to. At the end of the blue bar there is the command box Sel. The second row of a main row contains the set-point and the analogue inputs like the probe values or other peculiar information of the instrument read-outs such as the electrical measurements of a net analyser. The third row of a main row is divided in three parts: the first area contains the icon symbols of the instrument status, the second area contains the icon symbols of the instrument outputs (relays) and the third area shows the digital input status with their complete description. An icon not surrounded by a blue square means the corresponding function is not active. The active status of an instrument function is represented with the corresponding blue icon. More information about the icon function can be red, pointing the mouse arrow over a single icon, on the left down corner of the browser border. Devices in alarm In case of alarm event the corresponding instrument is signalled with the red blinking description. Immediately also the message box, on the top of the browser bar, will indicate the alarm situation with a red Alarms label.
Find the complete alarm description clicking on the row blue bar. 56/103 10/01/2006 - 1592010900
A pop up message box will appear, inside you will find the list of the actual alarms that also includes the starting date of each event.
Send the commands to devices From the run time page you are allowed to interact with the instruments by sending commands to them. The user is requested to select the instrument or the instruments to which the command has to be sent. To do that click into the Sel. box to select the instrument.
On the right top side of the browser border will appear a Toolbar which contains the Commands button and the possibility of selecting or deselecting all the instruments together. To define the command to send click on Commands and immediately a choice list will appear. For multiple selection of some or all instruments the available commands will be only the common commands among the instrument selected. Select the command and click on Send button. Before proceeding a message box will tell you how many instruments are involved.
10/01/2006- 1592010900
Pag. 57 / 103
The popup box also shows, with a blinking message, the status of the operation just executed and then also the ending report result. If an error occurs the corresponding diagnostic message is displayed.
58/103
10/01/2006 - 1592010900
3.5.3 PARAMETERS
The Parameter function allows management of the parameters of a selected device. The parameters can be displayed and modified. From the Home Page, select the Parameters item from the Devices menu. From the Actions select one of the following functions:
Load from Device: Load from File: Write on Device: Write on Devices: Save on File:
to load and display the parameters from a device; to load and display the parameters from the Hard Disk of the Client PC to updated the displayed parameters into the selected device; to updated the displayed parameters into the selected devices to save the displayed parameters into the Hard Disk of the Client PC.
To show the parameters of a device select load from device from the action menu: Use the filter mask to limits the range of the device selection:
DEVICE TYPOLOGY:
Select a Device: Select a Group: Select Menu:
To filter among the different typologies (All includes all the instrument); To select the desired instrument; To defines only a limited group of parameters to load; To defines which is the parameter level to use (Pr1, Pr2, All).
After filling the filter mask, click on Read button to load the parameter from the instrument to the client pc. The loading time depends on the number of parameter selected.
The parameter table is defined by these columns: Label: Description: Actual: The parameter label as described into the instruction manual of the instrument itself; Description of the parameter function; Actual value of the parameter loaded from the instrument; 10/01/2006- 1592010900 Pag. 59 / 103
New value of the parameter decided by the user; Minimum and maximum limits available for that parameter; Unit of measurement; Parameter level of the parameter itself; Selection box to enable the parameter saving.
To change a parameter value To insert the desired value of a parameter click into New box. Depending on the kind of parameter, it is possible to insert the value or select it from a drop-down list of available values. To confirm the new value introduced click the mouse outside the New box area. It is not allowed to set a value exceeding the minimum and maximum limits. In any case a wrong value is signalled with violet background colour of the box itself. The user can change one or more parameters before sending back the new list. To change the programming level Select 1 level or 2 level under the Pr column. To send the new parameter map to the instrument After modifying the parameters, select Write on Device from the Action menu. To confirm the operation click on the Ok button into the message box. To send the new parameter map to the instruments The displayed parameter map can be sent to many compatible devices. Select Write on Devices from the Action menu. The message box will show all the compatible instruments with that map. Select which instruments are included (or All). Click on the Write button to start the procedure. A warning box will appear reminding you how many parameters you are changing. Each writing operation is described into the message box. At the end of the operation a conclusive report will be showed. To save the parameter in your Client PC The parameter can be saved into the hard disk of the Clients PC, reloaded and used for other parameter programming. With a displayed parameter list, click on Save on File from the Action menu. Select the Save box to include the interested parameters. Click on the Save button situated in the top right position. Click on Save All button to save the complete list. Some operative system installed into the Client PC can require to Save before proceeding. From the next message box insert the name of the parameter map and then click on Save. To load a parameter map saved into your Client pc Click on Load from File from the Action menu. Use the find button to search among the files of the message box. Click on find or insert the file name including the path. These system always proposes the last folder used during the last saving. Confirm the name of the file to load. Click on Upload to proceed.
