E84aycpm Profibus Mci Module v5-0 en
E84aycpm Profibus Mci Module v5-0 en
E84aycpm Profibus Mci Module v5-0 en
PROFIBUS® E84AYCPM
L
Contents
________________________________________________________________
2 Safety instructions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 11
2.1 General safety and application instructions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 11
2.2 Device- and application-specific safety instructions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 12
2.3 Residual hazards _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 12
3 Product description _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 13
3.1 Application as directed _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 13
3.2 Identification _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 13
3.3 Features _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 14
3.4 Terminals and interfaces _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 14
4 Technical data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 15
4.1 General data and operating conditions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 15
4.2 Protective insulation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 16
4.3 Protocol data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 19
4.4 Communication time _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 19
4.5 Dimensions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 20
5 Installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 21
5.1 Mechanical installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 22
5.1.1 Mounting for 0.25 kW and 0.37 kW standard devices _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 22
5.1.2 Mounting for standard devices of 0.55 kW and more _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 23
5.1.3 Replacing the communication module _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 24
5.2 Electrical installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 25
5.2.1 Network topology _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 25
5.3 Activating the bus terminating resistor _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 27
5.3.1 Bus cable specification _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 28
5.3.2 PROFIBUS connection _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 29
6 Commissioning _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 30
6.1 Before initial switch-on _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 30
6.2 Configuration of the controller (master) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 31
6.3 Setting the station address _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 32
6.4 Initial switch-on _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 34
6.5 Going online with »Engineer« via TCI _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 35
7 Data transfer _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 44
2 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Contents
________________________________________________________________
10 Monitoring _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 81
10.1 Permanent interruption of PROFIBUS communication _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 81
10.2 Short-time interruption of PROFIBUS communication _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 82
10.3 Settings and displays in the »Engineer« _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 83
11 Diagnostics _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 84
11.1 LED status displays _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 84
11.1.1 Module status displays _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 85
11.1.2 Fieldbus status displays _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 86
11.2 Diagnosing with the »Engineer« _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 87
11.3 Advanced diagnostic message _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 89
12 Error messages _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 91
12.1 Short overview of the PROFIBUS error messages _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 91
12.2 Possible causes and remedies _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 92
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 3
Contents
________________________________________________________________
13 Parameter reference _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 95
13.1 Parameters of the communication module _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 95
13.2 Table of attributes _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 103
13.3 Implemented PROFIdrive objects (DP-V1) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 105
4 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
1 About this documentation
________________________________________________________________
Note!
This documentation supplements the mounting instructions supplied with the
communication module and the "Inverter Drives 8400" hardware manual.
The hardware manual contains safety instructions which must be observed!
The features and functions of the communication module are described in detail.
Typical applications are explained with the help of examples.
The theoretical connections are only explained in so far as they are necessary for comprehending
the function of the communication module.
This documentation does not describe the software of other manufacturers. No responsibility is
taken for corresponding information given in this documentation. Information on how to use the
software can be obtained from the documents of the control system (master).
All brand names used in this documentation are trademarks of their respective owners.
Tip!
Detailed information about PROFIBUS can be found on the website of the PROFIBUS &
PROFINET user organisation:
www.profibus.com
5 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
1 About this documentation
________________________________________________________________
Target group
This documentation is intended for all persons who plan, install, commission and maintain the
networking and remote servicing of a machine.
Tip!
Current documentation and software updates with regard to Lenze products can be found
in the download area at:
www.Lenze.com
Validity information
The information given in this documentation is valid for the following devices:
Screenshots/application examples
All screenshots in this documentation are application examples. Depending on the firmware
version of the communication module and the software version of the Engineering tools installed
(»Engineer«, »STEP7«), the screenshots in this documentation may differ from the actual screen
display.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 6
1 About this documentation
1.1 Document history
________________________________________________________________
Version Description
1.0 11/2007 TD17 First edition
2.0 11/2008 TD17 General revision
3.0 02/2010 TD17 • Update of chapter structure
• General revision
4.0 11/2010 TD17 General revision
5.0 11/2011 TD17 • New layout
• New: Going online with »Engineer« via TCI ( 35)
• General corrections
7 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
1 About this documentation
1.2 Conventions used
________________________________________________________________
This manual uses the following conventions to distinguish between different types of information:
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 8
1 About this documentation
1.3 Terminology used
________________________________________________________________
Term Meaning
Inverter Lenze inverter of the "Inverter Drives 8400" product series
Standard device
Code Parameters which serve to parameterise or monitor the inverter. This term is
usually called "index".
Subcode If a code contains several parameters, these are stored in subcodes.
This manual uses a slash "/" as a separator between code and subcode (e.g.
"C118/3").
This term is usually called "subindex".
GSD / GSE Device data base file (device description for PROFIBUS stations)
HW Hardware
Lenze setting Settings with which the device is preconfigured ex works.
Basic setting
PROFIBUS® (Process Field Bus) is a widely-used fieldbus system for the
automation of machines and production plants.
PROFIBUS® is a registered trademark and patented technology licensed by the
PROFIBUS & PROFINET International (PI) user organisation.
PDO Process data object
PLC Programmable Logic Controller
(German designation: SPS - Speicherprogrammierbare Steuerung)
»STEP7« Siemens software for programming and configuring PROFIBUS Siemens control
systems
SW Software
TCI Tool Calling Interface
9 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
1 About this documentation
1.4 Notes used
________________________________________________________________
The following signal words and symbols are used in this documentation to indicate dangers and
important information:
Safety instructions
Structure of the safety instructions:
Danger!
(characterises the type and severity of danger)
Note
(describes the danger and informs how to prevent dangerous situations)
Application notes
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 10
2 Safety instructions
2.1 General safety and application instructions
________________________________________________________________
2 Safety instructions
Note!
Always observe the specified safety measures to avoid severe injury to persons and
damage to property!
Always keep this documentation to hand in the vicinity of the product during operation.
Danger!
If you disregard the following basic safety measures, this can cause severe injury to
persons and damage to material assets.
11 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
2 Safety instructions
2.2 Device- and application-specific safety instructions
________________________________________________________________
• During operation, the communication module must be firmly connected to the standard device.
• Only use cables corresponding to the given specifications.
Bus cable specification ( 28)
Protection of persons
If the Inverter Drives 8400 are used on a phase earthed mains with a rated mains voltage ≥ 400 V,
protection against accidental contact is not ensured without implementing external measures.
Protective insulation ( 16)
Device protection
The communication module contains electronic components which may be damaged or destroyed
by electrostatic discharge.
