HHD High Voltage Fuses: The Temperature Limiting Function of The Fuse Striker Pin

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

FUSES

HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

The striker pin system is connected by means of a high


resistance parallel conductor. After melting the main fuse
elements the striker pin will indicate the operation status
of the fuse and open a load break switch or actuate a
microswitch for remote indication.

The temperature limiting function


of the fuse striker pin
SIBA HV Fuse-links up to and including 160 A with a
striker pin of 80 N are equipped with an integrated
temperature limiter as standard. The temperature limiter
is fitted inside the striker pin system. The SIBA striker pin
system therefore has the following functions:
• thermal protection of adjacent equipment, especially
SF6 Insulated switchgear
• limitation of failure current at the overload region
• improved properties for the switch-fuse combinations
according IEC 60420
The integrated temperature limiter avoids inadmissible
high temperatures – no matter for whatever reason they
are generated – in gas-insulated switchgear or narrow
switchgear enclosures. By means of a melting activator
Design and construction temperatures inside the fuse link enclosure are limited to
below approx. 100°C. This design especially considers
SIBA HV Fuse-links have parallel connected pure silver continuity of current supply for the end user for as long
fuse-elements. The design and method of production of as possible. The system reacts in such a way that short
the elements ensures narrow tolerances of time-current- time overloads do not cause the fuse to interrupt the
characteristics. circuit unnecessarily. Only when inadmissible values are
The fuse elements are wound on a ceramic support and exceedes the fuse will open the switch via the striker pin.
are attached to the silver plated connection caps by Higher temperatures on plastic fuse enclosures in SF6-
means of spot-welding. The connection caps are fitted insulated switchgear can be caused by:
inside the silver plated copper end caps by spot welding.
• selection of a fuse rating too low for transformer
The copper end caps themselves are press-fitted onto
protection
the porcelain tube which is glazed inside and outside.
The end caps are furthermore mechanically fixed to the • fuses are loaded with fault currents below the minimum
porcelain tube and additionally sealed by a durable operating current
elastic sealing medium. This sealing method has been • deterioration of fuse links caused by transient fault
proven over many decades of positive field experience currents (e.g. lightning strike)
and ensures tightness against ingress of humidity. • transformer faults currents (e.g. winding short-current)
• overloading of the fuse when loaded with currents as
Striker pin described in IEC 420 Test Duty 3
SIBA HV Fuse-links are available with striker pins of the • additional temperatures rise because of poor clip fitting
force: Fuse-links with integrated temperature limiter are com-
• 80 N (Part No. 30 … 13 for basic-type) and patible with standard Fuse links. All coordination sche-
• 120 N (Part No. 30 … 14 for variant-type) dules can be used.
The characteristics of both striker pins corresponds to Further information on our temperature limiter, design,
IEC 60282-1, VDE 0670 Part 4 and are of the energy- construction, can be obtained from our website.
category “medium”.

HHD 1
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

Selection
Guide

Rated Voltage DIN Size Class Part No. Selection Techn.


AC E Guide Data
kV mm Page Page
3/7.2 192 Back up 30 002 13 HHD 5 HHD 23
3/7.2 192 Back up 30 010 13 HHD 5 HHD 23
3/7.2 192 Back up 30 018 13 HHD 5 HHD 23
3/7.2 192 Back up 30 018 14 HHD 5 HHD 23
3/7.2 292 Back up 30 098 13 HHD 6 HHD 23
3/7.2 292 Back up 30 099 13 HHD 6 HHD 23
3/7.2 292 Back up 30 100 13 HHD 6 HHD 23
3/7.2 292 Back up 30 100 14 HHD 6 HHD 23
3/7.2 442 Back up 30 109 13 HHD 7 HHD 24
3/7.2 442 Back up 30 110 13 HHD 7 HHD 24
3/7.2 442 Back up 30 110 14 HHD 7 HHD 24
6/12 192 Back up 30 119 13 HHD 8 HHD 25
6/12 192 Back up 30 267 13 HHD 8 HHD 25
6/12 292 Back up 30 004 13 HHD 9 HHD 25
6/12 292 Back up 30 012 13 HHD 9 HHD 25
6/12 292 Back up 30 020 13 HHD 9 HHD 25
6/12 292 Back up 30 020 14 HHD 9 HHD 25
6/12 442 Back up 30 101 13 HHD 10 HHD 26
6/12 442 Back up 30 102 13 HHD 10 HHD 26
6/12 442 Back up 30 103 13 HHD 10 HHD 26
6/12 442 Back up 30 103 14 HHD 10 HHD 26
6/12 537 Back up 30 211 13 HHD 11 HHD 26
6/12 537 Back up 30 211 14 HHD 11 HHD 26
10/17.5 292 Back up 30 255 13 HHD 12 HHD 27
10/17.5 292 Back up 30 221 13 HHD 12 HHD 27
10/17.5 292 Back up 30 222 13 HHD 12 HHD 27
10/17.5 367 Back up 30 176 13 HHD 13 HHD 27
10/17.5 367 Back up 30 177 13 HHD 13 HHD 27
10/17.5 367 Back up 30 178 13 HHD 13 HHD 27
10/17.5 367 Back up 30 178 14 HHD 13 HHD 27
10/17.5 442 Back up 30 231 13 HHD 14 HHD 28
10/17.5 442 Back up 30 232 13 HHD 14 HHD 28
10/17.5 442 Back up 30 233 13 HHD 14 HHD 28

HHD 2
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

Selection
Guide

Rated Voltage DIN Size Class Part No. Selection Techn.


AC E Guide Data
kV mm Page Page
10/24 292 Back up 30 180 13 HHD 15 HHD 29
10/24 292 Back up 30 225 13 HHD 15 HHD 29
10/24 442 Back up 30 006 13 HHD 16 HHD 29
10/24 442 Back up 30 014 13 HHD 16 HHD 29
10/24 442 Back up 30 022 13 HHD 16 HHD 29
10/24 537 Back up 30 203 13 HHD 17 HHD 30
10/24 537 Back up 30 204 13 HHD 17 HHD 30
10/24 537 Back up 30 196 13 HHD 17 HHD 30
10/24 537 Back up 30 196 14 HHD 17 HHD 30
20/36 442 Back up 30 181 13 HHD 18 HHD 31
20/36 537 Back up 30 008 13 HHD 19 HHD 31
20/36 537 Back up 30 016 13 HHD 19 HHD 31
20/36 537 Back up 30 024 13 HHD 19 HHD 31
6/12 292 General purpose 30 004 93 HHD 21 HHD 32
6/12 292 General purpose 30 012 93 HHD 21 HHD 32
6/12 292 General purpose 30 020 93 HHD 21 HHD 32
10/24 442 General purpose 30 006 93 HHD 22 HHD 32
10/24 442 General purpose 30 014 93 HHD 22 HHD 32
10/24 442 General purpose 30 022 93 HHD 22 HHD 32

Selection Fuse-bases
Guide

Article Rated Voltage DIN-Size Part No. Techn.


AC E Data
kV mm Page
Indoor Fuse-bases 7.2 192 31 001 02 HHD 40
12 292 31 003 02 HHD 40
24 442 31 005 02 HHD 40
36 537 31 007 02 HHD 40
24 292 31 221 01 HHD 40
Outdoor Fuse-bases 7.2 192 31 002 01 HHD 41
12 292 31 004 01 HHD 41
24 292 31 006 01 HHD 41
36 537 31 008 01 HHD 41

HHD 3
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

Selection Microswitch fitting consists of


Guide

Article Length Part No. Techn.


mm Data
Page
Microswitch 660 31 001 10 HHD 42
900 31 001 14 HHD 42
Fuse Clip 34 002 01 HHD 43

Distance Plate 31 002 01.3 HHD 43

Selection Accessories
Guide

Article Rated Part No. Techn.


Voltage Data
kV Page
Extension Adapter 12/24 34 006 01 HHD 44

Test Fuse-link for gas 24 33 010 03 HHD 45


insulated switchgear
Contact Clip 200 A 31 003 02.20 HHD 46
indoor and outdoor
Contact Clip 34 001 01.20 HHD 46
heavy duty
Storage Holder 12 33 004 01 HHD 47
24 33 006 01 HHD 47
36 33 008 01 HHD 47

HHD 4
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E=192 mm AC 3/7.2 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 002 13 2.10 53 63 1.2 1
10 A 30 002 13 2.10 53 63 1.2 1
16 A 30 002 13 2.10 53 63 1.2 1
20 A 30 002 13 2.10 53 63 1.2 1
25 A 30 002 13 2.10 53 63 1.2 1
31.5 A 30 002 13 2.10 53 63 1.2 1
40 A 30 002 13 2.10 53 63 1.2 1
50 A 30 002 13 2.10 53 63 1.2 1
63 A 30 010 13 2.64 67 63 1.5 1
80 A 30 010 13 2.64 67 63 1.5 1
100 A 30 010 13 2.64 67 63 1.5 1
125 A 30 010 13 2.64 67 63 1.5 1
160 A 30 018 13 3.35 85 63 2.9 1
200 A 30 018 14 3.35 85 50 2.9 1
250 A 30 018 14 3.35 85 50 2.9 1

Prefered Standard size 3/7.2 kV

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 5
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 292 mm AC 3/7.2 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 098 13 2.10 53 63 1.6 1
10 A 30 098 13 2.10 53 63 1.6 1
16 A 30 098 13 2.10 53 63 1.6 1
20 A 30 098 13 2.10 53 63 1.6 1
25 A 30 098 13 2.10 53 63 1.6 1
31.5 A 30 098 13 2.10 53 63 1.6 1
40 A 30 098 13 2.10 53 63 1.6 1
50 A 30 098 13 2.10 53 63 1.6 1
63 A 30 099 13 2.64 67 63 2.0 1
80 A 30 099 13 2.64 67 63 2.0 1
100 A 30 099 13 2.64 67 63 2.0 1
125 A 30 099 13 2.64 67 63 2.0 1
160 A 30 100 13 3.35 85 50 3.8 1
200 A 30 100 14 3.35 85 50 3.8 1
250 A 30 100 14 3.35 85 50 3.8 1
315 A 30 100 14 3.35 85 50 3.8 1
355 A 30 100 14 3.35 85 50 3.8 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 6
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 442 mm AC 3/7.2 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
100 A 30 109 13 2.64 67 63 2.9 1
125 A 30 109 13 2.64 67 63 2.9 1
160 A 30 110 13 3.35 85 63 5.4 1
200 A 30 110 14 3.35 85 50 5.4 1
250 A 30 110 14 3.35 85 50 5.4 1
315 A 30 110 14 3.35 85 50 5.4 1
355 A 30 110 14 3.35 85 50 5.4 1
400 A 30 110 14 3.35 85 50 5.4 1
500 A 30 110 14 3.35 85 50 5.4 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 7
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 192 mm AC 6/12 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 119 13 2.10 53 63 1.2 1
10 A 30 119 13 2.10 53 63 1.2 1
16 A 30 119 13 2.10 53 63 1.2 1
20 A 30 267 13 2.64 67 63 1.5 1
25 A 30 267 13 2.64 67 63 1.5 1
31.5 A 30 267 13 2.64 67 63 1.5 1
40 A 30 267 13 2.64 67 63 1.5 1
50 A 30 267 13 2.64 67 63 1.5 1
63 A 30 267 13 2.64 67 63 1.5 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 8
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 292 mm AC 6/12 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 004 13 2.10 53 63 1.6 1
10 A 30 004 13 2.10 53 63 1.6 1
16 A 30 004 13 2.10 53 63 1.6 1
20 A 30 004 13 2.10 53 63 1.6 1
25 A 30 004 13 2.10 53 63 1.6 1
31.5 A 30 004 13 2.10 53 63 1.6 1
40 A 30 004 13 2.10 53 63 1.6 1
50 A 30 004 13 2.10 53 63 1.6 1
63 A 30 012 13 2.64 67 63 2.0 1
80 A 30 012 13 2.64 67 63 2.0 1
100 A 30 012 13 2.64 67 63 2.0 1
125 A 30 012 13 2.64 67 63 2.0 1
160 A 30 020 13 3.35 85 63 3.8 1
200 A 30 020 14 3.35 85 50 3.8 1

Prefered Standard size 6/12 kV

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 9
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 442 mm AC 6/12 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 101 13 2.10 53 63 2.2 1
10 A 30 101 13 2.10 53 63 2.2 1
16 A 30 101 13 2.10 53 63 2.2 1
20 A 30 101 13 2.10 53 63 2.2 1
25 A 30 101 13 2.10 53 63 2.2 1
31.5 A 30 101 13 2.10 53 63 2.2 1
40 A 30 101 13 2.10 53 63 2.2 1
50 A 30 101 13 2.10 53 63 2.2 1
63 A 30 102 13 2.64 67 63 2.9 1
80 A 30 102 13 2.64 67 63 2.9 1
100 A 30 102 13 2.64 67 63 2.9 1
125 A 30 102 13 2.64 67 63 2.9 1
160 A 30 103 13 3.35 85 63 5.4 1
200 A 30 103 14 3.35 85 50 5.4 1
250 A 30 103 14 3.35 85 50 5.4 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 10
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 537 mm AC 6/12 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
100 A 30 211 13 3.35 85 63 6.8 1
125 A 30 211 13 3.35 85 63 6.8 1
160 A 30 211 13 3.35 85 63 6.8 1
200 A 30 211 14 3.35 85 50 6.8 1
250 A 30 211 14 3.35 85 50 6.8 1
315 A 30 211 14 3.35 85 50 6.8 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 11
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 292 mm AC 10/17.5 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 255 13 2.10 53 63 1.6 1
10 A 30 255 13 2.10 53 63 1.6 1
16 A 30 255 13 2.10 53 63 1.6 1
20 A 30 221 13 2.64 67 63 2.0 1
25 A 30 221 13 2.64 67 63 2.0 1
31.5 A 30 221 13 2.64 67 63 2.0 1
40 A 30 221 13 2.64 67 63 2.0 1
50 A 30 221 13 2.64 67 63 2.0 1
63 A 30 221 13 2.64 67 63 2.0 1
80 A 30 222 13 3.35 85 63 3.8 1
100 A 30 222 13 3.35 85 63 3.8 1
125 A 30 222 13 3.35 85 63 3.8 1
160 A 30 222 13 3.35 85 63 3.8 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 12
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 367 mm AC 10/17.5 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 176 13 2.10 53 63 2.0 1
10 A 30 176 13 2.10 53 63 2.0 1
16 A 30 176 13 2.10 53 63 2.0 1
20 A 30 176 13 2.10 53 63 2.0 1
25 A 30 176 13 2.10 53 63 2.0 1
31.5 A 30 177 13 2.64 67 63 3.0 1
40 A 30 177 13 2.64 67 63 3.0 1
50 A 30 177 13 2.64 67 63 3.0 1
63 A 30 177 13 2.64 67 63 3.0 1
80 A 30 178 13 3.35 85 63 4.8 1
100 A 30 178 13 3.35 85 63 4.8 1
125 A 30 178 13 3.35 85 63 4.8 1
160 A 30 178 13 3.35 85 63 4.8 1
200 A 30 178 14 3.35 85 40 4.8 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 13
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 442 mm AC 10/17.5 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 231 13 2.10 53 63 2.2 1
10 A 30 231 13 2.10 53 63 2.2 1
16 A 30 231 13 2.10 53 63 2.2 1
20 A 30 231 13 2.10 53 63 2.2 1
25 A 30 231 13 2.10 53 63 2.2 1
31.5 A 30 231 13 2.10 53 63 2.2 1
40 A 30 231 13 2.10 53 63 2.2 1
50 A 30 232 13 2.64 67 63 2.9 1
63 A 30 232 13 2.64 67 63 2.9 1
80 A 30 232 13 2.64 67 63 2.9 1
100 A 30 233 13 3.35 85 63 5.4 1
125 A 30 233 13 3.35 85 63 5.4 1
160 A 30 233 13 3.35 85 63 5.4 1
200 A 30 233 14 3.35 85 40 5.4 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 14
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 292 mm AC 10/24 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 180 13 2.10 53 31.5 1.6 1
10 A 30 180 13 2.10 53 31.5 1.6 1
16 A 30 180 13 2.10 53 31.5 1.6 1
20 A 30 225 13 2.64 67 31.5 2.0 1
25 A 30 225 13 2.64 67 31.5 2.0 1
31.5 A 30 225 13 2.64 67 31.5 2.0 1
40 A 30 225 13 2.64 67 31.5 2.0 1
50 A 30 225 13 2.64 67 31.5 2.0 1
63 A 30 225 13 2.64 67 31.5 2.0 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 15
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 442 mm AC 10/24 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 006 13 2.10 53 63 2.2 1
10 A 30 006 13 2.10 53 63 2.2 1
16 A 30 006 13 2.10 53 63 2.2 1
20 A 30 006 13 2.10 53 63 2.2 1
25 A 30 006 13 2.10 53 63 2.2 1
31.5 A 30 006 13 2.10 53 63 2.2 1
40 A 30 006 13 2.10 53 63 2.2 1
50 A 30 014 13 2.64 67 63 2.9 1
63 A 30 014 13 2.64 67 63 2.9 1
80 A 30 014 13 2.64 67 63 2.9 1
100 A 30 022 13 3.35 85 63 5.4 1
125 A 30 022 13 3.35 85 40 5.4 1

Prefered Standard size 10/24 kV

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 16
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 537 mm AC 10/24 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 203 13 2.10 53 63 2.8 1
10 A 30 203 13 2.10 53 63 2.8 1
16 A 30 203 13 2.10 53 63 2.8 1
20 A 30 203 13 2.10 53 63 2.8 1
25 A 30 203 13 2.10 53 63 2.8 1
31.5 A 30 203 13 2.10 53 63 2.8 1
40 A 30 203 13 2.10 53 63 2.8 1
50 A 30 204 13 2.64 67 63 3.7 1
63 A 30 204 13 2.64 67 63 3.7 1
80 A 30 204 13 2.64 67 63 3.7 1
100 A 30 196 13 3.35 85 63 6.8 1
125 A 30 196 13 3.35 85 40 6.8 1
160 A 30 196 13 3.35 85 31.5 6.8 1
200 A 30 196 14 3.35 85 31.5 6.8 1
250 A 30 196 14 3.35 85 31.5 6.8 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 17
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 442 mm AC 20/36 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 181 13 2.10 53 20 2.2 1
10 A 30 181 13 2.10 53 20 2.2 1
16 A 30 181 13 2.10 53 20 2.2 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 18
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 537 mm AC 20/36 kV Back up DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 008 13 2.10 53 40 2.6 1
10 A 30 008 13 2.10 53 40 2.6 1
16 A 30 008 13 2.10 53 40 2.6 1
20 A 30 008 13 2.10 53 40 2.6 1
25 A 30 008 13 2.10 53 40 2.6 1
31.5 A 30 016 13 2.64 67 40 3.5 1
40 A 30 016 13 2.64 67 40 3.5 1
50 A 30 024 13 3.35 85 40 6.0 1
63 A 30 024 13 3.35 85 40 6.0 1
80 A 30 024 13 3.35 85 40 6.0 1

Prefered Standard size 20/36 kV

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 19
HHD FUSES

HIGH VOLTAGE FUSES FOR


AIR & GAS INSULATED SWITCHGEARS
GERMAN DIN STANDARD – GENERAL PURPOSE OUTDOOR SWITCHGEARS

 According IEC 60 282-1 and VDE 0670 Part


4, a General-Purpose-Fuse interrupts fault
currents between the rated breaking current
and the current which causes melting within
one hour. The protection range of the SIBA-
VS-Protector extends this basic demand.
The minimum breaking current is about 1.5
times the rated current. In combination with
the temperature released striker pin a full
range protection is possible. Additional fea-
ture is the small powerloss of the VS-Pro-
tector. It is up to 40 % smaller than the
standard DIN-fuse.

 The dimensions of the VS-Protector are


according to DIN 43625. The rated voltages
12 and 24 kV and also the available current
ratings allow protection of transformers up
to 630 kVA.
VS-Protector for the overload and
short-circuit range
 The function of the VS-Protector is compa-
rable to a typical Back up Fuse link. The
melting elements of pure silver are wound
inside onto a ceramic support. A short
section in the center of the fuse is designed
as a “Heat chamber”. Inside this chamber
the elements are made of silver-alloy. They
generate a certain level of temperature at
overloads. As a result the fuses interrupt at
low fault-currents without ageing.

HHD 20
FUSES
HHD

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 292 mm AC 6/12 kV General purpose DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 004 93 2.10 53 63 1.6 1
8A 30 012 13 2.64 67 63 2.0 1
10 A 30 012 93 2.64 67 63 2.0 1
16 A 30 012 93 2.64 67 63 2.0 1
20 A 30 012 93 2.64 67 63 2.0 1
25 A 30 012 93 2.64 67 63 2.0 1
31.5 A 30 012 93 2.64 67 63 2.0 1
40 A 30 012 93 2.64 67 63 2.0 1
50 A 30 020 93 3.35 85 63 3.8 1
63 A 30 020 93 3.35 85 63 3.8 1
80 A 30 020 93 3.35 85 63 3.8 1
100 A 30 020 93 3.35 85 63 3.8 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 21
HHD FUSES

HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS


GERMAN DIN STANDARD OUTDOOR SWITCHGEARS

DIN Size Rated voltage Class Standard


E= 442 mm AC 10/24 kV General purpose DIN 43625 · IEC 60282-1

Rated Part No. D= Diameter Rated breaking Weight Pack


current inch mm current (kg/1)
kA
6.3 A 30 006 93 2.10 53 40 2.2 1
10 A 30 014 93 2.64 67 40 2.9 1
16 A 30 014 93 2.64 67 40 2.9 1
20 A 30 014 93 2.64 67 40 2.9 1
25 A 30 014 93 2.64 67 40 2.9 1
31.5 A 30 022 93 3.35 85 40 5.4 1
40 A 30 022 93 3.35 85 40 5.4 1

A 1.77 ” (45 mm)


F 1.30 ” (33 mm)
O 0.40 ” (10 mm)
N 1.38 ” (35 mm)

HHD 22
Electrical Characteristics FUSES
HHD
DIN Size Rated voltage Class
E= 192 mm AC 3/7.2 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 3 kV @ 7.2 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 002 13 63 22 178.0 10 45 210 360
10 A 30 002 13 63 34 113.0 17 75 350 560
16 A 30 002 13 63 56 50.0 17 250 1,100 2,000
20 A 30 002 13 63 70 27.0 13 640 2,900 4,800
25 A 30 002 13 63 90 21.0 16 1,050 4,700 7,500
31.5 A 30 002 13 63 110 17.0 21 1,700 6,600 12,000
40 A 30 002 13 63 140 13.0 27 2,900 12,000 19,000
50 A 30 002 13 63 170 9.3 30 5,700 20,000 33,000
63 A 30 010 13 63 210 6.8 38 10,700 40,000 66,000
80 A 30 010 13 63 280 4.8 47 21,000 78,000 140,000
100 A 30 010 13 63 320 3.8 64 33,000 130,000 210,000
125 A 30 010 13 63 390 3.3 98 47,000 180,000 390,000
160 A 30 018 13 63 600 2.4 124 90,000 330,000 570,000
200 A 30 018 14 50 800 1.9 146 230,000 480,000 704,000
250 A 30 018 14 50 1,000 1.6 210 371,000 750,000 1,101,000

DIN Size Rated voltage Class


E= 292 mm AC 3/7.2 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 3 kV @ 7.2 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 098 13 63 22 178.0 10 45 210 360
10 A 30 098 13 63 34 113.0 17 75 350 560
16 A 30 098 13 63 56 50.0 17 250 1,100 2,000
20 A 30 098 13 63 70 27.0 13 640 2,900 4,800
25 A 30 098 13 63 90 21.0 16 1,050 4,700 7,500
31.5 A 30 098 13 63 110 17.0 21 1,700 6,600 12,000
40 A 30 098 13 63 140 13.0 27 2,900 12,000 19,000
50 A 30 098 13 63 170 9.3 30 5,700 20,000 33,000
63 A 30 099 13 63 210 6.8 38 10,700 40,000 66,000
80 A 30 099 13 63 280 4.8 47 21,000 78,000 140,000
100 A 30 099 13 63 320 3.8 64 33,000 130,000 210,000
125 A 30 099 13 63 390 3.3 98 47,000 180,000 390,000
160 A 30 100 13 63 600 2.3 103 90,000 330,000 570,000
200 A 30 100 14 50 800 1.9 134 230,000 480,000 704,000
250 A 30 100 14 50 1,000 1.6 191 371,000 750,000 1,101,000
315 A 30 100 14 50 1,260 1.2 281 545,000 1,066,000 1,616,000
355 A 30 100 14 50 1,420 1.0 336 825,000 1,420,000 2,225,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 23
HHD FUSES
Electrical Characteristics

DIN Size Rated voltage Class


E= 442 mm AC 3/7.2 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 3 kV @ 7.2 kV
current kA current A mOhm W A2s A2s A2s
100 A 30 109 13 63 320 3.8 64 33,000 130,000 210,000
125 A 30 109 13 63 390 3.3 98 47,000 180,000 390,000
160 A 30 110 13 63 600 2.3 85 90,000 330,000 570,000
200 A 30 110 14 50 800 2.1 155 230,000 480,000 704,000
250 A 30 110 14 50 1,000 1.8 233 371,000 750,000 1,101,000
315 A 30 110 14 50 1,260 1.5 281 545,000 1,066,000 1,616,000
355 A 30 110 14 50 1,420 1.3 320 825,000 1,420,000 2,225,000
400 A 30 110 14 50 1,600 1.1 347 1,000,000 1,900,000 2,528,000
500 A 30 110 14 50 2,000 0.85 430 1,668,000 3,162,000 4,500,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 24
Electrical Characteristics FUSES
HHD
DIN Size Rated voltage Class
E= 192 mm AC 6/12 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 6 kV @ 12 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 119 13 63 22 297 16 45 210 360
10 A 30 119 13 63 34 189 28 75 350 560
16 A 30 119 13 63 56 87 28 250 1,100 2,000
20 A 30 267 13 63 70 46 23 640 2,900 4,800
25 A 30 267 13 63 90 36 29 1,050 4,700 7,500
31.5 A 30 267 13 63 110 29 38 1,700 6,600 12,000
40 A 30 267 13 63 140 22 50 2,900 12,000 19,000
50 A 30 267 13 63 170 16 56 5,700 20,000 33,000
63 A 30 267 13 63 210 12 63 10,700 40,000 66,000

DIN Size Rated voltage Class


E= 292 mm AC 6/12 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 6 kV @ 12 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 004 13 63 22 297.0 16 45 210 360
10 A 30 004 13 63 34 189.0 28 75 350 560
16 A 30 004 13 63 56 84.0 28 250 1,100 2,000
20 A 30 004 13 63 70 45.0 23 640 2,900 4,800
25 A 30 004 13 63 90 34.0 29 1,050 4,700 7,500
31.5 A 30 004 13 63 110 28.0 38 1,700 6,600 12,000
40 A 30 004 13 63 140 22.0 50 2,900 12,000 19,000
50 A 30 004 13 63 170 16.0 56 5,700 20,000 33,000
63 A 30 012 13 63 210 12.0 63 10,700 40,000 66,000
80 A 30 012 13 63 280 8.5 76 21,000 78,000 140,000
100 A 30 012 13 63 320 6.5 104 33,000 130,000 210,000
125 A 30 012 13 63 390 5.5 159 47,000 180,000 390,000
160 A 30 020 13 63 600 3.9 173 90,000 330,000 570,000
200 A 30 020 14 50 800 3.0 234 230,000 480,000 704,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 25
HHD FUSES
Electrical Characteristics

DIN Size Rated voltage Class


E= 442 mm AC 6/12 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 6 kV @ 12 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 101 13 63 22 297.0 16 45 210 360
10 A 30 101 13 63 34 189.0 28 75 350 560
16 A 30 101 13 63 56 87.0 19 250 1,100 2,000
20 A 30 101 13 63 70 46.0 22 640 2,900 4,800
25 A 30 101 13 63 90 36.0 28 1,050 4,700 7,500
31.5 A 30 101 13 63 110 29.0 37 1,700 6,600 12,000
40 A 30 101 13 63 140 22.0 48 2,900 12,000 19,000
50 A 30 101 13 63 170 16.0 54 5,700 20,000 33,000
63 A 30 102 13 63 210 12.0 58 10,700 40,000 66,000
80 A 30 102 13 63 280 8.5 70 21,000 78,000 140,000
100 A 30 102 13 63 320 6.5 96 33,000 130,000 210,000
125 A 30 102 13 63 390 5.5 147 47,000 180,000 390,000
160 A 30 103 13 63 600 3.9 172 90,000 330,000 570,000
200 A 30 103 14 50 800 2.9 193 230,000 480,000 704,000
250 A 30 103 14 50 1,000 2.6 269 371,000 750,000 1,101,000

DIN Size Rated voltage Class


E= 537 mm AC 6/12 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 6 kV @ 12 kV
current kA current A mOhm W A2s A2s A2s
100 A 30 211 13 63 320 6.5 96 33,000 130,000 210,000
125 A 30 211 13 63 390 5.5 147 47,000 180,000 390,000
160 A 30 211 13 63 600 3.9 172 90,000 330,000 570,000
200 A 30 211 14 50 800 3.2 193 230,000 480,000 704,000
250 A 30 211 14 50 1,000 2.6 274 371,000 750,000 1,101,000
315 A 30 211 14 50 1,260 2.2 382 545,000 1,066,000 1,616,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 26
Electrical Characteristics FUSES
HHD
DIN Size Rated voltage Class
E= 292 mm AC10/17.5 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 10 kV @ 17.5 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 255 13 53 22 397.0 21 45 210 360
10 A 30 255 13 53 34 252.0 38 75 350 560
16 A 30 255 13 53 56 116.0 37 250 1,100 2,000
20 A 30 221 13 63 70 62.0 40 640 2,900 4,800
25 A 30 221 13 63 90 48.0 56 1,050 4,700 7,500
31.5 A 30 221 13 63 110 39.0 65 1,700 6,600 12,000
40 A 30 221 13 63 140 29.0 84 2,900 12,000 19,000
50 A 30 221 13 63 170 21.0 101 5,700 20,000 33,000
63 A 30 222 13 85 210 16.0 106 10,700 40,000 66,000
80 A 30 222 13 85 280 11.0 137 21,000 78,000 140,000
100 A 30 222 13 85 320 8.7 182 33,000 130,000 210,000
125 A 30 222 13 85 390 7.5 235 47,000 180,000 390,000
160 A 30 222 13 85 600 5.2 290 90,000 330,000 570,000

DIN Size Rated voltage Class


E= 367 mm AC 10/17.5 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 10 kV @ 17.5 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 176 13 63 22 397.0 21 45 210 360
10 A 30 176 13 63 34 252.0 38 75 350 560
16 A 30 176 13 63 56 116.0 37 250 1,100 2,000
20 A 30 176 13 63 70 62.0 40 640 2,900 4,800
25 A 30 176 13 63 90 48.0 56 1,050 4,700 7,500
31.5 A 30 177 13 63 110 39.0 65 1,700 6,600 12,000
40 A 30 177 13 63 140 29.0 84 2,900 12,000 19,000
50 A 30 177 13 63 170 21.0 101 5,700 20,000 33,000
63 A 30 177 13 63 210 16.0 106 10,700 40,000 66,000
80 A 30 178 13 63 280 11.0 137 21,000 78,000 140,000
100 A 30 178 13 63 320 8.7 182 33,000 130,000 210,000
125 A 30 178 13 63 390 7.5 235 47,000 180,000 390,000
160 A 30 178 13 63 600 5.2 290 90,000 330,000 570,000
200 A 30 178 14 40 800 3.85 330 230,000 480,000 704,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 27
HHD FUSES
Electrical Characteristics

DIN Size Rated voltage Class


E= 442 mm AC 10/17.5 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 10 kV @ 17.5 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 231 13 63 22 397.0 21 45 210 360
10 A 30 231 13 63 34 252.0 38 75 350 560
16 A 30 231 13 63 56 116.0 37 250 1,100 2,000
20 A 30 231 13 63 70 62.0 42 640 2,900 4,800
25 A 30 231 13 63 90 48.0 56 1,050 4,700 7,500
31.5 A 30 231 13 63 110 39.0 60 1,700 6,600 12,000
40 A 30 231 13 63 140 29.0 84 2,900 12,000 19,000
50 A 30 232 13 63 170 21.0 101 5,700 20,000 33,000
63 A 30 232 13 63 210 16.0 106 10,700 40,000 66,000
80 A 30 232 13 63 280 11.0 137 21,000 78,000 140,000
100 A 30 233 13 63 320 8.7 182 33,000 130,000 210,000
125 A 30 233 13 63 390 7.5 235 47,000 180,000 390,000
160 A 30 233 13 63 600 5.2 290 90,000 330,000 570,000
200 A 30 233 14 40 800 3.85 330 230,000 480,000 704,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 28
Electrical Characteristics FUSES
HHD
DIN Size Rated voltage Class
E= 292 mm AC 10/24 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 10 kV @ 24 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 180 13 31.5 22 546 29 45 210 360
10 A 30 180 13 31.5 34 347 52 75 350 560
16 A 30 180 13 31.5 56 160 59 250 1,100 2,000
20 A 30 225 13 31.5 70 86 46 640 2,900 4,800
25 A 30 225 13 31.5 90 66 56 1,050 4,700 7,500
31.5 A 30 225 13 31.5 110 53 72 1,700 6,600 12,000
40 A 30 225 13 31.5 140 41 106 2,900 12,000 19,000
50 A 30 225 13 31.5 170 29 108 5,700 20,000 33,000
63 A 30 225 13 31.5 210 21 132 10,700 40,000 66,000

DIN Size Rated voltage Class


E= 442 mm AC 10/24 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 10 kV @ 24 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 006 13 63 22 546 29 45 210 360
10 A 30 006 13 63 34 347 52 75 350 560
16 A 30 006 13 63 56 151 59 250 1,100 2,000
20 A 30 006 13 63 70 83 46 640 2,900 4,800
25 A 30 006 13 63 90 62 56 1,050 4,700 7,500
31.5 A 30 006 13 63 110 52 72 1,700 6,600 12,000
40 A 30 006 13 63 140 41 106 2,900 12,000 19,000
50 A 30 014 13 63 170 29 108 5,700 20,000 33,000
63 A 30 014 13 63 210 22 132 10,700 40,000 66,000
80 A 30 014 13 63 280 16 174 21,000 78,000 140,000
100 A 30 022 13 63 320 13 234 33,000 130,000 210,000
125 A 30 022 13 40 390 11 320 47,000 180,000 390,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 29
HHD FUSES
Electrical Characteristics

DIN Size Rated voltage Class


E= 537 mm AC 10/24 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 10 kV @ 24 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 203 13 63 22 546.0 29 45 210 360
10 A 30 203 13 63 34 347.0 52 75 350 560
16 A 30 203 13 63 56 160.0 57 250 1,100 2,000
20 A 30 203 13 63 70 86.0 45 640 2,900 4,800
25 A 30 203 13 63 90 66.0 55 1,050 4,700 7,500
31.5 A 30 203 13 63 110 53.0 70 1,700 6,600 12,000
40 A 30 203 13 63 140 43.0 103 2,900 12,000 19,000
50 A 30 204 13 63 170 29.0 101 5,700 20,000 33,000
63 A 30 204 13 63 210 21.0 121 10,700 40,000 66,000
80 A 30 204 13 63 280 16.0 147 21,000 78,000 140,000
100 A 30 196 13 63 320 13.0 240 33,000 130,000 210,000
125 A 30 196 13 40 390 11.0 320 47,000 180,000 390,000
160 A 30 196 13 31.5 600 8.0 381 90,000 330,000 570,000
200 A 30 196 14 31.5 800 5.3 440 230,000 480,000 704,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 30
Electrical Characteristics FUSES
HHD
DIN Size Rated voltage Class
E= 442 mm AC 20/36 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 20 kV @ 36 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 181 13 20 22 819 44 45 210 360
10 A 30 181 13 20 34 521 78 75 350 560
16 A 30 181 13 20 56 241 74 250 1,100 3,000

DIN Size Rated voltage Class


E= 537 mm AC 20/36 kV Back up

Rated Part No. Rated Minimum Cold Power Pre-arcing Total I2t value
current breaking breaking resistance loss I2t-value @ 20 kV @ 36 kV
current kA current A mOhm W A2s A2s A2s
6.3 A 30 008 13 40 22 819 44 45 210 360
10 A 30 008 13 40 34 521 78 75 350 560
16 A 30 008 13 40 56 241 79 250 1,100 2,000
20 A 30 008 13 40 70 129 66 640 2,900 4,800
25 A 30 008 13 40 90 99 87 1,050 4,700 7,500
31.5 A 30 016 13 40 110 80 102 1,700 6,600 12,000
40 A 30 016 13 40 140 60 144 2,900 12,000 19,000
50 A 30 024 13 40 170 44 186 5,700 20,000 33,000
63 A 30 024 13 40 210 32 224 10,700 40,000 66,000
80 A 30 024 13 40 280 23 280 21,000 78,000 140,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGES HHD 33 AND HHD 34

HHD 31
HHD FUSES
Electrical Characteristics

DIN Size Rated voltage Class


E= 292 mm AC 6/12 kV General Purpose

Rated Part No. Breaking Cold Power Pre-arcing Total I2t value
current current resistance loss I2t-value @ 12 kV
kA mOhm W A2s A2s
6.3 A 30 004 93 63 150 7 110 900
8A 30 012 93 63 120 9 180 1,400
10 A 30 012 93 63 100 12 240 2,000
16 A 30 012 93 63 40 12 530 4,400
20 A 30 012 93 63 31 15 850 7,000
25 A 30 012 93 63 25 18 1,330 11,000
31.5 A 30 012 93 63 20 23 2,100 18,000
40 A 30 012 93 63 16 29 3,400 28,000
50 A 30 020 93 63 15 42 5,500 33,000
63 A 30 020 93 63 12 54 8,500 68,000
80 A 30 020 93 63 9 79 16,200 142,000
100 A 30 020 93 63 7.7 108 23,500 183,000

DIN Size Rated voltage Class


E= 442 mm AC 10/24 kV General Purpose

Rated Part No. Breaking Cold Power Pre-arcing Total I2t value
current current resistance loss I2t-value @ 24 kV
kA mOhm W A2s A2s
6.3 A 30 006 93 40 273 13 110 900
8A 30 014 93 40 220 17 180 1,400
10 A 30 014 93 40 180 22 240 2,000
16 A 30 014 93 40 70 19 530 4,400
20 A 30 014 93 40 55 27 850 7,000
25 A 30 014 93 40 45 38 1,330 11,000
31.5 A 30 022 93 40 41 54 2,100 18,000
40 A 30 022 93 40 33 77 3,400 28,000

TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM


PLEASE REFER TO PAGE HHD 35

HHD 32
Electrical Characteristics FUSES
HHD
Time Current Characteristics Back up

t(s)
Virtual Pre-arcing Time

RMS Prospective Current I(A)

Cut Off Current Diagram Back up

Ic
(kA)
Cut-off Current Peak

Prospective Short Circuit Current I(kA)

HHD 33
HHD FUSES
Electrical Characteristics

Time Current Characteristics Back up

t(s)
Virtual Pre-arcing Time

RMS Prospective Current I(A)

Cut Off Current Diagram Back up

Ic
(kA)
Cut-off Current Peak

Prospective Short Circuit Current I(kA)

HHD 34
Electrical Characteristics FUSES
HHD
Time Current Characteristics General Purpose

t(s)
Virtual Pre-arcing Time

RMS Prospective Current I(A)

Cut Off Current Diagram General Purpose

Ic
(kA)
Cut-off Current Peak

Prospective Short Circuit Current I(kA)

HHD 35
HHD FUSES

HV fuse link
Vertical Cross Section

Weather resistant label

Integrated temperature limiter

Sealing compound

Shaped cap

Melting element support

Thermal Zone
(at General Purpose fuse only)

Ceramic insulating tube

Silver melting element


welded to contact strap

Connecting straps pastened to


contactcap by resistance welding
Force / distance diagram
80 N 120 N
Quarzsand

mm mm

HHD 36
FUSES
HHD
Recommendation for the protection of main transformer
with HV-Fuse links DIN Standard

Protection using LV-Fuse links* TYPE A


operating class gG / gL on the low voltage side

Transformer Line Voltage (kV) LV fuse


rated capacity 6 - 7.2 10 - 12 20 - 24 30 - 36 gG / gL
(kVA) Rated current of the HV-fuse (A) (A)
50 10 - 16 10 6.3 4 - 6.3 63
100 20 - 31.5 16 - 20 10 6.3 - 10 125
125 25 - 40 16 - 25 10 - 16 10 160
160 31.5 - 50 20 - 31.5 16 - 20 10 - 16 200
200 40 - 63 25 - 40 16 - 20 16 250
250 50 - 80 31.5 - 50 20 - 25 16 - 20 315
315 63 - 100 40 - 50 20 - 25 20 - 25 400
400 80 - 100 50 - 80 25 - 40 20 - 25 500
500 100 - 125 63 - 80 31.5 - 50 25 - 31.5 630
630 125 - 160 80 - 125 40 - 63 31.5 - 40 800
800 160 100 - 125 63 40 - 50 1000
1000 160 - 200 125 - 160 63 - 80 40 - 50 1250
1250 250 160 80 50 –
1600 2 x 160 200 100 63 –
2000 2 x 200 250 125 80 –

* Use of the recommended HV-Fuse links in connection with LV-fuse links of other manufacturer must be checked before installation

TYPE A

SIBA HV

SIBA
LV - gG / gL

SIBA LV - gG / gL

HHD 37
HHD FUSES

Recommendation for the protection of main transformer


with HV-Fuse links DIN Standard

Protection without using a common LV-Fuse link on the low voltage side; TYPE B
the individual cable exits
are protected with a LV-Fuse link operating class gL / gG

Transformer Line Voltage (kV)


rated capacity 6 - 7.2 10 - 12 15 - 17.5 20 - 24 30 - 36
(kVA) Rated current of the HV-fuse (A)
50 10 - 16 10 6.3 - 10 6.3 4 - 6.3
100 16 - 31.5 16 - 25 16 10 6.3 - 10
125 20 - 40 16 - 31.5 20 10 - 16 6.3 - 10
160 31.5 - 50 20 - 31.5 20 - 25 16 - 20 10 - 16
200 31.5 - 63 25 - 40 20 - 31.5 16 - 20 10 - 16
250 40 - 80 25 - 40 25 - 31.5 16 - 25 10 - 20
315 50 - 100 31.5 - 50 31.5 16 - 25 16 - 25
400 63 - 100 40 - 63 31.5 - 50 20 - 40 16 - 25
500 80 - 125 50 - 80 31.5 - 63 25 - 50 20 - 31.5
630 100 - 160 63 - 100 40 - 80 31.5 - 63 20 - 40
800 125 - 160 80 - 125 63 - 100 40 - 63 25 - 50
1000 160 - 200 100 - 160 63 - 100 50 - 80 31.5 - 50
1250 250 160 100 80 50
1600 2 x 160 200 125 100 63
2000 2 x 200 250 160 125 80

TYPE B

SIBA HV

SIBA LV - gG / gL

HHD 38
FUSES
HHD
Application recommendation for protection of capacitors
with HV-Fuse links DIN Standard

Assignment of rated currents of HV-Fuse links


to DIN Standard to Capacitor rated capacities

Capacitor Line Voltage (kV)


rated capacity 6 - 7.2 10 - 12 20 - 24
(kVAr) Rated current of the HV-fuse (A)
50 10 6.3 6.3
100 20 10 6.3
200 40 20 10
250 50 25 16
300 63 31.5 16
400 80 40 20
500 100 50 25
750 160 80 40
1000 200 100 50
1250 250 125 63
1600 315 160 80
2000 315 200 100

To control the occuring voltage during switch off Fuse link should be chosen from the next higher voltage range.
e.g. 10 kV Capacitor with 20 kV Fuse links. (See also IEC 549, Chapter II, § 3.2)

HHD 39
HHD FUSES

HV Fuse-bases for indoor application

Rated Voltage 7.2 kV Rated Voltage 12 kV Rated Voltage 24 kV Rated Voltage 36 kV Rated Voltage 24 kV
Part No. 31 001 02 Part No. 31 003 02 Part No. 31 005 02 Part No. 31 007 02 Part No. 31 221 01*

A 13.78 ” (350 mm) A 17.72 ” (450 mm) A 23.62 ” (600 mm) A 27.36 ” (695 mm) A 17.72 ” (450 mm)
B 1.38 ” (35 mm) B 1.38 ” (35 mm) B 1.38 ” (35 mm) B 1.38 ” (35 mm) B 1.38 ” (35 mm)
C 3.35 ” (85 mm) C 3.35 ” (85 mm) C 3.35 ” (85 mm) C 3.35 ” (85 mm) C 3.35 ” (85 mm)
D 0.70 ” (18 mm) D 0.70 ” (18 mm) D 0.70 ” (18 mm) D 0.70 ” (18 mm) D 0.70 ” (18 mm)
E 7.60 ” (193 mm) E 11.54 ” (293 mm) E 17.44 ” (443 mm) E 21.18 ” (538 mm) E 11.54 ” (293 mm)
F 6.14 ” (156 mm) F 6.14 ” (156 mm) F 9.30 ” (236 mm) F 12.83 ” (326 mm) F 9.30 ” (236 mm)
G 12.20 ” (310 mm) G 16.14 ” (410 mm) G 22.60 ” (574 mm) G 26.60 ” (676 mm) G 16.14 ” (410 mm)
H 9.53 ” (242 mm) H 9.53 ” (242 mm) H 12.68 ” (322 mm) H 16.22 ” (412 mm) H 12.68 ” (322 mm)
I 0.60 ” (15 mm) I 0.60 ” (15 mm) I 0.60 ” (15 mm) I 0.60 ” (15 mm) I 0.60 ” (15 mm)
J 2.17 ” (55 mm) J 7.10 ” (180 mm) J 11.80 ” (300 mm) J 14.96 ” (380 mm) J 7.10 ” (180 mm)
K 1.38 ” (35 mm)
L 14.96 ” (380 mm) L 18.90 ” (480 mm) L 24.80 ” (630 mm) L 28.54 ” (725 mm) L 18.90 ” (480 mm)

