INTERFACE B

MEDIUM VOLTAGE COMPACT


SEPARABLE CONNECTORS
CATALOGUE 2022
NEXANS NETWORK SOLUTIONS DIV. EUROMOLD

COMPANY PRESENTATION

EUROMOLD International standards Laboratory accreditation


Euromold is the leading All our products meet the Since June 2000, Euromold’s
European specialised designer, International standards like independent ELAB laboratory
manufacturer and distributor of CENELEC HD 629.1, CENELEC obtained the BELAC accreditation
prefabricated cable accessories EN 50180, IEC 60137, no.144-TEST conform with
for medium voltage energy IEC 60502-4… or country the European standards for
distribution. Euromold provides a specifications. Official certificates, laboratories ISO 17025 for
complete range of accessories for CESI, KEMA, ATEX… prove the electrical testing of low and
underground cables: premoulded conformity of our products. medium voltage cable accessories
EPDM rubber connectors for Long duration tests of existing or according to the international
cables and epoxy bushings for new products are continuously standards EN 50393, IEC 60502-
transformers and switchgear, as performed in our test fields. 4, IEC 61442 and HD 629.
well as a large range of cold-
shrinkable terminations and joints
from 12 to 42 kV.
Euromold is also the manufacturer
of electrical components for the
high voltage accessories of the
Nexans group.

ISO 9001 Certificate


Since 1992, Euromold’s
commitment to quality is
demonstrated by its ISO 9001
certification.

While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility
can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or
modify the characteristics of its products described in this catalogue as standards and technology evolve.
SEPARABLE CONNECTORS AND BUSHINGS
INTERFACE B

TABLE OF CONTENTS INTERFACE B


400LR - elbow connector Dimensions according to European
400T1 - equipment bushing CENELEC EN 50180 and 50181
400AR-1 - equipment bushing (in mm).
400AR-2 - equipment bushing
400AR-8 - equipment bushing
400SFR-P - equipment bushing
Accessories
Possible arrangements

Dia. 56±0.2

Dia. 46±0.2
Dia. for
0
pin 14 -0.04

40
min

90±0.2

11
min

Dia. 70±0.2

In mm.

01/2022
CONNECTING POSSIBILITIES

BUSHINGS / CONNECTION CONNECTORS /


ACCESSORIES ACCESSORIES

Equipment
interface dead-ending
of equipment
(K)(M)400DR
Dead-end receptacle

(K)(M)400T1
Equipment bushing

(K)(M)400AR-1
Equipment bushing

one cable to
equipment

(K)(M)400AR-2 (K)(M)400LR/G
Equipment bushing Elbow connector

(K)(M)400AR-8
Equipment bushing

(K)400SFR-P
Equipment bushing

cable
isolation
(K)(M)400SOP
Stand-off plug

cable
earthing
400GP
Earthing plug

01/2022
400LR INTERFACE B
ELBOW CONNECTOR

APPLICATION TECHNICAL
Separable elbow connector CHARACTERISTICS
(plug-in type) designed to • The thick conductive EPDM jacket
connect polymeric insulated cable provides a total safe to touch
to equipment (transformers, screen which ensures safety for
switchgear, motors...). personnel.
• Each separable connector is
tested for AC withstand and
partial discharge prior to leaving
the factory.

DESIGN 200 mm
Separable connector
comprising: 6/10 (12) kV
1. Conductive EPDM insert. 6.35/11 (12) kV
2. Conductive EPDM jacket. 8.7/15 (17.5) kV
3. Insulating EPDM layer. 12/20 (24) kV
4. Type B - interface as described 12.7/22 (24) kV
by CENELEC EN 50180 and
4
18/30 (36) kV
50181. 5 19/33 (36) kV
5. Conductor connector. 1
6. Cable reducer. 8 Up to 36 kV - 400 A
7. Earthing lead. 2
3 9
8. VD point. 285 mm
9. Conductive rubber cap.

