Atys-C35 Socomec
Atys-C35 Socomec
Atys-C35 Socomec
ATS Controller
ATyS C35
www.socomec.com
To download, brochures,
catalogues and technical manuals.
CONTENTS
ANNEX I. .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Annex I - 1. HMI Reminder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Annex I - 2. LED Functioning modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Annex I - 3. Connection diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Annexe I - 3.1. Connections with ATyS S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Annexe I - 3.2. Connections with ATyS dM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Annexe I - 3.3. Connections with standard CC type based TSE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Annexe I - 3.4. Connections with standard CB type based TSE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Annex I - 4. Phase rotation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Annex I - 5. Voltage/Frequency Levels configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Annex I - 6. Timers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Annexe I - 6.1. Fail timers and Return timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Annexe I - 6.2. Cooldown and start gen delay timers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Annexe I - 6.3. Dead band timer ODT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Annexe I - 6.4. All timers’ chronograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Annex I - 7. Priority settings & Retransfer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Annex I - 8. Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Annex I - 9. C35 DPS Operating sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Annex I - 10. C35 standard operating sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
ANNEX II. M
ODBUS COMMUNICATION ADDRESS AND DESIGNATION DETAILS. . . . . . . . . . . . . . . . . . 48
Annex II - 1. Input / Output state. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Annex II - 2. Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Annex II - 3. Voltage sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Annex II - 4. Communication parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Annex II - 5. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Annex II - 6. Product configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
The information provided in this instruction manual is subject to change without notice, remains for general information only and
is non-contractual.
This version of instruction sheet is based on C35 products with firmware version 1.28.
This instruction manual includes details and instructions specific to the “ATyS C35” ATS controller only. For all other ATyS family
of products please refer to the specific instruction manual related to that product.
(Available for download on www.socomec.com)
125A - 3200A
40A - 160A
Back to Back
Configuration
ATyS g ATyS g M
ATyS C55 Simple Genset Simple Genset
Programmable
Management Management
ATyS t ATyS t M
ATyS C35 Transformer Transformer (building)
LCD screen
Management Management
ATyS d S ATyS d M
ATyS A15/C25 Small Genset RTSE (DPS)
DIP switch configuration
with DPS
ATyS S (RTSE) ATyS r ATyS
(1)
Side by Side Configuration
Small Gense RTSE RTSE
(1) Available in UL version - contact us.
password (1000 default). To stop the test, long press on this button again. S1-UVhy 99-81% 95% Under voltage hysteresis for return
96
51 Common point
S2-OFth 120-102% 115% Over Frequency threshold for loss
52 Closed to start the Genset (closed when AC1 – General use – Ie: 3A , Ue: 250 V.a.c of source 2 (must be greater than
controller is powered off) DC1 – General use – Ie: 3A , Ue: 30 V.d.c POS. I COUNT OUTPUTS INPUTS
II I 0 C Genset output AC15 - Ie 54/51: 3A 52/51: 1.5A Ue: 120 V.a.c hysteresis setting).
00016 16 POS I OFF 71 POS I OFF S2-OFhy 119-101% 110% Over frequency hysteresis for return of
Ctrl OFF II I 0 C AC15 - Ie 54/51: 1.5A 52/51: 0.75A Ue: 240 V.a.c
54 Open to start the genset DC13 - Ie 54/51: 0.22A 52/51: 0.22 A 125 V.d.c S1-S2 15 POS II ON 72 POS II ON source 2 (must be inferior to threshold
312 313 314 315 316 317 63A 64A 24 14 04 13 DC13 - Ie 54/51: 0.11A 52/51: 0.11 A 250 V.d.c 14 POS 0 OFF 73 POS 0 OFF setting).
Phase angle POS. II COUNT S2-UFth 98-90% 90% Under frequency threshold for loss of
91 Common point for programmable inputs 13 OFF 92 OFF source 2 (must be inferior to hysteresis
-10° 00010 52 OFF 93 OFF setting).
All fuses 4A type gG* Controller 92 Programmable input 1 (Set as default to
«NOT IN AUTO») Do not use external voltage 94 OFF S2-UFhy 99-91% 95% Under frequency hysteresis for return
programmable Power from common point
inputs of source 2 (must be greater than to
93 Programmable input 2 threshold setting).
94 Programmable input 3 Timers S1-FT 3-60s 5s Source 1 fail timer.
70 Common point for position inputs S2-FT 3-60s 5s Source 2 fail timer.
51 54 52 37 36 35 94 93 92 91 F2 F1 73 72 71 70
Return of S1-RT 3-3600s 5s Source 1 return timer.
71 Position I RTSE
5. QUICK START
EN
(2) % of Frequency set in “NOM FREQ”.
DC13 - le: 0.11A ,Ue: 250 V.d.c (3) Only configurable when “APP” is set to S1-Mains S2-Mains.
*Using a Socomec cable harness kit excludes the need for fuses (4) If voltage is set to 1PH+N the default value for NOM. VOLT. Will automatically be set to 230Vph-n.
8
6. GENERAL OVERVIEW
2 1 3 4 5 6
9
10
11
12
1 8
2 3 4 5 6 7
6.3.1. IP Rating
6.3.2. IK Rating
• IK8 (6.8J) rating according to IEC 61010-2-201
6.3.5. EMC
• Class A according to IEC / EN 60947-6-1 and GB/T 14048.11 (including annex C) standards
• Class A according to IEC / EN 61326-1
6.3.6. Altitude
• Up to 2000m
7. CONTENT OF PACKAGING
The C35 packaging includes:
• 1 C35 controller
• 1 C35 quickstart guide
• All connector
• Door mounting clips
All other products described in this instruction sheet are delivered and sold separately.
96
92
5
8.2. Mounting
138 (0/+
1)
144
92 (0/+0,8)
96
-3
1,5
106
To remove from the DIN Rail, drag the two mounting clips down before removing the product.
X2
DANGER ! When using the ATyS C35 without the Socomec Harness, gG 4A fuse protection is required on the
voltage sensing inputs cf connection diagrams.
When using the C35 with ATyS R and the Socomec harness gG fuses are not mandatory.
9.1. Networks
Source 1 Source 2
1 1
N N
Load
Source 1 Source 2
2 2
3 3
Load
3P Three
phase network without neutral 3P+N Three phase network with neutral
Source 1 Source 2
Source 1 Source 2
1 1
1 1
2 2
2 2
3 3
3 3
N N
Load
Load
1P +N:
The C35 is suitable for single phase networks, for with voltages within 184-300 V.a.c Ph-N. In these networks, the phase must
be connected to the L1 input (terminal 104 for source 1 and 204 for source 2).
2P:
When monitoring a 2PH network without neutral 90-520 VAC PH-PH, connect the two phases to L1 & L2, the controller must be
supplied with 184-300 VAC between the L1 and N connector (in order to achieve this users can use a transformer connected to
the two phases to create this voltage and connect the secondary to the neutral connector).
3P:
The C35 is suitable for three phase without neutral networks, for with voltages within 318-520 PH-PH. In these networks, the
controller must be supplied by 184-300 V.a.c using L1 and N (this can be achieved by using a transformer between L1 and
another phase and connecting the secondary to the neutral input 103 & 203).
3P+N:
The C35 is suitable for three phase with neutral networks, for with voltages within 184-300 V.a.c Ph-N and 318-
520 PH-PH. In these networks, the phase must be connected to the L1 input (terminal 104 for source 1 and 204 for source 2).
Network type
1P 2P 3P+ 3P+N
Source 1
1 phase 2 phase 3 phase 3 phase
Source 2 2 wire 2 wire 3 wire 4 wire
1 1 1
1
Source 1
N 3 N
2 2 3 2
1 1 1
1
Source 2
N 3 N
2 2 3 2
Voltage sensing
1
- U12 U12, U23, U31 U12, U23, U31
Source V1 - - V1, V2, V3
2
- U12 U12, U23, U31 U12, U23, U31
Source V1 - - V1, V2, V3
Source presence
(source available)
Source in ranges
(U, V, F)
Rotation phase - - -
order
CAUTION ! In 3 phase networks with neutral; in balanced networks; there is a risk that loss of neutral will not be
detected. To limit this risk the reduce the source 1 and source 2 overvoltage and undervoltage thresholds.
(Cf chapter "12. Programming", page 27).
CAUTION ! When using 3P network without neutral, the controller must be powered using 184-300 VAC between
L1 and N. User may use a transformer between two phases to create this voltage.
TOP
1 2 3 4 5
BOTTOM
7
6
9
8
L1 L1
L2 L2
1 L3 L3 2
N N
301 302
II I 0 C
Ctrl OFF II I 0 C
51 54 52 37 36 35 94 93 92 91 F2 F1 73 72 71 70
+ - NC + - 0 II I C
SOURCE 1 103 104 105 106 203 204 205 206 SOURCE 2
Aux supply II I 0 C
S1 IN 102 101 302 301 202 201 S2 IN 81 - + 82 13 14 15 16 17
DPS OUT
*Using a Socomec cable harness kit excludes the need for fuses
Tightening
Recommended torque
Denomination Terminal Description Characteristics / screw
Cable section type
13 Not used / OPEN S2
AC1 – General use – Ie: 5A , Ue: 250 V.a.c
Control signal 14 Position II order / CLOSE S2 DC1 – General use – Ie: 5A , Ue: 30 V.d.c
outputs (orders AC15 - Ie: 3A, Ue: 120 V.a.c
to RTSE) (PC / 15 Position I order / OPEN S1 AC15 - Ie: 1.5A, Ue: 240 V.a.c
CB type) 16 Position 0 order / CLOSE S1 DC13 - Ie: 0.22A, Ue: 125 V.d.c
DC13 - le: 0.11A, Ue: 250 V.d.c
17 Common point for position output
35 NC – Not connected
RS485 36 Negative electrode RS485 Isolated bus
1-2.5mm² 0.58 Nm / M3
37 Positive electrode
51 Common point
Closed to start the Genset (closed AC1 – General use – Ie: 3A , Ue: 250 V.a.c
52 when controller is powered off) DC1 – General use – Ie: 3A , Ue: 30 V.d.c
Genset output AC15 - Ie 54/51: 3A 52/51: 1.5A Ue: 120 V.a.c
AC15 - Ie 54/51: 1.5A 52/51: 0.75A Ue: 240 V.a.c
54 Open to start the genset DC13 - Ie 54/51: 0.22A 52/51: 0.22 A 125 V.d.c
DC13 - Ie 54/51: 0.11A 52/51: 0.11 A 250 V.d.c
91 Common point
Programmable input 1 (set to
Controller inhibit 92 Do not use external voltage - Power from
default as "NOT IN AUTO")
input common point
93 Programmable input 2
94 Programmable input 3
70 Common point for position inputs
Return of 0.5-1.5mm² 0.2 Nm/ M2
information from 71 Position I RTSE Do not use external voltage - Power from
RTSE (Position 72 Position II RTSE common point
inputs)
73 Position 0 RTSE
9
10
11
12
1 8
2 3 4 5 6 7
• Inhibit mode
In this mode both the Automatic transfer and manual orders will be blocked. This mode is activated when the programmable
inputs are programmed to “NOT IN AUTO” or “INHIBIT”.
In this mode the fault LED (12) will be blinking, and AUTO LED will be OFF and the screen will show “NOT IN AUTO” or
“INHIBIT”. To leave the inhibit mode close the input, the controller will return to previous working mode. Message on the screen
should clear automatically after input has been deactivated.
