FP320X30
FP320X30
FP320X30
75 (CLEAR WIDTH)
32mmØ O.S. & GATE VALVE
40 Ø ANGLE VALVE ELECTRICAL WIRING & 2 1/2'' SIAMESE TWIN PERIPHERAL TYPE JOCKEY PUMP
CONDUIT DOWN TO FIRE 250
32mmØ PRESSURE RELIEF VALVE
PUMP CONTROL PANEL 32mmØ CHECK VALVE
(BY PLUMBING)
32mmØ UNION PATENTE
2 1/2'' x 1 1/4" Ø G.I. PIPE
1.00
REDUCER
65mmØ O.S. & GATE VALVE
PUSH BUTTON (TO START 65mmØ PRESSURE RELIEF VALVE
BOTH TRANSFER PUMPS IN 65mmØ CHECK VALVE
TIMES OF EMERGENCY 65mmØ O.S. & GATE VALVE
HORIZONTAL SPLIT CASE FIRE PUMP
BRASS POLISHED FIRE FOG
ADJUSTABLE NOZZLED
0.80 (CLEAR HEIGHT)
65
32mmØ SUCTION PIPE
1.00
1/4'' Ø G.I. PIPE, SCHED. 40 NOTE:
40 Ø x 30.00 METERS LONG
RUBBER LINE COTTON FIRE
HOSE JACKETED W/ CHROME 65mmØ O.S. & GATE VALVE
WATER FLOW METER
PLAN 65mmØ RETURN TEST LINE
PIN LUG COUPLING THREADED 65mmØ SUCTION PIPE
65mmØ SUCTION PIPE W STRAINER
PULL FLUSH MOUNTING DOOR JOCKEY PUMP CONTROLLER
W/ TRIM FOR ALL GLASS FIRE PUMP CONTROLLER
PLATE SHALL BE GAUGE # 18
W/ NOTE "BREAK GLASS
IN CASE OF FIRE"
1.80
ALUMINUM TRIM
EXISTING FLOOR LINE
ELEVATION
FIRE PUMP SHALL START IN TIME OF EMERGENCY BY PUSHING THE
PUSH BUTTON LOCATED INSIDE HOSE CABINETS (FHC) PER FLOOR
FIRE PUMP DETAILS
50MM Ø WSP
FIRE DEPT. CONN. DETAIL NOT TO SCALE
NOT TO SCALE
0.50
0.35
0.20
square inch; GPM is oil flow in gallons NOMINAL SIZE
SCALE 1:10 MTS.
per minutes.
W/ 12 MM. Ø RSB @ 0.20 M.
O.C., EACHWAY
0.15
PIPE SIZE 25 32 40 50 65 75 100 150 200
0.25
300
(PSI)
200
(HP)
50 220 3Ø 60 Hz
SINGLE STAGE END SUNCTION MOTOR DRIVEN
VERTICAL IN LINE ELECTRIC
HP = 46.67 HP OR SAY 50HP JP - 1 1 TYPE MOTOR DRIVEN 50 110 5 220 3Ø 60 Hz
0.25
0.15
CUT-IN AND CUT OFF PRESSURE SWITCH SETTINGS FOR THE JOCKEY PUMP
JOCKEY PUMP SETTING
SEE NOTE
SPRINKLER FEEDMAIN
PLAN
6.00
Rules-Of-Thumb: SHALL BE 80 PSI AND 90 PSI, RESPECTIVELY
ARCHITECT / ENGINEER : PROJECT TITLE: OWNER : DESIGNED BY : REVISION / S : SHEET CONTENTS: SHEET NO.: