403 Poyntz Ave.

, Suite B
Manhattan, KS 66502, USA
Phone: +1-785-770-8511
Email: support@thunderheadeng.com
Web: https://www.thunderheadeng.com

PyroSim User Manual


Version: 2022-2
Last Modified: 2022-07-20
Table of Contents
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Acknowledgements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1. Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2. Download and Install . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3. Some Modeling Suggestions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4. Using a Different FDS Executable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.5. Additional FDS and Smokeview Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.6. Contact Us . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2. PyroSim Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.1. PyroSim Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2. Navigation View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3. 3D View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4. 2D View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.5. Record View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.6. Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.7. Snapshots of Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.8. Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.9. Configuration Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.10. Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.11. Color Schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3. Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.1. Managing Views. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.2. Viewpoints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.3. Section Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.4. Smokeview Interoperability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4. Working with Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.1. Creating a New PyroSim Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.2. Saving a PyroSim Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.3. Open a Saved PyroSim Model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.4. Preventing Changes to a Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.5. Importing FDS Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.6. Exporting FDS Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.7. Importing CAD files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5. Meshes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.1. Working with Meshes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.2. Uniform Meshes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.3. Nonuniform Meshes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.4. Using Multiple Meshes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.5. Additional Mesh Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
6. Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.1. Solid Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.2. Liquid Fuels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
7. Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
7.1. Reserved Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
7.2. Surface Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
7.3. Surface Tabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
7.4. Surface Color and Appearance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8. Geometry (Basic Concepts) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
8.1. Obstructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
8.2. Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
8.3. Vents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
8.4. Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
8.5. Floors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
9. Drawing in PyroSim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.1. Drawing/Editing Tool Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.2. Snapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
9.3. Precise Keyboard Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
9.4. 2D versus 3D Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
9.5. Obstruction Drawing Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
9.6. Hole Drawing Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
9.7. Vent Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
9.8. Solution Mesh Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
9.9. Mesh Splitter Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
9.10. Device Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
9.11. Planar Slice Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
9.12. HVAC Node Tool. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
9.13. HVAC Duct Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
9.14. Other Box Drawing Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
9.15. Other Point Drawing Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
9.16. Editing Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
9.17. Transforming Objects. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
9.18. Painting Obstructions and Vents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
9.19. Measuring Length/Distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
10. Creating Complex Geometry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
10.1. Curved Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
10.2. Trusses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
10.3. Roofs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
10.4. Stairs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
11. Working with Geometry Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
11.1. Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
11.2. Context Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
11.3. Undo/Redo. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
11.4. Copy/Paste . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
11.5. Double-Click to Edit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
11.6. Move Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
11.7. Mirror Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
11.8. Scale Dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
11.9. Rotate Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
11.10. Object Visibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
12. Species . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
12.1. Primitive Species . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
12.2. Lumped Species . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
13. Reactions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
13.1. Defining the Combustion Reaction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
13.2. Custom Smoke . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
14. Particles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
14.1. Liquid Droplets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
14.2. Solid Particles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
14.3. Massless Tracers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
14.4. Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
14.5. Global Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
14.6. Particle Clouds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
15. Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
15.1. Aspiration Detection System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
15.2. Gas or Solid Phase Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
15.3. Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
15.4. Flow Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
15.5. Heat Release Rate Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
15.6. Layer Zoning Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
15.7. Path Obscuration (Beam Detector) Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
15.8. Heat Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
15.9. Smoke Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
15.10. Sprinkler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
15.11. Nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
16. Control Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
16.1. Activation Control Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
16.2. Creating Activation Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
16.3. Time-based Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
16.4. Detector-based Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
16.5. Deadband-based Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
16.6. Manual-based Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
16.7. Custom Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
16.8. Mathematical Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
17. HVAC Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
17.1. HVAC Duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
17.2. HVAC Node . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
17.3. HVAC Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
17.4. HVAC Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
17.5. HVAC Aircoil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
17.6. HVAC Vents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
18. Output Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
18.1. Solid Profiles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
18.2. 2D Slices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
18.3. 3D Slices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
18.4. Boundary Quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
18.5. Isosurfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
18.6. Plot3D Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
18.7. Statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
19. Running the Simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
19.1. Simulation Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
19.2. OpenMP Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
19.3. Run FDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
19.4. Parallel Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
19.5. Cluster Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
19.6. Cloud Execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
19.7. Resuming a Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
19.8. PyroGeom File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
20. Post-Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
20.1. Launching Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
20.2. Launching Smokeview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
20.3. Time History Results. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
20.4. Archiving Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
20.5. Restoring Archived Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
21. Managing Data Libraries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
21.1. Create and Manage Your Own Libraries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
21.2. Use the Library Provided with PyroSim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
21.3. Import a Material or Reaction from the FDS 4 Database. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
22. Advanced FDS Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
22.1. Additional Records Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
22.2. Advanced Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
23. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
23.1. How to Activate a Node-Locked License . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
23.2. Floating License Server Problems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
23.3. Floating License Server Too Old, Update Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
23.4. Licensing/Registration Problems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
23.5. Video Display Problems and Crashes on Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
23.6. Memory for Large Models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
23.7. Parallel Simulation (MPI) Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
23.8. Additional Support Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Appendix A: Opening FDS v4 and PyroSim v2006 Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
A.1. Global Simulation Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
A.2. Sprinklers and Pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
A.3. Reactions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
A.4. Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
A.5. Thermally Thin Surfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
A.6. Where is the Surface Database? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Appendix B: Opening FDS v5 and PyroSim v2012 Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
B.1. Global Simulation Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
B.2. Reactions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
B.3. Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
B.4. Particles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Bibliography . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
PyroSim - User Manual

Disclaimer
Thunderhead Engineering makes no warranty, expressed or implied, to users of PyroSim, and
accepts no responsibility for its use. Users of PyroSim assume sole responsibility under Federal
law for determining the appropriateness of its use in any particular application, for any
conclusions drawn from the results of its use, and for any actions taken or not taken as a result of
analyses performed using these tools.

Users are warned that PyroSim is intended for use only by those competent in the fields of fluid
dynamics, thermodynamics, combustion, and heat transfer, and is intended only to supplement
the informed judgment of the qualified user.

The software package is a computer model that may or may not have predictive capability when
applied to a specific set of factual circumstances. Lack of accurate predictions by the model could
lead to erroneous conclusions with regard to fire safety. All results should be evaluated by an
informed user.

All other product or company names that are mentioned in this publication are tradenames,
trademarks, or registered trademarks of their respective owners.

Throughout this document, the mention of computer hardware or commercial software does not
constitute endorsement by Thunderhead Engineering, nor does it indicate that the products are
necessarily those best suited for the intended purpose.

Disclaimer 6
PyroSim - User Manual

Acknowledgements
We thank Kevin McGrattan, Simo Hostikka, Randall McDermott, Jason Floyd, Craig Weinschenk,
Kristopher Overholt, and Glenn Forney in the Building and Fire Research Laboratory at the
National Institute of Standards and Technology and the VTT Technical Research Centre of Finland.
They are the primary authors of the Fire Dynamics Simulator and Smokeview, without which
PyroSim would not exist. They have been gracious in their responses to our many questions.

We would like to gratefully acknowledge the RJA Group for their collaboration with Thunderhead
engineering in the development of PyroSim. Feedback and testing from the engineers at RJA has
improved the usability and quality of PyroSim.

Development of PyroSim was originally supported by the National Science Foundation under
Grants DMI-0232401 and DMI-0349759. Any opinions, findings, and conclusions or
recommendations expressed in this material are those of the authors and do not necessarily
reflect the views of the National Science Foundation.

7 Acknowledgements
PyroSim - User Manual

Chapter 1. Getting Started


1.1. Introduction
PyroSim is a graphical user interface for the Fire Dynamics Simulator (FDS) version 6.7.9. FDS is
closely integrated into PyroSim. FDS models can predict smoke, temperature, carbon monoxide,
and other substances during fires. The results of these simulations are used to ensure the safety of
buildings before construction, evaluate safety options of existing buildings, reconstruct fires for
post-accident investigation, and assist in firefighter training.

FDS is a powerful fire simulator which was developed at the National Institute of Standards and
Technology (NIST). FDS simulates fire scenarios using computational fluid dynamics (CFD)
optimized for low-speed, thermally-driven flow. This approach is very flexible and can be applied
to fires ranging from stove-tops to oil storage tanks. It can also model situations that do not
include a fire, such as ventilation in buildings.

The PyroSim interface provides immediate input feedback and ensures the correct format for the
FDS input file.

Some highlights include:

• Import CAD files to create and manage complex models.

• High-level 2D and 3D geometry drawing tools.

• Integrated parallel processing.

• Flexible unit system that supports working in either metric or English units.

• Tools to manage multiple meshes.

• Multiple language translations.

• HVAC (Heating, Ventilation, and Air Conditioning) systems integrated into the CFD simulation.

• Import of existing FDS models.

• Integrated post-processing.

In summary, PyroSim helps you quickly and reliably build complex fire models.

1.2. Download and Install


You can download the current version, sign up for a free trial, and purchase the software from the
PyroSim Support Page. This page also provides instructions for installation and activation.
Troubleshooting info can be found on the PyroSim Answers page. There is no functional
difference between the trial version of PyroSim and the full version, the only limitation is the trial

Chapter 1. Getting Started 8


PyroSim - User Manual

license duration.

When installing PyroSim, the installer will either upgrade an existing version or install PyroSim to
a new location, this behavior is based on the version. In the case of minor updates (e.g. upgrading
from PyroSim 2020.1 to PyroSim 2020.2), the installer will remove the older version and replace it
with the new version. When installing a major update (e.g. PyroSim 2019 to PyroSim 2020), the
older version will not be modified and the newer version will be installed to a different folder.

Administrator privileges are required to install PyroSim. This is necessary because the installer
adds processes to the operating system for license management and parallel FDS simulation. The
PyroSim installer will also add Windows Defender exclusions for the bundled FDS executables in
order to avoid performance issues related to Windows Security. To see how to do this manually,
see Section 1.4.1.

PyroSim will regularly check for and notify the user of available updates to the software when
configured to do so. By default, PyroSim will check for updates on startup and display the relevant
information in the Check For Updates dialog when one is available.

Figure 1. The Check For Updates dialog.

Users can also access this dialog by navigating to Help→Check For Updates

The dialog can be disabled on startup by unchecking Check for newer version on startup.

1.3. Some Modeling Suggestions


In this section we make some suggestions that can help speed your model development. The big
issues most users will face are: selecting a mesh, defining your geometry, selecting a reaction, and
defining the correct boundary conditions.

9 Chapter 1. Getting Started


PyroSim - User Manual

We will broadly discuss each of those topics, but before you start thinking about them please:

Take the time to work through the examples.


On the PyroSim Fundamentals page we provide a series of examples that guide you through
increasingly complex fire modeling concepts. It is worth your time to work through these
examples.

Remember to "start small"


When developing a new model, don’t just rush in and make the final model. Use small models
to make sure you understand the details. For example, test your sprinklers on a small model
first. If you are using controls, practice on a simple case.

1.3.1. Selecting a mesh


The analyst will always need to balance solution time and accuracy. Reducing the mesh size by a
factor of 2, will result in approximately a factor of 16 more computation time (a factor of 8 due to
the number of cells and an additional factor of 2 due to reduced step size).

Two criteria will control the applicable mesh size:

• Resolving the flow field.

• Resolving the geometry.

For fire plumes, an initial mesh size estimate can be obtained as a fraction of the characteristic
*
fire diameter (D ), see Chapter 6 of the Fire Dynamics Simulator Technical Reference Guide Volume
*
3: Validation. You can download a D calculator from the PyroSim Resources page. Initial
calculations should be done with a coarse mesh ([stem fee07d91a4fada2c18cc5b57a207a621]), but
a mesh size study must be employed to analyze the suitability of the mesh ([stem
1f92cd70499116f44027a1eb9a5d7478]).

An example of a convergence study for jet fans (no fire) can be found in the series of posts
Modeling Jet Fans found on the PyroSim Tutorials web page. Here the solution was compared with
experimental data.

In some problems the mesh resolution must be selected to adequately represent the geometry. An
example where geometry controlled the mesh size is the modeling of a wood crib where each
stick had a small diameter (see Modeling Fire, Part 4 – Combustion with HRR, Ignition, and Burn
Away on the Thunderhead website).

1.3.2. Reactions
By default, no reaction is specified, a reaction is only needed if there will be a fire in the
simulation. In FDS, a reaction defines not only the fuel and the products but also the Heat of

Chapter 1. Getting Started 10


PyroSim - User Manual

Combustion. Once the heat of combustion and the desired HRR is known, FDS calculates the fuel
mass flow rate from the surface.

For most situations, it is sufficient to use the "Simple Chemistry" model, where a single fuel
species is composed of [stem 9b325b9e31e85137d1de765f43c0f8bc], [stem
7b9a0316a2fcd7f01cfd556eedf72e96], [stem 9afe6a256a9817c76b579e6f5db9a578], and [stem
f9c4988898e7f532b9f826a75014ed3c] that reacts with oxygen ([stem
a00259a5a7fc00723b6060a21001d1e7]) to form the product species consisting of [stem
d7fc8f229a929f93c03b951b7fe40bf0], [stem 8306272097a2ac71e3c568c80d48b7f9], [stem
58195e9dd077adcd98a0692c1d3fdd7d], [stem 9da8f3117d9b7d8ec90349680c3a1117], and [stem
f74275c195a72099e0b06f584fd5489a]. The user specifies the chemical formula of the fuel along
with the yields of [stem f74275c195a72099e0b06f584fd5489a] and [stem
58195e9dd077adcd98a0692c1d3fdd7d], and the volume fraction of hydrogen in the [stem
58195e9dd077adcd98a0692c1d3fdd7d], [stem 2b999b871586c2863f02433d19b56206]. A limited
number of reactions are included in FDS and can be added from the library.

See Chapter 12 of the FDS User Guide for a more detailed discussion of combustion. The PyroSim
Resources page provides Combustion and Fuel Composition calculators.

1.3.3. Parallel Processing


Parallel processing can speed the solution. In general, our experience indicates that running on
multiple cores on the same computer offers the most significant improvement. Using multiple
computers in a cluster can make it possible to solve larger problems, but the communication
delays between computers tend to cancel the speed improvement of parallel processing.

The good news is that that standard installation of PyroSim includes support for parallel
processing on the same computer. All the user must do is define multiple meshes and then select
Run FDS Parallel.

PyroSim includes tools to manage multiple meshes. One effective strategy is to first define a single
mesh that spans the entire model. Then use the PyroSim mesh splitting tool to create multiple
meshes. You can then change the resolution of selected meshes using the Refine Mesh option and
all the meshes will automatically stay correctly aligned.

1.3.4. FDS Snaps to the Mesh


All geometry in FDS is defined at the mesh resolution. Even if you input the geometry of an
obstruction or vent to lie between cell corner points, when FDS runs the solution, all the geometry
will be "snapped" to the grid.

If you are drawing your own geometry in PyroSim, you can select the Snap to Model Grids option
that will ensure that your geometry matches the grid. You can also ensure that objects will fill

11 Chapter 1. Getting Started


PyroSim - User Manual

entire grid cells rather than a cell face by turning on the Thicken option in the obstruction
properties, see Section 8.1.1.

1.3.5. Numerical Instabilities are Usually Model Problems


In our experience, numerical instabilities that may occur during the solution are the result of an
error in the model, not an error in FDS. The numerical instability typically arises due to either a
pressure increase (or decrease) in a mesh. If you see this error, add a pressure sensor to your
model and see what is happening to the pressures. Problems typically occur because of how
boundary conditions have been defined.

Some common problems with boundary conditions include:

• Lack of an open vent on the boundary. One typical case is that a fire heats the air in a room
but there is no open vent, so the heated air expands and increases the pressure in the room
which eventually causes an instability. The solution is to make sure all rooms have open vents.

• Imbalance on the flow conditions. This often occurs if the user specifies velocity boundary
conditions on both supply and exhaust vents in a room. If there is a fire in the room, the
density of the hot exhaust air is less than that of the ambient supply air, so velocity conditions
result in accumulation of mass in the room with a corresponding increase in the pressure. The
solution is to specify the velocity flow on the supply, but define the exhaust as an open vent
(or vice versa). The open vent will accommodate changes in density.

• Flow boundary conditions into a closed space. This is more likely to occur when CAD data is
used to import geometry. If a supply is defined on a mesh boundary, it can intersect both the
model (as intended), but there can also be cells outside the model that are included in the
supply. The solution is to make sure there are open vents on the boundaries outside a model.

1.4. Using a Different FDS Executable


Each PyroSim release comes bundled with FDS. A particular PyroSim release is designed and
tested against the bundled version of FDS. You can use PyroSim to run any version of FDS,
however PyroSim will generate the input file based on the bundled version of FDS and it is
important to understand differences in input format between the FDS versions before changing
PyroSim’s FDS version.

To change the version of FDS used by PyroSim:

1. Download and install a new version of FDS from NIST.

2. On the File menu, click Preferences.

3. Click on the appropriate Folder icon in the FDS Execution section to select the executable you
want PyroSim to use.

Chapter 1. Getting Started 12


PyroSim - User Manual

4. Click OK to close the Preferences dialog.

1.4.1. Windows Defender FDS Exclusions


Windows Defender Antivirus may cause performance issues with FDS. PyroSim adds exclusions
for the bundled FDS executables on install, but if you are using a custom executable path then it is
recommended that you add these exclusions manually.

To add Windows Defender exclusions for your FDS executables:

• Use Windows Search to find and open Windows Security.

• In the left-hand menu, select Virus & threat protection.

• Under Virus & threat protection settings, click Manage settings.

• Under Exclusions, select Add or remove exclusions.

• Add both a File and Process exclusion for the path to your FDS executable.

• If you are using FDS 6.7.8 or newer, you will also want to add a exclusions for the path to the
openmp-optimized executable, fds_openmp.exe, which is described in Section 19.2.1.

1.5. Additional FDS and Smokeview Documentation


In preparing this manual, we have liberally used descriptions from the FDS User’s Guide
(McGrattan, et al., 2015). Links to the FDS Users Guide, the FDS Technical Reference, and the
Smokeview Users Guide are included in PyroSim on the Help menu. You can also download
documentation, executables, and verification and validation examples at: https://pages.nist.gov/
fds-smv/ .

1.6. Contact Us
Thunderhead Engineering
403 Poyntz Avenue, Suite B
Manhattan, KS 66502-6081
USA

Sales Information: sales@thunderheadeng.com


Product Support: support@thunderheadeng.com
Phone: +1.785.770.8511

13 Chapter 1. Getting Started


PyroSim - User Manual

Chapter 2. PyroSim Basics


2.1. PyroSim Interface
PyroSim provides four editors for your fire model: the 3D View, 2D View, Navigation View, and the
Record View. These all represent your current model. If an object is added, removed, or selected in
one view, the other views will simultaneously reflect the change.

Each view is briefly described below.

Navigation View
This view lists many of the important records in the model. It allows you to organize your
model geometry into groups such as room or sofa. Locating and modifying records is often
faster and easier in this view.

3D View
This view shows a 3D representation of your current fire model. You can explore the model
using different view controls. You can also control the appearance of the model with options
like smooth shading, textures, and object outlines. Geometric features can also be changed.

2D View
This view is useful for quickly sketching geometry such as walls and furniture. You can choose
from three viewing planes and perform many useful geometric manipulations.

Record View
This view gives a preview of the FDS input file that will be generated for the simulation. It also
provides a way to add custom records that will not be processed by PyroSim, but will be sent to
FDS.

2.2. Navigation View


The navigation view is a tree-like view on the left side of the PyroSim main window. An example
of this view in use is shown in Figure 2. When you right-click on an item in this view, a list of the
functions PyroSim can perform on that item is shown. To rearrange objects in the Navigation
view, make a selection and then drag the object(s) to the new location.

Chapter 2. PyroSim Basics 14


PyroSim - User Manual

Figure 2. Using the context menu in the Navigation View

2.3. 3D View
Use the 3D view to rapidly obtain a visual image of the model and perform some drafting. In this
view, the user can navigate through the model in 3D and select objects. This view also provides
display filters to quickly show/hide entire categories of objects or switch between floors. In
addition, any drafting that requires objects to be snapped to faces of other objects, such as
drawing a vent on an obstruction or attaching a measuring device to a solid can be easily
achieved in this view. For more information on drafting, see Chapter 9.

2.3.1. Camera Views


The traditional orthographic views are pre-programmed into PyroSim and are valid in both the
3D and 2D views. It is also possible to save custom camera views, for more information, see
Chapter 3.

To change the camera view, select the desired view in the drop-down menu, as shown in Figure 3
or press the appropriate hotkey from Table 1.

15 Chapter 2. PyroSim Basics


PyroSim - User Manual

Table 1. Camera View


Hotkeys

View Hotkey

Front CTRL+1

Back CTRL+2

Left CTRL+3

Right CTRL+4

Top CTRL+5

Bottom CTRL+6

The drop-down menu is also a clickable button that will reset to the most recent view.

Figure 3. Camera Views Drop-Down Menu

2.3.2. Navigation/Selection
There are several tools that can be used to navigate the model and select objects. The tools for the
3D view are found in the navigation toolbar above the 3D view as shown in Figure 4.

Figure 4. 3D navigation toolbar

Select/Manipulate Tool ( )
This general-purpose tool can be used to perform most navigation activities.

Selection
The following actions can be used to select items.

• Left-click an object to select it.

• Drag the left mouse button to draw a selection box and select all objects within the box.

Chapter 2. PyroSim Basics 16


PyroSim - User Manual

• Double-click the left mouse button to select and open a properties dialog for the object
under the cursor.

• Hold ALT while performing selection to select the hierarchical parent of the object
under the cursor.

• Right-click to show a context menu for selected items under the cursor.

Panning
Drag the middle mouse button to pan the model.

Orbiting
Drag the right mouse button to orbit the model.

Zooming
Roll the scroll wheel on the mouse to zoom in and out of the cursor position.

Manipulating
If a single object is selected, it may show manipulation handles (blue dots or faces). Left-
click one of the handles to begin manipulation or drag the left mouse button to perform
manipulation in one gesture. For more information on manipulation, see Section 9.16.

Orbit Tool ( )
This is another general-purpose tool that is a bit more limited than the Select/Manipulate
Tool.

Orbiting
Drag any mouse button to orbit.

Panning
Hold the SHIFT key down while dragging any mouse button to pan.

Zooming
Hold the ALT key down while dragging any mouse button to zoom.

Manipulating
This tool cannot perform manipulation.

Roam Tool ( )
This tool allows the user to move into the model rather than viewing it only from the outside as
shown in Figure 6. This tool can take some experimentation, but once mastered, it can provide
unique views of the model.

17 Chapter 2. PyroSim Basics


PyroSim - User Manual

Selection
This is the same as with the Orbit Tool.

Looking
Drag any mouse button to look around. This pivots the camera about the camera’s location,
similar to a first-person video game.

Moving
There are keyboard shortcuts to modify the mouse actions.

• Hold the ALT key while dragging a mouse button to move the camera up and down
along the Z axis.

• Hold the CTRL key while dragging a mouse button to move the camera forward,
backward, and side-to-side in the camera’s XY plane.

Pan Tool ( ), Zoom Tool ( ), Zoom Box Tool ( )


These tools break out the functionality of the above tools so that dragging any mouse button
will perform the needed action.

Exterior and Interior Views of a Model

Figure 5. Exterior view (PyroSim model by John Figure 6. Interior view of the same model looking
McKinney) at the roof and bleachers

2.3.3. Zooming
The model can also be zoomed in and out with any of the navigation tools by using the scroll
wheel. Scrolling up zooms in and scrolling down zooms out. With all but the Roam Tool, using the
scroll wheel will zoom in on the point under the cursor. With the Roam Tool, the scroll wheel
only zooms the center of the view.

Chapter 2. PyroSim Basics 18


PyroSim - User Manual

2.3.4. Resetting the View


At any time, the camera’s view can be reset to see the entire extents of the model by clicking the
Reset View button ( ) or pressing CTRL+r. In addition, the camera can be reset to only the
currently selected objects by clicking the Reset to Visible button ( ) or pressing CTRL+e.
Resetting the view also has the effect of changing the orbit center when orbiting.

2.3.5. Orbiting
Orbiting is the action of spinning the camera about its focal point, which is the center of the
model or center of the selection, depending on which reset action was last performed. By default,
orbit works as if there is an invisible sphere around the model on which you click and drag the
mouse to spin. Alternatively, orbiting can be performed similarly to Smokeview by going to the
View menu and selecting, Use Smokeview-like Navigation. In this mode the camera spins about
the Z axis with left and right mouse movements and about the local X axis with up and down
movements.

2.3.6. Filtering
There are several ways to filter the objects shown in the 3D view. Filtering can be performed with
clipping planes that are associated with floors or through filter buttons that can quickly show/hide
categories of objects.

To use clipping, the user must first define floors for the model as discussed in Section 8.5. Once the
floors are defined, a floor can be selected by using the Floor Drop-down above the 3D or 2D view
as shown in Figure 7.

Figure 7. Floors drop-down

Once a floor has been selected, its clipping planes will be applied to the entire scene to only show
objects within the clipping region.

Filtering can also be performed using the filter toolbar buttons as shown in Figure 8.
Selecting/deselecting these buttons will quickly show/hide all objects of a specific type, such as

19 Chapter 2. PyroSim Basics


PyroSim - User Manual

obstructions, holes, vents, etc.

Figure 8. Filter toolbar

Filtering can also be applied to meshes but in a slightly different way. Instead of showing/hiding
all meshes, the user can selectively show/hide three different elements of them using the mesh
filter toolbar shown in Figure 9. This toolbar selectively allows viewing mesh grid lines, mesh
boundaries, and mesh outlines. Filtering mesh elements shows the different mesh elements.
Figure 10 shows the grid lines, Figure 11 shows the boundary, and Figure 12 shows the outline.

Figure 9. Mesh filter toolbar

Filtering mesh elements

Figure 10. Mesh lines Figure 11. Mesh boundary Figure 12. Mesh outline

Background images attached to floors can be quickly shown/hidden using the Show Background
Image filter button ( ) next to the floor drop-down.

2.4. 2D View
The 2D view is mostly the same as the 3D view with some key differences:

• The 2D view does not have the Orbit and Roam tools.

• The Select/Manipulate tool pans the model when dragging the right mouse button rather
than orbiting.

• Drafting is performed differently in the 2D View. For more information, see Section 9.4.

• Snapping can be performed to either the solution mesh or to a user-defined sketch grid.

• When snapping to a solution mesh, the mesh grid lines are always shown, the boundary is
never shown, and only the outline of the mesh can be optionally shown.

Chapter 2. PyroSim Basics 20


PyroSim - User Manual

• Floor clipping is slightly different, for more information see Section 8.5.

2.5. Record View


The Record View shows an up-to-date display of the FDS input file currently represented by the
PyroSim model. This view is divided into two sections, the Model Records and the Additional
Records.

2.5.1. Model Records


This read only sections allows the user to see an exact copy of the file that will be input into the
FDS simulator based on their current model. The user adjust font size of this using the Increase
Font Size ( ) and Decrease Font Size ( ) buttons at the top of the page. Other settings related to
the file display can be toggled through the Preferences menu item.

2.5.2. Additional Records


Due to the complexity of the FDS simulator, it is difficult to support all possible records and input
files. The Additional Records section of the Record View can be used to inject lines of text into
the top of the FDS input file.

2.6. Scenarios
Scenarios can be used to manage variations of a single model. Any time a simulation object is
enabled or disabled, that change is retained by only the current scenario. Objects can also be
enabled or disabled per scenario via the Enable/Disable Object(s) per Scenario dialog, found in
the context menu opened by right-clicking a selected object.

Multiple fire scenarios can be managed using the Scenarios box on the main toolbar. The Edit
Scenarios dialog, activated by the toolbar button next to the Scenarios box, can be used to
manage scenarios and examine which objects are enabled in a specific scenario.

For models that use multiple scenarios, a bulk export option is available on the File menu in the
Export submenu, called Export Scenarios. Using this feature will export an FDS input file (and
other supporting files) for each scenario in subfolders where the PSM file has been saved. A BAT
file will also be produced that can be double-clicked in Windows Explorer to run all scenarios in
sequence.

You can learn more about the scenarios feature by following along with the PyroSim Scenarios
Tutorial.

21 Chapter 2. PyroSim Basics


PyroSim - User Manual

2.7. Snapshots of Display


Images of the current display can be saved to a file by opening the File menu and clicking
Snapshot. The user can specify the file name, image type (png, jpg, tif, bmp), and the resolution. A
good choice for image type is Portable Network Graphics (png).

2.8. Preferences
PyroSim preferences can be set by going to the File menu and choosing Preferences. Any changes
to the preferences will be set for the current PyroSim session and be remembered the next time
PyroSim is started. The preferences are split into several groups, including PyroSim, Record
View, FDS, Results, and Display preferences.

2.8.1. PyroSim Preferences


These describe global PyroSim preferences as shown in Figure 13.

Figure 13. PyroSim preferences

Format FDS file for easy reading


Controls the format of real numbers in the FDS input file created by PyroSim. When this is
checked, a real number is written such that if the absolute value is >=.001 and < 10000, it is

Chapter 2. PyroSim Basics 22


PyroSim - User Manual

written in decimal notation; otherwise, it is written in scientific notation.

Max precision
Controls the number of significant digits written to the input file.

Number of Recent Files


The maximum number of files that will be shown in the File → Recent PyroSim Files or File
→ Recent FDS Files menus.

Autosave
Instructs PyroSim to periodically create a backup of the current model that is deleted when the
PyroSim model is closed. This backup is useful in case PyroSim crashes or the computer loses
power. The backup file is stored in the same directory as your PyroSim file. If your working
PyroSim file (testing.psm for example) becomes corrupted, then you can find the file that starts
with a tilde like ~testing.psm shown in Figure 14. This file is sometimes preferred if you have a
crash, as it will be the most up to date version of your work before your crash. If it cannot be
opened or results in an immediate crash, there is another backup file described next that is the
second best option. The default setting enables this feature and saves every 10 minutes. In
some cases, when working with large models, this can cause unexpected delays during the
save and some users prefer to disable the feature and save manually.

Figure 14. PyroSim backup files

Create Backup on Open


Controls whether PyroSim makes a backup copy of the PyroSim file after last successfully
opening it. This backup remains on disk when the main PyroSim file is closed, and so it can be
used in case the main file somehow becomes corrupted. The backup file is stored in the same
directory as your PyroSim file. If your working PyroSim file or the automatic backup file
becomes corrupted, then you can find the autosave backup file that has a tilde in the file
extension, like testing.~sm shown in Figure 14. Rename (recommended) or delete your current
working file, then change the file extension on this backup file, changing the tilde in the
extension (.~sm) to a p character to get .psm. You can now open the new .psm file as you
normally would.

If this is enabled, PyroSim files may take slightly longer to load depending on how
NOTE
quickly the file can be copied to backup.

23 Chapter 2. PyroSim Basics


PyroSim - User Manual

Record Preview
Adds a preview pane to many of the dialogs in PyroSim. This preview pane shows the text that
will be produced for the FDS input file. This can be helpful for users that want to understand
exactly how PyroSim options correspond to FDS input.

Show Splash Screen on Startup


Controls whether the PyroSim splash screen is shown when starting PyroSim.

Keyboard Shortcuts
Launches a dialog for mapping various PyroSim actions to user specified shortcuts.

2.8.2. Keyboard Shortcuts


The Keyboard Shortcuts dialog is launched from the PyroSim preferences panel. These
preferences bind combinations of modifier keys (ALT, CTRL, SHIFT, etc.) with other key presses
to activate PyroSim actions.

Figure 15. Keyboard Shortcuts Dialog

Chapter 2. PyroSim Basics 24


PyroSim - User Manual

The dialog is divided into three sections.

Global
These actions are available in most cases and generally match the behavior of other modeling
tools.

View
Changes the way the current model is displayed.

Tool
Generally used to draw or to manually manipulate the model.

To change the keybinding for an action, click the value in the Key Press column. This launches an
editor window (Figure 16) with four options.

Figure 16. Keyboard Shortcut Editor Dialog

Awaiting Input
Press a key to assign the desired keybinding and map it to the action.

Cancel
Exit the editor window without making any changes.

Reset
Assign the action it’s default keybinding.

Clear
Remove the currently assigned keybinding from the action.

Some keyboard shortcuts are used by Java UI components. If a shortcut does not result in the
expected behavior, it may be in direct conflict with a preexisting Java shortcut. It is best practice
to avoid these conflicts (Default Swing key bindings).

2.8.3. Record View Preferences


These preferences control the visualization of the FDS input file in the Record View. They can be
seen in Figure 17.

25 Chapter 2. PyroSim Basics


PyroSim - User Manual

Figure 17. Record View Preferences

Font Size
Change the size of the text used to display the FDS input file.

Enable Syntax Highlighting


Controls whether or not PyroSim uses colors to improve readability of the FDS input file.
Disabling this option will cause the record view to update faster and consume less memory.

Set Limit for Highlighting HOLE and OBST records


Sets the total number of HOLE and OBST records to highlight in the FDS input file, which
improves readability. Increasing this value will decrease performance and consume more
memory, and decreasing this value will increase performance and consume less memory.

2.8.4. FDS Preferences


These preferences define the execution of FDS within PyroSim. They can be seen in Figure 18.

Chapter 2. PyroSim Basics 26


PyroSim - User Manual

Figure 18. FDS Preferences

Executable Locations
Allow you to specify the FDS and Smokeview executables that are used by PyroSim.

PyroSim is designed to work with a specific version of FDS as noted below the
NOTE executable locations. If you specify a different version, you may encounter
unpredictable FDS results or errors.

Optimize Processor Utilization


Controls how meshes are distributed between available MPI processes.

Basic (Default)
PyroSim distributes meshes evenly across MPI processes.

None
PyroSim allows MPI to manage mesh distribution (default prior to PyroSim 2020.3). MPI
assigns one mesh to all available MPI processes, however if the model has more meshes
than available logical processors the last MPI process will be assigned multiple meshes. This
can lead to increased simulation time.

27 Chapter 2. PyroSim Basics


PyroSim - User Manual

Auto-save PyroSim model before running FDS


Controls whether PyroSim automatically saves the current PyroSim file just before beginning
an FDS simulation.

Run Results when FDS simulation completes


Indicates whether to automatically launch the PyroSim 3D Results when an FDS simulation
completes.