• Programming mode
This mode allows product parameter configuration.
To access this mode , long press (>3s) on the button, the screen will prompt to enter the password (Configurable, default
1000), while in the programming mode the LED 8 will be ON. To exit this mode press the (return button) until the LED 8 is OFF,
the controller will then return to the previous working mode (Auto or Manual).
S1 50.1Hz
U1n=232V
S2 50.2Hz
U1n=234V
Sceen 2: voltage threshold and hysteresis settings. A global view of all the hysteresis and thresholds set on the product:
S1=OVth=116%
S1=OVhy=110%
S1=UVth=85%
S1=UVhy=95%
S2=OVth=112%
S2=OVhy=110%
S2=UVth=85%
S2=UVhy=95%
S1=OFth=116%
S1=OFhy=110%
S1=UFth=90%
S1=UFhy=95%
S2=OFth=112%
S2=OFhy=110%
S2=UFth=90%
S2=UFhy=95%
S1=RT=0005s
S1=FT=05s
S2=RT=0005s
S2=FT=04s
S1-S2=0DT=00s
S2-S1=0DT=01s
SD=0000s
CT=0180s ST=0030s
Screen 5: global view of the input status, the numbers correspond to the input terminal (e.g. 71 pos I input):
INPUTS
71 POS I OFF
72 POS II ON
73 POS 0 OFF
92 OFF
93 OFF
94 OFF
Screen 6: global view of output status, the numbers correspond to the output terminal (eg. Terminal 15 for pos I output):
OUTPUTS
16 POS I OFF
15 POS II ON
14 POS 0 OFF
13 OFF
52 OFF
POS. I COUNT
00016
POS. II COUNT
00010
S1-S2
Phase angle
-10°
CAUTION ! The EXTERNAL AC DPS output to the RTSE will not be functional when powering through the DC
auxiliary power supply only.
• Loss of Neutral
In a 3phase network with unbalanced loads the loss of the neutral will be detected.
WARNING ! If the Neutral is lost in a balanced network, loss of source could be undetected, to minimize this reduce
the threshold on voltage sensing.
Techno type Order(1) Contact 17-16 Contact 17-15 Contact 17-14 Contact 17-13
Position 0 Closed Open Open NC
PC / CC Position I Open Closed Open NC
Position II Open Open Closed NC
Position 0 Open Closed Open Closed
CB Position I Closed Open Open Closed
Position II Open Closed Closed Open
(1) Orders can be given through the automatic logic of the controller in automatic mode or using the pushbuttons in manual mode
The duration of the order can be changed in the programming mode in “System” “SIGNALTIME”, the duration can be
changed from 0.1s up to 20s or changed to be maintained by going above the 20s value (default value is 5s).
From 0.1s-20s, orders are sent for duration set in "SIGNALTIME". If the RTSE does not reach the requested position in the set
time a FAULT for the corresponding position.
In CC Type technology when an order is sent it will be maintained until a different order is sent.
Genset start outputs are the output orders (dry contact), the contact between 51 and 54 will open & the
contact between 51 and 52 will close when the signal to start the genset should be sent (during a test on load
or when source 1 is lost). These outputs are rated for 250 V.a.c , 50/60 Hz 5A general use for NO contact and
3A general use for NC contact, and 30 V.d.c 5A general use for the contact between 51-54 and 3A general
use for the contact 51-52.
CAUTION ! If the 24 V.d.c auxiliary power supply is not used the timer 1FT will not count and the order to start the
generator will be sent immediately when source 1 is completely lost.
In Main-Main mode: if “S1-Mains S2-Mains” is selected in “System” “APP” the start-gen output can be configured for other
functions in the menu I/O. see chapter "12. Programming", page 27 for possible output functions.
The inputs 91-94 can be set in the programming menu “I/0”, by default output 1 (contact 91-92) is set to
“NOT IN AUTO”. See chapter 10.5.2 Programing for more details on the input functions.
