Nothing Special   »   [go: up one dir, main page]

Megger Mom200a Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

MOM200A

Micro-ohmmeter

„ Compact and rugged


„ Easy-to-use
„ 200 A output current

DESCRIPTION APPLICATION EXAMPLES


The MOM200A™ is designed to check and measure contact A. Measuring the resistance of a circuit breaker element
resistances in high-voltage circuit breakers, disconnecting switches
1. Connect the micro-ohmmeter to the circuit breaker.
(isolators) and busbar joints. The instrumen is an excellent choice when
2. Set the current (100 A in this example).
200 amperes or less are needed for measurement.
3. Press the resistance pushbutton.
Since the MOM200A weighs only about 14 kg (31 lbs), it is convenient
4. Read the result.
to take along with you.
B. Measuring the resistance of busbar joints
MOM200A is ideal for finding poor connections since it can put out
1. Connect the micro-ohmmeter’s current cables to the object being
100 A for extended periods. Its range extending up to 20 milliohms
tested. Do not connect the sensing cables since measurements
makes it ideal for measuring many different types of connections. will be taken using an external movable voltmeter.
A complete MOM200A includes a cable set (including separate sensing 2. Set the current (100 A in this example).
cables) and a transport case. 3. Connect an external voltmeter to the bus.
4. Read the voltmeter (0.1 mV = 1 µΩ in this example).
5. Move the voltmeter to the next joint.
6. Repeat step 4.

A B
SPECIFICATIONS MOM200A
Specifications are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.
Environment
Application field The instrument is intended for use in
high-voltage substations and industrial
environments.
Temperature
Operating 0°C to +50°C (32°F to +122°F)
Storage & transport -40°C to +70°C (-40°F to +158°F)
Humidity 5% – 95% RH, non-condensing
CE-marking
EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
General
Mains voltage 115 / 230 V AC, 50 / 60 Hz
Power consumption 1610 VA (max)
Protection Miniature circuit breakers, thermal cut- Cable set GA-02053
outs
Dimensions
Instrument 280 x 178 x 246 mm (11” x 7” x 9.7”)
Transport case 560 x 260 x 360 mm
(22” x 10.2” x 14.2”)
Weight 14.6 kg (32.2 lbs) 26 kg (54.1 lbs) with
accessories and transport case
Current cables 2 x 5 m (16 ft), 25 mm²
Sensing cables 2 x 5 m (16 ft), 2.5 mm²
Measurement section
Resistance Ground cable GA-00200 Optional accessory:
Range 0 – 1999 µΩ Calibration shunt BD-90022
0 – 19.99 mΩ
Resolution 1 µΩ
10 µΩ Ordering information
Inaccuracy ±1% of reading + 1 digit Item Art. No.
Output MOM200A
Current 0 – 200 A DC Incl. Cable set GA-02053,
Open circuit voltage 4.7 V DC 2 x 5 m (16 ft), 25mm² (current cables)
Current shunt output 10 mV / 100 A ±0.5%, max 20 mV out, 2 x 5 m (16 ft), 2.5 mm² (sensing cables)
max 10 V to protective earth (ground) Ground cable GA-00200,
Transport case GD-00010
Max. load capacity
115 V Mains voltage BD-11190
Current adjustment set to 100%
Output current Min. output Max. load Rest time 230 V Mains voltage BD-12390
voltage time Optional accessories
100 A DC 3.8 V DC 5 min. 15 min. Cable set 10 m
15 min. 60 min. 2 x 10 m (33 ft), 35 mm2 (current cables).
200 A DC 3.0 V DC 20 s 5 min. 2 x 10 m (33 ft), 2.5 mm2 (sensing cables)
Weight: 9 kg (19.8 lbs) GA-03103
Cable set 15 m
2 x 15 m (49 ft), 50 mm2 (current cables).
2 x 15 m (49 ft), 2.5 mm2 (sensing cables)
Weight: 18.6 kg (40.9 lbs) GA-05153
Calibration shunt
200 A/20 mV BD-90022

Postal address MOM200A_DS_en_V05a


Megger Sweden AB ZI-BD01E ▪ Doc. BD0242EE ▪ 2023
Box 724 Subject to change without notice
SE-182 17 Danderyd Registered to ISO 9001 and 14001
SWEDEN The word ‘Megger’ is a registered
trademark
T +46 8 510 195 00
E seinfo@megger.com www.megger.com