Parallel Execution Settings


Controls the number of MPI processes that are generated when using Parallel execution.

Create Process for Each Mesh


Creates one MPI process for each FDS mesh.

Limit Processes Based on Logical Processor Count (Default)


Creates one MPI process for each logical processor available.

FDS GEOM
Controls parameters related to immersed boundary obstructions, which is a new type of
obstruction coming in a future release of FDS. The current release of FDS provides preliminary
support for these types of obstructions but does not yet provide a guarantee on their level of
support. Unlike normal obstructions, immersed boundary obstructions do not need to be
converted to blocks when writing to the FDS input file. Instead, FDS will use their surfaces to
cut FDS cells for more accurate geometry representations.

Enable FDS GEOM


Enables support for immersed boundary obstructions in the PyroSim user interface. If
checked, additional actions are provided to convert obstructions into immersed boundary
obstructions as discussed in Section 8.1.5 and to write them to the FDS input file. When
importing an FDS file with immersed obstruction (GEOM) records, this option must be
checked in order for those objects to be written as GEOM records; otherwise, they will be
rasterized like other obstructions.

Validate GEOM obstructions


Indicates whether the geometry of obstructions should be validated when converting to
immersed obstructions. FDS' specification for immersed geometry is fairly strict in that an
object’s faces must form a closed, manifold volume. The validation process attempts to
correct slight errors in the geometry to ensure a closed manifold is generated. It may cause
conversion to take slightly longer but will help reduce geometry errors when writing the
FDS input file. It is recommended to leave this option enabled. See Section 8.1.5 for more
information.

Chapter 2. PyroSim Basics 28


PyroSim - User Manual

Enabling FDS GEOM will not automatically treat all obstructions as


immersed, as doing so could severely impact simulation performance and
cause other geometry issues. Instead, obstructions must be converted
NOTE
manually using one of the methods mentioned above. For now, it is
recommended to only convert obstructions with curved or slanted
geometry that are significant to the simulation, such as an angled roof.

2.8.5. Results Preferences


There are a number of preferences that control the files created by PyroSim when an FDS
simulation is started that affect the results (either PyroSim 3D Results or Smokeview).

Figure 19. Results Preferences

Include mesh boundaries in CAD files


Whether to include the non-open boundaries of the meshes in any CAD files that are written.

Output Views file


Whether to output a file that ends with the .views extension. This file contains information for
all the views in the model (see Chapter 3) and can only be read by the PyroSim 3D Results.
Enabling the views file prevents views from being written to the Smokeview INI file, see

29 Chapter 2. PyroSim Basics


PyroSim - User Manual

Section 3.4.

Output PyroGeom file


Whether to output a file that contains all CAD, obstruction, and vent geometry that can be
viewed in the PyroSim 3D Results. This file represents the geometry before being converted to
blocks for FDS and provides a high-quality visual in the 3D results. Objects in this file are also
properly animated (turned on/off) if the objects have control logic associated with them, unlike
the GE1 file.

NOTE This file is not viewable in Smokeview.

Output INI file


Whether to output an INI file for Smokeview. This file contains shading information and some
initialization information. If Output View file is unchecked, it also includes view information
for Smokeview.

Output GE1 file


Whether to output a GE1 file. The GE1 file is similar to the PyroGeom file in that it includes
CAD, obstruction, and vent geometry before block conversion. While this file format is
viewable in both PyroSim 3D Results and Smokeview, it has some limitations:

• CAD texture coordinates may not map properly.

• Objects with control logic are not animated.

Show GE1 file by default


Whether to show the GE1 file by default in Smokeview rather than snapped obstructions and
vents. This option can only be used if Output INI file is also checked.

2.8.6. Rendering and Display Preferences


These preferences define advanced 2D and 3D display properties, as shown in Figure 20. They can
be used to improve display performance on complex models, but they tend to create problems for
some older graphics cards, including crashing. For this reason, they are turned off when running
in safe mode.

Chapter 2. PyroSim Basics 30


PyroSim - User Manual

Figure 20. Rendering Preferences

GPU Information
Provides information about the graphics hardware being used to render the 3d and 2d
graphics.

Hardware accelerated cursor


When checked, mouse crosshairs and object editing will remain smooth even on complex
geometry that may be slow to pan or orbit. PyroSim does this by rendering the scene into an
image buffer and then rendering that buffer as a texture underneath the crosshairs or editing
geometry whenever the mouse cursor moves.

Hardware accelerated vertex buffers


When checked, this can significantly improve rendering performance of complex geometry.
PyroSim does this by storing the geometry in vertex buffers on the graphics card. PyroSim then
makes very few OpenGL calls to render the geometry.

Scene Geometry
Controls how scene geometry is rendered.

31 Chapter 2. PyroSim Basics


PyroSim - User Manual

Use Hardware Shaders


Uses OpenGL shaders to render the scene geometry if available. Typically, the use of
shaders will improve the shading quality of objects and on some GPUs may significantly
increase performance.

Use Compatibility Renderer


Uses the fixed-function OpenGL pipeline to render geometry. This is compatible with older
GPUs.

Multisamples
Controls the antialiasing setting to smooth edges of objects. The values available depend on
the GPU, but typically range from 0 to 16. A value of 0 will turn antialiasing off and will
cause edges of objects to look jagged. Larger values increase visual quality, but may lower
performance, depending on the GPU. A value of 4 usually provides a reasonable balance
between quality and speed.

Anisotropic Filtering
Controls the texture quality when textured geometry is viewed at a large angle to the
camera. Available values depend on the GPU and typically range from 1 to 16, where 1 turns
off anisotropic filtering. Larger values improve the texture quality. Most GPUs see negligible
performance impact setting this to a high value.

2.9. Configuration Files


PyroSim stores data related to user preferences in a file called PyroSim.props. By default, this file
can be found in one of the following locations.

%APPDATA%\PyroSim\PyroSim.props
%PROGRAMDATA%\PyroSim\PyroSim.props

If at least one of these files exists, PyroSim will use it to load the user preferences. If both files
exist, PyroSim will load user preferences from both files, giving preference to the file located in
the APPDATA folder. This way the preference file located in the PROGRAMDATA folder can be shared
among multiple machines, and the file located in the APPDATA folder on each machine overrides
the shared settings.

The PROPS file is stored in a plaintext format, and can be viewed or edited with any conventional
text editor. While it is not recommended to edit the file directly, some troubleshooting techniques
may involve deleting the PROPS file so that a new one can be created from scratch by PyroSim.

Configurations for hotkeys in PyroSim is stored in a separate file named keybindings.json located
in the APPDATA folder.

Chapter 2. PyroSim Basics 32


PyroSim - User Manual

2.10. Units
Models can be created in either English or Metric units. To select a system of units, on the View
menu, click Units, then click the desired unit. PyroSim will automatically convert your previous
input values into the unit system you select. The Record View will always display values in the
appropriate FDS units, regardless of what unit system you choose to work in.

2.11. Color Schemes


To select a Default, Black Background, White Background, or Custom color scheme, on the View
menu, click Color Scheme. The custom color scheme is defined in the PyroSim.props file in the
PyroSim installation directory (For Windows 10 look in
%USERPROFILE%\AppData\Roaming\PyroSim\PyroSim.props while some older operating systems use
C:\Program Files\PyroSim).

1. To define a custom color scheme:

2. Close PyroSim

3. Edit the PyroSim.props file

4. Change the following default colors to the colors you wish:

Colors.Custom.axis=0xffff00
Colors.Custom.axis.box=0x404040
Colors.Custom.axis.text=0xffffff
Colors.Custom.background=0x0
Colors.Custom.boundary.line=0xffffff
Colors.Custom.grid=0x4d4d66
Colors.Custom.group.highlight=0xffff00
Colors.Custom.heatDetector=0xff0000
Colors.Custom.obst=0xff0000
Colors.Custom.obst.highlight=0xb2b200
Colors.Custom.origin2D=0x737373
Colors.Custom.smokeDetector=0xff00
Colors.Custom.snap.point=0xff00
Colors.Custom.snapto.grid=0x404040
Colors.Custom.snapto.points=0xc0c0c0
Colors.Custom.sprk=0xff
Colors.Custom.text=0xffffff
Colors.Custom.thcp=0xffff00
Colors.Custom.tool=0xff00
Colors.Custom.tool.guides=0x7c00

5. Save the edited PyroSim.props file

33 Chapter 2. PyroSim Basics


PyroSim - User Manual

6. Restart PyroSim

Chapter 2. PyroSim Basics 34


PyroSim - User Manual

Chapter 3. Views
PyroSim provides the capability to save and recall view state from the 3D and 2D views in an
object called a View. Views can also be used to specify clipping regions that limit the amount of
the model shown in the 3D and 2D views. Views appear in the Navigation View as shown in
Figure 21.

There can be multiple views in a model, but at any given time, there is always one active view. A
new model will always start with one default view that has no view state associated with it. State
can be added to the view as described in the sections, Section 3.2 and Section 3.3.

Figure 21. Views Tree

3.1. Managing Views


Views are managed in the navigation view. From there, they can be created, deleted, grouped,
rearranged, etc.

A view can be created in one of the following ways:

• In the View menu, select New View.

• In the navigation view, right-click the Views group and select New View.

• Right-click empty space in the 2D or 3D view and select New View.

This will add a new view to the model, saving the current camera viewpoint and section box into
the new view (see the following sections to learn more about viewpoints and section boxes). The
new view will become the active view.

To delete a view, select it in the navigation view and in the Edit menu, select Delete. A view can
only be deleted if it is not active.

35 Chapter 3. Views
PyroSim - User Manual

To activate a view, perform one of the following:

• Double-click the view or the view’s viewpoint in the navigation view.

• Right-click a view in the navigation view and select Set Active.

Activating a view will restore all its saved state as described in the following sections.

View settings can be copied or moved between views. To copy settings such as the viewpoint or
section box select Copy, located in either the navigation view or in the Edit menu. To paste the
settings to another view, select the desired target view and in the Edit menu select Paste. To move
settings from one view to another, in the navigation view, drag the setting to the desired view.

Viewpoints and section boxes can only be moved or pasted into a view if the view
NOTE does not already contain a viewpoint or section box, depending on what is being
pasted.

3.2. Viewpoints
Each view can have one viewpoint associated with it. A viewpoint includes the 2D or 3D camera’s
position, orientation, zoom, and camera type (3D versus 2D). When a viewpoint is saved, the
current navigation tool is also saved with the view (Orbit, Roam, etc.). A viewpoint appears in the
navigation view as a child item of a view and is labelled Viewpoint. This can be seen in Figure 21
for the two views, Inside and Section.

A viewpoint is automatically saved to newly created views. A viewpoint can also be explicitly
saved in one of the following ways:

• In the View menu, select Save View. This will save the viewpoint to the active view.

• Right-click empty space in the 2D or 3D view and select Save View. This will also save the
viewpoint to the active view.

• Right-click a View or Viewpoint in the navigation view and select Save Viewpoint. This will
save the viewpoint to the selected view.

The scene camera can be reset to a viewpoint in one of the following ways:

• Double-click the currently active view. This will reset the viewpoint to that saved with the
active view.

• Double-click a viewpoint in the navigation view. If the viewpoint is not already in the active
view, that viewpoint’s view is activated.

• Right-click a viewpoint in the navigation view and select Reset to Selected Viewpoint.

Chapter 3. Views 36
PyroSim - User Manual

• Right-click empty space in the 3D or 2D view and select Reset to Viewpoint. This will reset to
the viewpoint in the active view.

• In the View menu select Reset to Viewpoint. This will also show the viewpoint stored in the
active view.

A viewpoint can be removed from a view by selecting the item, Viewpoint, in the navigation view
and deleting it.

When a view with a viewpoint is activated, the following occurs:

1. Either the 3D View or the 2D View is selected, depending which was active when the
viewpoint was saved.

2. The saved camera properties are restored.

3. The saved navigation tool is activated.

3.3. Section Boxes


A section box may also be added to a view. A section box is a convex region defined by six sides
that is used to limit the scope of visible geometry. All geometry outside the box is clipped from
view. An example of the clipping is shown below.

Effect of a Section Box

Figure 22. Section box disabled Figure 23. Section box enabled

A section box can be created in several ways:

• Right-click a view that does not already have a section box and select Add Section Box. This
will add a section box that encompasses all visible geometry.

37 Chapter 3. Views
PyroSim - User Manual

• In the View menu select Add Section Box. This will add a section box to the active view if it
does not already have one.

• Right-click in empty space in the 2D or 3D view and select Add Section Box. This will also add
a section box to the active view.

• Select several geometric objects, right-click one of them, and select Create Section. If the
active view does not already have a section box, one will be added that encompasses only the
selection. If the active view already has a section box, a dialog will be shown that gives the
option of replacing the active view’s section box or creating a new view with the section box.

When a section box is added to the active view, the selection tool is selected so the
NOTE
new section box can be quickly edited. See Section 2.3.2 for more information.

A section box is displayed as a dashed outline of the region. Each section box has a color
associated with it that is used to display both the outline of the section box and the clipped
portions of solid, clipped objects as shown in Effect of a Section Box, Figure 22. In this figure, the
section box is green, so any geometry that is clipped including the walls and slab in the image are
also colored green.

The scope of a section box can be edited by selecting the section box and manipulating it like any
other geometric object, see Section 9.16. Section boxes can also be rotated and moved like other
geometric items, see Section 9.17.

The properties of a section box can be edited by either double-clicking the section box or by right-
clicking it and selecting Properties.

See Figure 24 below.

Figure 24. Section box properties dialog

The active section box can be disabled in the 2D or 3D view by de-selecting Enable Section Boxes
in the View menu. The display for the section box can be independently hidden from view by de-
selecting Show Section Boxes in the View menu.

Chapter 3. Views 38
PyroSim - User Manual

A section box can also be reset to encompass the currently visible objects by performing one of
the following:

• Right-click the section box to reset, and select Reset Section Box.

• On the View menu, select Reset Section Box. This will reset the section box in the active view.

• Right-click on empty space in the 2D or 3D view and select Reset Section Box. This will also
reset the section box in the active view.

When viewing a section box with a specific Floor active (see Section 8.5), the
clipping region is the union of the sides of the section box and the Z clipping
NOTE
planes of the floor. The top and bottom faces of the section box are not used in
this configuration.

3.4. Smokeview Interoperability


Smokeview supports the concept of viewpoints, which are similar to PyroSim views. Smokeview
viewpoints are defined by camera position, orientation, a navigation tool, and up to six axis-
aligned clipping planes. Viewpoints are stored in the Smokeview INI file.

By default, when PyroSim prepares an FDS simulation or exports an FDS file, it also writes a Views
file that can be read in the PyroSim 3D Results but not Smokeview. It does not write the views to
the Smokeview INI file. This is to avoid view duplication in the 3D Results. This behavior can be
changed, however, by turning off the Views file in the preferences, see Section 2.8. If turned off,
PyroSim will instead write the view information to the INI file, which can be read in Smokeview.

At any time, the view information can be updated for the results without re-running the
simulation by explicitly writing either the PyroSim Views file or the Smokeview INI file. This can
be done by going to the File menu, and selecting either Export→PyroSim Viewpoints or
Export→Smokeview INI, respectively.

While the Views file exports views exactly as defined in PyroSim, there are some limitations to
how PyroSim views are exported to the Smokeview INI file:

• Only views with viewpoints that were saved from the 3D View are written.

• Camera "roll" information is not exported, which means that the Smokeview viewpoints might
not match the orientation in PyroSim perfectly. The only way to guarantee that the orientation
matches is to use the Roam tool in PyroSim to orient the camera.

• Zoom information is not exported.

• Only section boxes that have not been rotated are exported.

• Sometimes the geometry is not visible in Smokeview from an exported viewpoint due to

39 Chapter 3. Views
PyroSim - User Manual

incorrectly chosen near and far clipping planes in Smokeview.

In addition, if a view was saved in PyroSim with the Roam tool active, the Rotation type in
Smokeview is set to Eye centered. For all other navigation tools, the Rotation type in Smokeview
is set to 2 axis.

Smokeview viewpoints may also be imported into PyroSim. This is useful if additional views have
been specified in Smokeview while viewing the results and those viewpoints should be preserved
in PyroSim. To import Smokeview viewpoints, perform the following:

1. On the File menu, select Import FDS/CAD File.

2. Choose the INI file that accompanies the SMV file that was viewed.

Importing a Smokeview INI file also requires that the corresponding SMV file be
NOTE read by PyroSim. If an SMV file with the same name as the INI file is not found in
the same file directory as the INI file, the user is asked to choose the SMV file.

After importing, a new view group is added, containing one PyroSim view for each Smokeview
viewpoint that was in the INI file.

Chapter 3. Views 40
PyroSim - User Manual

Chapter 4. Working with Files


Several files are used when performing a fire analysis using PyroSim. These include the PyroSim
model file, the FDS input file, and FDS output files. This section describes how to load and save
files in the formats supported by PyroSim.

4.1. Creating a New PyroSim Model


When PyroSim is started, it begins with an empty model. You can close the current model and
create a new empty model by opening the File menu and clicking New. PyroSim always has one
(and only one) active model.

4.2. Saving a PyroSim Model


The PyroSim model file (PSM) is stored in a binary format that represents a PyroSim model. The
PyroSim model contains all the information needed to write an FDS input file, as well as
additional information such as obstruction grouping, floor heights, background images, and
textures. This format is ideal for sharing your models with other PyroSim users.

To save a new model:

1. On the File menu, click Save.

2. Enter the file name and click the Save button.

4.3. Open a Saved PyroSim Model


PyroSim model files have a PSM extension. To open a saved model:

1. On the File menu, click Open.

2. Select the file and click the Open button.

A list of recently opened files is also available. To open recent files, on the File menu, click Recent
PyroSim Files, then click the desired file.

PyroSim has an auto-save feature which stores a copy of your current model every 10 minutes.
This file is automatically deleted if PyroSim exits normally, but if PyroSim crashes, you can
recover your work by opening the autosave file. It can be found either in the same directory as
your most recent PSM file, or in the PyroSim installation directory if your model was unsaved.

For more information about opening files saved with previous versions of PyroSim, please refer to
Appendix A and Appendix B.

41 Chapter 4. Working with Files


PyroSim - User Manual

4.4. Preventing Changes to a Model


PyroSim supports write protection for a model. When write protection is enabled, users cannot
modify a model (e.g. change geometry, edit surface properties, etc). This option can be enabled
with or without password protection. If a model is write-protected, PyroSim will display
notification in the application title bar.

To add write protection to a model:

1. On the File menu, click Write Protection.

2. Click OK.

The model will now be write-protected. Since a password was not used, a password will not be
required to remove write protection.

To remove write protection from a model:

1. On the File menu, click Write Protection.

2. Click OK.

The model can now be edited. If needed, the dialog will require a password to release the lock.

4.5. Importing FDS Models


PyroSim allows you to import existing FDS input files. When you import an FDS file, PyroSim will
create a new PyroSim model from the imported file. During import, PyroSim will check for the
validity of each record. If errors are detected, you will be notified. You may then make the
required corrections and attempt to import the file again.

To import existing FDS models into PyroSim:

1. On the File menu, select Import FDS/CAD File. or click the Import button ( ) on the main
toolbar.

2. Select the FDS file and click Open.

PyroSim supports file import for versions 4, 5, and 6 of FDS. For more information about opening
files compatible with version 4 or 5 of FDS, please refer to Appendix A and Appendix B.

4.6. Exporting FDS Models


PyroSim also allows you to explicitly export the current model to an FDS input file. You can
manually edit the file to take advantage of advanced FDS features, or to easily transfer the input

Chapter 4. Working with Files 42


PyroSim - User Manual

file to a different machine or special version of FDS.

To export an FDS file:

1. On the File menu, click Export, then click FDS File. or click the Export button ( ) on the
main toolbar.

2. Enter the file name and click Save.

The file exported by PyroSim will be compatible with version 6 of FDS.

4.7. Importing CAD files


PyroSim can import geometry from several CAD formats, including buildingSMART’s IFC format
for Building Information Models (BIM), AutoCAD’s DXF (Drawing Exchange Format), DWG, FBX,
DAE, OBJ, and STL files. Each type of file provides a variety of geometry that can either be directly
represented as obstructions or as drawing guides in the PyroSim model.

IFC
Provides building information model (BIM) data in a fully 3d format. This format contains
advanced data about the types of objects in the building, including slabs, stairs, and doors,
though it is currently only used for geometry import in PyroSim. It also contains information
about whether objects are solid and is supported as an export format for many architectural
CAD packages, including Revit. Unlike with the other import formats, however, textures are not
currently supported.

DXF
A basic CAD format provided by Autodesk. This format supports robust geometry types,
including 3d faces, lines, and text, but it does not support appearance information, such as
textures, lighting parameters, etc. PyroSim may perform special post-processing of the data
because a single object in a DXF file may have mixed geometry types, including lines, points,
and faces. In PyroSim (and FDS), obstructions can only have faces. For this reason, PyroSim
splits up these mixed objects into two, so that one object is an obstruction with only faces, and
the other object is just meta data with lines and possibly points.

DWG
Similar to DXF, but it also has basic support for appearances, including textures. It has only
basic support for mapping textures onto objects, however, and few CAD applications can
export DWG files. Some, such as Revit, exclude material and texture information, see Section
4.7.2.

43 Chapter 4. Working with Files


PyroSim - User Manual

FBX
Provides support for 3d faces only, but it has very good support for appearance information
and texture mapping. In addition, many 3D modeling applications have built-in support for
exporting FBX files. Unfortunately, this format has no information about whether objects are
solid, so PyroSim treats them as collections of thin faces. This can cause issues if holes are
intersected with objects from these files, as smoke will be able to enter the cavity of solid
objects. With the exception of holes, though, this is still a good format for importing 3D
building models into PyroSim.

STL
A basic file format that is simply a listing of triangles. There is no appearance or texture
information.

Unlike FDS import, which completely replaces the current PyroSim model, CAD import appends
the data to the current model. This facilitates the ability to import data from several CAD files into
one PyroSim model. This is useful when there is one blueprint per floor of a building or a 3D
building has been split into several sections, each in a separate file.

To import one of these files, under the File menu, select Import FDS/CAD File and select the
desired file.

STL files will import as shown in Section 4.7.1. For non-STL files, a step-by-step dialog will open as
shown in Figure 25.

CAD files store display information in objects called "Materials". These materials
are converted into appearance objects and surfaces in PyroSim. They do not
NOTE
correspond with the FDS definition of a material. See Section 7.4 for more
information about appearances.

Chapter 4. Working with Files 44


PyroSim - User Manual

Figure 25. CAD import units

Figure 26. CAD import settings

45 Chapter 4. Working with Files


PyroSim - User Manual

Figure 27. CAD import options

1. FBX Exporter: If an FBX file is being imported, the second prompt will ask what software was
used to export the file. If a SimLab FBX plugin or Unreal Engine was used to create the FBX
file, choose the appropriate option from the drop-down box; otherwise; choose Unknown. This
selection controls the default settings in the subsequent prompts. In some cases, PyroSim is
able to detect whether the file was exported using a SimLab plugin and will select this option
automatically.

2. Units: The next prompt asks the user to select the base unit in which the CAD file was created.
If the drawing was saved in a more recent file format, the prompt will default to the unit type
stored in the file. The dialog box shows the model’s width, depth, and height based on the
selected unit as a guide for selecting the unit.

3. Import Settings: The next several prompts (Figure 26) allow the user to control how some of
the data is imported and to correct some data that may have been written incorrectly by the
file’s CAD exporter.

Normal Tolerance (DWG/DXF only)


Controls the quality of curved objects. Decreasing this value produces higher quality
objects at the expense of slower rendering speed. The default value of [stem
6fed8823511909ba34704c1948f66a03] provides a nice balance.

NURB Gridlines (DWG/DXF only)


Controls the quality of NURB surfaces. Increasing this value gives higher quality curves at

Chapter 4. Working with Files 46


PyroSim - User Manual

the expense of slower rendering speed. The default value of [stem


9612eecfec9dadf1a81d296bd2473777] provides a good balance.

Lighting
Controls how objects are lit.

Auto-correct inverted polygons


Some CAD files contain information about the normal of a polygon that affects how the
polygon is lit. In some cases, the normal may not match the orientation of the polygon,
which can cause the polygon to appear too dark. Selecting this option will allow
PyroSim to try to detect these cases and correct the orientation of the polygon so it may
be lit correctly. This option works well in most models and is generally safe to leave on.

Crease Angle
Some CAD files do not provide lighting data for objects to determine whether they
should look smooth or faceted. In this case the crease angle is used to determine this
information. If the angle between two adjacent faces is greater than this value, the faces
will be look like they are two separate, faceted faces. Otherwise, the two faces will look
like one smooth curved face. This option may also affect whether the edges of faces are
displayed when the Show Object Outlines option is enabled.

Materials
Specifies how CAD materials are imported. CAD materials control the imported objects'
color and lighting. See Section 7.4 for more information.

Merge identical materials


Some CAD exporters (namely SimLab’s Revit FBX plugin) will create a unique material
(appearance) per object in the file, which may lead to hundreds or thousands of
materials that have duplicate properties. Selecting this option allows the materials with
duplicate properties to be merged into one material, significantly reducing the number
of materials in the model with no loss of quality.

Ignore transparency color (FBX only)


In FBX files, material transparency is determined from a transparency color and factor.
Some CAD exporters (SimLab’s FBX plugins) export the color incorrectly. Selecting this
option will allow PyroSim to ignore the transparency color in the FBX file and only use
the transparency factor, which allows transparency in these files to import correctly.
This option should only be selected if it is known that the file came from a SimLab
plugin or there are transparency problems without it selected (For example, objects that
should be transparent are not or vice versa).

47 Chapter 4. Working with Files


PyroSim - User Manual

DirectX normal maps (FBX and IFC only)


Indicates whether the normal maps in the imported file use the DirectX convention,
where +Y is down.

Workflow (FBX and IFC only)


Specifies the lighting workflow to be used for imported materials. More information
can be found in Section 7.4. The following values are available:

As defined in file
The materials are imported exactly as they were specified in the file. Currently, this
means that the materials will be imported using the Specular (Basic) workflow, as
this is the only workflow currently supported by IFC and FBX files. In some cases,
however, such as when an FBX file is exported from Unreal Engine, the PBR
parameters are packed into the basic specular texture property. In this case, the
following two options can be used to reinterpret the basic specular workflow as a
PBR workflow for correct lighting.

Metallic (PBR)
The materials should be imported as if they use the Metallic (PBR) workflow, even if
they are specified in the import file using the Specular (Basic) workflow. When
using this option, the PBR parameters can either be set to constant values or can be
reinterpreted from other non-PBR color properties. For instance, when an FBX file is
exported from other software, for each material it might create a single image
containing the Metallic, Roughness, and Ambient Occlusion parameters, stored in
the red, green, and blue color components, respectively. It then might set the
specular texture in the FBX file to this combined image. When an exporter does this,
there should be accompanying documentation with the FBX file that indicates how
these PBR parameters are stored in the FBX file. When importing the FBX file in the
above example, in the import dialog, the Metallic, Roughness, and Ambient
Occlusion properties should all be set to From Specular, and the color components
should be set to R, G, and B, respectively. See Section 7.4 for more information on the
PBR properties.

Specular (PBR)
Similar to the Metallic (PBR) option, this forces imported materials to use the
Specular (PBR) workflow, where the PBR parameters can be reinterpreted from
non-PBR properties.

Object Grouping (IFC only)


Specifies how objects will be grouped once imported into PyroSim. The value can be one of
the following:

Chapter 4. Working with Files 48


PyroSim - User Manual

Spatial (default)
The objects are grouped based on the spatial layout of the model. For instance, the top
group is the building site, the next group is the building, the next are the floors, etc.

By Type
Objects are grouped by type. For instance, there will be a group for walls, furniture,
slabs, etc.

4. Import Options: This prompt allows the user to specify more options for import. Before this
prompt is shown, PyroSim will attempt to discern if the CAD file contains a 2D Floorplan or a
3D Model and will select default values for the options based on the detected type, see Figure
27.

Lines
Check to import lines in the file (default=checked only for floorplans)

Faces
Check to import faces in the file (default=checked only for 3D models)

Move geometry to origin (0,0,0)


If checked, the imported geometry will be moved such that the minimum point of the
bounding box surrounding the imported geometry will correspond with the model origin.

Geometry Offset
Will offset imported geometry on the X, Y, and Z planes by the specified values. If Move
geometry to origin is checked, the geometry will be moved to the origin before being
moved additionally by the Geometry Offset.

Flatten so geometry lies in one plane


If checked, all geometry will be scaled in the Z dimension by a very small scale (1e-9). This
is useful for floorplans that have entities drawn in several planes. This option will flatten
them all into one plane. (default=checked only for 2d floorplans).

Add a blank rectangle to obscure lower floors


If checked, a solid rectangle of the specified color will be added to the model. This is useful
to obscure geometry located on lower floors. The imported rectangle will not become an
obstruction and will be excluded from the simulation. (default=checked only for 2d
floorplans).

5. Choose Finish to import the file.

When PyroSim imports a CAD file, it will treat all 3D face data as obstructions and all other data

49 Chapter 4. Working with Files


PyroSim - User Manual

(lines, curves, etc.) as separate CAD data. If an object in the file contains both face and CAD data,
the entity will be split into two entities so that CAD data can be easily deleted or hidden after
import using the CAD filter button on the 3D/2D View toolbar, see Section 2.3.6.

An object with CAD data can be snapped to while drawing in PyroSim but is not converted to any
type of FDS geometry.

In DWG and DXF files, an entity with face data will either be treated as a single, solid obstruction
with some volume or as a collection of thin obstructions depending on the entity type in the
DWG/DXF file. These objects will be represented as FDS geometry. The following DWG/DXF entity
types are treated as solids in PyroSim:

• 3D Solid

• Mass Element

• Mass Group

• Roof

• Slab4

• Roof Slab

• Stair

• Wall

• Door

• Window

• Curtain Wall

• Curtain Wall Unit

• Curtain Wall Assembly

• Structural Member

While PyroSim allows the user to draw walls and slabs, it will not convert
DWG/DXF wall and slab entities to native walls and slabs, due to the complexity
NOTE with which walls and slabs can be represented in the DWG/DXF file. They will
instead be represented as collections of individual faces, representing one solid
object.

With the exception of IFC files, all other entities and objects from other CAD formats that contain
faces are treated as collections of thin obstructions by PyroSim. They cannot be reliably treated as
solid since there is no guarantee that their faces form a closed and non-self-intersecting shell or
that this would even be desired.

Chapter 4. Working with Files 50


PyroSim - User Manual

Once the file is imported, PyroSim creates a hierarchy of groups and objects, such that there is one
top group, named after the file. The next levels depend on the imported file type. For non-
DWG/DXF files, the structure will mimic the node structure in the source file. For DWG/FXF files,
the next level contains a group for every layer containing geometry. Under each layer group there
are one or more objects representing the entities in the file. The following illustrates the hierarchy
as it would appear in the Navigation View:

• FileName

◦ Layer1

▪ Entity1

▪ Entity2

▪ …

◦ Layer2

▪ Entity3

▪ Entity4

▪ …

◦ …

If the DWG/DXF file contains a block insert and the block contains entities from multiple layers,
the block insert is split into several PyroSim objects, one for each layer of the block’s originating
entities. If all the entities in the block are from the same layer, however, there will be one
resulting PyroSim object that will belong to the group corresponding to the block’s entities’ layer
rather than the block insert’s layer.

4.7.1. Importing STL Files


PyroSim can also import objects from STL files, which are simply listings of triangles. Usually,
each STL file represents the shell of one 3D solid object.

To import an STL file, perform the following:

1. On the File menu, select Import FDS/CAD File. or click the Import button ( ) on the main
toolbar.

2. Select the desired STL file and click Open.

3. Enter the import options in the STL Import Options dialog as shown in Figure 28.

4. Click OK to begin import.

51 Chapter 4. Working with Files


PyroSim - User Manual

Figure 28. STL Import Options dialog

In Figure 28, the following options can be specified:

File Units
The units used to store the 3D coordinates in the STL file.

Vertex weld tolerance


A distance used to determine how far apart vertices must be to be considered separate.

Resulting Geometry Type


Filled Obstruction
Imports the triangles as solid obstructions. The triangles must form one or more closed,
manifold collections of triangles. Each collection of connected triangles is treated as a
separate shell. The shells are grouped such that if one shell is immediately inside another
shell, the outside shell defines the outside of the solid, and the interior shell defines a
hole/cavity in the solid. This option should not be used if there are several touching or
intersecting solids. If this is the case, it is preferable to import the objects using a different
file type.

Hollow Obstruction
Imports the triangles as is. Each set of connected triangles is treated as a separate unfilled
obstruction.

Unstructured GEOM
Imports the triangles as immersed boundary obstructions. The geometry must follow the

Chapter 4. Working with Files 52


PyroSim - User Manual

same rules as with the Filled Obstruction option. See FDS GEOM for more information
about immersed boundary obstructions.

Hole
Imports the triangles as holes that will be subtracted from existing obstructions. The
geometry must follow the same rules as with the Filled Obstruction option.

Surface
The surface to apply to the resulting obstructions if applicable.

Convert to solid obstructions


Whether to treat the resulting objects as solid obstructions. If this is unchecked, each resulting
object will be a collection of thin obstructions.

Because the STL file is simply a listing of triangles, there may be more than one object represented
in the file. PyroSim will use the vertex weld tolerance to detect triangle connectivity and
determine if there are several, disconnected sets of faces in the file. If there are, there will be one
resulting PyroSim object per connected set of faces.

In addition, if the solid option is enabled or the objects are being treated as holes, import will only
succeed if each face set is detected as a closed shell by PyroSim.

4.7.2. Importing Revit Files


While PyroSim cannot directly import Autodesk Revit files (RVT), there are several ways to export
the data from Revit into a file format that PyroSim can read. Each method has advantages and
disadvantages as discussed below.

