Contents
Compressors
Compressors used in PAC-L packaged unit series are hermetically
sealed, compact scroll with the following features:
• High Efficiency.
• Quite operation, Low Sound levels.
Figure 2 : Condenser Fan Motor arrangement for
• Better debris handling. Models PAC-L 52160-52330.
• Self compensating of wear (“wears-in” vs. “wears-out”).
• 70% fewer moving parts than comparably sized reciprocating
compressors
• Internal motor protection / Advanced scroll temperature Evaporator
protection.
• Suction gas motor cooling. Evaporator coils are manufactured from plain copper tubes
• Suction screen. mechanically bonded to aluminium cross wave fins to ensure
• Disc type check valve. optimum heat transfer. All evaporator coils are tested against
• Centrifugal oil pumps with filter and magnet. leakage by air pressure of 300 psig (2068 kPa) under water.
• Brazed fittings or Rotalock options. Coils conform to AHRI-410.
The evaporator section is insulated from all the sides with 1” thick Liquid Line Sight Glass (RSG)
fiber glass insulation with extremely tough and durable black
For monitoring refrigerant charge and to provide visual indication
composite surface. The insulation cum sound liner meets the fire
of moisture presence in the system.
requirements of NFPA90A & 90B and is secured with mechanical
fasteners in addition to water resistant adhesive.
Electric Heating (HC@)
The following electric heaters are available as optional accessories
Control Panel on request. Components include electric heater elements,
magnetic contactors, thermal safety cut-out (manual & auto)
and airflow switch.
The PAC-L packaged Air Conditioners are provided with IP-54
control panel enclosure comprising all starting, operating and MODEL Heater (kW) STAGES
safety controls. PACL
51050
The following are the standard components used in all PAC-L 51060 4.5
series units. 51070
51085 1
• Individual compressor motor contactors. 51095
9
52110
• Condensor & Evaporator Fan motor contactor and overload 52120
relays. 52145
52160
• 24Volts low voltage fused transformer for user supplied and 52180 18 2
installed room thermostat.
52205
52225
• Compressor short cycling protection.
52240
• Control disconnect switch for each circuit. 52260
24 2
52290
• Power and control circuit terminal blocks. 52330
Table 1
• High pressure protector.
Pump Down Facility with solenoid valve (PDS)
• Low pressure protector. The compressors will switch off each time with a pumpdown cycle
in order to prevent Liquid refrigerant migration to the compressor
during off cycle periods.
Code AT-12/12 SC2 AT-12/12 SC2 AT-12/12 SC2 AT-12/12 SC2 AT-15/15 SC2 AT-15/15 SC2 AT-15/15 SC2 AT-15/15 SC2
Fan Blower Qty. 2 2 2 2 2 2 2 2
cfm 6000 6000 7000 7000 8000 8000 9100 10500
Air Flow
l/s 2832 2832 3303 3303 3775 3775 4294 4955
Type Totally Enclosed, Class F insulated, IP55 Protected
Motor
Size kW 2.2 2.2 3.0 3.0 3.0 3.0 3.0 4.0
Refrigerant Operating Charge lbs 22.9 25.9 29.6 29.6 33.4 33.4 45.6 45.6
(R-22) kg 10.4 11.7 13.4 13.4 15.1 15.1 20.7 20.7
lbs 1342.0 1501.0 1640.0 1640.0 1897.0 1902.0 2062.0 2076.0
Operating Weight Approximate
kg 608.6 680.7 743.8 743.8 860.3 862.6 935.1 941.5
Notes: Table 3
*
(1) The capacity ratings are based on EN 14511-2. Evaporator entering air conditions of 80.6°F/66.2°F (27°C/19°C) dry bulb/wet
bulb and condenser entering air temperature of 95°F (35°C) dry bulb.
(2) Evaporator entering air conditions of 80°F/67°F (26.7°C/19.5°C) dry bulb/wet bulb and condenser entering air temperature of
115°F(46°C) dry bulb.