These inputs must be connected from the RTSE to the controller in order to indicate the position of the
RTSE, when the controller gives an order both through manual command and automatically it will check
that the position input corresponding to this order has closed. If this is not the case the controller fault LED
will blink and the buzzer will be on, to clear the fault expected position input should be closed and the user
must press the AUTO button.
In PC mode:
73/70 must be closed when the RTSE is in position 0.
72/70 must be closed when the RTSE is in position II.
71/70 must be closed when the RTSE is in position I.
In CB techno only inputs I (for breaker 1 closed) and II (for breaker 2 closed) are mandatory. To connect the 0 input both breaker
open contacts can be placed in series and inserted in the O output, however this is not mandatory.
In CC techno the input outputs are the same as in PC techno but the position O feedback (73/70) is optional.
This input is activated by applying 24 V.d.c (12-24 V.d.c) on F1 and F2 (negative electrode connected to F1 and
positive electrode on F2.
When this input is activated, the Fire LED (13) will be ON (fixed) and the buzzer will sound, the controller will give
the order to the switch to go to position 0 and both manual and automatic controls will be inhibited. When the
input is removed, the switch will go back to the last working mode automatically.
11.4.4. RS485
The RS485 connector provides the Modbus communication allowing to read values from the controller
(eg: Voltage values, settings, switch position etc...) for details on the values that can be read through
communication (see Annex II).
While in the programming mode, the LED 8 will be ON. To exit this mode press the (return button) until the LED 8 is OFF,
the controller will then return to the previous working mode (Auto or Manual).
To save parameters validate using the leave the programing mode using button and select “YES” when prompted to
save the settings, the controller will beep twice to indicate that parameters have been saved.
DANGER ! When leaving automatic mode, if previous mode was automatic the RTSE might transfer directly.
Therefore it is recommended to place the C35 in manual mode before programming.
Outputs:
Output can only be configured in Main-Main application, in all other cases the output will be used for genset start (GENSET).
(1) 6 kV tested between phases of a different source and 4 kV tested between phases of a the same source.
(2) 190 - 300 VAC in CC type TECHNO.
It is recommended to verify at least once a year the tightening torque of all connections and to operate the product in a full
operating cycle (I – O – II – O – I: Auto and Manual) as well as tightening the door mounting clips and testing the LED’s with the
lamp test button when applicable.
In case of upstream protection tripping (fuse protection / Circuit breakers) make sure that the ATS remains functional by doing a
functional test with the RTSE connected to the controller.
To clean the front face of the equipment, use a soft cloth with water and non-abrasive liquids.
Note: Maintenance should be planned carefully and carried out by qualified and authorized personnel. Consideration of the
critical level and application where the product is installed should form an essential and integral part of the maintenance plan.
Good engineering practice is imperative whilst all necessary precautions must be taken to ensure that the intervention (whether
directly or indirectly) remains safe in all aspects.
16.1. RTSE
ATyS d M
ATyS d M devices are 2 pole or 4 pole transfer switches that are remotely
controlled using volt-free contacts from an external controller. They are modular
products with positive break indication. They are intended for use in low
voltage power supply systems where a brief interruption of the load supply is
acceptable during transfer.
References
ATyS S
ATyS S products are 4 pole re motely operated transfer switches with positive
break indication. They enable the on-load transfer of two three-phase supplies
via remote volt-free contacts, from either an external automatic controller, using
pulse logic, or a switch. They are intended for use in low voltage power supply
systems where a brief interruption of the load supply is acceptable during
transfer.