Revit to IFC (direct)


The first method exports a building information model (BIM) in the industry foundation
classes (IFC) format. This method is simple to use and preserves much of the building
information present in the model. Unfortunately, this method loses all texture information, so
models are not as visually interesting when displayed in PyroSim. To perform the export in
Revit 2019, perform the following:

1. Open the desired RVT file within Revit.

2. Under the File menu, click Export→IFC.

3. Choose the desired IFC filename.

4. Click Modify setup to choose different export settings, if desired.

5. Click Export to save the file.

53 Chapter 4. Working with Files


PyroSim - User Manual

6. Import the IFC file into PyroSim.

Revit to DWG (direct)


This method exports a DWG directly from Revit, which can then be imported into PyroSim.
While simple to perform and only requires Revit, this method loses all information about
materials, including textures, due to Revit’s limited DWG support. To perform the export in
Revit Architecture 2014, perform the following:

1. Open the desired RVT file within Revit Architecture.

2. Click the Revit icon at the top left .

3. Select Export→CAD Formats→DWG.

4. In the DWG Export dialog, for Export, select <In session view/sheet set>.

5. For Show in list, select Views in the Model.

6. Click the Check None button, and then in the view table, select the check box for 3D View:
3D (Other views may be chosen, but the DWG will only contain entities visible in the
selected views).

7. Click the Next. button and choose a file name for the DWG file.

8. Click OK to create the DWG.

9. Import the DWG into PyroSim.

Revit to FBX (direct)


This method exports an FBX file directly from Revit, which can then be imported into PyroSim.
As with exporting a DWG, this method is simple to perform and only requires Revit.
Unfortunately, this method also loses all information about materials and textures because
Revit encrypts the material data, making it unreadable by PyroSim. To export using Revit
Architecture 2014, perform the following:

1. Open the desired RVT file within Revit Architecture.

2. Click the Revit icon at the top left .

3. Select Export→FBX.

4. Choose a file name for the FBX file.

5. Click OK to create the FBX.

6. Import the FBX into PyroSim.

Revit to FBX using third-party plugin


This method requires the use of a third party plugin, but it generally produces good results
with materials, textures, and texture coordinates well-supported. In many cases, this is the

Chapter 4. Working with Files 54


PyroSim - User Manual

most reliable method of reproducing the graphical representation of the original Revit file
within PyroSim. SimLab Soft is one company that provides commercial FBX export plugins for
several CAD packages, including Revit and Sketchup, among others, and provides robust
texture support. To export using a third-party plugin, perform the following:

1. Download and install the appropriate plugin.

2. Follow the plugin’s instructions to export an FBX file from Revit. If the plugin supports
embedded media, select this option before exporting. This option allows textures to be
embedded into the FBX file, making it much easier to transfer the FBX to another
computer, as only file has to be transferred.

3. If the FBX file is to be imported into PyroSim on the same computer as the one that
exported the file or the embedded media option was selected, continue to step 4; otherwise,
some additional steps may be necessary to ensure the textures can be found when
importing into PyroSim:

a. Determine the directory into which the FBX exporter saved the textures. Some
exporters may place the textures in a sub-directory of the FBX file and give it the same
name as the FBX file. Others may save the textures to a common program-specific
location. The SimLab Revit exporter, for example, saves textures for a particular file to
C:\ProgramData\Autodesk\Revit\Addins\SimLab\FBXExporter\data\Imported_Textures\#
where # is a number specific to the exported file, such as 40.

b. If the folder is not already a sub-directory of the FBX file, cut this folder and paste it in
the same location as the FBX file. The pasted folder may be left as is or renamed to be
the same as the FBX file, without the .fbx extension.

c. Transfer the FBX file and the texture folder to the computer that will be importing the
FBX file into PyroSim.

4. Import the FBX file into PyroSim.

Revit to FBX to AutoCAD to DWG


This method requires both Revit and AutoCAD and does not perform a perfect conversion, but
it retains some information about materials and texture coordinates. The steps described here
use Revit Architecture 2014 and AutoCAD 2014.

1. Open the desired RVT file within Revit Architecture.

2. Click the Revit icon at the top left .

3. Select Export→FBX.

4. Specify the desired filename and click Save.

5. Open AutoCAD.

55 Chapter 4. Working with Files


PyroSim - User Manual

6. On the Insert tab in the ribbon, select Import.

7. Select the FBX file created by Revit.

8. The FBX Import Options dialog will appear. The following are recommended settings for
the FBX import:

a. Import section: Make sure Objects and Materials are checked. Lights and Cameras
are unused in PyroSim.

b. Assign Objects to Layers: any option may be selected, but By Material is a useful
option for PyroSim.

c. Unit Conversion: This section is somewhat misleading. While the Current Drawing
Unit is correct, the FBX file unit tends to be incorrect. No matter what unit is displayed
in the greyed-out text for FBX file units, the actual unit in the FBX file is always FOOT.
The appropriate values need to be specified to make the proper unit conversion. For
instance, if the current drawing unit is Millimeters, you can enter the value, 1 on the
left and 304.8 on the right because there is 1 foot per 304.8 millimeters.

d. Block: Uncheck Insert file as block.

9. Click OK to finish the import. You may receive a warning about the clip plane of the
camera.

10. Save the file as a DWG.

11. Import the DWG into PyroSim.

4.7.3. Converting 2D Floor Plans Into 3D Geometry


Some CAD files contain 2D floor plans, which, on their own, cannot be used in a simulation. These
types of files must first be converted into solid 3D geometry. There are two ways in which this can
be accomplished.

The first involves using the floor plan as a guide to draw the 3D model. See Chapter 9 for more
information.

The second is to convert lines that represent walls into 3D walls using automated tools. This can
be done as follows:

• Select a set of 2D lines that represent walls in the model.

• Right-click the selection and select Convert CAD lines into Walls.

• Enter the desired Height and Thickness of the walls.

• Click OK.

This will replace each line with a 3D wall, whose base is centered on the original line.

Chapter 4. Working with Files 56


PyroSim - User Manual

Chapter 5. Meshes
5.1. Working with Meshes
All FDS calculations are performed within computational meshes. Every object in the simulation
(e.g. obstructions and vents) must conform to the mesh. When an object’s location doesn’t exactly
conform to a mesh, the object is automatically repositioned during the simulation. Any object that
extends beyond the boundary of the physical domain is cut off at the boundary. There is no
penalty for defining objects outside of the domain, but these objects do not appear in the Results.

To achieve optimal simulation accuracy, it is important to use mesh cells that are approximately
the same size in all three directions.

FDS uses a Poisson solver based on Fast Fourier Transforms (FFTs). A side effect of this approach
u v w
is that optimal mesh divisions are constrained to the form 2 3 5 , where u, v and w are integers.
6 3 2 2 3
For example, 64 = 2 , 72 = 2 * 3 , and 108 = 2 * 3 are good mesh dimensions. However, 37, 99 and
109 are not. In addition, using a prime number of cells along an axis may cause undesirable
results. PyroSim warns when the number of divisions is not optimal.

5.2. Uniform Meshes


This example illustrates creating a multiple mesh model.

To create the first mesh:

1. On the Model menu, click Edit Meshes.

2. Click New.

3. In the Max X box, type 5.0, in the Max Y box, type 1.0, and in the Max Z box, type 1.0.

4. In the X Cells box, type 50, in the Y Cells box, type 10, and in the Z Cells box, type 10.

5. Click OK.

The 3D View will now display the resulting mesh.

57 Chapter 5. Meshes
PyroSim - User Manual

Figure 29. Defining properties of the new mesh

5.3. Nonuniform Meshes


To create a second, nonuniform mesh:

1. On the Model menu, click Edit Meshes.

2. Click New

Chapter 5. Meshes 58
PyroSim - User Manual

3. In the Min X box, type 0.0, in the Min Y box, type 1.0, and in the Min Z box, type 0.0

4. In the Max X box, type 1.0, in the Max Y box, type 3.0, and in the Max Z box, type 1.0

5. In the Division method box, select Non-Uniform

6. In the table, enter the data shown in Table 2

Table 2. Non-Uniform Mesh Parameters

Dir (X,Y,Z) Num Cells Size

X 10 0.1

Y 10 0.1

Y 5 0.2

Z 10 0.1

7. Click OK

59 Chapter 5. Meshes
PyroSim - User Manual

Figure 30. Defining properties of the nonuniform mesh

You can click or type Ctrl+R to reset the model. The resulting meshes are displayed below.

Chapter 5. Meshes 60
PyroSim - User Manual

Figure 31. 3D display of uniform (blue) and non-uniform (red) meshes

5.4. Using Multiple Meshes


The term "multiple meshes" means that the computational domain consists of more than one
rectangular mesh, usually connected, although this is not required. In each mesh, the governing
equations can be solved with a time step based on the flow speed within that particular mesh.
Some reasons for using multiple meshes include:

• Multiple meshes can be simulated in multiple FDS processes via MPI, leading to faster
simulation run times than using multiple OpenMP threads in a single mesh simulation.

• If the geometry of the problem has corridors such as shown in Figure 31, using multiple
meshes can significantly reduce the number of cells and the solution time.

• Because each mesh can have different time steps, this technique can save CPU time by
requiring relatively coarse meshes to be updated only when necessary. Coarse meshes are
best used in regions where temporal and spatial gradients of key quantities are small or

61 Chapter 5. Meshes
PyroSim - User Manual

unimportant.

Meshes can overlap, abut, or not touch at all. In the last case, essentially two separate calculations
are performed with no communication at all between them. Obstructions and vents are entered in
terms of the overall coordinate system and need not apply to any one particular mesh. Each mesh
checks the coordinates of all the geometric entities and decides whether or not they are to be
included.

As described in the FDS User Guide (McGrattan et al. 2021) the following rules of thumb should
also be followed when setting up a multiple mesh calculation:

Mesh Alignment
The most important rule of mesh alignment is that abutting cells ought to have the same cross
sectional area, or integral ratios, as shown in Correct Mesh Alignment Examples.

Mesh Priority
In general, the meshes should be entered from finest to coarsest. FDS assumes that a mesh with
higher priority has precedence over a mesh with a lower priority if the two meshes abut or
overlap.

Mesh Boundaries
Avoid putting mesh boundaries where critical action is expected, especially fire. Sometimes
fire spread from mesh to mesh cannot be avoided, but if at all possible try to keep mesh
interfaces relatively free of complicating phenomena since the exchange of information across
mesh boundaries is not as accurate as cell to cell exchanges within one mesh.

Data Exchange
Information from other meshes is received only at the exterior boundary of a given mesh. This
means that a mesh that is completely embedded within another receives information at its
exterior boundary, but the larger mesh receives no information from the mesh embedded
within. Essentially, the larger, usually coarser, mesh is doing its own simulation of the scenario
and is not affected by the smaller, usually finer, mesh embedded within it. Details within the
fine mesh, especially related to fire growth and spread, may not be picked up by the coarse
mesh. In such cases, it is preferable to isolate the detailed fire behavior within one mesh, and
position coarser meshes at the exterior boundary of the fine mesh. Then the fine and coarse
meshes mutually exchange information.

Boundary Obstructions
If a planar obstruction is close to where two meshes abut, make sure that each mesh "sees" the
obstruction. If the obstruction is even a millimeter outside of one of the meshes, that mesh may
not account for it, in which case information is not transferred properly between meshes.

Chapter 5. Meshes 62
PyroSim - User Manual

Parallel Calculation
In a parallel calculation, it is recommended that the time steps in all meshes to be the same.
This is the default setting in PyroSim and FDS 6 and provides a tighter connection between
meshes. This option is selected by the Synchronize time step for tighter connection between
meshes checkbox on the Edit Meshes dialog.

Trial and Error


Experiment with different mesh configurations using relatively coarse mesh cells to ensure
that information is being transferred properly from mesh to mesh.
There are two issues of concern.

• Does it appear that the flow is being badly affected by the mesh boundary? If so, try to
move the mesh boundaries away from areas of activity.

• Is there too much of a jump in cell size from one mesh to another? If so, consider whether
the loss of information moving from a fine to a coarse mesh is tolerable.

Correct Mesh Alignment Examples

Figure 32. Ideal 1:1 mesh alignment. Figure 33. Acceptable 1:n alignment.

Incorrect Mesh Alignment Examples

Figure 34. Questionable value, warning. Figure 35. Not allowed in FDS 5.1+, error.

63 Chapter 5. Meshes
PyroSim - User Manual

5.5. Additional Mesh Actions


To simplify working with multiple meshes, PyroSim provides the following additional mesh
operations:

Split Mesh
Splits selected meshes at a coordinate along a single axis.

Refine Mesh
Makes selected meshes finer or coarser by a factor (e.g. refine a mesh by 4 to turn 1.0 meter
cells into 0.25 meter cells).

Merge Meshes
Combines two or more meshes into a single mesh.

Partition Meshes
Divides selected meshes in to the desired number of (2-96) partitions, with each partition
having as equal cell count as possible.

To use any of the above actions, select one or more meshes, right-click to open a popup menu,
then click the desired mesh action.

Chapter 5. Meshes 64
PyroSim - User Manual

Chapter 6. Materials
To simulate a surface made of heat-conducting solids or a fuel you must specify a material that
describes certain thermal properties and pyrolysis behavior. PyroSim offers two categories of
materials: solid materials and liquid fuels.

To create a new material, you can use the Edit Materials dialog. On the Model menu, click Edit
Materials.

6.1. Solid Materials


Examples of solid materials include brick, gypsum board, and upholstery. To create a solid
material:

1. In the Edit Materials. dialog, click New.

2. In the Material Name box, type the name of the new material

3. In the Material Type box, select Solid

4. Click OK

After following these steps, a default solid material will be created. Text entered in the
Description box will not affect the simulation, but will be preserved in the FDS input file using
the FYI field of the material. Including a description of the material is recommended.

The Thermal Properties tab provides the following options:

Density
The material’s density.

Specific Heat
The material’s specific heat. Specific heat can be specified as a function of temperature.

Conductivity
The material’s heat conductivity. Conductivity can be specified as a function of temperature.

Emissivity
The material’s emissivity. A value of 1.0 corresponds to maximum radiation.

Absorption Coefficient
This coefficient refers to the depth over which thermal radiation can be absorbed.

The Pyrolysis tab provides options to set the heat of combustion and add reactions that will be

65 Chapter 6. Materials
PyroSim - User Manual

used to govern how the material burns.

This is an advanced approach, for most fire modeling applications pyrolysis is


NOTE modeled using a Heat Release Rate (HRR) which is specified by the HRRPUA
defined on surfaces.

Each material can have a maximum of 10 reactions. To add a reaction, click the Add button. This
will open a dialog to edit the new reaction. It provides the following options:

On the Rate tab:

Reference Temperature
The temperature at which the material mass fraction decreases at its highest rate.

Heating Rate
The reaction rate at a given temperature.

Pyrolysis Range
The approximate temperature range over which the reaction occurs.

A (Pre-exponential Factor)
(parameter shown in equation)

E (Activation Energy)
(parameter shown in equation)

Mass Fraction Exponent


(parameter shown in equation)

Exponent
(parameter shown in equation)

Value
(parameter shown in equation)

On the Byproducts tab:

Heat of Reaction
Heat yield of this reaction. This must be a positive number.

Endothermic/Exothermic
Specifies if the heat yield is endothermic or exothermic.

Chapter 6. Materials 66
PyroSim - User Manual

Residue
The material that will be used to represent the residue. If there is only one material defined in
PyroSim, this option will not be available.

6.2. Liquid Fuels


Examples of liquid fuels include kerosene and ethanol.

To create a liquid fuel:

1. In the Edit Materials. dialog, click New.

2. In the Material Name box, type the name of the new material

3. In the Material Type box, select Liquid Fuel

4. Click OK

After following these steps, a default solid material will be created. Text entered in the
Description box will not affect the simulation, but will be preserved in the FDS input file using
the FYI field of the material. Including a description of the material is recommended.

The thermal properties tab for liquid fuels is identical to the thermal properties tab for solid fuels,
see Section 6.1.

The Pyrolysis tab provides the following parameters:

Heat of Vaporization
Heat yield when this liquid fuel is converted to gas. This must be a positive number.

Endothermic/Exothermic
Specifies if the heat yield is endothermic or exothermic.

Heat of Combustion
The heat released when the liquid fuel combusts.

Boiling Temperature
The temperature at which the liquid fuel changes to a gaseous fuel.

Residue
The material that will be used to represent the residue. If there is only one material defined in
PyroSim, this option will not be available.

67 Chapter 6. Materials
PyroSim - User Manual

Chapter 7. Surfaces
Surfaces are used to define the properties of solid objects and vents in your FDS model. The
surface can use previously defined materials in mixtures or layers. The default surface of all solid
objects and vents, initialized as INERT, is defined by the default surface property in the
Simulation Parameters dialog. The default temperature is fixed at the ambient temperature also
set in the Simulation Parameters dialog. In addition to defining heat conduction in a solid,
surfaces can also be used to define a burner, specify the ignition temperature for an object, give a
vent a supply velocity, and set the many other properties supported by FDS.

To create, modify, and delete surfaces, you can use the Edit Surfaces dialog. To open the Edit
Surfaces dialog, on the Model menu, click Edit Surface Properties. The dialog in Figure 36
shows the dialog being used to edit an upholstery surface.

Figure 36. The Edit Surfaces dialog

Chapter 7. Surfaces 68
PyroSim - User Manual

7.1. Reserved Surfaces


There are six fundamental or "reserved" surface types: ADIABATIC, INERT, MIRROR, OPEN, HVAC,
and PERIODIC. These surfaces cannot be changed and are present in every analysis.

ADIABATIC
There is no net heat transfer (radiative and convective) from the gas to the solid. FDS will
compute a wall temperature so that the sum of the net convective and radiative heat flux is
zero.

INERT
This surface remains fixed at the ambient temperature. Heat transfer does occur from gases to
INERT surfaces.

This is the initial default surface in PyroSim. The default surface may be
NOTE
changed in the Simulation Parameters dialog.

MIRROR
This surface is used only for vents on the exterior mesh boundary. A MIRROR is a no-flux, free-
slip boundary that reverses flow. It is intended to be applied to an entire mesh boundary to
symmetrically double the size of the domain.

Vents of this type should not be toggled (deactivated or activated) during the
NOTE
simulation.

OPEN
This surface is used only for vents on the exterior mesh boundary. OPEN denotes a passive
opening to the outside and is often used to model open doors and windows.

PERIODIC
This surface is used only for vents on the exterior mesh boundary. PERIODIC boundaries can
be used to approximate an infinitely large system with the domain as a representative unit
cell.

PERIODIC FLOW ONLY


This surface is used only for vents on the exterior mesh boundary. PERIODIC FLOW ONLY
boundaries have similar effects as PERIODIC boundaries, however the PERIODIC FLOW ONLY
only affects the velocity field - not scalar quantities.

HVAC
This surface is used only for vents that are part of an HVAC system.

69 Chapter 7. Surfaces
PyroSim - User Manual

7.2. Surface Types


PyroSim aids the user by organizing the surface options into logical types, such as a burner to
define a simple fire or a layered surface to represent a solid, heat conducting wall.

There are eight surface types in alphabetical order that you can create in PyroSim.

• Air Leak

• Basic

• Burner

• Exhaust

• General Surface

• Heater/Cooler

• Layered

• Supply

The Edit Surfaces dialog helps define a surface type with a set of tabs. Each tab provides a
collection of input fields and settings for the user to customize that surface type.

7.2.1. Air Leak


Air leak surfaces can be used to create a permeable barrier between two pressure zones, defined
by the Leak Path in the Edit Surfaces dialog. The leak area is defined by the zones selected.

Tabs: Advanced, Air Leak

7.2.2. Basic
This surface type is identical to the built-in INERT surface type. It allows you to customize the
description, color, and texture of the inert surface described in Reserved Surfaces.

Tabs: Advanced, Properties (only on this Surface Type)

7.2.3. Burner
This surface type represents a fire with a known heat release rate or mass (fuel) loss rate.

The heat release rate for a burner surface is specified per unit area. A surface
2 2
NOTE with a 500 kW/m heat release rate applied to a 2.0 m vent would result in a 1000
kW fire.

Chapter 7. Surfaces 70
PyroSim - User Manual

Tabs: Advanced, Geometry, Heat Release, Particle Injection, Thermal

7.2.4. Exhaust
Exhaust surfaces can be used to remove gas from the simulation domain. The specification of
their air movement parameters is identical to that of a supply surface, but instead of the velocity
or flux driving air into the domain, they are pulling air out. Exhaust surfaces do not have the
option to apply injection or geometry properties.

Tabs: Advanced, Air Flow, Thermal

7.2.5. General Surface


The General Surface type is a hybrid between the Burner and Supply surface types. Adding a little
more flexibility than either of them individually.

Tabs: Advanced, Air Flow, Geometry, Heat Release, Particle Injection, Species Injection, Thermal

7.2.6. Heater/Cooler
This surface type represents a radiative heat source. The options are identical to the options for a
burner without the heat release options. If the surface temperature is less than the ambient
temperature, the surface will remove heat from the surrounding gases.

Tabs: Advanced, Geometry, Particle Injection, Thermal

7.2.7. Layered
Layered surfaces are composed of one or more material definitions. Materials include solid and
liquid substances such as concrete, pine, and ethanol. For more information about materials and
how they can be specified in PyroSim, please refer to Chapter 6. This type of surface is ideal for
walls and other objects that are composed of real-world materials. This surface type can also be
used to inject extra (non-reactive) species into the simulation.

Tabs: Advanced, Geometry, Material Layers, Particle Injection, Reaction, Species Injection, Surface
Props, Thermal

7.2.8. Supply
This surface represents a vent that injects air into the simulation domain. The temperature of the
air injected by supply vents can be controlled using settings on the thermal tab. Species Injection
options are available if the Specify Mass Flux of Individual Species option in the Air Flow group
is selected and there are extra, non-reactive species present in the simulation.

71 Chapter 7. Surfaces
PyroSim - User Manual

Tabs: Advanced, Air Flow, Geometry, Particle Injection, Species Injection, Thermal

7.3. Surface Tabs


Each tab of the Edit Surfaces dialog provides a set of inputs and settings that can be used to build
a custom surface type as listed in Section 7.2. The following sections describe the parameters on
each tab and are listed in alphabetical order, not the order they might appear for a surface type.

• Advanced

• Air Flow

• Geometry

• Heat Release

• Material Layers

• Particle Injection

• Reaction

• Species Injection

• Surface Props

• Thermal

7.3.1. Advanced
Sometimes there will not be UI elements in PyroSim for an FDS input parameter that you want to
configure. The Advanced tab can be used to enter Additional Fields as Name and Value pairs
that will be placed into that specific FDS &SURF record. For more information about custom FDS
record input that is not supported by the PyroSim UI, see Section 22.2.

7.3.2. Air Flow


Specify Volume Flow
Use a constant volume flux to define air movement through the vent.

Specify Velocity
Use a constant velocity to define air movement through the vent.

Specify Total Mass Flux


Use a constant mass flux to define air movement through the vent.

Chapter 7. Surfaces 72
PyroSim - User Manual

Specify Mass Flux of Individual Species


Define air movement through the vent using a table of species and their mass fluxes. This
method requires a model that includes extra (non-reactive) species. Flux data is specified on
the Species Injection tab.

Tangential Velocity
The tangential velocity of the air flow. The first parameter is the velocity in the X or Y direction
and the second parameter is in the Y or Z direction, depending on the normal direction of the
vent. An example is shown in Figure 37.

Ramp-Up Time
At the beginning of the simulation, vents with this surface will not be blowing. This parameter
controls the time it takes to ramp the air flow up to the specified amount.

Wind Profile
The default wind profile is constant (Top Hat), to model wind conditions outdoors there are
two additional options: parabolic and atmospheric.

Parabolic
Produces wind with a parabolic profile whose maximum is the specified velocity.

Atmospheric
Produces a wind profile of the form [stem 6347831c479ff418659e138921cefe44].

Atmospheric Profile Exponent


The term [stem 2ec6e630f199f589a2402fdf3e0289d5] in the atmospheric profile
equation. This option is only available when atmospheric profile is selected.

Atmospheric Profile Origin


The term [stem d1a81d9dc6dd30e43ba27c5490a34a32] in the atmospheric profile
equation. This option is only available when atmospheric profile is selected.

73 Chapter 7. Surfaces
PyroSim - User Manual

Figure 37. Effect of normal axis on the direction of tangential velocity

7.3.3. Geometry
Geometry
Specify the type of geometry for solid particles that reference the surface. Options are Default,
Cartesian, Spherical, and Cylindrical.

Length
The length of the surface. Specified for both Cartesian and cylindrical geometries.

Width
The width of the surface.

Radius
The total radius of the rounded surface. Defined in the place of thickness.

Chapter 7. Surfaces 74
PyroSim - User Manual

Half-Thickness
For Cartesian geometry, the plate is assumed symmetric front and back, thus only the half-
thickness needs specified.

7.3.4. Heat Release


Heat Release Rate (HRRPUA)
The heat release rate per unit area of this burner.

Mass Loss Rate (MLRPUA)


The mass loss rate per unit area of this burner.

Ramp-Up Time
At the beginning of the simulation, this surface will not be burning. This field allows you to
describe how the heat release ramps up from ambient to the specified value.

Extinguishing Coefficient
This parameter governs the suppression of the fire by water.

7.3.5. Material Layers


Thickness
The thickness of this material layer.

Material Composition
Within a layer (row), you can specify multiple materials based on mass fraction. For example,
to specify a layer that is just brick, type 1.0 BRICK (assuming you have created a material called
BRICK). To specify a layer of wet brick, you could enter 0.95 BRICK; 0.05 WATER. Each material
is separated by a semi-colon.

Edit
Click to specify the materials in this layer using an alternate table UI.

7.3.6. Particle Injection


Emit Particles
Enable this option to emit particles from the surface.

Particle Type
Select a particle to emit. To create a new particle, click the Edit Particles. button.

75 Chapter 7. Surfaces
PyroSim - User Manual

Number of Particles per Cell


Controls the number of particles inserted per time step.

Insertion Interval
The frequency at which particles are inserted at the solid cells.

Mass Flux
For particles that have mass, this option provides an alternate way to control the number of
particles inserted per second.

7.3.7. Reaction
The reaction used to model a given surface can either be taken from the material specifications, or
given explicitly by the surface. Manually specifying the parameters will produce a surface similar
to a burner.

You can edit this behavior using the reaction options:

Governed by Material
This surface’s reaction will be controlled by the materials that it is constructed from.

Governed Manually
Override the default reaction behavior for this surface and specify the following parameters.

Heat Release Rate


The heat release rate per unit area of this surface.

Mass Loss Rate


The mass loss rate per unit area of this surface.

Ramp-Up Time
This field allows you to describe how the heat release ramps up from ambient to the specified
value.

Extinguishing Coefficient
This parameter governs the suppression of the fire by water. For more information, refer to
section 15.6.2 Reduction of the Burning Rate in the FDS User Guide (McGrattan et al. 2021).

Burn Immediately
Select this option to create a surface that is initially burning.

Chapter 7. Surfaces 76
PyroSim - User Manual

Ignite at
Select this option to create a surface that will begin burning at a specified temperature.

Heat of Vaporization
Heat yield when this fuel is converted to gas.

Allow obstruction to burn away


Surfaces of this type can be removed from the simulation after expending all available fuel.

7.3.8. Species Injection


You can inject extra (non-reactive) species into the simulation using the species injection options.
To use these options, you must first specify species using the Edit Species dialog.

You can edit the following species options:

Inject by Mass Fraction


Select this option to specify species injection using mass fractions.

Inject by Mass Flux


Select this option to specify species injection using mass flux.

Species
This value cannot be edited. It displays the name of one of the species selected in the Edit
Species dialog.

Mass Fraction
The mass fraction of species to inject. This option is only available if Inject by Mass Fraction is
selected.

Mass Flux
The mass flux of species to inject. This option is only available if Inject by Mass Flux is
selected.

Ramp-Up Type
This field allows you to describe the function used to ramp up the injection rate from zero to
the specified value.

Ramp Value
The time it takes to achieve the specified injection rate.

77 Chapter 7. Surfaces
PyroSim - User Manual

7.3.9. Surface Props


Enable Leakage
This option allows you to select two pressure zones for leakage across the surface.

Initial Internal Temperature


Starting temperature inside the solid. The temperature can also be varied using a ramp of
depth vs. temperature.

Backing
The backing of a surface is the boundary condition behind the surface. The default value, Air
Gap represents an air gap, Exposed will allow the surface to transfer heat into the space
behind the wall, and Insulated prevents any heat loss from the back of the material.

Gap Temperature
The temperature of air in the air gap. This option is only available when the Air Gap backing
type is selected.

Temperature Ramp
Specifies the surface temperature ramp from ambient, to the specified surface temperature.

7.3.10. Thermal
Emissivity
This parameter controls how the surface radiates heat. Using a value of 1.0 makes this surface
a black body. Lower values increase the amount of radiated heat.

Surface Temperature
The surface temperature of this burner. The default temperature is [stem
35523c0803e5e60ff0a4aa71c9da5f87] based on the 'typical' surface temperature of a burning
surface. The user should verify that this is appropriate for their scenario. A value of TMPA
represents ambient temperature.

Temperature Ramp-Up Time


This field allows you to describe how the temperature ramps up from ambient to the specified
value.

Convective Heat Flux


The heat flux per unit area at the surface.

Convective Flux Ramp-Up Time


This field alls you to specify how the convective heat flux changes over a specified period of

Chapter 7. Surfaces 78
PyroSim - User Manual

time.

Net Heat Flux


The net heat flux per unit area at the surface.

Net Flux Ramp-Up Time


This field alls you to specify how the net heat flux changes over a specified period of time.

7.4. Surface Color and Appearance


Each surface has an associated Color value that defines the color and opacity (also known as
Alpha) of the obstructions using that surface. Each referencing obstruction may optionally
override the color/opacity value in the Obstructions Dialog.

A surface may also define an optional Appearance that specifies more advanced attributes, such
as textures or lighting details to increase the realism of the model. When an Appearance is
defined for a surface, the Appearance may override both the surface’s and the object’s
color/opacity settings when the View Mode is set to Realistic or Realistic with Outlines. The
exception is when the Appearance’s Diffuse/Albedo option is set to From Object Color. See
Appearance Properties for more information.

In most CAD applications, an Appearance would be called a "Material". PyroSim


NOTE
calls it an Appearance to avoid conflicting with the naming of FDS materials.

Some default appearances are provided with PyroSim or you can import your own. The Room Fire
example demonstrates using a wood texture for a pine floor and hanging a picture on a wall. Your
textures will be automatically displayed in PyroSim.

To define an appearance with a texture and attach it to a Surface:

1. On the Model menu, click Edit Surfaces.

2. Either create or edit the surface to which you want to add a texture.

3. Click on the Appearance box.

4. Either select a pre-defined appearance or click the Import. button and select your own image
file. If using the import option, a new appearance will be created with the specified image as a
texture.

5. The image you selected will be displayed. On the right, set the Width and the Height values to
correspond to physical size of the data in the image. For example if the image is of a plank of
wood, enter the real-world dimensions of the plank.

6. Click OK to close the Appearances dialog.

79 Chapter 7. Surfaces
PyroSim - User Manual

Appearances can also be viewed by going to the Model menu and selecting Edit Appearances.
This will show the Appearances Dialog.

Because Appearances can be shared by multiple surfaces, making a change to a


NOTE shared Appearance will change the display for all objects using a surface that
references that Appearance.

Chapter 7. Surfaces 80
PyroSim - User Manual

Figure 38. Appearances dialog

Appearances can be added manually by clicking New under the appearance list. Newly created
appearances are added to the database, and can be used across instances of PyroSim.

Appearances can be deleted by clicking Remove under the appearance list. If the appearance
exists in the database, all its associated files in the database directory will also be permanently

81 Chapter 7. Surfaces
PyroSim - User Manual

removed.

The following appearance properties can be edited from this dialog:

Diffuse/Albedo
Defines the color of the object.

From Object Color


Uses the color and opacity settings from the objects using this appearance. Selecting this
option allows multiple objects to use the same appearance and have the same advanced
appearance effects but with different colors. For instance, multiple objects can have the
same bumpiness and roughness, but have different colors using one appearance.

Color
Sets the color of all objects using the appearance to a specific value.

Texture Image
Causes all objects using the appearance to display a texture image.

Opacity Value
Defines the opacity of the appearance.

Opacity Texture Image


Defines a texture which controls the opacity of the appearance.

Masking
Specifies whether to enable masking for the appearance. Masking is a feature that treats
rendered pixels as either opaque or completely transparent. This can help improve the edges
of foliage, text decals, and other opaque, decal-like appearances. When enabled, pixels with
opacity values >= 0.5 are drawn as opaque and those with opacity < .5 are not drawn. The
following masking options are available:

Automatic
Masking will be enabled automatically if the opacity texture or the alpha channel of the
diffuse texture contains both opaque and completely transparent pixels. In most cases, this
is a safe option to use.

Enabled
Masking is enabled. This may need to be set if the edges of some objects have halos around
them or appear fuzzy when using the Automatic option.

Chapter 7. Surfaces 82
PyroSim - User Manual

Disabled
Masking is disabled. This may need to be set if an appearance that should be translucent
appears opaque when using the Automatic option.

7.4.1. Advanced Appearance Properties


Additional appearance properties can be edited by pressing the Advanced Materials button. This
will show the Advanced Materials Dialog for the currently selected material.

83 Chapter 7. Surfaces
PyroSim - User Manual

Chapter 7. Surfaces 84
PyroSim - User Manual

Figure 39. Advanced Materials dialog

Most properties in this dialog can be specified as either a constant color/value or as a texture
image. For those properties that represent a single value as opposed to a color, such as the
Roughness value for PBR workflow, a dropdown next to the texture chooser can be used to pick
which color component is the source of the values. This is useful when multiple properties are
packed into a single image, but in different color components. For instance, say the PBR
parameters, metallic, roughness, and ambient occlusion, are packed into the red, green, and blue
color components of a single image. In this case, the same image can be chosen for the metallic,
roughness, and ambient occlusion textures. The dropdowns next to each texture would be set to R,
G, and B, respectively.

The following appearance properties can be edited from this dialog:

Ambient
Defines the color used to modulate ambient lighting applied to the appearance. This will only
be applied when Image Based Lighting is disabled. Selecting the From Diffuse/Albedo option
for this channel causes the Diffuse channel value to modulate ambient lighting instead.

Emissive
Defines the amount and color of light emitted by the appearance.

