Nothing Special   »   [go: up one dir, main page]

Presentation ESP Grounding

Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

Stopping Oilfield Lightning Damage

You can not stop lightning!

True. But you can stop the damage it does! An Engineering Approach

Oil Production Priorities


Tank Batteries, does NFPA 780 really apply? Disposal pump motors and controls Electric Submersible Pumps, ESP, does API RP11S really apply? ESP Variable Frequency Drives Pumping unit motors and controls

Tank Battery Protection


Strike Collection with Franklin rods (Also called lightning rods, air terminals, etc.), catenary wires, early streamer emitters National Fire Protection Association (NFPA) and Lightning Protection Institute Strike Avoidance Charge Transfer Systems

Electrical Equipment Protection


4-wire Transient Voltage Surge Suppressors (TVSS) Wellhead Grounding Junction box TVSS mounting Ungrounded transformer windings Separate Ground Wires Power distribution with an overhead neutral, OHN, or shield wire

Tank Battery Protection

E 1000 Barrels ach, 15'-5" dia, 30' high Fiber glass, gun barrel, w sep. ater

CLVSD 125 H SWD P M otor

500 H SWD P M otor catw alk Disposal Well 150' E ast

Rolling Sphere Calculation


74 foot diameter

K nockouts, steel 10' dia x 20' long & 10' dia x 15' long

Vertical G Separator as 3' dia x 12' high

Oil Storage 300 Barrel 12' dia, 15'-5" high Steel E ach

catwalk

Scale 1" = 20'

North

Problems
Presence of explosive gases Fluids that develop an electrical charge Attracting lightning and getting it safely into the ground without igniting gases Does NFPA 780 really apply?

Solution
Prevent lightning from striking tank batteries Charge Transfer Systems - Explanation Demonstration Details !! The devil is in the.. MIL TFP 41

Leader Delayed by _ Space Charge _

_ _ ___ _ _ _ _ _
Competing Leaders Continue toward Earth

++ + + + + + + + + + + + ++ + + + + ++ + + + +

+ + +

+ +

_ _ _ _ ___ _ _ _ _ _
Winning the Competition

+ + + + + + + + + ++ ++ + + ++ +

++

Grounding Making Contact with Charge beneath the tanks and in the tanks
Ground rods, loops, grids Chemical grounds Thief hatch ground rods Carbon C Veil Bonding

Electrical Equipment Protection

Metal Oxide Varistors (MOV) TVSS (SPD) Basic Element


Varistor = variable resistor Resistance changes with voltage Convert lightning energy into heat, if properly installed Analogous to Back Pressure Relief Valve

+ Volts Current or Flow

Current

M OV Pressure or Volts X
Pressure or Voltage Limit Maximum Allowable Working Pressure or Insulation Puncture Voltage

TVSS Modes and Wires


A B A G B

delta
Three Mode
C A B

A G

Four Mode

Six Mode

3-wire SPD (TVSS), No Ground

Effect of Long Ground Wire


V oltage Im pulse P ressure Im pulse P ressure R elief V alve MV O

Large voltage drop along ground w ire inductance

Large pressure drop in long, sm diam all eter discharge pipe.

Valve bypass into a small diameter discharge tube equivalent to a TVSS with long ground wire and high ground resistance.

Wellhead Grounding
Getting to Infinite Ground water table? A ground rod thousands of feet long Ground resistance less than ONE ohm Can the wellhead be damage by lightning? National Electric Code (NEC) requirement Opus 250, No. .-112M Corrosion? AC No, Cathodic protection evaluation CPET. Coexistence Surge and Cathodic protection

Wellhead Electrical Connection


Ground Clamps loose, loose wire, paint and corrosion, few contact points, shock, workover crew removal and replacement? Cad Weld Great connection, RR signal lights & substation ground grids, can not be removed to check wires, welding around natural gas? Service Post Grounding

Service Post Wellhead Grounding

Welded Bolt and Ground Lug

Lightning Arresters
H1 H2 H1 H2 H1 H2

X1

X2

X1

X2

X1

X2

Transformers Power System Ground Switchboard W ellhead

Junction or Vent Box

G roundw ire E surface line arth E Cable SP arm groundw or ire

Pole Butt Plate or W rap Additional ground rods as needed Ground connection point

10,000 V

Inductance of pole ground wire

Inductance of pole to wellhead ground wire

0V

Voltage at switchboard Butt wrap ground resistance

Voltage at wellhead W ellhead ground resistance

Lightning at arrester common

Infinite Ground

Ground Wire and Wellhead Voltages


9000

8000

7000

g
6000

a b c
5000
Volts

Switchboard Mounted TVSS

4000

3000
.5 Ohm 5 Ohm 10 Ohm 20 Ohm

2000

1000

Vent Box a b c Mounted TVSS g


3.E-06 Time 4.E-06 5.E-06 6.E-06 7.E-06

0 0.E+00

1.E-06

2.E-06

MOV Volt Amp Characteristics


Current

-MOV volts +MOV volts

Volts

Backwards

Lightning voltage onbutt w rap

G M OV volts

C + M OV volts _

Separate Bonded Ground Wires


An Improperly Installed TVSS Can Cause ESP Damage
Indian Basin and Tatum, NM

ShieldWire (OverheadNeutral, OH N)

Backward Through:

Lightning Arresters
H 1 H 2 H 1 H 2 H 1 H 2

Lightning Arresters TVSS or Secondary Lightning Arresters Switchboard Mounted TVSS

