Fire Alarm Book
Fire Alarm Book
Fire Alarm Book
CONTENTS CONTENTS
Chapter 1 - Introduction
1.1 Chapter 8 - Fire Phones & Disable Refuge 8.1 Chapter 9 - Water Leak Detection 9.1
Chapter 2 - MZX Technology 2.1 Minerva MZX Addressable Control Panels 2.2 Minerva MX2 Range 2.4 Minerva MX1000 & MX4000 2.5 Battery & Expansion Boxes 2.6 Minerva MX Repeaters 2.7 MZX4000 Black Box 2.8 Minerva T2000 & T2000 CV Marine Detection Panels 2.9 Minerva T2000R & T2000R CV Marine Repeaters 2.10 MX Panel Components 2.13 DDA Compliant Pager 2.25 MX Virtual Multi-Sensor Detectors 2.28 Beam and Linear Heat Detectors 2.32 Detector Bases & Accessories 2.35 Detector Ancillaries 2.39 Duct Probe Air Sampling 2.41 MX Addressable Input/Output Modules 2.43 MX Ancillary Housings 2.47 Callpoints 2.49 Sounders & Beacons 2.55 Software Tools & Accessories 2.69 2.70 MZX Interactive Training CD Programming and Service Tools 2.72 Service & Spares 2.75 Chapter 3 - Conventional Systems Control Panels and Repeater Panels DDA Compliant Pager Point Detectors Beam Detectors Linear Heat Detectors Detector Bases and Accessories Duct Probes Callpoints Sounders & Beacons Service & Spares Chapter 4 - Networks & Graphics Tyco Expert Graphics (TXG) MXNet MX Minerva - Bridge Chapter 5 - Detector Test Equipment Chapter 6 - System Accessories Batteries, PSU and Chargers Door Release Units Auxiliary Interface Relays Fire Resistant Cable Chapter 7 - VESDA LaserFOCUS Aspirating Smoke Detection LaserCOMPACT and MX LaserCOMPACT LaserPLUS Standard Modular Range LaserPLUS Scanners ICAM IAS Air Sampling Smoke Detection Pipe and Fittings 3.1 3.1 3.9 3.11 3.16 3.18 3.19 3.23 3.25 3.32 3.46 4.1 4.1 4.4 4.6 5.1 6.1 6.1 6.3 6.4 6.5 7.1 7.1 7.2 7.3 7.4 7.7 7.8
Chapter 10 - Special Hazards 10.1 Special Hazard Flame Detectors 10.3 System 800 Fire Detection for Hazardous Areas 10.7 System 620 Fire Detection for Hazardous Areas 10.13 MZX SensorLaser Plus Fibre Optic Linear Heat Detection System 10.24 Chapter 11 - Useful Information MX Addressable Detector, Mode Selection & Design Charts Conventional Detector Selection & Design Charts MKII Sounder Base Application Table Sounder Tone Tables Consultants Guide 11.1 11.1 11.3 11.4 11.6 11.8
Fire Catalogue
07/10
Website The Tyco Safety Products website is full of up-to-date information including a section dedicated to fire detection products where you will find lots of useful information including; Approval Certificates AutoCAD Downloads Catalogues Datasheets Forums Marketing Bulletins Presentations Technical Information including; User manuals Application & Design Manuals Installation Manuals Commissioning Manuals Service Manuals Sales Information Software Downloads Contact Us For further details on this catalogue, contact our customer telephone Help Line at Letchworth Customer Services on + 44 (0) 1462 66 77 00. TFS Technical Support Call Centre:Direct: +31 475 352 722 Fax: +31 475 352 725 Hours: 9:00 to 19:00 CET, 8:00 to 18:00 GMT, 7:00 to 17:00 EET UK only: 08701-238 787 Toll Free: 0800 CALL TYCO or (0800 22 55 89 26) E-Mail: TSPEuropeSupport@tycoint.com Our web site can be found at: www.tycoemea.com
03/10
Fire Catalogue
Chapter 1 Page 1
Chapter 1 - Introduction
Chapter 1 Page 2
Fire Catalogue
03/10
Tyco MX detection panels support Tyco MX Technology: MX VIRTUAL Multi-sensor detectors MX DIGITAL high speed reliable digital protocol MX FASTLOGIC fuzzy logic smoke detection algorithms MX CCO universal carbon monoxide fire detection algorithms
Tyco MX panels include advanced manager and engineer functions including: Menu driven Multi-level password protected Viewing 3000 event log Detailed fault reporting Isolate by point, zone or sector Viewing and printing status Viewing and printing isolated points Manual and automatic walk test and reporting functions Viewing and printing maintenance reports Extensive diagnostic functions including simulation and force outputs Text and configuration changes/Automatic battery test Detector service functions Tyco MX detection panels include very powerful event/action programming including: Seamless network wide event/action 240 x 240 Output map and output sequencing algorithms Over 3000 event/action groups for the most complex applications Templates for fast programming of standard applications including: - EN54/BS5839 - EN54 Marine User defined templates Time, date and special day programming Wide range of co-incidence, double knock and delay functions
Tyco MX detection panels provide modular cost effective solutions: Networked panels from 1 to 792 detection loops Powerful central loop processing functions Powerful and modular user interface MX REMOTE diagnostics and service functions TXG graphical user interfaces MZX, MX2 and designer housing options
Tyco MX detection panels provide long term fire detection solutions including upgrade paths from earlier panel models and a long term develop-ment strategy providing future upgrade paths. Tyco MX detection panels include: MZX for compact single loop solutions MINERVA MX for EN54 LPCB approved systems MINERVA T2000 for Marine approved systems Tyco MX detection panels include a powerful user interface: 640 Character display Displays first alarm and most recent alarm Permanently displays systems status including number of alarms, number of faults, number of isolated points Scroll function allows details of all events and status to be easily viewed Displays temperature, CO level and smoke level at point in alarm Displays 95 character custom messages for emergency procedures
09/10
Fire Catalogue
Chapter 2 Page 1
Product Codes
557.200.501 557.200.502 557.200.503 557.200.506 557.200.520 557.200.521 557.201.502 557.201.501 557.201.503 MZX125 1 loop 16 Zone Fire Controller MZX250 1 loop 32 Zone Fire Controller MZX251 1 loop 32 Zone Fire Controller MZX252 2 loop 32 Zone Fire Controller MZX16R 16 Zone Repeater (mains powered) MZX32R 32 Zone Repeater (mains powered) Semi-Flush Bezel for MZX125/MZX16R Semi-Flush Bezel for MZX250/251/252/MZX32R Accessory mounting plate for std modules, IOB800, LIM800 and TUD800 (MZX250/251/252 only) Accessory mounting plate for CCU3 (MZX250/251/252 only) MZX250 17Ah Battery Clamp MZX251/ 252 38Ah Battery Clamp
Chapter 2 Page 2
Fire Catalogue
09/10
1.6A
Note 1 Max PSE output current with the charger interrupted (I max b, EN54-4)
09/10
Fire Catalogue
Chapter 2 Page 3
Product Codes
557.200.203 557.200.205 557.200.207 557.200.208 557.200.209 557.200.210 557.202.007 557.202.026 557.202.021 557.202.022 557.202.020 557.202.024 557.201.211 MX2-210 Two loop c/w LEDs shallow housing MX2-211 Two loop c/w LEDs deep housing MX2-XB0 Expansion Box Shallow MX2-XB1 Expansion Box Deep MX2-FB Panel/repeater flush mounting bezel MX2-FBX Expansion box flush mounting bezel XLM800 Loop expansion module TLI800 MXNet network node interface module ANN840 LED Annunciator 40 way bi-colour ANN880 LED Annunciator 80 way COM820 Status command module 20 way PRN800 In-built thermal printer (expansion box) Ancillary/expansion board mounting kit 557.202.206 557.202.204 557.202.205 557.202.209 557.202.208 557.202.200 MX battery expansion aperture installation kit. MX2 Battery housing MX2 Battery and Expansion Housing (65AH) MX2 LCD Assembly (Spare) MX2 8 Loop Expansion Kit DCM800 (Display + Control Module)
Chapter 2 Page 4
Fire Catalogue
09/10
Product Codes
Standard Panels MX1000 Single Loop Panel Shallow 557.200.001 Back Box 557.200.002 MX1000 Single loop panel - Flush Back Box 557.200.003 MX4000 Two to Four Loop Panel Shallow Back Box 557.200.004 MX4000 Two to Eight Loop Panel Deep Back Box 557.200.009 MX4000 Two to Four Loop Panel - Flush Back Box Options 557.202.006 IOB800 (8in/8out) expansion board (Max. 24 I/O on main panel 8in/16out) 557.202.007 XLM-MX two loop MX DIGITAL expansion card 557.202.026 TLI 800 ThornNet & MX-NET network card
09/10
Fire Catalogue
Chapter 2 Page 5
Product Codes
557.200.005 557.200.019 557.200.006 557.200.016 572.065 MX-BBX 17Ah shallow expansion and battery box MX-BBX-F 17Ah shallow flush expansion and battery box MX-DPBX 38Ah deep expansion and battery box. MX-BATT Deep Battery Box (322H x 442W x 217D mm) MX Rack Mounting Kit for standard 19 racks
Chapter 2 Page 6
Fire Catalogue
09/10
Minerva MX Repeaters
The MINERVA MX full function repeater is an EN54 LPCB approved repeater with optional addressable EN54:Pt.4 power supply. The repeater consists of a steel backbox and cast aluminium front door which incorporates the ODM800 operator display module with a 16 x 40-character backlit LCD display, simple alphanumeric keypad and 5 softkeys. The OCM800 operator control module provides all mandatory operator control keys and LED functions including Day/Night switching. One control key and 2 indication LEDs are provided for site-specific functions. Control keys and LEDs are labelled in English according to the default LPCB functionality. The slide in decals can be reversed and alternative text added. Two power supply options are available for repeaters. The MXR incorporates an RSM800 repeater supply module for connection to a 24 Vdc supply. Or the MXR-PSU which incorporates a PSM800 power supply module for connection to a 120-240Vac mains supply and an APM800 addressable power monitor for connection to an MX addressable loop, providing power supply monitoring in accordance with EN54-pt.4. The back box has a removable chassis plate with either the RSM800 or the PSM800 power supply. APM800 addressable PSU monitor and provides space for 2 x 7 Ah batteries to provide 72 h backup. The MINERVA MX repeater is connected to the Panel via the remote bus (RS485, 1200 m distance). A maximum of 7 repeaters (including one MX REMOTE repeater) can be linked to each MINERVA MX panel and can provide full repeater functions for all panels on the system. The operator control module (OCM800) can support up to 80 inputs and outputs in the form of LED annunciators, IOB800 input/output modules, or com 820 command modules.
Product Codes
Standard Repeaters 557.200.012 MXR Repeater with shallow backbox (24Vdc) 557.200.017 MXR-F Repeater with flush backbox (24Vdc) 557.200.013 MXR-PSU Repeater and addressable PSU (120-240 Vac) Options 557.202.006 IOB-800 (8in/8out) expansion board 557.180.005 Mimic driver module 557.180.016 XIOM universal I/O module 557.202.028 RSM800 PSU Module (24Vdc)
09/10
Fire Catalogue
Chapter 2 Page 7
Technical Specification
Dimensions (mm): Aprox weight: Colour, housing & front cover: Operating Temp: Storage Temp: Relative Humidity: Supply voltage: Input current: 640H X 440W X 230D 16Kg Dawn Grey (BS 4800 10A) Range -8C to +55C -20C to +70C 95% non condensing 120 to 240 Vac 0.8 to 2.2A
Product Code
542.098 MZX4000 Black Box
Chapter 2 Page 8
Fire Catalogue
09/10
Product Codes
557.200.600 557.200.602 557.200.610 557.200.605 557.201.216 557.200.620 557.202.127 557.202.128 557.180.454 557.180.452 557.180.022 557.201.233 557.201.234 T2000 Two To Eight Loop Marine Panel (Stainless steel enclosure) T2000B Battery Box (Stainless steel enclosure) T2000 Standard Two to Eight Loop Marine Panel (Mild steel enclosure) T2000 BM Battery Box (Mild steel enclosure) T2000 XLM 8-Loop Mounting Kit T2000CV 3 loop marine panel (mild steel back box) VDR Cable For a Standalone panel, Com port 3 VDR Cable for a networked system, Com port 1 Marine Bulkhead Mount Marine 19 rack mount kit for use with surface mounting housings Terminal chamber PCB assembly PSU 830 T2000/T2000R Conversion Kit PSU 830 T2000 120VAC Kit
09/10
Fire Catalogue
Chapter 2 Page 9
Product Codes
557.200.601 557.200.604 557.200.611 557.200.612 557.200.621 557.201.233 557.201.234 T2000R Marine Repeater with Power Supply Unit 240Vac (Stainless steel enclosure) T2000R Marine Repeater without Power Supply Unit 24Vdc (Stainless steel enclosure) T2000R Standard Marine Repeater with Power Supply Unit 240Vac (Mild steel enclosure) T2000R Standard Marine Repeater without Power Supply Unit 24Vdc (Mild steel enclosure) T2000R CV Marine Indicating Repeater without Power supply unit 24Vdc (Mild Steel enclosure) PSU 830 T2000/T2000R Conversion Kit PSU 830 T2000 120VAC Kit
Chapter 2 Page 10
Fire Catalogue
09/10
Dimensions (mm) Approx Weight Temperature (Storage) Temperature (Operating) Humidity Colour (Housing) Colour (Modules) EMC/RFI Shock Vibration
6.2kg -20 C to + 70C -5C to +55 C Up to 90 % RH Non Condensing Dawn Grey (BS4800 10A-03) Pantone 431C EN50130-4 EN61000-6-3 IP30
09/10
Fire Catalogue
Chapter 2 Page 11
CPU PSB FIM Loop C XLM 110-240Va.c. Loop A Loop D Loop B TLI RBus
ODM
FRONT DOOR
OCM
XBus
TUD/ IOB
IOB
PSB/PSM MX FILNET
17 or 38Ah
17 or 38Ah
MPM
MX2 Schematic
NETWORK FIELD I/O 110-240 Vac
DCM PSB
FIM
PRINTER
NETWORK
PC MODEM
24Vdc
ANN881
17AH OR 38AH
17AH OR 38AH
Technical Specification
32 bit Processor: Data Memory SRAM: Prog. Memory Flash EPROM: Config. Memory Flash EPROM: Boot EPROM: Number of serial Interfaces: Quiescent Current: Alarm Current: Motorola 68331 1 MByte 2 MByte 1 Mbyte 64 kByte 4 67mA 67mA
Product Code
557.202.002 CPU800 standard MX central processor
09/10
Fire Catalogue
Chapter 2 Page 13
Technical Specification
Dimensions: Battery Requirements: 17.5H x 104W x 196Dmm Standby 104.3mA+loop current Alarm105.3mA + loop current Loop Current 495mA maximum
Product Code
557.202.007 XLM-MX Two Loop MX Digital Expansion Card
Chapter 2 Page 14
Fire Catalogue
09/10
Technical Specification
Dimensions: Weight: Power Consumption: 25H x 105W x 196D mm 156g 119mA (Quiescent excluding loops and operator interface) 169mA (Alarm) 30Vdc @ 2A 10k Ohm EOL, 3KHz in parallel RS-485 , default 19.6kB, up to 1200m RS232C, 19.6kB, up to 10m Up to 2 modules, up to 24 I/O, max. 300mm
Product Codes
557.202.000 557.202.001 557.202.008 557.180.053 FIM801 field interface module with one MX loop driver FIM802 field interface module with two MX loop drivers FIM801CV for Marine T2000 CV MX RBUS Driver chip (spare)
Relay Outputs: Monitored inputs: RBUS: Serial Ports: Local I/O Expansion:
09/10
Fire Catalogue
Chapter 2 Page 15
Technical Specification
Dimensions: Weight: Input Voltage: Input Current: Max. charge current : 50H x 114W x 190D mm 0.9Kg 120-240 Vrms, 50/60Hz (Auto ranging) 0.8-1.6ARMS Rated Load Up to 3.8A (dependant on standby current)
Product Codes
557.200.014 557.200.015 MXAPSU17 Boxed Addressable PSU (17Ah) MXAPSU38 Boxed Addressable PSU (38Ah)
Max. battery size (24hr charge): 38Ah Max. total supply current: 5A@24Vdc Maximum external current:4A@24Vdc Output Voltages: 24Vdc (22.8 -26.4V) Non-resettable: 24Vdc @ 4A Resettable: 24Vdc @ 4A 5Vdc @ 3A Power Consumption: PSB - 90mA (quiescent & alarm) PSM - 65mA (quiescent & alarm)
PSM800 Power Supply Only PSM800M Marine approved power supply PSB800M Marine Panel Power Supply (spare) APM800 Addressable Power Supply Monitor PSM800 Temp. Sensor Accessory kit PSB800MK Marine Power Expansion kit LBM800 Spare Loop Voltage Booster PCB
Chapter 2 Page 16
Fire Catalogue
09/10
Technical Specification
Dimensions (HWD): 62 x 132 x 242mm Electrical Characteristics: Input Voltage: 120-240Vac 50/60Hz (auto ranging) Input Current Rated Load: RMS 0.8-2.2A Output Voltages 27.3Vdc @ +25C Non-reset: 27.3Vdc @ 2A 5Vdc @ 2.2A 40Vdc @ 2.2A Reset: 27.3Vdc @ 2A Rated Output Maximum Alarm current 5A for 30 minutes Maximum continuous load current (excluding charging): 2.5A Battery Requirements 17Ah or 38Ah single PSU 65Ah dual PSU Standby Current Consumption: 90mA @ 24Vdc Battery Fault High Resistance: Single PSU: 0.6 Ohms Dual PSU: 0.3 Ohms
Product Codes
557.202.210 557.201.232 557.201.231 557.202.044 557.202.030 557.202.031 PSU830 Power Supply Module PTM800 Power Terminal Module MX2 PSU830 Dual PSU Kit PSU 830K Power Expansion Kit PSU 830 Panel Fixing Conversion Kit PSU 830 Small Chassis Plate Conversion Kit
09/10
Fire Catalogue
Chapter 2 Page 17
Technical Specification
Dimensions: Weight: Power Consumption: 50H x 232W x 133D mm 0.272Kg 35mA (Quiescent) 36mA (Lamp test) 81mA (Alarm) 7 18 RS-485: RBus Default 9.2Kb MX X-Bus UK/English, Marine
Product Code
557.202.013 OCM800 with Minerva MX Inserts
Control Buttons: Indication LEDs: Communications: Expansion Bus: Legends for LPCB modules:
Chapter 2 Page 18
Fire Catalogue
09/10
Technical Specification
Dimensions: Weight: Power Consumption: 25H x 232W x 133D mm 0.361Kg 50mA (Quiescent) 900mA (Alarm Backlit) 50mA (Alarm during mains failure)
Product Code
557.202.019 ODM800 operator display module
09/10
Fire Catalogue
Chapter 2 Page 19
Remote Mimics
The 80-Way Mimic allows custommade display and presentation panels to be incorporated in the MINERVA MX addressable system. It is supplied as a single PCB, which may be mounted in an expansion box or on the rear of a free-standing panel, as required. It may be used to drive up to 80 zonal LED indicators, arranged in any configuration, together with two FIRE LEDs, one FAULT LED and one ISOLATE LED. These indicators can operate in the same manner as the corresponding indicators on the panel. A remote Mimic can be connected to the MPM800s configured as remote Mimic drivers via the remote bus. Up to 15 MPM800s may be connected on to the remote bus, each with a unique address [set onboard]. The Mimic includes audible and visible warning facilities. Technical Specification Dimensions: 235H x 190Wmm Operating Temp: -10C to +55C Storage Temp: -20C to +65C Relative Humidity: Up to 95% RH NonCondensing Power Consumption: 11mA (Quiescent) 200mA (25% Alarm) 800mA (Lamp Test) Product Code 557.180.005 MINERVA 80 way mimic driver module
Chapter 2 Page 20
Fire Catalogue
09/10
Technical Specification
Dimensions: Weight: Power Supply: Communications: Printer Connection: 25.4H x 92W x 167.64D mm 98g 24Vdc (from PSB or PSM800) RS-485, up to 19.6kB Serial or Parallel
Product Codes
557.202.012 557.202.117 557.180.052 557.180.053 MPM800 multi-purpose interface modules Serial printer cable for MPM800 or FIM800 Serial Printer Driver Kit Isolated RS485 IC (for U16)
09/10
Fire Catalogue
Chapter 2 Page 21
Chapter 2 Page 22
Fire Catalogue
09/10
Technical Specification
Mechanical Weight: Dimensions: Mounting: Operating Temperature: Operating Humidity: Storage Temperature: Electrical Input Voltage: 130 g 67 x 22 x 100.4 mm DIN-Rail, wall -10 to 60C 5 to 95% RH -20 to 80C 12 to 48 VDC
Product Code
557.202.135 BACnet Converter for MZX
09/10
Fire Catalogue
Chapter 2 Page 23
In-Built Printer
The PRN800 Printer Kit is designed for use with the designer range of MX Controllers (MX1000, MX4000 and T2000). It is fitted to the front cover of the MX battery housing and is powered from the PSB 800 power supply via an FB800 fuseboard in the MX Controller housing. Features A thermal printer mechanism which ensures high reliability. Quiet Operation Lightweight and Compact Design High Speed Printing: 40mm per second. High quality printing: 384 dots. 40 Columns Friction paper feed Technical Specification Dimensions: 230H x 137W x 85D mm Weight: 0.38Kg Operating Temp: +5C to +45C Storage Temp: -20C to +70C Relative Humidity: Up to 80% noncondensing EMC: 61000-6-3 for emissions BS EN 50082-1 for immunity Product Codes 557.202.024 PRN 800 Printer c/w front cover module 557.301.014 Spare Paper Roll (pk of 5)
Chapter 2 Page 24
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 2 Page 25
Product Codes
557.200.071 557.200.074 557.200.076 557.200.077 557.200.078 557.200.079 557.200.080 Paging Transmitter 40 Character Alpha Numeric Pager 1/2 wave dipole antenna Wall mounting folded dipole antenna Pole mounting folded dipole antenna 5 metre antenna feeder cable 10 metre antenna feeder cable
Chapter 2 Page 26
Fire Catalogue
09/10
Pager Interface
The MX pager system is designed to provide a facility to signal all text messages or alarm/fault messages from a local transmitter to the pagers. The transmitter connects to the serial printer port of an MPM800, if a local printer is connected to the controllers MPM800 serial port, a second MPM800 must be used. The pager system requires a +12V d.c. connection (from a remote psu) and a serial port connection. If the transmitter needs to be located further than 2 m from the MX Panel, then a non-standard serial printer cable may be used, up to a maximum distance of 14m. The Type A alarm pager can display alarm/fault messages. The Type B maintenance pager displays all messages sent by the fire controller. CAUTION: Before any installation is carried out, an on site radio paging license must be obtained by the customer. Care should be taken when designing pager systems. Normal practice indicates that a site survey should be done. Contact Product Management for additional advice on site surveys.