*
(3) Evaporator entering air conditions of 80°F/67°F (26.7°C/19.5°C) dry bulb/wet bulb and condenser entering air temperature of
118.4°F(48°C) dry bulb.
Capacity for all conditions are gross capacity which does not include the effect of evaporator fan motor heat.
* Capacity rating is certified by “TUV SUD Industrie Service GmbH, Germany”.
Notes: Table 4
1. Ratings are based on 80.6°F (27°C) DB evaporator entering air temperature.
2. Capacity rating at 95°F condenser air entering temperature is certified by “TUV SUD Industrie Service GmbH, Germany”.
3. Direct interpolation is permissible. Do not extrapolate.
4. SKM Computer selections are available for quick and accurate selection.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data page (14) should be referred for the same.
Notes:
1. See Page 3 for legend
*
3. Capacity rating at 118.4°F (48°C) condenser air entering temperature is certified by “TUV SUD Industrie Service GmbH,
Germany”.
5. SKM Computer Selections are available for quick and accurate selections..
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
page (14) should be referred for the same.
2. Areas shaded in grey indicate operating range outside the standard motor. Shift to larger motor size in this area.
3. Internal static pressure is based on pressure drops through evaporator coil and fan casing only.
4. Internal static pressure is based on pressure drops through evaporator coil, fan casing and 1” flat filter (if specified).
Legend
MFA Maximum Fuse Amps (for fuse sizing), complies with RLA Rated Load Amps. (at worst operating condition)
NEC Article 440-22 & 430-52. LRA Locked Rotor Amps
FLA Full Load Amps
MCA Minimum Circuit Amps.(for wire sizing), complies with
NEC article 440-33.
ICF Maximum Instantaneous Current Flow
Note :
Voltage imbalance not to exceed ± 2 % of the rated voltage
24V
CCH
* SUITABLEF
TYPICAL WIRINGDIAGRAM SHOWN IS
OR 380~ 415V/3Ph/50Hz ONLY.
CR1 CR2 C3 TDR C1 C2
FOR 440V/3Ph/50Hz PLEASECONSULT SKM.
N
E CONTROL CIRCUIT
T1 T3
OL2 OL3 OL4
T2
CF1 CF2
2A 4A MODELS: PACL-51060,51070,
C1 CS
51085 & 51095
TH (BY OTHERS) C1
C R G Y
C4
CR1 CR2
FCS
TFR
220V-240V
CCH
24V
HPS
M
OL2 OL3
OL4 LPS
TDR
N
E CONTROL CIRCUIT
PTB POWERSUPPLY(V/Ph/Hz)
** L1
L2 * * PROVIDEOVERCURRENT, EARTHFAULTPROTECTION,
L3 SHORTCIRCUITANDDISCONNECTMEANSASREQUIREDBY
N LOCAL& NATIONAL ELECTRICCODE.
C1 C2 C3 C4 C5
L EGEND
C CONTACTOR
T1 T3 T1 T3
T2 T2 OL3 OL4 OL5 CCH CRANKCASEHEATER
CF CONTROLFUSE
CFM CONDENSERFANMOTOR
CFM1 CFM2 EFM
PAC-L Series - R22
CM1 CM2
CM COMPRESSORMOTOR
CS CONTROLSWITCH
CF1 CF2
EFM EVAPORATORFANMOTOR
2A 10A FCS FANCYCLINGSWITCH
HPS HIGHPRESSURESWITCH
C1 C2 LPS LOWPRESSURESWITCH
TH (BYOTHERS) CS1 CS2 C1 C2
OL OVERLOADRELAY
C R G Y1 Y2 PTB POWERTERMINALBLOCK
TFR TRANSFORMER
TH THERMOSTAT
C5 C5
TDR TIMEDELAYRELAY
------ FIELDWIRINGAND
TFR
FIELDSUPPLIEDDEVICES
CR1 CR2 CR3
Typical Wiring Diagram
FCS1 FCS2
24V
CCH1
CCH2
220V-240V
HPS1 HPS2 WIRING DIAGRAM SHOWN IS
M M * TYPICAL
SUITABLE FOR 380~ 415V/3Ph/50Hz ONLY.