Normal/Bump
Whether to use normal mapping or bump mapping for the appearance.

Normal
The normal map used for the appearance.

Y-Down Normals
Whether or not to invert the y-component of the provided normals. This should be enabled
for normal maps designed for DirectX. Check any documentation that comes with the
appearance to determine if this applies.

Bump
The bump map used for the appearance.

Bump Scale
The strength of the bump map effect.

Displacement/Height
The parallax displacement or height map to use.

85 Chapter 7. Surfaces
PyroSim - User Manual

Parallax Scale
The strength of the parallax mapping effect. This unit of this scale is purely visual, but it
should be kept low to prevent rendering artifacts.

Invert Parallax
Whether or not to invert the displacement/height map. This should be enabled for height
maps.

Workflow
The appearance workflow to use. Provided options are Specular (Basic), Metallic (PBR), and
Specular (PBR). Appearances with a Specular map are designed for either the Specular (Basic)
or Specular (PBR) workflow. Specular appearances with a Roughness, Glossiness, or Ambient
Occlusion map are meant for the Specular (PBR) workflow. Appearances with a Metallic map
are designed for the Metallic (PBR) workflow.

Depending on which workflow is selected, the following additional properties are provided:

Specular
Defines the specular reflectance of the appearance. This property is only available in the
Specular (Basic) and Specular (PBR) workflows.

Metallic
Defines whether or not the appearance is metallic. This property is only available in the
Metallic (PBR) workflow.

Shininess
Defines how shiny the appearance’s surface is. This property is only available in the Specular
(Basic) workflow.

Roughness/Glossiness
Determines whether to use roughness or glossiness to define the appearance’s microsurface.
This option is only available in the Metallic (PBR) and Specular (PBR) workflows.

Roughness
Defines how rough an appearance’s microsurface is. This is the exact inverse of Glossiness.
This option is only available in the Metallic (PBR) and Specular (PBR) workflows.

Glossiness
Defines how glossy an appearance’s microsurface is. This is the exact inverse of Roughness.
This option is only available in the Metallic (PBR) and Specular (PBR) workflows.

Chapter 7. Surfaces 86
PyroSim - User Manual

Ambient Occlusion
Provides additional shading information for the appearance. Note that this property is not
related to the scene-wide Ambient Occlusion in Results. This property is only available in the
Metallic (PBR) and Specular (PBR) workflows.

Invert Ambient Occlusion


Whether to invert the values read from the ambient occlusion texture (ao_inverted = 1.0 -
ao_texture). This is useful when the ambient occlusion texture specifies the amount of
occlusion (increasing values lead to more occlusion) rather than amount of visible light
(lower values lead to more occlusion).

87 Chapter 7. Surfaces
PyroSim - User Manual

Chapter 8. Geometry (Basic Concepts)


PyroSim provides tools to help the user rapidly create and organize model geometry.

Geometry can either be created through dialogs or by using the drafting tools in the 2D or 3D
views as discussed in Chapter 9.

There are typically three types of geometry that can be created in PyroSim:

Obstructions
Solid barriers to flow

Holes
Negative regions that carve holes in obstructions

Vents
Patches that define a sub region on an obstruction’s surface that can have a different surface
than the rest of the obstruction

The user can also organize the model by creating floors and groups. In addition, the user can
assign background images to floors to aid in drafting.

8.1. Obstructions
Obstructions are the fundamental geometric representation in FDS. In FDS, obstructions are
rectangular, axis-aligned solids defined by two points. Surface properties are assigned to each face
of the obstruction. In PyroSim, obstructions can take any shape, have any number of faces, and
have different surfaces applied to each face. At the time of simulation, PyroSim will automatically
convert the obstructions to axis-aligned blocks required by FDS as discussed in Section 19.1.8.

FDS defines three types of obstructions:

Solid Obstructions
Obstructions that are at least one grid cell thick in all dimensions. FDS allows heat transfer
calculations only on these types of obstructions. In addition, only these obstructions can have
vents applied.

Thin Obstructions
Obstructions that have zero thickness in one dimension. These obstructions are mainly used to
prevent flow. In addition, only this type of obstruction may be a fan as discussed in Chapter 7.

Chapter 8. Geometry (Basic Concepts) 88


PyroSim - User Manual

Immersed Obstructions
Obstructions that do not need to be converted into blocks when written to the FDS input file.
These are only enabled if FDS GEOM is enabled. See FDS GEOM for more information.

Conversion of a slab obstruction to FDS blocks shows an example of a polygonal slab drawn in
PyroSim (Figure 40) and its conversion to blocks for use in FDS (Figure 41).

Conversion of a slab obstruction to FDS blocks

Figure 40. PyroSim slab obstruction Figure 41. Slab converted to FDS blocks

8.1.1. Creating Obstructions


To create a new obstruction, either use an obstruction drawing tool as discussed in Chapter 9 or
on the Model menu, click New Obstruction. or New Slab.

89 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

Figure 42. Obstruction dialog

8.1.2. General
This tab of the obstruction panel presents all options other than those controlling geometry and
surface information. This includes activation events (conditions that can cause the obstruction to
be added or removed from the simulation) and miscellaneous options such as color and
smoothing.

Description
A human-readable description for the object. This value will not affect the result of the
simulation.

Chapter 8. Geometry (Basic Concepts) 90


PyroSim - User Manual

Group
Controls the position of the object in PyroSim’s tree view.

Activation
Bind this object to new or existing activation control logic. Activation control logic is used to
add or remove the object based on time or measurement conditions. To learn more about
activation events, please refer to Chapter 16.

Specify Color
Override the surface color and opacity for this object. See Section 7.4 for more information.

Texture Origin
Properties for where to place the origin point of the texture image.

Relative to Object
When textures are attached to an object, they are tiled based on an origin point. By default,
this point is the origin; Relative to Object makes the anchor point the minimum point of
the object.

x,y,z
These values offset the texture origin based on the default texture origin. If the origin is
relative to the object, leave at zero to use the object’s min point.

Obstruction Properties
Group of properties for the selected obstruction(s).

Thicken
When this option is selected, this object will not be reduced to 2D faces by FDS. This is
needed for obstructions to have vents attached.

Record BNDF
When this option is selected, this object is included in boundary data output.

Permit Holes
When this option is selected, holes can modify the geometry of this object.

Allow Vents
Makes it possible for this object to be the backing object for a vent.

Removable
Makes it possible for the object to be removed from the simulation by activation events or

91 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

the BURN_AWAY surface option.

Display as Outline
Changes the appearance of this object.

Bulk Density
Use this option to override the amount of fuel provided by this object.

Write as Geom
Causes the obstruction to be written as an immersed obstruction (GEOM) record when written to
the FDS input file. If this is checked, additional options will be presented when OK is pressed.
See Section 8.1.5 for more information about the options.

This option is only available if FDS GEOM is enabled. See FDS GEOM for more
NOTE
information.

8.1.3. Geometry
This tab allows you to enter the min and max coordinates of the object. For more elaborate
geometry, such as slabs, this tab may contain a table of points and extrusion options. Extrusion is
the mechanism PyroSim uses to extend 2-dimensional objects along a vector - creating a 3-
dimensional object.

8.1.4. Surfaces
By default, all six sides of an obstruction use the default surface specified in the Simulation
Parameters dialog. The default surface for new models is initialized as INERT. The Surfaces tab
can be used to specify one surface to be used for all six sides of the object or assign surfaces on a
per-face basis. Alternately, surfaces can be "painted" using the Paint Tool as discussed in Section
9.18.

8.1.5. Converting to an Immersed Obstruction


If FDS GEOM is enabled, obstructions must be manually converted into immersed boundary
obstructions in order for them to be written as GEOM records in the FDS input file. This can be
accomplished in two ways:

• Double-click the obstruction to edit its properties, check the box next to Write as Geom, and
press OK. The object can be converted back by unchecking Write as Geom.

• Right-click the desired obstructions to convert and select Write as GEOM. The objects can be
converted back to regular obstructions by selecting Write as OBST instead.

Chapter 8. Geometry (Basic Concepts) 92


PyroSim - User Manual

In either case, if Validate GEOM obstructions is enabled in the preferences dialog (see FDS
GEOM), a dialog will appear as shown in Figure 43. This dialog can be used to specify how the
selected objects should be validated such that they can be converted to immersed obstructions.
FDS requires that an immersed obstruction consists of a closed, manifold set of faces defining a
volume. This requires that each face connect to exactly one other face on each edge and that the
object does not self-intersect. Imported CAD objects often do not meet this criteria, so PyroSim’s
validation process can help check and in many cases fix issues that arise.

Figure 43. FDS GEOM cleanup dialog

The following validation options are available in the Convert to GEOM dialog:

Conversion Mode
Controls how geometry will be checked and whether to attempt to fix the geometry. The
following modes are available:

Quick
Performs a basic test to see if the object appears manifold, but does not check for self-
intersection or attempt to clean the object. This option is the fastest and ensures the object’s
geometry will not change, but it also cannot fix errors in the object’s geometry.

Clean if non-manifold
Checks if the object appears to be manifold, and if not, performs an object cleanup. This
option will only change the object’s geometry if necessary, but it might not correct the
geometry of objects that self-intersect.

Force cleanup
Forces the object to be cleaned if possible. This option will likely change the geometry of the
object, but it will ensure the object does not self-intersect.

Geometry Clean-up
Specifies additional geometry clean-up options to help ensure an object is manifold:

93 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

Remove internal faces


Removes invalid faces that appear to be internal to the object. In certain cases, this option
may remove valid portions of the object. Uncheck if this happens.

Remove vestigial non-manifold faces


Removes faces that are not connected to others on at least one edge in an attempt to make
the object manifold.

When PyroSim cleans geometry for an immersed obstruction, it will always attempt to apply the
following set of fixes:

• Vertices that are very close within a tolerance are merged together.

• Vertices that lie on or very near another edge will split the edge.

• Edges that intersect (or nearly intersect) will be split at the intersection point.

• Edges that intersect faces will be split at the intersection point.

• Faces that intersect each other will be split along the intersection line.

If the cleanup fails to result in a valid manifold object, the geometry of the
NOTE
obstruction will not be changed.

8.2. Holes
Holes are used to carve negative spaces out of obstructions. In FDS, holes are similar to
obstructions in that they are defined as axis-aligned blocks. Like obstructions in PyroSim,
however, holes can be any shape. PyroSim automatically converts them to blocks in the FDS input
file.

PyroSim treats holes as first-class objects that can be selected, deleted, and have other operations
performed on them like obstructions as discussed in Chapter 11.

In the 3D and 2D views, holes appear as transparent objects. In addition, for display purposes
only, PyroSim carves holes out of obstructions as shown in Figure 44. For complex holes or
obstructions or large holes that span many obstructions, this process may be slow. In these cases,
hole-cutting display can be turned off by going to the View menu and deselecting Cut Holes From
Obstructions.

By default, all obstructions allow holes to be cut from them. To prevent an obstruction from
allowing holes, edit the properties of the obstruction as discussed in Section 8.1 and deselect
Permit Holes.

Chapter 8. Geometry (Basic Concepts) 94


PyroSim - User Manual

There are various rules that govern how holes are written to the FDS input file. In general, if the
PYROGEOM file is enabled, a hole has control logic, and the hole intersects obstructions, the hole
will be pre-subtracted from obstructions before the obstructions are converted into blocks, and
the holes will be excluded from the FDS file. If the above conditions do not hold, the holes are
converted to blocks similarly to obstructions and are written as HOLE records. For more
information, see Section 19.8.

Figure 44. A slab obstruction with a hole cut from it

8.2.1. Creating Holes


Holes can either be drawn as discussed in Chapter 9 or can be created by opening the Model
menu and clicking New Hole.

This will open the Hole Properties dialog as shown in Figure 45.

95 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

Figure 45. Hole Properties dialog

Like obstructions, holes can also be activated as discussed in Chapter 16. Holes can also have a
color applied.

8.2.2. Holes at Mesh Boundaries


When starting a simulation or exporting an FDS file for some models, the user may receive the
following message as shown in Figure 46: "PyroSim has detected a hole touching a mesh
boundary, which may cause cutting problems in FDS. Would you like to slightly expand these
types of holes?"

Figure 46. Expand Boundary Holes dialog

FDS currently has an issue where it will not fully cut a hole from an obstruction if both the hole
and obstruction touch a mesh boundary at the same location. Instead, FDS leaves a thin
obstruction along the mesh boundary. Figure 47 shows a model in PyroSim that can lead this
problem. In this model, both the hole and the obstruction touch the bottom of the mesh, and the

Chapter 8. Geometry (Basic Concepts) 96


PyroSim - User Manual

hole should cut all the way through the mesh. Figure 48 shows this model in FDS where the hole
has not been punched all the way through the obstruction.

PyroSim detects potential cases where this might happen and prompts the user with the Expand
Boundary Holes dialog. If the user chooses to expand the hole (the Yes option), PyroSim will
expand the hole to 1/10 of a mesh cell past the mesh boundary for every side of the hole that
touches a mesh boundary. This ensures the hole is properly cut all the way through the
obstruction as shown in Figure 49. If the user chooses not to expand these types of holes (the No
option), the hole will be written exactly as specified and may lead to the thin obstruction problem.

Cutting holes in mesh boundaries

Figure 47. Hole along a mesh


Figure 48. Improperly cut hole Figure 49. Properly cut hole
boundary
along mesh boundary in FDS along mesh boundary in FDS

8.3. Vents
Vents have general usage in FDS to describe a 2D rectangular patch on the surface of a solid
obstruction or on a mesh boundary as shown in Figure 50. A vent may have a different surface
applied to it than the rest of the obstruction to which it is attached.

97 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

Figure 50. Vents on a mesh boundary and obstruction

Taken literally, a vent can be used to model components of the ventilation system in a building,
like a diffuser or a return. In these cases, the vent coordinates form a plane on a solid surface
forming the boundary of the duct. No holes need to be created through the solid; it is assumed that
air is pushed out of or sucked into duct work within the wall.

You can also use vents as a means of applying a particular boundary condition to a rectangular
patch on a solid surface. A fire, for example, is usually created by first generating a solid
obstruction and then specifying a vent somewhere on one of the faces of the solid with the
characteristics of the thermal and combustion properties of the fuel.

There are two reserved surface types that may be applied to a vent: OPEN and MIRROR. For more
information on these types, see Chapter 7.

8.3.1. Creating Vents


Vents can either be drawn as discussed in Chapter 9 or be created by opening the Model menu
and clicking New Vent.

This will open the New Vent dialog as shown in Figure 51. Like obstructions and holes, vents can

Chapter 8. Geometry (Basic Concepts) 98


PyroSim - User Manual

also be activated, but only if the surface is not MIRROR or OPEN. With the exception of Fire
Spread, the other properties are similar to obstructions. Fire Spread can be specified on vents
using a burner surface (Chapter 7). This option simulates a radially spreading fire at the vent. A
vent can also be given radial properties. Defining a Center Point and Radius for a vent will cause
FDS to define a vent bounded by the vent’s Bounding Box and the circle generated by the point
radius combination.

Figure 51. New Vent dialog

8.4. Groups
Groups can be used to hierarchically organize the model. Groups can only be seen in the
Navigation View. The "Model" is the base group. Users can nest groups inside other groups,
allowing the user to work with thousands of objects in an organized way. When the user performs
an action on a group, that action will be propagated to all objects in the group.

99 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

8.4.1. Creating Groups


There are two ways to create a group:

• Right-click the desired parent group from the Navigation View and select New Group. from
the context menu. This will create a child group in the selected parent.

• Click the New Group. button ( ) from the main tool bar.

Both of these actions will show the Create Group dialog as shown in Figure 52. This dialog allows
the user to choose the parent group and name of the new group.

Figure 52. Create Group dialog

8.4.2. Adding Objects to Groups


There are several ways to add objects to a group:

• For existing objects, in the Navigation View, select the objects and drag them into the
desired group as shown in Dragging objects to a new group in the Navigation View..
Alternatively, right click them in any view and select Change Group.

In the Change Group dialog shown in Figure 56, select the desired group. If a new group is
desired, select New Subgroup and specify a name. If this is chosen, a new group will be created
under the specified existing group, and the selected objects will be moved to this new group. * For
newly drawn objects, in the 3D or 2D view select the desired group from the group drop-down
above the view as shown in Figure 57. All newly drawn objects will be added to this group.

Dragging objects to a new group in the Navigation View.

Chapter 8. Geometry (Basic Concepts) 100


PyroSim - User Manual

Figure 53. Select the objects to Figure 54. Drag and Drop on new Figure 55. Objects placed in new
move into group. group group

Figure 56. The Change Group dialog

Figure 57. The Group drop-down

8.5. Floors
Floors are used in PyroSim to quickly apply clipping filters to the scene to only show a portion of
the model. They are also used to initialize the properties of drawing tools so that they draw at the
proper Z location.

An example of floor clipping is shown in Floor clipping, where Figure 58 shows all floors and
Figure 59 shows a single floor.

Floor clipping

101 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

Figure 58. All floors Figure 59. Single floor

To define the floors in a model, go to the 2D or 3D View and click the Define Floor Locations
button ( ). This will display the Manage Floors dialog shown in Figure 60.

Figure 60. Manage Floors dialog

Floors are defined by the following properties:

Elevation
The Z location at which walls and other obstructions will be drawn. This is the location where
occupants would walk on that floor.

Slab Thickness
The thickness of the slab for the floor. When the active floor is changed, this value is applied to

Chapter 8. Geometry (Basic Concepts) 102


PyroSim - User Manual

the slab drawing tools but can be changed in the slab tool’s properties. This value is used such
that the top of the slab is at the elevation and the bottom is at the elevation minus slab
thickness.

Wall Height
The height of the walls for floors. When the active floor is changed, this value is applied to the
wall drawing tools but can be changed in the wall tool’s properties. Walls are drawn from the
elevation to the elevation plus wall height.

Clip Color
The color used to display clipped portions of solid geometric objects in the 3D or 2D view. This
can be seen in Figure 60.

Background Image
An image display along with the floor that can be traced over.

To add a new floor, click the Add Floor. button at the top of the Manage Floors dialog. This will
show the New Floor dialog shown in Figure 61. By default this dialog will assume the user wants
a floor above the previous floor using that floor’s slab thickness and wall height properties. In
this dialog, if the user enters a new slab thickness, the elevation will be automatically updated so
the new floor does not overlap the others unless the user enters a specific value for the elevation.
In addition, unless the user enters a specific name, a name will be automatically generated based
on the elevation.

Press OK to create the new floor.

Figure 61. New Floor dialog

Press OK again in the Manage Floors dialog to commit the changes.

By default, the model contains one floor at elevation 0.0 m with a slab thickness of .25 m and a

103 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

wall height of 2.75 m. Using these values leaves a distance of 3.0 m from one floor elevation to
another.

Once the floors have been defined, the user can filter the display to show either a single floor or
all floors as shown in Figure 7. For most views, the Z clipping range for a particular floor is from
the floor elevation minus slab thickness to floor elevation plus wall height. The Z clipping
range works differently for the top camera of the 2D view, however. In this view, the clipping is
from the elevation of the floor BELOW to the elevation plus wall height of the current floor. This
allows the geometry on the floor below to be snapped to in drawing geometry for the current
floor. For this to be useful, however, the user may want to use wireframe rendering.

8.5.1. Adding a Floor to Fit Objects


Quickly define floors by selecting some geometry, right-click the selection, and choose the Add
Floor to Fit Objects item in the context menu. This will automatically add a floor in the Manage
Floors dialog with values based upon the selected geometry.

See Figure 61 for an illustration of the information below.

• The slab thickness (A) will always be set to 0.0 m.

• The elevation value (B) is determined by the minimum z-value of the selected piece of
geometry.

• The wall height (C) value is determined by the maximun z-value of the selected piece of
geometry.

• If you have a slab that should be part of this floor but is not, adjust the slab thickness value
according to the slab’s dimensions.

8.5.2. Adding a Background Image to a Floor


Each floor can have an associated background image. To add a background image to a floor, go to
the 2D or 3D View, select a specific floor, then click the Configure Background Image button ( ).
Alternately click the Define Floor Locations button, ( ), and then in the Background Image
column, select the Edit button. This will display the Configure Background Image dialog shown
in Figure 62.

You will be guided through the following steps:

1. Choose a background image file. Valid image formats are bmp, dxf, gif, jpg, png, tga, and tif.

2. Specify the Anchor Point for the image by clicking on the image. The Anchor Point is a point
on the image at which the coordinates are specified in the model coordinate system. The
model coordinates of the anchor point are not required to be at the origin.

Chapter 8. Geometry (Basic Concepts) 104


PyroSim - User Manual

3. Set the model scale. Select the Choose Point A button, then select the first point that will be
used to define a length. Select the Choose Point B button and select the second point to define
a length. Input the Distance between points A and B.

4. Use the sliding scale to change the image transparency.

5. If the image needs to be rotated, check the box next to Dist. A to B and enter an angle. This
specifies the angle between the positive X axis and the vector from reference point A to B. For
instance, if A→B should be aligned with the X axis, enter 0 for the angle or if A→B should be
aligned with the positive Y axis, enter 90.

6. Click OK to close the Configure Background Image dialog.

Figure 62. Display of background image

Now, in the 3D or 2D views, when the user displays a specific floor, the background image for that
floor will be displayed. To turn off the background images, go to the 2D or 3D View, and click the
Show Background Images button ( ) next to the floors drop-down.

105 Chapter 8. Geometry (Basic Concepts)


PyroSim - User Manual

Chapter 9. Drawing in PyroSim


While not a full-fledged drafting application, PyroSim does provide useful drawing features,
including the following:

• Snapping to grids, objects, and polar and orthographic constraints

• Precise keyboard entry

• 3D and 2D drawing, each having strengths over the other

• Mesh, Obstruction, Hole and Vent drawing tools

• Editing tools

• Transforming tools

• Surface painting tools for obstructions and vents

9.1. Drawing/Editing Tool Overview


PyroSim provides several drawing and editing tools. These tools are located on the drawing
toolbar at the left side of the 3D and 2D Views as shown in Figure 63.

Figure 63. Drawing/Editing toolbar

Some of these tools allow a user to create and edit objects such as slabs and walls that are not
constrained to the FDS mesh. In these cases, PyroSim will automatically convert the shapes to

Chapter 9. Drawing in PyroSim 106


PyroSim - User Manual

mesh-based blocks when the FDS input file is created. These blocks can be previewed by clicking
the Preview FDS Blocks button ( ) on the filter toolbar above the 3D or 2D View. For
information on block conversion, see Section 19.1.8.

9.1.1. Selecting a Tool


To begin drawing or editing with a tool, the user can single-click the tool from the tool bar. Once
the tool has finished drawing/editing its object, the last-used navigation tool is automatically
selected.

If the user would like to create several objects with the same tool in succession, the desired tool
can be pinned by clicking the tool’s button twice.

The button will show a green dot when pinned ( ).

Every time the same tool button is clicked, the pinned state of that tool will be toggled, so clicking
the button again after pinning will disable pinning ( ).

At any time, the current drawing/editing tool can be cancelled by pressing ESC on the keyboard.
This will also cancel pinning and will revert back to the last-used navigation tool.

9.1.2. Tool Modes


Most drawing/editing tools require at least two points to be specified to complete its action, such
as drawing the points for a wall or defining the extents of a box.

These tools can operate in two modes:

Multi-click mode
This mode allows the user to specify each desired point by single-clicking the left mouse button
for each point. This mode also facilitates precise keyboard entry.

Click-drag mode
This mode only allows the user to specify two points. When the left mouse button is pressed,
the first point is committed. Then the mouse is dragged to the next location while still holding
the left mouse button. The button is then released to specify the second point.

9.1.3. Tool Properties


Each tool has a set of properties that can be modified by clicking the Tool Properties ( ) button
located at the bottom of the toolbar after selecting the desired tool. Options such as elevation,
height, surface, and color can all be edited in the Tool Properties dialog.

107 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

9.1.4. Quick Actions


In addition to the tool properties, each tool also has additional quick actions. To show these
actions, start the desired tool and then right-click in the 2D or 3D View. This opens a context menu
with the quick actions. Figure 64 shows an example of the quick action menu for the wall tool.

Figure 64. The quick action menu for the wall tool

This menu allows the user to perform actions specific to the tool, such as closing a polygon,
picking a surface, setting wall alignment, accessing the tool properties, etc.

9.2. Snapping
Snapping is one way to precisely draw and edit objects. It is the process of finding some element
in the scene, such as a vertex or edge close to the cursor, and snapping the cursor to that element
like a magnet.

In PyroSim, snapping can be performed against the solution meshes, objects in the model, and
orthographic constraints. The 2D View additionally provides a sketch grid and polar (angle)
constraints. If a snap point is found, an indicator dot shown in Figure 65 will appear at the snap
point.

Figure 65. Snap point indicator dot

By default, snapping is enabled. It can be disabled by holding ALT on the keyboard while using a
drawing/editing tool.

9.2.1. Solution Mesh Snapping


If there are any solution meshes in the model (see Chapter 5), PyroSim can snap to them during
drawing and editing. For each mesh that is visible, PyroSim can snap to its boundary edges,

Chapter 9. Drawing in PyroSim 108


PyroSim - User Manual

boundary faces, grid lines, and the intersections of the grid lines, depending on which mesh
display filters are active as discussed in Section 2.3.6.

9.2.2. Sketch Grid Snapping (2D View Only)


PyroSim also provides a user-defined drawing grid, or sketch grid, in the 2D View as shown in
Figure 66.

Figure 66. Sketch grid

When a new model is created, the sketch grid is visible and can be snapped to in the 2D view. The
default spacing for the divisions is 1 m, but can be changed by going to the View menu and
clicking Set Sketch Grid Spacing.

Once the user has created a solution mesh, PyroSim will automatically switch to solution mesh
snapping and disable sketch grid snapping. In the 2D View, PyroSim will only snap to the sketch
grid or visible solution meshes. To switch which snapping is being used, on the View menu choose
Snap to Sketch Grid or Snap to Model Grids. To disable grid snapping altogether, on the View
menu choose Disable Grid Snapping.

109 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

In FDS, the spatial resolution of the solution is defined by the solution mesh, not
the Sketch Grid. Using the solution mesh for 2D View drawing ensures that the
model geometry matches the FDS solution geometry. Some users create all model
NOTE
objects using mesh dimensions. While this leads to a "blocky" appearance, it does
represent the true solution geometry and ensures there will be no unexpected
gaps in the model.

9.2.3. Object Snapping


All objects displayed in the model can be snapped to when using the drawing/editing tools. There
are three basic categories of geometry that can be snapped to on objects: faces, edges, and
vertices. Objects can have any combination of types. If there are multiple types close to the
cursor, PyroSim will give vertices precedence over edges and edges precedence over faces.

9.2.4. Constraint Snapping


Constraints are dynamic snapping lines that are only visible when the cursor is near them. They
appear as infinite dotted lines as shown in Figure 67.

PyroSim contains two types of constraints:

Orthographic
These constraints allow the user to snap to a line parallel to the X, Y, or Z axis from the last
relevant point. For instance, when drawing a polygonal slab, after each point specified, there
will be three orthographic constraints extending from the last drawn point to aid in drawing
the next point.

Polar (2D View Only )


These constraints are similar to orthographic constraints, but they are found at 15 degree
increments from the current view’s local X axis.

Chapter 9. Drawing in PyroSim 110


PyroSim - User Manual

Figure 67. Polar constraint at an angle of 45 degrees

9.2.5. Constraint Locking


If a constraint is currently being snapped to, that constraint can be locked by holding SHIFT on
the keyboard. While holding SHIFT, a second dotted line will extend from the cursor to the locked
constraint (the first dotted line). This is useful for lining up objects along a constraint with other
objects.

For instance, in Figure 68, a box already exists in the model. A second slab is being drawn such
that the third point of the slab lines up with the right side of the first box. This was done as
follows:

1. After the second point for the slab was clicked, the cursor was moved until the X-axis
constraint became visible.

2. SHIFT was pressed and held on the keyboard to lock the constraint.

3. The cursor was moved to a point on the right edge of the box while still holding SHIFT.

111 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

The distance displayed in the figure is the distance from the second point to the
NOTE third point on the locked constraint and NOT from the second point to the cursor
location.

Figure 68. Locked constraint

9.2.6. Asynchronous Snapping


Snapping may be a slow operation in complex models. In these cases, asynchronous snapping is
used to keep the cursor and application responsive while the snapping operation takes place in
the background. During asynchronous snapping, a wait cursor will appear at the cursor
crosshairs while the snapping completes. While this takes place, either keep the cursor still to
allow the current snapping operation to complete, or move the cursor to abort the operation and
snap to a different location. Asynchronous snapping can be disabled by unchecking
File→Preferences→Enable asynchronous snapping. Note that if it is disabled, the cursor may
briefly hang and the application will become unresponsive while these long snapping calculations
take place.

Chapter 9. Drawing in PyroSim 112


PyroSim - User Manual

9.3. Precise Keyboard Entry


While using a drawing/editing tool, a popup window may appear next to the cursor, such as in
Figure 69. This window shows the value used to determine the next point or value for the current
tool. In this figure the value is the Distance from the previous point along the vector from the
previous point to the current cursor location. For other tools, this value may be angle or relative
offset, etc.

The value is editable if the status bar at the bottom of the 3D or 2D View indicates it is. For
instance, in the figure, the status bar says "<Type to enter Distance or press TAB for alternatives>".
If the user starts typing, the popup window will be replaced with an editing window as shown in
Figure 70. If the user presses ENTER, the typed value will be committed. If the user presses ESC
instead, the keyboard entry will be cancelled.

Pressing TAB cycles through alternate input methods to determine the next value. For instance,
pressing TAB with the wall tool allows the user to enter a relative offset from the last point
instead of a distance. Pressing TAB a second time allows the user to enter an absolute position for
the next point, and pressing TAB a third time will cycle back to the distance input.

113 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 69. Tool editor window

Chapter 9. Drawing in PyroSim 114


PyroSim - User Manual

Figure 70. Precise keyboard entry

Precise keyboard entry may be easiest for some users when using the multi-click mode of
drawing rather than using the click-drag mode. Using multi-click allows both hands to be used to
type as opposed to click-drag, which requires one hand to remain on the mouse.

9.4. 2D versus 3D Drawing


There are some key differences between drawing in the 2D and 3D Views. The 2D View is useful
when drawing should be restricted to one pre-defined plane. It is also useful for lining up objects
along the X, Y, or Z axes. The 3D View is useful when an object such as a vent or solid-phase device
needs to be snapped to the face of an obstruction or vent or if the user would like to build objects
by stacking them on top of one another.

9.4.1. 2D View Drawing


When drawing in the 2D View, the drawing will always take place in the drawing plane specified
in the tool properties, and snapping is only performed in the local X and Y dimensions. The local Z

115 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

value will remain true to the drawing plane. In addition, if a tool has some sort of height or depth
property, the tool will also remain true to that value. Slabs in different planes aligned in the 2D
View shows two slabs that have been drawn in the top view (Figure 71), one at Z = 0 m and the
other at Z = 1.5 m. While snapping was used to partially align the objects, they both remain in the
Z planes specified in their tool properties shown in the rotated view (Figure 72).

Slabs in different planes aligned in the 2D View

Figure 71. Top view Figure 72. Rotated view

9.4.2. 3D View Drawing


The 3D View uses snapping in all three dimensions, causing tool properties to be interpreted more
loosely. The drawing plane and depth properties for a drawn object are context-sensitive in the 3D
View. When using tools such as the slab tool, the first clicked point determines the drawing plane.
If, on this first click, another object is snapped to, the drawing plane is set at the Z location of that
snap point. The tool properties’ drawing plane is only used if nothing is snapped to on the first
click.

This 3D snapping feature of the 3D View is useful for drawing vents on obstructions and attaching
solid-phase devices to obstructions as shown in Figure 73.

Chapter 9. Drawing in PyroSim 116


PyroSim - User Manual

Figure 73. Vent and devices attached to a wall

The 3D snapping feature is also useful for stacking objects, as shown in Figure 74. In this figure,
the drawing plane was never changed. All the objects were stacked on top of each other using
snapping.

117 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 74. Objects stacked in the 3D View

9.4.3. Holes in the 3D View


While stacking can be useful for obstructions, a user must be more careful when drawing holes in
the 3D View. For instance, with the slab hole tool and block hole tool, the user will need to
change the extrusion direction to properly direct the hole into the obstruction.

For instance, if the user draws a slab obstruction in the 3D View and then draws a slab hole while
snapping to the obstruction, the hole will be stacked on top of the obstruction without cutting a
hole as shown in Figure 75.

To draw this properly, the user would need to change the extrusion direction when drawing the
hole by pressing CTRL on the keyboard or changing it through the tool’s right-click menu. This
will result in a proper hole as shown in Figure 76.

This is not a problem in the 2D View since it always uses the drawing plane set in the tool
properties instead of stacking the objects.

Improper vs proper hole drawing in the 3D view

Chapter 9. Drawing in PyroSim 118


PyroSim - User Manual

Figure 76. Properly drawn hole


Figure 75. Improperly drawn hole

9.4.4. Projected Drawing in the 3D View


Once the drawing plane for a tool has been established by the first click, the tool can still
determine the next points by snapping to objects in another plane. In this case, the snapped points
will be projected to the drawing plane for the current tool. A dotted line will show how the
snapped point was projected to the plane. For instance, Figure 77 shows a new slab being drawn
in the Z = 1.5 plane. A slab below the new slab is being snapped to determine the new slab’s
points.

119 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 77. Snapping to another plane in the 3D View

9.5. Obstruction Drawing Tools


There are four tools that can draw obstructions, for more information on obstructions, see Section
8.1.

Slab Obstruction Tool: Used to draw the slab for a floor.

Wall Obstruction Tool: Used to draw a wall.

Block Obstruction Tool: Used to fill grid cells with obstructions.

Room Tool: Used to draw a rectangular room

For all the obstruction tools, the tool properties dialog ( ) will appear similar to that in Figure 78.
The only section of the dialog that will change between these tools is the geometry, such as Z
Location and Thickness. All other properties, including name, surface, color, and obstruction
flags appear in all obstruction dialogs. These parameters control the properties that will be
applied to the next drawn obstruction.

