SITE INSPECTION AND TEST RECORD

Contract No:
PIC P - 7703
Name of Substation: 10J SUBSTATION
Description: F50/51 P142 RELAY TEST RESULT
Panel: Location: Page 1 of 4

1. RELAY IDENTIFICATION:

Designation Bay Name


Manufacturer MICOM Binary Input Supply 125V
Auxiliary Voltage Rated Frequency 60Hz
Ordering Number P142 Serial Number
34500 115
CT Ratio 1200/1A VT Ratio /
√3 √3

2. RELAY CHECKS:

Sr. No. Relay Checks Status


1 Visual Inspection / Rating Information
2 Case Earthing
3 Ferrule check
4 Wiring against Diagram Checked

3. BINARY INPUT TEST (With Relay Energized):

INPUT# TERMINALS STATUS

TESTED BY WITNESSED BY
xx/xx/20xx
ALFANAR T&C SIEMENS MARAFIQ RCA
Name Eng. Eng. Eng. Eng.
Signature
SITE INSPECTION AND TEST RECORD

Contract No:
PIC P - 7703
Name of Substation: 10J SUBSTATION
Description: F50/51 P142 RELAY TEST RESULT
Panel: Location: Page 2 of 4

4. LED CHECK:

OPTO INPUT NO. STATUS


LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8

5. BINARY OUTPUT TEST (Relay Energized):

OUTPUT # CONTACT # STATUS

6. ANALOGUE INPUT MEASUREMENT TEST:

Calculated Values Measured Values


Measured Item Injected Values
Primary Angle Primary Angle
IA 5∟0°
IB 5∟-120°
IC 5∟120°
IN 5∟0°
VAB 69.28∟0°
VBC 69.28 ∟-120°
VCA 69.28∟120°
Frequency 60

TESTED BY WITNESSED BY
xx/xx/20xx
ALFANAR T&C SIEMENS MARAFIQ RCA
Name Eng. Eng. Eng. Eng.
Signature
SITE INSPECTION AND TEST RECORD

Contract No:
PIC P - 7703
Name of Substation: 10J SUBSTATION
Description: F50/51 P142 RELAY TEST RESULT
Panel: Location: Page 3 of 4

8. SECONDARY INJECTION TESTS FOR O/C & E/F UNIT:

a- Relay Operating Value as Per IDMT (IEC normal inverse used is IEC curve A)

¿=,(Ip pick up)=,(Ig pick up)=,Tp=¿


Injected Expected Time Operating Time (sec)
FUNCTION
Current (A) (sec) R Y B N

Normal Inverse

Tolerance: Timers: ± 2% or 50ms whichever is greater (manual page: 26/132)


0.14 × Tp
Normal Inverse t (s)= 0.02
I
( ) −1
Ip
b- OC/EF Pick up & Drop Off Test (IDMT):

Tolerance: I > Pick-up: Setting ±5% or 20 mA & I > Drop-off: 100% of setting ±5% or 20 mA(manual page:
26/132)

Iset I > A Iset I > A


R Y B N
P.U (A) D.O (A) P.U (A) D.O (A) P.U (A) D.O (A) P.U (A) D.O (A)

c- Relay Operating Value as Per DMT:

TIMING SET (sec)


R Y B N
Exp (s) Actual (s) Exp (s) Actual (s) Exp (s) Actual (s) Exp (s) Actual (s)

d- OC/EF Pick up & Drop Off Test (DMT):

Iset I > A Iset I > A


R Y B N
P.U (A) D.O (A) P.U (A) D.O (A) P.U (A) D.O (A) P.U (A) D.O (A)

TESTED BY WITNESSED BY
xx/xx/20xx
ALFANAR T&C SIEMENS MARAFIQ RCA
Name Eng. Eng. Eng. Eng.
Signature
SITE INSPECTION AND TEST RECORD

Contract No:
PIC P - 7703
Name of Substation: 10J SUBSTATION
Description: F50/51 P142 RELAY TEST RESULT
Panel: Location: Page 4 of 4

9. CBF TEST:

a. Pick up test
PICK-UP CURRENT (A) DROP OFF CURRENT (A)
Set
value(A) R Y B R Y B
0.1
0.15

Tolerance: 2 % of the setting value or 1 % of the rated current

b. Timing Test for CBF:

Set Time Operating Time at 2 * I set (ms)


Set value(A)
(sec) R Y B
0.1 0.15
0.15 0.15

Tolerance: 1 % of the setting value or 15ms

TESTED BY WITNESSED BY
xx/xx/20xx
ALFANAR T&C SIEMENS MARAFIQ RCA
Name Eng. Eng. Eng. Eng.
Signature