OL3 OL4 FOR 440V/3Ph/50Hz PLEASECONSULT SKM.
SKM Packaged Airconditioning Units
OL5
LPS1 LPS2
TDR1 TDR2 MODELS: PACL-52110,52120,52145,
N
52290 & 52330
E CONTROL CIRCUIT
SKM Packaged Airconditioning Units
PAC-L Series - R22
Dimensional Data
PAC-L Models - 51050
10 10
[254] 2 [254]
[51]
A1 A3 LEGEND
4 1 CONTROL PANEL
3 2 COMPRESSOR
AIR IN 3 CONDENSER FAN
4 CONDENSER COIL
5 EVAPORATOR COIL
6 EVAPORATOR FAN
A2 A4 7 EVAPORATOR FAN MOTOR
4-Ø0.79 [20] HOLES DRAIN ALL DIMENSIONS ARE IN INCHES [MM]
FOR ANCHOR BOLTS 2 x FPT 3/4 [19]
42.5
59
[1080]
[1499] 22 1 30
[559] [25] [762]
[30]
1.2
6 = 13.03 =
AIR OUT [331]
11.38
[289]
1 S/A
5
[1124]
44.25
[559]
[126]
2
22
5
R/A
ACCESS PANEL 7
FOR COMPRESSOR 10.8
[100]
[140]
3.94
RIGGING HOLES
5.5
= G =
AIR OUT [25]
1
J
S/A
6
C
[1227]
48.3
[1327]
AIR IN
52.3
5
[126]
B
5
R/A
2 7
[100]
[140]
5.5
4
1 CONTROL PANEL
2 COMPRESSOR
3 CONDENSER FAN
4 CONDENSER COIL
POWER
5 EVAPORATOR COIL
CONTROL
CIRCUIT SOURCE 6 EVAPORATOR FAN
1 DETAIL AT `A' 7 EVAPORATOR FAN MOTOR
ALL DIMENSIONS ARE IN INCHES [MM]
MODEL DIMENSIONS
PACL- L A B C D J G H
[30]
1.2
= G =
6
AIR OUT
S/A
J
C
[1219]
AIR IN
[1319]
5
48
H
52.3
[100]
R/A
3.94
2 7
13.8
[126]
[140]
5.5
5
MODEL DIMENSIONS
PACL- L W A B D J E H C
75 75 60 32 28 13.43 43.7 59.6 7.5
52160 [1905] [1905] [1524] [813] [711] [341] [1109] [1515] [191]
W
L 1
[25] A
D
AIR OUT
[30]
1.2
= E =
6
S/A
JC
[1472]
57.96
[1227]
AIR IN
48.31
5
H
B
[126]
[100]
R/A
3.94
5
2 7
13.8
[140]
5.5
LEGEND
1 CONTROL PANEL
2 COMPRESSOR
3 CONDENSER FAN
4 CONDENSER COIL
CONTROL POWER 5 EVAPORATOR COIL
CIRCUIT SOURCE
6 EVAPORATOR FAN
DETAIL AT `A'
7 EVAPORATOR FAN MOTOR
A2 A4
2
[51] DRAIN 88
101.6
2 x FPT 1[25] [2235]
[2581] 78
69 32.6 [1981]
[1753] [828] = 52.3 =
[30]
6 1.2
[1328]
3
15.91
[404]
S/A
14.03
[356]
[1947]
[1947]
76.65
76.65
[1702]
5
67
[1016]
40
R/A
4 7 13.8
[100]
[126]
[140]
3.94
5.5
ACCESS PANEL
5
52145 354 348 267 252 1221 582 573 469 452 2076
52330 [264] [260] [213] [204] [941]
[161] [158] [121] [114] [554]
MODEL A B C
44 72
PACL- 51050 [1118] [1829]
34
[864]
PACL- 51060
54
B
PACL- 51095
[1372]
60
PACL- 52110
DUCT
[1524]