60/103
10/01/2006 - 1592010900
To print the displayed map Click on Print from the Action menu. Use the message box to select the print properties. Confirm the printing to proceed.
With this function it is possible to build up a Layout view of the system been monitoring. The user can creates as many layers as he needs and place important information and data value coming directly from the instruments. XWEB 500 uses 2 different menus to deal with Layout: one is Layout Edit, the other is Layout Viewer. Both of them use web-technology, so Java Virtual Machine is needed. More importantly that all data information is stored inside the XWEB server and it is pushed dynamically to your client. This means that according to the connection speed pages could take different loading time. The Editor is the most important part, we start discussing it first. We strongly suggest to set client PC resolution to 1024 x 768 pixels and use the same resolution for the background images. 3.5.4.1 LAYOUT EDITOR To start Layout Editor, go to Devices then choose Layout Editor. If this is the first time you run the Layout, a blank windows will appear. The available menus are:
File Submenu:
NEW LAYOUT
This function is used when you want to start a new Layout. Beware that the system can only manages one layout per time. There is no possibility to save a Layout with a particular name and then build up a new one.
SAVE
This function allow you to save the changes done till now. Beware that the system can not go back to a previous save, only the last one is available.
LOAD
10/01/2006- 1592010900 Pag. 61 / 103
EXIT
Layers Submenu:
ADD LAYER
It is used to add a new layer to the layout. Selecting it this windows will appear:
User has to compile Name with any text value, then he can choose the background colour and also a background image pushing Image button. In this case a new window will appear:
62/103
10/01/2006 - 1592010900
Choose an image and press Ok. When you use images the system has to send them to your client. Depending on the speed of the connection the download procedure may take up to some minutes. According to the client screen resolution the system will load up a new page. The real dimensions (width and height) come from the monitor setting of the client itself. The system later is capable of dynamically resize this value to show images and layers in a proper format. We strongly suggest making some test before proceeding with the complete layout design. Usually images are taken with a digital camera. Beware do not confuse this resolution value (e.g. megapixel 3, 4 or more) with the one of your monitor (800x600, 1024x768 pixels). When you take a digital picture, your camera saves it according to its setup. Once you download these photos to your PC you need to resize them to the value you want to use in the layout. Example Table 1 Digital Picture resolution 2048 x 1536 (3-megapixel) 2272 x 1712 (4-megapixel) 2592 x 1944 (5-megapixel) File size RAW 9MB 12Mb 15MB File size JPG highest resolution ~1,10MB ~1,47MB ~1,82MB
With a image editing software you can resize all the picture to the proper size. Size also means kilobytes to download for the client. We suggest to use images not bigger than 40~50 Kb. Of course if you have a fast connection you may exceed this value. File format supported are: JPG and GIF. We strongly suggest to use JPG due to its better compression factor. As an example you can refer to the following table chart: Example Table 2 File Resolution 800 x 600 (outdoor image) 800 x 600 (outdoor image) 1024 x 768 (outdoor image) 1024 x 768 (outdoor image) Compression ratio 45% 65% 45% 65% File Size 64Kb 44Kb 98Kb 67Kb
Actual file size, if you use JPG compression, depends on the picture you are compressing. Different pictures with same compression ratio and same file resolution, may have different file size.
NAME
10/01/2006- 1592010900
Pag. 63 / 103
BACKGROUND COLOUR
It is used to change to background colour of the page. Use the drop down menu to make a choice.
BACKGROUND IMAGE
It is used to change the actual background image or to set an image as background. When you choose this option, the following windows will appear:
Choose an image and press Ok. When you use images the system has to send them to your client. Depending on the speed of the connection the download procedure may take up to some minutes.
It allows you to cancel the background image, if present. This function is very important. With this feature you can decide which is the homepage of the layout. Each time an user will load the layout viewer this is the page that firstly appears. It allows the user to remove the actual layer from the layout.
64/103
10/01/2006 - 1592010900
Insert Submenu:
DEVICE
It allows you to place a real Instrument directly linked to the RS 485 serial line The following windows will appear:
With the first drop down menu you can filter the instruments, with the second one you select the instrument you want to show in the layer. A new windows will appear:
10/01/2006- 1592010900
Pag. 65 / 103
You can check/uncheck the name. It is also possible to change: BG= background colour TX= text colour SZ= font size You can check/uncheck the values or modify them. It is also possible to change: BG= background colour TX= text colour SZ= font size You can check/uncheck the values or modify them. It is possible to let them blink (if active) or to change: BKG= background colour SZ= font size
Analog values.