Installation ( 21)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 12
3 Product description
3.1 Application as directed
________________________________________________________________
3 Product description
3.2 Identification
The type designation as well as the hardware and software version of the communication module
are indicated on the nameplate:
HW: SW:
1 Type designation (type)
E84 Product series
A Version
8400 Y Module identification: extension module
C Module type: communication module
Type:
HW: SW: PM PROFIBUS
V/S V: coated version
Ser.No.:
S: standard version
2 Hardware version (HW)
3 Software version (SW)
E84YCPM001E
13 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
3 Product description
3.3 Features
________________________________________________________________
3.3 Features
• Interface module for the PROFIBUS communication system for connection to the expansion
slots of the Inverter Drives 8400
• Support of parameter data channels DRIVECOM (DP-V0) and PROFIDrive (DP-V1)
• A maximum of 16 process data words per direction can be exchanged.
• The communication module is supplied with voltage via the standard device.
• Bus coupling via remote bus according to the RS485 standard
• Automatic detection of the baud rate (9.6 kbps to 12 Mbps)
• Setting of the station address is possible via DIP switch or code.
• Access to all Lenze parameters
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 14
4 Technical data
4.1 General data and operating conditions
________________________________________________________________
4 Technical data
Area Values
Order designation • E84AYCPMV (coated version)
• E84AYCPMS (standard version)
Communication profile • PROFIBUS DP-V0 (DRIVECOM)
• PROFIBUS DP-V1 (PROFIdrive)
Communication medium RS485
Interface 9-pin Sub-D socket
Network topology • Line (without repeater)
• Tree/line (with repeater)
Bus device type PROFIBUS slave
Number of slaves • Max. 31 (without repeater)
• Max. 125 (with repeater)
Max. cable length 1200 m (depending on the selected baud rate and the cable type used)
PNO identification number 0x0A89
Baud rate for cable type A (EN 50170) 9.6 kbps ... 12 Mbps (automatic detection)
Conformities, approvals • CE
• UL
15 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
4 Technical data
4.2 Protective insulation
________________________________________________________________
Danger!
Dangerous voltage
If the Inverter Drives 8400 are used on a phase earthed mains with a rated mains voltage
≥ 400 V, protection against accidental contact is not ensured without implementing
external measures.
Possible consequences:
Death or severe injury
Protective measures:
If protection against accidental contact is required for the control terminals of the
inverter and the terminals of the plugged-in device modules, ...
• a double isolating distance must be provided.
• the components to be connected must be provided with a second isolating distance.
Note!
The existing protective insulation in the Inverter Drives 8400 is implemented according
to EN 61800-5-1.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 16
4 Technical data
4.2 Protective insulation
________________________________________________________________
Bus Ext. DC
Reinforced insulation
X101
X106
Basic insulation
X100
Functional insulation
MCI
X6
X3 MMI
X4 X5
X105
X106 X1
E84YCXX007
17 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
4 Technical data
4.2 Protective insulation
________________________________________________________________
Example
Which type of protective insulation is used between the bus terminal of the device module in the
MCI slot and the mains terminal X100?
The separate potential area with the better protective insulation is decisive.
• The separate potential area of the device module's bus terminal is "functionally insulated".
• The separate potential area of the mains terminal has a "reinforced insulation".
Result: The insulation between the mains terminal X100 and the bus terminal is of the "reinforced
insulation" type.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 18
4 Technical data
4.3 Protocol data
________________________________________________________________
Area Values
Process data words (PCD) 1 ... 16 words (16 bits/word)
Cyclic parameter data channel (DP- 4 words
V0)
Acyclic parameter data channel (DP- Max. 240 bytes
V1)
PROFIBUS user data length 1 ... 16 words process data channel + 4 words parameter data channel
The communication time is the time between the start of a request and the arrival of the
corresponding response.
The communication times in a PROFIBUS network depend on ...
• the processing time in the inverter;
• the transmission delay time (baud rate / telegram length);
• the nesting depth of the network.
19 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
4 Technical data
4.5 Dimensions
________________________________________________________________
4.5 Dimensions
E84YCPM001B
[4-2] Dimensions
Dimensions in mm
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 20
5 Installation
________________________________________________________________
5 Installation
Stop!
Electrostatic discharge
Electronic components within the communication module can be damaged or destroyed
by electrostatic discharge.
Possible consequences:
• The communication module is defective.
• Communication via the fieldbus is not possible or faulty.
Protective measures
Discharge electrostatic charges before touching the module.
21 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
5 Installation
5.1 Mechanical installation
________________________________________________________________
The communication module can be plugged into the MCI slot or unplugged while the inverter is
switched on. When the module is plugged in, it is detected automatically, and a plausibility check
regarding the function and version is carried out.
E84YCPM002D
Mounting steps
1. Pry the cover out of the MCI slot using a screwdriver and remove it (1, 2).
2. Loosen the securing screw for the communication module on the standard device (3).
3. Insert the communication module into the MCI slot of the standard device (4).
4. Fasten the securing screw (5).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 22
5 Installation
5.1 Mechanical installation
________________________________________________________________
E84YCPM002A
Mounting steps
1. Slightly press on the area indicated in the illustration at the top of the cover for the standard
device's MCI slot (1).
2. Tilt the cover forward and remove it from the standard device (2).
3. Loosen the securing screw for the communication module on the standard device (3).
4. Insert the communication module into the MCI slot of the standard device (4).
5. Fasten the securing screw (5).
23 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
5 Installation
5.1 Mechanical installation
________________________________________________________________
E84YCPM002B
Mounting steps
1. Loosen the securing screw for the communication module on the standard device (1).
2. Remove the communication module from the MCI slot of the standard device (2).
3. Insert the new communication module into the MCI slot of the standard device (3).
4. Fasten the securing screw (4).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 24
5 Installation
5.2 Electrical installation
________________________________________________________________
M
Z
S S S
1
E94YCPM012a
An RS485 network consisting of several segments contains repeaters (R) for coupling the segments.
The repeaters are provided with integrated bus terminating resistors.
M
Z Z Z Z Z
R R
Z
S S S S S
1 2 3
E94YCPM012b
If no repeater is to be used at the end of the segment, the bus terminating resistor must be activated
in the connector of the last device. The bus termination is supplied by the station itself.
Stop!
The bus terminator must always be supplied. Otherwise, the bus can get unstable.
25 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
5 Installation
5.2 Electrical installation
________________________________________________________________
Number of stations
M
R R
S S S S S
1 2 3
2133PFB004
Tip!
Repeaters do not have a station address. When calculating the maximum number of
stations, they reduce the number of stations by 1 on each side of the segment.
Repeaters can be used to build up line and tree topologies. The maximum total bus system
expansion depends on ...
• the baud rate used;
• the number of repeaters used.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 26
5 Installation
5.3 Activating the bus terminating resistor
________________________________________________________________
The PROFIBUS must be terminated by a bus terminating resistor at the first and last physical bus
station.
The bus terminating resistor in the bus connector of the bus cable is activated by means of a switch.