Technical Specification
Dimensions: System operating voltage: Effective radiated power: Frequency range: Channel spacing: TX baud rate: Type approval 328H x 190W x 75D mm 12 to 13.8Vdc 500mW 50-470 MHz 25KHz 512 or 1200 ETS 300 224, MPT1383 Cert No. 13249, EC type approved to ETS 300 682 Approval No. 13331
Product Codes
557.200.029 577.002.002 577.002.003 577.002.007 577.002.008 1381N Pager Transmitter Type A alarm pager Type A maintenance pager Pager aerial 60 db gain up to 1km (c/w mounting bracket) Optional feeder cable (10m long) Elmdene 12V 1A PSU in Housing
Manual - Vol17A-2-Pager
09/10
Fire Catalogue
Chapter 2 Page 27
Chapter 2 Page 28
Fire Catalogue
09/10
Technical Specification
Mechanical Detector Material Weight Colour Environmental Operating Temp. Storage Temp. Relative Humidity FR110 "Bayblend" Fire resistant 0.2Kg detector and base (approx) White
Product Codes
516.800.800 516.800.800.A 516.800.800.Y 516.800.801 801PC 801PC 801PC 811PC Unbranded ADT branded Tyco branded Marine Approved
801PC Mode 1 Mode 2 Mode 3 Mode 4 Mode 5 Mode 6 Certification 09/10 Universal multi-criteria sensor false alarm immunity multi-criteria A1R Enhanced Optical Enhanced CO CO Toxic Gas LPCB \ VdS Fire Catalogue Chapter 2 Page 29
THORN
801PH Optical Yes* Enhanced Optical (HPO) Yes* Normal Ambient ROR A1R Fixed Heat A2S 60oC Certification LPCB * Approved with MX Fastlogic algorithms
THORN
Carbon Monoxide Enhanced CO (CCO) Normal Ambient ROR Fixed Heat CCO plus ROR (A1R) Certification
Chapter 2 Page 30
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 2 Page 31
Features
Motorised Auto-Aligning Up to 4 Detectors per System Controller Each Detector configurable from 8m to 100m Integral LASER Auto-Align Fast Automatic BeamAlignment Auto-Optimise Building Movement and Contamination Compensation Low Level System Controller 20mm Cable Gland Knockouts on System Controller 2-wire interface from System Controller to Detector Worldwide Approvals including EN54:12 and UL268 Up to 4 Detectors per System Controller
FIRERAY 5000 Multi Head Auto Aligning Infrared Optical Beam Smoke Detector
The FIRERAY 5000 motorised, auto aligning infrared optical beam smoke detector can now be installed with up to four detector heads per system, thus saving on installation time and costs. This innovative system has been designed from the ground up to include pioneering technology that fully addresses the needs of the installer and user, both now and in the future. With its industry leading optics, the FIRERAY 5000 is ideally suited for the protection of large areas where the use of traditional detection technologies would prove to be too difficult and/or costly to install. The FIRERAY 5000 combines an infrared transmitter and receiver in the same discrete unit and operates by projecting a well-defined beam to a reflective prism, which returns the beam to the receiver for analysis. Smoke in the beam path causes a drop in power, which, if below a pre-determined level, results in an alarm signal. Getting the system operational is simplified by a number of groundbreaking features that combine to make the FIRERAY 5000 the quickest and easiest detector of its type to install. Once the detector heads are connected, using the Easifit First Fix system, an integral LASER, which is aligned along the optical path of the beam, can be activated. This allows the reflective prism to be sighted quickly and with confidence. Once the LASER has been used to coarsely align the beam, the AutOptimise beam alignment system takes over and automatically steers the beam into the optimum position. The system can be fully customised, according to local conditions; both alarm thresholds (sensitivity) and time to Alarm/Fault can be set from the ground level System Controller. Each detector head is independently configurable from 8m through to 100m and has its own individual fire threshold. The System Controller retains one set of Fire and Fault relays that is common to all detectors that are installed. The FR5000 MultiHead is supplied with one detector head and reflector for single beam operation from 8 to 50 meters. Up to 3 additional detector heads can be added to the controller to enable larger or more complex areas to be protected (Subject to local codes and standards). The Fireray 5000 when used in its low power mode can be interfaced to the MZX Fire Controller using the BDM800 module.
Technical Specification
Controller: 202w x 230h x 81d mm 0.9 Kg Detector: 134w x 135h x 134d mm - 0.5 Kg Additional detector head 2mA @ 24VDC Operating Current (low power mode): 10mA @ 24VDC Operating Voltage: 14 to 28VDC IP Rating: IP54 Operating Temp: -20 to +55oC Humidity: 93% RH (non condensing) max
Product Codes
516.015.020 516.015.021 516.015.007 FireRay 5000 System (50m) FR 5000 Detector Head (50m) FireRay Reflector 100 x 100mm 4 reflectors are required for distances from 50 to 100m
Chapter 2 Page 32
Fire Catalogue
09/10
Technical Specification
Technical Specification Dimensions(mm) Height Width Depth 95 75 115 260 210 80 87 148 14 Weight (Kg) 0.4 2.25 0.1
Product Codes
516.015.006.A 516.015.006.T 920450 516.015.007 516.015.008 FireRay2000 optical beam smoke detector VdS approved, ADT Branded FireRay2000 optical beam smoke detector VdS approved, Thorn Branded FireRay2000 -UL Optical beam smoke detector - UL approved FireRay2000 Retro-Reflector 100 x100mm FireRay2000 Alignment tool
Fireray 2000 BDM800 Fireray 2000 Quiescent Current Fireray 2000 Alarm Current Operating Temp. Range Humidity (Fireray 2000 & LPBD521) Fireray 2000 Enclosure Fireray BDM800
+11.5 to +28Vdc 40V Loop Power <13mA <20mA -10oC to +55oC -10oC to +55oC up to 95% RH (Non-condensing) IP54
Product Codes
5000-005 5000-006 5000-007 5000-008 09/10 Fire Catalogue Universal Mounting Bracket Flat Mounting Plate for 1 to 4 Prisms Prism Mounting Plate for 4 Prisms Prism Mounting Plate for 1 Prism Chapter 2 Page 33
Technical Specification
Dimensions: Weight: Operating Temp: Relative humidity: Rating: Operating Voltage: Quiescent Current: 178H x 130W x 75D mm 0.55Kg -25C to +70C Up to 98% RH non-condensing IP55 +8 to +30Vdc 60-80A
Product Codes
516.016.005 516.016.006 LD40 High resistance sensor cable blue - 200M reel LD40 High resistance sensor cable black - 200M reel (Nylon sheath suitable for petrochemical exposure) LD40 EOL Termination kit (PK10) LD40 In-line Jointing kit LD40 Analyser module with conventional detection zone interface B6782-003 EDGE CLIP 2-3mm WEB B6782-024 EDGE CLIP 3-8mm WEB B6782-025 EDGE CLIP 8-13mm WEB B6782-026 EDGE CLIP 14-20mm WEB B6782-004 'T' CLIP B6782-005 PIPE CLIP B6782-023 'V' CLIP B6782-008 NEOPRENE SLEEVE B6782-151 THERMAL SPACER B6782-152 THERMAL SPACER
516.016.010 516.016.011 516.016.012 516.016.201 516.016.202 516.016.203 516.016.204 516.016.205 516.016.206 516.016.207 516.016.208 516.016.209 516.016.210
Ceiling Clip
Edge Clip
Pipe Clip
Thermal Spacer
V Clip
Chapter 2 Page 34
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 2 Page 35
4 Universal Base
4 Universal base. Used where space is limited or compatibility with older systems is required Product Code 517.050.401 4 base
Chapter 2 Page 36
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 2 Page 37
Chapter 2 Page 38
Fire Catalogue
09/10
Product Codes
516.800.915 516.800.931 516.800.932 516.800.933 516.800.934 MX Address flags (pack of 100) Address flag labels Loop A - White Address flag labels Loop B - Yellow Address flag labels Loop C - Purple Address flag labels Loop D - Green 516.800.935 516.800.936 516.800.937 516.800.938 Address Address Address Address flag flag flag flag labels labels labels labels Loop Loop Loop Loop E - Grey F - Blue G - Orange H - Red
Features
Colour coded for Easy Loop Identification Space for Zonal Label Strong Adhesive Backing
Product Codes
Zone Labels 599.047.011 599.047.012 599.047.013 599.047.014 599.047.015 599.047.016 599.047.018 599.047.019 599.047.020 599.047.021 599.047.022 09/10 Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone labels labels labels labels labels labels labels labels labels labels labels Zones Zones Zones Zones Zones Zones Zones Zones Zones Zones Zones 1 - 16 17 - 32 33 - 48 49 - 64 65 - 80 81 - 100 101 - 120 121 - 140 141 - 160 161 - 180 181 - 200 599.047.023 599.047.024 Address Labels 599.047.030 599.047.031 599.047.032 599.047.033 599.047.005 599.047.006 599.047.007 599.047.008 Fire Catalogue Zone labels - Zones 201 - 220 Zone labels - Zones 221 - 240 Address Address Address Address Address Address Address Address Labels Labels Labels Labels Labels Labels Labels Labels 1 1 1 1 1 1 1 1 250 250 250 250 127 127 127 127 Loop Loop Loop Loop Loop Loop Loop Loop A - White B - Yellow C - Purple D - Green E - Grey F - Blue G - Orange H - Red
Chapter 2 Page 39
Chapter 2 Page 40
Fire Catalogue
09/10
Warning Duct probe units sited in the common duct work to several extract grills may fail to respond to smoke from any one extract due to the effect of dilution. The SMP units will not respond to airflow of less than 1.5m/sec.
Technical Specification Operating temperature: -20C to +70C Storage temperature: -25C to +80C Relative Humidity: 0 to 95% SMP69 Stainless steel 316 housing with transparent polycarbonate cover
09/10
Fire Catalogue
Chapter 2 Page 41
Product Codes
517.025.049 517.025.050 517.025.051 517.025.052 517.025.053 517.025.054 517.025.055 DPK4 - Duct Probe with MZX detector base 5" - 5B DPK4I - Duct Probe with MZX detector base 5" with isolator - 5BI DPK600 - Duct Probe Tube 600 mm DPK1500 - Duct Probe Tube 1500 mm DPK2800 - Duct Probe Tube 2800 mm DPKM - Duct Probe Mounting Bracket Spare Filters for DPK4/DPK4I (PK of 10)
Chapter 2 Page 42
Fire Catalogue
09/10
Technical Specification EMC/RFI: Equal or exceeds EN500811 & EN50130-4 Operating Temp.: -20oC to +70oC Relative Humidity: up to 95% RH non-condensing Dimensions: 14H x 148W x 87D mm Weight: 100g EOL & monitor resistor: 10k Ohms
Product Codes 555.800.002 CIM800 contact input monitor 555.800.032 CIM800 Module c/w Front Cover
09/10
Fire Catalogue
Chapter 2 Page 43
Chapter 2 Page 44
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 2 Page 45
Chapter 2 Page 46
Fire Catalogue
09/10
Technical Specification
Input Voltage: Output Voltage: Output Current: Temperature: Relative Humidity: IP Rating: Material: Dimensions: 230VAC +10%/-15% 50Hz 24VDC 4 Amps Continuous -10C to +40C 95% RH IP41 (excluding rear face) 1.2mm white powder coated steel 230mm (W) x 200mm (H) x 80mm (D)
Product Code
558.004.011 ELM24TSM 4 Amp 24VDC Addressable Door Holder PSU
09/10
Fire Catalogue
Chapter 2 Page 47
M520
M520 Ancillary cover for use with 800 series modules. Will fit onto a MK style double gang back box. Product Code 517.035.007 M520 Ancillary Cover
D800
D800 IP55 ancillary housing 140W x 120H x 70mmD incorporates window to view module LED Product Code 557.201.401 D800 IP55 Ancillary Housing
Chapter 2 Page 48
Fire Catalogue
09/10
K2214 ALM
K2214 ALM Metal surface mount MK backbox for use with 800 Series addressable ancillaries using 517.035.007 cover. Product Code 517.035.011 K2214 ALM Metal Surface Mount MK backbox
MK K2142
MK K2142 White plastic surface mount MK backbox for use with 800 Series addressable ancillaries using 517.035.007 cover. Product Code 517.035.010 MX K2142 White plastic surface mount backbox
8621C
8621C Steel flush mount MK backbox for use with 800 Series addressable ancillaries using 517.035.007 cover.
Product Code
517.035.014
Technical Specification
Product Code 517.035.011 517.035.010 517.035.014 517.035.015 MK Ref K2214 K2142 8621C QFB/2 Mounting Surface Surface Flush Flush/ Dry Lining Dimensions 146x86x40mm 146x86x34mm 132x72x26mm 146x85x38mm Knockouts 1x20mm rear/7x20mm sides One rear (25x35mm) 4x20mm rear/12x20mm sides 2 top & bottom Earth Screw Material Yes Steel N/A Plastic Yes Steel N/A Plastic
09/10
Fire Catalogue
Chapter 2 Page 49
CP Series Callpoints
A comprehensive range of callpoints for use with addressable systems. All the callpoints are designed to enable an alarm signal to be given by breaking a glass element. This operates a switch and is indicated by an LED indicator. If required, an optional transparent hinged cover may be installed to guard against accidental operation.
Technical Specification
(Indoor & Outdoor) Housing: Operating Temp.: Outdoor Indoor Relative Humidity: PC/ABS -25oC TO +70oC -10oC TO +55oC up to 95% RH (non-condensing)
Chapter 2 Page 50
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 2 Page 51
515.001.128 Callpoint hinged cover for use on MCP callpoints models (Colour Clear)
Chapter 2 Page 52
Fire Catalogue
09/10
STOPPER
The callpoint STOPPER provides protection from malicious or accidental activation of manual callpoints. Available for flush or surface mounted callpoints the STOPPER is also available with optional high pitch sounder which is activated when the lid is lifted. An optional Break-Seal fitting kit allows Break-Seals to be used to provide extra protection.
