Eaton SPD3Ni Technical Specification
Eaton SPD3Ni Technical Specification
Eaton SPD3Ni Technical Specification
(3 Phase, 380-440V, 50kA per mode) The SPD3i is designed to protect 3-phase power
systems against damage from surges and spikes
INSTALLATION INSTRUCTIONS caused by lightning and other electrical sources. The
FEATURES unit is intended for point-of-entry or sub-board
• 2 mode protection (L-N, N-E) protection and is connected in parallel with the power
• Compact solution for 3-phase protection system via HRC fuses. This unit is available in
• DIN43880 case, 35 mm DIN-rail mountable various models for different voltages and
• All MOVs thermally protected applications. Check that the model you have
• Includes dry-contact alarm purchased is rated correctly for your power system.
Applications .
• Secondary power circuits / Sub-boards
This model (SPD3Ni/A) is designed for TN-C and
• Telecommunication Systems / Rectifiers TN C-S power systems in the range of 220-
• Process and Control Systems / Homes & Units 277V(380-440V). If your power system is TN-S, TT
• Computer Systems / Medical Systems or IT, or of a different voltage, this model is NOT
• All sensitive Electronic Equipment suitable.
Specification are subject to change without notice. Copyright 2005 Eaton Power Quality Pty Ltd
Technical Specification – SPD3Ni/A
Tvss Doc# 510073
Page 1 of 2
Web: http://www.powerware.com.au Phone: 1300 UPS UPS
INSTALLATION
EARTHING
Refer to the procedure and diagram shown to connect the
SPD3Ni/A. For proper operation, all surge diverters rely upon a good earth
connection. In some installations the existing earth system may
PROCEDURE: require upgrading. Important things to look for are:
• The main earth wire (from earth link on switchboard to ground
1. CHECK
rod or system) MUST be at least 6mm diameter (preferably
• Always work safely – disconnect power before making
connections. larger) and should be as short as possible.
• All wiring must be carried out by suitably qualified • Earth connections from the unit to earth link MUST be as short
personnel according to the applicable standards.
as possible.
• Check for correct operating voltage and power system.
Failure to consider the above points can result in improper
This model (SPD3Ni/A) is designed for TN-C and TN C-
operation of the unit and possible damage to the installation.
S power systems in the range of 220-277V(380-440V). If
your power system is TN-S, TT or IT, or of a different
voltage, this model is not suitable. Please contact
your supplier for a suitable model to suit your
application.
• Always use the correct size HRC fuses.
• For services >125A, use 125A fuses. For services
<125A, use one step below service fuses (i.e. 80A
service = 63A fuses). DO NOT USE A 3-PHASE MCB.
• Always use Gg or Gl-rated fuses. Do not use delay types
or ‘semiconductor’ fuses.
• Consider fitting a fuse-switch or a separate isolation
switch to facilitate safe maintenance in the future.
2. INSTALL
• Locate a fuse position as close as possible to the Main
Switch.
• Install fuseholders or fuse-switch.
• Locate a suitable position for the SPD3, ensuring
adequate space for cables. Do not install above heat-
generating objects or in any position that is exposed to
weather.
• Install unit to DIN-rail in switchboard or cabinet.
3. CONNECT
• Connect wiring - refer to connection diagram. If using
stranded cable, always use wire ferrules for lowest
resistance and to prevent damage to the wire.
• Use a suitably-rated cable for power connections. Cable
should be rated for operation at the system voltage and
2 2
should be 4mm to 16mm .
• Use short cables for phase, neutral and earth
connections or protection will be reduced.
• Use a suitably-rated cable for alarm connections. Cable
should be rated for operation at the system voltage and
2 2
should be 0.5mm to 1.5mm .
4. NOTES:
• 125A fuses are rated such for maximum surge rating.
On services below 150A, use the correspondingly lower
sized fuse (i.e. 80A service = 63A fuse).
• Wiring from fuse to SPD is carrying surge currents only,
not load current. This means that smaller cables may be
used than is normal for the current rating.
• If using under-sized cables, some energy authorities WARNING – OBSERVE THE SUPPLY VOLTAGE LIMITATIONS
OF THIS UNIT. FAILURE TO OBSERVE THIS WARNING WILL
require double insulation (i.e. sleeving) of the cables.
RESULT IN DAMAGE TO THE UNIT. DAMAGE FROM
• Maximum alarm relay resistive load is 5A. EXCESSIVE SUPPLY VOLTAGE IS NOT WARRANTABLE.
• It is recommended not to connect the alarm contacts to
AC mains circuits if possible, to prevent flashover from
surges on the AC line. Connect to a PLC or BMS if
available. If you experience any problems with the
• Do not Megger test cabling with unit connected – unit installation or commissioning, contact your
may be damaged. Eaton representative for guidance.
Specification are subject to change without notice. Copyright 2005 Eaton Power Quality Pty Ltd
Technical Specification – SPD3Ni/A
Tvss Doc# 510073
Page 2 of 2
Web: http://www.powerware.com.au Phone: 1300 UPS UPS