T-348 - 072012 Air Condiction Mci D4500
T-348 - 072012 Air Condiction Mci D4500
T-348 - 072012 Air Condiction Mci D4500
REV. 07/2012
DANGER
Indicates an immediate hazard which WILL result in severe personal injury or death.
WARNING
Indicates hazards or unsafe conditions which COULD result in severe personal injury or death.
CAUTION
Indicates potential hazards or unsafe practices which COULD result in minor personal injury, product or
property damage.
WARNING
Be sure to observe warnings listed in the safety summary in the front of this manual before
performing maintenance on the hvac system
WARNING
Read the entire procedure before beginning work. Park the coach on a level surface, with park
ing brake applied. Turn main electrical disconnect switch to the off position.
WARNING
Do not use a nitrogen cylinder without a pressure regulator
WARNING
Do not use oxygen in or near a refrigeration system as an explosion may occur.
WARNING
The filter-drier may contain liquid refrigerant. Slowly loosen the ORS hex nuts to avoid refriger
ant contact with exposed skin or eyes.
WARNING
Battery disconnect should be off.
WARNING
Extreme care must be taken to ensure that all the refrigerant has been removed from the com
pressor crankcase or the resultant pressure will forcibly discharge compressor oil.
CAUTION
Do not under any circumstances attempt to service the microprocessor. Should a problem de
velop with the microprocessor, replace it.
CAUTION
Use care when checking/manipulating wires/plugs attached to the Logic Board. Damage to
the board or wiring harness can occur.
Connection Kit
PID Condenser
PID Evaporator
Controller Kit
Electrical Kit
Air Exchange
Evaporator
Condenser
Evaporator
Evaporator
Condenser
Evaporator
Evaporator
Condenser
Blower Kit
Skins Kit
Skins Kit
AC353C
AC353E
In Dash
Fan Kit
MODEL
S/D
Kit
68AC353
7 8
6 9
4 5
2
12 Dash--Air
Option
11
1 10
13
1
6
PID
Model/Serial
Number Tag
7
4
1 8
3
2
3
13 6
5
10
1 12
2
4
11
9
8
7
PID
Model/Serial
Number Tag
FRESH AIR
COACH RETURN
AIR FILTER
EVAPORATOR
Return To Ambient
From Ambient Through Fan Through Fan From Ambient
24
18 14
11 12 11
2 5 13
3
4
1
6
10 7
9
8
LEGEND
INLET
OUTLET
BOOST
PUMP
EVAPORATOR
AC 353
MAIN ENGINE /
RADIATOR
2 1 5
9 5 3 2 1 8
4
7
J3
J
7
J4
J7
J6
J8
J2
J
5
J1
a. Relays d. LEDS
K1 Energizes evaporator fans in low speed D 2 Evaporator fans output active -- high
K2 Energizes evaporator fans in high speed speed
(not energized in low speed). D 6 Evaporator fans output active.
K 7 Energizes condenser fans in low speed D26 Condenser fans output active.
K 8 Energizes condenser in high speed D30 Condenser fans on high speed
(not energized in low speed). D51 A/C clutch and liquid line solenoid valve
K13 Energizes the A/C clutch and liquid line output active.
solenoid valve. D54 Unloader 1 output active.
K14 Energizes unloader 1. D57 Unloader 2 output active.
K15 Energizes unloader 2. D63 Heat output active (RCV).
K16 Energizes fresh air damper. D66 Fault output active.
K17 Energizes reheat coolant valve. D69 Boost pump output active.
K18 Energizes the fault light output. D72 Driver’s liquid line solenoid valve active.
K19 Energizes the boost pump. D17 Fresh air relay fuse out.
K20 Energizes the driver’s liquid line solenoid D38 Unloader 1 relay fuse out.
valve. D18 Evaporator fan motor relay fuse out.
b. Connectors D68 Fault light out relay fuse out.
JA Relay board connector(communication D47 Unloader 2 relay fuse out.
to system). D61 Heater relay fuse out.
JB Boost pump. D90 Clutch relay fuse out.
JC Ribbon Cable (Logic Module to Relay D77 Unloader 1 fuse out.
Board) D31 Condenser motor fan relay fuse out.
c. Fuses D83 Boost pump relay fuse out.
F1 Fresh air relay.
F2 Unloader 1 relay.
F3 Evaporator fan motor relay.
F4 Fault light out relay.
F5 Unloader 2 relay.
F6 Heater relay.
F7 Clutch relay.
F8 Spare.
F9 Condenser motor fan relay.
F10 Boost pump relay.
1 8
9 15
16 23
1 2 3 4 5 6
11 10 9 8
COOL
3°F HIGH SPEED 3°F
LOADED
COOL
2°F HIGH SPEED 2°F
4 CYLINDERS
COOL
1°F LOW SPEED 1°F
2 CYLINDERS
SETPOINT SETPOINT
--2°F --2°F
HEAT
--3°F --3°F
HEAT
LOW SPEED
--4°F --4°F
Cool Heat
Figure 2-1 Capacity Control Diagram
Cooling is accomplished by energizing the Relay Board mounted unloader outputs control the
compressor and condenser fans, opening the liquid capacity of the compressor by energizing or
line solenoid valve and closing the heating valve. de-energizing unloader solenoid valves. The model
Once interior temperature reaches the desired set 05G compressor has three banks of two cylinders
point, the system may operate in the clutch cycle or each. Energizing a valve de-activates a bank of
reheat mode. Selection of clutch cycle or reheat is cylinders. The outboard cylinder banks of the 05G
factory programmed in accordance with the bus are equipped with unloader valves (UV1 and UV2),
purchase specification. each controlling two cylinders; this allows the 05G to
be operated with two, four or six cylinders.
A controller programmed for clutch cycle will Whenever the compressor is started, the unloaders
de-energize the compressor clutch and allow the are energized for a preset delay time to reduce
system to operate in the vent mode until further starting torque. After the delay, unloaders may be
cooling is required. de-energized. Any subsequent changes between
A controller programmed for reheat will maintain energizing and de-energizing the unloaders for
compressor operation and cycle the heat valve to temperature control is also staged for a preset delay
allow reheating of the return air. In the reheat mode time. Once an unloader is energized for pressure
interior temperature is maintained at the desired set control, it remains energized for two minutes to
point while additional dehumidification takes place. prevent short cycling. Only one unloader may
change state at a time when staging is required.
2.3.3 Heating Mode Operating parameters for temperature control,
suction pressure control and discharge pressure
In the heat mode the liquid line solenoid is closed and control are as follows.
the compressor and condenser fans are shut down.
The heat valve is opened to allow a flow of engine a. Temperature Control
coolant through the heat section of the evaporator The unloaders are used to control system capacity by
coil. The evaporator fans speed is varied as required controlling compressor capacity.
to circulate air over the evaporator coil based on the
temperature difference from setpoint. 1. Compressor Unloader UV1 Relay. When return
air temperature falls to less than 2°F (1.1°C)
Operation in the heating mode is controlled by the above set point unloader UV1 is energized. If
water temperature switch (WTS). The WTS is temperature rises to greater than 3°F (1.7°C)
located on the engine block of the vehicle and is above set point, UV-1 will be de-energized to
provided by the OEM. It senses the engine coolant place the compressor at 100% capacity.
temperature and reverses its contacts on
temperature rise at 105°F. The switch prevents the 2. Compressor Unloader UV2 Relay. When return
circulation of cooler air throughout the vehicle as the air temperature falls to less than 1°F (0.6°C)
engine comes up to temperature. above set point unloader UV2 is energized. If
temperature rises to greater than 2°F (1.1°C)
2.3.4 Boost Pump above set point, UV-2 will be de-energized to
place the compressor at 66% capacity.
When the unit is in the heat mode, and if a boost
pump is supplied by the coach manufacturer, the b. Suction Pressure
boost pump relay is energized, providing 24 VDC to The unloaders are used to control suction pressure
activate the boost pump. and thereby prevent coil frosting:
2.3.5 Vent Mode 1. Compressor Unloader UV1 Relay. When the suc
In the vent mode the evaporator fans are operated to tion pressure decreases below 26 psig, unloader
circulate air in the bus interior. UV1 is energized unloading a cylinder bank (two
cylinders); this output will remain energized until
2.3.6 Compressor Unloader Control the pressure increases to above 34 psig.
CAUTION
Do not under any circumstances attempt to service the microprocessor. Should a problem de
velop with the microprocessor, replace it.