Product Code 515.001.029 515.001.030 515.001.036 515.001.034 515.001.035 515.001.031 515.001.032 Ref STI6530 STI6531 STI6535 STI1230 STI3150 STI6532 STI6533 STOPPER Flush Surface 4 4 4 4
WARNING:- Break seals only to be fitted by agreement with relevant fire authorities. The STOPPER is suitable for all callpoints up to 100mm square.
STOPPER II
With Sounder
Weatherproof
4 4
4 4 4 4
STOPPER Dimensions
Product Code
515.001.033 IPO36 Break Seal Kit (pack of 1)
Flush Fit Millimetres A 137 B 140 C 104 D 45 E 12.5 F 12.5 G 185 H 12.5 Stopper STI6530 Stopper with Sounder STI6532
Surface Fit
(+30mm)
STI6531 STI6533
STOPPER STOPPER II Max. Callpoint Size 100 x 100mm 160 x 160 mm Max. Callpoint Depth 57.5 120 (+30mm Surface)
STOPPER II Dimensions
09/10
Fire Catalogue
Chapter 2 Page 53
STOPPER II
STOPPER II is constructed as the STOPPER from tough injection moulded polycarbonate. Physically larger than the STOPPER the STOPPER II extends the number of products to which these tough multi-purpose covers can protect. It consists of a strong tamper-proof clear polycarbonate cover and frame that fits easily over such products as break glass callpoints. STOPPER II can also be fitted with an integral battery powered sounder which activates if the cover is lifted. The STOPPER II is suitable for callpoints up to 160mm square.
Product Code
515.001.034
Features
Strong polycarbonate construction Provides environmental protection Ideal for offshore environments
Product Codes
515.001.036 515.001.035
STI6535 Surface fit Weather STOPPER STI3150 Surface fit Weather STOPPER II
Chapter 2 Page 54
Fire Catalogue
09/10
Keybox
This tough polycarbonate breakglass keybox is available to protect emergency keys. Product Code 515.001.043 STI6720 Keybox with printed glass
09/10
Fire Catalogue
Chapter 2 Page 55
Sounders
A range of sounders to meet a wide variety of alarm applications where loud, penetrating and distinctive warnings must be given to alert people of fire situations. In addition, multi-tone electronic sounders can give a variety of sounds to signal other conditions e.g.extinguishing gas release imminent, etc.
Note: For I.S. & Flameproof sounders, please see the special hazards section in Chapter 10.
Chapter 2 Page 56
Fire Catalogue
09/10
Technical Specification
System Environment Temp- Operating Temp - Storage Dimensions Weight: Materials EMC For use with MX/ZX fire alarm controllers Up to 95% RH (non condensing) IP Rating 21 C EN60529 -20C to +70C -25C to +70C 102 mm dia x 42 mm high LPSB3000 0.160 kg LPAV3000 0.170 Kg Housing ABS FR & Polycarbonate The range complies with the following: Product family standard EN50130-4 in respect of conducted disturbances, radiated immunity, electrostatic discharge, fast transients and slow high energy EN61000-6-3 for emissions
Product Codes
516.800.957 516.800.958 516.800.959 557.001.040.A 557.001.040.Y LPSB3000 Sounder only L/P addressable base LPAV3000 Sounder beacon L/P addressable base DAB3-4 Mounting flange type B for conduit (supplied in packs of 10) Mark 2 Sounder Cap (ADT Branded) Mark 2 Sounder Cap (Tyco Branded)
09/10
Fire Catalogue
Chapter 2 Page 57
Technical Specification
Operating temp Indoor devices -10C to +55C Outdoor devices -20C to +70C IP rating Indoor devices IP21C Outdoor devices IP65 EMC Product family standard EN50130-4 in respect of Conducted Disturbances, Radiated Immunity, Electrostatic Discharge, Fast Transients and Slow High Energy EN61000-6-3 for Emissions
Product Codes
516.800.960 516.800.961 516.800.962 516.800.963 516.800.964 516.800.965 LPSY800-R L/P Symphoni (indoor use) red LPSY800-W LP Symphoni (indoor use) white LPSY865 L/P Symphoni IP65 (out door use) LPAV800-R L/P Symphoni Sounder/Beacon (indoor use) red LPAV800-W L/P Symphoni Sounder/Beacon (indoor use) white LPAV865 L/P Symphoni Sounder/ Beacon IP65 (outdoor use)
Chapter 2 Page 58
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 2 Page 59
Product Codes
576.500.014 576.500.015 577.001.002 240V Red bell 6 240Vac solenoid operated. Fire text 24V Red bell 6 24Vdc solenoid operated. Fire text Weatherproof gasket box for use with Solenoid operated bells
Features
CE marked Low current 6 bell (ONLY 11mA) Low cost Extra high 95dBA/m Slim profile (53mm) Fully suppressed and polarised Quick and easy to install LPCB approved to EN54 Pt 3
Product Codes
576.501.039.A 576.501.039.T 576.501.040.A 576.501.044.A 576.501.044.T 576.501.045 MBF-6EV ADT Branded MBF-6EV Thorn Branded MBF-8EV ADT Branded MBA-8EV ADT Branded MBA-8EV Thorn Branded BBX4 (2) W/P Backbox for MBA-8 Bell
Chapter 2 Page 60
Fire Catalogue
09/10
Technical Specification
Dimensions: Voltage: Typical Current: Typ. Sound Output: 6 diameter 18-30Vdc 24Vdc@30mA 94dB (A)@1m
Product Codes
20-100 6 24Vdc Electronic bell, weatherproof 20-101 6 24Vdc Electronic bell - red 20-111 6 24Vdc Electronic bell - white
09/10
Fire Catalogue
Chapter 2 Page 61
Technical Specification
LPCB and Vds approved to EN54 pt 3 Low Current consumption 32 Tones 3 Volume settings Rated at IP66 or IP45 Operating temperature: -40C to +70C Operating Voltage: 9 to 30 Vdc
Product Codes
576.501.005.A Banshee Multi-Tone Sounder Red, Low profile base (ADT) (Replaces 576.501.004.A & 576.001.008.A) Banshee Multi-Tone Sounder Red, Low profile base (Thorn) (Replaces 576.501.004.T, 576.501.008.T & 576.501.019) Banshee Multi-Tone Sounder Red, Weather Proof base (ADT) (Replaces 576.501.015.A & 576.501.024.A) Banshee Multi-Tone Sounder Red, Weather Proof base (Thorn) (Replaces 576.501.015.T & 576.501.024.T) Banshee Multi-Tone Sounder White, Low Profile base (ADT) (Replaces 576.501.033.A)
576.501.005.T
576.501.016.A
576.501.016.T
576.501.025.A
Chapter 2 Page 62
Fire Catalogue
09/10
Yodalarms
This versatile range of sounders are ideally suited for fire, safety and security hazard warning. Technical Specification Dimensions: YO3: 89H x 89W x 85D mm YO5: 134H x 134W x 128D mm YO8: 216H x 216W x 153D mm Product Codes 576.501.001 YO3 Yodalarm 3 24Vdc 100dB @ 1Mtr 576.501.002 YO5 Yodalarm 5 24Vdc 106dB @ 1Mtr 576.501.003 YO8 Yodalarm 8 24Vdc 112dB @ 1Mtr
09/10
Fire Catalogue
Chapter 2 Page 63
Technical Specification
Model Operation Operating Voltage Range Sound Output @ 1m Volume Control Current Consumption Tones Symphoni High Output 2 Hours Continuous 9-28Vdc Up to 120dB(A) 240mA +/- 20mA on Tone 3 1 to 32 Symphoni (Low Power) Continuous 12-30Vdc 100dB(A) +/- 2dB(A) @24Vd. c. Down to 80dB approx. 5mA +/- 1mA at all volumes Alternating 990Hz/650Hz@2Hz Continuous 990Hz Intermittent 990Hz, On/Off@1Hz Synchronised Start +/- 0.5% -25C to +70C Polarised Input ABS Plastic Case IP42 0.212Kg
Synchronisation Frequency Stability Operating Temperature Line Monitoring Method Construction Ingress Protection Weight
Synchronised Start +/- 0.15% -25 C to +55C Polarised Input ABS Plastic Case IP42 0.58Kg
Roshni
A flexible alarm sounder for Fire and Security applications complete with volume control and dil switch to provide 32 tones. Low profile Roshni with Deep base offers IP65 protection. All Roshni sounders have synchronised start for self synchronisation without third wire. Technical Specification Dimensions: 93 Dia x 105D mm (Deep base) Colour: Red or white Output Voltage: 9-28Vdc Typical Current: 24Vdc@16mA Typ. Sound Output: @1m 102dB Product Codes ROSHRDSR ROSHNI Sounder c/w deep base red 576.501.220 ROSHNI Sounder c/w shallow base red 576.501.221 ROSHNI Sounder c/w shallow base white 576.501.222 ROSHNI/Flashni Deep Base - Red 576.501.223 ROSHNI/Flashni Deep Base - White
Chapter 2 Page 64
Fire Catalogue
09/10
Firecryer
The FIRECRYER is an electronic sounder which provides as default the same electronic sound as the MT Besson Banshee and in addition, provides 4 predefined voice messages, which can be synchronised across a zone of sounders. The FIRECRYER offers an excellent service upgrade opportunity in the UK for systems installed to BS5839pt1 and may also provide opportunities elsewhere.
Technical Specification
Dimensions: Operating Voltage: Current Consumption: IP45 - 92dia 61.3 Hmm IP66 - 92dia 85.5 Hmm Nominally 24Vdc Min. 18Vdc Max. 30Vdc Average 19mA Min. 10mA Max. 23mA (Subject to message) Fast sweep - 100dBA 97dBA approx reverse polarity protection -25C to +70C 90% relative humidity (non-condensing) Standard base - IP45 Special base - IP66 Red Flame-retardant ABS
Product Codes
576.501.042 576.501.052 576.501.051 576.501.035.A 576.501.104.A 576.501.105 Banshee IP66 backbox for Firecryer Sounders Mini Fire Cryer Voice Enhanced Base Sounder Cable Spacing Ring Multi Message Synchronised Mini Fire Cryer Voice Enhanced Base Sounder MFC4SUA 4 message Red ADT Branded Fire Cryer Sounder MFC4SCA Custom Message Red ADT Branded Fire Cryer Sounder MFC-CM Fire Cryer Custom Message Chip
Sound output: Voice message: Polarity D.C. Operating Temp: Humidity: Weatherproofing:
Housing Material: Standard Messages: AK - Fire Emergency, please remain calm and evacuate the building immediately. AB - This is a fire alert. This is a fire alert. Await further instructions. Await further instructions. SP - This is an ADT fire alarm test. No action required. AD - Fire Alarm Test Now Complete.
09/10
Fire Catalogue
Chapter 2 Page 65
Product Codes
Product Message Brand Synchronised Reference 1 2 3 4 576.501.035.A MFC4SUA AK AB AD SP ADT Yes 576.501.104.A *MFC4SCA Customer Defined ADT Yes 576.501.051 F/C/4A AK AB AD SP Yes * For recording of special messages there is a charge. This can be ordered under product code 576.501.105 MFC-CM. This includes the supply of a different timer chip for the F/S/VMC synchronisation board.
Chapter 2 Page 66
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 2 Page 67
Technical Specification
Voltage V d.c. 24 24 24 24 Power Output Alarm Current Watt(s) mA 1 42 2 84 3 126 5 210 Flash Rate 60/min 60/min 60/min 60/min Rating IP65 IP65 IP65 IP65 Temp. Range Height -30 to +70C -30 to +70C -30 to +70C -30 to +70C Dimensions (mm) Diameter 51 75 51 75 51 75 75 90
Product Codes
540.001.030 540.001.031 540.001.032 540.001.033 20-112 20-113 20-120 Low Low Low Low Low Low Low profile profile profile profile profile profile profile clear 24Vdc 1 watt blue 24Vdc 1 watt amber 24Vdc 1 watt red 24Vdc 1 watt red 24Vdc 2 watt red 24Vdc 5 watt red 24Vdc 3 watt
Features
High Power 10 Candela Current Surge Suppression High Efficiency 88mA at 24VDC 1 Hz Flash Rate Protected to IP54 Wide Operating Voltage 10 to 60 VDC Operating Temperature -25oC to + 70oC
Product Code
576.501.232 Solex 10 cd Beacon with red lens and white base
Chapter 2 Page 68
Fire Catalogue
09/10
Flashni
A combined sounder and beacon which combines the features of the Roshni electronic sounder with a fully integrated Xenon beacon. These sounders are fully compatible with all Roshni tones.
Technical Specification
Dimensions: 93 Dia x 92D mm (Shallow base) 93 Dia x 121D mm (Deep base) 18-30Vdc 68mA@24Vdc 101dB (A)@1m
Product Codes
20-118 576.501.224 Combined Roshni sounder/strobe complete with deep base (IP65). Combined Roshni Sounder/Strobe, Red Body/Red Lens complete with shallow base & tone switch. Combined Roshni Sounder/Strobe, Red Body/Red Lens, deep base, tone switch & separate sounder/strobe operation.
576.501.227
Features
Combined Sounder and LED Beacon Low Current -10mA @ 24VDC 6 selectable tones Volume control (2 levels) White housing, clear lens with red LEDs DDA compliant audio visual solution for UK Neat unobtrusive design Ideal for hotels, care homes, schools & offices Independent power cables allow a large number of AV platform sounders to be driven from a single 24V circuit 90dB sound output >1Cd light output at 1 Hz Approved to EN54-3 (pending)
.
Product Codes
576.501.250 576.501.255 517.050.401 517.050.005 09/10 Fire Catalogue Squashni G3/AV Sounder Beacon Squashni G3/AV Blanking Cap Pack of 5 4 Universal Base 4 Detector Base Locking Pin Kit (PK100) Chapter 2 Page 69
MXChecker
MXChecker - MXChecker replaces, in software, all configured MX loop devices on a single panel. It offers a user the following major functionality: Connection to a panel directly, or indirectly via the MXNetwork (in the same way Consys does to perform a download/upload). Provides the input status of each and every device configured on the Loops, e.g. make a Sounder go No Response, a detector appear active, etc. The ability to display the General Status of each and every Point configured on the Loops, e.g.indicate a Sounder is Isolated, a Callpoint is Disarmed, a Detector is Resetting, etc. The ability to display the Output Status of each and every Point configured on the Loops, e.g. indicate a Sounder is being driven to P1, a Relay Module is not being driven, etc.
MXConsys
MXConsys, the highly flexible and extremely powerful programming tool that has been used successfully with MX systems since day one. Specially designed for MX it is constantly being extended and refined to meet ever changing demands. Available for free download from the Tyco Fire and Security Website but requires a dongle and license to operate. Incorporated into MXConsys is MXConsys-Express An alternative approach to system configuration that simplifies the programming effort by automating many of the processes. Its heart lies in a number of pre-defined templates that have been expertly designed to match a selection of building types. The demands on users in terms of experience and training are considerably reduced.
MXLogger
MXLogger MXLogger enables the engineer to selectively monitor any device or devices on the addressable loops. The returned values are displayed on a PC screen and can be saved to a file for later analysis. Available for free download from the Tyco Fire and Security Website.
MXDesigner
MXDesigner is a sophisticated engineering design tool that not only ensures system parameters and design rules are obeyed but are key to the ordering and documentation processes. Battery calculations, loop loading calculations, remote bus parameters, system schematics and parts lists are all included. The extensive use of graphics and 'drag and drop' techniques makes the system easy and quick to use. In addition, a design module for the intrinsically safe MXDigital detectors and associated system 800 components is included. Available for free download from the Tyco Fire and Security Website.
MXRemote
MXRemote - Remote communications software provides a fast and efficient means of diagnosis without anyone having to leave the office. In situations where access to a site may be difficult or where an attending technician requires high level assistance then MXRemote is the tool for the job. Using modems, MXRemote can link to the MXDigital fire system via PSTN or IP and once connected, becomes an integral part of the fire system, acting as a fully functional repeater. All system functions are then available to the MXRemote operator. Available for free download from the Tyco Fire and Security Website but requires a dongle and license to operate.
MXFlow
MXFlow - If you have ever been involved in the configuration process for a complex 'cause and effect' programme, you will appreciate the benefits of an automated method of documenting your work. MXFlow does just that; it takes your MXConsys 'event action' and transcribes it into a graphical format that is comprehensive and easy to follow. It can be a valuable commissioning tool that saves time and effort as well as an easily understood form of documentation for future service use. Available for free download from the Tyco Fire and Security Website to authorised personnel.
MXService Tool
The TYCO MXService tool is a powerful and flexible tool for assistance in the installation, commissioning, diagnostics and service of Tyco MX detection systems. The MXService tool allows all MX addressable devices to be interrogated, tested and programmed. Suitable for desktop or single handed operation the MXService tool is battery operated using standard rechargeable batteries.
MXLoop Tester
The MXLoop Tester can test, commission and fault-find a loop of up to 250 MX analogue addressable detectors/devices, without a fire panel. A laptop is generally used for operation & display, but a One Person Installation Mode is automatically enabled on power up. Identifies all devices on the loop, determining addresses and types. Over-addressed (>250), unknown device types, and, generally, duplicate addressed devices are recognised. Monitors analogue values of all detectors/modules on the loop to determine device status: normal/alarm/fault/dirty etc.
Chapter 2 Page 70
Fire Catalogue
09/10
Product Code
TCD-1 MZX Interactive Training CD
09/10
Fire Catalogue
Chapter 2 Page 71
MXConsys
MXConsys is a powerful Windows programming tool which provides full system programming functions and project configuration and issue control. MXConsys is used on MINERVA MX, MX2,T2000 & MZX panels. It also supports automatic data transfer to MXGraph & TXG graphical mimic and alarm management systems. MXConsys is available under document control from authorised personnel in the Tyco businesses.
Product Codes
557.203.001 557.203.003 557.202.118 MXConsys Dongle and license (parallel) MXConsys Dongle and license (USB) MXConsys Download lead
Features
Facilitates remote diagnostics Display identical to panel view Remote Assistance
MXRemote
MXRemote is a Windows based software tool for remote service and support of MX detection panels. MXRemote provides a full function fire panel repeater running on a PC either locally or over dial up telephone lines or via the internet. Providing the operator has the correct passwords MXRemote allows all operator, manager, service and engineer functions available at the panel to be provided at the PC. This allows the customer or the Tyco service organisation to provide remote assistance, service and limited configuration assistance to the installation. MXRemote is available as a stand-alone software application for Tyco service operations. Alternatively Tyco Safety Products are able to provide consultancy and assistance in implementing MXRemote as an integrated part of a central station and service centre system.