PROFIBUS cables with integrated bus terminating resistor are offered by several cable
manufacturers.
Note!
If you want to disconnect individual bus stations, ensure that the bus terminators at the
cable ends remain active.
Please observe that the bus termination is not active any longer if ...
• the bus connector has been disconnected;
• the voltage supply of the Inverter Drive 8400 has been switched off.
27 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
5 Installation
5.3 Activating the bus terminating resistor
________________________________________________________________
Note!
Only use cables which meet the listed specifications of the PROFIBUS user organisation.
Area Values
Cable resistance 135 ... 165 Ω/km, (f = 3 ... 20 MHz)
Capacitance per unit length ≤ 30 nF/km
Loop resistance < 110 Ω/km
Core diameter > 0.64 mm
Core cross-section > 0.34 mm2
Cores Twisted in pairs, insulated and shielded
Note!
The baud rate depending of the data volume, cycle time and number of stations should
only be selected as high as required for the application.
Tip!
We recommend taking the use of optical fibres into consideration for high baud rates.
Advantages of optical fibres:
• External electromagnetic interferences have no effect on the transmission path.
• Bus lengths of several kilometres are also possible with higher baud rates.
• The bus length is ...
• independent of the baud rate;
• dependent on the optical fibre used.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 28
5 Installation
5.3 Activating the bus terminating resistor
________________________________________________________________
The 9-pole Sub-D socket X201 serves to connect the communication module to the bus system.
29 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
6 Commissioning
6.1 Before initial switch-on
________________________________________________________________
6 Commissioning
During commissioning, plant-specific data such as motor parameters, operating parameters,
responses, and parameters for fieldbus communication are defined for the inverter. Lenze devices
use codes for this purpose.
The codes of the inverter and for communication are saved to the memory module in a non-volatile
data set.
In addition, there are codes for diagnosing and monitoring the stations.
Parameter reference ( 95)
Stop!
Before switching on the inverter for the first time, check ...
• the entire wiring for completeness, short circuit and earth fault.
• whether the bus system is terminated by means of a bus terminating resistor at the
first and last physical bus station.
Activating the bus terminating resistor ( 27)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 30
6 Commissioning
6.2 Configuration of the controller (master)
________________________________________________________________
The controller (master) must be configured before communication with the communication
module is possible.
Configuration for the controller (master) and the DP-V0 parameter data channel
For configuring the PROFIBUS you must read the device description file of the communication
module into the master.
The device description file for the E84AYCPM communication module (PROFIBUS) can be found in
the Download area at:
www.Lenze.com
The following language variants of the device description file can be used:
• LENZ0A89.GSD (source file, English)
• LENZ0A89.GSG (German)
• LENZ0A89.GSE (English)
Tip!
A detailed description of consistency is given in the chapter "Consistent parameter data"
( 80).
31 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
6 Commissioning
6.3 Setting the station address
________________________________________________________________
The station address can be set via DIP switches 1 ... 64 or via the
»Engineer« (code C13899).
The unlabelled DIP switch (topmost position) does not have any
function.
Lenze setting: all switches in OFF position
E84YCPM001G
The station addresses must differ from each other if several networked PROFIBUS stations are used.
The station address can be set via DIP switches 1 ... 64 or via the »Engineer« (code C13899).
The housing labelling indicates the valencies of the individual DIP switches for setting the station
address.
DIP switch 64 32 16 8 4 2 1
Switch position OFF OFF ON OFF ON ON ON
Value 0 0 16 0 4 2 1
Station address = sum of the valencies = 16 + 4 + 2 + 1 = 23
DIP switch positions for setting the station address ( 107)
Note!
Switch off the voltage supply of the communication module and then on again in order
to activate changed settings.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 32
6 Commissioning
6.3 Setting the station address
________________________________________________________________
Impermissible addresses are displayed in red in the Station address (code C13899).
Save the changed settings with device command C00002/11 (save all parameter sets).
33 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
6 Commissioning
6.4 Initial switch-on
________________________________________________________________
Note!
Establishing communication
In order to establish communication via an externally supplied communication module,
the standard device must be switched on as well.
After communication has been established, the externally supplied module operates
independently of the power on/off state of the standard device.
Protection against uncontrolled restart
After a fault (e.g. short-time mains failure), the restart of a drive is not always wanted
and - in some cases - even not allowed.
In the Lenze setting of the Inverter Drives 8400, the restart protection is activated.
The restart behaviour of the inverter can be set via C00142 ("Autostart Option"):
C00142 = 9 (Lenze setting)
• The inverter remains inhibited (even if the fault is no longer active).
• Bit 0 (inhibited at power-on) and bit 3 (inhibited at undervoltage) are set.
• The drive starts in a controlled mode by explicitly enabling the inverter: LOW-HIGH
edge at digital input X4/RFR.
C00142 = 8 (enabled)
• To enable the device directly at power-on, bit 0 must be set to zero (FALSE).
• An uncontrolled restart of the drive is possible.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 34
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
Via Tool Calling Interfaces (TCI) you can connect to a TCI-capable integrated development
environment and parameterise and diagnose your field devices without having to exit the
integrated development environment.
You cannot set the TCI communication path directly in the »Engineer«. The selection is carried out
by the »STEP7« Siemens software.
The TCI function requires a PN/DP-CPU. Information on the Siemens PLC types that are equipped
with the TCI function is provided via the Siemens Support at:
http://support.automation.siemens.com
35 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
Here a Servo Drive 9400 (address 3) and an Inverter Drive 8400 (address 4) are operated on
the PROFIBUS.
• The names of the PROFIBUS slaves in the »HW Konfig« must be identical to those of the
corresponding Lenze axes in the »Engineer« (here "9400" and "8400").
• The selection of the process data configuration has no impact on TCI communication.
3. Establish an Ethernet connection to the PROFIBUS CPU.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 36
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
37 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
8. Select the Ethernet connection which you are using to go online with »STEP7« (the same
Ethernet connection that has been configured in the »HW Konfig«).
In our case this is the Ethernet(1) connection:
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 38
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
10. Select the actual PG/PC connection under the Assignment tab.
39 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
12. After the assignment, the connection appears in the "Assigned" display area. Close the
dialog with OK.
13. In the »STEP7« project, the PG/PC station is marked with a yellow arrow. (The connection
selected is active.)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 40
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
14. Start the transfer of the TCI communication parameters in the »HW Konfig« using the right
mouse button and the menu command Start Device Tool L-force Engineer.
15. If the »Engineer« has already been started with the applicable project, the following
message will appear:
• The message says that the »Engineer« project is not set to a TCI communication path and
provides information about whether this action is to be executed now.
• If you confirm the message with Yes, the applicable TCI communication parameter
settings of the »STEP7« project are transferred to the »Engineer«.
