Nothing Special   »   [go: up one dir, main page]

FP320X30

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

0.

75 (CLEAR WIDTH)
32mmØ O.S. & GATE VALVE
40 Ø ANGLE VALVE ELECTRICAL WIRING & 2 1/2'' SIAMESE TWIN PERIPHERAL TYPE JOCKEY PUMP
CONDUIT DOWN TO FIRE 250
32mmØ PRESSURE RELIEF VALVE
PUMP CONTROL PANEL 32mmØ CHECK VALVE
(BY PLUMBING)
32mmØ UNION PATENTE
2 1/2'' x 1 1/4" Ø G.I. PIPE

1.00
REDUCER
65mmØ O.S. & GATE VALVE
PUSH BUTTON (TO START 65mmØ PRESSURE RELIEF VALVE
BOTH TRANSFER PUMPS IN 65mmØ CHECK VALVE
TIMES OF EMERGENCY 65mmØ O.S. & GATE VALVE
HORIZONTAL SPLIT CASE FIRE PUMP
BRASS POLISHED FIRE FOG
ADJUSTABLE NOZZLED
0.80 (CLEAR HEIGHT)

65
32mmØ SUCTION PIPE

1.00
1/4'' Ø G.I. PIPE, SCHED. 40 NOTE:
40 Ø x 30.00 METERS LONG
RUBBER LINE COTTON FIRE
HOSE JACKETED W/ CHROME 65mmØ O.S. & GATE VALVE
WATER FLOW METER
PLAN 65mmØ RETURN TEST LINE
PIN LUG COUPLING THREADED 65mmØ SUCTION PIPE
65mmØ SUCTION PIPE W STRAINER
PULL FLUSH MOUNTING DOOR JOCKEY PUMP CONTROLLER
W/ TRIM FOR ALL GLASS FIRE PUMP CONTROLLER
PLATE SHALL BE GAUGE # 18
W/ NOTE "BREAK GLASS
IN CASE OF FIRE"
1.80

ALUMINUM TRIM
EXISTING FLOOR LINE

COVER FOR SIAMESE CONNECTION MOUNTING DETAILS OF PORTABLE FIRE EXTINGUISHER


SHOULD BE PROVIDED WITH CHAIN NOT
FIRE PUMP OPERATION IN TIME OF EMERGENCY: TO SCALE
1.00 (FROM PCCP LEVEL)

ELEVATION
FIRE PUMP SHALL START IN TIME OF EMERGENCY BY PUSHING THE
PUSH BUTTON LOCATED INSIDE HOSE CABINETS (FHC) PER FLOOR
FIRE PUMP DETAILS
50MM Ø WSP
FIRE DEPT. CONN. DETAIL NOT TO SCALE
NOT TO SCALE

PIPE SIZE CONVERSION TABLE


FIRE PUMP RATE COMPUTATION: NOMINAL SIZE
EXISTING ROAD LINE
MM. (DIAMETER) 25 32 40 50 65 75 100 150 200
IN. (DIAMETER) 1'' 11/4'' 11/2'' 2'' 21/2'' 3'' 4'' 6'' 8''
Formula: HP = PSI x GPM / 1714
PSI is gauge pressure in pounds per SCHEDULE OF PIPE SLEEVE
FIRE HOSE CABINET DET. 125 MM. THK. R.C. SLAB
0.35
0.20 0.50
6.00

0.50
0.35
0.20
square inch; GPM is oil flow in gallons NOMINAL SIZE
SCALE 1:10 MTS.
per minutes.
W/ 12 MM. Ø RSB @ 0.20 M.
O.C., EACHWAY
0.15
PIPE SIZE 25 32 40 50 65 75 100 150 200
0.25

SLEEVE SIZE 50 50 65 100 125 125 200 250 300


FIRE PUMP COMPUTATION:
OUTLET OUTLET
PIPE PIPE

FIRE RATED SEALANT


HP = 200 PSI X 400 GPM
MH MH
PUMP MOTOR DATA
CHARACTERISTICS
0.50
2.50
3.00

INLET INLET DESIGNATION QUANTITY TYPE DRIVE


PIPE PIPE
CAPACITY HEAD RATING VOLTAGE PHASE CYCLE
1714 PSI FP - 1 1 CENTRIFUGAL PUMP ELECTRIC
(GPM)

300
(PSI)

200
(HP)

