Installation and
Commissioning Handbook
Contents
1 Introduction ...........................................................3
1.1 The Product..................................................................................... 3
1.2 About the Manual ........................................................................... 3
1.3 The Reader...................................................................................... 3
1.4 Other Reference Material ............................................................... 3
1.5 Approvals........................................................................................ 3
2 Installation .............................................................4
2.1 Cabinet Dimensions........................................................................ 4
2.2 Positioning of Control Panel........................................................... 4
2.3 Recommended Height for Mounting .............................................. 4
2.4 Wall Mounting................................................................................ 5
2.4.1 Fixing Holes.................................................................... 5
2.4.2 Recess Dimensions for Flush Mounting in Wall............ 6
2.4.3 Flush mounting in instrument console............................ 7
2.5 Dismantling the Control Panel Cabinet .......................................... 8
2.5.1 Opening the Front Door.................................................. 8
2.5.2 Releasing the Front Panel From the Cabinet .................. 9
2.6 Refitting the Front Panel................................................................. 11
2.7 Installing the Batteries .................................................................... 12
2.8 Cable Feed ...................................................................................... 12
2.9 Recommended Cables..................................................................... 13
2.10 Cabling............................................................................................ 13
2.11 Adding Zone Information to the Front Label ................................. 14
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 1
Contents
4 Commissioning .....................................................29
4.1 Commissioning Responsibility for the Control Panel .................... 29
4.2 Recommended Testing Equipment................................................. 29
4.3 Pre-commissioning Checks............................................................. 29
4.4 Mains Supply - 230V AC ............................................................... 30
4.5 Battery Connection ......................................................................... 31
4.5.1 Temperature compensated charging of battery............... 32
4.5.2 Adjusting the charging voltage....................................... 32
4.6 Final Task ....................................................................................... 33
4.7 Operating Levels............................................................................. 33
4.8 Commissioning Checks .................................................................. 33
4.9 Configuration.................................................................................. 33
5 Additional functions..............................................34
5.1 Disabling/Restoring of Zones (loops) from Aux. Switch............... 34
5.2 Activating Alarm Delay from an Auxiliary Switch........................ 35
5.2.1 Note................................................................................. 35
7 Appendix ................................................................37
7.1 Recommended Cable Types ........................................................... 37
7.2 Positioning of Detectors ................................................................. 38
7.3 Installation of Heat Detectors. ........................................................ 39
7.4 Installation of Smoke Detectors...................................................... 39
7.5 BX-10 Control Panel variants......................................................... 40
7.5.1 BX-10M(M2)/ xx-24 ...................................................... 42
8 Reader’s Comments..............................................43
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 2
Introduction
1 Introduction
1.5 Approvals
BX-10 is approved according to EN-54 part 2 and 4, and LVD
(IEC 60950).
BX-10M (Maritim version) approved according to:
• Det Norske Veritas (DNV)
• Lloyd’s Register of Shipping (LR)
• American Bureau of Shipping (ABS)
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 3
Installation
2 Installation
BX-10
Sone 2 Sone 2 Styringer Kraftfor. Alarmsender aktivert
Sone 3 Sone 3 Al/Fe-utg. Jord
125
350
175 cm
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 4
Cable Connections
• Mark off and drill holes to take 6 mm (max.) screws (and plugs if
necessary (the height above the floor should be approx. 174 cm).
• Screw in the 2 uppermost screws half way.
There are 4 fixing holes in the rear of the cabinet. The 2 uppermost are
keyhole types.
• Hang the cabinet on the 2 uppermost screws.
• Screw in the 2 lower screws and tighten all four.
10 10
320
186 Cabinet
166
10
340
Approx. 174 cm
to floor
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 5
Installation
Wall
190 mm
75 mm 75mm is the necessary depth for flush
mounting the unit.
344 mm (Mounting depth, see fig. below.)
The wall must be fitted with transverse screw fastenings so that the cabinet
fixing holes can be utilised. The distance from the wall surface to the
screw fixing plate shall be 67 mm (max.). If the recess forms a gap around
the cabinet, this must be covered by a frame (max. thickness 2 mm) fitted
to the side edges of the cabinet.
If the cabinet is to be set into the wall, vertical and horizontal
reinforcement bars must be fitted inside the cabinet.
Fixing screws
Fixing plate
Front panel
Cabinet
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 6
Cable Connections
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 7
Installation
Finger
recess
BXX-10
Termination
board
TORX locking
screw for opening
BXA-10 Main door
board
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 8
Cable Connections
Front door
Left side -frame Right side-frame
Hinge
Velcro Velcro
Y Y
Z X Z
X
Locking screws (X)
for front panel
Cabinet
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 9
Installation
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 10
Cable Connections
Press here
and on the
left side
Locking screw
IMPORTANT!
If this is a first-time installation, go directly
! to chapter 4, Commissioning.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 11
Installation
It is also possible to feed in cables (such as the mains cable) through the
floor of the cabinet.