41 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
If the »Engineer« has not already been started, it is started automatically now and you have
to open the applicable project.
If the project selected has not been set to a TCI communication path yet, this can now be
executed by clicking Yes:
16. The transfer of the TCI communication parameters is documented in the »Engineer«
message window.
Here the communication settings have been carried out successfully. The individual
PROFIBUS addresses in the respective codes have been adapted to the »STEP7« project.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 42
6 Commissioning
6.5 Going online with »Engineer« via TCI
________________________________________________________________
17. If you now call the "Go online" function of the »Engineer«, the TCI communication settings
are displayed as follows:
43 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
7 Data transfer
________________________________________________________________
7 Data transfer
The PROFIBUS master and inverter communicate through the exchange of data telegrams via
PROFIBUS. The user data area of the data telegram contains parameter data or process data. In the
inverter, different communication channels are assigned to the parameter data and process data.
Communication channels
The process data channel serves to transfer process data.
• The process data serve to control the inverter.
• The controller (master) can directly access the process data. In the PLC, for instance, the data are
directly saved to the I/O area.
• Process data are not saved in the inverter.
• Process data are transferred cyclically between the controller and the inverters (permanent
exchange of current input / output data).
• Process data are, for instance, setpoints, actual values, control words and status words.
• The Inverter Drives 8400 can exchange a maximum of 16 process data word (16 bits/word) per
direction.
Note!
Observe the direction of the information flow!
• Process input data (Rx data):
• Process data from the inverter (slave) to the master
• Process output data (Tx data):
• Process data from the master to the inverter (slave)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 44
8 Process data transfer
8.1 Access to process data / PDO mapping
________________________________________________________________
Note!
PDO mapping and the objects required for this purpose are not supported in the
software version 01.00 of the E84AYCPM communication module.
The process data (MCI-PDOs) are transferred via the MCI interface.
• A maximum of 16 words for each direction is exchanged.
• The process data are accessed via the LP_MciIn and LP_MciOut port blocks. These port blocks are
also referred to as process data channels.
• The port/function block interconnection of the process data objects (PDO) takes place via the
Lenze »Engineer«.
)LHOGEXV
&RPPXQLFDWLRQPRGXOH
0&,LQWHUIDFH
E&WUOB% E6WDWHB%
Z&WUO Z6WDWH
E,QB%
$SSOLFDWLRQ E2XWB%
)%LQWHUFRQQHFWLRQ
Z,Q Z2XW
Z,Q Z2XW
GQ,QBS GQ2XWBS
[8-1] External and internal data transfer between the bus system, inverter, and function block interconnection
45 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
8 Process data transfer
8.2 Preconfigured port interconnection of the process data objects (PDO)
________________________________________________________________
The preconfigured port interconnection of the process data objects is activated by setting standard
device code C00007 = "40: MCI".
It is possible to display the port blocks "LP_MciIn" and "LP_MciOut" as well as the preconfigured
interconnections in the »FB Editor« :
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 46
8 Process data transfer
8.3 Free configuration of the port interconnection of process data objects (PDO)
________________________________________________________________
8.3 Free configuration of the port interconnection of process data objects (PDO)
2. Go to the Ports tab and select the port block "MCI_IN" or "MCI_OUT" via mouse-click.
Activate it by clicking Activate.
47 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
8 Process data transfer
8.3 Free configuration of the port interconnection of process data objects (PDO)
________________________________________________________________
4. Via the button, you can assign signals to the process data words in the Assignment
Signal --> Function Block dialog box.
Select the signals and then confirm the selection with OK.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 48
8 Process data transfer
8.3 Free configuration of the port interconnection of process data objects (PDO)
________________________________________________________________
For the process data words WORD_1 and WORD_2, you can also assign signals to the
individual control bits and status bits via the and buttons.
Select the signals and then confirm the selection with OK.
49 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
8 Process data transfer
8.3 Free configuration of the port interconnection of process data objects (PDO)
________________________________________________________________
Tip!
If the port blocks "LP_MciIn" and "LP_MciOut" are activated (see step 1), they are displayed
in the »FB Editor«. Here you can also assign signals to the process data words.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 50
9 Parameter data transfer
9.1 Addressing of the parameter data
________________________________________________________________
The parameter data are addressed via codes which can be found in this documentation and in the
corresponding documentation of your inverter.
Parameter reference ( 95)
51 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 52
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
7 6 5 4 3 2 1 0
Bit 3
Reserved
Bit 6: Handshake
Indicates a new request.
• The state of this (toggle) bit is changed by the master for every new request.
• The inverter copies the bit into its response telegram.
Bit 7: Status
Status information from the inverter to the master when sending the request confirmation.
This status bit informs the master whether the request has been carried out without errors.
0 Request completed without errors.
1 Request not completed because of an error.
• The set status bit indicates that the telegram is an "error telegram". The data of bytes 5 ... 8 (data/
error) must be interpreted as an error message.
Error codes ( 58)
53 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
General procedure:
1. Define the user data area of the inverter, i.e. define the location of the DP user data in the
controller (observe manufacturer-specific information).
2. Enter the address of the required parameter in the "Index" and "Subindex" fields (DP output
data).
3. Request in the service byte = read request.
The handshake bit in the service byte must be changed (DP output data).
4. Check whether the handshake bit in the service byte is the same for the DP input data and the
DP output data.
• If the handshake bit is the same, the response has been received.
• It is useful to implement a time monitoring tool.
5. Check whether the status bit in the service byte is set:
• Status bit is not set: The "Data/Error" field contains the required Parameter value (data)
( 57).
• Status bit is set: The read request has not been executed correctly. The "Data/Error" field
contains the Error codes ( 58).
General procedure:
1. Define the user data area of the inverter, i.e. define the location of the DP user data in the
controller (observe manufacturer-specific information).
2. Enter the address of the required parameter in the "Index" and "Subindex" fields (DP output
data).
3. Enter the parameter value in the "Data/Error" field.
4. Request in the service byte = write request.
The handshake bit in the service byte must be changed (DP output data).
5. Check whether the handshake bit in the service byte is the same for the DP input data and the
DP output data.
• If the handshake bit is the same, the response has been received.
• It is useful to implement a time monitoring tool.
6. Check whether the status bit in the service byte is set:
• Status bit is not set: The write request has been executed correctly.
• Status bit is set: The write request has not been executed correctly. The "Data/Error" field
contains the Error codes ( 58).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 54
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
1t110000 SIDX IDXH IDXL Error Class Error code Additional Additional
Code High Code Low
1txx0100 0 0 0 0 0 0 0
1t110000 0 0 0 0 0 0 0
55 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
Additional addressing via the subindex is required for those codes of the Inverter Drives 8400 that
contain a subcode (see code table).
