iRTUe Brochure-11.2023
iRTUe Brochure-11.2023
iRTUe Brochure-11.2023
IEC 61850
COMPLIANT
iRTUe units communicate with IEC 61850 GOOSE, allowing to extend and distribute the acquisition and
command capabilities of any master device. We offer flexible I/O board configurations to fulfill any
application requirement, making the iRTUe the perfect choice to both set-up and retrofit electrical
communication networks.
Contemporary substation automation calls for advanced I/O modules to provide modern services such as
interlocking or load shedding. These functionalities rely on state-of-the-art characteristics, which cannot be
realised with serial communication media and old protocols. For this reason, the iRTUe handles IEC 61850
GOOSE messaging (with a processing time under 3ms) for newer projects but also Modbus with events buffer
and timestamping for older substations/ master units.
They connect via double Ethernet (RJ45, ST or SC) or serial (EXP422) port and are time synchronized to ensure
optimal time accuracy. This allows the iRTUe to communicate with any other equipment in the network: for
instance RTUs, gateways, other iRTUe modules and third-party IEDs on the substation process bus.
11/2023
IEC 61850 GOOSE I IEC 61850 GOOSE II
GOOSE communication works with enhanced re- Since these systems are based on software
transmission mechanisms on a publisher/subscriber configurations rather than hardwired signal paths,
basis, allowing P2P communication between iRTUe they are more cost-effective, easily extendable and
and IEDs with a processing time under 3ms on demand reconfigurable, making them highly
(performance class P2). adaptive to changing substation configurations and
network topologies.
IEC 61850 GOOSE also features strong VLAN and pri-
ority tagging functionalities via IEEE 802.1Q to send The operational reliability of these schemes is
messages efficiently across complex physical net- significantly enhanced by GOOSE’s continuous and
works. Combined with a substation-wide Ethernet inherent supervision of the communication and the
LAN, it enables flexible and sophisticated logic message’s data integrity. With its strong IEC 61850
schemes for substation protection and automation, GOOSE capabilities, the iRTUe is the perfect I/O
such as interlocking and load shedding. extension to employ these advantages.
The diverse backgrounds of our partners and clients iRTUe addresses, in both Modbus and GOOSE, can
from all over the world have helped us gather state-of be easily configured using the side microswitches.
-the-art know-how and firsthand experience in a For GOOSE, the default multicast group is set to zero
great variety of energy applications. This joined (modifiable with iConf).
knowledge is the foundation of our optimized iRTU
family, which has a proven track record of being par-
ticularly effective and resistant for a diverse range of
applications and harsh environments belonging to
the energy industry.
As a result, the iRTU meets the requirements of ex-
tensive standards, such as IEC61850-3, IEC60870-2-1 &
IEC60255-26.
www.igrid-td.com
COMMUNICATION FEATURES
Protocols IEC 61850 GOOSE messaging or serial proprietary EXP422 MTBF 177,000h (one hundred seventy seven thousand
hours)
IEC 61850 Logical Nodes GGIO predefined (future firmware upgrades allow any SCL file)
Environmental Operating temperature : -25ºC to +70ºC
Time response under 3ms following the performance test in IEC 61850 (type 1A class P2) IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-3, IEC 60068-2-14,
IEC 60068-2-30, IEC 60068-2-38
DIGITAL INPUTS Vibration & shock test IEC 60068-2-6, IEC 60068-2-7
Isolation 2.5 kVrms Physical external dimensions: 173 x 78.4 x 137 mm (HxWxD)
IP30 enclosure with DIN Rail mounting
Activation ON when Vi>85%Vn | OFF when Vi<60%Vn | other levels upon request
Configuration simple configuration with iConf tool
Connectors MVSTBR 2,5 9 pins - grouping digital inputs in isolated blocks of 8 inputs and
one common terminal CPU 32 bits microcontroller @ 40MHz
Breaking Capacity 8A @ 220Vac – 8/0.3/0.12A @ 30/110/220Vdc DC Ranges 4-20mA (+/-20% tolerance), +/-10Vdc, with 0.15%
accuracy after calibration
EMC STANDARDS AC Ranges 1-5 A and 110Vac, with an accuracy better than
IEC 60950-1, IEC 60255-5:2000, EC 60255-22:2000, EN 55022, IEC 61000-6-4, IEC 61000-6-5,
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8,
IEC 61000-4-9, IEC 61000-4-10, IEC 61000-4-12, IEC 61000-4-16, IEC 61000-4-17, IEC 61000-4-
18, IEC 61000-4-29
ORDERING INFORMATION
iRTUe#iioovvwwwmc