Chapter 9. Drawing in PyroSim 120


PyroSim - User Manual

Figure 78. Tool properties dialog for obstructions

The surface and color of the next obstruction can also be set via the right-click menu for the tool.

9.5.1. Slab Obstruction Tool


A slab is an extruded polygonal object as shown in Figure 79 that can be used to draw the slab for
a floor in a building.

121 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 79. A polygonal slab obstruction

The slab obstruction tool adds two additional properties to the tool dialog for obstructions:

[X,Y, or Z] Location
The drawing plane for the slab. When the active floor is changed, this is set to the floor’s
elevation minus the floor’s slab thickness.

Thickness
The thickness of the slab. When the active floor is changed, this is set to the floor’s slab
thickness. If this value is positive, the slab is extruded toward the camera. If it is negative the
slab is extruded away from the camera. The extrusion direction can be toggled by pressing
CTRL on the keyboard or from the tool’s right-click menu.

To draw the polygon vertices of the slab obstruction, perform the following:

1. Select the Slab Obstruction Tool ( ) from the drawing toolbar.

2. Define the slab points using one of the two tool modes:

◦ Use Click-drag mode to draw an axis-aligned box between two points.

Chapter 9. Drawing in PyroSim 122


PyroSim - User Manual

◦ Use Multi-click mode to click several points defining the polygonal boundary for the slab.

The slab will automatically close if the first point is clicked again or if the user
NOTE
selects Close from the right-click menu.

9.5.2. Wall Obstruction Tool


The wall obstruction tool ( ) can be used to draw multi-segmented walls as shown in Figure 80.
In this figure, there is only one wall. The user specifies a path along the floor from which the wall
is extruded up. The wall can be aligned to the left, right, or center of the drawn path.

Figure 80. A wall obstruction

The wall obstruction tool adds three properties to the tool properties dialog:

Z Location
The drawing plane for the bottom of the wall. When the active floor is changed, this is set to
the floor’s elevation property.

123 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Height
The height of the wall as a positive number. When the active floor is changed, this is set to the
floor’s wall height property.

Wall Thickness
The thickness of the wall.

The alignment of the wall can be controlled through the right-click menu for the tool or can be
cycled by pressing the CTRL key on the keyboard. The alignment options are Left (Figure 81),
Center (Figure 82) and Right (Figure 83) as shown in Wall alignment options.

Wall alignment options

Figure 81. Left-aligned Figure 82. Center-aligned Figure 83. Right-aligned

To draw a wall, perform the following steps:

1. Select the Wall Obstruction Tool ( ) from the drawing toolbar.

2. Define the wall points using one of the two tool modes:

◦ Use Click-drag mode to draw a single wall segment.

◦ Use Multi-click mode to click several points, with wall segments between each pair of
points.

If the first clicked point is clicked again after drawing at least two segments or Close is chosen
from the right-click menu, the tool will draw one last segment from the last clicked point to the
first point and finish. Alternately, the wall can be ended at the last clicked point by choosing
Finish from the right-click menu.

9.5.3. Block Obstruction Tool


The Block Obstruction Tool ( ) can be used to quickly fill grid cells with blocks as shown in
Figure 84 or place a block with a single click.

Chapter 9. Drawing in PyroSim 124


PyroSim - User Manual

Figure 84. Blocks drawn with the block obstruction tool

This tool adds the following properties to the tool properties dialog:

[X,Y, or Z] Location
The drawing plane. When the active floor is changed, this is set to the floor’s elevation.

Height
The distance the block is extruded toward or away from the camera. When the active floor is
changed, this is set to the floor’s wall height property.

Size
The size of the block when there is no snap grid under the cursor.

In addition, the extrusion direction for the block can be toggled by pressing CTRL on the keyboard
or through the right-click menu for the tool.

To create blocks using this tool, perform the following:

1. Select the Block Obstruction Tool ( ) from the drawing toolbar.

125 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

2. If a solution mesh or sketch grid is visible, either click the desired cell to fill or click-drag the
mouse across the grid to "paint" blocks. The depth of the cells will not necessarily be the depth
of a cell in the filled mesh, however. The depth is strictly controlled by the height property for
the tool.

9.5.4. Room Tool


The Room Tool ( ) can be used to draw a rectangular room using one closed wall as shown in
Figure 85.

Figure 85. A room drawn with the room tool

The room tool contains the same properties as the wall obstruction tool.

To draw a room with the room tool perform the following:

1. Select the Room Tool ( ) from the drawing toolbar.

2. Use Click-drag mode or Multi-click mode to draw two points defining the extents of the
room.

Chapter 9. Drawing in PyroSim 126


PyroSim - User Manual

9.6. Hole Drawing Tools


There are three tools that can draw holes, for more information on holes, see Section 8.2.

Slab Hole Tool: Used to draw a hole in a floor slab. Wall Hole Tool: Used to draw an
opening in a wall, such as for a doorway or window. Block Hole Tool: Used to fill grid cells
with holes.

All these tools work the same as their obstruction counterparts, but they do not have the
properties specific to obstructions, such as the surface or obstruction flags.

9.7. Vent Tool


There is only one tool for drawing vents (for more information on vents, see Section 8.3). PyroSim
only allows vents in an X, Y, or Z plane. Vents cannot currently be drawn off-axis like walls can.

Vents also must be attached to solid obstructions (at least one grid cell thick). This is easily
accomplished by drawing the vent in the 3D View (see Section 9.4).

To draw a vent, perform the following:

1. Select the Vent Tool ( ) from the drawing toolbar.

2. Use Click-drag Mode or Multi-click Mode to specify two points that define the extents of the
vent.

◦ When this is performed in the 2D View, the vent will be drawn in the plane specified in
the tool properties and is view-dependent (in the top view, the vent will be drawn in the
XY plane, in the front view, the vent will be drawn in the XZ plane, etc.).

◦ If the vent is drawn in the 3D View, the vent will be drawn in the plane containing the two
specified points. If the two points are not in an axis-aligned plane, an axis-aligned plane
will be chosen containing the first point while maximizing the area of the vent.

9.8. Solution Mesh Tool


Solution meshes can also be drawn in PyroSim with the Solution Mesh Tool ( ) as shown in
Figure 86.

127 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 86. A solution mesh drawn with the mesh tool

The solution mesh tool has the following tool properties:

[X,Y, or Z] Location
The drawing plane containing the bottom of the mesh. When the active floor is changed, this is
set to the floor’s elevation minus the floor’s slab thickness.

Height
The depth of the mesh in the current view. When the active floor is changed, this is set to the
floor’s wall height plus the floor’s slab thickness.

Cells
Define how cells are generated as the mesh is being drawn. This can be one of two values:
fixed size, or fixed count:

Fixed Size
Each cell will have a fixed size. While drawing the mesh, the mesh boundary will snap to

Chapter 9. Drawing in PyroSim 128


PyroSim - User Manual

integer multiples of the cell size. Two types of drawn meshes (A) shows a mesh drawn with
fixed cell sizes of .25 x .25 x .25 m. As can be seen, the grid has been snapped away from the
cursor the nearest multiple of .25 m.

Fixed Count
Each dimension of the drawn mesh will be evenly divided to have the specified number of
cells. Two types of drawn meshes (B) shows a mesh drawn with fixed counts of 10 x 10 x 10.
As can be seen, the cells are stretched to match the drawn mesh boundary.

Two types of drawn meshes

Figure 87. Fixed cell size Figure 88. Fixed cell count

To draw a solution mesh, perform the following:

1. Select the Solution Mesh Tool ( ).

2. Use the Click-drag Mode or Multi-click Mode to draw two points defining the extents of the
mesh.

9.9. Mesh Splitter Tool


Solution meshes can be easily split into two or more sub-meshes by using the Mesh Splitter Tool
( ).

To split one or more meshes, perform the following:

1. Select the desired meshes to split either in the navigation view or by holding g on the
keyboard while selecting a grid in the 2D or 3D view.

2. Select the Mesh Splitter Tool ( .

3. Move the cursor over one of the meshes. A preview slice will show where the meshes will be

129 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

split as shown in Figure 89. By default the tool will choose the split axis based on the nearest
boundary edge of a selected mesh. The split axis can be explicitly set through the right-click
menu, in the tool properties dialog, by click-dragging the left mouse button, or by pressing
CTRL on the keyboard to cycle through the options.

4. Once the desired split location can be seen, left-click the mouse to set the location.

5. Repeat steps 3) and 4) to set more split locations. The meshes can be split along any number of
axes in a single operation.

6. To perform the split, right-click in the 2D or 3D view and select Finish.

7. PyroSim will create a new mesh group for each selected mesh and place the resulting meshes
in the appropriate groups.

Figure 89. Meshes being split by the mesh splitter tool

9.10. Device Tool


PyroSim allows point devices to be drawn with the Device Tool ( ), for more information on
devices, Chapter 15.

Chapter 9. Drawing in PyroSim 130


PyroSim - User Manual

The device tool has the following properties:

[X,Y, or Z] Location
The drawing plane on which to place the device. When the active floor is changed, this is set to
the floor’s elevation plus the floor’s wall height * 0.5.

Device Type
The type of point device to draw. This can include sprinklers, smoke detectors, gas-phase
devices, solid-phase devices, etc. Changing the device type also changes the other properties
editable in the properties dialog.

To draw a device, perform the following:

1. Select the Device Tool ( ).

2. Click on the desired location.

When drawing a device in the 3D View, the device’s location will snap differently
NOTE depending on whether the device is a solid-phase device, such as one that
measures wall temperature, or a gas-phase device, such as a smoke detector.

If it is a solid-phase device, the device’s location will snap directly to the point under the cursor if
one is found. This makes it trivial to attach a solid-phase device to an obstruction. If the device is a
gas-phase device, however, the device’s location will be projected to the plane as set in the device
tool properties as shown in Figure 90. This makes it easy to draw devices at a specific height
above the floor. This behavior can be overridden for either type of device by selecting Lock Z to
[V] (where V is the drawing plane) or Lock Z to Snap Location in the tool’s right-click menu.
Lock Z to [V] is the automatic behavior for gas-phase devices and Lock Z to Snap Location is the
automatic behavior for solid-phase devices.

131 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 90. A gas-phase device being drawn in the 3D View

9.11. Planar Slice Tool


Planar slices, as discussed in Section 18.2 can be drawn with the planar slice tool ( ).

To do so, perform the following:

1. Select the Planar Slice Tool ( ).

2. In the tool properties dialog, select the desired quantity to record on the slice, the desired
plane on which to draw the slice, and whether to include flow vectors.

3. Move the cursor to the desired slice location. A preview slice will be displayed as shown in
Figure 91.

NOTE A planar slice can only be seen if the slice intersects a solution mesh.

The slice plane can be changed through the right-click menu, by click-dragging the left mouse
button, or by pressing CTRL on the keyboard to cycle through the options.

Chapter 9. Drawing in PyroSim 132


PyroSim - User Manual

4. Left-click the mouse to create the slice.

Figure 91. Drawing a slice with the planar slice tool

9.12. HVAC Node Tool


HVAC nodes as discussed in Section 17.2, can be drawn with the HVAC Node Tool ( ).

To do so, perform the following:

1. Select the HVAC Node Tool ( ).

2. In the tool properties dialog, select the desired height of the node.

3. Move the cursor to the desired slice location.

4. Left-click the mouse to create the node.

133 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 92. Using the HVAC Node drawing tool

9.13. HVAC Duct Tool


PyroSim allows HVAC ducts to be drawn with the HVAC Duct Tool ( ).

To do so, perform the following:

1. Select the HVAC Duct Tool ( ).

2. Click to select the first HVAC Node. It is best to select the nodes in the direction air will flow
through them.

3. After selecting the first node, a green line will appear from the node to the cursor,
representing the duct. Complete the duct by selecting the second node.

Chapter 9. Drawing in PyroSim 134


PyroSim - User Manual

Figure 93. Drawing an HVAC Duct

9.14. Other Box Drawing Tools


PyroSim can also be used to draw:

Init Regions (Section 19.1.4) with the Init Region Tool.

Particle Clouds (Section 14.6) with the Particle Cloud Tool.

3D Slices (Section 18.3) with the 3D Slices tool.

These tools draw axis-aligned boxes like the Solution Mesh Tool, so they behave similarly. They
all have the following drawing properties:

[X,Y, or Z] Location
The drawing plane for the tool. When the active floor is changed, this is set to the floor’s
elevation.

Height
The depth of the drawn box in the current view. When the active floor is changed, this is set to

135 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

the floor’s wall height.

To draw one of these objects, perform the following:

1. Select the appropriate tool.

2. Use Click-drag Mode or Multi-click Mode to draw two points defining the extents of the
object’s box.

9.15. Other Point Drawing Tools


Single Particles (Chapter 14) with the Particles at a Point Tool.

Pressure Zones with the with the Zone Tool.

These tools draw points like the Device Tool, so the they behave similarly. They all have the
following drawing property:

[X,Y, or Z] Location
The drawing plane for the tool. When the active floor is changed, this is set to the floor’s
elevation.

To draw one of these objects, perform the following:

1. Select the appropriate tool.

2. Click on the desired location.

9.16. Editing Objects


Nearly all geometric objects can also be graphically edited in the 3D or 2D View with the
Select/Manipulate Tool ( ).

Editing is performed through an object’s editing handles. Handles appear on an object either as a
blue dot as shown in Figure 94 or a face with a different color. The dots indicate a point that can
be moved in either two or three dimensions. A discolored face indicates that a face can be moved
or extruded along a line.

Imported objects may be very complex with thousands or even millions of


potential handles. By default, PyroSim limits the number of displayed handles to
improve application responsiveness. The maximum value can be changed under
NOTE
File→Preferences→Maximum manipulation handles. Lower values will
increase responsiveness but may limit the extent to which the object can be
manipulated. Enter max to disable the limit.

Chapter 9. Drawing in PyroSim 136


PyroSim - User Manual

Figure 94. Editing handles on an object

To graphically edit an object, perform the following:

1. Select the Select/Manipulate Tool ( ) from the navigation toolbar.

2. Select one object to edit If the object can be graphically edited, blue editing handles will
appear.

Only one object can be edited at a time. Editing handles will only appear if exactly
NOTE
one object is selected.

3. Hover the cursor over the desired handle. If the handle is a dot, it will turn yellow. If the
handle is a face, the entire face will turn yellow as shown in Figure 95.

4. Move the handle using Click-drag Mode or Multi-click Mode to specify two points defining
the movement vector.

137 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 95. A highlighted face handle

9.17. Transforming Objects


PyroSim provides a variety of tools to transform geometry objects. With the transform tools, users
can move, rotate, and mirror objects.

9.17.1. Copy Mode


Each tool has an alternate mode to copy the source objects with the transform. To toggle copy
mode on/off, press the CTRL key on the keyboard. Alternately, choose Copy Mode or Move Mode
from the tool’s right-click menu. When using copy mode, the selected objects are copied and the
copies are transformed.

9.17.2. Move Tool


This tool allows the user to move selected objects to a new location as shown in Figure 96, or to
create and move a copy of the selected objects.

To use this tool, perform the following:

Chapter 9. Drawing in PyroSim 138


PyroSim - User Manual

1. Select the desired objects to move from any of the views.

2. Select the Move Tool ( ) from the drawing toolbar.

3. Use Click-drag Mode or Multi-click Mode to draw two points defining the movement vector.

NOTE Use the CTRL key to toggle between move mode and copy mode.

Figure 96. Moving an object using the Move Tool

9.17.3. Rotate Tool


This tool allows the user to rotate selected objects as shown in Rotating an object with the Rotate
Tool, or to create and rotate a copy of the selected objects.

Some objects, such as a solution mesh can only be rotated by 90 degree


NOTE
increments.

To use this tool, perform the following:

1. Select the desired objects to rotate from any of the views.

139 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

2. Select the Rotate Tool ( ) from the drawing toolbar.

3. Single-click to specify the rotation center (Figure 97).

4. Single-click another point to define a reference vector from the first point to the second point
(Figure 98). This reference vector is what the angle is based from.

5. Single-click a third point to define the angle vector from the first point to the third point
(Figure 99).

The selected objects will be rotated by the angle between the reference and angle vectors.

The rotate tool can only be performed with Multi-click Mode since it requires
NOTE
three reference points.

The following defines the axis about which objects are rotated for each view:

• 3D View: Z axis

• Top View: Z axis

• Front View: -Y axis

• Side View: -X axis

Rotating an object with the Rotate Tool

Figure 97. Click rotation center Figure 98. Define reference Figure 99. Define angle vector
vector

9.17.4. Mirror Tool


The mirror tool allows selected objects to be mirrored across a plane as shown in Mirroring an
object using the Mirror Tool, or to create a mirrored copy of the selected objects.

To use the mirror tool, perform the following:

1. Select the desired objects to mirror from any view.

Chapter 9. Drawing in PyroSim 140


PyroSim - User Manual

2. Select the Mirror Tool ( ) from the drawing toolbar.

3. Use Click-drag Mode or Multi-click Mode to define two points that create a plane about
which the selected objects are mirrored (Figure 101).

Mirroring an object using the Mirror Tool

Figure 100. Define first point Figure 101. Define second point and mirror line

Some objects, such as solution meshes, can only be mirrored about an X, Y, or Z


NOTE
plane.

9.18. Painting Obstructions and Vents


PyroSim provides tools to paint obstructions and vents with a surface and/or color. A user can also
use a picking tool to pick the surface and/or color used to draw new obstructions or vents or to
perform painting.

9.18.1. Paint Tool


A user can use the Paint Tool ( ) to paint the faces of obstructions and vents a specific surface
and/or color.

The Paint Tool has the following tool properties:

Apply Surface
Specifies whether to paint faces with surfaces and which surface to use.

Apply Color
Specifies whether to paint faces with a specific color and which color to use.

141 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

These painting options can also be cycled by pressing CTRL on the keyboard or through the tool’s
right-click menu. The right-click menu also allows quick selection of a surface in the model or
recently-used color.

To paint faces with the paint tool, perform the following:

1. Select the Paint Tool ( ) from the drawing toolbar.

2. Hover the cursor over the desired face to paint. If the face can be painted with the current
surface/color, the face with highlight yellow as shown in Figure 102.

3. Either single-click the face to paint only that face, or click-drag the left mouse button to paint
all faces the cursor moves over. Hold SHIFT on the keyboard while painting to paint all the
faces of the object rather than just one face.

A popup window will show which surface/color is currently being painted, but
NOTE
unlike other popup windows, this one is NOT editable.

Figure 102. An obstruction face highlighted by the paint tool

Chapter 9. Drawing in PyroSim 142


PyroSim - User Manual

9.18.2. Pick Tool


The Pick Tool ( ) can be used to pick the next color/surface to use when drawing or painting
obstructions and vents.

The Pick Tool has the following tool properties:

Pick Surface
Whether to pick the surface under the cursor

Pick Color
Whether to pick the color under the cursor.

The pick options can also be toggled by pressing CTRL on the keyboard or from the tool’s right-
click menu.

To use the Pick Tool, perform the following:

1. Select the Pick Tool ( ) from the drawing toolbar.

2. Hover the cursor over the object from which the color/surface should be chosen. A popup
window will show what that color/surface is.

3. Single-click the left mouse button to pick.

The chosen color/surface will then be applied to the surface or color properties for the
obstruction, vent, mesh, and paint tools.

9.19. Measuring Length/Distance


PyroSim provides a Measure Tool ( ) to measure distances in the model.

To measure a distance, perform the following:

1. Select the Measure Tool ( ).

2. Either click several points to measure the total distance along a path or click-drag to measure
a single distance between two points. As the cursor is moved, the current cursor location, total
path length, and length of the most recent segment are displayed as shown in Figure 103.

3. To copy the distance, right-click and from the menu, choose Copy total distance to clipboard.
This will make the total distance measurement available on the clipboard so it can be pasted
into a field or any other paste location. The text that is copied to the clipboard includes both
the full precision value and the current display length unit. For example, it might copy
"3.2808399 ft" if working in the English unit system.

143 Chapter 9. Drawing in PyroSim


PyroSim - User Manual

Figure 103. Information displayed by the measure tool

When working in the 3D View, all distances are true to the 3D snapped locations
of the cursor. In the 2D Views, however, the cursor locations are projected to a
NOTE single plane parallel to the view before determining the distance. This means that
in the Top View, all Z distances are ignored. In the Front View, all Y distances are
ignored. In the Side View, all X distances are ignored.

Chapter 9. Drawing in PyroSim 144


PyroSim - User Manual

Chapter 10. Creating Complex Geometry


This chapter provides guidance on using the geometry tools available in PyroSim to create several
geometric shapes that often appear in building models. The ability to sketch in different planes,
copy, replicate, drag, scale, and rotate objects can greatly simplify the tasks of geometry creation.

10.1. Curved Walls


While PyroSim’s tools do not explicitly produce curved walls, they can approximate them using
any of the following techniques:

• Draw the wall using several straight wall segments.

• Draw the wall using individual blocks.

• Rotate a single object to produce the desired arc.

In all of the following examples, we will use a background image as a pattern to draw against.
While this is not required, it makes creating curved surfaces much easier and one of the strengths
of PyroSim is that it allows you to sketch geometry directly on top of building design images. The
background image we will be using is shown in Figure 104.

Figure 104. Background image used for all curved wall examples

For simplicity, we will assume that horizontal distance across the entire image is 50 feet, and we
will place the origin of the model at the lower-left corner of the room shown in the image. The
brightness of the image will be set to 50%. The Configure Background Image dialog shown in
Figure 105 illustrates these settings.

145 Chapter 10. Creating Complex Geometry


PyroSim - User Manual

Figure 105. Background image settings for curved wall examples

10.1.1. Using the Wall Tool


To create a curved wall section from wall segments, you can follow these steps:

1. Click the 2D View tab, and select the Draw Wall Obstruction ( ) tool.

2. Turn off grid snapping. In the View menu, click Disable Grid Snapping.

3. Position the cursor at the beginning of the curve where you want to place the first wall
segment.

4. Use Multi-click Mode to click several points along the curve. More points will create a
smoother curve.

5. Right-click in the 2D View and select Finish to finish drawing the wall.

This is the fastest way to create smooth curves in PyroSim. PyroSim will convert the curved walls
to blocks before running the FDS simulation. While smaller segments will make the wall look
better in PyroSim, placement of obstructions generated for FDS depends on the resolution of your
mesh. A curved wall drawn with three different segment lengths created with this technique are
shown below.

A curved wall drawn with three different segment lengths

Chapter 10. Creating Complex Geometry 146


PyroSim - User Manual

Figure 106. Curved wall Figure 107. Shorter segments Figure 108. Shortest segments
segments

Using extremely short line segments will probably not be of any benefit unless you also use very
small mesh cells.

10.1.2. Using the Block Tool


To create a curved wall section from blocks, you can follow these steps:

1. Create a mesh. This example uses a 50.0 ft x 50.0 ft mesh with 1 ft mesh cells.

2. Click the 2D View tab, and select the Block Obstruction Tool ( ).

3. Turn grid snapping on. If snapping is off: in the View menu, click Snap to Model Grid.

4. Click each cell along the curved wall to place the necessary blocks.

This technique forces you to convert the curve to blocks manually, but the advantage is you know
exactly what geometry will be generated for FDS. If you have a high resolution mesh, it may be
useful to drag the mouse and "paint" the curve rather than clicking individual blocks. The
example curved wall is shown in Figure 109.

147 Chapter 10. Creating Complex Geometry


PyroSim - User Manual

Figure 109. A curved wall drawn using individual blocks

10.1.3. Rotating an Object


To create curved objects using the rotation technique, you must place an initial segment, then
perform a rotate operation about the center point of your desired curve.

This process is illustrated in the following steps:

1. Click the 2D View tab, and select the Wall Obstruction Tool ( ).

2. Turn off grid snapping. If snapping is on: in the View menu, click Disable Grid Snapping.

3. Create an initial wall segment somewhere on the curve.

4. In the Model menu, click Rotate.

5. Select the Copy mode.

6. Specify the necessary parameters for the rotation operation. In this example, the Number of
Copies is 15, the Angle is 6.0 degrees, and the Base Point is: x=32.0 feet, y=16.5 feet.

7. Click Preview to verify that the settings are correct, then click OK.

The curve for this example is shown in Figure 110.

Chapter 10. Creating Complex Geometry 148


PyroSim - User Manual

Figure 110. A curved wall drawn using the rotate technique

If we would have created 60 copies instead of 15 this procedure would have created a cylinder.
While complicated, the rotation approach is the most effective at creating complex symmetrical
geometry.

10.2. Trusses
Trusses can be created by drawing a single truss out of slab obstructions and slab holes, then
replicating that truss as many times as needed as shown in Figure 111.

The following steps show how to create the trusses for an example roof.

1. Click the 2D View tab

2. On the toolbar, click the Reset to Front option.

3. On the drawing toolbar, select the Slab Obstruction Tool ( ).

4. On the drawing toolbar, click the Tool Properties ( ) button, and set the thickness to the
desired thickness of the truss.

149 Chapter 10. Creating Complex Geometry


PyroSim - User Manual

5. Draw a triangle representing the outer boundary of the truss.

6. On the toolbar, select the Slab Hole Tool ( ).

7. Draw a triangular hole in the left half of the truss.

8. Select the newly created hole.

9. Select the Mirror Tool ( ).

10. Right click in the 2D View and select Copy Mode.

11. Draw a line from the top vertex of the outer obstruction to the center of the bottom to define
the mirror plane.

12. Select the entire truss, including the outer obstruction and two holes.

13. Open the Model menu, and click Move.

14. In the Move dialog: select Copy, set Number of Copies to 4, set Offset to be 2.0 meters along
the Y axis, and click OK.

Figure 111. Trusses created using PyroSim tools

Chapter 10. Creating Complex Geometry 150


PyroSim - User Manual

10.3. Roofs
You can quickly add a roof to the model using the Slab Obstruction Tool ( ).

The following steps show how to add a roof to the previous truss example.

1. Click the 2D View tab.

2. On the view toolbar, Reset to Front.

3. On the drawing toolbar, select the Slab Obstruction Tool ( ).

4. Draw the profile of the roof as one polygon so that it touches the trusses. Click the top point,
then bottom point, and the top point once more to create the slab.

5. On the view toolbar, Reset to Top.

6. On the navigation toolbar, select the Select/Manipulate Tool .

7. Click to drag the leading edge of the slab to the opposite truss.

8. Single-click to end manipulation.

9. Repeat steps 7-9 for the back edge of the roof slab to line it up with the back of the last truss.

The resulting roof section is shown in Figure 112.

151 Chapter 10. Creating Complex Geometry


PyroSim - User Manual

Figure 112. A roof created with the slab obstruction tool

The extruded polygon tool can be used to create obstructions with any number of boundary
points (triangles, quads, etc).

10.4. Stairs
Users can create simple stairways by placing the initial stair, then using the move operation. This
section will present a simple example to illustrate the approach.

We will create a 10 step stairway. Each step will have a 7 inch rise (0.58 feet), and a 10 inch (0.83
feet) run. The stairway itself will be 24 inches (2.0 feet) wide. To keep things as simple as possible,
we will construct the stairway in an empty model.

1. On the Model menu, click New Obstruction.

2. In the Obstruction Properties dialog, specify the min point as (0.0, 0.0, 0.0) and the max point
as (2.0, 0.83, 0.58).

3. On the Model menu, click Move.

4. In the Move dialog, select Copy, set the Number of Copies to 9, set the Offset to (0.0, 0.83,

Chapter 10. Creating Complex Geometry 152


PyroSim - User Manual

0.58), and click OK.

The stairway generated in this example is shown in Figure 113.

Figure 113. A stairway created with the copy tool

153 Chapter 10. Creating Complex Geometry


PyroSim - User Manual

Chapter 11. Working with Geometry Objects


11.1. Selection
PyroSim relies heavily on the idea of selected objects. For almost all operations, the user first
selects an object(s) and then changes the selected object(s). The Selection Tool ( ) is used to
select objects.

• A left mouse click on an object in any view will select it.

• Holding Ctrl while clicking will toggle the item in the selection, adding previously unselected
items and removing previously selected items.

• Holding Alt while clicking an object in the 3D View or the 2D View will select the entire group
that the object belongs to.

• In the Navigation View, a range of objects can be selected by clicking the first object, then
holding Shift while clicking the last object.

• In the 2D and 3D Views, multiple objects can be selected with the Selection Tool and a click-
drag motion to define a selection box.

Once objects have been selected, the user can modify the object using the menus.

Selection can be made in any of the views using the Selection tool. Multiple objects can be
selected using the Ctrl key or click and drag to define a box. In the Navigation View, the Shift key
can be used to select a consecutive list of objects.

11.2. Context Menus


A right-click on a selection displays a context menu. This menu includes the most common options
for working with the object. The user may also right-click on individual objects for immediate
display of the context menu.

11.3. Undo/Redo
All geometric changes to the model can be undone and redone using the Undo ( ) and Redo ( )
buttons, as well as Ctrl+Z and Ctrl+Y, respectively.

11.4. Copy/Paste
Select an object to copy, then either use Ctrl+C or Edit→Copy to copy. Alternately, right-click on an
object to display the context menu with Copy.

Chapter 11. Working with Geometry Objects 154


PyroSim - User Manual

Either use Ctrl+V or Edit→Paste to paste a copy of the object. Alternately, right-click on an object
to display the context menu with Paste.

11.4.1. Copy/Paste from Other Models


By running two instances of PyroSim, you can copy objects from one model and paste them into a
second model. If the copied objects rely on other properties, such as surfaces, that are not
included in the second model, these properties will be pasted into the model when the objects are
pasted.

11.4.2. Copy/Paste from Text Files


Copy/paste can also be performed to and from text files. For example the user can select an object
in PyroSim, open a text file, and paste the object. The text FDS representations of the object and
dependent properties will be pasted. Alternatively, the user can copy the text from an FDS file and
paste into PyroSim (the 3D View, 2D View, or Navigation View). The object will be added to the
PyroSim model. An error message will be received if the pasted object depends on data that is not
available in the PyroSim model. The user will then need to paste that information (such as surface
properties) first before pasting the geometric object.

11.5. Double-Click to Edit


Double-clicking on an object opens the appropriate dialog for editing the object properties.

11.6. Move Dialog


The Move dialog can be used to both move an object and to create copies of an object, each offset
in space.

To move an object in this manner, perform the following:

1. Right click the object(s) to move.

2. From the right-click menu, select Move.

3. This will show the Move dialog, Figure 114.

The Mode selects either the option to move only the selected object or to create copies of the
object and move them. The Offset parameters indicate the increment to move or offset the copies.

To preview the changes without applying them, click Preview. To apply the changes and close the
dialog, click OK. To cancel the changes instead, click Cancel.

155 Chapter 11. Working with Geometry Objects


PyroSim - User Manual

Figure 114. The move dialog

11.7. Mirror Dialog


The Mirror dialog can be used to mirror an object about a plane or planes or create a mirrored
copy of an object. To mirror an object in this manner, perform the following:

1. Right click the object(s) to mirror.

2. From the right-click menu, select Mirror*.

3. This will show the Mirror dialog as in Figure 115.

The Mode selects either the option to mirror only the selected object or to create a mirrored copy
of the object. The Mirror Plane(s) define planes normal to the X, Y, and Z axes about which the
object will be mirrored. The Use Center button can be used to fill the Mirror Plane data with the
center coordinates of the selected objects.

To preview the changes without applying them, click Preview. To apply the changes and close the
dialog, click OK. To cancel the changes instead, click Cancel.

Chapter 11. Working with Geometry Objects 156


PyroSim - User Manual

Figure 115. The mirror dialog

11.8. Scale Dialog


The Scale dialog can be used to change the size of an object or create scaled copies of an object. To
scale an object, perform the following:

1. Right click the object(s) to scale.

2. From the right-click menu, select Scale*.

3. This will show the Scale dialog as in Figure 116.

The Mode selects either the option to scale only the selected object or to create multiple scaled
copies of the object. The Scale values define the scale factors in the X, Y, and Z directions. The
Base Point defines the point about which the scaling will be performed. The Use Center button
can be used to fill the Base Point data with the center coordinates of the selected objects.

To preview the changes without applying them, click Preview. To apply the changes and close the
dialog, click OK. To cancel the changes instead, click Cancel.

157 Chapter 11. Working with Geometry Objects


PyroSim - User Manual

Figure 116. The scale dialog being used to scale an object

11.9. Rotate Dialog


The Rotate dialog can be used to rotate an object or to create rotated copies of an object. To rotate
an object, perform the following:

1. Right click the object(s) to rotate.

2. From the right-click menu, select Rotate

3. This will show the Rotate dialog as in Figure 117.

The Mode selects either the option to rotate only the selected object or to create multiple rotated
copies of the object. The Rotation values allow the user to select the axis about which the rotation
will be made and the angle is the rotation angle (counter-clockwise is positive). The Base Point
defines the point about which the rotation will be performed. The Use Center button can be used
to fill the Base Point data with the center coordinates of the selected objects.

To preview the changes without applying them, click Preview. To apply the changes and close the
dialog, click OK. To cancel the changes instead, click Cancel.

Chapter 11. Working with Geometry Objects 158


PyroSim - User Manual

Figure 117. The rotate dialog being used to rotate an object

11.10. Object Visibility


Often it is desirable to turn off the display of selected objects, for example, to hide a roof of a
building in order to visualize the interior. In any of the views, right-click on a selection to obtain
the following options:

• Hide object(s) - This turns off the display of the selected object(s).

• Show object(s) - This turns on the display of the selected object(s).

• Filter object(s) - This turns off the display of all objects except the selection(s).

• Show all objects - Turns on the display of all objects.

159 Chapter 11. Working with Geometry Objects


PyroSim - User Manual

Chapter 12. Species


Gas species can serve many different roles in a PyroSim model. In the simplest applications, a
number of gaseous species are implicitly defined and tracked within the simulator to model the
combustion of hydrocarbon fuels. For this type of model, the Fire Dynamics Simulator simulates
and tracks three unique species; AIR, PRODUCTS, and FUEL. These three species can consequently
be used anywhere else in the model, and their major components; OXYGEN, CARBON DIOXIDE,
WATER VAPOR, NITROGEN, CARBON MONOXIDE, and SOOT can be referenced for output data.