3.1 SELF DIAGNOSTICS number of times that the Logic Board STATUS and
CODE LED's (see Figure 1-10) flash
A self test is performed by the Micromax Logic simultaneously. The Micromate control panel
Board each time the board is powered up. Errors, if display will indicate errors with the code ER-#,
any, will be indicated and the unit will not be allowed where “ER” is the error prefix and # is the error
to start. The error codes can be read by counting the number.
Table 3-1 Error Codes
CODE NAME DESCRIPTION
ER 1 Data Memory Logic board data memory failure.
ER 2 Program Memory Logic board program memory failure.
ER 3 A/D A/D and multiplexer failure.
ER 4 Communication Failure Failure in communication between the logic board and MDST.
ER 5 Program Memory Display program memory failure.
3.2 SYSTEM ALARMS VENT key to scroll back, only the alarm code will be
shown, the alarm time will not be shown. If the
3.2.1 Alarm Codes AUTO key is held down for five seconds while “---”
The Micromax Logic Board continuously monitors is displayed all inactive alarms are cleared. A listing of
system parameters and will generate an ALARM if a alarm codes is provided in Table 3-2.
parameter exceeds preset limits. Alarms are indicated 3.2.2 Activation
and the controller will respond in accordance with When alarms are detected, they are placed in an alarm
the information provided in Table 3-2. The alarm queue in the order at which they initiated unless the
codes can be read by counting the number of times alarm is already present. Each alarm recorded will
that the Logic Board CODE LED (see Figure 1-10) also capture an evaporator hour meter reading
flashes. Each alarm code is a two digit number, the corresponding to the activation time. If the AUTO
first set of flashes is the first digit and (after a slight key is pressed while an alarm is displayed, the
pause) the second set of flashes is the second digit. activation time capture will be shown.
The Micromate control panel display will indicate 3.2.3 Alarm Queue
alarms with the code A-## or i-##, where “A” is an The alarm queue consist of 10 alarm locations. When
active alarm prefix, “i” is an inactive alarm prefix and the alarm queue is full the Logic Board will take the
## is the alarm number. If no alarms are present, the required action but the alarm will not be recorded.
display will show “---”. To access the alarm codes, When this situation occurs, an “Alarm Queue
press the UP and DOWN arrow keys at the same Full”alarm will be generated. When the alarms are
time and hold for 3 seconds. If multiple alarms are viewed this will be the first alarm to be shown.
present the user can scroll through each alarm by
pressing the AUTO key. When the end of the alarm 3.2.4 Alarm Clear
list is reached the display will show “---”. Press The user may clear inactive alarms using the
VENT to scroll backward from the latest alarm to Micromate control panel keypad. Refer to paragraph
the earliest alarm in the queue. When using the 3.2.1.
WARNING
Be sure to observe warnings listed in the safety summary in the front of this manual before
performing maintenance on the hvac system.
WARNING
Read the entire procedure before beginning work. Park the coach on a level surface, with
parking brake applied. Turn main electrical disconnect switch to the off position.
NOTE
Following completion of all maintenance or service activities, the alarm queue should be cleared of any
original alarms and any alarms generated during service. Refer to paragraph 3.2.1
NOTE
To avoid damage to the earth's ozone layer, use a refrigerant recovery system whenever removing refrig
erant. When working with refrigerants you must comply with all local government environmental laws.
4.1 MAINTENANCE SCHEDULE
SYSTEM REFERENCE
SYSTEM
ON OFF SECTION
a. Daily Maintenance
X Pre-trip Inspection - after starting 2.2
X Check tension and condition of V-belt None
b. Weekly Inspection
X Perform daily inspection See above
X Check condenser, evaporator coils and air filters for cleanliness Figure 1-5
X Check refrigerant hoses and compressor shaft seal for leaks 4.6
X Feel filter-drier for excessive temperature drop across drier 4.11
c. Monthly Inspection and Maintenance
X Perform weekly inspection and maintenance See above
X Clean evaporator drain pans and hoses None
X Check wire harnesses for chafing and loose terminals Replace/Tighten
X Check fan motor bearings None
X Check compressor mounting bolts for tightness None
X Check fan motor brushes None
CAUTION
Figure 4-3 Suction or Discharge Service Valve
To prevent trapping liquid refrigerant in
4.4.1 Installing R-134a Manifold Guage Set
the manifold gauge set be sure set is
A R-134a manifold gauge/hose set with self-sealing brought to suction pressure before dis
hoses is required for service of models covered connecting.
within this manual. The manifold gauge/hose set is
available from Mobile Climate Control Transicold. 3. Backseat the low side service valve. Backseat both
(Mobile Climate Control P/N 07-00294-00, which field service couplers and frontseat both manifold
includes items 1 through 6, Figure 4-4). To perform set hand valves. Remove the couplers from the
service using the manifold gauge/hose set, do the access valves.
following:
4. Install both service valve stem caps and access
a. Preparing Manifold Gauge/Hose Set For Use valve caps (finger-tight only).