The parameter (Lenze code) is selected via these two bytes according to the formula:
• Index = 24575 - Lenze code number
(Also see "Addressing of Lenze parameters" ( 51))
Example:
The parameter C00105 (quick stop (QSP) deceleration time) is to be addressed:
• Index = 24575 - 105 = 24470 = 0x5F96
• The entries in bytes 3 + 4 for this example would be:
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 56
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
The state of status bit 7 in the service byte determines the meaning of this data field:
Note!
Strings or data blocks cannot be transmitted.
Depending on the data format, the length of the parameter value is between 1 and 4 bytes.
Data are saved in the Motorola format, i.e. first the high byte (high word), then the low byte (low
word):
Principle for the assignment of bytes 5 ... 8 with parameter values of different lengths:
57 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 58
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
Byte 2: Subindex
Subindex = 0 because code C00061 does not contain any subindices.
Bytes 3 + 4: Index
Index = 24575 - code number = 24575 - 61 = 24514 = 0x5FC2
• Byte 3 (high byte) = 0x5F
• Byte 4 (low byte) = 0xC2
Result:
Request telegram from master to drive:
59 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
________________________________________________________________
9.2.7.2 Write request: Setting the deceleration time for quick stop (QSP)
In the inverter, the deceleration time for quick stop (QSP) is to be set to 50 ms.
• Code to be written: C00105
Byte 2: Subindex
Subindex = 0 because code C00105 does not contain any subindices.
Bytes 3 + 4: Index
Index = 24575 - code number = 24575 - 105 = 24470 = 0x5F96
• Byte 3 (high byte) = 0x5F
• Byte 4 (low byte) = 0x96
Result:
Request telegram from master to drive:
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 60
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Data communication with PROFIBUS-DP-V0 is characterised by cyclic diagnostics and cyclic process
data and parameter data transfer.
An optional service expansion is the acyclic parameter data transfer of PROFIBUS-DP-V1. This
service does not impair the functionality of the standard services under PROFIBUS-DP-V0.
PROFIBUS-DP-V0 and PROFIBUS-DP-V1 can be operated simultaneously in the same network. This
enables the step-by-step expansion or retrofitting of a system.
The services of PROFIBUS-DP-V1 can be used by the class 1 master (PLC) and the class 2 master
(diagnostics master, etc.).
The integration of the acyclic service into the fixed bus cycle depends on the corresponding
configuration of the class 1 master:
• With configuration, a time slot is reserved.
• Without configuration the acyclic service is appended when a class 2 master acyclically accesses
a DP-V1 slave.
Features
• Parameter number and subindex addresses with a width of 16 bits each.
• Several parameter requests can be combined to one request (multi-parameter request).
• There is always only one parameter request in process (no pipelining).
• A parameter request/response must fit into a data block (max. 240 bytes). Requests/responses
cannot be split into several data blocks.
• No spontaneous messages are transferred.
• There are only acyclic parameter requests.
• Profile-specific parameters can be read independently of the slave state.
61 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
A class 1 master can always request parameters from a slave if the slave is in the "Data_Exchange"
state.
In addition to the class 1 master, a class 2 master can establish a communication connection to the
slave:
DPV1- Master
parameter data channel class 1
Read
Slave
Write
Master
class 2
E94YCPM010
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 62
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Note!
A parameter request refers to one or several parameter(s) (multi-parameter request).
Write.res
without data
Read.req
without data
Parameter
Read.res (-) processing
without data
Read.req
without data
E94YCPM011
Explanation
• A "Write.req" is used to pass the data set (DB47) to the slave in the form of a parameter request.
• With "Write.res" the master receives the confirmation for the receipt of the message.
• The master requests the response of the slave with "Read.req".
• The slave responds with "Read.res (-)" if processing has not yet been completed.
• After parameter processing, the parameter request is completed by transmitting the parameter
response to the master with "Read.res (+)".
63 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
E82ZAFP015
The data unit (DU) contains the DP-V1 header and the parameter request or the parameter
response.
The following subchapters describe the parameter request and the parameter response in detail.
Note!
The DP-V1 header consists of:
• Function identification
• Slot number
• Data set
• Length of the user data
Please refer to the corresponding PROFIBUS specification for further information on the
DP-V1 header.
U8 1 byte 0x00
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 64
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Note!
• When a read request is processed, no parameter value is written to the slave.
• In the case of a multi-parameter read request, the parameter attribute, index, and
subindex are repeated with the number "n" of the requested parameters.
• A read request must not exceed the maximum data length of 240 bytes.
Request header
Parameter attribute
Byte 5 Byte 6
Attribute Number of subindices
65 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Note!
Responses to a read request do not contain parameter attributes, indices and subindices.
Response header
Parameter format
Byte 5 Byte 6
Format Number of values
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 66
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Parameter value
67 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Note!
In the case of a multi-parameter request, correct and possible faulty messages are
summarised in one telegram. They have the following data contents:
Correct message
• Format: data type of the value requested
• Number of values: as described in the chapter "Reading parameter data from the
inverter" ( 65).
• Parameter value: value requested
Faulty message
• Format: 0x44
• Number of values: 0x01 or 0x02
• Error code without additional information (for number of values = 0x01) or
• Error code with additional information (for number of values = 0x02)
A faulty access to a parameter "n" is indicated at the nth position in the response
telegram of a multi-parameter request.
Response header
Parameter format
Byte 5 Byte 6
Format Number of values
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 68
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Error code
69 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Note!
When a multi-parameter write request is transferred, the ...
• Parameter attribute
• Index and subindex
and then the ...
• Parameter format
• Parameter value
... are repeated with the number "n" of the parameters addressed.
A write request must not exceed the maximum data length of 240 bytes.
Request header
Parameter attribute
Byte 5 Byte 6
Attribute Number of subindices
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 70
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Parameter format
Byte 11 Byte 12
Format Number of values
Parameter value
71 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Note!
In the case of a multi-parameter request, correct and possible faulty messages are
summarised in one telegram. They have the following data contents:
Correct message
• Format: 0x40
• Number of values: 0x00
Faulty message
• Format: 0x44
• Number of values: 0x01 or 0x02
• Error code without additional information (for number of values = 0x01) or with
additional information (for number of values = 0x02)
A faulty access to a parameter "n" is indicated at the nth position in the response
telegram of a multi-parameter request.
Response header
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 72
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Response header
Parameter format
Byte 5 Byte 6
Format Number of values
Error code
73 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 74
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
75 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Parameter request
Byte 5 Byte 6
Attribute Number of subindices
0x10 0x00
Value No subindex
Byte 5 Byte 6
Format Number of values
0x03 0x01
Integer16 1 value
Byte 7 Byte 8
Value
High byte Low byte
0x00 0x2B
Value read = 0x 00 2B = 43 x 1 (internal factor) = 43 [°C]
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 76
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Byte 5 Byte 6
Format Number of values
0x44 0x01
Error Error code without
additional information
Byte 7 Byte 8
Error code
High byte Low byte
77 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
9.3.5.2 Write request: Setting the deceleration time for quick stop (QSP)
In the inverter, the deceleration time for quick stop (QSP) is to be set to 50 ms.
