Presentation ESP Grounding
Presentation ESP Grounding
Presentation ESP Grounding
True. But you can stop the damage it does! An Engineering Approach
E 1000 Barrels ach, 15'-5" dia, 30' high Fiber glass, gun barrel, w sep. ater
K nockouts, steel 10' dia x 20' long & 10' dia x 15' long
Oil Storage 300 Barrel 12' dia, 15'-5" high Steel E ach
catwalk
North
Problems
Presence of explosive gases Fluids that develop an electrical charge Attracting lightning and getting it safely into the ground without igniting gases Does NFPA 780 really apply?
Solution
Prevent lightning from striking tank batteries Charge Transfer Systems - Explanation Demonstration Details !! The devil is in the.. MIL TFP 41
_ _ ___ _ _ _ _ _
Competing Leaders Continue toward Earth
++ + + + + + + + + + + + ++ + + + + ++ + + + +
+ + +
+ +
_ _ _ _ ___ _ _ _ _ _
Winning the Competition
+ + + + + + + + + ++ ++ + + ++ +
++
Grounding Making Contact with Charge beneath the tanks and in the tanks
Ground rods, loops, grids Chemical grounds Thief hatch ground rods Carbon C Veil Bonding
Current
M OV Pressure or Volts X
Pressure or Voltage Limit Maximum Allowable Working Pressure or Insulation Puncture Voltage
delta
Three Mode
C A B
A G
Four Mode
Six Mode
Valve bypass into a small diameter discharge tube equivalent to a TVSS with long ground wire and high ground resistance.
Wellhead Grounding
Getting to Infinite Ground water table? A ground rod thousands of feet long Ground resistance less than ONE ohm Can the wellhead be damage by lightning? National Electric Code (NEC) requirement Opus 250, No. .-112M Corrosion? AC No, Cathodic protection evaluation CPET. Coexistence Surge and Cathodic protection
Lightning Arresters
H1 H2 H1 H2 H1 H2
X1
X2
X1
X2
X1
X2
Pole Butt Plate or W rap Additional ground rods as needed Ground connection point
10,000 V
0V
Infinite Ground
8000
7000
g
6000
a b c
5000
Volts
4000
3000
.5 Ohm 5 Ohm 10 Ohm 20 Ohm
2000
1000
0 0.E+00
1.E-06
2.E-06
Volts
Backwards
G M OV volts
C + M OV volts _
ShieldWire (OverheadNeutral, OH N)
Backward Through:
Lightning Arresters
H 1 H 2 H 1 H 2 H 1 H 2
X1 X2
X1 X2
X1 X2
Transform ers
Reda Cable
TVSS
X1
X2
X1 X2
X1
X2
Transformers
a b c g
6. A service post (Burndy K2C23B1 or Penn-Union SCS-4A1) screwed into a tapped hole between bolts in the lower flange is the recommended wellhead grounding method. A "hot work" permit will be required if natural gas is present. Connection at the lower flange should eliminate the need for ground wire removal during a workover.
Pole Butt Plate or W rap Additional ground rods as needed Ground connection point
Lightning Arresters
H1 H2 H1 H2 H1 H2
X1
X2
X1 X2
X1
X2
Arm or ground
Pole Butt Plate or W rap Additional ground rods as needed Ground connection point
Preferred Submersible Pump Lightning Protection Grounding for Variable Speed Drives
Lightning Arresters
H1 H2 H1 H2
X1 X2 X1 X2
H1
H2
X1
X2
Disconnect
TVSS1
1. Ground wires should be green THHN insulated, #2AW stranded copper to minimize G breakage and corrosion. 2. Power system ground wire should not connect directly to the drive through conduit or the disconnect. It should go directly to the wellhead. This is critical to preventing TVSS1 from damaging the VSD and ESP when lightning strikes. Disconnect, VSD and step-up transformers are still bonded via the ESP system ground wire. 3. 480V power into VSD should be ungrounded. 4. For safety ESP cable armor must be connected to the ESP System Ground or TVSS Ground with #8 AW solid copper wire as shown. Between the switchboard and G poles it should be isolated from the Power System Ground. 5. Power System, ESP System and TVSS ground wires should be isolated from each other to avoid sideflash 6. TVSS Ground wire should connect to the ground lug on the side of TVSS2 at the junction box. The small green TVSS wire should ground the junction box internally. 7. At the junction box armors should not come in contact with each other or the metal box to minimize ground loop interference. 8. A service post (Burndy K2C23B1 or Penn-Union SCS-4A1) screwed into a tapped hole between bolts in the lower flange is the recommended wellhead grounding method. A "hot work" permit will be required if natural gas is present. Connection at the lower flange should eliminate the need for ground wire removal during a workover. 9. If drive is trailer mounted junction box should W ellhead be fiber glass for electrical isolation
arm ground or w ire Step-U Transform p er
TVSS2
or
Earthsurface line
480V, 3 phase
Control box
TVSS Motor
Wellhead
Y X
Earth surface Z
Summary
Charge Transfer Systems can provide improved tank battery protection. Reliability has been over 99% for 40,00 service years Properly designed and installed TVSS can prevent almost all equipment damage if: 4-wire TVSS are used grounded to wellhead junction box mounting ungrounded transformer windings separate ground wires