The screen break design enables


cable outer sheath testing without
removing or dismantling the 7

connector.
6

SPECIFICATIONS AND
STANDARDS
The separable connector 400LR
meets the requirements of
CENELEC HD 629.1.

Separable Voltage Current


Conductor sizes (mm2)
connector Um Ir
type (kV) (A) min max
400LR/G 12 400 25 240
K400LR/G 24 400 25 240
M400LR/G 36 400 35 185
01/2022

4
KIT CONTENTS The kit also comprises silicone grease,
gloves, wipers, roll adhesive tape and
The complete (K)(M)400LR/G
installation instructions.
elbow connector kit comprises the
following components:

400LR/G-W-X
connector kit

Connector housing Pin contact Conductor Bail Cable reducer


(K)(M) 400BLR/G + hex. key contact restraint CA0-W
400LRF 400LRMC-X 400BA

ORDERING INSTRUCTIONS TABLE W


To order the elbow connector,
Ordering Dia. over core insulation (mm)
select the part number which gives
part number min max
the best centring to the cable core
insulation diameter and substitute
400LR/G-011-X 12.0 19.0
X using table X, according to the
400LR/G-015-X 16.0 26.5
conductor size and type. 400LR/G-018-X 19.0 32.6
Add a 'K' for use up to 24 kV, add 400LR/G-021-X 22.0 34.6
an 'M' for use up to 36 kV. 400LR/G-027-X 28.5 37.5

TABLE X

EXAMPLE: Conductor sizes Aluminium and copper conductor


The cable is 24 kV, 185 mm² (mm2) Bolted
stranded copper with a diameter 25
over core insulation of 27.5 mm. 35
Order a K400LR/G-018- 50 25.95UN5

95.240UN5 elbow connector kit. 70


95
120
150 95.240UN5
185
240

For use with For use with Alupe or For use with For applications Components can be
copper tape C 33-226 cables. other cable types. outdoors and in ordered individually. 5
screened cables. Please contact our Please contact our humid climate.
Order: Kit MT. representative. representative. Order: +MWS.
400T1/400AR-1 /400AR-2 INTERFACE B2
EQUIPMENT BUSHINGS

APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with oil fluid, typically for Each bushing is tested for
transformers, switchgear, AC withstand and partial
capacitors... discharge prior to leaving the
factory.

SPECIFICATIONS AND
STANDARDS
The plug-in type equipment 6/10 (12) kV
bushings are moulded epoxy
103
6.35/11 (12) kV
insulated parts and meet the 8.7/15 (17.5) kV
requirements of IEC 60137. The 12/20 (24) kV
(K)(M)400T1 also meets CENELEC C
12.7/22 (24) kV
EN 50180 . 10
18/30 (36) kV
A Up to 36 kV - 400 A

ORDERING INSTRUCTIONS
Minimum oil level: Dia.
- 12 kV: 40 mm H
- 24 kV: 50 mm
To order the equipment bushing, - 36 kV: 75 mm
specify the type.
The bushings are supplied with an E
earth jumper (/J) or an earth plate
(/GS). This earth connection must D
Dia. 70
be specified when ordering. Dia. F
E.g. K400AR-1/J. Dia. G

In mm.

Equip- Dimensions (mm)


Voltage Current
ment
Um Ir
bushing
(kV) (A) A B C D E Dia. F Dia. G Dia. H
type
400T1 12 400 310 144 30 M12 22 88 128 16
K400T1 24 400 310 144 30 M12 22 88 128 16
M400T1 36 400 310 144 30 M12 22 88 128 16
400AR-1 12 400 380 213 30 M12 22 74 128 16
K400AR-1 24 400 380 213 30 M12 22 74 128 16
M400AR-1 36 400 380 213 30 M12 22 74 128 16
400AR-2 12 400 329 138 36 M16 40 100 150 30
K400AR-2 24 400 329 138 36 M16 40 100 150 30
M400AR-2 36 400 329 138 36 M16 40 100 150 30 01/2022