• The mains cable is fed in through the right-hand entry hole located in
the cabinet base.
• The other cables are fed in through the subsequent holes.
• Feed the thinnest cables through the entry hole to the left.
• •A minimum 0.5 m of cable must be fed into the cabinet before
stripping and connecting up.
Topp
ø16mm
ø19mm
Base
ø16mm
ø19mm
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 12
Cable Connections
2.10 Cabling
• Adjust the cable lengths to fit the connection terminals.
• Strip the cables and make the required connections.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 13
Installation
Lugs Lugs
Power 4: Reset R
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 14
Cable Connections
3 Cable Connections
3.1 Introduction
This chapter describes all necessary cable connections and procedures.
IMPORTANT:
The following procedure is for a first-time installation:
. Connect all necessary cables except the mains cable and cables from
! the batteries.
. Turn to Commissioning, p. 29, and systematically go through the check
points described.
. Connect the mains cable, see Mains Supply - 230V AC, p. 30.
. When all cables are properly connected (including the mains cable),
switch on the power and then connect the batteries, see Batteries, p. 31.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 15
Commissioning
32 33
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 16
Commissioning
F9 F8 F5 F3 F6 F7 F1 F2
1.4AT, 1.4AT, 0.2AT 0.2AT 0.63AT 0.63AT 0.63 AT, 0.4AT,
24V DC 24V DC General General Alarm Alarm common common
Battery Operating control alarm sounder sounder for all 24V for all 12V
voltage output output circuit 1 circuit 2 DC DC
(DHM) (BMA) (AK1) (AK2) voltage voltage
outputs outputs
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 17
Commissioning
NO 15 NO contact
Activated by alarm NC contact Common alarm output (BMA) for activating
NC 16
and reset by common functions on alarm, potential free relay
resetting. output.
The outputs can be
delayed by 17 C contact
C
activating the
day/night function. Monitored 24V 18 Common alarm output (BMA) for activating
alarm transfer +24V / 0.2A power output at alarm
F=0,2A
24V V (FARE).
R 2K
0 volts 19 K Break and short-circuit monitored. R=2kΩ,
V=diode, K=relay, Output secured with 0,2A.
+24V DC +
Activated by alarm in 20
one of the detector Sounder output AK-1, +24V / 0.63A,
2K
zones. parallel function.
Reset by operating 0-volt 21 Pulsing outputs 1 sec. on and 1 sec. off.
the “Reset alarm” - 0V (appendix 7.5, BX-10M)
function.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 18
Commissioning
28 +
29 - (0V) Comm.channel, aux.units/
PC for configuration
30 (screen)
Telephone autodialer 31
Independent of
Telephone line- Modem connection.
Telephone autodialer 32 polarity (Not in use).
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 19
Commissioning
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 20
Commissioning
In the fixed mains wiring to the panel a two-pole disconnect device must
be provided to disconnect the equipment from the power supply when
servicing is required. Normally, this switch is a two-pole automatic fuse
located in the fuse terminal box at the premises. This fuse location must be
marked “Fire Alarm System”.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 21
Commissioning
Terminal borad
BXX-10
12V DC 12V DC
L1
26 + 27,3V Battery
27 -
Battery support + -- + -
H=134 ± 1
+ - + - D=63 ± 1
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 22
Commissioning
By connecting +leads for input and output cables between 1 and 6, the
zone will report a fault when one of the detector heads is removed.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 23
Commissioning
Polarised
sounders
NOTE!
Maritime version BX-10M has a fix sounder output signal.
By strapping input 5 and 6 (signal on input 5) gives a pulsating output with
7 short and 1 long puls. (SOLAS regulation). Maritime version BX-10M2
has pulsating output signal and is not able to activate 7 short and 1 long
signal.
Dutch version BX-10/NL has a fix sounder output signal.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 24
Commissioning
There is a control output for each detector zone (loop), one common for all
zones and one for disabled zones. The outputs are supplied as transistor
controls (open collectors); one control per zone (L1. 51-L1.48).
The 24V output (44, 45) has a 0.63A fuse (F1).
The following is an example of an external relay connection:
+24 V
+
L1. (44, 45)
Potential free
relay
L1. (51, 50, 49, 48, 47, 46)
Control outputs
-
zones 1 - 4
BX-10
18 +
V
BMA-output
R 2k External equipment
(FARE)
K
19
-
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 25
Commissioning
13 + + Monitored circuit
V1
BMF-output R=1K
A
Maximum. 150mA
AC or DC
(Normally closed)
14 - V2 B
-
R=1k
V1=Diode
V2= Optoisoloator PVT312LS
BMF-output
R=2kΩ
14
-
An end resistor R=2kΩ must be applied in the control panel.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 26
Commissioning
The output is break and short circuit monitored via a 2kΩ parallel resistor
Secured with a 0,2A fused.
An end resistor R=2kΩ must be applied to an unused output.
BX-10
+ Door coil
Monitored output.