ALL DIMENSIONS ARE IN INCHES [MM]
[762]
30
A
[762]
30
[762]
DUCT
30
DUCT
B
A
PACL- 51050
B
A
PACL- 51050
A
B
DUCT
A
[762]
30
[762]
30
DUCT
C
B
[762]
30
A
DUCT
A
PACL- 51060 to 52110
MULTIPLE UNIT
[762]
30
30
[762]
DUCT
[762]
30
DUCT
C
A
DUCT
PACL- 52120 & 52145
A
MODEL A B C
B
60
PACL- 52120 [1524]
PACL- 52145 64 PACL- 52120 & 52145
PACL- 52160
PACL- 52180 52 [1626] 88
[1321] 74 [2438]
PACL- 52205
PACL- 52225 [1880]
A
PACL- 52240 82
PACL- 52260
PACL- 52290 [2083]
PACL- 52330
A
DUCT
30
[762]
[762]
30
C
DUCT
DUCT
A
SINGLE UNIT
PACL- 52160 to 52260
MULTIPLE UNIT
• Install the unit in such a location which is flat and strong enough to support its weight.
• Provide a trap of over 2" (50mm) in the drain piping for water seal.
• All field wiring must comply with applicable local and national codes.
• Service spacing should be provided as shown in the figure. If any obstacles are around the unit, distributed air is short-circuited
so that the unit stops frequently and access to the unit is difficult for inspection and aftersales services.
C ON TRO L No obstacle
P ANE L BO X
3000
S .A IR
AIR IN
R.A IR
No obstacle
PACL- 51050 C O NTR OL
P ANE L B OX
PACL- 51060 to 52110
3000
AIR OUT
P O WE R
SO UR CE
CONTROL
CIRCUIT
… … … A IR IN
S .A IR
No obstacle
A IR IN
AIR IN CO NT RO L R.A IR
CIRCUT
AIR IN PA NE L BO X
AIR OUT
PO W ER
S O URCE
AIR IN
S .A IR
AIR IN
R.AIR
AIR OUT
CONTROL CONTROL
AIR IN
AIR IN PANEL BOX CIRCUT
AIR OUT
P OW E R
S O UR CE
A IR IN
S.AIR
S.AIR
R.AIR
GUIDE SPECIFICATIONS
GENERAL REFRIGERANT PIPING
Packaged Air Conditioners shall be composed of Refrigerant circuit piping shall be fabricated from ACR
compressor(s), condenser & evaporator coils with fans, refrigerant grade copper including shut-off valve, filter drier & thermostatic
piping, electrical components & enclosing cabinet in one piece. expansion valve. Suction line shall be insulated with
These units shall be factory assembled, internally wired, fully ½” (12 mm) wall thickness enclosed cell pipe insulation
refrigerant charged with R22, tested under strict quality standards with maximum k factor 0.28 Btu.in/ft2 h°f (0.040 W / m °k).
