18-505_M-MV-202 MEZ FLOOR PLAN
18-505_M-MV-202 MEZ FLOOR PLAN
18-505_M-MV-202 MEZ FLOOR PLAN
NOTES
LIM
K
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL SERVICES.
AC
2. ALL DUCT AND GRILLE SIZES ARE IN MM.
SETBACK LIMIT
TB
3. ALL PIPE SIZES ARE IN MM.
7500
SE
4. ALL DUCT WORK TO BE INSULATED IN ACCORDANCE WITH THE SPECIFICATION.
5. ALL CONDENSATE DRAINS SHALL RUN WITH A FALL TO THE NEAREST DEDICATED CONDENSATE DRAIN
NETWORK OR FLOOR DRAIN.
6. ALL DUCT CONNECTIONS TO AHU & FCU SHALL BE OF THE FLEXIBLE TYPE.
SE
N 7.
8.
PROPRIETARY, INSULATED ACCESS PANELS SHALL BE INSTALLED AT ALL FD'S VCD'S AND NRD'S.
FD'S SHALL BE PROVIDED WHERE DUCTS CROSS FIRE BARRIERS. ALL FD'S TO HAVE BLADES OUT OF
THE AIR STREAM.
TB 9. SUITABLE, APPROVED SLEEVES AND SEALANTS SHALL BE PROVIDED WHERE BOTH INSULATED AND NON
1IT 2 3 4 5 6 7 11.
RELEASE FASTENINGS.
CHILLED WATER PIPE SUPPORTS SHALL NOT PENETRATE INSULATION VAPOUR SEALS.
12. ALL DUCT WORK WITHIN 4.0 M OF UNITS OUTLETS SHALL BE ACOUSTICALLY LINED.
13. ALL DUCTWORK/PIPEWORK CROSSING EXPANSION JOINTS TO BE PROVIDED WITH EXPANSION
COMPENSATION FITTINGS.
9200 8650 8650 8650 8650 9200 14. CONTRACTOR SHALL PROVIDE BALANCING DAMPERS ON EACH DUCT BRANCH AND WHERE REQUIRED TO
ACHIEVE AIR BALANCE.
LIMIT OF 15. CONTRACTOR SHALL PROVIDE BALANCING AND REGULATING VALVES IN CHILLED WATER PIPE WORK AS
1ST FLOOR REQUIRED TO ACHIEVE WATER BALANCE EVEN NOT INDICATED ON DRAWINGS.
15000 16. CONTRACTOR SHALL PROVIDE SOUND ATTENUATORS WITHIN DUCTWORK AND OTHER SOUND ATTENUATION
ABOVE SETBACK LIMIT MEANS TO ENSURE FOLLOWING NOISE LEVELS ARE NOT EXCEEDED.
2 1
BED ROOMS - NC 35
GUEST ROOMS - NC 35
LOUNGES/LOBBIES/PREFUNCTION - NC 35
SERVICE AREAS - NC 45
17. PROVIDE STEEL PLATFORMS/RAISED WALKWAYS TO CROSS OVER SERVICES ON ROOF & PLANT ROOMS, TO
RAD-150X150 @ 32 L/s (PANTRY) ACHIEVE ADEQUATE MAINTANANCE ACCESS TO THE APPROVAL OF THE ENGINEER.
RAD-150X150 @ 32 L/s (PANTRY) RAD-150X150 @ 25 L/s (TOILET) RAD-150X150 @ 32 L/s (PANTRY)
RAD-150X150 @ 25 L/s (TOILET) G L10 RAD-150X150 @ 25 L/s (TOILET) 18. THE CONTRACTOR SHALL VERIFY SIZES OF PIPES & CIRCULATION PUMPS AND EXPANSION VESSELS OF
DUCT-150X150 HEAT RECOVERY SYSTEMS AS PER THE MANUFACTURER'S RECOMMENDATIONS. THE CALCULATION SHALL
DUCT-150X150 DUCT-150X150
BE SUBMITTED TO THE ENGINEER FOR APPROVAL.
C FD
200
FD
VD PANTRY
DUCT- 150X150 @ 64 L/S (T/A) PANTRY TOILET
VD VD
DUCT- 150X150 @ 32 L/S (F/B) 0 17-08-2023 ISSUED FOR CONSTRUCTION
VOID
DUCT- 200X200 @ 100 L/S (T/A) TOILET VD
PANTRY
VD TOILET GARBAGE RM.