Code to be written: C00105
Parameter request
Byte 5 Byte 6
Attribute Number of subindices
0x10 0x00
Value No subindex
Byte 11 Byte 12
Format Number of values
0x43 0x01
Double word 1 value
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 78
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
________________________________________________________________
Byte 5 Byte 6
Format Number of values
0x44 0x01
Error Error code without
additional information
Byte 7 Byte 8
Error code
High byte Low byte
79 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
9 Parameter data transfer
9.4 Consistent parameter data
________________________________________________________________
In the PROFIBUS communication system, data are permanently exchanged between the control
system (CPU + PROFIBUS master) and the inverter via the plugged-on slave interface module. Both
the PROFIBUS master and the CPU (central processing unit) of the control system access a joint
memory: the dual port memory (DPM).
The DPM permits a data exchange in both directions (write/read):
It could happen that a slower PROFIBUS master writing would be overtaken by a faster CPU reading
within a cycle time without any further data organisation.
In order to avoid such an impermissible state, the parameter data to be transmitted must be marked
as "consistent".
1. As the master can only write if the CPU does not read, the master waits until the data are read
completely by the CPU.
2. The master only writes a complete data set into DPM.
Note!
Consistency is achieved by an appropriate PROFIBUS master configuration.
For this purpose, refer to the documentation for your configuring software.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 80
10 Monitoring
10.1 Permanent interruption of PROFIBUS communication
________________________________________________________________
10 Monitoring
81 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
10 Monitoring
10.2 Short-time interruption of PROFIBUS communication
________________________________________________________________
POWER ON
Set_Slave_Add Slave_Diag
Slave_Diag WAIT_PRM Get_Cfg
Slave_Diag
WAIT_CFG Set_Prm
Get_Cfg
Chk_Cfg, o.k.
Chk_Cfg, not o.k.
Set_Prm, not o.k. DATA_EXCH
2133PFB006
The master detects the communication fault and, only after a few microseconds, transfers the slave
to the "WAIT_PRM" status of the DP state machine (see fig. [10-1]).
Only after the state chain of the DP state machine ending in the "Data_Exchange" state
(DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the slave (in
milliseconds) continues to run.
Note!
The watchdog monitoring time does not continue running if the slave does not reach the
"Data_Exchange" state due to repeated communication errors (e.g. caused by loose
contact).
Note!
Observe the following condition for the time setting:
Monitoring time for the data exchange (C13881) ≤ watchdog monitoring time of the
PROFIBUS (C13882/1).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 82
10 Monitoring
10.3 Settings and displays in the »Engineer«
________________________________________________________________
On the Monitoring tab of the »Engineer«, you can set or display the following parameters:
Parameter Description
Reaction on communication The response set here takes place if the PROFIBUS station ...
fault • does not receive a message from the master within the watchdog
(C13880/1) monitoring time (displayed in C13882/1) if there is an active connection;
• recognises that it is not in the "Data_Exchange" status anymore.
Please see also the information on .
Clear process data Selection of the process data which the inverter will process in the event of
(C13885) a PROFIBUS failure in order to maintain internal communication.
The process data sent last by the master can be used or the process data can
be set to zero.
Monitoring time: Data After the monitoring time set here has elapsed, the response set in takes
exchange place for the data exchange.
(C13881) • The value "65535" deactivates the monitoring function.
• The monitoring time set here must be smaller than the watchdog
monitoring time .
• A change in monitoring is effective immediately.
Permanent interruption of PROFIBUS communication ( 81)
Monitoring time: Watchdog Display of the watchdog monitoring time determined by the PROFIBUS
(C13882/1) master
• Monitoring starts with the receipt of the first telegram.
• When a value of "0" is displayed, the monitoring function is deactivated.
• A change in the watchdog monitoring time in the master is immediately
effective.
Permanent interruption of PROFIBUS communication ( 81)
Set ext. diagnostic bit upon Bit-coded selection of the error responses in the standard device causing the
(C13886) external diagnostic bit ("diag bit") to be set (see PROFIBUS specification; bit 3
of byte 1 of the DP diagnostic messages).
• The diagnostic bit is sent to the PROFIBUS master where it is evaluated
separately.
• The diagnostic bit is always set when a system error occurs.
• The Lenze setting "0" means that the diagnostic bit is not set for the
following error responses.
• An advanced diagnostic message is always sent.
83 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
11 Diagnostics
11.1 LED status displays
________________________________________________________________
11 Diagnostics
For diagnosing faults of the PROFIBUS module, the LEDs on the front panel are provided.
Furthermore you can query the current bus status via code C13861.
Note!
During normal operation, the LED BS ( 86) blinks and the LED MS ( 86) is lit
permanently.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 84
11 Diagnostics
11.1 LED status displays
________________________________________________________________
MS
ME
DE
E84YCPM006
The communication module is supplied with voltage, but has not yet
established a connection to the standard device. (Standard device is
switched off, initialising or not present.)
ME Red On
85 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
11 Diagnostics
11.1 LED status displays
________________________________________________________________
BS
BE
E84YCPM006
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 86
11 Diagnostics
11.2 Diagnosing with the »Engineer«
________________________________________________________________
In the »Engineer«, the Diagnostics tab displays various pieces of PROFIBUS diagnostic information.
87 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
11 Diagnostics
11.2 Diagnosing with the »Engineer«
________________________________________________________________
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 88
11 Diagnostics
11.3 Advanced diagnostic message
________________________________________________________________
Errors in the inverter and its plugged-in modules are transmitted to the PROFIBUS master in the
form of advanced diagnostic messages.
Byte Description
1 Bit 0: Station does not exist (set by the master).
Bit 1: Slave is not ready for data exchange.
Bit 2: Configuration data do not correspond.
Bit 3: Slave has extended diagnostic data.
Bit 4: Requested function is not supported by the slave.
Bit 5: Slave response is invalid (set by the master)
Bit 6: Incorrect parameter setting
Bit 7: Slave has been parameterised by another master (set by the master).
2 Bit 0: Slave must be parameterised again.
Bit 1: Static diagnostics
Bit 2: Permanently set to "1".
Bit 3: Watchdog active
Bit 4: Freeze command received.
Bit 5: Sync command received.
Bit 6: Reserved
Bit 7: Slave is deactivated (set by the master).
3 Bit 7: Diagnostics overflow - amount of diagnostic information present in the slave is too large to fit
into one telegram.