Digital Inputs.
Outputs.
You can check/uncheck the values. It is possible to use icon or animated square. User can also modify: BKG= background colour SZ= font size
In the output section if you choose Icon the system will show a small drawing with the following meaning: Example Table 3 Icon Description Value On Off
66/103
10/01/2006 - 1592010900
In the output section if you choose Motion a new window will appear:
User has to choose the rectangle property: Label BG FG PX Meaning Rectangle background colour Rectangle foreground colour Line thickness in pixels
With the first left button mouse click you place the control in the layer, then point to the top left corner of the rectangular area, hold down left mouse and drag the pointer to the bottom right corner. Release left mouse button move the rectangular area to centre it and push left mouse button once. In the following example you can see a compressor rounded with a blue/red rectangular area. We also used load 1 icon:
Left mouse click here Hold down left mouse button and drag the pointer to the blue arrow.
When you reach the blue arrow release the left mouse button. One more left mouse click to place.
SENSIBLE AREA
It allows to define a particular zone that can be linked to a layer. Mouse pointer change itself to a finger-icon when it is moved on these areas. The following window will appear:
10/01/2006- 1592010900
Pag. 67 / 103
It is possible to choose a transparent area or a coloured one. We suggest to use the first one when the background is an image. The procedure is the same as the one highlighted above in the motion rectangular area.
TEXT AREA
It allows you to insert a text area inside the layer. We suggest to use this function each time you need to write something inside the layer. To not try to write text inside background image with your editing software instead use text area. Insert your text here
By using the four drop down menu, choose: font type, style, size and colour.
RECTANGLE
This function is useful when you want to highlight some area inside the layer. User can choose the rectangle colour and the shadow effect. The procedure to draw the rectangular area is the one described above Device section.
Shadow effect
Without Shadow
68/103
10/01/2006 - 1592010900
Off course user can combine this function with text area and build up his own button-like graphics. Then with sensible area function you can link it to a specific layer. Here it is an example:
Images Submenu:
SEND TO SERVER
It allows you to store inside the hard-disk of XWEB 500 all the pictures or drawings you want to use. Do not forget that we are working with web-technology and XWEB 500 acts as a server. In your PC you store temporarily the data later you will upload to the server. From the left sub-windows you can browse your hard-disk to find the image you want to upload. Once you find it, select it and push > on the central portion of the window.
Repeat this operation for each image you want to upload. Once the list is complete, push Send button.
When you push Send the system first opens a windows to inform you about the upload procedure, once it is complete a new summarising window will appear. Close it by pushing Ok.
It allows you to delete unused images, simply choose the image to delete from the list, then push Ok button.
It allows you to download an image to the hard disk of your computer. Once you have selected an image, push Ok. Standard Windows file manager will open.
Layout Submenu:
START STOP
It allows you to test your layout. Once you push this button the editor transform itself in the viewer. You can have an overview of the layer with real data coming from the instruments you have selected. This function interrupts the start function described above. 10/01/2006- 1592010900 Pag. 69 / 103
Window Submenu:
WINDOW NAME
Let you choose among the available layers.
3.5.4.2
LAYOUT VIEW
With this function the user can use the layout previously prepared via Layout Editor. Beware that the final user can interact with the real application if you used Global command function (see the above point P). Of course Java Virtual Machine is needed. Your browser helps you during the download procedure. Quite probably the image you uploaded will not change frequently, so once they all are in the browsers cache next time the load time will be faster. According to this function please check if your browser settings support cache. You can do this by clicking Tools menu, then Internet Options general TAB.
70/103
10/01/2006 - 1592010900
You can check/uncheck manually the instruments or you can use the Select/Deselect All. Then push Continue
By pushing Continue the system makes a check to show you only the compatible commands to the instruments you have selected. Choose the command/s you want to send by checking it, then give it the proper meaning by using the blank field.
BG: button background colour TXT: button text colour SZ: button font size Dim: button size Code: check it if you need a password command
protected
Here it is some button size examples. All screen captures are made at 1280 x 1024 pixels, standard resolution for a 17 LCD.
10/01/2006- 1592010900
Pag. 71 / 103
Once a button is password protected, each time someone push it, this window will appear:
If you insert a wrong code, the field reset itself. You can continue inserting a code until you press Exit.