DUCT- 150X150 @ 75 L/S (F/B)
FD FD
VD FD VD
FD FD DUCT- 150X150 @ 75 L/S (T/A)
D
± 0.00 m
MOSONRY DUCT- 1100X600 @ 3760 L/S (F/A) RECYCLE GND F.F.L DUCT- 150X150 @ 60 L/S (F/B)
CANOPY
MOSONRY DUCT- 1100X600 @ 2820 L/S (T/B)
8650
73 67 DG - 300 x 200 81
FD VD UP STAIR-2
72 68 -
DUCT- 150X150 @ 32 L/S (T/A) PANTRY 71 69
UP DN
70 JANITOR VD
4/M A --
FD
VD
+3.85 m
CW02 CORRIDOR MEZ F.F.L
200
AREA = 82.76 sq m.
DUCT- 150X150 @ 50 L/S (T/A)
DUCT- 150X150 @ 25 L/S (F/B)
+3.75 m +3.75 m DUCT- 150X150 @ 25 L/S (T/A)
DUCT- 150X150 @ 64 L/S (T/A) FD FD S.S.L S.S.L DUCT- 150X150 @ 25 L/S (F/B)
DUCT- 150X150 @ 32 L/S (F/B) G L12
± 0.00 m
GND F.F.L
DUCT- 150X150 @ 32 L/S (T/A) FADEL FOUANI --
VD 2 DUCT- 150X150 @ 32 L/S (F/B)
TOILET --
E VD FD
3226
FD DUCT- 150X150 @ 32 L/S (T/A)
PANTRY 1
DUCT- 150X150 @ 64 L/S (T/A) LIMIT OF PANTRY TOILETVD DUCT- 150X150 @ 32 L/S (F/B)
DUCT- 150X150 @ 32 L/S (F/B) 1ST FLOOR VD VOID
± 0.00 m
ABOVE GND F.F.L
LIMIT OF DUCT- 150X150 @ 25 L/S (T/A)
DUCT- 150X150 @ 50 L/S (T/A) 1ST FLOOR DUCT- 150X150 @ 25 L/S (F/B)
DUCT- 150X150 @ 25 L/S (F/B) 2 G L12
ABOVE
G L08
1
OFFICE-06 OFFICE-07
AREA = 121.73 sq m.
8650
AREA = 122.59 sq m. Commer ia Li ense: 13160 Ex : 12/12/2023 MME / EEOACC: 4/M Ex : 13/01/2025
VOID
G L12 RAD-150X150 @ 32 L/s (PANTRY)
RAD-150X150 @ 25 L/s (TOILET)
DUCT-150X150
(2B+G+M+3 TYP FLRS) OFFICE BUILDING
(ECQ-B04, PIN:69040300)
F RAD-150X150 @ 32 L/s (PANTRY) ENERGY CITY - QATAR
RAD-150X150 @ 25 L/s (TOILET)
DUCT-150X150
QATAR ENDOWMENT AUTHORITY
F
GL12a
IMPORTANT NOTE:
AUG.2023 18-505
G L07
(A) PROVIDE FIRE DAMPERS / MOTORIZED COMBINATION FIRE
SMOKE DAMPERS AS PER REQUIREMENTS OF NFPA / LOCAL QATAR MEZZANINE FLOOR PLAN
CIVIL DEFENSE DEPARTMENT WHETHER SHOWN ON DESIGN
DRAWING OR NOT. CONTRACTOR SHALL SUBMIT ARCHITECTURAL MECHANICAL VENTILATION LAYOUT
FIRE ZONES DRAWING INDICATING ALL DUCT PENETRATING. THE
1 2 LIMIT OF M-MV-202 1:100
8050
ABOVE
FOR INSPECTION TESTING AND SERVICE. ALL FIRE ACCESSORIES
KL
(VCD) ON EACH SUPPLY / RETURN DUCT, BRANCH DUCT AND 3529 3529
WHERE REQUIRED TO ACHIEVE AIR BALANCE. THE HAND
LOCK SHALL BE ACCESSIBLE FOR INSPECTION TESTING AND
G G
SERVICE / AIR BALANCING.
0