* Reduced Length for 24


kV Fuse links, E= 292 mm

HHD 40
FUSES
HHD
HV Fuse-bases for outdoor application

Rated Voltage 7.2 kV Rated Voltage 12 kV Rated Voltage 24 kV Rated Voltage 36 kV


Part No. 31 002 01 Part No. 31 004 01 Part No. 31 006 01 Part No. 31 008 01

A 13.78 ” (350 mm) A 17.72 ” (450 mm) A 23.62 ” (600 mm) A 27.36 ” (695 mm)
B 1.38 ” (35 mm) B 1.38 ” (35 mm) B 1.38 ” (35 mm) B 1.38 ” (35 mm)
C 4.72 ” (120 mm) C 4.72 ” (120 mm) C 4.72 ” (120 mm) C 4.72 ” (120 mm)
D 0.80 ” (20 mm) D 0.80 ” (20 mm) D 0.80 ” (20 mm) D 0.80 ” (20 mm)
E 7.60 ” (193 mm) E 11.54 ” (293 mm) E 17.44 ” (443 mm) E 21.18 ” (538 mm)
F 9.33 ” (237 mm) F 9.33 ” (237 mm) F 12.09 ” (307 mm) F 15.24 ” (387 mm)
G 16.14 ” (410 mm) G 20.08 ” (510 mm) G 25.98 ” (660 mm) G 30.91 ” (785 mm)
H 12.80 ” (325 mm) H 12.80 ” (325 mm) H 15.55 ” (395 mm) H 18.70 ” (475 mm)
I 0.60 ” (15 mm) I 0.60 ” (15 mm) I 0.60 ” (15 mm) I 0.60 ” (15 mm)
J 2.17 ” (55 mm) J 7.10 ” (180 mm) J 11.81 ” (300 mm) J 14.95 ” (380 mm)
K 1.38 ” (35 mm)
L 14.96 ” (380 mm) L 18.90 ” (480 mm) L 24.80 ” (630 mm) L 28.54 ” (725 mm)
N 3.15 ” (80 mm) N 3.15 ” (80 mm) N 3.15 ” (80 mm) N 3.15 ” (80 mm)
O 0.43 ” (11 mm) O 0.43 ” (11 mm) O 0.43 ” (11 mm) O 0.43 ” (11 mm)
P 14.57 ” (370 mm) P 18.50 ” (470 mm) P 24.40 ” (620 mm) P 29.33 ” (620 mm)

HHD 41
HHD FUSES

Microswitch Part No.


L= 660 mm 31 001 10
L= 900 mm 31 001 14

Microswitch
Part No. 28 001 04
250 V / 6 A
1 change over contact

Flexible
Cable

HV-Fuse cap
Connection bar
of the
spring clip contact
Part No. 34 002 01

HHD 42
FUSES
HHD
Fuse Clip Part No.
HV-Spring clip contact with connection bar 34 002 01

A 1.38 ” (35 mm)


B 1.26 ” (32 mm)
F 0.24 ” (156 mm)
G 2.80 ” (71.5 mm)
H 3.74 ” (95 mm)
L 3.66 ” (93 mm)
M M 10

Spacer Part No.


31 002 01.3

A 1.26 ” (32 mm)


B 1.38 ” (35 mm)
C 0.24 ” (6 mm)
D 0.40 ” (18 mm)
E 0.20 ” (5 mm)
F 0.70 ” (18 mm)
G 0.26 ” (6.5 mm)

HHD 43
00
HHD FUSES

24 kV Extension adapter for high voltage Fuses 12kV

Part No.
34 006 01

A 1.77 ” (45 mm)


B 0.06 ” (1.5 mm)
C 2.00 ” (51 mm)
D 1.73 ” (44 mm)
F 1.77 ” (45 mm)
G 0.20 ” (5 mm)
H 2.76 ” (70 mm)
L 7.28 ” (185 mm)

HV-Fuse with 24 kV Extension adapter (Part No. 34 006 01)

A 1.77 ” (45 mm)


E1 11.50 ” (292 mm)
E2 17.40 ” (442 mm)
F 1.30 ” (33 mm)
L 20.00 ” (508 mm)

HHD 44
FUSES
HHD
Test-Fuse with time delayed release
for testing the release mechanism in enclosed medium voltage switchgear

Part No.
33 010 03

A 1.77 ” (45 mm)


D 2.76 ” (70 mm)
E 7.56 ” (192 mm)
F 1.34 ” (34 mm)
G 0.30 ” (8 mm) Clamp lever
H 1.06 ” (27 mm) for timer
L 10.24 ” (260 mm)
Force (N)

To change E an adaptor is available


from 192 mm to 292 mm Part No. 34 004 02
from 192 mm to 442 mm Part No. 34 006 02

Travel (mm)

HHD 45
00
HHD FUSES

HV-Contact clip Rated Current for indoor and outdoor application


200 A

Part No.
31 003 02.20

B 1.26 ” (32 mm)


G 2.80 ” (71.5 mm)
H 3.74 ” (95 mm)

HV-Contact clip Rated Current for indoor and outdoor application


> 200 A

Part No.
34 001 01.20

B 1.26 ” (32 mm)


G 2.90 ” (73.5 mm)
H 4.92 ” (125 mm)

HHD 46
FUSES
HHD
Storage holder
for HV- and LV-Fuses

Rated Part No. HV-Fuses LV-Fuses L B T Weight


Voltage (pieces) (pieces) inch mm inch mm inch mm (kg/1)
kV
12 33 004 01 3 6 11.96 304 16.06 408 4.13 105 1.0
24 33 006 01 3 6 17.87 454 16.06 408 4.13 105 1.4
36 33 008 01 3 6 21.65 550 16.06 408 4.13 105 1.9

HHD 47
00
HHD FUSES