GRID
It helps you to align all the objects you want to place in the layer. By choosing this option you can also select the grid colour.
72/103
10/01/2006 - 1592010900
3.5.5.1.1 DIGITAL INPUT SENDING COMMANDS It is possible to send a set of command to a specific range of controller. The user must setup the polarity of the contact. This can be achieved by means of Close contact setup or Close contact setup.
Use the device filter to add the controllers to the digital input command sending feature.
Choose which command you want to send. 10/01/2006- 1592010900 Pag. 73 / 103
3.5.5.2
GLOBAL COMMANDS
This function allows the user to load a window containing all the global commands previously defined in the Global Edit. In the main page go under Device menu and choose Global Commands.
74/103
10/01/2006 - 1592010900
The first information about the archive shows into Available Interval the first and the last recording date, while the Select Interval includes the period you can decided to show. If necessary, modify the Select Interval period. Longer is the time interval to show, longer the loading time needed to show the data graph. For a first analysis select a time period not so wide but centred on the target of your interest, this ensure higher graph precision. You can also act on Graph Density parameters to decide if you need all data samples. This feature is very useful if you are connected via modem at a slow speed. You have many rows: Analog Input Setpoint Digital Input Output Status Devices Staus - Alarm. The number of the rows depends on the controller type. For each of them you can graphs as many values as you want. The only limitation is 3 analog values and 2 digital ones. For each selection is possible to decide the colour of the line that will be represented. It is also possible to group the analogue inputs into a unique graph or to display them into separated ones. For example if you want to display all data using only one graph, select for each value AG1 from the roll-down menu, then in Graph labels write some words reminding you the meaning of the graphs. On the other side if you want to display the values in different graphs, you have to chose AG1 for the first values, AG2 for the second and AG3 for the third. Remember that each graph can be renamed by the user with an appropriate name into the corresponding Graph Labels situated into the low side of the page. Before clicking the command View it is possible to define the graph density to decide the resolution of the lines and recordings. Select the box Graph Density. Higher is the value of this parameter better will be the graph resolution, but longer the downloading time from the XWEB 500. Now Click on View to start the transferring process of data from the XWEB 500 to your PC. The displaying structure is based on a Java Applet and the Java Virtual Machine program installed into the remote PC that computes the data coming from the XWEB 500. Depending on the Virtual Machine version installed a message to accept the term of use will appear during the operation. Dixell S.p.a.. guarantees that the software is free from viruses and the request can be accepted.
10/01/2006- 1592010900
Pag. 75 / 103
The counter signals shows the status of the data you are downloading
Zoom in/out procedures Before executing the zoom it is necessary, if there is more than a graph displayed, to select the desired graph. Click, with the left button of the mouse, into the top bar of the information of graph itself. To zoom in you just have to keep pressed to left mouse button. To zoom out you just have to keep pressed to right mouse button Zoom into an area To enhance the portion of a displayed graph click and keep pressed the left button of the mouse on the hypothetical top-left corner of the area to zoom.
76/103
10/01/2006 - 1592010900
Than drag the mouse down to the low right corner to complete the window to zoom. If the selected area have not the proper dimensions click one time outside the area itself to abort the zoom, then repeat the operation to select the area to zoom. Otherwise, if you click one time with the left button inside the selected area, immediately this area will be zoomed to the borders of the graph. Back to the original size To resize the graph to its original dimension select from the Scale menu the Reset Size option. Manual Scale The first time the graph is displayed with an auto scale function defined by highest and lowest peek and the whole interval time selected. Do define a personal scale of the graph view select from the Scale menu the Manual Size item. The next windows will show the X and Y scale limits that the user can adapt to his requirement.
Graph Synchronism When a instrument information are displayed into 2 or more graphs, all the horizontal time axes are synchronised together. By zooming only one of the graphs the result is that the other are no more synchronised with the new time base. To keep all the graph synchronised you can use the Sync function from tools menu Select it for each graph that has to be included into the synchronism function, then zoom into one of them. You can notice that all time axes are now synchronized Graph info The graph information area is immediately displayed with the graph itself. If necessary move or drag it where it does not cover part of the interested area. To close the information window click on its crossed button. To make it appear again select Legenda from the Tools menu. Save a graph format This function provides to save the data of the displayed graph into the hard disk of the client computer connected to XWEB 500. To start the operation select Save from the Tools menu. After that you can proceed by using the typical saving method of Windows operative system, remember to assign a proper name and origin of the data. On the bottom left side of the window ypou can decide which data format to save: text (TXT) or html. Load a graph Chose this option to load a graph previously saved. Print a graph To print a graph on the printer of the client PC or on another net printer, select Print from the Tools menu, the follow the typical Windows structure.