8
6 7
12 1
11 COMPRESSOR
20
23
EVAPORATOR
22
21 18 13
15
20 19
16
14
12
17
S D
4 2 3
5
8 6
10 7
1 9
COMPRESSOR
There are only three possible valve malfunctions: coil 4.12.3 Replace Entire Valve
burnout, failure to open, or failure to close. a. Perform a low side pump down. Refer to para
Coil burnout may be caused by the following: graph 4.5.1.
1 Improper voltage. b. Remove coil assembly. Refer to paragraph 4.12.1.
2 Continuous over-voltage, more than 10% or un c. Disconnect valve from liquid line and filter-drier.
der-voltage of more than 15%.
d. Unbolt valve body from frame and remove from
3 Incomplete magnet circuit due to the omission of unit. See Figure 4-9, item 8.
the coil housing or plunger.
e. Install new valve onto frame.
4 Mechanical interface with movement of plunger
which may be caused by a deformed enclosing f. Apply a light coat of oil to the O-Rings and con
tube. nect the liquid line and the filter-drier.
Failure to open may be caused by the following: g. Leak check connections.
1 Coil burned out or an open circuit to coil connec h. Evacuate low side and re-open charge isolation
tions. valve.
2 Improper voltage.
i. Replace coil assembly and test operation.
3 Defective plunger or deformed valve body assem
bly.
1
Failure to close may be caused by the following:
2
1 Defective plunger or deformed valve body assem 3
bly.
2 Foreign material in the valve. 4
4.12.1 Coil Replacement
5
a. It is not necessary to remove the refrigerant charge
from the system. 6
b. Place main battery disconnect switch in OFF posi 7
tion and lock.
c. Disconnect wire leads to coil.
d. Remove coil locking nut and O-Ring, then the
threaded collar.
e. Lift coil from enclosing tube and replace. 8
f. With the coil installed replace the threaded collar,
then the O-Ring and locking nut. 1. Locking Nut 5. Plunger Assembly
2. O--Ring 6. O-Ring
g. Connect wire leads and test operation 3. Threaded Collar 7. Body
8. Mount
4.12.2 Internal Part Replacement 4. Coil
a. Perform a low side pump down. Refer to para
graph 4.5.1 . Figure 4-9 Liquid Line Solenoid Valve
CAPSCREWS
BYPASS (NOT INTERCHANGEABLE WITH
PISTON CONTROL VALVE SCREWS)
PLUG 1. Compressor 6. Armature
2. Seal Cover 7 Spacer Nuts
Figure 4-13 Removing Bypass Piston Plug 3. Coil 8. Retaining Capscrew,
4. Rotor Lockwasher, 3/8 Washer
h. Remove the pressure switches and install on re 5. Rotor Nut
placement compressor after checking switch op
eration. Refer to paragraph 4.10. Figure 4-14 Compressor Clutch
A B
4.17 PRESSURE TRANSDUCER CHECKOUT
NOTE
System must be operating to check transduc
ers. Figure 4-15 Transducer Terminal Location
Configuration Description
High Reheat - When this configuration is removed, the unit will default to high speed in reheat mode and
A in the low speed cool band. If not removed, heat/reheat will default to low speed.
High Vent - When this configuration is removed, the unit will default to high speed in vent mode. If not
B* removed vent mode will default to low speed.
C* Dry Heat - When this configuration is removed, the unit will run on 100% reheat instead of heat.
Reheat/Cycle - When the reheat cycle configuration is removed, the unit is in reheat mode. The default
D configuration is cycle clutch mode.
E Transducers - When the transducer configuration is removed, transducers will assume to be present.
Refrigerant R-22/R-134a - When the refrigerant configuration is removed, the refrigerant is set for R-22.
F* The default refrigerant is R-134a.
G Unit Type - Rearmount unit enabled with “G” removed and “H” installed.
H Unit Type - With “H” removed and “G” installed, roof top unit will be enabled.
I Factory - Reserved for the manufacturer.