50 220 3Ø 60 Hz
SINGLE STAGE END SUNCTION MOTOR DRIVEN
VERTICAL IN LINE ELECTRIC
HP = 46.67 HP OR SAY 50HP JP - 1 1 TYPE MOTOR DRIVEN 50 110 5 220 3Ø 60 Hz
0.25

0.15

CUT-IN AND CUT OFF PRESSURE SWITCH SETTINGS FOR THE JOCKEY PUMP
JOCKEY PUMP SETTING
SEE NOTE
SPRINKLER FEEDMAIN
PLAN

6.00
Rules-Of-Thumb: SHALL BE 80 PSI AND 90 PSI, RESPECTIVELY

FOR SPRINKLER RISER


FOR DEATILS SEE 125 MM. THK. R.C. SLAB
0.35
0.20 0.50 0.50
0.35
0.20 Horsepower for driving a pump: For CUT-IN PRESSURE SWITCH FOR THE PUMP SHALL BE AT 65 PSI AND SHALL
FEEDMAN CONNECTION
AT DWG. NO. P1050/F/049
W/ 12 MM. Ø RSB @ 0.20 M.
O.C., EACHWAY
OUTLET
PIPE MH MH
OUTLET
PIPE
every 1 HP of drive, the equivalent of FIRE PUMP SETTING
BE STOPPED MANUALLY THROUGH THE FIRE PUMP MOTOR CONTROLLER
0.125

FIRE RATED WALL


INLET
PIPE
FLOATING FLOATING
INLET
PIPE 1 GPM @ 230 PSI can be produced.
Horsepower for idling a pump: To idle
VALVE VALVE

OF STAIRCASE 12 MM. VER. & HOR. BAR


@ 0.20 M. O.C., EACHWAY
19mmØ FOOTHOLDS
a pump when it is unloaded will SPACED @ EVERY
require about 5% of its full rated 300MM O.C. TO SYSTEM
2.675
3.00

4" THK. CHB, W/ 12 MM. Ø


horsepower. 65mmØ O.S. & GATE VALVE
VERT. BAR @ 0.60 M. O.C.,
B.W., & 12 HOR. BAR @ 65mmØ O.S. & GATE VALVE
EVERY 3RD LAY. OF CHB 65mmØ VICTAULIC COUPLING
32mmØ PRESSURE RELIEF VALVE
CHECK
VALVE
CHECK
VALVE
PRESSURE SWITCH
65mmØ VICTAULIC COUPLING 300LBS. GUAGE
65mmØ ALARM CHECK VALVE
HORIZONTAL SPLIT CASE FIRE RETARD CHAMBER
0.20

0.15 INLET PIPE & VALVE


PUMP
65mmØ O.S. & GATE VALVE 65mmØ DRAIN
SECTION
100 MM. THK. R.C. SLAB (SLOPING)
W/ 12 MM. Ø RSB @ 0.30 M.
65mmØ SUCTION PIPE 65mmØ O.S. & GATE VALVE
O.C., EACHWAY
65mmØ VICTAULIC COUPLING
VICTAULIC COUPLING

CISTERN TANK DETAIL 32mmØ BIP TAPPING POINT


DISCHARGE OF JOCKEY PUMP
PIPE SADDLE
SCALE 1:100 MTS.
CONCRETE TRUST BLOCK
FLOOR CLAMP (PROVIDE
EVERY OTHER FLOOR)
WATER
STORAGE TANK
50,000 GAL

NOTE: CHECK VALVE


FIRE PUMP ELEVATION
ALTERNATIVE CONNECTION IS THRU NOT TO SCALE
THE USE OF BOLTED MECHANICAL
BRANCH CONNECTION SIMILAR TO INCOMING COLD
"VICTAULIC MECHANICAL TEE". WATER MAINS
SUPPLY TO FHC

PIPE RISER SCHEDULE TANK & MOTOR CONNECTION


NOT TO SCALE
NOT TO SCALE

ARCHITECT / ENGINEER : PROJECT TITLE: OWNER : DESIGNED BY : REVISION / S : SHEET CONTENTS: SHEET NO.:

(PROPOSED) THREE(3) STOREY DUSTIN KIRK L. CHUA CADD BY :

& DELWYN KARL L. CHUA


FP
COMMERCIAL BUILDING CHECKED BY :
REG. NO. :
ISSUED ON / AT :
T. I. N. :
PTR NO. :
SITE LOCATION: #003 HERMOSO ST. HERMOSO CMPD. BRGY.
OWNER'S APPROVAL : DATE :
03 04
DALANDANAN,VALENZUELA CITY