Product Codes
557.203.002 557.203.004 557.202.116 UDS1100 MXRemote dongle and license (parallel) MXRemote Dongle and license (USB) MX-FIM Modem Lead Lantronics Device Server LAN
Chapter 2 Page 72
Fire Catalogue
09/10
MXService Tool
The TYCO MXSERVICE tool is a powerful and flexible tool for assistance in the installation, commissioning, diagnostics and service of Tyco MX detection systems. The MX SERVICE tool allows all MX addressable devices to be interrogated, tested and programmed. Suitable for desktop or single handed operation the MXSERVICE tool is battery operated using standard rechargeable batteries. An accessory pack provides alternative straps, and cigarette lighter adaptor. The MXService tool has a finite life time after which the software must be recharged by an MX authorised administrator.
Product Codes
516.800.918 516.800.922 516.800.924 516.800.926 516.800.927 516.800.929 801AP MXService tool Spare ancillary programming lead Pack of Spare Pins (Pk 10) MXService Tool PMS Dongle Parallel MXService Tool PMS Dongle (USB) PMS Programming Lead
Features
Compact Organises Tools Sturdy Construction Protects Tools
Product Code
516.800.923 MXService accessory kit
09/10
Fire Catalogue
Chapter 2 Page 73
Chapter 2 - MX Technology
Features
Pre-Programmed with latest AVR firmware Powered from XLM Loop card or FIM, No external power required Simple to operate Compact handheld device Complete with ribbon cable and connector
MXService Tool
This unit will allows the MZX Technology Fire Controller Loop Drivers to be updated to the latest software version. When required upgrades can be performed easily and quickly in the field with minimal system downtime. The MZX AVR Programmer is designed for use with MX,MZX,ZX and T2000 addressable fire controllers, please check document 17-05-AVR for compatibility details.
Technical Specifications
2 Button Keypad 3 Status LEDs Operating Temperature 0C to 50C Size 189 x 80 x 31
Product Code
516.800.941 Tyco MZX AVR Programmer
Chapter 2 Page 74
Fire Catalogue
09/10
Chapter 2 - MX Technology
Features
Ability to commission loops without a panel Verify installed loops before connection to panel Fault find loops whilst disconnected from panel
MXLoop Tester
The MX Loop Tester can test, commission and fault-find a loop of up to 250 MX digital addressable detectors/devices, without a fire panel. A laptop is generally used for operation & display, but a One Person Installation Mode is automatically enabled on power up. Identifies all devices on the loop, determining addresses and types. Over-addressed (>250), unknown device types, and, generally, duplicate addressed devices are recognised. Monitors analogue values of all detectors/modules on the loop to determine device status: normal/alarm/fault/dirty etc. Provides alarm test for detectors that support it. Allows Walk Test. Any device going into alarm is shown on the laptop with address and time. Walk Test Status (devices not tested yet) can be requested. Walk test mode overrides detection algorithm delays for fast testing. Monitors loop current and status, identifying open / short and over-current conditions. Details devices present on each side of break (so that position of break or tripped isolator can be determined). Includes commands to operate device LED and control output modules (relays and sounders). Turns on LED of faulty detectors (when there is no alarm) to aid visual identification. Automatic addressing mode allows un-programmed devices to be added in sequence and be automatically addressed. Detailed diagnostics and commissioning modes via laptop.
Technical Specification
Powered from 110V/230V mains supply via 24V, 3A plug pack, or from 24V batteries (batteries not included). Dimensions Unit: 200mm x122mm x 46mm Carry Bag: 250mm x 250mm x 70mm Weight: 2 kg (without battery)
Product Codes
557.203.021 557.203.022 557.203.023 557.203.024 557.203.026 MXLoop tester with EUROPEAN/UK MAINS to IEC CABLE SPARE ECM prog DB6 (FEM) - DB9 (FEM) null modem Spare carry bag with 2 pockets and strap Spare PSU 90-264VAC IN/24VDC 3A out Spare MX loop tester battery lead set
Features
Lightweight Convenient Compact
MX Service Case
There are 12 main circuit boards shared between the Minerva MX1000, MX4000 and MX2 Control Panels, Repeater Panels and Black Box Panels. The Engineers Minerva MX Service Kit is designed to hold one of each board in a convenient lightweight and portable case that will protect the boards whilst taking the minimum amount of space in a service engineers vehicle. The case also contains a fault finding manual and list of spares part numbers for re-order. The Engineers Minerva MX Service Kit allows a service engineer to carry onto site, sufficient spares to effect a panel repair efficiently and in a professional manner. It will avoid unnecessary return trips to the service vehicle or branch to collect spares and negates the need to carry cumbersome panels & enclosures in service vehicles. The contents of the case are detailed in the Service and Spares section of this catalogue.
Product Code
557.202.299 09/10 Fire Catalogue MX Service Case Chapter 2 Page 75
Tester ECM Prog Null Modem Tester Carry Bag tester PSU Tester Battery lead set
MX Service Kit The Engineers Minerva MX Service Kit 557.202.299 The Engineers Minerva MX Service Kit consists of an MX Service Case and the following MX Spare Service PCBs:1 1 1 1 1 1 1 1 1 1 1 1 x x x x x x x x x x x x Minerva 16 way input/output module FIM802 2 loop field interface module CPU800 1MB CPU PCB PSB800M panel power supply c/w loop booster module IOB800 8 Input/8 Output Expansion Board XLM800 2 Loop Expansion Module + Cable OCM800 Operator Control Module ODM800 Operator Display Module DCM800 Display & Control Module PSU830 Panel Power Supply C/W Loop Booster Module MX2 LCD Assembly MPM800 Multi Purpose Interface Module
Chapter 2 Page 76
Fire Catalogue
09/10
Minerva MZX-c
The Minerva MZX-c range of conventional twin wire fire alarm control panels will satisfy a wide range of applications from 2 to 8 zones and have many features that are normally associated with more expensive addressable systems. The Minerva MZX-c range of conventional fire detection control panels are designed to be both installer and user friendly. A high degree of flexibility and programmability allows the systems to be customised without the need for any configuration software. The range consists of 2, 4 and 8 zone panels together with an 8 zone repeater which is compatible with the 4 and 8 zone variants. The matching repeater panel has an inbuilt 240Vac power supply.
09/10
Fire Catalogue
Chapter 3 Page 1
2 x 0.5A
230VAC +10% - 15% 138W 1.5A 4 x 0.5A 4 x 0.5A 0.25A 2 x 3.4 A/H (PS-1230) -5C to +40C 95% Non Condensing 365 x 273 x 110 2.2 Light Grey RAL7035
N/A N/A
Product Codes
508.031.004.EG 508.031.005.EG 508.031.006.EG 508.031.016.EG MZX-c MZX-c MZX-c MZX-c 2 4 8 8 ZONE ZONE ZONE ZONE PANEL TYCO 2 WIRE PANEL TYCO 2 WIRE PANEL TYCO 2 WIRE REPEATER PANEL
Chapter 3 Page 2
Fire Catalogue
09/10
Minerva MZX-c+
The MZX-c+ range of Conventional Control Panels are designed to be both installer and user friendly. They are designed and manufactured to a high standard and are approved by LPCB to EN54 parts 2 & 4. These Panels are available in 4,8,16 & 32 zone versions along with suitable Repeaters for all models. The 8 to 32 Zone Panels are capable of driving any combination of 8 channel output expansion boards (relays, alarm circuits & open collector 0v outputs) up to a maximum of 12 boards which can be set to zonal activated or common output modes. Each Panel has extensive configuration options but remains easy to install, program and operate and are supported by detailed documentation on commissioning, operation and maintenance. The Panels are designed to work with a wide range of manufacturers detectors (in addition to Tyco detectors) and are suitable for use in many types of installation including upgrades and new installations Ancillaries and Expansion C1631 Repeater Interface Board provides a port for driving up to 5 repeater panels. One C1631 Repeater interface board is required for the panel and one for each repeater. Repeaters are supplied with a C1631 fitted. C1630 Output Expansion Interface Board provides a port for driving up to 12 output expansion boards. EXP 4 and EXP 4 PSU Expansion Housings are designed to house any combination of up to four output expansion boards. The PSU version is equipped with a 5A 24Vdc power supply with space for 2 x 12V 12Ah batteries. Housing dimensions 325W x 370H x 126D mm EXP 5 and EXP 5 PSU Expansion Housings are similar to the EXP 4 and EXP 4 PSU but accommodate five output expansion boards. Housing dimensions 400W x 441H x 131D mm C1633 LED Driver Board provides eight open collector outputs rated @ 60mA. Outputs can be zonal alarm or common alarm. C1634 Relay Output Module provides eight volt free changeover contacts rated at 1A 30Vdc. Outputs can be zonal alarm or common alarm. C1635 Monitored Output Board provides eight fault monitored 24Vdc outputs. Power can be derived from the control panel or an external source. Outputs can be zonal alarm or common alarm.. C1651 MZX-c+ Timer Module is an optional plug-in board with an alphanumeric LCD to provides a real-time clock display. The clock can be programmed to provide investigate delays, sequential alarms and day night settings. The unit is also used to store and display a total count of the number of times the panel enters the alarm condition. Can be fitted to 8, 16 and 32 zone panels. Additional Benefilts Inputs for remote Silence, Evacuate, Reset and Class change Configurable monitored or volt free outputs for Fire, Fault and Protection Outputs for zones 1 to 4 (open collector) with 8, 16 or 32 zonal outputs provided by optional expansion boards Outputs for Disablement active, Evacuate active and buzzer active (open collector) Volt free reset relay. Active for 10 seconds following a panel reset 8 to 32 zone systems can drive up to 12 expansion input / output modules per panel Drive up to 5 repeater panels
09/10
Fire Catalogue
Chapter 3 Page 3
N/A 6.2
Product Codes
508.032.002.EA 508.032.003.EA 508.032.004.EA 508.032.005.EA 508.032.006.EA MZXC+ 4 Zone Panel English/Arabic MZXC+ 8 Zone Panel English/Arabic MZXC+ 16 Zone Panel English/Arabic MZXC+ 32 Zone Panel English/Arabic MZXC+ 8 Zone Repeater 240Vac English/Arabic 508.032.007.EA MZXC+16 Zone Repeater 240Vac English/Arabic 508.032.008.EA MZXC+ 32 Zone Repeater 240Vac English/Arabic 508.032.012 MZXC+ 4 Way Expansion Housing 508.032.013 MZXC+ 4 Way Expansion Housing with PSU 508.032.014 MZXC+ 5 Way Expansion Housing 508.032.015 MZXC+ 5 Way Expansion Housing with PSU 557.201.502 Flush Mount Bezel for MZXC+ 4/8/16 Zone Panel and Repeater 2605060 C1630 O/P Expansion Interface Board 2605061 C1631 Repeater Interface Board 2605062 C1632 16 Zone Interface Board 2605063 C1633 LED Driver Board 2605064 C1634 Relay Output Board 2605065 C1635 Monitored Output Board 2605070 C1651 MZX-c+ Timer Board
Chapter 3 Page 4
Fire Catalogue
09/10
Technical Specification
Dimensions: T1204 & T1216RDC 335w x 270h x 148d mm T1216 & T1216R 420w x 445h x 148d mm T1232/T1216W/T1232RAC/T1232R DC/T1200EA/T1200EDC 500w x 535h x 174d mm T1200B 335w x 170h x 102d mm Designed to IP56 -10C to +55C 95% RH (non condensing)
09/10
Fire Catalogue
Chapter 3 Page 5
508.023.003
508.023.004
508.023.005
508.023.006
508.023.011 508.023.012 508.023.013 508.023.014 508.023.015 508.023.016 508.023.021 508.023.022 508.023.023 508.023.025 2605061 2605063 2605064 2605065 508.023.035 508.023.036 508.023.051 508.023.052 508.023.053 508.023.054
Chapter 3 Page 6
Fire Catalogue
09/10
Product Codes
508.033.050.EA MZX-e Extinguishing Control Panel English / Arabic 508.033.002.EA MZX-e SLU1 Status Lamp Unit, Indication only English / Arabic 508.033.003.EA MZX-e SLU2 Status Lamp Unit, Indication, Auto/Manual Select and Manual Release English / Arabic 508.033.004.EA MZX-e SLU3 Full Function Status Lamp Unit, Indication, Auto/Manual Select, Manual Release, Hold, Abort & Time Counter English / Arabic 508.033.005.EA MZX-e SLU4 Weatherproof Status Lamp Unit, Indication and Auto/Manual Select English / Arabic Chapter 3 Page 7
09/10
Fire Catalogue
Technical Specification Dimensions: H(mm) W(mm) D(mm) E1 100 100 115 E3 300 100 115
E3 Red/Amber/Green lamp unit Heavy Duty IP67 Cast Aluminium Surface Mount Lamp Unit Three 24Vdc lamps: Red labelled 'Extinguishing System Operated'
Amber labelled 'Extinguishing System Automatic Control' Green labelled 'Extinguishing System Manual Control'
Product Codes 540.007.002 E3 Red/Amber/Green lamp unit 599.001.029 Spare Bulb for E1/E3 24V-5W
Chapter 3 Page 8
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 3 Page 9
Product Codes
557.200.071 557.200.074 557.200.076 557.200.077 557.200.078 557.200.079 557.200.080 Paging Transmitter 40 Character Alpha Numeric Pager 1/2 wave dipole antenna Wall mounting folded dipole antenna Pole mounting folded dipole antenna 5 metre antenna feeder cable 10 metre antenna feeder cable
Chapter 3 Page 10
Fire Catalogue
09/10
Through innovative design the Series 600 detectors have reduced the installation and servicing time to a minimum, needing only one visit to complete the installation and having a park position for the detector to ease the servicing. The Series 600 includes the unique enhanced Carbon Monoxide CO fire detector, which provides a general purpose fire detector with unprecedented early detection capability and excellent false alarm immunity. The CO fire detectors are the first choice for sleeping risks. Also included within the range is the intelligent high performance optical smoke (HPO) detector. The use of the patented optical sensing chamber, together with refined signal processing, has enabled the introduction of a smoke detector suitable for fast, reliable smoke detection of both slow and fast developing fires.
The HPO can be seen as a truly universal smoke detector, suitable for most applications. Approvals:-
09/10
Fire Catalogue
Chapter 3 Page 11
Optical Smoke
These detectors are capable of detecting the visible smoke produced by materials which smoulder or burn slowly, i.e. soft furnishings, plastic foam etc;. or 'smoke' produced by overheated but unburnt PVC. These detectors are particularly suitable for general applications and areas where cable overheating may occur e.g. electrical services areas. The novel design of the asymmetrical sampling chamber and signal processing techniques stop unwanted alarms caused by very small insects. i.e. thrips. Smoke entering the sampling chamber scatters the infra-red light pulses onto a photo-diode. These pulses are converted to an electrical signal which is compared against a preset alarm level. Datasheet - Product Code PSF123 Manual - Vol01C-02-D6 Detectors Fire Manual Product Codes 516.600.001.A Approval Branded LPCB ADT 516.600.001.T Approval Branded LPCB 516.600.001.Y Approval LPCB 516.600.201 Approval Marine Thorn Branded Tyco Branded Tyco
Heat
These detectors use two networked thermistors in a bridge configuration to provide a fast response, that depends both on absolute temperature and notes the change of temperature. The rate of rise/fixed temperature heat detectors can be used in areas where smoke sensors are unsuitable due to environmental conditions (smoke, dust etc,). Such areas include kitchens, locker rooms, canteens, garages, loading bays etc. Datasheet - Product Code PSF123 Manual - Vol01C-02-D5 Detectors Fire Manual Rate of Rise Product Codes 516.600.003.A Approval Branded Model LPCB ADT 601H-R 516.600.003.T Approval Branded Model LPCB Thorn 601H-R 516.600.003.Y Approval Branded Model LPCB Tyco 601H-R 516.600.203 Approval Branded Model Marine Tyco 601H-R-M Fixed Temperature 60C Product Code 516.600.214 Approval LPCB /Marine Fixed Temperature 90C Product Code 516.600.033 Approval LPCB/Marine
Model 611H-F
Model 631H-F
Chapter 3 Page 12
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 3 Page 13
43
109
21.2
108
Technical Specification - Series 600 601 601PH/P/601PH-M/601P-M Weight 100g 93g Material Operating Temp. -20 to +70C -20 to +70C Storage Temp. -40 to +80C -25 to +80C Relative Humidity Quiescent Current(typ) 62A 65A Alarm Current(typ) 54mA 45mA Operating Voltage 10.5 - 33 Vdc 10.5 - 33 Vdc *Short Term (<3min) -40 to +120C
601H-R/611H-F/601H-R-M/631H-F 80g FR 110 Bayblend -20 to +70C* -25 to +80C 95/98% Non-Condensing 61/65A 53mA 10.5 - 33 Vdc
601CH/601CH-M 90g -10 to +55C -20 to +55C 87A 53mA 10.5 - 33 Vdc
Chapter 3 Page 14
Fire Catalogue
09/10
Technical Specification
Operating voltage @ 0.5A: Switching Current: Contact Resistance: Actuating Temp: (factory set) Fixed Temp. only: Accuracy: Ambient Temp.: Relative Humidity: Protection Category: Thread Size: 240Va.c. to 24Vdc 5 to 500mA <1 ohm 60 to 240C Type E + or - 5% -40 to +270C 100% RH IP67 M20 x 1.5mm
Product Codes
516.033.011 516.033.012 516.033.013 516.033.014 T4E60X T54B Point Type heat detector - 60C T4E90X T54B Point Type heat detector - 90C T4E100X T54B Point Type heat detector - 100C T4E145X T54B Point Type heat detector - 145C
09/10
Fire Catalogue
Chapter 3 Page 15
FIRERAY 5000 Multi Head Auto Aligning Infrared Optical Beam Smoke Detector
The FIRERAY 5000 motorised, auto aligning infrared optical beam smoke detector can now be installed with up to four detector heads per system, thus saving on installation time and costs. This innovative system has been designed from the ground up to include pioneering technology that fully addresses the needs of the installer and user, both now and in the future. With its industry leading optics, the FIRERAY 5000 is ideally suited for the protection of large areas where the use of traditional detection technologies would prove to be too difficult and/or costly to install. The FIRERAY 5000 combines an infrared transmitter and receiver in the same discrete unit and operates by projecting a well-defined beam to a reflective prism, which returns the beam to the receiver for analysis. Smoke in the beam path causes a drop in power, which, if below a pre-determined level, results in an alarm signal. Getting the system operational is simplified by a number of groundbreaking features that combine to make the FIRERAY 5000 the quickest and easiest detector of its type to install. Once the detector heads are connected, using the Easifit First Fix system, an integral LASER, which is aligned along the optical path of the beam, can be activated. This allows the reflective prism to be sighted quickly and with confidence. Once the LASER has been used to coarsely align the beam, the AutOptimise beam alignment system takes over and automatically steers the beam into the optimum position. The system can be fully customised, according to local conditions; both alarm thresholds (sensitivity) and time to Alarm/Fault can be set from the ground level System Controller. Each detector head is independently configurable from 8m through to 100m and has its own individual fire threshold. The System Controller retains one set of Fire and Fault relays that is common to all detectors that are installed. The FR5000 MultiHead is supplied with one detector head and reflector for single beam operation from 8 to 50 meters. Up to 3 additional detector heads can be added to the controller to enable larger or more complex areas to be protected (Subject to local codes and standards)
Technical Specification
Controller: 202w x 230h x 81d mm 0.9 Kg Detector: 134w x 135h x 134d mm - 0.5 Kg Additional detector head 2mA @ 24VDC Operating Current (low power mode): 10mA @ 24VDC Operating Voltage: 14 to 28VDC IP Rating: IP54 Operating Temperature: -20 to +55oC Humidity: 93% RH (non condensing) max
Product Codes
516.015.020 516.015.021 516.015.007 FireRay 5000 System (50m) FR 5000 Detector Head (50m) FireRay Reflector 100 X 100mm 4 reflectors are required for distances from 50 to 100m
Chapter 3 Page 16
Fire Catalogue
09/10
Technical Specification
Technical Specification Dimensions(mm) Height Width Depth 95 75 115 260 210 80 +11.5 to +28Vdc <13mA <20mA -10oC to +55oC up to 95% RH (Non-condensing) IP54 Weight (Kg) 0.4 2.25
Product Codes
516.015.006.A 516.015.006.T 920450 516.015.007 516.015.008 FireRay2000 optical beam smoke detector VdS approved, ADT Branded FireRay2000 optical beam smoke detector VdS approved, Thorn Branded FireRay2000 -UL Optical beam smoke detector - UL approved FireRay2000 Retro-Reflector 100 x100mm FireRay2000 Alignment tool
Voltage RangeFireray 2000 Fireray 2000 Quiescent Current Fireray 2000 Alarm Current Operating Temp. Range Humidity Fireray
Product Codes
5000-005 5000-006 5000-007 5000-008 Universal Mounting Bracket Flat Mounting Plate for 1 to 4 Prisms Prism Mounting Plate for 4 Prisms Prism Mounting Plate for 1 Prism
09/10
Fire Catalogue
Chapter 3 Page 17
Technical Specification
Dimensions: Weight: Operating Temp: Relative humidity: Rating: Operating Voltage: Quiescent Current: 178H x 130W x 75D mm 0.55Kg -25C to +70C Up to 98% RH non-condensing IP55 +8 to +30Vdc 60-80A
Product Codes
516.016.005 516.016.006 LD40 High resistance sensor cable blue 200M reel LD40 High resistance sensor cable black - 200M reel (Nylon sheath suitable for petrochemical exposure) LD40 EOL Termination kit (PK10) LD40 In-line Jointing kit LD40 Analyser module with conventional detection zone interface. B6782-003 EDGE CLIP 2-3mm WEB B6782-024 EDGE CLIP 3-8mm WEB B6782-025 EDGE CLIP 8-13mm WEB B6782-026 EDGE CLIP 14-20mm WEB B6782-004 'T' CLIP B6782-005 PIPE CLIP B6782-023 'V' CLIP B6782-008 NEOPRENE SLEEVE B6782-151 THERMAL SPACER B6782-152 THERMAL SPACER
516.016.010 516.016.011 516.016.012 516.016.201 516.016.202 516.016.203 516.016.204 516.016.205 516.016.206 516.016.207 516.016.208 516.016.209 516.016.210
Ceiling Clip
Edge Clip
Pipe Clip
Thermal Spacer
V Clip
Chapter 3 Page 18
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 3 Page 19
Chapter 3 Page 20
Fire Catalogue
09/10
09/10
Fire Catalogue
Chapter 3 Page 21
Chapter 3 Page 22
Fire Catalogue
09/10
The units are designed to operate in airspeeds of 1.5 to 25 metres per second. A range of sampling tubes from 525mm to 1575mm are available.