10/01/2006- 1592010900
Pag. 77 / 103
78/103
10/01/2006 - 1592010900
From now on you can find the program Dixells graphs viewer inside your PC start menu:
The first time you run it, depending on your PC security setup, you are required to let the software start.
You can do this by clicking with right mouse button in the window header and choose Allow Blocked Content. 10/01/2006- 1592010900 Pag. 79 / 103
80/103
10/01/2006 - 1592010900
Pushing Open a graph button, first you are required to confirm java virtual machine start, then you can browse your PC for a graph file.
10/01/2006- 1592010900
Pag. 81 / 103
82/103
10/01/2006 - 1592010900
The Alarm Filter defines which alarm level and which kind of alarm to search. The Device Filter defines the typology and the name of the instrument to search. The Action menu allows the user to decide what action to start: Save on disk in html format, view in the current window or print alarm. The system automatically loads all the alarm. The user can filter which one wants to view using Actual or Last and insert the number of days back to show. The alarm description is displayed in table format.
Beware to the status of an alarm: Active (To column): Auto (ending column): Stop Acq. (ending column): Restart (ending column): Alarm is still active Alarm stopped automatically. It means that alarm event is now ended. Someone has stopped the recording activity System has been rebooted by someone/something.
Actual view of a device included into the alarm list The user could be interested in having more and deep information about the actual situation of an instrument with an active alarm that is included into the alarm list. Thats why if you click on the description of the instrument itself the XWEB 500 will load a snapshot page showing all the controller information. Print the alarm list 10/01/2006- 1592010900 Pag. 83 / 103
Select the Print from the Action menu situated on the left corner of the alarm page under the Dixell logo. Use the structure of the operative system of your client PC to select and configure the printer then proceed with the printing.
84/103
10/01/2006 - 1592010900
3.8 PERMISSIONS
From the Configuration menu you can access Users. This section is one of the most important to preserve the correct functioning of the unit. You can setup others users account and grant them the permission to interact with the XWEB 500. Permissions are a powerful tool to avoid accidental system damage and security holes.
We strongly suggest you to create a user with read only privileges and another one with the ability to change system behaviour. The third user must be the administrator who should be the only one to be able to interact with critical system behaviour, such as alarm setup menu or devices add/delete etc. To modify an existing user you just have to put the correct name and password (by clicking inside the box), then push on Modify button. Default configuration consists of one Administrator.
To allow a user to interact with the unit, please assign him correct rights. To do this check/uncheck the proper permission. At the end of the procedure you have to confirm the changes by clicking on apply button. 10/01/2006- 1592010900 Pag. 85 / 103
86/103
10/01/2006 - 1592010900
By clicking on Test XWEB 500 starts sending data packet to the selected controller. Depending on the number of sent back packet the percentage is shown in 3 different colours: red (bad connection), yellow (average connection) and green (good connection). This tool is useful to discover problem on the RS 485 wiring.
10/01/2006- 1592010900
Pag. 87 / 103
88/103
10/01/2006 - 1592010900
10/01/2006- 1592010900
Pag. 89 / 103
Enviromental Safe
Temperature range Humidity
90/103
10/01/2006 - 1592010900
5 APPENDIX
Appendix A: Appendix B: Appendix C: Appendix D: DEVICE ADVANCED SECTION GLOSSARY SUPPORTED INSTRUMENTS ACCESSORIES
10/01/2006- 1592010900
Pag. 91 / 103
Digital Input row need particular attention. The values you find here are the factory defaults, so if you have made modifications to the device setup, you are requested to apply the same modifications in this menu. This is very important because all the values stored inside XWEB 500 devices section must be the same as the ones stored inside the EEPROM of the instrument. A common error for example is to modify Generic Alarm to some other values inside the instrument, than leave the value marked inside Advanced section. XWEB 500 will send you an alarm every time the switch changes status, even if it is not a generic alarm.
Device Status section allows you to customize your instruments, of course the same values have to be set both on XWEB 500 and the instruments themselves.