X1 X2

X1 X2

X1 X2

Transform ers

Reda Cable

TVSS

Preferred Submersible Pump Grounding for Lightning Protection


1. Ground wires should be green THHN insulated, #2AW stranded copper to minimize G breakage and corrosion. 2. For safety ESP cable armor must be connected to the ESP System Ground with #8 AW solid copper wire as shown. Between the switchboard and poles it should be G isolated from the Power System Ground. 3. Power System and ESP System ground wires should be run no closer than 6" apart to avoid sideflash. Pole ground wire and wellhead are the only permissible connections on the Power System ground wire. 4. ESP System Ground wires should connect to the ground lug on the TVSS at the junction box. The small green TVSS wire should ground the junction box internally. 5. At the junction box armors should not come in contact with each other or the metal box to minimize ground loop interference. Switchboard W ellhead ESP System Ground, Blue Tape Junction or Vent Box
E surface line arth E Cable SP Lightning Arresters
H1 H2 H1 H2 H1 H2

X1

X2

X1 X2

X1

X2

Transformers

a b c g

Pro-M oDr TVSS

Power System Ground, W hite Tape

6. A service post (Burndy K2C23B1 or Penn-Union SCS-4A1) screwed into a tapped hole between bolts in the lower flange is the recommended wellhead grounding method. A "hot work" permit will be required if natural gas is present. Connection at the lower flange should eliminate the need for ground wire removal during a workover.

Pole Butt Plate or W rap Additional ground rods as needed Ground connection point

Simplified Submersible Pump Grounding for Lightning Protection


1. Transformer windings to the ESP must be ungrounded. 2. Power System Ground connects to the switchboard and cable armors as shown. 3. Power System Ground goes directly to the wellhead without contacting the junction box. 4. TVSS and Power System ground wires should be green THHN insulated, #2 AW stranded G copper to minimize breakage and corrosion and isolated from each other to avoid sideflash. 5. At the junction box armors should not come in contact with each other or the metal box. 6. TVSS Ground wire should connect to the ground lug on the TVSS at the junction box. The small green TVSS wire grounds the junction box internally. 7. A service post (Burndy K2C23B1 or Penn-Union SCS-4A1) screwed into a tapped hole between bolts in the lower flange is the recommended wellhead grounding method. A "hot work" permit will be required if natural gas is present. Connection at the lower flange eliminates the need for ground wire removal during a workover. Switchboard W ellhead TVSS Ground Blue Tape
a b c

Lightning Arresters
H1 H2 H1 H2 H1 H2

X1

X2

X1 X2

X1

X2

Transformers (secondary windings ungrounded)

Arm or ground

Junction or Vent Box


E surface line arth

Pro-M oDr TVSS Cable arm or grounds E Cable SP

Power System Ground - W hite & Red Tape

Pole Butt Plate or W rap Additional ground rods as needed Ground connection point

Preferred Submersible Pump Lightning Protection Grounding for Variable Speed Drives

Lightning Arresters
H1 H2 H1 H2
X1 X2 X1 X2

H1

H2

X1

X2

T ransformers Power System Ground

Disconnect

TVSS1

1. Ground wires should be green THHN insulated, #2AW stranded copper to minimize G breakage and corrosion. 2. Power system ground wire should not connect directly to the drive through conduit or the disconnect. It should go directly to the wellhead. This is critical to preventing TVSS1 from damaging the VSD and ESP when lightning strikes. Disconnect, VSD and step-up transformers are still bonded via the ESP system ground wire. 3. 480V power into VSD should be ungrounded. 4. For safety ESP cable armor must be connected to the ESP System Ground or TVSS Ground with #8 AW solid copper wire as shown. Between the switchboard and G poles it should be isolated from the Power System Ground. 5. Power System, ESP System and TVSS ground wires should be isolated from each other to avoid sideflash 6. TVSS Ground wire should connect to the ground lug on the side of TVSS2 at the junction box. The small green TVSS wire should ground the junction box internally. 7. At the junction box armors should not come in contact with each other or the metal box to minimize ground loop interference. 8. A service post (Burndy K2C23B1 or Penn-Union SCS-4A1) screwed into a tapped hole between bolts in the lower flange is the recommended wellhead grounding method. A "hot work" permit will be required if natural gas is present. Connection at the lower flange should eliminate the need for ground wire removal during a workover. 9. If drive is trailer mounted junction box should W ellhead be fiber glass for electrical isolation
arm ground or w ire Step-U Transform p er

Variable Speed Drive

Junction or Vent Box


E Cable SP TVSS groundblue tape

TVSS2

or
Earthsurface line

Pole Butt Plate or Wrap Additional ground rods as needed

arm groundw or ire Pow systemground er w tape hite E systemground SP redtape

Ground connection point

Ungrounded Transformer Windings


The preferred way for 80 years Continuous oil production through first insulation fault Grounding will damage cable or motor on first fault so that ESP must be pulled Improved lightning protection Grounding is to LA common Perfectly Safe

Junction Box Mounting


Shortest ground wire to the wellhead On load side of switchboard contactor so overload protection will be activated if TVSS fails Wellhead connects directly to the housing of the downhole ESP motor

Priority 2 Protection of Disposal Pump Motor and Control


A Wellhead ground is normally not available Connect to ground loop around tank battery If possible separate lightning arrester ground wire from motor and control ground wire

480V, 3 phase

Power System Ground and Lightning Arrester Common

Control box

TVSS Motor

Wellhead
Y X

Earth surface Z

Ground wires Ground rod (Optional)

Summary
Charge Transfer Systems can provide improved tank battery protection. Reliability has been over 99% for 40,00 service years Properly designed and installed TVSS can prevent almost all equipment damage if: 4-wire TVSS are used grounded to wellhead junction box mounting ungrounded transformer windings separate ground wires

Lightning Damage can be Stopped!


Science and Engineering will Ultimately Prevail
Equipment Repair and Replacement can be Reduced

Lost Production can be Minimized

A Bad Day in the Neighborhood

You might also like