6
FIXINGS FOR EQUIPMENT BUSHINGS
400AR-2/GS BUSHING 400AR-2/J BUSHING 400AR-1/J AND 400T1/J
BUSHINGS
bushing
bushing interface interface
fixing studs
fixing studs

fixing flange
fixing flange B DIN 42 538

NF C 52-053 F DIN 42 538


stud clamp E DIN 42 538
claw clamp
stud clamp

equipment
equipment

sealing gasket
sealing gasket

equipment
equipment
connection
connection

tabs for the tabs for the


bail restraint bail restraint

earth
jumper
earth
plate
earth
jumper

BUSHING CLAMPING KIT BUSHING CLAMPING KIT BUSHING CLAMPING KIT


To order the bushing clamping kit, To order the bushing clamping kit, To order the bushing clamping
according to NF C 52-053 simply specify: KBC-RING kit, according to DIN 42 538
standards, simply specify: KBC- CLAMP 3. standards, simply specify: KBC -
NFC 52-053 /400 SERIES (for Contents: - 1 x fixing flange RING CLAMP 2.
bushing type 400AR-2). Ø150 mm Contents: - 1 x fixing flange B
Contents: - 4 x claw clamp NF - 6 x stud clamp F - 6 x stud clamp E
- 1 x sealing gasket. - 1 x sealing gasket. - 1 x sealing gasket.

FIXING DIMENSIONS FIXING DIMENSIONS FIXING DIMENSIONS


STANDARDS NF C 52-053 STANDARDS DIN 42 538
French standards. German standards.

M10 or M12 M12 M10

Min. 55 Min. 60 Min. 55


Max. 30 Max. 30
Max. 25

6 fixing 6 fixing Dia. 90


4 fixing Dia. 105
Dia. 105 studs studs Dia. 140
studs
Dia. 171
Dia. 171 7
In mm.
400AR-8 INTERFACE B
EQUIPMENT BUSHING

APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with oil fluid, typically for Each bushing is tested for
transformers, switchgear, AC withstand and partial
capacitors... discharge prior to leaving
the factory.

SPECIFICATIONS AND
STANDARDS
The plug-in type equipment 6/10 (12) kV
bushings 400AR-8 are moulded 6,35/11 (12) kV
epoxy insulated parts and meet 8,7/15 (17,5) kV
the requirements of CENELEC EN 12/20 (24) kV
50180 and IEC 60137. 28 231.5 12,7/22 (24) kV
18/30 (36kV)
Minimum oil level: Dia.
8.5 19/33 (36kV)
- 12 kV: 40 mm 20 80
- 24 kV: 50 mm
- 36 kV: 75 mm Up to 36 kV - 250 A
20

M10

ORDERING INSTRUCTIONS Dia. 74

To order the equipment bushing, Dia. 110

specify the type.


The bushings can be supplied
with an earth jumper (/J).
E.g. M400AR-8/J.

In mm.

Equipment Voltage Current


bushing Um Ir
type (kV) (A)
400AR-8 12 250
K400AR-8 24 250
M400AR-8 36 250

01/2022

8
FIXINGS FOR EQUIPMENT BUSHINGS
400AR-8/J BUSHING BUSHING CLAMPING KIT
To order the bushing clamping kit,
according to DIN 42 538 stand-
ards, simply specify: KBC - RING
bushing interface CLAMP 1 DIN 42538.
Contents: - 1 x fixing flange A
- 4 x stud clamp E
4 x fixing stud M10 - 1 x sealing gasket.

A DIN 42 538
fixing flange
E DIN 42 538
stud clamp
equipment
sealing gasket
FIXING DIMENSIONS
equipment STANDARDS DIN 42 538
connection
German standards.

tabs for the


bail restraint

M10

Min. 55
earth jumper Max. 30

4 fixing
studs Dia. 78
Dia. 123

In mm.