Technical Specification Operating temperature: -20C to +70C Storage temperature: -25C to +80C Relative Humidity: 0 to 95% SMP69 Stainless steel 316 housing with transparent polycarbonate cover
09/10
Fire Catalogue
Chapter 3 Page 23
Product Codes
517.025.049 517.025.051 517.025.052 517.025.053 517.025.054 517.025.055 DPK4 - Duct Probe with MZX detector base 5" - 5B DPK600 - Duct Probe Tube 600 mm DPK1500 - Duct Probe Tube 1500 mm DPK2800 - Duct Probe Tube 2800 mm DPKM - Duct Probe Mounting Bracket Spare Filters for DPK4/DPK4I (Pk 10)
Chapter 3 Page 24
Fire Catalogue
09/10
Technical Specification
(Indoor & Outdoor) Housing: Operating Temp.: Outdoor Indoor Relative Humidity: PC/ABS -30oC TO +70oC -10oC TO +55oC up to 95% RH (non-condensing) Commonly Used Callpoints
Model MCP200 MCP210 MCP230 MCP270 Keyswitch Colour Red Red Red Yellow White Type Conventional Conventional Conventional Conventional Conventional Alert Evacuate Alert Evacuate IP Rating 24D 24D 67 24D 24D R4/R1 Ohms 120/470 47/39 120/470 47/39 Not Applicable
09/10
Fire Catalogue
Chapter 3 Page 25
Chapter 3 Page 26
Fire Catalogue
09/10
515.001.128 Callpoint hinged cover for use on MCP & CP style callpoint models (Colour -Clear)
09/10
Fire Catalogue
Chapter 3 Page 27
Chapter 3 Page 28
Fire Catalogue
09/10
STOPPER
The callpoint STOPPER provides protection from malicious or accidental activation of manual callpoints. Available for flush or surface mounted callpoints the STOPPER is also available with optional high pitch sounder which is activated when the lid is lifted. An optional Break-Seal fitting kit allows Break-Seals to be used to provide extra protection.
Product Code 515.001.029 515.001.030 515.001.036 515.001.034 515.001.035 515.001.031 515.001.032 Ref STI6530 STI6531 STI6535 STI1230 STI3150 STI6532 STI6533 STOPPER Flush Surface 4 4 4 4
WARNING:- Break seals only to be fitted by agreement with relevant fire authorities. The STOPPER is suitable for all callpoints up to 100mm square, including the MCP200 and other indoor KAC style callpoints.
STOPPER II With Sounder Weatherproof
4 4
4 4 4 4
STOPPER Dimensions
Product Code
515.001.033 IPO36 Break Seal Kit (pack of 1)
Flush Fit Millimetres A 137 B 140 C 104 D 45 E 12.5 F 12.5 G 185 H 12.5 Stopper STI6530 Stopper with Sounder STI6532
Surface Fit
(+30mm)
STI6531 STI6533
STOPPER STOPPER II Max. Callpoint Size 100 x 100mm 160 x 160 mm Max. Callpoint Depth 57.5 120 (+30mm Surface)
STOPPER II Dimensions
09/10
Fire Catalogue
Chapter 3 Page 29
STOPPER II
STOPPER II is constructed as the STOPPER from tough injection moulded polycarbonate. Physically larger than the STOPPER the STOPPER II extends the number of products to which these tough multi-purpose covers can protect. It consists of a strong tamper-proof clear polycarbonate cover and frame that fits easily over such products as break glass callpoints. STOPPER II can also be fitted with an integral battery powered sounder which activates if the cover is lifted. The STOPPER II is suitable for callpoints up to 160mm square.
Product Code
515.001.034
Features
Strong polycarbonate construction Provides environmental protection Ideal for offshore environments
Product Codes
515.001.036 515.001.035
STI6535 Surface fit Weather STOPPER STI3150 Surface fit Weather STOPPER II
09/10
Chapter 3 Page 30
Fire Catalogue
Keybox
This tough polycarbonate breakglass keybox is available to protect emergency keys. Product Code 515.001.043 STI6720 Keybox with printed glass
09/10
Fire Catalogue
Chapter 3 Page 31
Sounders
A range of sounders to meet a wide variety of alarm applications where loud, penetrating and distinctive warnings must be given to alert people of fire situations. In addition, multitone electronic sounders can give a variety of sounds to signal other conditions e.g.extinguishing gas release imminent, etc.
Note: For I.S. & Flameproof sounders, please see the special hazards section.
Chapter 3 Page 32
Fire Catalogue
09/10
Product Codes
576.500.014 576.500.015 577.001.002 240V Red bell 6 240Vac solenoid operated. Fire text 24V Red bell 6 24Vdc solenoid operated. Fire text Weatherproof gasket box for use with Solenoid operated bells
Features
CE marked Low current 6 bell (ONLY 11mA) Low cost Extra high 95dBA/m Slim profile (53mm) Fully suppressed and polarised Quick and easy to install LPCB approved to EN54 Pt 3
Product Codes
576.501.039.A 576.501.039.T 576.501.040.A 576.501.044.A 576.501.044.T 576.501.045 MBF-6EV ADT Branded MBF-6EV Thorn Branded MBF-8EV ADT Branded MBA-8EV ADT Branded MBA-8EV Thorn Branded BBX4 (2) W/P Backbox for MBA-8 Bell
09/10
Fire Catalogue
Chapter 3 Page 33
Technical Specification
Dimensions: Voltage: Typical Current: Typ. Sound Output: 6 diameter 18-30Vdc 24Vdc@30mA 94dB (A)@1m
Product Codes
20-100 6 24Vdc Electronic bell, weatherproof 20-101 6 24Vdc Electronic bell - red 20-111 6 24Vdc Electronic bell - white
Chapter 3 Page 34
Fire Catalogue
09/10
Technical Specification
LPCB and Vds approved to EN54 pt 3 Low Current consumption 32 Tones 3 Volume settings Rated at IP66 or IP45 Operating temperature: -40C to +70C Operating Voltage: 9 to 30 Vdc
Product Codes
576.501.005.A Banshee Multi-Tone Sounder Red, Low profile base (ADT) (Replaces 576.501.004.A & 576.001.008.A) Banshee Multi-Tone Sounder Red, Low profile base (Thorn) (Replaces 576.501.004.T, 576.501.008.T & 576.501.019) Banshee Multi-Tone Sounder Red, Weather Proof base (ADT) (Replaces 576.501.015.A & 576.501.024.A) Banshee Multi-Tone Sounder Red, Weather Proof base (Thorn) (Replaces 576.501.015.T & 576.501.024.T) Banshee Multi-Tone Sounder White, Low Profile base (ADT) (Replaces 576.501.033.A)
576.501.005.T
576.501.016.A
576.501.016.T
576.501.025.A
09/10
Fire Catalogue
Chapter 3 Page 35
Yodalarms
This versatile range of sounders are ideally suited for fire, safety and security hazard warning. Technical Specification Dimensions: YO3: 89H x 89W x 85D mm YO5: 134H x 134W x 128D mm YO8: 216H x 216W x 153D mm Product Codes 576.501.001 YO3 Yodalarm 3 24Vdc 100dB @ 1Mtr 576.501.002 YO5 Yodalarm 5 24Vdc 106dB @ 1Mtr 576.501.003 YO8 Yodalarm 8 24Vdc 112dB @ 1Mtr
Chapter 3 Page 36
Fire Catalogue
09/10
Technical Specification
Model Operation Operating Voltage Range Sound Output @ 1m Volume Control Current Consumption Tones Symphoni High Output 2 Hours Continuous 9-28Vdc Up to 120dB(A) 240mA +/- 20mA on Tone 3 1 to 32 Symphoni (Low Power) Continuous 12-30Vdc 100dB(A) +/- 2dB(A) @24Vd. c. Down to 80dB approx. 5mA +/- 1mA at all volumes Alternating 990Hz/650Hz@2Hz Continuous 990Hz Intermittent 990Hz, On/Off@1Hz Synchronised Start +/- 0.5% -25C to +70C Polarised Input ABS Plastic Case IP42 0.212Kg
Synchronisation Frequency Stability Operating Temperature Line Monitoring Method Construction Ingress Protection Weight
Synchronised Start +/- 0.15% -25 C to +55C Polarised Input ABS Plastic Case IP42 0.58Kg
Roshni
A flexible alarm sounder for Fire and Security applications complete with volume control and dil switch to provide 32 tones. Low profile Roshni with Deep base offers IP65 protection. All Roshni sounders have synchronised start for self synchronisation without third wire. Technical Specification Dimensions: 93 Dia x 105D mm (Deep base) Colour: Red or white Output Voltage: 9-28Vdc Typical Current: 24Vdc@16mA Typ. Sound Output: @1m 102dB Product Codes ROSHRDSR ROSHNI Sounder c/w deep base red 576.501.220 ROSHNI Sounder c/w shallow base red 576.501.221 ROSHNI Sounder c/w shallow base white 576.501.222 ROSHNI/Flashni Deep Base - Red 576.501.223 ROSHNI/Flashni Deep Base - White
09/10
Fire Catalogue
Chapter 3 Page 37
Chapter 3 Page 38
Fire Catalogue
09/10
Firecryer
The FIRECRYER is an electronic sounder which provides as default the same electronic sound as the MT Besson Banshee and in addition, provides 4 predefined voice messages, which can be synchronised across a zone of sounders. The FIRECRYER offers an excellent service upgrade opportunity in the UK for systems installed to BS5839pt1 and may also provide opportunities elsewhere.
Technical Specification
Dimensions: Operating Voltage: Current Consumption: IP45 - 92dia 61.3 Hmm IP66 - 92dia 85.5 Hmm Nominally 24Vdc Min. 18Vdc Max. 30Vdc Average 19mA Min. 10mA Max. 23mA (Subject to message) Fast sweep - 100dBA 97dBA approx reverse polarity protection -25C to +70C 90% relative humidity (non-condensing) Standard base IP45 Special base IP66 Red Flame-retardant ABS
Product Codes
576.501.042 576.501.052 576.501.051 576.501.035.A 576.501.104.A 576.501.105 Banshee IP66 backbox for Firecryer Sounders Mini Fire Cryer Voice Enhanced Base Sounder Cable Spacing Ring Multi Message Synchronised Mini Fire Cryer Voice Enhanced Base Sounder MFC4SUA 4 message Red ADT Branded Fire Cryer Sounder MFC4SCA Custom Message Red ADT Branded Fire Cryer Sounder MFC-CM Fire Cryer Custom Message Chip
Sound output: Voice message: Polarity D.C. Operating Temp: Humidity: Weatherproofing:
Housing Material: Standard Messages: AK - Fire Emergency, please remain calm and evacuate the building immediately. AB - This is a fire alert. This is a fire alert. Await further instructions. Await further instructions. SP - This is an ADT fire alarm test. No action required. AD - Fire Alarm Test Now Complete.
09/10
Fire Catalogue
Chapter 3 Page 39
Product Codes
Product Message Brand Synchronised Reference 1 2 3 4 576.501.035.A MFC4SUA AK AB AD SP ADT Yes 576.501.104.A *MFC4SCA Customer Defined ADT Yes 576.501.051 F/C/4A AK AB AD SP Yes * For recording of special messages there is a charge. This can be ordered under product code 576.501.105 MFC-CM. This includes the supply of a different timer chip for the F/S/VMC synchronisation board.
Chapter 3 Page 40
Fire Catalogue
09/10
NOTE: For I.S. Flameproof Beacons, please see the special hazards section.
09/10
Fire Catalogue
Chapter 3 Page 41
Technical Specification
Voltage V d.c. 24 24 24 24 Power Output Alarm Current Watt(s) mA 1 42 2 84 3 126 5 210 Flash Rate 60/min 60/min 60/min 60/min Rating IP65 IP65 IP65 IP65 Temp. Range Height -30 to +70C -30 to +70C -30 to +70C -30 to +70C Dimensions (mm) Diameter 51 75 51 75 51 75 75 90
Product Codes
540.001.030 540.001.031 540.001.032 540.001.033 20-112 20-113 20-120 Low profile clear 24Vdc 1 watt Low profile blue 24Vdc 1 watt Low profile amber 24Vdc 1 watt Low profile red 24Vdc 1 watt Low profile red 24Vdc 2 watt Low profile red 24Vdc 5 watt Low profile red 24Vdc 3 watt
Features
High Power 10 Candela Current Surge Suppression High Efficiency 88mA at 24VDC 1 Hz Flash Rate Protected to IP54 Wide Operating Voltage 10 to 60 VDC Operating Temperature -25oC to + 70oC
Product Code
576.501.232 Solex 10 cd Beacon with red lens and white base
Chapter 3 Page 42
Fire Catalogue
09/10
Flashni
A combined sounder and beacon which combines the features of the Roshni electronic sounder with a fully integrated Xenon beacon. These sounders are fully compatible with all Roshni tones.
Technical Specification
Dimensions: 93 Dia x 92D mm (Shallow base) 93 Dia x 121D mm (Deep base) 18-30Vdc 68mA@24Vdc 101dB (A)@1m
Product Codes
20-118 576.501.224 Combined Roshni sounder/strobe complete with deep base (IP65). Combined Roshni Sounder/Strobe, Red Body/Red Lens complete with shallow base & tone switch. Combined Roshni Sounder/Strobe, Red Body/Red Lens, deep base, tone switch & separate sounder/strobe operation.
576.501.227
09/10
Fire Catalogue
Chapter 3 Page 43
Product Codes
576.501.250 576.501.255 517.050.401 517.050.005 Squashni G3/AV Sounder Beacon Squashni G3/AV Blanking Cap Pack of 5 4 Universal Base 4 Detector Base Locking Pin Kit (PK100)
Chapter 3 Page 44
Fire Catalogue
09/10
Product Codes
576.501.251 576.501.255 517.050.401 517.050.005 Squashni G3/AV 2 Wire Sounder Beacon Squashni G3/AV Blanking Cap Pack of 5 4 Universal Base 4 Detector Base Locking Pin Kit (PK100)
09/10
Fire Catalogue
Chapter 3 Page 45
Chapter 3 Page 46
Fire Catalogue
09/10
High level user interface allows end user to make changes to point attributes and layout further reducing lifetime cost of ownership. Centralised security administration means that operator accounts are administered through the TXG clients common database Mouse, keyboard or touch-screen control with full multimedia compatibility Dual language switching The ability to display live video when specific predefined alarm conditions occur Easy to configure and set-up. No special networking or PC training required Facilities and maintenance management report and analysis tools are available
09/10
Fire Catalogue
Chapter 4 Page 1
Product Codes
508.040.100 508.040.001 508.040.002 508.040.003 TXG USB Server Dongle/License/Software English TXG001-Single Client with 1 panel (Requires TXG USB) TXG004-Single Client with 2 to 4 panels (Requires TXG USB and TXG001) TXG010-Single Client with 5 to 10 panels (Requires TXG USB, TXG001 and TXG004) TXG020-Single Client with 11 to 20 panels (RequiresTXG USB, TXG001, TXG004 and TXG010) TXG999-Single Client with 21 or above panels (Requires TXG USB, TXG001, TXG004 TXG010 and TXG020) TXG-C Additional Client license TXG-MIN80 Minerva driver license TXG-OPC - OPC Alarm / Event & Data Access Server Licence TXG-CPP - SIMPLEX CPP driver TXG-PBS/FAST2000 DRIVER Dell Optiplex 780 DT PC (no monitor) for use with TXG 19 LCD Touchscreen
508.040.004
Chapter 4 Page 2
Fire Catalogue
09/10
RS232
TO A COMPLEX INSTALLATION WITH MULTIPLE DIVERSE NETWORKS AND DISTRIBUTED CLIENTS Large multi-building facilities may have a number of fire detection networks, possibly installed over an extended period of time. TXG can be used as a hub to integrate these systems with a number clients providing annunciation and control where it is needed.