References
Rating (A) No. of poles Power supply ATyS S Bridging bars Terminal shrouds Voltage tap Terminal retainer DIN rail
4P 24/48 VDC 9506 4004
40 A 4P 12 VDC 9505 4004
4P 230 VAC 9503 4004 9599 4001
4P 24/48 VDC 9506 4006
63 A 4P 12 VDC 9505 4006
4P 230 VAC 9503 4006 Source side 9599 4001
4P 24/48 VDC 9506 4008 2 pieces
9594 4012
4P 2 pieces 4 modules
80 A 4P 12 VDC 9505 4008 9509 4013 9599 4003 9599 4002
Load side
4P 230 VAC 9503 4008 2 pieces 9599 4001
4P 24/48 VDC 9506 4010 9594 9012
100 A 4P 12 VDC 9505 4010
4P 230 VAC 9503 4010 9599 4001
4P 24/48 VDC 9506 4012
125 A 4P 12 VDC 9505 4012
4P 230 VAC 9503 4012 9599 4001
References
3P 9523 3016 3P 3P 3P
160 A / B3 4109 3019 2694 3014(2) 1509 3012
4P 4P 4P
4P 9523 4016 4109 4019 2694 4014(2) 1509 4012
3P 9523 3020
200 A / B3
4P 9523 4020
3P 9523 3025 3P
4109 3025
250 A / B4 4P
4P 9523 4025 4109 4025
3P 3P 1599 0502 9599 0003(3)
3P 9523 3031
2694 3021(2) 1509 3025
315 A / B4 4P 4P
4P 9523 4031 3P
4109 3039 2694 4021(2) 1509 4025
4P
3P 9523 3040 4109 4039
400 A / B4
4P 9523 4040
3P 9523 3050 3P
4109 3050
500 A / B5 4P 3P 3P
4P 9523 4050 4109 4050 2694 3051(2) 1509 3063
3P 4P 4P
3P 9523 3063 2694 4051(2) 1509 4063
4109 3063 400/230 VAC
630 A / B5 4P 1599 4064
4P 9523 4063 4109 4063
3P 9523 3080
800 A / B6
4P 9523 4080 3P
4109 3080
4P 3P
3P 9523 3100 4109 4080
1000 A / B6 1509 3080
4P 9523 4100 4P
1509 4080
1599 0532
3P 9523 3120 3P
4109 3120
1250 A / B6 4P
4P 9523 4120 4109 4120
3P 9523 3160 3P 3P
4109 3160 1509 3160 9599 0004(3)
1600 A / B7 4P 4P
4P 9523 4160 4109 4160 1509 4160
3P 9523 3200
2000 A / B8
4P 9523 4200
3P 9523 3250 3P
1509 3200
2500 A / B8 (1)
included
4P
4P 9523 4250 1509 4200
3P 9523 3320
3200 A / B8
4P 9523 4320
(1) See “Copper bar connection pieces”.
(2) To fully shroud front, rear, top and bottom 4 references required.
To shroud front switch top and bottom 2 references required (Whenever a bridging beam is fitted, it is then only possible to fit 3 times the reference for the terminal cover).
(3) Factory mounting only.
9
10
11
12
1 8
2 3 4 5 6 7
L1 L1
L2 L2
1 L3 L3 2
N N
301 302
0 II I
C 0 I II
51 54 52 37 36 35 94 93 92 91 F2 F1 73 72 71 70
+ - NC + - 0 II I C
SOURCE 1 103 104 105 106 203 204 205 206 SOURCE 2
Aux supply II I 0 C
S1 IN 102 101 302 301 202 201 S2 IN 81 - + 82 14 15 16 17
DPS OUT
LOAD
OR
22 24 21 22 24 21
II II
318-520 ph-ph
184-300 ph-n I I
11 14 12 11 14 12
O O
01 04 02 01 04 02
1309 1001 1309 1011
22 24 21
II
1309 1011
fuses 4A type gG* I fuses 4A type gG*
11 14 12
O
01 04 02
51 54 52 37 36 35 94 93 92 91 F2 F1 73 72 71 70
+ - NC + - 0 II I C
SOURCE 1 103 104 105 106 203 204 205 206 SOURCE 2
Aux supply II I 0 C
S1 IN 102 101 302 301 202 201 S2 IN 81 - + 82 14 15 16 17
DPS OUT
K1 K2
L1 L1
L2 L2
1 L3 L3 2
N N
K2 K1
51 54 52 37 36 35 94 93 92 91 F2 F1 73 72 71 70
+ - NC + - 0 II I C
SOURCE 1 103 104 105 106 203 204 205 206 SOURCE 2
Aux supply II I 0 C
S1 IN 102 101 302 301 202 201 S2 IN 81 - + 82 14 15 16 17
DPS OUT
WARNING ! Controller output relays 14-15-16-17 are rated for 5A , 250 VAC AC1 - general use, 1.5A 240 VAC AC-
15. DPS output is rated for 6A 250VAC general use, 1.5A 240 VAC AC 15. When supplying the RTSE motor/coils or
power through these outputs make sure that the CC based RTSE used is compatible with these characteristics, if
not use relays in-between outputs and RTSE supply.