4 Bits 0 ... 7: Master address after parameterisation ("0xFF" without parameterisation)
5 Bits 0 ... 7: ID number (high byte)
6 Bits 0 ... 7: ID number (low byte)
7 Header
• The header contains the block length of the advanced diagnostics including the header byte.
• In this case, the value of the entry is "0x0A" (bytes 7 ... 16 = 10 bytes).
8 Status_Type
The value of this entry is fixed. For the following bit assignment it is "0x81":
• Bit 7 = 1: "status"
• Bit 0 = 1: "status message"
• Value of all other bits = 0
9 Slot_Number
The value of the slot number is "0x00".
10 Specifier
• An indicated error is entered in the specifier with the identification "0x1" (status coming).
• An eliminated error is entered in the specifier with the identification "0x02" (status going).
• If no errors are indicated, the entry in the specifier has the value "0x00" (no further
differentiation).
11 Reserved
12
13 ... 16 Error code of the Inverter Drive 8400
• Code C00165 can be used to read out the contents of the fault memory.
• Detailed information regarding the error codes of the Inverter Drive 8400 can be found in the
documentation of the inverter.
89 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
11 Diagnostics
11.3 Advanced diagnostic message
________________________________________________________________
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 90
12 Error messages
12.1 Short overview of the PROFIBUS error messages
________________________________________________________________
12 Error messages
This chapter supplements the error list contained in the software manual and in the »Engineer«
online help for Inverter Drives 8400 by the error messages of the communication module.
The following table lists all PROFIBUS error messages in numerical order of the error number.
Furthermore the preset error response and – if available – the parameters for setting the error
response are specified.
Tip!
When you click the cross-reference in the first column, you will see a detailed description
(causes and remedies) of this error message.
91 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
12 Error messages
12.2 Possible causes and remedies
________________________________________________________________
This chapter lists all PROFIBUS error messages in the numerical order of the error numbers. Possible
causes and remedies as well as responses to the error messages are described in detail.
Cause Remedy
• Network cable (plug) is defective. Check cables and terminals.
• Network cable is not connected to the PROFIBUS Connect network cable to the PROFIBUS terminal X201.
terminal X201.
• Voltage supply is interrupted.
Cause Remedy
Access to memory was not possible. Repeat the download of the application
(including module)
Cause Remedy
Parameter could not be read. Repeat the download of the application
(including module)
Cause Remedy
Parameter could not be written. Repeat the download of the application
(including module)
Cause Remedy
Module defective. If this occurs repeatedly, contact the Lenze service.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 92
12 Error messages
12.2 Possible causes and remedies
________________________________________________________________
Cause Remedy
Module defective. If this occurs repeatedly, contact the Lenze service.
Cause Remedy
Internal error. If this occurs repeatedly, contact the Lenze service.
Cause Remedy
The communication module carries out an automatic If this occurs repeatedly, contact the Lenze service.
software reset and reinitialises itself.
Cause Remedy
Module defective. If this occurs repeatedly, contact the Lenze service.
Cause Remedy
No active parameter set could be loaded. Repeat the download of the application
(including module)
Cause Remedy
Access to parameter set was not successful. Repeat the download of the application
(including module).
93 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
12 Error messages
12.2 Possible causes and remedies
________________________________________________________________
Cause Remedy
Permanent interruption of communication to the Check cables and terminals.
PROFIBUS master.
Also see the chapter "Permanent interruption of
PROFIBUS communication" ( 81).
Cause Remedy
Data exchange via PROFIBUS has been stopped. Check cables and terminals.
Also see the chapter "Permanent interruption of The slave must receive new parameterisation and
PROFIBUS communication" ( 81). configuration files from the master in order to be able to
exchange data again.
Cause Remedy
Permanent interruption of communication to C2- Check cables and terminals.
PROFIBUS master.
Also see the chapter "Permanent interruption of
PROFIBUS communication" ( 81).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 94
13 Parameter reference
13.1 Parameters of the communication module
________________________________________________________________
13 Parameter reference
This chapter supplements the parameter list and the table of attributes contained in the software
manual and in the »Engineer« online help for Inverter Drives 8400 by the parameters of the
E84AYCPM communication module (PROFIBUS).
This chapter lists the parameters of the E84AYCPM communication module (PROFIBUS) in
numerically ascending order.
C13850
Display of the process data words transferred from the communication module to the PROFIBUS master.
In subcodes 1 ... 16, all process data words to the master are displayed. Only the process data words configured are
valid.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13850/1
...
C13850/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13851
Display of the process data words transferred from the PROFIBUS master to the communication module.
In subcodes 1 ... 16, all process data words to the master are displayed. Only the process data words configured are
valid.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13851/1
...
C13851/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
95 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
13 Parameter reference
13.1 Parameters of the communication module
________________________________________________________________
C13852
Display of process data words 1 ... 16 which are transferred from the communication module to the standard device.
In subcodes 1 ... 16, all process data words from the communication module are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13852/1
...
C13852/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13853
Display of process data words 1 ... 16 which are transferred from the standard device to the communication module.
In subcodes 1 ... 16, all process data words from the standard device are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13853/1
...
C13853/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13860
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 96
13 Parameter reference
13.1 Parameters of the communication module
________________________________________________________________
C13861
C13862
When the maximum count value of 65535 is reached, the counter starts again with 0.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13862/1 Data cycles per second
C13862/2 Total data cycles
C13862/3 Total parameterisation events
C13862/4 Total configuration events
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13863
97 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
13 Parameter reference
13.1 Parameters of the communication module
________________________________________________________________
C13864
C13865
Display of the last parameter data sent by the PROFIBUS master with the "Set-Prm" telegram (ASCII string with 24
characters)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13866
Display of the last configuration data sent by the PROFIBUS master with the "Chk-Cfg" telegram (ASCII string with
22 characters)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13867
Display of the last diagnostic data sent to the PROFIBUS master (ASCII string with 16 characters)
Advanced diagnostic message ( 89)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 98
13 Parameter reference
13.1 Parameters of the communication module
________________________________________________________________
C13880
C13881
If the "Data Exchange" state is exited, the response parameterised under C13880/1 is carried out when the
monitoring time for data exchange set here has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change in monitoring is effective immediately.
• The value set here for the monitoring time must be smaller than the watchdog monitoring time (C13882/1).
Permanent interruption of PROFIBUS communication ( 81)
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 65535 ms
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
99 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
13 Parameter reference
13.1 Parameters of the communication module
________________________________________________________________
C13882
C13885
Selection of the process data which the inverter will process in the event of a PROFIBUS failure in order to maintain
internal communication.
Selection list (Lenze setting printed in bold)
0 Use of most recent master PDOs
1 PDOs are set to the value '0'
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13886
Bit-coded selection of the error responses in the standard device causing the external diagnostic bit ("diag bit") to
be set (see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).