By default, PyroSim adds all species which have been implicitly defined by FDS to the model on
startup. These species are unique from those involved in the reaction chemistry, and will not take
part in the simple reaction chemistry if referenced. While PyroSim manually handles the logic
that determines whether or not it is necessary to include a species in the FDS input file, it is
important to understand what requires a species line be written to the output. A species
referenced by any of the following will cause it to be written:

1. The species has a non-zero Initial Mass Fraction.

2. An initialization region includes some mass fraction of the species (see Chapter 19).

3. A liquid particle referenced in the model refers to the species (see Chapter 14).

4. A supply surface referenced in the model injects the species (see Chapter 7).

5. A material referenced in the model creates the species through its pyrolysis reaction (see
Chapter 6).

6. An HVAC filter absorbs some fraction of the species (see Chapter 17).

Three different classifications of species type can be created in a PyroSim model. The first type are
predefined species, whose name’s and chemical properties are known by FDS. The second type are
custom primitive species. These differ from predefined species in that they must have their
chemical properties defined. And lastly, there are custom lumped species, which are defined as
either a mass or volume fraction of predefined and custom primitive species.

Species can be managed by opening the Model menu and selecting Edit Species.

To create either a new species, or include a predefined one, select New and choose whether the
species should be Predefined, Primitive, or Lumped.

12.1. Primitive Species


Primitive species can be tracked individually, or as a component of a more complex lumped
species.

Chapter 12. Species 160


PyroSim - User Manual

To edit primitive species:

1. On the Model menu, click Edit Species.

2. On the Primitive tab, set the Molecular Weight (MW) of the species. You may also specify the
chemical formula for the reaction if you plan to use the species in a combustion reaction.

3. On the Vis/Dif tab, you can specify the Diffusivity (DIFFUSIVITY) or Viscosity (VISCOSITY) for
the species. These can either be fixed, or specified as ramps using the Custom option in the
respective combo boxes. You can also specify the Lennard-Jones Parameters (SIGMALJ,
EPSILONKLJ).

4. Some species need to absorb or emit thermal radiation. In this case, you may specify a Radcal
Surrogate on the Radiation tab. The species will use the absorbing properties of the specified
surrogate. It is best to use a surrogate with molecular properties similar to the custom species.

5. To invoke the aerosol deposition model of FDS, select the Aerosol (AEROSOL) checkbox on the
Soot tab. If the deposition model is used, you must also specify Density (Solid)
(DENSITY_SOLID), Conductivity (Solid) (CONDUCTIVITY_SOLID), and Mean Diameter
(MEAN_DIAMETER).

6. The Liquid tab is used to define the thermal properties of evaporating liquid droplets. Note
that these variables are only used when a particle evaporates. For more information about
specifying an evaporating liquid droplet, see Chapter 14.

7. The Gas tab is used to set parameters related to the enthalpy of the gas species. The enthalpy
is specified by a combination of Specific Heat (SPECIFIC_HEAT), Reference Temperature
(REFERENCE_TEMPERATURE), and Reference Enthalpy (REFERENCE_ENTHALPY). For more
information on how enthalpy is calculated, refer to the FDS User Manual.

12.2. Lumped Species


Species mixtures can be defined as a mixture of any number of primitive species. Because all
species in the simulation must be tracked by a transport equation, a lumped species can be used to
save on simulation time.

To create a lumped species:

1. On the Model menu, click Edit Species.

2. Click New

3. Select the Lumped option.

4. Click OK

To edit the lumped species:

161 Chapter 12. Species


PyroSim - User Manual

1. On the Model menu, click Edit Species.

2. Lumped species cannot be assigned fixed values like a primitive species can. Instead, the
simulator derives this information from the combination of all the individual components of
the species. In the Lumped panel, you can specify the composition as either a Mass Fraction
or a Volume Fraction. In either case, a table of all declared Primitive Species and their
fractional composition is displayed on the panel.

When using lumped species, it is recommended that certain actions be taken to reduce the
complexity of the simulation.

To save on simulation time:

1. On the Model menu, click Edit Species.

2. If a primitive species is to be used only as a component of a lumped species, select that species.

3. Click the Advanced panel.

4. Add the line LUMPED_COMPONENT_ONLY = .TRUE. to the list of Additional Fields. For more
information about Advanced FDS Parameters, see Chapter 22>.

5. Click OK.

Doing this check for all primitive species will reduce the number of transport equations solved by
the simulator, and save significant time on the simulation.

Chapter 12. Species 162


PyroSim - User Manual

Chapter 13. Reactions


This chapter provides an overview of how to specify combustion (the reaction of fuel vapor and
oxygen) using PyroSim. A more detailed discussion of this topic is provided in the Fire Dynamics
Simulator User’s Guide and the Fire Dynamics Simulator Technical Reference Guide.

As described in the Fire Dynamics Simulator User’s Guide, a common source of confusion in FDS
is the distinction between gas phase combustion and solid phase pyrolysis. The former refers to
the reaction of fuel vapor and oxygen; the latter the generation of fuel vapor at a solid or liquid
surface. In an FDS fire simulation, there is only one gaseous fuel that acts as a surrogate for all the
potential fuel sources.

In most fire simulations, pyrolysis is defined by specifying a Heat Release Rate Per Unit Area
(HRRPUA) as part of a surface. A more complex approach is to define a material with a pyrolysis
reaction.

The reaction is defined using the Edit Reactions dialog in PyroSim.

13.1. Defining the Combustion Reaction


PyroSim supports the "simple chemistry" combustion model in FDS that considers a single fuel
species composed of [stem 9b325b9e31e85137d1de765f43c0f8bc], [stem
7b9a0316a2fcd7f01cfd556eedf72e96], [stem 9afe6a256a9817c76b579e6f5db9a578], and [stem
f9c4988898e7f532b9f826a75014ed3c] that reacts with oxygen in one mixing-controlled step to
form [stem d7fc8f229a929f93c03b951b7fe40bf0], [stem 8306272097a2ac71e3c568c80d48b7f9],
[stem 58195e9dd077adcd98a0692c1d3fdd7d], and [stem f74275c195a72099e0b06f584fd5489a] (see
Chapter 12 in the FDS User Guide).

To create a reaction:

1. On the Model menu, click Edit Reactions.

2. Click New and give the Reaction Name.

3. The fuel composition is entered on the Fuel tab. If the user selects the Simple Chemistry
Model, define the fuel composition by specifying the number of [stem
9b325b9e31e85137d1de765f43c0f8bc], [stem 7b9a0316a2fcd7f01cfd556eedf72e96], [stem
9afe6a256a9817c76b579e6f5db9a578], and [stem f9c4988898e7f532b9f826a75014ed3c] atoms
(fractions are acceptable). Alternately, the user can select the fuel from a predefined species
list that is given in the FDS User Guide, Table 11.1: Optional gas and liquid species.

To do this:

a. From the Fuel Type list, select Predefined.

163 Chapter 13. Reactions


PyroSim - User Manual

b. Click Edit Species.

c. Click New.

d. From the Predefined list, select the fuel.

e. Return to the Fuel tab and from the Fuel Species list, select the fuel species you just
added.

4. On the Fire Suppression tab, you can enable fire suppression and then enter values for the
Critical Flame Temperature (CRITICAL_FLAME_TEMPERATURE) and the Automatic Ignition
Temperature (AUTO_IGNITION_TEMPERATURE).

5. On the Byproducts tab, you can select either Specify release per unit mass oxygen (EPUMO2)
or specify heat of combustion (HEAT_OF_COMBUSTION). You can also specify the [stem
f74275c195a72099e0b06f584fd5489a] yield, [stem 130817f05ce47d5d4434c48f84c2bd07] yield,
and [stem 58195e9dd077adcd98a0692c1d3fdd7d] yield.

FDS will use the chemical formula of the fuel along with the yields of [stem
f74275c195a72099e0b06f584fd5489a] and [stem 58195e9dd077adcd98a0692c1d3fdd7d], and the
volume fraction of hydrogen in the soot to calculate the stoichiometric coefficients for the
reaction. Details of the reaction are output by FDS in the *.out file written during execution.

13.2. Custom Smoke


PyroSim supports the custom smoke features available in FDS. To create custom smoke, first
define an species with the desired mass extinction coefficient. This "smoke" species can then be
injected into the domain like any other species. Smoke detectors can also detect this smoke species
if it is selected under the smoke detector’s model, which can be edited under Edit Smoke
Detector Models. on the Devices menu. Finally, if the Results should track this species as smoke,
go to the Analysis menu, select Simulation Parameters. and on the Output tab select the mass
fraction quantity of the desired species from the Smoke Quantity drop-down box. Note that in
addition to specifying the mass fraction of a species, the mass fraction of any mixture fraction
species can also be selected for smoke display, including the mass fraction of oxygen, water vapor,
and the other species specified in the gas-phase reaction.

Chapter 13. Reactions 164


PyroSim - User Manual

Chapter 14. Particles


PyroSim supports three types of particles: massless tracers, liquid droplets, and solid particles. To
create a new particle:

1. On the Model menu, click Edit Particles.

2. Click New.

3. In the Particle Type box, select one of the types.

4. Click OK

14.1. Liquid Droplets


Evaporating liquid droplets can be used with sprinkler spray models and nozzles to customize the
spray. They can also be used in particle clouds and surface types that support particle injection.

14.1.1. Liquid
Species
The species that defines the thermal properties of the particles.

Movement
Defines whether the particles can move or are static, causing them to act as obstructions to
flow.

14.1.1.1. Liquid Species Parameters

To specify a liquid droplet, you must specify a species. This can be one of the predefined species
recognized in Table 11.1 of the FDS User’s Guide, or any other user defined species. If the species
is not predefined, it is important to specify the liquid properties of the species.

To edit the liquid properties of the species:

1. On the Model menu, click Edit Species.

2. Select the primitive species.

3. Select the Liquid tab.

4. Specify the fields below.

5. Click OK.

Liquid species have the following properties.

165 Chapter 14. Particles


PyroSim - User Manual

Specific Heat
The droplet specific heat.

Density
The droplet density.

Vaporization Temperature
The droplet liquid boiling temperature.

Melting Temperature
The droplet melting/freezing temperature.

Heat of Vaporization
The droplet latent heat of vaporization.

Enthalpy of Formation
The heat of formation of the gaseous species.

H-V Reference Temperature


The temperature associated with the Heat of Vaporization

Properties of the liquid particles are specified in the Particle Dialog.

14.1.2. Drag
Drag refers to the drag force the particle exerts on the flow around it, see section "17.4.2 Drag" in
the FDS User Guide. There are four Drag options: Sphere (default), Cylinder, Screen and Specify
Drag Coefficient.

The Dense Volume Fraction value must be ⇐1.0 and is discussed in section "17.3.5 Dense Clouds of
Droplets" in the FDS Users Guide.

14.1.3. Size Distribution


Median Diameter
The median volumetric diameter of each droplet.

Constant
Use a constant diameter for each droplet.

Rosin-Rammler
Allow each droplet to be sized according to Rosin-Rammler distribution.

Chapter 14. Particles 166


PyroSim - User Manual

Lognormal
Allow each droplet to be sized according to a lognormal distribution.

Rosin-Rammler-Lognormal
Rather than use a constant diameter for each droplet, allow each to be sized according to a
combination of Rosin-Rammler and lognormal.

Gamma D
The width of the Rosin-Rammler distribution. The larger the value of gamma, the narrower the
droplet size is distributed about the median value.

Sigma D
The width of the lognormal distribution.

Minimum Diameter
Droplets smaller than the minimum diameter are assumed to evaporate in a single time step.

Maximum Diameter
Droplets larger than the maximum diameter are assumed to break up in a single time step.

14.1.4. Coloring
Default
Allows FDS to select a color for this particle.

Specify
Select to choose a custom particle color.

By Droplet Property
Select this option to choose one or more scalar quantities that will be used to color this particle
in the 3D Results.

14.1.5. Injection
Duration
The amount of time a water droplet will remain in the simulation.

Sampling Factor
Sampling factor for the particle output file. A value of -1 uses the FDS default value for this
property. Set to an integer greater than 1 to reduce the size of particle output.

167 Chapter 14. Particles


PyroSim - User Manual

14.1.6. Special Topic: Fuel Droplets


Liquid particles can be injected into the domain as evaporating fuel vapor that will burn
according to the combustion model specified in the active reaction. To specify a fuel particle, set
the liquid particle’s species to the same species as the Fuel Species for the active reaction, see
Section 1.3.2. For instance, if the fuel species of the active reaction is METHANE, choose METHANE for
the particle species as well. If the active reaction is using the Simple Chemistry Model option,
choose the species, REAC_FUEL for the particle species.

14.2. Solid Particles


PyroSim provides basic support for specifying solid particles. A solid particle must reference a
surface, from which it derives its thermophysical and geometric parameters. A solid particle can
be used to model various heat transfer, drag, and vegetation applications. Most of the parameters
unique to solid particles must be defined on the Advanced Panel, see Chapter 22.

14.3. Massless Tracers


Massless tracer particles can be used to track air flow within a simulation. They can be used with
the particle injection feature of the Burner, Heater/Cooler, Blower, and Layered surface types.
They can also be used in particle clouds.

By default, PyroSim provides a black, massless tracer particle called Tracer. To use a custom tracer
particle in your simulation, you can modify the parameters of this default particle to suit your
needs, or you can create a new particle.

The tracer particle properties are as follows:

Color
The color of the tracer particle.

Duration
The amount of time a droplet of this type will remain in the simulation.

Sampling Factor
Sampling factor for the particle output file. A value of -1 uses the FDS default value for this
property. Set to an integer greater than 1 to reduce the size of particle output.

14.4. Activation
Normally, the insertion of particles into the domain is controlled by the surface or object emitting
them, such as by a fan or supply surface or a particle cloud. Alternatively, the insertion of

Chapter 14. Particles 168


PyroSim - User Manual

particles can be controlled by a device or other control logic. For more information on controls,
see Chapter 16.

14.5. Global Parameters


There are two global options relating to particles in the Simulation Parameters dialog. The first
option, Droplets Disappear at Floor, can be used to prevent droplets from gathering on the floor
of the simulation area. The default value for this option is ON. The second option, Max Particles
per Mesh, can be used to set an upper limit on the number of particles allowed in any simulation
mesh.

14.6. Particle Clouds


Particle Clouds provide a way to insert particles into the simulation either in a box-shaped region
or at a specific point. Particles can either exist at the start of the FDS simulation or can be inserted
periodically.

To create a particle cloud, on the Model menu, click either New Particle Cloud. to create a region
of particles or New Particle Location. to specify a specific point for the particles. This will show
the particle cloud dialog as in Figure 118.

169 Chapter 14. Particles


PyroSim - User Manual

Figure 118. Particle Cloud dialog

Particle clouds have the following properties:

Particle
The type of particle to insert in the volume.

Droplet Count
Controls the number of particles in the volume.

Density
Specifies the particle count as a volume density (NOTE: this is only available when the
geometry is a volume).

Droplets/cell
FDS intersects the particle cloud’s geometry with the mesh cells in the model. For each cell,

Chapter 14. Particles 170


PyroSim - User Manual

FDS inserts the specified number of particles. The particles may optionally be cell-centered.

Constant
Species a constant number of particles for the region.

Insertion
How often the particles are inserted in the region.

Insert Once
Inserts the particles once at the beginning of the simulation.

Mass Per Volume


Specifies the total density of the particles if the geometry is a volume. This is
independent of the particle density, which is specified per particle type.

Insert Periodically
Inserts particles periodically during the simulation.

Insertion Interval
Specifies how often the particles are inserted when the control is true.

Mass Per Time


Controls how much mass is distributed across the inserted particles.

Activation
A control may be specified to control when the particles can be inserted.

The geometry properties, including the size and location of the volume or the point location can
be specified on the Geometry tab.

Press OK to create the new particle cloud. It will appear as a translucent box or a point in the 3D
and 2D Views.

171 Chapter 14. Particles


PyroSim - User Manual

Chapter 15. Devices


Devices are used to record quantities in the model or to represent more complex sensors, such as
smoke detectors, sprinklers, and thermocouples. You can make time history plots of device output
in PyroSim by opening the CHID_devc.csv file.

Devices can be moved, copied, rotated, and scaled using the tools described in Chapter 11. Most
often, the user will simply select one or more devices, right-click to display the context menu, and
click Move. By copying a single device along a line and then copying the line in the normal
direction, it is possible to quickly define an array of devices.

When a device is defined, a trigger value (setpoint) can be created that can be used to activate
other objects. This is discussed more in Chapter 16. When acting as a detector you may specify
whether the signal from the device starts as true (initially activated), whether the logic signal is
locked after the setpoint is tripped (triggers only once), and whether the signal should flip when
the device output ascends or descends (trip direction) across the setpoint.

In addition, the output of a device can be frozen at its current value when another control
activates. This can be used to create more complex logic, such as holding the heat release rate of a
fire at its current value when a sprinkler activates.

15.1. Aspiration Detection System


An aspiration detection system groups together a series of soot measurement devices. An
aspiration system consists of a sampling pipe network that draws air from a series of locations to
a central point where an obscuration measurement is made. To define such a system in FDS, you
must provide the sampling locations, sampling flow rates, the transport time from each sampling
location, and if an alarm output is desired, the overall obscuration setpoint.

To define the soot measurement devices:

1. On the Devices menu, click New Aspirator Sampler.

2. Enter the Name and Location of the sampler.

3. Click OK to create the sampler.

To define the aspiration detection system:

1. On the Devices menu, click New Aspirator.

2. Give the Name and select which Aspirator Samplers will be included. For each sampler,
provide the data described below.

3. Click OK to create the aspirator detector.

Chapter 15. Devices 172


PyroSim - User Manual

Supply the following information for the aspiration detection system, Figure 119.

Aspirator Name
The name of the aspiration detection system.

Freeze Output
An input control that will cause the output of the device to freeze at its current value when the
control activates.

Bypass Flow Rate


The flow rate of any air drawn into the system from outside the computational domain.

Transfer Delay
The transport time from the sampling location to the central detector.

Flowrate
The gas flow rate.

Location
The coordinates of the aspiration detection system.

Orientation
Not used.

Rotation
Not used.

173 Chapter 15. Devices


PyroSim - User Manual

Figure 119. Creating an aspirator sampler

The output of the aspiration detection system will be the combined obscuration.

15.2. Gas or Solid Phase Device


Simple gas phase and solid phase devices can be used to measure quantities in the gas or solid
phase. To define a measurement device, on the Devices menu, click New Gas-phase Device or
New Solid-phase Device.

The device properties are:

Device Name
The name of the device.

Chapter 15. Devices 174


PyroSim - User Manual

Freeze Output
An input control that will cause the output of the device to freeze at its current value when the
control activates.

Quantity
The quantity to measure.

Location
The coordinates of the device.

Orientation
Gas-phase only, not used.

Normal of Solid
Solid-phase only, specifies the outward normal of the surface on which the device is attached.

Rotation
Not used.

15.3. Thermocouple
To create a thermocouple, on the Devices menu, click New Thermocouple.

The thermocouple properties are:

Device Name
The name of the thermocouple.

Freeze Output
An input control that will cause the output of the device to freeze at its current value when the
control activates.

Bead Diameter
The bead diameter of the thermocouple.

Emissivity
The emissivity of the thermocouple.

Bead Density
The material density of the bead. The default value is that for nickel.

175 Chapter 15. Devices


PyroSim - User Manual

Bead Specific Heat


The material specific heat of the bead. The default value is that for nickel.

Location
The coordinates of the device.

Orientation
Not used.

Rotation
Not used.

The output of the thermocouple is the temperature of the thermocouple itself, which is usually
close to the gas temperature, but not always, since radiation is included in the calculation of
thermocouple temperature.

15.4. Flow Measurement


The flow measurement device can be used to measure a flow quantity through an area. To create
a flow measuring device, on the Devices menu, click New Flow Measuring Device.

The flow measurement device properties are:

Device Name
The name of the flow measuring device.

Freeze Output
An input control that will cause the output of the device to freeze at its current value when the
control activates.

Measurement Type
The quantity to be measured. The selected measurement type is not the FDS quantity itself, but
a category of quantity types that PyroSim infers based on other settings. Measurement types
are either in the gas-phase, or in the solid-phase if the type contains the text "at a boundary".

Flow Direction
This is shown only for gas-phase quantities. Select the direction of flow to be considered. By
default, the flow measurer includes all mass, volume, or enthalpy across the measurement
region. You may select either "Positive" or "Negative" to isolate the flows in one direction.

Chapter 15. Devices 176


PyroSim - User Manual

Species
This is shown only for mass flow measurement types. Either select "All" to consider all mass
across the measurer, or specify a species to consider its flow in isolation.

Component
This is shown only for mass flow measurement types. For gas-phase quantities, you may select
one of the "Default", "Total", "Diffusive", or "Advective" components of mass flow. For solid-
phase quantities, you may select of the "Default" ("Mass Flux"), "Mass Flux Wall", or "Total Mass
Flux Wall".

Wall Normal
This is shown only for solid-phase quantities. Either select "Auto" to have this value auto-
calculate or select the obstruction’s normal direction at the location of the device.

Plane
The axis normal to the measurement plane and the location of that plane on the axis. For gas-
phase flow measurers, PyroSim will use the selected plane to determine the required flow
quantity.

Bounds
The coordinates of the area normal to the axis.

The output will be the total flow through the defined area.

15.5. Heat Release Rate Device


The heat release rate device measures the heat release rate within a volume. To define a heat
release rate device, on the Devices menu, click New Heat Release Rate Device.

The heat release rate device properties are:

Device Name
The name of the heat release rate device.

Freeze Output
An input control that will cause the output of the device to freeze at its current value when the
control activates.

Bounds
The coordinates of the volume within which to calculate the heat release rate.

The output will be the total heat release rate within the volume.

177 Chapter 15. Devices


PyroSim - User Manual

15.6. Layer Zoning Device


There is often the need to estimate the location of the interface between the hot, smoke-laden
upper layer and the cooler lower layer in a burning compartment. Relatively simple fire models,
often referred to as two-zone models, compute this quantity directly, along with the average
temperature of the upper and lower layers. In a computational fluid dynamics (CFD) model like
FDS, there are not two distinct zones, but rather a continuous profile of temperature. FDS uses an
algorithm based on integration along a line to estimate the layer height and the average upper
and lower layer temperatures. To define a layer zoning device, on the Devices menu, click New
Layer Zoning Device.

The layer zoning device properties are:

Device Name
The name of the layer zoning device.

Freeze Output
An input control that will cause the output of the device to freeze at its current value when the
control activates.

Measure Layer Height


Enables measurement of the layer height.

Measure Upper Temperature


Enables measurement of the upper layer temperature.

Measure Lower Temperature


Enables measurement of the lower layer temperature.

Path
The coordinates of the end points of a line along which the layer height will be calculated. The
two endpoints must lie in the same mesh.

The output will be the quantities selected.

15.7. Path Obscuration (Beam Detector) Device


A beam detector measures the total obscuration between points. To define a beam detector device,
on the Devices menu, click New Path Obscuration Device.

The path obscuration device properties are:

Chapter 15. Devices 178


PyroSim - User Manual

Device Name
The name of the path obscuration device.

Freeze Output
An input control that will cause the output of the device to freeze at its current value when the
control activates.

Path
The coordinates of the end points of a line along which the obscuration will be calculated. The
two endpoints must lie in the same mesh.

The output will be the percent obscuration along the path.

15.8. Heat Detector


A heat detector measures the temperature at a location using a Response Time Index model. To
define a heat detector device, on the Devices menu, click New Heat Detector.

The heat detector device properties are:

Device Name
The name of the heat detector.

Freeze Output
An input control that will cause the output of the heat detector to freeze at its current value
when the control activates.

Link
The link defines the activation temperature and the response time index.

Location
The coordinates of the device.

Orientation
Not used.

Rotation
Not used.

The output will be the heat detector temperature.

179 Chapter 15. Devices


PyroSim - User Manual

15.9. Smoke Detector


A smoke detector measures obscuration at a point with two characteristic fill-in or "lag" times. To
define a smoke detector, on the Devices menu, click New Smoke Detector.

The smoke detector device properties are:

Detector Name
The name of the smoke detector.

Freeze Output
An input control that will cause the output of the smoke detector to freeze at its current value
when the control activates.

Model
Select the smoke detector type. You can edit the smoke detector parameters to create a new
type.

Location
The coordinates of the device.

Orientation
Not used.

Rotation
Not used.

The output will be the percent obscuration per meter.

15.10. Sprinkler
Sprinklers can spray water or fuel into the model. To define a sprinkler:

1. On the Devices menu, click New Sprinkler. This will display the Sprinkler dialog, Figure 120.

2. Select the desired options and define required input parameters as described below.

3. Click OK to create the sprinkler.

Chapter 15. Devices 180


PyroSim - User Manual

Figure 120. Creating a new sprinkler

The sprinkler properties are:

Sprinkler Name
The name of the sprinkler.

Freeze Output
An input control that will cause the output of the sprinkler’s link to freeze at its current value
when the control activates.

Spray Model
The spray model defines the particle type (water and fuel are default options), the flow rate,
and the jet stream shape.

Dry Pipe
In a dry pipe sprinkler system, the normally dry sprinkler pipes are pressurized with gas.
When a sprinkler link attached to the dry pipe activates, the pressure drops, allowing water to

181 Chapter 15. Devices


PyroSim - User Manual

flow into the pipe network. Once the pipe is full, any activated sprinkler nozzles attached to
that pipe will begin to flow. You can create any number of dry pipes and attach any number of
sprinklers to them. Each dry pipe simulates the time to fill the pipe with a simple time delay
parameter.

Activator
By default the sprinkler is activated by a temperature link, with a response time index. You can
edit the activation temperature and the response time index. Alternately, you can select a more
general quantity to activate the sprinkler. By default the sprinkler is initially not active and is
triggered only once.

Location
The coordinates of the sprinkler.

Orientation
The components of the direction vector.

Rotation
Normally not used for a sprinkler. It could be used to rotate a spray pattern that varies with
latitude (circumferentially).

15.11. Nozzle
Nozzles are very much like sprinklers, only they do not activate based on the standard RTI model.
They can be set to activate by custom control logic.

Chapter 15. Devices 182


PyroSim - User Manual

Chapter 16. Control Logic


Objects can be set to activate or deactivate during the simulation using activation events.
Activation events are the control logic system in FDS and can be set on each geometric simulation
object (e.g. walls, holes, vents) using the Activation option in the object’s Properties dialog.
PyroSim supports activation events based on time, input devices, and math operations applied to
such inputs. Some uses of activation events include:

• Causing a door obstruction to be removed (i.e. opened) from the simulation at a particular
time,

• Causing a window obstruction to be removed (i.e. break) when a heat detector triggers, and

• Causing a ventilation system to activate when any of several smoke detectors activates

To open the dialog shown in Figure 121: On the Devices menu, click Edit Activation Controls.

183 Chapter 16. Control Logic


PyroSim - User Manual

Figure 121. The Activation Controls dialog.

16.1. Activation Control Types


PyroSim allows the creation of three unique control types. When creating a new Activation
Control, you may select from one of the following:

1. Activation - An Activation Control manages the activation state of an object according to user
specified inputs.

2. Custom - A Custom Control is a specialized Activation Control that manages object creation
and removal according to multiple events which vary over time.

3. Mathematical - A Mathematical Control applies the selected math operation to device inputs.
The output of a Mathematical Control can be used as an input to an Activation Control in
order to manage PyroSim objects.

Chapter 16. Control Logic 184


PyroSim - User Manual

Figure 122. The New Control Dialog.

16.2. Creating Activation Controls


Creating controls in PyroSim takes 3 steps:

1. Select an input type (time, detector, deadband, or custom). This is the source of the signal that
will trigger the control.

2. Choose an action to perform (e.g. create an object).

3. Set specific inputs for the control based on a pattern created by steps 1 and 2.

After selecting an input type and an action, a pattern (in sentence form) for describing the control
logic will appear in the dialog. Some key words and numbers will be drawn in blue and
underlined. Any blue text can be clicked to modify the behavior of the specific control.

Figure 123 shows the selector popup for objects. Objects are selected by name. To quickly find
objects in the selector popup, you can type the first few letters of the object’s name.

185 Chapter 16. Control Logic


PyroSim - User Manual

Figure 123. The Activation Controls object popup.

Activation controls are stored separately from specific geometric objects. This makes it possible to
bind an object to a control after it has been created. You can use the Activation box in an object’s
properties editor to bind that object to an existing activation control, or even create a new control
directly. Figure 124 shows the activation control in the object properties dialog for a hole.

Chapter 16. Control Logic 186


PyroSim - User Manual

Figure 124. The Activation Control selection field.

Once a control has been bound to an object (or objects) any objects linked to that control will
show a text description of the control in their properties editor. This text will be shown in blue
and underlined and can be clicked to edit the activation control. Changes made to the activation
control will impact all referencing objects.

16.3. Time-based Input


To create or remove an object at a specific time, select Time for the Input Type in the Activation
Controls dialog. When using time as the input, objects can be created at a specific time, removed
at a specific time, or be created and removed periodically throughout the simulation. To create or
remove the objects once, select Create/Activate or Remove/Deactivate under the Action to
Perform. To create/remove the object periodically, select Multiple under the Action to Perform.
When performing multiple timed events, the creation and removal and times at which they occur
are specified in the table at the bottom of the dialog. The create and remove events should
alternate as time increases.

16.4. Detector-based Input


To create or remove some objects based on a device in the model, the device or math operation
must first have a setpoint enabled.

To specify a device setpoint, perform the following:

187 Chapter 16. Control Logic


PyroSim - User Manual

1. Create a new device or open the properties for an existing device.

2. Check the box next to Enable Setpoint:

3. Enter the desired value at which the device will trip.

4. Choose the options for the detector:

◦ Trigger only once - the detector will only trigger once at the setpoint during the entire
simulation.

◦ Initially activated - if this is unchecked, the detector is untriggered at the start of the
simulation and will turn on when the setpoint is reached for the first time. If this is
checked, the detector is triggered at the start and will turn off when the setpoint is
reached.

◦ Trip Direction - if this is set to Ascending the detector will trigger when the device value
is greater than the setpoint. If set to Descending, the detector will trigger for the opposite
behavior.

5. Click OK to close the device dialog.

Once the desired devices have been given a setpoint, they can be used as inputs to the control
logic expression. Now in the Activation Controls dialog, select Detector as the Input Type. The
detector can be used to Create/Activate or Remove/Deactivate the desired objects when the
detector either activates or deactivates. If more than one detector is to be used to activate the
objects, the descriptive sentence can be used to decide if the objects should trigger when any, all,
or a certain number of the devices activate.

16.5. Deadband-based Input


To create or remove an object according to bounding setpoints on device or math operation, select
Deadband Control under the Input Type. Unlike Detector-based inputs, a Deadband-based
control does not require a setpoint. The descriptive sentence will guide the user towards selecting
an upper and a lower range at which the controlled objects will turn on or off.

16.6. Manual-based Input


Selecting Manual for the Input Type allows you to enter the exact CTRL record to be managed by
the control. After defining a valid CTRL record in the text editor, the descriptive sentence can be
used to specify the objects managed by the control.

16.7. Custom Controls


Custom controls allow objects to be created and removed periodically according to a table of
setpoints. Use the Function Input combobox to specify either Time or a device as the input to the

Chapter 16. Control Logic 188


PyroSim - User Manual

control. The table can then be used to specify multiple values at which the logic signal switches
and the managed objects are created or removed. The create and remove events should alternate
as values in the left hand side of the table increase.

Figure 125. The Custom Control Dialog.

16.8. Mathematical Controls


Mathematical controls apply simple math operations on the selected input signals. Input signals
may be any of Time, the output value of a device, a constant value, or the output of another
Mathematical control.

The following operations use a single value as an input: Exponential, Logarithm, Cosine, Sine,
Arccosine, Arcsine, Arctangent.

The following operations use a single value in addition to specialized parameters: PID, Percentile.

The following operations use two values as inputs: Subtract, Multiply, Divide, Power.

189 Chapter 16. Control Logic


PyroSim - User Manual

The following operations may use many values as inputs: Sum, Maximum, Minimum.

To use a Mathematical control as an input to a detector, perform the following:

1. Check the box next to Enable Setpoint:

2. Enter the desired value at which the control will trip.

3. Choose the options for the detector:

◦ Trigger only once - the detector will only trigger once at the setpoint during the entire
simulation.

◦ Initially activated - if this is unchecked, the detector is untriggered at the start of the
simulation and will turn on when the setpoint is reached for the first time. If this is
checked, the detector is triggered at the start and will turn off when the setpoint is
reached.

◦ Trip Direction - if this is set to Ascending the detector will trigger when the device value
is greater than the setpoint. If set to Descending, the detector will will trigger for the
opposite behavior.

Chapter 16. Control Logic 190


PyroSim - User Manual

Figure 126. The Mathematical Control Dialog.

191 Chapter 16. Control Logic


PyroSim - User Manual

Chapter 17. HVAC Systems


In PyroSim, HVAC (Heating, Ventilation, and Air Conditioning) systems are specified as networks
of ducts, nodes, and some combination of fans, aircoils, and filters.

17.1. HVAC Duct


A duct is required for any HVAC system. At a basic level, a duct represents the joining of two HVAC
Nodes.

To define an HVAC Duct:

1. On the Model menu, click New HVAC Duct.

You can now edit the duct:

17.1.1. General
Node
The names of nodes on either side of the duct (Nodes must already exist to be selected.) A
positive velocity is described as flowing from Node 1 to Node 2.

Length
By default, PyroSim estimates the length of the duct based on the straight line geometry
between the specified nodes. If for any reason this is not a sufficient representation of the
model, you may explicitly specify a fixed length for the duct.

Shape
Defines the cross-sectional shape of the duct. Used by the simulator to compute a hydraulic
diameter for predicting the flow.

Circular
The Diameter for a circular duct.

Non-Circular
Specify the cross-sectional Area and Perimeter of the duct.

17.1.2. Flow Model options


Forward Loss
The friction loss in the duct going from Node 1 to Node 2.

Chapter 17. HVAC Systems 192


PyroSim - User Manual

Reverse Loss
The friction loss in the duct going from Node 2 to Node 1.

Roughness
The absolute roughness of the duct material.