+
37 + 24V
DHM-output R=2kΩ
36
- +
− Door coil
BX-10
37 +
DHM-output
R=2kΩ
36
-
An end resistor R=2kΩ must be applied in the control panel.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 27
Commissioning
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 28
Commissioning
4 Commissioning
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 29
Appendix
Earth
230V AC L
N
Block 2
Power
Mains fuse in 230V AC
power unit 27,3V DC
(1,6A) 1.2A
27.3 VDC
BXX-10 35 +
terminal board 34 -
List 1 33
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 30
Additional functions
Terminal board
BXX-10
12V DC 12V DC
L1
• Connect the (-) leads when the panel is connected to the mains.
• Terminal type: 4,8mm flat contact (male).
• RESET the panel to check if the unit is in order.
Ex..: 06 98 7
Manufacture line (line 7)
Manufacture year (1998)
Manufacture mounth (june)
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 31
Appendix
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 32
Additional functions
4.9 Configuration
The BX-10 fire alarm control panel is supplied in a standard version from
the manufacturer.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 33
Additional functions
5 Additional functions
Each of the four detector zones can also be disabled via external disabling
switches connected between terminals 1 and 6 (zone 1), 2 and 6 (zone 2), 3
and 6 (zone 3) and 4 and 6 (zone 4). The zone is disabled as long as the
contact is closed.
A cycle timer can be used for variable time-controlled disabling.
IMPORTANT: When a zone (detector loop) is disabled the detectors will
be disabled, while manual call-points will remain active.
If a zone is disabled using an auxiliary switch, it will not be possible to re-
activate the zone from the control panel’s front panel.
With each disabling operation (from either the front panel or an auxiliary
switch), the output for auxiliary warning of a disabled zone (output 47 -
AUX1) will be activated (e.g. this may be used to activate an auxiliary
warning light).
NB!
All disabling will be automatically restored after 24 hours.
• Disabled zones in BX-10L for agricultural are automatically restored
after 4 hours.
• BX-10I for intruder version, zone 4 will not be automatically restored.
Zone1
1
Zone 2
Zone 3
Zone 4 External
switch for disablement
0V
6
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 34
Service and maintenance
Signal
64 64
External strap
0V switch 60
60
5.2.1 Note
BX-10M (Maritime version) must always have a stropping between 60 and
64. This will give a 2 minutes delay on sounder outputs, and the activation
of alarm delay will not restore automatically after 12 hours. Common
LED-indications “Disabled” and “Imm.alarm disabled” are not activated
(Appendix 7,5). BMA-output will not be delayed.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 35
Service and maintenance
The batteries are marked with a label which indicates the manufacture
date.
Ex..: 06 98 7
Manufacture line (line 7)
Manufacture year (1998)
Manufacture mounth (june)
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 36
Appendix
7 Appendix
Detector loops BPR 2x1mm ø 680 2xPN 0.75 mm2 650 RCOP 2x0.50 mm2 430
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 37
Appendix
b) Roofs and ceilings with falls shallower than 1:10 are defined as flat.
Roofs with falls of 1:10 and steeper, together with arched roofs, are
defined as sloping roofs, and (a row of) detectors should be placed at
the highest point (the ridge).
The height of the roof is equal to the max. height of the room.
e) Detectors should not be placed closer than 0.5 m to a wall unless the
room is less than 1.0 m wide/deep. Exemption from this rule requires
written dispensation from the insurance company.
< 15 cm
≥ 0,5m ≥ hb ell. hb
≥ 0,5 mm hk
≥ hb ell.
≥ 0,5 mm
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 38
Appendix
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 39
Appendix
Brief explanation of what is unique about the different control panel variants.
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 40
Appendix
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 41
Appendix
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Page 42
Reader’s Comments
8 Reader’s Comments
Please help us to improve the quality of our documentation by returning your comments on this
manual:
Title: Installation- And Commissioning Handbook, Fire Alarm Control Panel BX-10
Ref. No.: P-BX10/IE - Rev. L, 040504
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 43
Reader’s Comments
Tel: + 47 73 58 25 00
Fax: + 47 73 58 25 01
Installation and Commissioning Handbook, Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 44
Reader’s Comments
Installation and Commissioning Handbook,Fire Alarm Control Panel BX-10, P-BX10/IE - Rev. L, 040504,
Autronica Fire and Security AS
Side 45
Autronica Fire and Security AS is an international company, based in Trondheim,
Norway and has a world-wide sales and service network. For more than 40 years
Autronica’s monitoring systems have been saving lives and preventing catastrophes
on land and at sea. Autronica Fire and Security’s most important business area is fire
detection & security. Autronica Fire and Security stands for preservation of
environment, life and property.
Quality Assurance
Stringent control throughout Autronica Fire and Security assures the excellence of
our products and services. Our quality system conforms to the Quality System
Standard NS-EN ISO 9001, and is valid for the following product and service
ranges: marketing, sales, design, development, manufacturing, installation and