Generator Set Data Sheet Hryw 1275 d5 6 Rental English
Generator Set Data Sheet Hryw 1275 d5 6 Rental English
Generator Set Data Sheet Hryw 1275 d5 6 Rental English
Powered byYANMAR
416/240 416/240
380/220 380/220
AVAILABLE VOLTAGES V 440/245 440/245
415/240 415/240
460/265 460/265
RATED AT POWER
Cos Phi 0,8 0,8
FACTOR
directives: 20FT
WATER-COOLED
Data Center Power (DCP): Complies with Uptime Institute: Tier III & IV. The
manufacturer declares a load factor for grid failure of 100% per 24h and an average
load factor per year less than 75%. No overload margin available. It can be operated for
an unlimited number of hours per year. Applicable in countries with stable network. If and dimensions based on standard products. Illustrations may
the model is for DCC application, inform Factory
Technical data described in this catalogue correspond to the available
information at the moment of printing.
The illustrations and images are indicative and may not coincide in their
entirety with the product.
Industrial design under patent.
| MOROCCO |
AUSTRALIA
HRYW-1275 D5/6
(PRP/DCP) 2
(PRP/DCP)
(COP) 177,1 184,2
Direct
mm 5
mm 205
Consumption (PRP/DCP) vs Fan Revolutions | 50Hz Consumption (PRP/DCP) vs Fan Revolutions | 60Hz
0
2020 OCT29
HRYW-1275 D5/6
APPLICATION DATA
EXHAUST SYSTEM NECESSARY AMOUNT OF AIR
1.500 rpm 1.800 rpm 1.500 rpm 1.800 rpm
Maximum exhaust temperature ºC 493 503 Intake air flow m³/h 6084 6300
Exhaust Gas Flow m³/min 241,8 256,8 Cooling Air Flow m³/s 22,2 27,3
Maximum allowed back pressure kPa 6 Alternator fan air flow m³/s 2,69 3,45
Container version
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HRYW-1275 D5/6
SYNCHRONIZING
PANEL
Automatic control panel WITHOUT ATS (Automatic Transfer Switch) and WITHOUT
mains control with thermal magnetic protection (according to voltage and number of
phases) and Earth leakage protection, composed by:
• Control and power electric panel, with measurements device and controller
(according to necessity and configuration), both fitted on the Genset.
• 4P automatic circuit breaker (one for each set) of suitable rated current
completed with motorized driver 230Vac, opening coil MN12/24Vdc and aux.
contacts.
• Earth leakage adjustable protection (time [inst 0,2 0,5 3 5 sec] & sensibility
[30 300mA 3A])
• Battery Charger 3A 230Vac
• Engine water preheating
CONTROL UNIT
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HRYW-1275 D5/6
FEATURES OF THE
CONTROL UNIT
OPERATING MODE
CONTROL UNIT
1. Locked | OFF. Controller is switched off, it is not allowed any operation on the Genset, all sequences are blocked. This has to be
configured for maintenance operation.
2. Manual Mode | MAN. Gensets starts through frontal command, breaker closing is manual but all protection devices are activated..
3. Automatic Mode | AUTO.
a. Parallel with main| LOAD SHARING. Genset and the main work together sharing the load. Back-Synch is not available.
b. Parallel with main | BASE LOAD. Genset and the main work together. Genset works at a fixed power. Back-Synch is not
available.
c. Parallel with main | PEAK SHAVING. Genset and the main work together. The main is the main supplier and the Genset
supplies peaks. Back-Synch is not available.
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HRYW-1275 D5/6
ALARMS
CONTROL UNIT
READINGS
CONTROL UNIT
PROTECTIONS
CONTROL UNIT
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com