Data sheet 3RV2711-0BD10

Circuit breaker size S00 for system protection with approval circuit breaker UL 489,
CSA C22.2 No.5-02 A-release 0.2 A N-release 2.6 A screw terminal Standard
switching capacity

product brand name SIRIUS


product designation Circuit breaker
design of the product For system protection according to UL 489/CSA C22.2 No. 5
product type designation 3RV2
General technical data
size of the circuit-breaker S00
product extension auxiliary switch Yes
power loss [W] for rated value of the current
● at AC in hot operating state 5.5 W
● at AC in hot operating state per pole 1.8 W
insulation voltage with degree of pollution 3 at AC rated value 690 V
surge voltage resistance rated value 6 kV
shock resistance according to IEC 60068-2-27 25 g / 11 ms (rectangular impulse and sine pulse)
mechanical service life (operating cycles)
● of the main contacts typical 100 000
● of auxiliary contacts typical 100 000
electrical endurance (operating cycles) typical 100 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 10/01/2009
SVHC substance name Blei - 7439-92-1
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -20 ... +60 °C
● during storage -50 ... +80 °C
● during transport -50 ... +80 °C
relative humidity during operation 10 ... 95 %
Main circuit
number of poles for main current circuit 3
operating voltage
● rated value 20 ... 690 V
● at AC-3 rated value maximum 690 V
● at AC-3e rated value maximum 690 V
operating frequency rated value 50 ... 60 Hz
operational current rated value 0.2 A
operational current
● at AC-3 at 400 V rated value 0.2 A
● at AC-3e at 400 V rated value 0.2 A
operating power
● at AC-3

3RV27110BD10 Subject to change without notice


12/6/2023
Page 1/5 © Copyright Siemens
— at 230 V rated value 0 kW
— at 400 V rated value 0.1 kW
— at 500 V rated value 0.1 kW
— at 690 V rated value 0.1 kW
● at AC-3e
— at 230 V rated value 0 kW
— at 400 V rated value 0.1 kW
— at 500 V rated value 0.1 kW
— at 690 V rated value 0.1 kW
operating frequency
● at AC-3 maximum 15 1/h
● at AC-3e maximum 15 1/h
Protective and monitoring functions
product function
● ground fault detection No
● phase failure detection No
design of the overload release thermal
maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value 100 kA
● at AC at 400 V rated value 100 kA
● at AC at 500 V rated value 100 kA
● at AC at 690 V rated value 100 kA
● at 480 AC Y/277 V according to UL 489 rated value 65 kA
operating short-circuit current breaking capacity (Ics) at AC
● at 240 V rated value 100 kA
● at 400 V rated value 100 kA
● at 500 V rated value 100 kA
● at 690 V rated value 100 kA
response value current of instantaneous short-circuit trip unit 2.6 A
Short-circuit protection
product function short circuit protection Yes
design of the short-circuit trip magnetic
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
height 144 mm
width 45 mm
depth 97 mm
required spacing
● for grounded parts at 400 V
— downwards 30 mm
— upwards 30 mm
— at the side 30 mm
● for live parts at 400 V
— downwards 30 mm
— upwards 30 mm
— at the side 30 mm
● for grounded parts at 500 V
— downwards 30 mm
— upwards 30 mm
— at the side 30 mm
● for live parts at 500 V
— downwards 30 mm
— upwards 30 mm
— at the side 30 mm
● for grounded parts at 690 V
— downwards 70 mm
— upwards 70 mm
— backwards 0 mm
— at the side 30 mm

3RV27110BD10 Subject to change without notice


12/6/2023
Page 2/5 © Copyright Siemens
— forwards 0 mm
● for live parts at 690 V
— downwards 70 mm
— upwards 70 mm
— backwards 0 mm
— at the side 30 mm
— forwards 0 mm
Connections/ Terminals
type of electrical connection
● for main current circuit screw-type terminals
arrangement of electrical connectors for main current Top and bottom
circuit
type of connectable conductor cross-sections
● for main contacts
— solid or stranded 1 ... 10 mm², max. 2x 10 mm²
— finely stranded with core end processing 1 ... 16 mm², max. 6 + 16 mm²
● for AWG cables for main contacts 2x (14 ... 10)
tightening torque
● for main contacts with screw-type terminals 2.5 ... 3 N·m
design of screwdriver shaft Diameter 5 to 6 mm
size of the screwdriver tip Pozidriv size 2
design of the thread of the connection screw
● for main contacts M4
Safety related data
proportion of dangerous failures
● with low demand rate according to SN 31920 50 %
● with high demand rate according to SN 31920 50 %
failure rate [FIT] with low demand rate according to SN 50 FIT
31920
B10 value with high demand rate according to SN 31920 5 000
T1 value for proof test interval or service life according to 10 a
IEC 61508
protection class IP on the front according to IEC 60529 IP20
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front
display version for switching status Handle
Approvals Certificates
General Product Approval

Confirmation KC

General Product Ap-


Test Certificates Marine / Shipping other
proval

Special Test Certific- Type Test Certific- Miscellaneous


ate ates/Test Report

other Railway

Confirmation Vibration and Shock

Further information
Siemens has decided to exit the Russian market (see here).
https://press.siemens.com/global/en/pressrelease/siemens-wind-down-russian-business
Siemens is working on the renewal of the current EAC certificates.

3RV27110BD10 Subject to change without notice


12/6/2023
Page 3/5 © Copyright Siemens
Please contact your local Siemens office on the status of validity of the EAC certification if you intend to import or offer to supply these products to an
EAC relevant market (other than the sanctioned EAEU member states Russia or Belarus).
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2711-0BD10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2711-0BD10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2711-0BD10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2711-0BD10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2711-0BD10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2711-0BD10&objecttype=14&gridview=view1

3RV27110BD10 Subject to change without notice


12/6/2023
Page 4/5 © Copyright Siemens
1/L1

3/L2

5/L3

-F

I> I> I>


2/T1

4/T2

6/T3

last modified: 8/29/2023

3RV27110BD10 Subject to change without notice


12/6/2023
Page 5/5 © Copyright Siemens

You might also like