92/103
10/01/2006 - 1592010900
Commands row is very important. You have to mark same values that you have marked before in the other section. In order to give XWEB 500 the possibility to send commands to the instruments. This is necessary because for example if you have changed Generic Alarm to Ausiliary in digital Resources section, then you have to mark Aux on and Aux off in Commands section to be able to turn on/off the output by means of the XWEB 500. Of course you have to do this kind of changes every time you have made some modifications to the controllers.
10/01/2006- 1592010900
Pag. 93 / 103
APPENDIX 0: GLOSSARY
C
Cable - Transmission medium of copper wire or optical fiber wrapped in a protective cover. Client/Server - A networking system in which one or more file servers (Server) provide services; such as network management, application and centralized data storage for workstations (Clients). CSMA/CD - Carrier Sense Multiple Access Collision Detection is a network access method in which devices that are ready to transmit data first check the channel for a carrier. If no carrier is sensed, a device can transmit. If two devices transmit at once, a collision occurs and each computer backs off and waits a random amount of time before attempting to retransmit. This is the access method used by Ethernet. Coaxial Cable - Cable consisting of a single copper conductor in the center surrounded by a plastic layer for insulation and a braided metal outer shield. Concentrator - A device that provides a central connection point for cables from workstations, servers, and peripherals. Most concentrators contain the ability to amplify the electrical signal they receive.
E
E-mail - An electronic mail message sent from a host computer to a remote computer. End User - Refers to the human executing applications on the workstation.
F
File Server - A computer connected to the network that contains primary files/applications and shares them as requested with the other computers on the network. If the file server is dedicated for that purpose only, it is connected to a client/server network. An example of a client/server network is Novell Netware. All the computers connected to a peer-to-peer network are capable of being the file server. Two examples of peerto-peer networks are LANtastic and Windows for Workgroups.
I M P
Modem (Modulator/Demodulator) - Devices that convert digital and analog signals. Modems allow computer data (digital) to be transmitted over voice-grade telephone lines (analog).
PCMCIA - An expansion slot found in many laptop computers. Point-to-Point - A direct link between two objects in a network. Ports - A connection point for a cable. Protocol -A formal description of a set of rules and conventions that govern how devices on a network exchange information.
94/103
10/01/2006 - 1592010900
R
RAM (Random Access Memory) - The working memory of a computer where data and programs are temporarily stored. RAM only holds information when the computer is on.
S
Speed of Data Transfer - The rate at which information travels through a network, usually measured in megabits per second.
W
Workstation - A computer connected to a network at which users interact with software stored on the network.
10/01/2006- 1592010900
Pag. 95 / 103
XR 100/500/700
2.0
2.1 1.0
XLR
563D 570D
1.0
96/103
10/01/2006 - 1592010900
XW 200/500
1.5
XM 400K
XC
2.0
1.0
XT
100C 200C
1.2
XH
1.0
XW220L XW230L XW260L XW270L XW271L XW570L XW263L XW264L XW563L XM440K XM460K XM463K XM470K XM460K XM463 XC706M XC807M XC811M XC907M XC911M XC650C XC642C XC640C XC420C XC440C XC420D XC440D XC460D XA100C XT110C XT111C XT120C XT121C XT130C XT131C XT141C XT210C XT211C XT220C XT221C XA100C XT110C XT111C XT120C XT121C XT130C XT131C XT141C XT210C XT211C XT220C XT221C XH240L XH260L XH340L XH360L XH460L
XH240K
10/01/2006- 1592010900
Pag. 97 / 103
1.4 1.5
98/103
10/01/2006 - 1592010900
10/01/2006- 1592010900
Pag. 99 / 103
APPENDIX 0: ACCESSORIES
TYPE MODEM DESCRIPTION Analog SERIAL modem, PDA compatible, 56kbps COMMERCIAL NAME XWEB MODEM TC35-KIT ### ### HOW-TO ORDER XWEBMODEM-200 (24Vac) XWEBMODEM-400 (110Vac) XWEBMODEM-500 (230Vac) TC35-KIT CAB/WEB/NET CAB/WEB/PC
MODEM GSM GSM modem KIT Ethernet patch cable CABLE compatible with XWEB500, 3m Ethernet patch crossCABLE over cable compatible with XWEB500, 1m
100/103
10/01/2006 - 1592010900
NOTES
______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ 10/01/2006- 1592010900 Pag. 101 / 103
102/103
10/01/2006 - 1592010900
10/01/2006- 1592010900
Dixell S.p.a.. Z.I. Pag. 103 / 103 Via dellIndustria, 27 32010 Pieve dAlpago (BL) ITALY tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13 E-mail: dixell@dixell.com - http://www.dixell.com