& are suitable for outdoor installation on rooftop or ground level
with ducted system. These units shall be capable to operate from
50 °F (10°C) to 125.6 °F (52°C) ambient temperature without
failure & shall be rated in accordance with AHRI-340/360 and CASING
AHRI- 210/240 standards. Capacity as per attached schedule. Casing shall be made of hot dip galvanized (zinc coated),
phosphatized steel sheets which are then electrostatically
polyester powder coated to provide an extremely tough, scratch
resistance & excellent anti-corrosive protection. Casing shall
COMPRESSOR(S) pass1000 hours in 5% salt spray testing at 95°F (35°C) & 95%
Compressor shall be hermetically sealed, compact high efficiency relative humidity as per ASTM B117. Evaporator section shall
and low noise scroll type. These compressors are refrigerant gas be sealed with vinyl gaskets & completely insulated faced
cooled, furnished with advanced scroll temperature protection with black glass tissue (BGT) heavy density, fire retardant,
or internal motor protection. permanent odorless fiberglass insulation of minimum
1” (25 mm) thickness and 32 kg/m3 density having maximum
k factor 0.23 Btu.in/ft2 h°f. (0.033 W / m °k). Unit casing shall be
provided with access panels for easy service and maintenance
CONDENSER COIL(S) of all unit parts.
Condenser coils shall be air cooled with integral sub cooler,
constructed of special inner grooved seamless copper tubes
3/8” OD mechanically expanded into waffle louver aluminum cross
fins. These coils shall be tested against leakage by air pressure FILTER SECTION
of 450 psig (3100 kPa) under water, cleaned & dehydrated at Flat Filter Section incorporating 1” (25mm) or 2” (50mm) thick
the factory. filter having an average arrestance efficiency of 54% as per
ASHRAE Standard 52.1 or equivalent can be provided, if desired.
Dubai Riyadh
P.O Box: 98822 )DZD]5HI $LU&RQGLWLRQLQJ&R
Dubai, United Arab Emirates P.O Box: 85123
Tel: +9714 2940 900 Riyadh, Saudi Arabia
Fax: +9714 2940029 Tel: +96 61 4794499
email: dubaisales@skm.ae Fax: +96 61 4785354
HPDLOVDOHHP#IDZD]JURXSFRP
Iraq
$O5DZELWW$O,UDTLD&R Qatar
4DWDURI¿FH
,UDT6DOHV+HDG2I¿FH 0DQQDL7UDGLQJ&R://
P.O Box: 76
Sales Manager : Eng. Ayman Noor
Doha, Qatar
HPDLOD\PDQ#DOUDZDELWWFRP Tel: +974 4455 8787 / 4455 8788
Tel:+964(0)7504973434 Fax: +974 4455 8781
email: dohasales@skm.ae
+HDG2I¿FH0DQDJHPHQW +9$&#PDQQDLFRPTD
HPDLOLQIR#DOUDZDELWWFRP
Egypt
9 Mosadak Street
(UELO2I¿FH
UGÀRRU'RNNL*L]D(J\SW
,WDOLDQ&LW\±+RPH1R Tel: +20 2 7619617 / +20 2 7621974
6DOHV'HSDUWPHQW±(QJ6DLI$EGXO.DULP Fax: +20 2 7621973
Tel:+964(0)7504271698 email: egyptsales@skm.ae
HPDLOVDLIDEGXONDULP#DOUDZDELWWFRP
$O0HVVLOD+9$&(TXLSPHQW)DFWRU\
%DJKGDG2I¿FH 3DUWRI6.0$&IDFWRU\LQ6DXGL$UDELD
6DXGL$UDELD(DVWHUQSURYHQDQFH
Arasat Al-Hindiya Street
$''DPPDPQGLQGXVWULDOFLW\
Near Qamar Al-Zaman Resrt. Abqiq main road Hail Street
6DOHV'HSDUWPHQW±(QJ.KDOLG1RRUL Tel No: +966-3-8123332/4/5
Tel:+964(0)7704249681 Fax No: +966-3-8123337
HPDLONKDOHGQRRUL#DOUDZDELWWFRP +966-3-8123092
%DVUD2I¿FH
%UDG\HDK±1HDU$O6DGU+RVSLWDO
Sales Department
Eng. Ammar Al- Hashemi
Tel:+964(0)7710010030
HPDLODPRQHP#DOUDZDELWWFRP
31
www.skm.ae
Air Conditioning Equipment . Built in the Gulf... for the World
24 070/2012 A