TXG Client
TLI800G Interface
TXG Server
TXG Client
Minerva MX Network
09/10
Fire Catalogue
Chapter 4 Page 3
MXNet
MXNet provides a true peer to peer communications interface for up to 99, MINERVA MX, or MINERVA T2000 fire controllers in any combination and the TXG, graphical user interface. The units can be inter-connected into a large network without the need for a host or master controller. MXNet is based upon a combination of hardware and software that allows MX fire controllers (Nodes) to be linked together. The MXNet supports up to 99,000 analogue/addressable points and over 49,000 digital I/0 points. The network co-ordinates and distributes alarm annunciation and supervises system operation. When connected to the network, each MX Fire controller maintains its full stand-alone features, functions and capabilities.
Additional Features Automatic network re-configuration when a previously failed node is restored to the network. Up to 3,000 metres between nodes with twisted/shielded cable. System will operate on standard 2 core MICC. MX controllers may be grouped into sub-nets where each panel is programmed to inter-act only with other selected controllers. Plug-in module (TLI-800) easily connects an MX fire controller to the network. Data is re-generated at each MX controller and is sent out over the MXNet as new clean data. All degradation in received data due to noise on a line, line attenuation, or phase shifting is eliminated when the data is re-generated. The MXNet uses a token-passing, non collision communication protocol for data transmission. "Network zones" and "sectors" allow the network controllers to be configured as a single "seamless" system. TXG, a P based graphical user interface, connects .C. directly on to the network. MXNet supports combinations of MICC, twisted/shielded pair cabling, fibre optic cabling, and dedicated telephone line. Multiple communication topologies bus or ring.
Chapter 4 Page 4
Fire Catalogue
09/10
TLD-530 The Telephone Line Driver Module (TLD-530) is used to interface two (2) dedicated telephone line circuits to the TLI-800 module. The TLD-530 line driver module converts the RS-485 signals received from the TLI-800 network interface module to signals capable of being transmitted over the telephone line circuits. One TLI-800 supports two channels so only one module is required per controller for both single path and redundant path star connections. The interface allows for field configured baud rates and supports distances of up 3,000 metres. Up to two units can be fitted into a TLO/TLD Housing. Technical Specification Dimensions 170H x 120W x 20D mm Weight 140g
Product Codes TLD 530 ThornNet/MXNet 557.180.699 direct line driver PCB 557.180.148.A TLO/TLD Housing - ADT branded
CCU3 The CCU3/C-MXMB provides a MODBUS interface to a number of MX panels on an MXNet. CCU/IO boards may also be connected to provide general I/O devices accessed through the MODBUS interface. The CCU3/C-MXMB connects to MX panels on the MXNet via a TLI-800 (TPI) interface card using RS232 (PL2 socket). It connects to MODBUS via either an RS232, RS485 (default) or RS422 connection. Another port allows up to 8 CCU/IO boards to be connected. Each CCU/IO has 8 relay outputs that can be used as inputs to the MX. These contacts are controlled via WRITE commands to the MODBUS map. Each CCU/IO also has 8 supervised inputs whose status can be read from the MODBUS map. The CCU3/C-MX Bridge enables the direct connection of an MX Technology fire controller and Minerva 16E or 80 fire controllers via the H-Bus Communications Driver Module (CDM). No network cards are required in this configuration. The CDM attaches on to the Minerva H-Bus and provides a serial port for the CCU3/C-MX bridge. Technical Specification Input Voltage 18-30Vdc Current 150mA at 24Vdc Dimensions 140 x 105 x 15mm Product Code MX CCU3/C-MXMB 557.202.046 MX to MOD Bus Interface
Product Codes MX Bridge CCU3/C-MX Bridge 557.202.123 557.180.025 Minerva Comms Driver Module
09/10
Fire Catalogue
Chapter 4 Page 5
MX Minerva - Bridge
The MX Minerva bridge enables a mix of Minerva and MX Panels anywhere on a shared network to operate as an integrated system. Housed in either a MXAPSU17 or MXAPSU38 housing, the MX-Minerva bridge is a translating host converting packets between the Minerva format and the MX format in both directions. Flexibility is provided for packet conversion in the bridge configuration programme. The bridge comprises of 2 network cards and a translating host (CCU). The MX Minerva bridge can be added to one mixed network using both Minerva and MX Nodes or it can be connected to span between two physically separated network rings, one with Minerva nodes and one with MX nodes.
Technical Specification
Size: Input voltage: Operating Temp: EMC/RFI: 320x440x120mm (17A/H) 320x440x215mm (38A/H) 120-250VAC - 50/60Hz 8 to +55C EN50130-4
Product Codes
557.202.120 557.202.121 MX-Minerva Bridge Kit (17AH) MX Minerva Bridge Kit (38AH)
Chapter 4 Page 6
Fire Catalogue
09/10
Chapter 5 - Detector Test Equipment Detector Test Equipment for Point Detector Testing/ Commissioning
The solo range of test equipment provides a range of easy to use products for commissioning and servicing all types of point detectors. Telescope Poles
Product Codes 517.001.230 SOLO100 Telescopic pole 1.26M to 4.5M long 517.001.226 SOLO101 Extension tube 1.13M long for use with Telescopic extension pole (517.001.230) 517.001.264 SOLO 610 Protective Carry/Storage Bag for Solo Detector Test Kit
SOLO704
Product Code 517.001.224 SOLO704 Adaptor tube B - Adapts SOLO100/101 pole sets for TYCO detector changers and testers
SOLO200
Product Code 517.001.240 SOLO200 Universal detector changer for use with various manufacturers detectors - not suitable for 600/800/900 series low profile detectors. Connects directly to the SOLO100/101 poles.
04/10
Fire Catalogue
Chapter 5 Page 1
517.001.262
517.001.256
516.800.917 800 RT DETECTOR CHANGER
Chapter 5 Page 2
Fire Catalogue
04/10
Product Codes
592.001.016 T210+ Test source for use with Solo 704 Adaptor Tube B (517.001.224) and Solo 100/101 Poles (517.001.230/226) T210+Adaptor required for the T210+ to be used with S200 and S200 Plus Flame Detectors T110 PP9 Battery and Charger Kit
592.001.014
592.001.010
04/10
Fire Catalogue
Chapter 5 Page 3
Chapter 5 Page 4
Fire Catalogue
04/10
Product Codes PS-1221 PS-1230 PS-1270 PS-1212 PS-12650 PS-12380 PS-6100 PS-12170 PS-12260 PS-1242 PS-12120
Voltage (V) 12 12 12 12 12 12 6 12 12 12 12
Ah at 20h rate 2.1 3.0 7.0 1.2 65.0 38.0 10.0 17.0 26.0 4.5 12.0
Length 178 134 151 97 348 197 151 181 166 90 151
Product Codes
PS-1221 PS-1230 PS-1270 PS-1212 PS-12650 PS-12380 PS-6100 PS-12170 PS-12260 PS-1242 PS-12120 12 Volt 2.1 Ampere hour rechargeable sealed lead acid battery 12 Volt 3.0 Ampere hour rechargeable sealed lead acid battery 12 Volt 7.0 Ampere hour rechargeable sealed lead acid battery 12 Volt 1.2 Ampere hour rechargeable sealed lead acid battery 12 Volt 65.0 Ampere hour rechargeable sealed lead acid battery 12 Volt 38.0 Ampere hour rechargeable sealed lead acid battery 6 Volt 10.0 Ampere hour rechargeable sealed lead acid battery 12 Volt 17.0 Ampere hour rechargeable sealed lead acid battery 12 Volt 26.0 Ampere hour rechargeable sealed lead acid battery 12 Volt 4.5 Ampere hour rechargeable sealed lead acid battery 12 Volt 12.0 Ampere hour rechargeable sealed lead acid battery
07/10
Fire Catalogue
Chapter 6 Page 1
Product Code
558.004.020 Minerva MXP24/50-U/TSP 5A Charger & Housing
Chapter 6 Page 2
Fire Catalogue
07/10
Features
Integral release button Attractive design Slimline ABS housed units Robust floor mounted unit
Door release magnet set, Wall Mount, Metal Housing, 24VDC Door release magnet set, Wall Mount, Metal Housing, 230VAC
Door release magnet set, Wall Mount, ABS Housing, 24VDC Door release magnet set, Wall Mount, ABS Housing, 230VAC
Floor mounting bracket for adapting wall mounted door magnets to floor mount
Technical Specifications 3-59-0404-S001 - 89 x 89 x 70mm, 0.5Kg, 180N Holding Force, 1.15W Coil @ 24VDC 3-59-0404-S002 - 89 x 89 x 70mm, 0.5Kg, 180N Holding Force, 1.15W Coil @ 230VAC 3-87-0351 - 95 x 87 x 46mm, 0.36Kg, 200N Holding Force, 1.15W Coil @ 24VDC 3-87-0352 - 95 x 87 x 46mm, 0.36Kg, 200N Holding Force, 1.15W Coil @ 230VAC 3-84-0301 - 110 x 96 x 96mm, 0.7Kg, 200N Holding Force, 45mA Coil @ 24VDC
07/10
Fire Catalogue
Chapter 6 Page 3
Product Codes 567.007.008 Alarm Relay 240Vac MK4 567.007.009 Alarm Relay 24Vdc MK4
Relays
Product Code 569.001.007 Cradle relay and retaining clip 2 C/O 26V nominal 700 ohm coil 5 amp (used with Relay 5000 and 5010). Product Code 609.001.015 Polarised & suppressed 24VDC double pole C/O relay with gold clad contacts, 2K ohm coil, 2 Amps @ 30VDC (PCB Mounted)
Chapter 6 Page 4
Fire Catalogue
07/10
Technical Specification
Construction Conductor: Bare copper, solid or stranded to BS 6360 Insulation: Special double layer insulation according to BS 7655, E15 Inner Covering: High temperature resistant glass fibre tape Screening: Al-Laminated tape with tinned copper drain wire, solid to BS 6360 Outer Sheath: Flame retardant polyolefin compound according to BS 7655, LTS3 Technical Properties Rated Voltage: 300/500V Test Voltage: 2000V, 50Hz core/core 2000V, 50Hz core/screen Operating Temp: -15oC to +90oC Core Colours: 2 cores + earth: red, black 4 cores + earth: red,yellow,blue,black Sheath Colour: Red or white General Properties Zero Halogen, no corrosive gases IEC 60754-2, BS 6425 part 1 Reduced fire propagation - IEC 603323, BS 4066 part 3 Minimum smoke emission - IEC 61034, BS 7622 Insulation integrity - IEC 60331 (FE180), BS 6387 (cat. CWZ) Approvals BASEC
No. of Cores x Cross Section (n x mm2) Copper Content (Kg/Km) 2 x 1.0 19 2 x 1.5 29 2 x 2.5 48 4 x 1.0 39 4 x 2.5 96
Product Codes
Product Codes 599.048.020 599.048.022 599.048.023 599.048.024 599.048.032 599.048.034 599.048.035 599.048.036 No. Cores 2 + earth 2 + earth 2 + earth 2 + earth 4 + earth 4 + earth 4 + earth 4 + earth DTWYLER Lifeline cable Core Size Colour 1 mm Red 1.5 mm Red 1.5 mm White 2.5 mm Red 1 mm Red 1.5 mm Red 1.5 mm White 2.5 mm Red Clips P34 R P34 R P34 W P37 R P37 R P40 R P40 W P43 R
Product Codes
DTWYLER Lifeline Fire Resistant P Clips & Glands Qty. per pack Reference Colour 50 P34 Red 50 P34 White 50 P37 Red 50 P40 Red 10 NG1 Red 10 NG1 White
Total Weight (Kg/Km) Outer Diameter (approx. mm) Calorific Potential (KWh/m) 75 7.4 0.16 97 8.2 0.18 141 9.6 0.24 114 8.6 0.23 223 11.3 0.37
07/10
Fire Catalogue
Chapter 6 Page 5
Chapter 6 Page 6
Fire Catalogue
07/10
Features
Laser Based Absolute Smoke Detection Very Early Warning of a Potential Fire Incident Wide Sensitivity Range (0.025%-20% obs/m) (0.008 - 6.4% obs/ft) Detection Capabilities for smaller critical areas up to 500m Dual Stage Dust Filtration Programmable Alarm Thresholds Reliable Air Flow Monitoring Easy User Interaction AutoLearn Smoke & Flow Pre-engineered Pipe Designs
Technical Specification
Supply Voltage: Current Consumption: Dimensions: Weight: IP Rating: Operating Temp: Sampled Air: Humidity: 18 to 30 Vdc 220mA quiescent 295 mA alarm 255H x 185W x 90Dmm 2 kg IP30 0C to + 40C 0C to + 40C 5% to 95% (non condensing)
Product Codes
516.018.020 516.018.022 516.018.023 VLF-250 Vesda Laserfocus (with English overlay) VIC-010 LaserFocus VesdaNetwork Card VLF-500 Vesda Laserfocus (with English overlay)
09/10
Fire Catalogue
Chapter 7 Page 1
Chapter 7 - VESDA
Features
Reduced size Absolute smoke detection Wide sensitivity range Single pipe inlet Simple display Referencing VESDAnet communication (VN) Dual stage dust filter Three alarm levels Configurable relays Air flow monitoring Optional remote display and relay capability Simple mounting design AutoLearnTM Marine Approved Version
Technical Specification
Supply Voltage: Current Consumption: Dimensions: Weight: Operating Temp: Sampled Air: 18 to 30Vdc 225mA quiescent, 245mA in alarm 225H x 225W x 85Dmm 1.9Kg -10C to+ 39C -20C to +60C
Product Codes
516.018.011 516.018.010 516.018.012 VLC-505-VN VESDA net Version (VN) VLC-500-RO Relays Only Version (RO) VLC800 MX Addressable Vesda Laser compact (Compatible with MX Consys versions 2.1 and above) VLC-500-RO Relays Only Version (RO) Marine VLC-500-VN Vesdanet Version (VN) Marine VRT-J00 Remote Display c/w 7 relays Marine
Chapter 7 Page 2
Fire Catalogue
09/10
Chapter 7 - VESDA
Features
Wide sensitivity range Laser-based light source 4 Configurable alarm levels Purpose built Aspirator 4 In-line Inlet pipes Flow sensor for each inlet pipe Wide range DC power Low-cost maintenance Dual stage filter Easy access to filter cartridge 7 Software configurable relays Recessed mounting Multiple exhausts
Technical Specification
Supply Voltage: Current Consumption: 18 to 30Vdc (No display or programmer) 240mA quiescent plus 50mA alarm (24Vdc at 3000 rpm) 225H x 350W x 125D mm 4.0Kg (including display and programmer modules) 0C to + 39C 0-95% RH, non condensing
Product Codes
516.018.001 516.018.002 516.018.013 VLP-012 LaserPLUS Detector, programmer and display VLP-002 LaserPLUS Detector and display VLP-400 LaserPLUS Detector with fire OK LED
09/10
Fire Catalogue
Chapter 7 Page 3
Chapter 7 - VESDA
Features
Individual pipe annunciation Adaptive scan threshold Wide sensitivity range (0.005 to 20% obs/m) Laser based light source Configurable alarm levels Purpose built Aspirator 4 In-Line inlet pipes Flow sensor for each pipe inlet Low-cost maintenance Dual stage filter Easy access to filter cartridge Recessed mounting
LaserPLUS Scanners
VESDA LaserPLUS is also available in a Scanner configuration, which allows the system to distinguish and identify the pipe carrying smoke, while sampling multiple sectors. VLS-214/314 FD7/FD12 Scanner
Product Codes 516.018.004 VLS-214 FD7 Scanner, programmer and display with 7 relays. 516.018.007 VLS-314 FD12 Scanner, programmer and display with 12 relays
The VESDA LaserPLUS will continue to sample from all sectors to monitor the fire growth and maintain full protection.