Flow Device
The type of flow device you would like to use in the duct.

Damper
A damper device sets an open/closed state for the duct. When a damper control is TRUE it
allows normal airflow. When a damper is FALSE, the duct is closed and blocks 100% of the duct
area.

Basic Fan
A basic fan represents a fan between the two nodes of the duct. Basic fans are defined on the
duct itself, rather than on a fan object, are limited to simpler use cases.

Aircoil
An aircoil represents a heat exchanger between the two nodes of the duct.

Fan
Selecting Fan as the flow device allows you to choose a defined fan object as the airflow device
between the nodes of the duct.

Activation
Specifying Activation for either a damper, a fan, or an aircoil attaches a device to set the state
of the HVAC component as active or inactive.

Volume Flow
The fixed volumetric flow rate through the duct.

Ramp up time
Used to define a custom time ramp of the duct flow rising to the Volume Flow.

Fan
Selects a defined HVAC Fan object to use as the flow device.

Flow Direction
Choose the direction of airflow. By default, air moves from Node 1 to Node 2.

193 Chapter 17. HVAC Systems


PyroSim - User Manual

Aircoil
Selects a defined HVAC Aircoil object to use as the flow device.

17.2. HVAC Node


An HVAC Node represents a either a joining of two or more HVAC Ducts, or the meeting point
between a duct and the PyroSim computational model. To create an HVAC Node:

1. On the Model menu, click Edit HVAC.

2. Click New.

3. In the Type box, select NODE.

4. Click OK.

You can now edit the node.

Filter
Select the HVAC Filter to be used at the node.

Auto
Selecting Node Type Auto tells PyroSim to predict the node type based on its interaction with
other HVAC objects.

Internal
An Internal node is one connected to only ducts. An internal node must be connected to at least
two ducts.

Ambient Endpoint
A node specified as an Ambient Endpoint is connected to at least one duct and is equivalent to
an OPEN surface.

Vent Endpoint
If you select a node as a Vent Endpoint, you can select a vent with surface type HVAC, and the
node will be the meeting point between the HVAC system and the rest of the PyroSim model.

Location
The 3D coordinates of the node. If the location is not specified, the default values of 0, 0, 0 will
be used by the simulator.

In Loss
The flow loss for gases entering the HVAC system.

Chapter 17. HVAC Systems 194


PyroSim - User Manual

Out Loss
The flow loss for gases exiting the HVAC system.

17.3. HVAC Fan


An HVAC Fan is used to generate airflow in a HVAC network. A fan is specified between two nodes
by selecting it as the Flow Device for an HVAC Duct. Note that an HVAC Fan is a class of object, and
a single fan definition can be used by any number of ducts.

To create an HVAC Fan:

1. On the Model menu, click Edit HVAC.

2. Click New.

3. In the Type box, select FAN.

4. Click OK.

Activation
Attach a control logic device to the fan.

Flow Loss
The loss through the fan when the fan is not operational.

Initial Ramp up time


2
Specify either a Tanh or a t ramp up time to the flow rate.

Maximum Flow Rate


The maximum volumetric flow rate used for the quadratic fan model.

Maximum Pressure
The maximum stall pressure of the fan used for the quadratic fan model.

Volume Flow Rate


The fixed volumetric flow of the fan.

Fan Curve
Used to specify a table of pressure drops across the fan versus the volumetric flow rates.

17.4. HVAC Filter


An HVAC Filter is used to stop gaseous species from circulating in the HVAC system. A given filter

195 Chapter 17. HVAC Systems


PyroSim - User Manual

can limit the flow of any number of valid species defined in the model. Note that an HVAC Filter is
a class of object, and a single filter definition can be referenced by any number of nodes.

To create an HVAC Filter:

1. On the Model menu, click Edit HVAC.

2. Click New.

3. In the Type box, select FILTER.

4. Click OK.

Clean Loss
The flow loss across the filter at zero loading.

Loss
The loss as function of the clean loss and the species loadings/multipliers for the filter.

Loss (Custom)
Specify a ramp loss table as a function of total loading.

Species
The tracked species to be filtered.

Efficiency
The efficiency at which the species is filtered.

Initial Loading
The loading on the filter for the given species at t = 0.

Loading Multiplier
A factor used for calculating the overall flow loss at the filter.

17.5. HVAC Aircoil


An HVAC Aircoil is a device that provides a heating or cooling element to an HVAC system. An
aircoil is specified between two nodes by selecting it as the Flow Device for an HVAC Duct. Note
that an HVAC Aircoil is a class of object, and a single aircoil definition can be used by any number
of ducts.

To create an HVAC Aircoil:

1. On the Model menu, click Edit HVAC.

Chapter 17. HVAC Systems 196


PyroSim - User Manual

2. Click New.

3. In the Type box, select AIRCOIL.

4. Click OK.

Activation
Attach a control logic device to the aircoil.

Heat Exchange Rate


A constant exchange rate between the aircoil and the air across it. A negative value
represents heat removal.

Ramp-Up Time
2
Specify either a Tanh or a t ramp up time to the heat exchange rate.

Coolant Specific Heat


The specific heat of the working fluid.

Coolant Mass Flow Rate


The mass flow rate of the working fluid.

Coolant Temperature
The inlet temperature of the working fluid.

Heat Exchanger Efficiency


A value from 0 to 1 representing the efficiency of the aircoil. A value of 1 indicates the exit
temperatures on both sides of the heat exchanger will be equal.

17.6. HVAC Vents


HVAC Vents are used to represent the junction between the HVAC system and the rest of the
computational model. See Section 8.3 for more information on using vents.

To define an HVAC Vent:

1. On the Model menu, click New Vent.

2. In the Surface box, select HVAC.

3. Click the Geometry tab. Specify the appropriate 2D geometry of the vent.

4. Click the HVAC Properties tab. If you want the flow from the vent to go in a direction not
perpendicular to the vent, click Louver. Specify the values X, Y, and Z as a vector of the
direction you would like the flow to be directed.

197 Chapter 17. HVAC Systems


PyroSim - User Manual

5. Click OK.

Chapter 17. HVAC Systems 198


PyroSim - User Manual

Chapter 18. Output Controls


In this chapter we describe the simulation output options available in PyroSim. Each of these
options is located in the Output menu.

18.1. Solid Profiles


Solid profiles measure quantities (e.g. temperature, density) as they extend into solid objects. The
output file for this measurement device will be named CHID_prof_n where CHID is the job ID and
n is the index of the solid profile. This output file contains the data necessary to create an
animated 2D chart of the quantity as it extends into the object over time. PyroSim does not
currently support displaying this output file.

To generate solid profile output, on the Output menu, click Solid Profiles.

Each solid profile requires the following parameters:

ID
The name of this solid profile entry.

X, Y, Z
The coordinates of a point on the face that will be examined by this solid profile.

ORIENT
The direction of the face that will be examined by this solid profile. To generate solid profile
output for the top of an object, this value will be Z+. This parameter prevents any ambiguity
that might result from a point that lies on two adjoining faces.

QUANTITY
The quantity that will be measured in this solid profile.

The surface to be measured must be heat-conducting. If the surface on the


NOTE specified face is not heat-conducting, FDS will issue an error and exit before
running the simulation.

18.2. 2D Slices
2D Slices or slice planes measure gas-phase data (e.g. pressure, velocity, temperature) on an axis-
aligned plane. This data can then be animated and displayed using the 3D Results (Figure 127).

199 Chapter 18. Output Controls


PyroSim - User Manual

Figure 127. A slice plane shown in the 3D Results.

To generate animated slice planes, either draw them using the drawing tools as described in
Section 9.11 or on the Output menu, click 2D Slices.

Each slice plane requires the following parameters:

XYZ Plane
The axis (X, Y, or Z) along which to place the slice plane.

Plane Value
The value along the specified axis where the plane will be placed.

Gas Phase Quantity


The quantity that this plane will measure. This list includes built-in options such as
temperature as well as dynamic options such as those based on particles.

Use Vector?
Setting this option to YES will cause FDS to generate additional flow vector data for this slice.

Cell Centered?
Whether to output cell-centered data. In this mode, each cell is filled completely by a solid

Chapter 18. Output Controls 200


PyroSim - User Manual

color representing the value of the cell at the center.

18.3. 3D Slices
3D Slices represent volumetric regions that measure gas-phase data (e.g. pressure, velocity,
temperature). This data can then be animated and displayed using the 3D Results in several
different ways, including volumetric renderings, plotting 2D slices through the data, plotting
points, or creating isosurfaces, all in the 3D Results application. Figure 128 shows a volumetric
rendering.

Figure 128. A volumetric rendering of a 3D slice shown in the 3D Results

To generate animated 3D slices, either draw them using the drawing tools as described in Section
9.14 or on the Output menu, click 3D Slices.

Each 3D slice requires the following parameters:

Min X,Y,Z
The minimum corner of the box defining the 3D slice.

201 Chapter 18. Output Controls


PyroSim - User Manual

Max X,Y,Z
The maximum corner of the box defining the 3D slice.

Gas Phase Quantity


The quantity that this region will measure. This list includes built-in options such as
temperature as well as dynamic options such as those based on particles.

Use Vector?
Setting this option to YES will cause FDS to generate additional flow vector data for this slice.

Cell Centered?
Whether to output cell-centered data.

18.4. Boundary Quantities


Boundary quantities provide a way to visualize output quantities (e.g. temperature) on the walls
of every obstruction in the simulation. This data can be animated and visualized in the 3D Results
(Figure 129). Since the data applies to all surfaces in the simulation, no geometric data needs to be
specified.

Figure 129. An example of a boundary quantity shown in the 3D Results

Chapter 18. Output Controls 202


PyroSim - User Manual

To generate boundary quantity data, on the Output menu, click Boundary Quantities. In the
Animated Boundary Quantities dialog, you can select each quantity you would like to be
available for visualization.

18.5. Isosurfaces
Isosurfaces are used to plot the three dimensional contour of gas phase quantities. This data can
be animated and visualized in the 3D Results (Figure 130).

Figure 130. An example of an isosurface shown in the 3D Results

To generate isosurface data, on the Output menu, click Isosurfaces, In the Animated Isosurfaces
dialog, you can select each quantity you would like to be available for visualization. Then you
must enter values at which to display that quantity in the Contour Values column. If you enter
more than one contour value, each value must be separated by the semi-colon character (;). Once
you have finished typing the value, press enter.

18.6. Plot3D Data


Plot3D is a standard file format and, like 3D slices, can be used to display 2D contours, vector
plots, and isosurfaces in a volumetric region the 3D Results (Figure 132). PLOT3D output is formed
of two parts: an XYZ file containing information about the structure of the mesh, and a Q file for

203 Chapter 18. Output Controls


PyroSim - User Manual

each output time. Each Q file contains data for up to five quantities. Simulations with multiple
meshes have XYZ and Q files for each mesh. The 3D Results will automatically stitch the individual
Q files together to animate the results.

Figure 131. The Plot3D Data dialog

PLOT3D data can also be used by the Pathfinder evacuation simulation software to integrate with
FDS results. To quickly select the quantities useful in Pathfinder, including the FED calculation,
click the Reset button and click Pathfinder Quantities.

Chapter 18. Output Controls 204


PyroSim - User Manual

Figure 132. An angled temperature slice through Plot3D data shown in the 3D Results

Enabling PLOT3D data in PyroSim will cause the XYZ file to be written. In previous versions of
PyroSim, it was possible to generate PLOT3D output without writing the XYZ file. While this
offered a way to save space in the simulation output, this sometimes led to errors when loading
PLOT3D output without an XYZ file. Loading an old PyroSim file that includes PLOT3D output but
is set not to write the XYZ file will cause the XYZ file settings to be ignored and the file will be
written anyway.

18.7. Statistics
Statistics output is an extension of the devices system. You can insert a statistics gathering device
and it will output data about the minimum, maximum, and average value of a particular quantity
in one or more mesh. This data can then be viewed in a 2D chart using PyroSim (Figure 133).

205 Chapter 18. Output Controls


PyroSim - User Manual

Figure 133. An example of statistic output

To generate statistics data for some region, on the Output menu, click Statistics. then click New.
Once a quantity is selected, some combination of the following options is available depending on
whether the quantity is gas or solid-phase and what units are output by the quantity:

Quantity
The quantity that will be measured. This value is set when you create the statistics entry and
cannot be modified.

Mean
Select this option to output the average value of the measured quantity over time in a mesh.

Minimum
Select this option to output the minimum value of the measured quantity over time in a mesh.

Maximum
Select this option to output the maximum value of the measured quantity over time in a mesh.

Volume Mean
This option is available for gas-phase quantities only. It is similar to "Mean," but each cell value
is weighted according to its relative size.

Chapter 18. Output Controls 206


PyroSim - User Manual

Mass Mean
This option is available for gas-phase quantities only. It is similar to "Mean," but each cell value
is weighted according to its relative mass.

Volume Integral
-3
This option is available for gas-phase quantities whose units involve m , such as heat release
rate per unit volume.

Area Integral
-2
This option is available for gas-phase quantities whose units involve m . If this option is
selected, a recording area rather than a recording volume must be defined.

Surface Integral
-2
This option is available for solid-phase quantities whose units involve m , such as heat and
mass fluxes.

Centroids
This option is available for gas-phase quantities only.

Recording Volume
This is available for gas-phase quantities as long as the Area Integral option is not selected.
This defines a volume over which the statistics will be taken.

Recording Area
This is available for gas-phase quantities if the Area Integral option is selected. This defines an
area over which the statistics will be taken.

Recording Mesh
This is available for solid-phase quantities. Select the mesh for which you would like to output
this statistical data. A proper location will automatically be chosen for the device in the FDS
output file.

The output file for measurement devices will be named CHID_devc.csv where CHID is the job ID.

When using statistics data, it is important to consider nuances of FDS’s numerical


NOTE solver. For instance, the minimum statistic is sensitive to numerical errors in the
solver during species transport and will sometimes report artificially low values.

207 Chapter 18. Output Controls


PyroSim - User Manual

Chapter 19. Running the Simulation


All aspects of running an FDS simulation can be performed through the PyroSim user interface.
This includes setting up simulation parameters, executing single- and multi-threaded simulations,
running a remote cluster simulation, and resuming previously stopped simulations.

19.1. Simulation Parameters


Before running a simulation, FDS simulation parameters should be adjusted to fit the problem.
This can include parameters such as simulation time, output quantities, environmental
parameters, conversion of angled geometry to blocks, and miscellaneous simulator values.

To edit the simulation parameters, on the Analysis menu, select Simulation Parameters.

This shows the simulation parameters dialog. The parameters are split into several categories,
with each category on another tab of the dialog.

19.1.1. Time
All time-related values can be entered on the Time tab as shown in Figure 134.

Chapter 19. Running the Simulation 208


PyroSim - User Manual

Figure 134. Time tab of the simulation parameters dialog

Start Time
A remapping of simulation time, t=0, to a different time. This is used to format the output time,
and can be useful for recreation scenarios.

End Time
The ending simulation time.

Initial Time Step


Overrides the default time step.

209 Chapter 19. Running the Simulation


PyroSim - User Manual

Do not allow time step changes


Prevents FDS from dynamically altering the time step.

Do not allow time step to exceed initial


Prevents FDS from allowing the time step to go above the initial time step.

19.1.2. Output
The Output tab provides fine-grained control of how output values are recorded.

Figure 135. Output tab of the simulation parameters dialog

Chapter 19. Running the Simulation 210


PyroSim - User Manual

Enable 3D Smoke Visualization


Whether to show smoke in the results. If enabled, the visualization can be based on various
species in the model.

Limit Text Output to 255 Columns


Limits how many columns are written to CSV output files.

Output File Write Intervals


Specifies intervals at which to write to various output files.

Limit HRR to Gas-Phase Combustion


Only the contribution from gas-phase combustion is included in the total Heat Release Rate.

19.1.3. Environment
The Environment tab enables various ambient environmental properties to be set as shown in
Figure 136

211 Chapter 19. Running the Simulation


PyroSim - User Manual

Figure 136. Environment tab of the simulation parameters dialog

A unique aspect of this tab is the specification feature for gravity. Gravity, in each of the X, Y, and Z
directions, can be defined as a ramped function. This allows users to model complex behavior of
gravity in tunnel or space applications where spatial or temporal variations in direction may
change the magnitude vector. Each ramp can be set to vary as a function of either the position
along the X direction, or time.

Chapter 19. Running the Simulation 212


PyroSim - User Manual

19.1.4. Init Regions


While the Environment tab provides control over ambient environmental conditions, different
temperatures, pressures, and mass fractions of species can be specified in various sub-regions of
the model by using Init Regions.

To create an Init Region, exit the Simulation Parameters dialog, and on the Model menu, choose
New Init Region.

This opens the Initial Region dialog as shown in Figure 137. Specify the desired temperature,
pressure, or mass fraction of species to override in the region on the General tab and enter the
volume parameters on the Geometry tab. Press OK to create the Init Region.

Figure 137. Init Region Properties

19.1.5. Wind
Wind parameters can be specified by checking Configure Wind and then clicking the Edit button.
This will open the Wind dialog as shown in Figure 138.

213 Chapter 19. Running the Simulation


PyroSim - User Manual

Figure 138. Wind dialog showing a custom wind profile

The Wind Profile tab provides control over how the wind speed and temperature develops as a
function of the elevation. There are two options available for defining the Wind Profile, Custom
and Monin-Obukhov Similarity.

The Custom Profile parameters provide fine-grained control over the initial wind speed,
direction, and velocity and temperature as a function of elevation.

Chapter 19. Running the Simulation 214


PyroSim - User Manual

Initial Wind Velocity


Can be specified using three methods.

Speed and Direction


Allows the absolute speed and direction to be specified. The direction is specified as an
angle where 0° indicates a northerly wind that blows from north to south. An angle of 90°
indicates an easterly wind that blows from east to west.

Friction Velocity (u*)


Speed is calculated by FDS using Monin-Obukhov similarity as defined in the FDS user’s
guide. Direction is explicitly stated as defined above.

UV Components
The U and V components of velocity are defined, where U corresponds to the X axis and V
corresponds to the Y axis.

Z Velocity
Allows the definition of the velocity component in the Z direction.

Speed Profile
Can be used to define the wind velocity in X,Y and Z directions as a function of Elevation.

Temperature Profile
This section defines the atmospheric temperature profile for the wind.

Ground Level
The elevation in the model where the 'Ground' plane (sea-level) is located, by default, this is
at Z=0.0.

Lapse Rate
Defines a constant rate at which the temperature increases or decreases with elevation.

Z Temperature Profile
Alternatively, a custom function can be specified for the temperature as a function of
elevation.

If the Wind Profile is set to Monin-Obukhov Similarity as shown in Figure 139, the wind profile
is specified using a set of similarity parameters as defined in the FDS User’s Guide.

215 Chapter 19. Running the Simulation


PyroSim - User Manual

Figure 139. Monin-Obukhov Similarity wind parameters

Thermal Stability
Indicates the stability of the temperature with rises in elevation. This can be set to several
predefined values or to a custom value.

Landscape
Indicates the type of terrain in the model. This can also be set to several pre-defined values or a
custom value.

Chapter 19. Running the Simulation 216


PyroSim - User Manual

Reference Height
Defines a height at which various parameters were measured, such as the wind Speed,
Friction Velocity and Scaling Potential Temperature. If the scaling potential temperature or
friction velocity are unknown, they will be calculated by FDS using the speed, reference height,
and landscape value.

The Speed Change over Time tab allows control over the wind velocity as a function of time.
While the wind profile determines the base speed at various locations and elevations in the
model, the speed change over time parameters provide multipliers that are applied to these
values to vary them over time.

The Natural Wind tab provides the ability to allow wind to develop naturally by specifying
pressure drops over distance. This may be useful for modeling transit tunnels.

19.1.6. Simulator
The Simulator tab provides control over the simulator used in FDS. Refer to the FDS User Manual
for more information on various parameters.

19.1.7. Radiation
The Radiation tab provides control over radiation parameters used in FDS. Refer to the FDS User
Manual for more information on radiation parameters.

19.1.8. Angled Geometry


PyroSim allows obstructions and holes to be drawn that are not aligned with the solution mesh
needed by FDS (Figure 143). To write the FDS input file, PyroSim must convert the objects that are
not immersed boundary obstructions to axis-aligned blocks, first. PyroSim will either do this
automatically when the FDS input file is generated, or this can be done manually for individual
objects by right-clicking the object and selecting Convert to Blocks. For more information about
immersed boundary obstructions, see FDS GEOM.

The Angled Geometry tab of the simulation parameters dialog provides default parameters that
control conversion of obstructions and holes into blocks for the FDS input file as shown in Figure
140.

If objects are converted manually through the right-click menu, a dialog with the
NOTE same conversion parameters is shown to the user that is initialized with the
values from the angled geometry tab of the simulation parameters dialog.

217 Chapter 19. Running the Simulation


PyroSim - User Manual

Figure 140. Angled Geometry tab of the simulation parameters dialog

Conversion Filtering
Controls which objects are converted into blocks.

Rasterize axis-aligned
This option forces non-GEOM objects that are axis-aligned to be rasterized.

Chapter 19. Running the Simulation 218


PyroSim - User Manual

Rasterize GEOM
Forces immersed boundary (GEOM) obstructions to be rasterized and written as OBST
records rather than GEOM records. This option is only available if FDS GEOM is enabled. See
FDS GEOM for more information.

Grouping
Controls how resulting objects are created after being converted to blocks. This is more
relevant to manual conversion of objects to blocks.

Group blocks into composite objects [default]


For each converted object (such as a wall), creates one resulting object that is a composite of
all the sub-blocks.

Create an object for each block and add to a group


Creates a new PyroSim object for each resulting block. These objects are then added to a
group representing the original object.

Block Size
Controls how large resulting blocks may be, see Merging converted blocks below.

Allow resulting blocks to span multiple mesh cells [default]


Resulting adjacent blocks with the same properties are merged into one block, vastly
reducing the number of produced blocks (Figure 141).

Force blocks to be no larger than one grid cell thick


Blocks will not be merged (Figure 142). This may create great numbers of blocks that will
take additional memory but have the advantage of being more easily deleted.

Thickening
Controls whether objects are allowed to be thin.

Allow thin obstructions [default]


Allows objects to become thin as shown in Figure 144. This may be overridden for
obstructions by turning on Thicken in the obstruction properties dialog.

Force all obstructions to be thickened


Prevents all obstructions from becoming thin (Figure 145).

NOTE FDS does not allow thin obstructions to have vents attached to them.

219 Chapter 19. Running the Simulation


PyroSim - User Manual

Merge objects with identical properties [default=true]


Allows blocks to be merged across source objects if their resulting blocks have similar
properties. For instance, if this is true and two walls are drawn with similar properties, their
converted blocks will be merged into the same group or composite object. This can further
reduce the number of resulting objects.

Separate disjoint objects [default=true]


Prevents objects’ block from being merged if their blocks do not touch.

Ignore names while merging [default=false]


Controls whether names are considered when determining whether objects are "similar."

Merging converted blocks

Figure 141. Span mesh cells Figure 142. No larger than one cell

Effect of thickening on converted blocks

Figure 143. Original wall Figure 144. Allow thin Figure 145. Thicken obstructions
obstructions

Chapter 19. Running the Simulation 220


PyroSim - User Manual

19.1.9. Misc Tab


This tab allows some miscellaneous simulation and model properties to be set.

Figure 146. Misc. tab on the Simulation Parameters dialog

Default Surface Type


This specifies the surface to apply to mesh boundaries, solid objects, and vents by default.

221 Chapter 19. Running the Simulation


PyroSim - User Manual

Force the Mixture Fraction Model (If Needed)


This detects if an output quantity is being used, such as by a device,

Texture Origin
Sets the global XYZ position of all texture origin points. See Section 7.4 for more details on
textures.

19.2. OpenMP Environment


As of FDS version 6.1, FDS added multithreading support using a library called OpenMP. OpenMP
will automatically be used to utilize multiple processing cores, if available, during the simulation
procedure. The behavior of OpenMP during an FDS simulation is not controlled by the FDS input
file, but rather by environment variables.

The OpenMP environment dialog provides a way to edit the environment variables that control
OpenMP (Figure 147). These settings are applied to the execution context created by PyroSim and
do not alter system environment variables.

Figure 147. The OpenMP Environment dialog

OpenMP Threads
Controls the OMP_NUM_THREADS variable and limits number of threads OpenMP is able to
use when running FDS in a single MPI process.

OpenMP Threads MPI


Controls the OMP_NUM_THREADS variable and limits number of threads OpenMP is able to
use when Running FDS in parallel.

OpenMP Stack
Controls the OMP_STACKSIZE variable which controls the amount of memory available to
OpenMP threads.

When left unset, OpenMP calculates a value (for example, 32-bit OpenMP uses 256M). Because the

Chapter 19. Running the Simulation 222


PyroSim - User Manual

OpenMP’s calculated value tends to cause FDS to crash with a segmentation fault, PyroSim sets
this value to 16M by default. An upper bound suggested by NIST is 200M.

Processors manufactured by Intel support a technology named Hyper Threading.


When Hyper Threading is enabled, the operating system doubles the number of
apparent processors available (e.g. a computer with 2 physical cores will appear
to have 4 processors available). Unfortunately, this causes OpenMP to use twice as
NOTE many processors as would be ideal. For computers that use Intel’s Hyper
Threading technology, the ideal setting for OpenMP Threads is the number of
physical cores available on the system (half the default value). The system Task
Manager will report only 50% CPU utilization, but the simulation should complete
faster than it would if the OpenMP Threads option were left unset.

19.2.1. OpenMP Optimization


As of FDS version 6.7.8, two separate executables are provided for optimized performance. These
are bundled as fds.exe and fds_openmp.exe, the former being optmized for single-threaded
calculations and the latter being optimized for multi-threaded calculations. PyroSim will
automatically select the correct executable if detected for the type of calculation being done.

19.3. Run FDS


Once you have created a fire model, you can run the simulation from within PyroSim. FDS actions
can be accessed from either the Analysis menu or the main toolbar, as shown in Figure 148. To
begin a simulation: on the Analysis menu, click Run FDS. or click from the main toolbar.
Simulations launched in this way can use multiple OpenMP threads, but will not use multiple MPI
processes.

By default, PyroSim will not automatically save the current model to disk unless
NOTE
indicated to do so under File→Preferences under the FDS tab.

Figure 148. The FDS Toolbar

PyroSim will create a sub-directory of the current PyroSim file to store FDS input and results. So
for instance, if the PyroSim file is named C:\pyrosim_files\switchgear.psm, the results will be
stored in C:\pyrosim_files\switchgear.

PyroSim will save a copy of the current PyroSim file into this directory and create the following
files:

223 Chapter 19. Running the Simulation


PyroSim - User Manual

FDS input file (.fds)


Contains all the data necessary to run the FDS simulation.

Views file (.views) [optional]


Contains information about the views.

Floors file (.floors)


Contains information about the floors.

PyroGeom file (.pyrogeom) [optional]


Contains detailed information about CAD objects, obstructions, and vents before they were
converted to blocks. See Section 19.8 for more information.

Smokeview INI file (.ini) [optional]


Contains initialization information for Smokeview and view information if the Views file was
not written.

GE1 file (.ge1) [optional]


Contains basic information about CAD objects, obstructions, and vents before they were
converted to blocks.

The file preferences control whether the optional files are written, see Section 2.8 for more
information.

The input files will automatically be named after the PyroSim file. With the default preferences,
for the "switchgear" example, the files would be switchgear.fds, switchgear.views,
switchgear.pyrofloors, and switchgear.pyrogeom. All result files from FDS will also be stored in this
directory.

Next, the FDS Simulation dialog shown in Figure 149 is launched. This dialog, which shows FDS
progress and messages, can be minimized and you can continue using PyroSim (and even run
additional simulations) while a simulation is running.

Chapter 19. Running the Simulation 224


PyroSim - User Manual

Figure 149. The FDS simulation dialog

Save Log
You can save the simulation log at any time by clicking this button. The log will be saved as a
text file.

Show Results
You can run the 3D Results viewer while the simulation is in progress by clicking this button.
For details on how to use the 3D Results, please consult the Results User Manual. The 3D
Results will run automatically when the simulation is finished.

Stop
Will cause PyroSim to create a .stop file that signals FDS to stop the simulation, but also write
out a checkpoint file that can be used to resume the simulation later. There is often a
significant delay between the time when you click the Stop button and when the simulation
actually terminates. This is because FDS checks for the stop file at the same rate that it updates
the progress information.

225 Chapter 19. Running the Simulation


PyroSim - User Manual

Kill
Will immediately terminate the current simulation, you can click Kill or close the dialog. You
will not be able to resume the current simulation if you kill it.

19.4. Parallel Execution


PyroSim includes support for FDS’s MPI-based multi-process execution. When running a
simulation with multiple MPI processes, all of the computation within each of the meshes can take
place independently. Assuming a simulation executes in t seconds using only one processor, the
best possible performance improvement using n processors and n meshes is a reduction to t/n
seconds.

This is also referred to as a linear performance improvement, or linear speedup.


NOTE In reality, this is not generally possible due to communications overhead and
imperfect load balancing.

To launch a simulation that uses multiple MPI processes:

• On the Analysis menu, click Run FDS Parallel.

or

• Click the down arrow next to the Run FDS button ( ) and select Run FDS Parallel.

Before running a parallel simulation, you may want to take into account some guidelines:

• Use at least as many meshes as available processors (or cores). If there are 4 available
processors and only two meshes, the additional two processors will not be used.

• Do not overlap meshes. Since information is exchanged between meshes at the edges, it is
ideal to organize meshes in such a way that they touch, but do not overlap. It is not
recommended to embed a fine mesh within a coarse mesh in an attempt to improve localized
mesh resolution. Because information is exchanged at mesh boundaries, the outer mesh will
not receive any data from the inner mesh.

• Do not allow a fire source to cross mesh boundaries. When a fire source crosses mesh
boundaries, it is not possible to maintain the same level of simulation accuracy.

For a detailed list of suggestions and information about running FDS in parallel, please consult
section 6.3.2 of the FDS Users Guide.

Chapter 19. Running the Simulation 226


PyroSim - User Manual

19.5. Cluster Execution


PyroSim supports the ability to run an FDS simulation on a network cluster using MPI. This has
similar restrictions to running a parallel simulation, in that each grid is run in a separate process.
The cluster may be composed of several computers, or nodes, and each node may have any
number of processors.

Cluster simulations have the following configuration requirements:

• PyroSim must be installed in the exact same folder on all cluster machines. This requirement
is imposed by the way MPI’s HYDRA process scheduler locates a program called pmi_proxy.exe.
It is not necessary to license PyroSim on machines that will be used only as simulation cluster
nodes.

• All PyroSim installations must be the exact same version. This ensures that the same version
of FDS is used in each location.

• The simulation folder where input and results are stored must be available to all cluster
machines via the same UNC path. The UNC path may not contain spaces.

To launch a cluster simulation within PyroSim:

• On the Analysis menu, click Run FDS Cluster.

or

• Click the down arrow next to the Run FDS button ( ) and select Run FDS Cluster.

This will launch the Cluster FDS Parameters dialog as shown in Figure 150.

227 Chapter 19. Running the Simulation


PyroSim - User Manual

Figure 150. The Cluster FDS Parameters dialog

All nodes in the cluster can be entered in the table, along with the number of processes to launch
on each node.

NOTE These nodes will be remembered the next time a cluster simulation is run.

Assigned Meshes
Previews which FDS meshes will run on each computer, which is determined by the order of
the meshes and the order of the hosts.

FDS File Location


Must be in a directory that is visible to all nodes in the cluster.

Click the OK button to begin the simulation.

All input and output files will be stored in the same directory as the specified FDS file. In addition
to the standard input files, PyroSim will also copy the appropriate FDS and MPI executables into
the FDS file’s directory. This ensures that all nodes in the cluster use the same versions of FDS and
MPI.

19.6. Cloud Execution


PyroSim supports the ability to run an FDS simulation in the cloud. PyroSim currently integrates
with CFD FEA Service’s Cloud HPC. Users can view pricing details and register for Cloud HPC on

Chapter 19. Running the Simulation 228


PyroSim - User Manual

their website.

To launch a cloud simulation within PyroSim:

• On the Analysis menu, click Run FDS Cloud.

This will launch the Cloud FDS Parameters dialog as shown in Figure 151.

Figure 151. The Cloud FDS Parameters dialog

Cloud Provider
Determines the Cloud Provider to use in running the simulation. PyroSim currently only
integrates with CFD FEA Service.

API Key
A required field that is used to authenticate with the Cloud Provider. You may locate your
private API Key on the CFD FEA profile page after you have registered.

FDS Version
Used to select the FDS version to run the simulation with. Available versions must be
compatible with both PyroSim and the Cloud Provider.

Number of vCPUs
Determines the number of Virtual CPUs to provision for the Virtual Machine in the Cloud.

229 Chapter 19. Running the Simulation


PyroSim - User Manual

Memory Options
Determines the amount of memory (GB) per Virtual CPU provisioned.

The Cloud FDS Simulation dialog, as seen in Figure 152 has a few distinct differences from the
normal FDS Simulation dialog.

Figure 152. The Cloud FDS Simulation Dialog

After a simulation is launched in the cloud, the Cloud FDS Simulation dialog will not keep track of
its status. It instead cedes to the dashboard of the Cloud Provider once the simulation has
successfully been started. The simulation will continue to run, even after you close the Cloud FDS
Simulation dialog. You may access the dashboard page for your simulation from the link provided
in the Status field on the dialog.

The behavior of the Kill and Stop buttons may change depending on your Cloud Provider. For
CFD FEA, the Kill button will wipe the simulation and not produce any results, while the Stop
button will save the simulation and its results at its current step.

Chapter 19. Running the Simulation 230


PyroSim - User Manual

Users may also find links to the dashboards for the available Cloud Providers from within
PyroSim:

• On the Analysis menu, navigate to Manage Cloud Simulations to view a list of the available
Cloud Providers.

19.7. Resuming a Simulation


If an FDS simulation has been gracefully stopped by pressing the Stop button in the simulation
dialog, it can later be resumed. To do so, on the Analysis menu, click Resume Simulation. This
will cause an additional RESTART flag to be written to the FDS input file. When FDS detects this
flag it will automatically attempt to reload the previous execution state from the hard disk and
resume where it left off. If FDS is unable to load the previous execution state, it will exit with an
error.

