SEPARABLE CONNECTORS AND BUSHINGS
INTERFACE B
Dia. 56±0.2
Dia. 46±0.2
Dia. for
0
pin 14 -0.04
40
min
90±0.2
11
min
Dia. 70±0.2
In mm.
01/2022
CONNECTING POSSIBILITIES
Equipment
interface dead-ending
of equipment
(K)(M)400DR
Dead-end receptacle
(K)(M)400T1
Equipment bushing
(K)(M)400AR-1
Equipment bushing
one cable to
equipment
(K)(M)400AR-2 (K)(M)400LR/G
Equipment bushing Elbow connector
(K)(M)400AR-8
Equipment bushing
(K)400SFR-P
Equipment bushing
cable
isolation
(K)(M)400SOP
Stand-off plug
cable
earthing
400GP
Earthing plug
01/2022
400LR INTERFACE B
ELBOW CONNECTOR
APPLICATION TECHNICAL
Separable elbow connector CHARACTERISTICS
(plug-in type) designed to • The thick conductive EPDM jacket
connect polymeric insulated cable provides a total safe to touch
to equipment (transformers, screen which ensures safety for
switchgear, motors...). personnel.
• Each separable connector is
tested for AC withstand and
partial discharge prior to leaving
the factory.
DESIGN 200 mm
Separable connector
comprising: 6/10 (12) kV
1. Conductive EPDM insert. 6.35/11 (12) kV
2. Conductive EPDM jacket. 8.7/15 (17.5) kV
3. Insulating EPDM layer. 12/20 (24) kV
4. Type B - interface as described 12.7/22 (24) kV
by CENELEC EN 50180 and
4
18/30 (36) kV
50181. 5 19/33 (36) kV
5. Conductor connector. 1
6. Cable reducer. 8 Up to 36 kV - 400 A
7. Earthing lead. 2
3 9
8. VD point. 285 mm
9. Conductive rubber cap.
connector.
6
SPECIFICATIONS AND
STANDARDS
The separable connector 400LR
meets the requirements of
CENELEC HD 629.1.
4
KIT CONTENTS The kit also comprises silicone grease,
gloves, wipers, roll adhesive tape and
The complete (K)(M)400LR/G
installation instructions.
elbow connector kit comprises the
following components:
400LR/G-W-X
connector kit
TABLE X
For use with For use with Alupe or For use with For applications Components can be
copper tape C 33-226 cables. other cable types. outdoors and in ordered individually. 5
screened cables. Please contact our Please contact our humid climate.
Order: Kit MT. representative. representative. Order: +MWS.
400T1/400AR-1 /400AR-2 INTERFACE B2
EQUIPMENT BUSHINGS
APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with oil fluid, typically for Each bushing is tested for
transformers, switchgear, AC withstand and partial
capacitors... discharge prior to leaving the
factory.
SPECIFICATIONS AND
STANDARDS
The plug-in type equipment 6/10 (12) kV
bushings are moulded epoxy
103
6.35/11 (12) kV
insulated parts and meet the 8.7/15 (17.5) kV
requirements of IEC 60137. The 12/20 (24) kV
(K)(M)400T1 also meets CENELEC C
12.7/22 (24) kV
EN 50180 . 10
18/30 (36) kV
A Up to 36 kV - 400 A
ORDERING INSTRUCTIONS
Minimum oil level: Dia.
- 12 kV: 40 mm H
- 24 kV: 50 mm
To order the equipment bushing, - 36 kV: 75 mm
specify the type.
The bushings are supplied with an E
earth jumper (/J) or an earth plate
(/GS). This earth connection must D
Dia. 70
be specified when ordering. Dia. F
E.g. K400AR-1/J. Dia. G
In mm.
6
FIXINGS FOR EQUIPMENT BUSHINGS
400AR-2/GS BUSHING 400AR-2/J BUSHING 400AR-1/J AND 400T1/J
BUSHINGS
bushing
bushing interface interface
fixing studs
fixing studs
fixing flange
fixing flange B DIN 42 538
equipment
equipment
sealing gasket
sealing gasket
equipment
equipment
connection
connection
earth
jumper
earth
plate
earth
jumper
APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with oil fluid, typically for Each bushing is tested for
transformers, switchgear, AC withstand and partial
capacitors... discharge prior to leaving
the factory.
SPECIFICATIONS AND
STANDARDS
The plug-in type equipment 6/10 (12) kV
bushings 400AR-8 are moulded 6,35/11 (12) kV
epoxy insulated parts and meet 8,7/15 (17,5) kV
the requirements of CENELEC EN 12/20 (24) kV
50180 and IEC 60137. 28 231.5 12,7/22 (24) kV
18/30 (36kV)
Minimum oil level: Dia.
8.5 19/33 (36kV)
- 12 kV: 40 mm 20 80
- 24 kV: 50 mm
- 36 kV: 75 mm Up to 36 kV - 250 A
20
M10
In mm.
01/2022
8
FIXINGS FOR EQUIPMENT BUSHINGS
400AR-8/J BUSHING BUSHING CLAMPING KIT
To order the bushing clamping kit,
according to DIN 42 538 stand-
ards, simply specify: KBC - RING
bushing interface CLAMP 1 DIN 42538.
Contents: - 1 x fixing flange A
- 4 x stud clamp E
4 x fixing stud M10 - 1 x sealing gasket.
A DIN 42 538
fixing flange
E DIN 42 538
stud clamp
equipment
sealing gasket
FIXING DIMENSIONS
equipment STANDARDS DIN 42 538
connection
German standards.
M10
Min. 55
earth jumper Max. 30
4 fixing
studs Dia. 78
Dia. 123
In mm.
9
400SFR-P INTERFACE B
EQUIPMENT BUSHING
APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with SF6 gas. Each bushing is tested for
AC withstand and partial
discharge prior to leaving the
factory.
DESIGN Dia. 70
The equipment bushing is a
moulded epoxy insulated part with 6/10 (12) kV
a connector interface in accordance 6.35/11 (12) kV
with CENELEC EN 50181. 8.7/15 (17.5) kV
The 400SFR-P bushing has a shank 12/20 (24) kV
outside this standard, adapted for 12.7/22 (24) kV
use in SF6 gas.
218
Up to 24 kV - 400 A
SPECIFICATIONS AND
STANDARDS 33
The plug-in type equipment
bushing 400SFR-P meets the
requirements of CENELEC EN
50180 and IEC 60137.
95
ORDERING INSTRUCTIONS
To order the equipment bushing,
simply specify the type.
M12
Dia. 25
Dia. 70
Dia. 109
In mm.
10
FIXINGS FOR EQUIPMENT BUSHINGS
UNMOUNTED
earth
60° connection
M4
60° 60°
30°
83
M6
Dia. 91.5
Dia. 103.1
equipment
MOUNTED
Dia. 4
97.5
Dia. 100
equipment
connection
earth
connection
bail sealing M4 In mm.
tab O-ring
gasket
6 fixing
screws
M6
11
ACCESSORIES
Up to 36 kV
01/2022
12
KIT MT ORDERING INSTRUCTIONS
EARTHING KIT FOR COPPER Order
TAPE SCREENED CABLES Kit MT for 12 kV, 24 kV
Contains a tinned copper braid or 36 kV applications.
(25 mm² - L=500 mm), a tinned
copper wire for cleating and water
sealing mastic.
13
POSSIBLE ARRANGEMENTS
stand-off
plug
earthing
plug
In mm.
01/2022
14