Technical Specification
Supply Voltage: Current consumption: Dimensions: Weight: Operating Temp: Humidity: Relay Outputs: 18 to 30Vdc (No display or programmer) 240mA quiescent plus 70mA alarm (24Vdc at 3000 rpm) 225H x 350W x 125D mm 4.0Kg including display and programmer modules 0C to + 39C 10-95% RH, non condensing 7 or 12
Product Codes
516.018.004 516.018.007 516.018.005 516.018.008 516.018.016 516.018.019 VLS-214 FD7 Scanner, programmer and display with 7 relays. VLS-314 FD12 Scanner, programmer and display with 12 relays VLS-204 FD7 Scanner and display with 7 relays. VLS-304 FD12 Scanner and display with 12 relays VLS-600 FD7 Scanner with Fire OK LED VLS-700 FD12 Scanner with Fire OK LED
Chapter 7 Page 4
Fire Catalogue
09/10
Chapter 7 - VESDA
Features
Four alarm levels (Alert/Action, Fire 1 & Fire 2) 20 segment vertical bar graph Alarm threshold indicators (Alert, Action & Fire 1) Audio and visual indication Alarm indicators Informative fault indicators Multi-mode numeric display(defaults to smoke obscuration) Acknowledged push-button presses Multiple language supported Addressable to any detector
VRT-300
Product Code 516.018.103 VRT-300 Remote VESDAnet socket
VRT-100
Product Code 516.018.101 VRT-100 Remote programmer
Technical Specification
Supply Voltage: Current Consumption: 18-30Vdc (when used in detector unit, Remote unit or 19 rack) 60mA quiescent plus 20mA alarm @24Vdc - (module only)/90mA quiescent plus 20mA alarm @24Vdc Dimensions: Operating Temp: Humidity: 150H x 140W x 90D mm 0C to +39C 10-95% RH, non condensing
09/10
Fire Catalogue
Chapter 7 Page 5
Chapter 7 - VESDA
LaserPLUS Standard 19 Inch Sub-Rack Remote Display Assemblies
The 19 sub-rack is available as a mounting option, with 4 mounting slots for display or programming modules. Technical Specification Dimensions: 128H x 482W x 120D mm Product Codes 516.018.201 VSR-2000 19 Sub-rack with 1 detector display and 3 blanks 516.018.203 VSR-2210 19 Sub-rack, 2 detector displays, programmer and 1 blank 516.018.204 VSR-2221 19 Sub-rack with 3 detector displays and programmer 516.018.206 VSR-2222 19 Sub-rack with 4 detector displays
LaserPLUS Spares
The following common VESDA LaserPLUS spares are kept in stock by Tyco Safety Products. Other spares can be supplied if required. Product Codes 516.018.501 VSP-002 Display (spare) 516.018.502 VSP-004 Scanner display (spare) 516.018.503 VSP-001 Programmer (spare) 516.018.505 VSP-019 Filter cover door (spare) 516.018.506 VSP-006 Spare detector chassis and manifold 516.018.508 VSP-008 Spare remote termination card 7 relays 516.018.509 VSP-009 Spare scanner chassis and manifold 516.018.514 VSP-014 Spare header termination card 7 relays 516.018.515 VSP-015 Spare aspirator fan 516.018.504 VSP-005 Filter cartridge (spare)
Chapter 7 Page 6
Fire Catalogue
09/10
Chapter 7 - VESDA
Features
Powerful fan Upto two x 100m pipe runs Pipes can be individually monitored for air flow with LED bar graph MX Loop and 24 VDC connections Fault monitored via the MX Loop IP65 enclosure Field serviceable air filters Uses standard 25mm Vesda pipe & fittings
Technical Specification
Supply Voltage Current Consumption Dimensions Weight Operating Temp Humidity Sampling Pipes 18 to 30Vdc 300mA 259w x 184h x 166d mm 2.77 Kg -10 to +55C (with detectors) 10 to 90% RH NonCondensing 25 mm dia, 100m per inlet
Product Codes
516.016.301 516.016.304 516.016.305 516.016.303 ICAM IAS800 Aspirated Smoke Dual Detector common fault monitor ICAM IAS801 Aspirated Smoke Single Detector common fault monitor ICAM IAS802 Aspirated Smoke Dual Detector dual fault monitor ICAM Course Filter (PK10)
09/10
Fire Catalogue
Chapter 7 Page 7
Features
Toughness and durability Chemical resistance Easy to joint Low Friction Wide temperature range Lightweight Red colour for easy identification
Socket 25mm
Straight socket for 25mm pipe. Order in multiples of 10. Product Code 516.018.902 Socket 25mm
Bend 25mm
90 degree Long Radius bend Order in multiples of 5 Product Code 516.018.904 Long Radius bend 90
Chapter 7 Page 8
Fire Catalogue
09/10
Chapter 7 - VESDA
Elbow 25mm
45 deg elbow Order in multiples of 5 Product Code 516.018.905 Elbow 25mm
Capillary Tube 10 mm
Capillary Tube 10 mm 10mm o/d x 30m length (tube colour - red) Product Code 516.018.915 Capillary Tube 10 mm
Pipe Cutters
Pipe Cutter Product Code 516.018.918 Pipe Cutter
Pipe Ties
Pipe Ties (Red) Order in multiples of 100. Product Code 516.018.920 Pipe Ties (Red)
09/10
Fire Catalogue
Chapter 7 Page 9
Chapter 7 - VESDA
Sampling Point Label (1 reel)
Sampling point label. Order in multiples of 100. Product Code 517.017.005 Sampling point label.
Pipework designs for Vesda Systems must be verified by the use of the Aspire pipework Design Software Tool. Available for download from the Xtralis Website at www.vision-fs.com.
Test Equipment
Wire Burn Test Box
Wire burn test box designed to heat up a measured length of special wire to produce smoke, used to test the transport time and performance of Vesda aspirating smoke detectors. Built in timer Insulated terminals Selectable input voltage Illuminated power on indicator Robust enclosure Supplied with UK power lead Technical Specification Input Voltage 110-120 or 220240VAC Output Voltage 6.3VAC @ 20A IP rating IP30 Timer 1 to 3 mins Dimensions 170w x 120d x 135h (mm) Weight 2.75Kg Product Code 516.018.921 Wire Burn Test Box
Chapter 7 Page 10
Fire Catalogue
09/10
Chapter 8 - Fire Phones & Disable Refuge Fire Phones & Disable Refuge
Features
Only three main functional building blocks simplify the system design Compliant with BS5839 Pt 9:2003 Compatible with enhanced fire rated cable System can control & monitor up to 265 lines Up to 8 master handsets per system Large clear display on master handsets Optional Lockable and Weatherproof Outstations Battery backup for continued operation in the event of a mains failure
03/10
Fire Catalogue
Chapter 8 Page 1
EMERCALL TYPE A
The EmerCall Type A outstation handsets as defined by BS5839 Pt 9 can be used as a fire telephone or disabled refuge call point. Intended for use by firemen or building marshals. BS5839 Pt 9:2003 compliant, compact design, high volume ringer, Status LED, 20mm cable glands, telecoil for hearing impaired users, magnetic push catch or locking door, fully monitored, flush or surface mount, stainless steel option. For outdoor applications an IP66 protected outstation is also available. Product Codes 2572003 EmerCall Type A Flush Outstation Handset with push door 2572004 EmerCall Type A Flush Outstation Handset with locking door 2572013 EmerCall Type A Flush Outstation Handset with push door - stainless steel 2572005 EmerCall Type A Surface Outstation Handset with locking door 2572006 EmerCall Type A Surface Outstation Handset with push door 2572010 EmerCall Type A Surface Outstation IP66 2572015 EmerCall Type A Surface Outstation IP66 - stainless steel
EMERCALL TYPE B
The EmerCall Type B hands free outstation as defined by BS5839 Pt 9 can be used in a disabled refuge call point. It can only be used as a fire telephone when it is impractical to use a Type A outstation. BS5839 Pt 9:2003 compliant, hands free operation, compact design, high volume ringer, flashing status LED, braille signage, duplex speech, 20mm cable glands, fully monitored, stainless steel option. Product Codes 2572009 EmerCall Type B Outstation 2572016 Flush Bezel for 2572009 - stainless steel
Chapter 8 Page 2
Fire Catalogue
03/10
03/10
Fire Catalogue
Chapter 8 Page 3
Chapter 8 Page 4
Fire Catalogue
03/10
There are also sensors for the detection of non-conductive fluids such as diesel/oil.
Features
Suitable for computer rooms Wide range of sensors Relay contacts to interface to BMS or fire alarmcontrollers
Technical Specification
Dimensions: 160H x 220W x 62D mm (Single Zone) 270H x 362W x 84D mm (Multi Zone) Single phase 240VAC, 25VA Max. Relay Contacts: Two sets of volt free change over contacts for alarm and one set for wiring fault or power loss. These may be used to link into Building Management Systems or for remote alarms and beacons up to 2A, 50Va.c./d.c.
Product Codes
508.200.004 508.200.005 508.200.006 1 Zone - water/flood control panel 2 Zone - water/flood control panel 4 Zone - water/flood control panel
Supply:
04/10
Fire Catalogue
Chapter 9 Page 1
Chapter 9 Page 2
Fire Catalogue
04/10
04/10
Fire Catalogue
Chapter 9 Page 3
Chapter 9 Page 4
Fire Catalogue
04/10
Introduction
Tyco Safety Products manufacturers and provides a wide range of equipment suitable for use in hazardous areas where normal equipment cannot be safely used. The range extends from IS detectors for use on conventional systems to flameproof and I.S. flame detectors for use in the most demanding of environments. A complete range of Barriers, Housings, Callpoints and Sounders are available to fully support the product range. Electrical equipment supplied for use in Hazardous Areas must comply with rigid requirements to ensure that its introduction into the area does not increase the existing risk. Thorn Security Limited have designed Intrinsically Safe (I.S.) systems and equipment for use in Hazardous Areas which can be connected to Fire Detection Systems installed in Safe Areas. There are two I.S. systems used by Thorn Security Limited. System 620 for use in conventional fire detection circuits and System 800 for use with MINERVA MX digital addressable circuits. The control equipment of the fire detection system must be connected either via a Shunt Diode Safety Barrier or by an Isolating Interface to System 620 and System 800. Two Sounder Systems (one earthed and one isolated) are available for use with System 620 and System 800. APPLICATION - GENERAL The System Designer must be familiar with BS EN 60079-14: 2003, EN 50, EN 50020 and ATEX certification and have successfully completed an appropriate recognised course in Intrinsic Safety. Design of the system requires that the designer has all the information concerning the installation correctly documented. The nature of the Hazard must be defined by the customer and a survey carried out to determine the proximity of the safe area to establish cable runs. The probability of a flammable mixture being present is defined by a Zone Number. Flammable gases are classified in Groups and their minimum spontaneous ignition temperature is categorised by Class. Thorn Security equipment marked EExe ia IIC T5 would be suitable for use in worst case conditions, e.g. Zone 0 (ia), Hydrogen (IIC), T5 (100 deg C). The Fire Alarm Equipment and Safety Barriers should be placed as near as possible to the containment wall of the Hazardous Area. This minimises the cable lengths between the barrier and the Hazardous Area and thus the capacity to store energy. In order that an Installation will comply with the ATEX certification designated for each system it is essential that the certified devices are connected with cables of the specified limits. These limits have been certified for specific classifications of hazard in order that energy storage is limited. Safety Barriers are incorporated into the circuit feeding the Hazardous Area to limit the voltage excursion and the current. The limit of voltage and current will prevent a fault within the I.S. circuit exceeding the ignition conditions. THE FITTING OF SAFETY BARRIERS, ISOLATING INTERFACES OR SOUNDER DRIVERS DOES NOT IN ITSELF MAKE A CIRCUIT TO WHICH THEY ARE CONNECTED INTRINSICALLY SAFE.
09/10
Fire Catalogue
Chapter 10 Page 1
Chapter 10 Page 2
Fire Catalogue
09/10
Markets:
The FlameVision FV300 detectors are intended for applications demanding a high level of protection and where a rapid response to fire is important. Typical applications are: Refineries Drilling and production plants Fuel loading facilities Compressor stations LNG/LPG processing & storage Gas turbines Chemical production Aircraft hangars Waste management/transfer Sports stadiums Tank farms Printing industry Warehousing Munitions storage
Range of Interfaces:
As standard the FV300 is supplied with the following interfaces: Fire and fault relays, programmable as normally open or normally closed 4 to 20mA analogue current output, proportional to the flame detection signal (sink or source) RS485 serial data port suitable for network connection using a MODBUS protocol. This can be used to communicate the positional co-ordinates of a flame within the field of view of the detector Video output compatible with twisted pair video cable
FV300 Flame Detector Model Nos. No camera PAL Format camera NSTC Format camera
09/10
Fire Catalogue
Chapter 10 Page 3
Product Codes
516.300.006 516.300.008 516.300.007 516.300.055 516.300.057 516.300.056 517.300.001 517.300.002 517.300.005 517.300.006 517.300.021 517.300.022 FV311S Flameproof Detector - cable gland entries - no camera FV311SC Flameproof Detector - cable gland entries - PAL camera FV311SC-N Flameproof Detector - cable gland entries - NTSC camera FV312S Flameproof Detector - sealed back box - no camera FV312SC Flameproof Detector - sealed back box - PAL camera FV312SC-N Flameproof Detector - sealed back box - NTSC camera MB300 Mounting Bracket WH300 Stainless Steel Weather Hood JB300 Exe Junction Box MK300 Field Spares Kit WT300 Walk-test Controller CTI300 Off-line Configuration Tool Kit
Electrical access FV311 Series detectors: Standard M20 gland holes (two) FV312 Series detectors: Multi twisted pair screened cable Environmental Temp. Humidity, Enclosure Protection and Pressure Operating temp. range without camera: Operating temp. range with camera: Maximum withstand temp: Storage temp. range: Relative humidity: Enclosure protection: Normal operating atmospheric press: Heat radiation from sun:
- 40C to + 80C - 10C to + 55C 120C (for 10minutes) - 40C to + 80C Up to 99% (non condensing) Tested to IP66 and IP67 910 mbar to 1055 mbar 0 to 1kWm2 typical
Chapter 10 Page 4
Fire Catalogue
09/10
Technical Specification
Detector Material: Dimensions: Weight: Gland Entry: Range: Operating Temp: Response Time: Sensitivity: Relative Humidity: Enclosure: Stainless Steel 316L/316 167H x 167W x 89D MM 4.5Kg 2 x 20mm 0.1m2 petrol at 50m 0.4m2 petrol at 60m -40 to +80C Field Selectable 3,6 and 12s 3 range settings 95% (100% intermittent) IP 66 and IP 67
Product Codes
517.001.266 517.001.263 517.001.184 S200+ Spares Kit & Sealant S200+ Weather Protection Assembly S200+ Detector Mounting Bracket
Approvals Various models are certified by a number of approval bodies including those listed below. ATEX Approved models have a suffix 1 as the third digit. FM Approved models have a suffix 2 as the third digit.
09/10
Fire Catalogue
Chapter 10 Page 5
Approvals Interface Conventional S231i+ S231f+ S232f+ S241i+ S241f+ S261f+ S271i+ S271f+ FV282F+ 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4-20mA MZX Addressable Relay 4 4 4 ATEX Ex ia Ex d FM Ex d 516.037.004 516.037.003 516.037.015 516.038.004 516.038.003 516.040.002 516.041.004 516.041.003 516.040.014 Product Codes
Chapter 10 Page 6
Fire Catalogue
09/10
Chapter 10 - Special Hazards System 800 Fire Detection for Hazardous Areas
Features
Addressable I.S. MX Technology Compatible with S271i+ flame detector Compatible I.S. callpoint. Atex certified intrinsically safe Ex II 1 GD System Suitable for use in Zone 0, 1, 2, 20, 21 & 22
09/10
Fire Catalogue
Chapter 10 Page 7
Technical Specification ATEX Code: Ex II 1GD/3G Cenelec Code: Ex ia IIC T5/Ex iaD 20 T100C/ EExnA II T4 Weight: 0.2Kg detector and base (approx) Operating Temp. Range: -25C to +70C
Chapter 10 Page 8
Fire Catalogue
09/10
IS Barrier Enclosure
The MTLDX Series enclosure equipment will house the EXI800 20mm pitch), Pepper+Fuchs KFDOCS-Ex1.54 Galvanic Isolator (20mm pitch) and MTL 5021 I.S. Sounder Driver 16.2mm pitch). The units are DIN rail mounted with 70mm of rail supplied with the DX070 and 170mm of rail with the DX170. Enclosures are usually selected on the number of units they will accommodate. The following table shows the capacity of each of the enclosure types. Product Codes 517.001.248 DX070 Enclosure 517.001.247 DX170 Enclosure
Enclosure
DX070 4(2*) 9(5*) DX170 10 (8*) 22(18*) * Use these figures when two IMB57 mounting brackets for tagging/earth rail accessories are included.
09/10
Fire Catalogue
Chapter 10 Page 9
BG MIM800 Callpoint EX II 2 GD
An Ex II 2 GD Dust Approved & Increased Safety (EExemd) Resettable Manual Alarm Call Point for use with the EExd Flameproof MIM800 input module in EExd housing on an Addressable Detection & Releasing System in gas and dust explosive risks. Please note that the above part is only compatible with Consys Version 17.0 and above when used with 577.800.067.