19.8. PyroGeom File


When PyroSim creates an FDS input file, it also outputs a PyroSim Geometry (.pyrogeom) file if
enabled in the preferences, see Section 2.8.5. This file contains information about the scene
geometry, including obstructions, vents, meshes, and other CAD data before they are converted to
blocks. This allows the Results to show a detailed, animated view of the model along with FDS
results.

Each object in this file is linked with the corresponding FDS blocks in the input file. This allows
the Results application to show and hide the detailed objects that are activated/deactivated over
time due to control logic in the FDS input file (see Chapter 16). In order to make this work
correctly, however, PyroSim must perform some additional processing on the geometry, including
the following:

1. Before converting objects into blocks, PyroSim detects which obstructions intersect holes that
have activation logic.

2. For each of these obstruction/hole pairs, PyroSim subtracts the hole from the obstruction and
creates a new obstruction that is the intersection of the original obstruction with the hole. If
the original obstruction had no control logic, the new obstruction’s control logic is the inverse
of the hole’s logic. Otherwise, the new obstruction’s control logic is the logical AND of the
original obstruction’s logic and the inverse of the hole’s logic. This causes it to appear and
disappear at the correct times.

3. Because the holes with activation logic have been pre-subtracted from the obstructions, they
are removed from the list of objects to send to FDS and will not be converted into HOLE
records.

231 Chapter 19. Running the Simulation


PyroSim - User Manual

If there are any OBST, VENT, or HOLE records in the Additional Records section of the Record View,
the following message will appear in PyroSim when writing an FDS file:

The additional records section contains OBST, VENT, and/or HOLE


records. These objects will not appear in the PyroSim Geometry file
and will prevent the geometry file from containing activation logic.

This message indicates that the PyroGeom file will no longer accurately represent FDS objects as
they are activated and deactivated. Instead, the PyroGeom objects will always be visible, and all
obstructions have all holes subtracted from them in this view (but not in the FDS input file).
Objects will no longer show and hide as they would before. Because of this, the FDS snapped
obstructions are shown by default in the Results instead of the PyroGeom file.

In order to fix this issue, the OBST, VENT, and HOLE records must be moved from the Additional
Records section into the PyroSim model. This can be accomplished by cutting the text of these
records and pasting them into the 2D or 3D model view.

Chapter 19. Running the Simulation 232


PyroSim - User Manual

Chapter 20. Post-Processing


PyroSim supports post-processing in three ways:

• Launching of PyroSim’s Results viewer,

• Launching of Smokeview from within PyroSim, and

• Time history plots of output data.

20.1. Launching Results


Results is a powerful post-processor for FDS created by Thunderhead Engineering. It allows the
user to view the FDS model along with results in 3D. For Pathfinder users, it also allows the user to
combine evacuation results in the same window. For more information, see the Results User’s
Manual located in your PyroSim install folder or under the Help menu.

By default, if you run FDS from within PyroSim, the Results Viewer will automatically be launched
at the end of the FDS run. This can be configured in the FDS Simulation dialog by checking "Show
results when finished", or by going to the FDS tab in the Preferences dialog and selecting "Run
Results when FDS simulation completes". Alternately, you can click ( ) on the Analysis toolbar to
launch the most recent results. You may also run the Results at any time by going to the Analysis
menu and selecting Run Results. This will prompt you to choose a Results file (.smv) to open.

20.2. Launching Smokeview


Smokeview is a post-processor for FDS supplied by NIST. It allows the user to view the FDS model
along with results in 3D. The user can view animated smoke, slices, Plot3D, and various other
output quantities.

If you run FDS from within PyroSim, Smokeview will not be automatically launched at the end of
the FDS run. You may run Smokeview at any time by going to the Analysis menu and selecting
Run Smokeview. This will prompt you to choose a Smokeview file to open.

20.3. Time History Results


Time history results are saved for heat detectors, thermocouples, and other fire output. After
running an FDS simulation, the most recent plots can be viewed by clicking on the FDS toolbar.
This will show a plot of thermal results. Device and control results may also be viewed by by
clicking the down-arrow and selecting the desired plot.

Not all results are supported for viewing in PyroSim. FDS output files that are known to not
display correctly in PyroSim include CHID_pressit.csv and CHID_cpu.csv. The files CHID_devc.csv,

233 Chapter 20. Post-Processing


PyroSim - User Manual

CHID_hrr.csv, and CHID_ctrl.csv are expected to work in most configurations.

Additional plots may be shown by going to the Analysis menu and choosing Plot Time History
Results. A typical heat detector plot is shown in Figure 153. The user can export the image to a
file.

Figure 153. Time History Results

20.4. Archiving Results


After running a simulation, the results may be archived along with the FDS and PyroSim input
files. To do so, on the Analysis menu, click Archive FDS Results. This will show the Archive FDS
Results dialog as shown in Figure 154.

Chapter 20. Post-Processing 234


PyroSim - User Manual

Figure 154. Archive FDS Results dialog

Archive name
Identifies the archive for later retrieval. The default name contains the name of the model
along with a date stamp.

Retain current results


If checked, the current results will remain in place and a copy will be made for the archive. If
unchecked, the current results will be deleted.

Compress to a ZIP file


if checked, the archive will be stored in a compressed ZIP file. If unchecked, the archive will be
stored as a duplicate folder of the current results.

Press OK to create the archive. The archive will be stored in the directory of the current PyroSim
file.

In order for PyroSim to remember the archive for later retrieval, the PyroSim file
NOTE
must be saved after creating the archive.

20.5. Restoring Archived Results


Once results have been archived, they can be later restored. To do so, on the Analysis menu, click
Restore FDS Results. This will show the Restore Archived Results dialog as shown in Figure 155.

235 Chapter 20. Post-Processing


PyroSim - User Manual

Figure 155. Restore Archived Results dialog

Destination directory
Indicates the folder where the results will be restored. By default, this is the results directory of
current PyroSim file.

Retain selected archive


If checked, the selected archive will be kept on disk. If it is unchecked, the selected archive will
be deleted.

Available Archives
shows a record of all archives made under the current PyroSim file. Select one of these
archives and then press the OK button to restore the archive.

Chapter 20. Post-Processing 236


PyroSim - User Manual

Chapter 21. Managing Data Libraries


Libraries of material, or other model data, can reduce errors and speed the creation of new
models. The user can import data from the library into a new model. This section describes how to
manage PyroSim libraries.

21.1. Create and Manage Your Own Libraries


You can create and manage your own libraries for data that you commonly use. A library is a
single file that can contain several categories of objects, such as Materials, Gas-phase Reactions,
and Surfaces.

To manage your library:

1. On the Model menu, click Edit Libraries.

2. Select the Category that you want to manage and move selected items from the Current
Model into the Library, Figure 156.

3. Click Save Current Library and save the library in a location and with a name that you can
access in the future.

4. Close the PyroSim Libraries dialog.

237 Chapter 21. Managing Data Libraries


PyroSim - User Manual

Figure 156. Creating a library of materials

After you have saved your library, you can load it into a new model and copy data from the
library to your model.

21.2. Use the Library Provided with PyroSim


PyroSim includes a library of reaction and material data that has been gathered from the
verification analyses provided with FDS. Each of these reactions and materials has a reference in
the Description that documents the source of the data. This library is presently quite limited, and
should be used as a starting point and not some kind of "standard" library.

It is your responsibility to verify that this data is correct and applicable to your simulation.

To import data from the PyroSim database:

1. On the Model menu, click Edit Libraries.

2. Click Load Library and open the property_library.fds file that is found in the C:\Program

Chapter 21. Managing Data Libraries 238


PyroSim - User Manual

Files\PyroSim 2022 folder.

3. In the Category box, select Gas-phase Reactions and copy appropriate reactions into your
model.

4. In the Category box, select Materials and copy the appropriate materials into your model.

5. Close the PyroSim Libraries dialog.

21.3. Import a Material or Reaction from the FDS 4


Database
First, a caution. Version 4 of FDS provided a database that included several common materials
and reactions. In version 5, the FDS developers made a conscious choice to remove material and
reaction data. Many of the materials in FDS 4 were simply examples, and they were worried that
users were applying them without using their own test or lab data as validation. In this section,
we describe how to import the FDS 4 database, however, it is your responsibility to verify that
this data is correct and applicable to your simulation.

You can convert the old FDS 4 materials and reactions for use in PyroSim 2007.

To import FDS 4 data:

1. On the File menu, click Import and select FDS File.

2. In the Open dialog, browse to Program Files/PyroSim 2007/fds folder and open the
database4.data file.

3. You will receive conversion warning messages depending on what is converted and what
properties are defined. Because of the change in material and reaction models between FDS 4
and FDS 6, you should review these carefully and edit the imported data appropriately for use
with FDS 6. You can save the warnings to a file for future reference.

4. Click OK to close the File Conversion Warnings dialog.

5. The imported materials and reactions are now available for use in PyroSim 2007.

239 Chapter 21. Managing Data Libraries


PyroSim - User Manual

Chapter 22. Advanced FDS Parameters


PyroSim tries to support FDS completely, but there are some more obscure features that might not
be found in the PyroSim user interface. For these items, PyroSim provides additional mechanisms
to allow these features through the Additional Records section of the Record View and the
Advanced tab of some dialogs.

22.1. Additional Records Section


There are times when PyroSim does not support an entire record. In this case, the record can be
entered into the Additional Records Section of the Record View as shown in Figure 157.

Figure 157. Additional Records Section

When PyroSim write the FDS input file, it copies the contents of the Additional Records Section
exactly at the beginning of the FDS file.

Because PyroSim performs no validation on text in this view, it is up to the user to ensure that the
statements are well-formed FDS statements and that they do not conflict with any records
generated by PyroSim. In addition, none of the records written in this section can be referenced

Chapter 22. Advanced FDS Parameters 240


PyroSim - User Manual

by other PyroSim objects. For instance, if a SURF record is entered in this section, it cannot be
referenced by an obstruction in the PyroSim user interface. The only way to do so would be to
write the obstruction in the Additional Records Section as well.

Some records, such as MISC, RADI, and others that occur once in the FDS input file can be entered
in the Additional Records Section even if PyroSim has generated the record already. For
instance, if PyroSim generates the record, &MISC TMPA=30.0/, you can still enter another entry for
MISC in the Additional Records Section, such as &MISC P_INF=2.0E5/. FDS will merge these MISC
records together to form &MISC P_INF=2.0E5, TMPA=30.0/.

22.2. Advanced Parameters


Sometimes PyroSim may support a record but may not support it completely. For many of these
records, including SURF, REAC, MATL, PART, TIME, DUMP, RADI, and MISC, PyroSim provides a
way to enter additional fields. For Surfaces, Materials, Reactions, and Particles, there is an
Advanced tab in the properties dialog where these additional fields may be entered, as shown in
Figure 158. To enter additional fields for TIME, DUMP, RADI, and MISC, on the Analysis menu
choose Simulation Parameters then choose the Misc. tab.

241 Chapter 22. Advanced FDS Parameters


PyroSim - User Manual

Figure 158. Additional Fields

When entering additional fields, you must specify the field name and the field value. These
additional fields will then be appended to the FDS record generated by PyroSim. As in the
Additional Records Section, PyroSim will write these fields to the file exactly as entered in the
table, so care must be taken by the user to make sure they are correct.

When PyroSim generates an FDS input file, some model objects may be ignored. PyroSim attempts
to use a system of dependencies to determine whether or not a PyroSim object needs to be written
out to the input file. Occasionally, this can lead to problems, especially when the Additional
Records section is in use. For some objects, this default behavior can be modified by specifying
that PyroSim always write the object to the input file, via the Always Write FDS Record checkbox
in the Advanced tab.

Chapter 22. Advanced FDS Parameters 242


PyroSim - User Manual

Chapter 23. Troubleshooting


23.1. How to Activate a Node-Locked License
23.1.1. Online
With the License dialog open, as shown in Figure 159, Step 1 is to click the [Online] button under
the 'License File' option. Step 2 is to paste the activation key that you received from Thunderhead
and click [OK].

Figure 159. License Activation Dialog

23.1.2. Local License file


This is similar to the Online activation, except that you will click the [Local] button instead of
"Online" and find the license file that was emailed to you from Thunderhead on your computer.

243 Chapter 23. Troubleshooting


PyroSim - User Manual

This is often in Docwnloads where you saved it from the email you received.

23.2. Floating License Server Problems


The floating license server provides an administration web service that can assist with diagnosing
many floating license problems. If the license server is installed on the local machine, the license
administration server can be accessed at the following web address:

http://localhost:5054

If the license server is installed on a remote machine, replace "localhost" with the name of the
remote machine (i.e. the host name of the floating license server).

Once you have opened the Reprise License Server Administration page, you can use the Status
commands to attempt to debug the license server problem yourself, or you can send a diagnostic
report to support@thunderheadeng.com for assistance. To generate a diagnostic report:

1. Under RLM Administration Commands, click Diagnostics

2. Click Run Diagnostics

3. Email the generated file (rlmdiag.txt) to support@thunderheadeng.com

23.3. Floating License Server Too Old, Update


Required
PyroSim 2017 and newer require and updated version of the Thunderhead License Manager. You
can download an updated license manager from the PyroSim download page:

http://www.thunderheadeng.com/pyrosim/download/

The license manager is often not installed on the same computer where PyroSim is running and
instead installed on a shared server. Please review the Floating License Manager Installation
guide for details on the install process.

In most cases, the newer version of the floating license manager will replace the previous version,
the LIC files will be retained throughout the update process, and PyroSim will authorize against
the updated server with no additional work.

23.4. Licensing/Registration Problems


If you experience trouble registering PyroSim, please contact support@thunderheadeng.com.

Chapter 23. Troubleshooting 244


PyroSim - User Manual

23.5. Video Display Problems and Crashes on Startup


PyroSim utilizes many advanced graphics card features in order to provide accelerated and
enhanced display of models.

Sometimes these graphics features combined with certain display drivers can cause display issues
or crashes on startup. The first step in these cases is to ensure you have the latest operating
system updates and graphics drivers installed. If you do and you still have display problems or
crashing on startup, you can start PyroSim in Safe Mode, which disables several graphics features.
To start in Safe Mode:

1. Open a command-prompt by opening the start menu and typing cmd. Then press Enter.

2. In the command-prompt, navigate to the PyroSim install folder by typing cd "C:\Program


Files\PyroSim 2022".

3. Start PyroSim in Safe Mode by typing pyrosim -DSafeMode.

4. If PyroSim starts up successfully, you can see which display properties were changed. Under
the File menu, click Preferences, and then click on the Rendering tab.

5. You can enable each item one at a time to see which ones caused the issue.

Disabled safe-mode properties will remain disabled the next time you run
NOTE PyroSim, even if not in Safe Mode. If you’ve re-enabled some of those options,
running in Safe Mode again will disable the options again.

If you encounter display problems or crashes, please let us know the make/model of your video
card and what video driver you are using, even if Safe Mode fixes your issues. That will help us
improve the software in future updates.

23.6. Memory for Large Models


When running large models, it is possible that an out of memory error will be encountered. If this
occurs, you can increase the default Java heap size. In our experience, the maximum size can be
specified to approximately 70% of physical memory. By default, PyroSim will specify a java heap
size of 50% of physical memory.

To specify the memory, you can either run from a command line or change the Start Menu
shortcut properties. To run from a command line, open a command window and then go to the
PyroSim installation directory (usually C:\Program Files\PyroSim 2022). Execute PyroSim on the
command line using the -JXmx argument. In this argument, the J specifies that the command will
be passed along to the Java VM, not PyroSim. For example, pyrosim -JXmx1200m will request 1200
MB of memory.

245 Chapter 23. Troubleshooting


PyroSim - User Manual

To edit the PyroSim shortcut properties . Right-click on the PyroSim icon . Select the Shortcut tab .
Edit the Target by adding a space and -JXmx1200m to the end of the Target.

A typical Target will then read C:\Program Files\PyroSim 2022\pyrosim.exe" –JXmx1200m.

23.7. Parallel Simulation (MPI) Problems


23.7.1. PyroSim Requires a Password to Run Parallel
MPI processes communicate using network protocols that are disabled by default for accounts
without passwords. In order to work, MPI must have access to a password-protected account.
Users without passwords can overcome this problem in a couple ways:

• Set a password for the account.

• Instruct MPI to authenticate using an alternate account.

To instruct MPI to authenticate using an alternate account (e.g. set to mpi_user on a computer
named aurora), you must issue a command using the console.

Microsoft Windows [Version 10.0.18363.778]


(c) 2019 Microsoft Corporation. All rights reserved.

C:\>cd "\Program Files\PyroSim {versionyear}\fds\mpi"

C:\Program Files\PyroSim {versionyear}\fds\mpi>mpiexec -remove


Account and password information removed from the Registry.

C:\Program Files\PyroSim {versionyear}\fds\mpi>mpiexec -register


account (domain\ user) [aurora\thornton]: aurora\mpi_user
password:
confirm password:
Password encrypted into the Registry.

To verify that MPI will function with the account information:

C:\Program Files\PyroSim {versionyear}\fds\mpi>mpiexec -validate


SUCCESS

23.7.2. PyroSim Repeatedly Requests a Password


PyroSim attempts to validate the MPI configuration prior to running the simulation. If this
validation fails, PyroSim assumes it was because of a password mismatch. If you know this is not

Chapter 23. Troubleshooting 246


PyroSim - User Manual

the case (e.g. you know you entered your password correctly), PyroSim may be responding
incorrectly to a different error. To diagnose this error, please run PyroSim in safe mode. The error
output should appear at the bottom of the console window. Forward this text to
<support@thunderheadeng.com> and the support staff will help resolve the problem.

23.7.3. FDS Completes Immediately with No Output


This indicates that MPI started successfully, but the FDS executable failed to run. To gather
additional information about this error, you must run the MPI executable manually from the
command prompt and observe the error output. To run the MPI executable manually, open a
console window and issue the following commands:

Microsoft Windows [Version 10.0.18363.778]


(c) 2019 Microsoft Corporation. All rights reserved.

C:\>cd "\Program Files\PyroSim {versionyear}\fds"

C:\Program Files\PyroSim {versionyear}\fds>fds

The subsequent output should resemble the start of a successful FDS run; however, in this case it
will probably contain error output. Copy this error output and email
<support@thunderheadeng.com>, the support staff will help resolve the problem.

23.8. Additional Support Resources


PyroSim has a support forum located at https://forum.thunderheadeng.com/index.php.

If you are unable to resolve your issues from the suggestions in the table, please contact
Thunderhead Engineering Email Support.

The PyroSim software is available for download at: https://www.thunderheadeng.com/pyrosim/


download

The same site provides PyroSim user manuals and example problems. Please follow the examples
to become familiar with the software.

Mail should be sent to:

Thunderhead Engineering
403 Poyntz Ave. Suite B
Manhattan, KS 66502-6081
USA

247 Chapter 23. Troubleshooting


PyroSim - User Manual

Appendix A: Opening FDS v4 and PyroSim


v2006 Files
Due to the differences between versions 4 and 5 of FDS, it is not always possible to automatically
convert legacy FDS input files and PyroSim 2006 PSM files to the new version. However, many
conversions are possible and in many cases PyroSim can completely convert old input files to the
new format.

PyroSim will begin the conversion process as a result of either of two actions:

• Opening a PSM file saved with a version of PyroSim designed to work with version 4 of FDS

• Importing an FDS input file designed to work with version 4 of FDS.

In many cases, PyroSim 2015 can import records intended for version 4 of FDS that PyroSim 2006
could not. This is because PyroSim 2015 supports a broader range of FDS features than the
previous version. Examples of previously unsupported version 4 features that can now be
imported include solid-phase thermocouples and species.

The process for converting PSM files and FDS input files is identical. PyroSim first loads the data
into a form designed to work with version 4 of FDS, then applies conversion logic to produce the
corresponding data structures designed to work with version 5 of FDS. For more information
about how the data is converted from a format suitable for version 5 of FDS to version 6 of FDS,
see Appendix B. When PyroSim encounters a record that cannot be automatically converted, a
warning message is generated. Each warning contains information about the source of the
problematic record and the action taken. Some records are simply dropped and others are
converted to default values. If a record is encountered that cannot be converted, but contained
only default values and would not have affected the simulation, that record is dropped without
issuing a warning.

Great care was taken to ensure that PyroSim generates these warnings whenever they contain
important information, but not so often that they distract from important issues. When in
question, PyroSim will err on the side of caution and generate a warning message. An example of
this warning dialog is shown in Figure 160. If no warning dialog appears, PyroSim was able to
convert the input file without encountering any compatibility issues.

Appendix A: Opening FDS v4 and PyroSim v2006 Files 248


PyroSim - User Manual

Figure 160. Example import warnings

In most cases, the following records can be converted with no additional input:

• Geometry Data (walls, holes, triangles, etc)

• Textures

• Mesh

• Floors

• Particles

PyroSim 2006 did not properly support initial droplets or particle clouds. In
NOTE PyroSim 2007 particle clouds are supported and existing particles with initial
droplets specified will now be handled correctly.

• Smoke Detectors

• Thermocouples

• Heat Detectors

• Boundary Quantity Output

• Plot3D Data

• Isosurfaces

• Slices

• Unsupported Records

249 Appendix A: Opening FDS v4 and PyroSim v2006 Files


PyroSim - User Manual

The unsupported records are copied verbatim from your previous version. Even
NOTE though some of these records may now be supported, PyroSim will not perform
any automated handling.]

A.1. Global Simulation Parameters


The following items that can be set in the Simulation Parameters dialog of PyroSim 2006 are not
supported in PyroSim 2015 and will be dropped.

• Under the Simulator tab, Incompressible Calculation (excludes heat)

• Under the Environment tab, External Temperature

• Under the Particles tab, Droplet Insert Interval

• Under the Particles tab, Max Particles per Second

All other simulation parameters will be converted to PyroSim 2015 without warnings.

In PyroSim 2015 it is possible to specify both the particle insertion interval and
the particle insertion rate on a per particle basis. These options are available in
NOTE
the Edit Particles dialog, in the Injection tab. PyroSim does not automatically
apply the global data to these fields.

A.2. Sprinklers and Pipes


All correctly specified sprinkler parameters are converted without warnings. If a sprinkler has
been assigned a massless particle, however, that sprinkler will be assigned a particle with
parameters from the make file, and a warning will be issued.

For FDS 4 sprinkler make files, PyroSim has a robust built-in parser that can handle both simple
and complex spray patterns. The only requirement is that referenced make files must exist in the
fds folder in the PyroSim install directory. PyroSim 2015 ships with the make files provided by
NIST for FDS 4. If a file uses another make file, place it in this directory before importing or
opening the file.

If there is a dry pipe delay greater than zero, PyroSim 2015 will create a single dry pipe with that
delay and attach it to all the sprinklers in the model. Note, however, that in PyroSim 2015 the
water pressure is specified per sprinkler rather than per pipe. Because of this, PyroSim will not
convert the dry pipe pressure specified in the pipe record, and a warning will be issued.

Appendix A: Opening FDS v4 and PyroSim v2006 Files 250


PyroSim - User Manual

A.3. Reactions
To convert reaction data into a form useable by version 5 of FDS, PyroSim 2015 must reverse-
engineer the fuel molecule composition based on stoichiometric coefficients. To accomplish this,
PyroSim uses the equations given in section 4.4.2 of the users guide for version 4 of FDS. The
result is then checked to ensure that the total molecular weight is the same as the specified
molecular weight. If this check succeeds, no warning will be issued. If the test fails, PyroSim will
issue a "Converted stoichiometry" warning and you must manually update reaction data to ensure
accurate simulation results.

A.4. Surfaces
Some surface properties are converted with no additional input or warnings, including surface
names, colors, and textures. The different surface types, however, undergo more complicated
conversions. The following describes how PyroSim 2006 surface types are converted to Surfaces
and Materials in PyroSim 2015:

• Inert and Adiabatic - converted directly.

• Burner Fire - converted to a Burner Surface.

• Fan/Wind - converted to a Supply surface if the air flow is negative, an Exhaust surface,
otherwise.

• Flammable Solid of Fixed Temperature or Heat Flux - converted to a Heater/Cooler surface.

• Thermally Thick/Thin Flammable Solid - converted to a Layered Surface with one single-step
reacting Material.

• Flammable Solid (Constant HRR) of Fixed Temperature or Heat Flux - converted to a burner.

• Thermally Thick/Thin Flammable Solid (Constant HRR) - converted to a Layered Surface with
one non-reacting Material. The reaction is controlled at the surface.

• Non-Flammable Solid of Fixed Temperature or Heat Flux - converted to a Heater/Cooler.

• Thermally Thick/Thin Non-Flammable Solid - converted to a Layered Surface with one non-
reacting Material.

• Liquid Fuel - converted to a Layered Surface with one Liquid Fuel Material.

• Charring Fuel - converted to a Layered Surface with one layer. The layer is composed of a
water and a virgin material. The virgin material undergoes one reaction where half of it is
converted to fuel and the other half is converted to the charring material specified in the
original surface. This ratio may need to be adjusted after conversion.

• Liquid Thermoplastic - converted to a Layered Surface with one Liquid Fuel Material.

• Charring Thermoplastic - converted to a Layered Surface with one single-step reacting

251 Appendix A: Opening FDS v4 and PyroSim v2006 Files


PyroSim - User Manual

Material.

A.5. Thermally Thin Surfaces


Unlike PyroSim 2006, PyroSim 2015 requires that every layered surface specify a thickness [stem
38f1e2a089e53d5c990a82f284948953] for each layer and that materials specify density [stem
6dec54c48a0438a5fcde6053bdb9d712], specific heat, and conductivity [stem
9b325b9e31e85137d1de765f43c0f8bc]. In PyroSim 2006, there were a number of ways for
thermally thin surfaces to either specify or omit these parameters. These surfaces allowed any
one or more of [stem 9b325b9e31e85137d1de765f43c0f8bc], [stem
38f1e2a089e53d5c990a82f284948953], and [stem 6dec54c48a0438a5fcde6053bdb9d712] to be
specified in addition to [stem 0c593e7fb35ac3261672a8219c5b1e8c]. PyroSim 2015 will make a
best-effort calculation of missing parameters. For instance, if [stem
0c593e7fb35ac3261672a8219c5b1e8c] is specified along with two of the parameters, the third will
be calculated; however, if more than one parameter is missing, PyroSim will use defaults for up to
two of the parameters and calculate the third missing one. The default thickness for thermally
thin surfaces is set to 1mm. In all cases where a default number has been assumed due to a
missing parameter, a warning will be shown for the parameter.

A.6. Where is the Surface Database?


PyroSim 2015 does not currently ship with a surface database, but users can still make their own.
In fact, many different objects can now be put into a database including materials and surfaces,
species, reactions, particles, and several more. As common surface descriptions and other of these
object properties become available from reliable sources in a format supported by version 5 of
FDS, PyroSim will again ship with a pre-filled database.

Appendix A: Opening FDS v4 and PyroSim v2006 Files 252


PyroSim - User Manual

Appendix B: Opening FDS v5 and PyroSim


v2012 Files
Due to the differences between versions 5 and 6 of FDS, it is not always possible to automatically
convert legacy FDS input files and PyroSim 2012 PSM files to the new version. However, many
conversions are possible and in many cases PyroSim can completely convert old input files to the
new format.

PyroSim will begin the conversion process as a result of either of two actions: * Opening a PSM file
saved with a version of PyroSim designed to work with version 5 of FDS * Importing an FDS input
file designed to work with version 5 of FDS.

The process for converting PSM files and FDS input files is identical. PyroSim first loads the data
into a form designed to work with version 5 of FDS, then applies conversion logic to produce the
corresponding data structures designed to work with version 6 of FDS. When PyroSim encounters
a record that cannot be automatically converted, a warning message is generated. Each warning
contains information about the source of the problematic record and the action taken. Some
records are simply dropped and others are converted to default values. If a record is encountered
that cannot be converted, but contained only default values and would not have affected the
simulation, that record is dropped without issuing a warning.

Great care was taken to ensure that PyroSim generates these warnings whenever they contain
important information, but not so often that they distract from important issues. When in
question, PyroSim will err on the side of caution and generate a warning message. An example of
this warning dialog is shown in Figure 160. If no warning dialog appears, PyroSim was able to
convert the input file without encountering any compatibility issues.

In most cases, the following records can be converted with no additional input:

• Geometry Data (walls, holes, triangles, etc)

• Textures

• Mesh

• Floors

• Smoke Detectors

• Thermocouples

• Heat Detectors

• Boundary Quantity Output

• Plot3D Data

253 Appendix B: Opening FDS v5 and PyroSim v2012 Files


PyroSim - User Manual

• Isosurfaces

• Slices

• Unsupported Records

The unsupported records are copied verbatim from your previous version. Even
NOTE though some of these records may now be supported, PyroSim will not perform
any automated handling.

B.1. Global Simulation Parameters


The following items that can be set in the Simulation Parameters dialog of PyroSim 2012 are not
supported in PyroSim 2015 and will be dropped.

• Under the Simulator tab, Isothermal Calculation

• Under the Simulator tab, Include Gas Phase Flame Extinction

• Under the Simulator tab, Use Moinuddin and Li Turbulent Model

• Under the Simulator tab, Specify forced coefficient

• Under the Simulator tab, Specify horizontal coefficient

• Under the Simulator tab, Specify verticlal coefficient

• Under the Radiation tab, Use Additional Fuel Bands

All other simulation parameters will be converted to PyroSim 2015 without warnings.

B.2. Reactions
While most reaction data can be converted easily, FDS6 does add new requirements to specify a
valid reaction. Most notable is the requirement that a Fuel Species by specified by the user. This
can be either a Predefined species, a User Defined species, or a Default species. When the
Default species type is used, a generic, non-editable species called REAC_FUEL is added to the list of
species. This species can be used the same way any other species would be, but its fields cannot be
edited. All reactions defined in PyroSim 2012 or older automatically use the Default fuel type.

It should also be noted that in FDS6 based PyroSim versions, it is required that a reaction be active
in order to simulate a fire. To make this transition easier, PyroSim automatically adds a reaction
called PROPANE_REAC when converting PyroSim files that do not specify a reaction. The PROPANE_REAC
attempts to mimic the default propane reaction that is used in FDS5.

The following items will be dropped from the Reaction record:

Appendix B: Opening FDS v5 and PyroSim v2012 Files 254


PyroSim - User Manual

• Under the Fuel tab, Mass Fraction of Fuel in Burner

• Under the Fuel tab, Other atoms

• Under the Fuel tab, Molecular Weight

• Under the Fire Suppression tab, Limiting Oxygen Index

• Under the Heat Release Rate tab, Use Eddy Dissipation model for heat release rate

• Under the Heat Release Rate tab, C (C_EDC)

• Under the Byproducts tab, Hydrogen Fraction

• Under the Soot tab, Hydrogen Fraction

• Under the Soot tab, Maximum Visibility

• Under the Soot tab, Mass Extinction Coefficient

• Under the Fuel tab, Ambient Oxygen Mass Fraction has moved to Simulation Parameters

B.3. Surfaces
Surfaces have undergone relatively few changes in from PyroSim 2012 to PyroSim 2015. However,
a number of items are no longer supported in the new version.

The following records will be dropped:

• A surface of type Fan will no longer set the FDS variable POROUS = .TRUE.

• Under the Surface Props tab, Porous

• Under the Surface Props tab, Surface Density

• Under the Air Duct tab, Enable Air Duct

• Under the Air Duct tab, Duct Path

• Under the Air Duct tab, Maximum Over-pressure

• Under the Air Leak tab, Porous

B.4. Particles
Unlike PyroSim 2006, PyroSim 2007 requires that every layered surface specify a thickness Delta
([stem 38f1e2a089e53d5c990a82f284948953]) for each layer and that materials specify density Rho
([stem 6dec54c48a0438a5fcde6053bdb9d712]), specific heat, and conductivity ([stem
9b325b9e31e85137d1de765f43c0f8bc]). In PyroSim 2006, there were a number of ways for
thermally thin surfaces to either specify or omit these parameters. These surfaces allowed any
one or more of [stem 9b325b9e31e85137d1de765f43c0f8bc], [stem

255 Appendix B: Opening FDS v5 and PyroSim v2012 Files


PyroSim - User Manual

38f1e2a089e53d5c990a82f284948953], and [stem 6dec54c48a0438a5fcde6053bdb9d712] to be


specified in addition to [stem 0c593e7fb35ac3261672a8219c5b1e8c]. PyroSim 2007 will make a
best-effort calculation of missing parameters. For instance, if [stem
0c593e7fb35ac3261672a8219c5b1e8c] is specified along with two of the parameters, the third will
be calculated; however, if more than one parameter is missing, PyroSim will use defaults for up to
two of the parameters and calculate the third missing one. The default thickness for thermally
thin surfaces is set to 1mm. In all cases where a default number has been assumed due to a
missing parameter, a warning will be shown for the parameter.

In PyroSim 2015, the interaction between particles and species has changed significantly. In
PyroSim 2012, a particle could be attributed various Thermal Properties and Fuel Properties. Most
of these variables have since been moved to the species object.

To handle converting legacy files, PyroSim 2015 generates a new species based on the Thermal /
Fuel Properties of the legacy particle. This species is then assigned under the Liquid tab of the
PyroSim 2015 particle.

The following is a list of items which are applied to the generated species:

• Under the Fuel tab, Melting Temperature

• Under the Fuel tab, Vaporization Temperature

• Under the Fuel tab, Heat of Vaporization

• Under the Fuel tab, Density

• Under the Fuel tab, Specific Heat

Some items are not convertible. The following are dropped from the record:

• Under the Fuel tab, Initial Temperature

• Under the Fuel tab, Heat of Combustion

All other items are converted properly.

Appendix B: Opening FDS v5 and PyroSim v2012 Files 256


PyroSim - User Manual

Bibliography
McGrattan, Kevin, Simo Hostikka, Randall McDermott, Jason Floyd, and Marcos Vanella. 2021. Fire
Dynamics Simulator User’s Guide, NIST Special Publication 1019. Sixth Edition. National Institute of
Standards and Technology, Gaithersburg, Maryland, USA: NIST.

257 Bibliography

You might also like