• The diagnostic bit is sent to the PROFIBUS master where it is evaluated separately.
• The diagnostic bit is always set when a system error occurs.
• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.
• An advanced diagnostic message is always sent.
Value is bit-coded:
Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 100
13 Parameter reference
13.1 Parameters of the communication module
________________________________________________________________
C13887
Selection of the error responses not causing a diagnostic request to the PROFIBUS master.
The Lenze setting "0" means that for each of the following error responses a diagnostic request is signalled.
Value is bit-coded:
Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13899
Optional setting of the station address (instead of setting via DIP switches 1 ... 64)
• The station address set here only becomes effective if the DIP switches 1 ... 64 have been set to OFF prior to mains
switching.
• The active station address is displayed under C13864.
Note: A change of the station address will not be effective until the " Save parameter set" device command has been
executed and another mains switching for the communication module/inverter has been performed.
Setting the station address ( 32)
Setting range (min. value | unit | max. value) Lenze setting
3 126 3
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX ; COM MOT
C13900
C13901
Display of the compilation date of the firmware (string with a length of 20 bytes)
The date ("MMM DD YYYY") and time ("hh:mm:ss") are displayed, e.g. "Mar 21 2005 12:31:21".
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
101 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
13 Parameter reference
13.1 Parameters of the communication module
________________________________________________________________
C13902
C13920
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 102
13 Parameter reference
13.2 Table of attributes
________________________________________________________________
The table of attributes contains information required for communication with the inverter via
parameters.
103 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
13 Parameter reference
13.2 Table of attributes
________________________________________________________________
Table of attributes
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 104
13 Parameter reference
13.3 Implemented PROFIdrive objects (DP-V1)
________________________________________________________________
I-918
I-963
I-964
105 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
13 Parameter reference
13.3 Implemented PROFIdrive objects (DP-V1)
________________________________________________________________
I-974
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 106
14 DIP switch positions for setting the station address
________________________________________________________________
107 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
14 DIP switch positions for setting the station address
________________________________________________________________
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 108
14 DIP switch positions for setting the station address
________________________________________________________________
109 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
14 DIP switch positions for setting the station address
________________________________________________________________
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 110
Index
________________________________________________________________
111 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Index
________________________________________________________________
E M
Electrical installation 25 Mechanical installation 22
E-mail to Lenze 114 Memory
Error: Lenze settings loaded (error message) 93 No access (error message) 92
Error codes (DP-V0) 58 Read error (error message) 92
Error codes (DP-V1) 74 Write error (error message) 92
Error messages 91 Module status displays 85
Causes and remedies 92 Monitoring 81
Short overview 91 Permanent interruption of PROFIBUS communication 81
Error number Settings and displays in the »Engineer« 83
0x01bc3100 92 Short-time interruption of PROFIBUS communication 82
0x01bc5531 92 Monitoring time
0x01bc5532 92 Data exchange (C13881) 99
0x01bc5533 92 Watchdog (C13882) 100
0x01bc6010 92 Mounting for 0.25 kW and 0.37 kW standard devices 22
0x01bc6011 93 Mounting for standard devices of 0.55 kW and more 23
0x01bc6100 93
0x01bc6101 93 N
0x01bc6110 93 Nameplate 13
0x01bc641f 93 Network topology 15, 25
0x01bc6420 93 Notes used 10
0x01bc8130 94
Number of stations 15, 26
0x01bc8131 94
0x01bc8132 94
O
Establishing communication 34
Operating conditions 15
F
P
Features 14
Parameter addressing 51
Feedback to Lenze 114
Parameter data transfer 51
Fieldbus status displays 86
Parameter reference 95
Firmware compilation date (C13901) 101
Parameters of the communication module 95
Firmware product type (C13900) 101
PDO mapping 45
Firmware version (C13902) 102
PNO identification number 15
Process data transfer 45
G
Processing time 19
General data 15
Product description 13
General safety and application instructions 11
Profibus: Data_Exchange state exited (error message) 94
Going online with »Engineer« via TCI 35
PROFIBUS connection 29
I PROFIBUS error messages
Causes and remedies 92
Identification 13
Short overview 91
Initial switch-on 34
Profibus watchdog
Installation 21
DP-V1 MSC2 monitoring time exceeded (error message) 94
Interface 15 Monitoring time elapsed (error message) 94
Interfaces 14 PROFIdrive 61
Internal error (error message) 93 PROFIdrive objects (DP-V1) 105
Invalid parameter record (error message) 93 PROFIdrive parameter data channel (DP-V1) 61
Protection against uncontrolled restart 34
L
Protection of persons 12
LED status displays 84
Protective insulation 16
Protocol data 19
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 112
Index
________________________________________________________________
Q
Querying the bus status 88
Querying the current bus status 88
R
Reaction on communication fault (C13880) 99
Reading parameter data from the inverter (DP-V0) 54
Reading parameter data from the inverter (DP-V1) 65
Replacing the communication module 24
Residual hazards 12
Restart after watchdog reset (error message) 92
S
Safety instructions 10, 11
Screenshots/application examples 6
Set ext. diagnostic bit upon (C13886) 100
Setting the station address 32
Settings (C13860) 96
Station address (C13899) 101
Status displays (LEDs) 84
Structure of the safety instructions 10
Suppress signalling diag. mess. upon (C13887) 101
System error messages 91
T
Table of attributes 103
Target group 6
TCI (Tool Calling Interfaces) 35
Technical data 15
Telegram examples (DP-V0) 59
Telegram examples (DP-V1) 76
Telegram structure (DP-V0) 52
Telegram structure (DP-V1) 64
Terminals 14
Terminology used 9
Terms 9
U
Use of repeaters 25
V
Validity of the documentation 6
W
Writing parameter data to the inverter (DP-V0) 54
Writing parameter data to the inverter (DP-V1) 70
X
XML file for configuration 31
113 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Your opinion is important to us
)(('%$&.
These instructions were created to the best of our knowledge and
belief to give you the best possible support for handling our product.
If you have suggestions for improvement, please e-mail us to:
feedback-docu@Lenze.de
114
E84AYCPM communication module (PROFIBUS®) · Communication Manual · EDS84AYCPM · 13422193 · DMS 5.0 EN · 11/2012 · TD17
Lenze Drives GmbH
Postfach 10 13 52
D-31763 Hameln
Germany
+49 (0)51 54 / 82-0
+49 (0)51 54 / 82-28 00
Lenze@Lenze.de
www.Lenze.com
Service
Lenze Service GmbH
Breslauer Straße 3
D-32699 Extertal
Germany
00 80 00 / 24 4 68 77 (24 h helpline)
+49 (0)51 54 / 82-11 12
Service@Lenze.de