Technical Specification
Explosion Protected EExed(Increased Safety) Certification: ATEX approved Ex II 2 GD BAS02ATEX2105X EExemdIICT4 CENELEC EN50014 EN50019 EN50018 EN50028 Suitable for use in Zones 1 & 2 Voltage: Up to 250V Certified Temperature: -20oC to +50oC Ingress Protection: IP66 & 67 Terminals: 7 x 2.5mm Switch Ratings(1 x Changeover): DC 0-30V 5A (Resistive) or 3A (Inductive) DC 30-50V 1A Resistive or Inductive AC 0-254V 5A Resistive or Inductive Cable Entries: 1 x M20 Bottom Weight: 1.2Kg Material: Anti Static U.V. Resistant Glass Reinforced Polyester Finish: Red Epoxy Paint Resistors: Alarm: 100 Ohm EOL: 250 Ohm Labelling: Burning House Symbol Dimensions (W X H X D): 120mm x 126mm x 75mm Protection:
Product Code
514.001.107 EX II 2 GD Dust Approved & Increased Safety (EExemd) Resettable Manual Alarm Callpoint
Chapter 10 Page 10
Fire Catalogue
09/10
Technical Specification
Protection: Certification: Explosion Protected EExd (Flameproof) Ex II 2 GD LOM02ATEX2037 EExdIICT6 CENELEC EN50014 EN50018 EN50019 EN50281-1-1 EN60439-1 Suitable for use in Zones 1 and 2 to IEC 60079-10 Suitable for use in Zones 21 and 22 to EN50281-3 40Vdc -20oC to +55oC IP67 9 x 2.5mm 3 x M20 0.8 Kg Metal Alloy Aluminium - Copper Free 108mm x 98mm x 90mm
Product Code
577.800.067 MIM800 Input Module in EExd Housing
Voltage: Certified Temperature: Ingress Protection: Terminals: Cable Entries: Weight: Material: Dimensions (W X H X D):
09/10
Fire Catalogue
Chapter 10 Page 11
Technical Specification
Protection: Certification: Explosion Protected EExd (Flameproof) Ex II 2 GD LOM02ATEX2037 EExdIICT6 CENELEC EN50014 EN50018 EN50019 EN50281-1-1 EN60439-1 Suitable for use in Zones 1 and 2 to IEC 60079-10 Suitable for use in Zones 21 and 22 to EN50281-3 40Vdc -20oC to +55oC IP67 12 x 2.5mm 5 x M20 1.3 Kg Metal Alloy Aluminium - Copper Free 150mm x 150mm x 104mm
Product Code
577.800.066 DDM800 Fire & Gas Detector Module in EExd Housing
Voltage: Certified Temperature: Ingress Protection: Terminals: Cable Entries: Weight: Material: Dimensions (W X H X D):
Chapter 10 Page 12
Fire Catalogue
09/10
Chapter 10 - Special Hazards System 620 Fire Detection for Hazardous Areas
Features
Conventional I.S. system Suitable for worst case (EEx ia IIC T5) High Performance Optical (HPO) smoke detector Compatible with S231i+ flame detector Compatible I.S. callpoint Suitable for use in Zone 0,1,2,20,21& 22
09/10
Fire Catalogue
Chapter 10 Page 13
Heat Detectors
If environmental conditions rule out the use of smoke detectors, then a heat detector of the type MD601Ex/MD611Ex may provide an acceptable, though less sensitive, alternative. For general use, and particularly where the ambient temperature may be low, a 'Rate-ofRise' heat sensor is to be preferred. This type of sensor reacts to abnormally high rates of change of temperature and provides the fastest response over a wide range of ambient temperatures. A fixed temperature limit is also incorporated in these detectors. In many environments, e.g. kitchens and boiler rooms, sudden, large changes in temperature are considered 'normal'. Rate-of-rise detectors are generally not suitable in these cases and fixed temperature [static] types should be used. ATEX Code : Cenelec Code: Ex iaD 20 T100C Ex II 1GD Ex ia IIC T5/ Operating Temp Range: -10C to +55C Storage Temp: -20C to +55C Relative Humidity: 90% noncondensing Product Codes 516.052.051.Y (Vol 01B-04-D11) MD601EX Conventional Rate of Rise Heat Detector 516.052.041.Y (Vol 01B-04-D11) MD611EX Conventional Fixed Temperature Heat Detector
Flame Detectors
Flame detectors, unlike smoke and heat detectors, do not rely on convection to transport the fire products to the detector nor do they rely on a ceiling to trap the products. They can therefore be used to protect large open areas without sacrificing speed of response to flaming fires. In order to ensure full coverage however, flame detectors do require direct line of sight to all parts of the protected area. Infra-red flame detectors such as the 601FEx are designed to respond rapidly to fires which involve clean-burning fuels such as alcohol or methane, i.e. fires which would not be detected by smoke detectors. The 601FEx Flame Sensor, by virtue of its operating wavelength and flicker discrimination is insensitive to normal environmental influences. For outdoor use a solar-blind detector [e.g. the S200 Plus] should be used. The 601FEx Flame detector should, normally, only be used inside buildings to supplement heat and smoke detectors. ATEX Code: Ex II 1GD Cenelec Code: Ex ia IIC T4/ Ex iaD 20 T135C Operating Temp Range: -10C to +55C Storage Temp: -20C to +55C Relative Humidity: 90% noncondensing Product Codes 516.600.066 (Vol 01C-02-D10) 601FEx Infra-Red Flame Detector 516.600.067 (Vol 01C-02-D10) 601FEx-M Infra-Red Flame Detector (Marine)
Chapter 10 Page 14
Fire Catalogue
09/10
Cenelec Code: Ex ia IIC T5/ Ex iaD 20 T100C Operating Temp Range: -10C to +55C Storage Temp: -20C to +55C Relative Humidity: 90% non-condensing
09/10
Fire Catalogue
Chapter 10 Page 15
Technical Specification
Dimensions: Weight: Material: Conventional: Colour: ATEX Code: CENELEC: ATEX Cert: IP Rating: 93H x 98W x 66Dmm 270g PC/ABS Yes Red Ex II 1GD EX ia IIC T4 Ga /EX iaD T135c Da SIRA 06ATEX2131X IP67
Product Code
514.001.109 MCP220Ex Red Callpoint intrinsically safe for use with ATEX certified conventional system 620.
Chapter 10 Page 16
Fire Catalogue
09/10
Technical Specification
Model: Protection: BG3I Explosion Protected EExia (Intrinsically Safe) Certification: CENELEC EN50014, 020 BASEEFA EExia IIC T4 Cert No. BAS00ATEX1067X Suitable for use in Zones 0,1 & 2 Voltage: Up to 28V (IS) Certified Temp: -55C to +55C Ingress Protection: IP66 & IP67 European Standard for Callpoints: EN54-11 Terminals: 6 X 4.0mm2 Cable Entries: 2 X M20 Bottom Weight: 0.5Kg Material: UV resistant glass reinforced polyester Finish: Natural Red GRP
Product Code
514.001.059 Intrinsically Safe Callpoint (BG3I4NBN)
09/10
Fire Catalogue
Chapter 10 Page 17
BG Conventional Callpoint EX II 2 GD
This EX II 2 GD Dust Approved & Increased Safety (EExemd) Conventional Break Glass Manual Alarm Call Point is fitted with a 470 ohm Alarm Level Resistor and a 4K7 ohm EOL Resistor for use with Tyco Conventional Detection Circuits including the DIM800 and DDM800 MX Modules. It is also fitted with a removable link which allows it to be connected on its own or with other Conventional Devices to a Tyco Conventional Detection Circuit.
Technical Specification
Explosion Protected EExed (Increased Safety) Certification: ATEX approved Ex II 2 GD BAS02ATEX2105X EExedmIICT4 CENELEC EN50014 EN50019 EN50018 EN50028 Suitable for use in Zones 1 & 2 Voltage: Up to 250V Certified Temperature: -20oC to +50oC Ingress Protection: IP66 & 67 Terminals: 9 x 2.5mm up to 60V Switch Ratings(1 x Changeover): DC 0-30V 5A (Resistive) or 3A (Inductive) 30-50 1A Resistive or Inductive AC 0-254V 5A Resistive or Inductive Cable Entries: 2 x M20 Bottom Weight: 1.2Kg Material: Anti Static U.V. Resistant Glass Reinforced Polyester Finish: Red Epoxy Paint Resistors: Alarm: 470 Ohm EOL: 4K7 Ohm Labelling: Burning House Symbol Protection:
Product Code
514.001.108 EX II 2 GD Dust Approved & Increased Safety (EExemd) Conventional Break Glass Manual Alarm Callpoint
Chapter 10 Page 18
Fire Catalogue
09/10
Banshee IS28
IS28VCL MK4 Banshee BS5839 Low Frequency ATEX and ICEX certified intrinsically safe grey sounder - 94dBA, 10mA. Certificate Number : ITS03ATEX21311x EXII 1GD EExia IIC T5.
Product Code
576.501.013 IS28VCL MK4 Banshee
Features
Robust GRP Body Suitable for offshore and petrochem Certificated Intrinsically Safe
Technical Specification
Certification: CENELEC EN50014, 20 & 39 BAS02ATEX1258X EExia IIB T4 Zones 0,1 & 2 Material: UV stable glass reinforced polyester body. Clear polycarbonate cover/lens. Retained stainless steel cover screws. Finish: Painted Red Tube Type: Xenon discharge Lens Colour: Clear Terminals: 8 x 2.5mm2 Flash Rate: 1 flash per second Cable Entries: Up to 3 x M20 via knockouts Tube Energy: 0.5 Joules Weight: 1.4kg Certified Temperature: -55C to + 60C Ingress Protection: IP66 & IP67 Tube Life: >1 x 106 Flashes Voltage: 24V via suitable barrier Current Consumption: 71mA max nominal
Product Code
540.001.038 Intrinsically Safe Xenon Beacon (XB8BB024CNR)
09/10
Fire Catalogue
Chapter 10 Page 19
Technical Specification
Terminals: Mounting: Cable Entries: Tone Selection: Certification: 6 x 2.5mm2 Stainless steel bracket with ratchet facility 2 x 20mm EExd. 27 user selectable tones. CENELEC EN50014,18,19 BASEEFA Cert. No. BAS00ATEX2097X, EExd IIC 100C (-55 t. amb + 55C)T5. Zones 1 and 2. Class I Div 2, Groups A-D Class II Div 2, Groups F & G Class I Zones 1 & 2, AExd IIC T4. Listing No. E203310. 1Exd IIC T4 & 1Exde IIC T4 Cert. No. A-0759 Russian Fire Alarm Approved (VNIIP0) GOST K Certification Exd IIC T4 Chinese (C&ST) Certification Exd IICT4 Body & horn in anti-static, UV stable, glass reinforced polyester. Swivel bracket & captive cover screws in stainless steel. 115dB(A) +/- 3dB(A)(tone dependent). Input Current (mA)* 50 100 150 200 250 300 350 *Output measured with 24V input voltage. Tone set to 970Hz continuous. Weight: Ingress Protection: Voltage: Current Consumption: 6.0kg approx IP66 & IP67 Up to 48Vdc 380mA at 24Vdc
UL Listed:
GOST Certification:
Certified Temperature: EExd UL GOST Exd DB3 -20C -55C -20C to +70C to +70C to +50C
Product Code
576.501.043 Flameproof Horn Sounder (DB3D048N2BNR)
Material:
Sound Output:
Chapter 10 Page 20
Fire Catalogue
09/10
Technical Specification
Voltage: Tube Energy: Peak Current Consumption (mA): Effective Intensity (Cd): Peak Intensity (Cd): Power Consumption (Watts): Note: Weight: Certified Temperature: Ingress Protection: Terminals: Entries: Certification: 24Vdc 5 Joules 320 29 22213 8 The Cd figures are for a clear lens @ 1Hz flash rate. For red lens multiple by 0.15 2.5Kg EExd -55C to + 70C (T4) -55C to + 55C (T5) -55C to + 40C (T6) IP66 & IP67 6 x 2.5mm2 2 x 20mm ISO EExd. BASEEFA EExd IIB 135C (-55 to AMB +70C)T4 100C (-55 to AMB + 55C)T5 85C (-55 to AMB + 40C)T6 Cert. No. 99 ATEX 2195X. CENELEC EN50014 and EN50018 Body: Glass reinforced polyester Lens: Glass Cover Screws + Backstrap: Stainless steel 316 Finish: Red
Product Code
540.001.039 Flameproof Xenon Beacon (XB11B02406RNBNNNR)
Material
09/10
Fire Catalogue
Chapter 10 Page 21
Product Code 517.001.301 MTL 7728 + Zener Safety Barrier for conventional detection circuits designed in accordance with System 601
Chapter 10 Page 22
Fire Catalogue
09/10
MT Series Enclosures
The MT series of enclosures provides a simple, effective means of mounting and protecting MTL700 Series barriers in safe areas or low-risk hazardous areas. Three lightweight polycarbonate enclosures with see through lids accommodate up to 2, 5 and 12 barriers in the safe area. All the enclosures are supplied ready fitted with a nickel plated brass busbar mount, so barriers can be installed and wired up immediately without special tools. Product Codes 517.001.198 MT2 2 Way Zener Barrier Housing. 517.001.199 MT5 5 Way Zener Barrier Housing. 517.001.200 MT12 12 Way Zener Barrier Housing
Ancillaries
The ERL7 earth rail is a nickel plated 3 x 10mm rail (1 metre long), suitable for a do-it-your self mounting arrangement. It will accommodate up to 2.5 ETM7 earth terminals per barrier location for terminating earth returns and cable screens from the hazardous area. The IMB7 mounts on a flat surface or top hat rail (35mm) or G-profile rail and acts as a convenient method for mounting the earth busbar. Product Codes 517.001.205 ERL7 Earth rail for I.S. systems 517.001.206 ETM7 Earth termination connection system 517.001.207 IMB7 Insulating mounting block 517.001.120 System 601 EOL Unit (PK10)
09/10
Fire Catalogue
Chapter 10 Page 23
Chapter 10 Page 24
Fire Catalogue
09/10
By means of the Relay Controller Set and the Relay Extension Set an additional 256 relays per sensor cable can be connected. 09/10 Fire Catalogue Chapter 10 Page 25
Product Codes
516.016.310 516.016.311 516.016.312 516.016.313 516.016.333 516.016.334 516.016.314 516.016.315 516.016.316 516.016.317 516.016.318 516.016.319 516.016.320 516.016.321 516.016.322 516.016.322.C 516.016.323 516.016.323.C 516.016.324 516.016.325 516.016.326 516.016.327 516.016.328 516.016.329 516.016.330 516.016.331 516.016.332 MZX SensorLaser Plus 1/1 1 km range, 1 sensor cable. MZX SensorLaser Plus 1/2 1 km range, 2 sensor cables. MZX SensorLaser Plus 2/1 2 km range, 1 sensor cable. MZX SensorLaser Plus 2/2 2 km range, 2 sensor cables. MZX SensorLaser Plus 3/1 3 km range, 1 sensor cable. MZX SensorLaser Plus 3/2 3 km range, 2 sensor cables. MZX SensorLaser Plus 4/1 4 km range, 1 sensor cable. MZX SensorLaser Plus 4/2 4 km range, 2 sensor cables. MZX SensorLaser Plus 8/1 8 km range, 1 sensor cable. MZX SensorLaser Plus 8/2 8 km range, 2 sensor cables. MZX SensorLaser Plus Connection Set. MZX SensorLaser Plus iBox MZX SensorLaser Plus Relay Controller Set. MZX SensorLaser Plus Power Supply. MZX SensorLaser Plus Safety Cable (per metre). MZX SensorLaser Plus Safety Connector. MZX Steel Wire Armoured SensorLaser Plus Cable (per metre). MZX SensorLaser Plus Steel Connector. MZX SensorLaser Plus Setting Tool. MZX SensorLaser Plus Relay Extension Set. MZX SensorLaser Plus Zinc Plastic Clamp Set. MZX SensorLaser Plus Steel Plastic Clamp Set. MZX SensorLaser Plus Steel Zinc Clamp Set. MZX SensorLaser Plus Stainless Steel Clamp Set. MZX SensorLaser Plus Spare Unit. MZX SensorLaser Plus Demo Unit. MZX SensorLaser Plus Demo Box. 09/10
Technical Specification
Operating temperature range: -10C to +60C (2 channel options: from -5C) Storage temperature range: -40C to +80C Operating humidity range: 0% to 95% RH (2 channel options: 15% to 85% RH) non condensing Dimensions (H x W x D): 88 x 448 x 364 mm (19 rack) Weight: 9 kg Fibre types: MM 50/125 m graded index MM 62.5/125 m graded index Dynamic range: 30 dB (2-way loss) Sensing temperature range: -273C to +700C depending on sensor coating Optical connector: E2000; 8 angled Number of channels: 1, 2 depending on channel option Computer interface: USB, LAN Relay board: 4 inputs / 20 outputs Power supply: 10 V to 30 Vdc Power consumption: 15 W typically, at 20C ambient temperature < 40 W (entire operating conditions) Measurement times: from 10s to 30s Available spatial resolution settings: 1 m; 1.5 m; 3 m; 5 m; 8 m Available measurement modes: Single ended/Dual ended; including fibre break recovery Internal data storage capability: 150 traces total Power Supply (option) operating conditions: 0C to +50C; non condensing; indoor use only Laser class (IEC 60825-1: 2001):1M
Chapter 10 Page 26
Fire Catalogue
Chapter 11 - Useful Information MX Addressable Detector , Mode Selection & Design Charts
These charts are designed to assist with the selection of the best detector for the risk. 1. First select the environment 2. Then select the fire loading or risk being protected
07/10
Fire Catalogue
Chapter 11 Page 1
Chapter 11 Page 2
Fire Catalogue
07/10
07/10
Fire Catalogue
Chapter 11 Page 3
POWERED FROM
577.001.035
577.001.037
516.800.911
516.800.912
577.001.036
577.001.038
516.800.910
516.800.913
577.001.035
577.001.037
516.800.911
516.800.912
577.001.036
577.001.038
516.800.910
Fire Catalogue
YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES , YES YES YES
516.800.913
DUTCH SLOW TEMPORAL 4 SLOW SWEEP (3) MARCH TIME BEEP(25) SWEEP (7)
577.001.035
577.001.037
516.800.911
516.800.912
YES
577.001.036
577.001.038
516.800.910
516.800.913
YES
07/10
CONTINUOUS
577.001.035
577.001.037
516.800.911
516.800.912
577.001.036
577.001.038
516.800.910
516.800.913
(2) (3) (7) (9) (11) (14) (25) (26) = ROSHNI TONE NUMBER
Fire Catalogue
Chapter 11 Page 5
Banshee 12V
dBa (Typ) 94 94 94 95 95 95 97 97 94 95 96 102 103 103 105 103 105 104 96 93 90 88 96 96 105 81 84 96 106 93 95 96 mA(Typ) 6 6 6 6 6 6 6 4 8 5 6 12 12 12 12 12 7 12 6 6 5 3 6 3 6 4 5 4 8 8 8 8
Banshee 24V
dBA(Typ) mA(Typ) 100 100 100 101 101 102 103 103 101 101 103 110 110 110 112 110 112 110 101 101 96 94 103 103 112 87 89 103 112 101 102 101 12 12 12 12 12 12 12 7 14 12 14 25 25 25 30 25 15 25 12 14 10 6 12 6 12 7 14 7 15 14 17 17 12345 00000 10000 01000 11000 00100 10100 01100 11100 00010 10010 01010 11010 00110 10110 01110 11110 00001 10001 01001 11001 00101 10101 01101 11101 00011 10011 01011 11011 00111 10111 01111 11111
16 Banshee/Bedlam HF Fast Sweep (New) 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Back up Alarm LF Alternate LF Slow Whoop Din Tone (DK) French Fire Sound Australian Alert SIgnal Australian Evacuation Signal US Temporal Tone LF US Temporal Tone HF Swedish Tone (Fire) Swedish Tone (all Clear) ISO8201LF ISO8201HF BT Banshee (FP1063.1) BT Banshee (FP1063.1) Bell Tone
Chapter 11 Page 6
Fire Catalogue
07/10
SWITCH 1 2 3 4 5 10010
07/10
Fire Catalogue
Chapter 11 Page 7
Consultants Guide
A Fire Detection System Consultants Guide for consultants designing systems to BS5839-1:2002.
Product Code
CGUK-01 Consultants Guide
Chapter 11 Page 8
Fire Catalogue
07/10
Notes
07/10
Fire Catalogue
Chapter 11 Page 9
European Distribution Centre - Echt, Holland (Warehousing / Distribution / Purchasing / Customer Service / Call Centre Helpdesk) Voltaweg 20 6101 XK Echt Holland Tel: +31 475 371 666 Fax: +31 475 371 660 E-mail: tfseu.service@tycoint.com
European TSP Technical Support Call Centre Toll Free: 0800 CALL TYCO or (0800 22 55 89 26) 9:00 AM to 5:00 PM EET, CET & GMT UK Only: 08701 238 787
UK Distribution Centre (Warehousing / Distribution / Purchasing) Dunhams Lane Letchworth Hertfordshire SG6 1BE United Kingdom Tel: +44 (0) 1462 667 700 Fax: +44 (0) 1462 667 777 E-mail: tfsuk.service@tycoint.com
www.tycoemea.com 2010 Tyco International PMC001 Issue 7.7 / 09.10 The right is reserved to modify or withdraw any product or service without notice