Invert H2O - When this configuration is removed, the logic for the water temperature switch will be in
J* verted.
K Voltage - When this configuration is removed, the voltage selection will be changed from 12 to 24 vdc.
L Factory - Reserved for the manufacturer.
Psig/Bars - When this configuration is removed, the display will indicate pressures in bars. When not re
M* moved, the display will indicate pressures in psig.
°C/°F - When this configuration is removed, the display will show temperatures in °F. When not removed
N the display will show temperatures in °C.
PI Reheat - When this configuration is removed, reheat mode will use the PI algorithm to vary the duty
O* cycle of the heat valve. If it is not removed, the heat valve will be on constantly.
Low Ambient Lockout - When this configuration is removed, the compressor clutch will disengage at 25°F.
P* With this configuration in place, the compressor will disengage at 45°F.
5-1 INTRODUCTION
This section includes electrical wiring schematics covering the models listed in Table 1-2. For applications with
OEM supplied operating switches, the switches are wired to the Logic Board connector J3 as shown. For units
with a Micromate control panel as the operators control, there is no wiring to the Logic Board J3 connector,
instead the Micromate control panel is hard wired to the Logic Board connector J2. When the micromate
control panel is used for service or diagnostic purposes, it is wired in the same manner as shown for drivers panel
use, thru the optional Service Port. Contact your Mobile Climate Control service representative or call the
technical hot line at 800-450-2211 for questions related to the schematic for your specific model.
Figure 5-1. Wiring Schematic - Legend (PM Motors) - 68AC353-102, 102-4, 102-5
98--63069
Figure 5-2. Wiring Schematic - Control Circuit (PM Motors) - 68AC353-102, 102-4, 102-5
98--63069
Figure 5-3. Wiring Schematic - Power Circuit (PM Motors) - 68AC353-102, 102-4, 102-5
Figure 5-4. Wiring Schematic - Legend (Brushless Motors) (CAN) - 68AC353-102-1, 102-3, 102-6
98--63098
Figure 5-5. Wiring Schematic - Control Circuit (Brushless Motors) (CAN) - 68AC353-102-1, 102-3, 102-6
98--63098
Figure 5-6. Wiring Schematic - Power Circuit (Brushless Motors) (CAN) - 68AC353-102-1, 102-3, 102-6
98--63098
Figure 5-7. Wiring Schematic - Condenser Circuit (Brushless Motors) (CAN) - 68AC353-102-1, 102-3, 102-6
98--63098
Figure 5-8. Wiring Schematic - Evaporator Circuit (Brushless Motors) (CAN) - 68AC353-102-1, 102-3, 102-6
Figure 5-9. Wiring Schematic - Legend (Brushless Motors) - 68AC353-102-2 & 102-7
98--63116
Figure 5-10. Wiring Schematic - Control Circuit (Brushless Motors) - 68AC353-102-2 & 102-7
98--63116
Figure 5-11. Wiring Schematic - Control Board Power Circuit (Brushless Motors) - 68AC353-102-2 & 102-7
98--63116
Figure 5-12. Wiring Schematic - Condenser Motor Power Circuit (Brushless Motors) - 68AC353-102-2 & 102-7
98--63116
Figure 5-13. Wiring Schematic - Evaporator Motor Power Circuit (Brushless Motors) - 68AC353-102-2 & 102-7
D M
DESCRIPTION, 1-1 Maintenance Schedule, 4-1
Diagnostics, 2-1, 2-4, 2-5 Micrormate Control Panel, 2-1, 3-1
Discharge Check Valve, 1-4 Modes Of Operation, 2-2
Discharge Pressure, 2-4
N
E Noncondensibles, Check For, 4-9
Evacuation, 4-8
Evacuation, One Time, 4-8 O
Evacuation, Triple, 4-8 Oil Level, 4-16
Evaporator Fan, 1-8, 2-4 Operating Controls, 1-8
S
V
SAFETY DEVICES, 1-9
Vent Mode, 2-3
Self Diagnostics, 3-1
SERVICE, 4-1
Service Valves, 4-3 W
Suction Pressure, 2-3 Water Temperature Switch, 1-8, 1-9
Superheat, 4-12 Wiring Schematics, 5-1
www.mcc-hvac.com
Member of MCC Group S Certified ISO 9001 and ISO 1 4001.
Specifications subject to change without notice. MCC is a registered trademark.