CAUTION ! Due to the numerous types of RTSE type CC (contactors) available on the market,
compatibility and specific wiring designs must be carried out and qualified by others.
L1
CB1 CB2 L1
L2 L2
1 L3 L3 2
N N
230/400 V 230/400 V
interlock
Aux. 2
Aux. 1
Mot CB1 Mot CB2
AC ON AC ON
AC OFF AC OFF
C C
C CLOSE OPEN C CLOSE OPEN All fuses 4A type gG
51 54 52 37 36 35 94 93 92 91 F2 F1 73 72 71 70
+ - NC + - 0 II I C
SOURCE 1 103 104 105 106 203 204 205 206 SOURCE 2 Source 2 Source 1
Aux supply Open Close Open Close Comm
Note: due to the numerous types of RTSE type CB (circuit breakers) available on the market, compatibility
and specific wiring designs must be carried out and qualified by others.
WARNING ! B
efore using the internal DPS on the CB aux input make sure that the the characteristics do not go
beyond maximum capacity of the DPS output (cf Chapter "9.4. Terminal denomination, description and
characteristics", page 19).
L1 (A) L1 (A)
OK NON OK
information: Phase rotation order is active only for 3P+N networks, in all other networks phase order will not be checked
to determine source availability
U/F
OVth/OFth
OVhy/OFhy
Unom/Fnom
UVhy/UFhy
UVth/UFth
Source available
Annex I - 8. Tests
The C35 allows for two configuration on the test button, “TEST ON LOAD” or “TEST OFF LOAD”, to change the configuration go
in programming mode “Test” “BUTTON TEST”.
To start a test do a long press (>3s) on the button test when in manual or automatic mode the controller will request the
user password before starting the test, once the test starts the test LED will turn on. The test will stop when the user presses the
test button again for at least 3 seconds, the controller will return to the last working mode.
In Main-Main mode the genset start output will not be activated.
Sequence for TEST ON LOAD:
Allows user to test the full genset + ATS function
(1)
Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7 Status
0 0 0 0 0 0 0 0 Normal
1 0 0 0 0 0 0 0 Missing phase
0 1 0 0 0 0 0 0 Overvoltage
0 0 1 0 0 0 0 0 Undervoltage
0 0 0 0 1 0 0 0 Overfrequency
0 0 0 0 0 1 0 0 Underfrequency
(1) Example:
Address 10170 10171 10172 10173 10174 10175 10176 10177 10178 10179
Hex 0x3139 0x3338 0x3736 0x3130 0x3030 0x3831 0x3630 0x3030 0x3032 0x3541
ASCII 19 38 76 10 00 81 60 00 02 5A
Serial number is : 1938761000816000025A
CORPORATE HQ CONTACT:
SOCOMEC SAS
1-4 RUE DE WESTHOUSE
67235 BENFELD, FRANCE
www.socomec.com Non contractual document. © 2022, Socomec SAS. All rights reserved.