9
400SFR-P INTERFACE B
EQUIPMENT BUSHING

APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with SF6 gas. Each bushing is tested for
AC withstand and partial
discharge prior to leaving the
factory.

DESIGN Dia. 70
The equipment bushing is a
moulded epoxy insulated part with 6/10 (12) kV
a connector interface in accordance 6.35/11 (12) kV
with CENELEC EN 50181. 8.7/15 (17.5) kV
The 400SFR-P bushing has a shank 12/20 (24) kV
outside this standard, adapted for 12.7/22 (24) kV
use in SF6 gas.
218
Up to 24 kV - 400 A
SPECIFICATIONS AND
STANDARDS 33
The plug-in type equipment
bushing 400SFR-P meets the
requirements of CENELEC EN
50180 and IEC 60137.

95
ORDERING INSTRUCTIONS
To order the equipment bushing,
simply specify the type.

M12
Dia. 25
Dia. 70
Dia. 109

In mm.

Equipment Voltage Current


bushing Um Ir
type (kV) (A)
400SFR-P 12 400
K400SFR-P 24 400
01/2022

10
FIXINGS FOR EQUIPMENT BUSHINGS

400SFR-P BUSHING FOR GAS


INSULATED SWITCHGEAR

UNMOUNTED
earth
60° connection
M4

60° 60°

30°

83

M6

Dia. 91.5
Dia. 103.1

equipment
MOUNTED
Dia. 4

97.5

Dia. 100

equipment
connection

earth
connection
bail sealing M4 In mm.
tab O-ring
gasket
6 fixing
screws
M6

11
ACCESSORIES

APPLICATION TECHNICAL 6/10 (12) kV


For use with connectors and CHARACTERISTICS 6.35/11 (12) kV
bushings with an interface B as All these products, except the 8.7/15 (17.5) kV
described by CENELEC EN 50180 earthing plug, are tested for 12/20 (24) kV
and 50181. AC withstand and partial 12.7/22 (24) kV
discharge prior to leaving the 18/30 (36) kV
factory. 19/33 (36) kV

Up to 36 kV

400DR ORDERING INSTRUCTIONS


DEAD-END RECEPTACLE Order
Fits over a bushing with a type B 400DR for 12 kV,
interface to provide 'dead-end' K400DR for 24 kV or
facility. M400DR for 36 kV
Is used with a 400BA restraint applications.
bail. Can be supplied with integral
earth lead: add -/G.

400SOP ORDERING INSTRUCTIONS


STAND-OFF PLUG Order
Is designed to support and 'dead- 400SOP for 12 kV,
end' connectors with a type B K400SOP for 24 kV or
interface when removed from M400SOP for 36 kV
equipment. applications.

400GP ORDERING INSTRUCTIONS


EARTHING PLUG Order
Is designed to support and earth 400GP for 12 kV, 24 or 36 kV
connectors with a type B interface applications.
when removed from equipment.

01/2022

12
KIT MT ORDERING INSTRUCTIONS
EARTHING KIT FOR COPPER Order
TAPE SCREENED CABLES Kit MT for 12 kV, 24 kV
Contains a tinned copper braid or 36 kV applications.
(25 mm² - L=500 mm), a tinned
copper wire for cleating and water
sealing mastic.

13
POSSIBLE ARRANGEMENTS

CONNECTOR ON STAND- CONNECTOR ON EARTHING


OFF PLUG PLUG
Order 400SOP for 12 kV, Order 400GP for 12 kV, 24 kV and
K400SOP for 24 kV or M400SOP 36 kV applications.
for 36 kV applications.

stand-off
plug

earthing
plug

In mm.

01/2022

14
NOTES

01/2022

15
NOTES

01/2022

16
Nexans Network Solutions N.V. - Div. Euromold
Zuid III, Industrielaan 12, B-9320 Erembodegem
Tel.: +32(0)53 85 02 11 • sales.euromold@nexans.com • www.euromold.be

Catalogue also available on Website and Mobile Apps

Find out more about Nexans Power Accessories.