Nothing Special   »   [go: up one dir, main page]

BENDER MK2430 TGH en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 84

Operating Manual

MK2430
Alarm indicator and test combination
Software version: 4.0x

TGH1389en/08.2012
Bender Inc.

USA:
700 Fox Chase
Coatesville, PA 19320
Toll Free: 800-356-4266
Phone: 610-383-9200
Fax: 610-383-7100
E-mail: info@bender.org

Canada:
5810 Ambler Drive, Unit 1
Mississauga, ON L4W 4J5
Toll Free: 800-243-2438
Phone: 905-602-9990
Fax: 905-602-9960
E-mail: info@bender-ca.com
© Bender Inc.

Web: http://www.bender.org
All rights reserved.
Content subject to change.
Table of Contents

1. How to get the most out of this manual ............................................. 7


1.1 How to use this manual ......................................................................................... 7
1.2 Explanation of symbols and notes .................................................................... 8

2. Safety instructions .................................................................................. 9


2.1 Intended use ............................................................................................................. 9
2.2 Qualified personnel .............................................................................................. 10
2.3 General safety instructions ................................................................................ 11
2.4 Delivery conditions, guarantee, warranty and liability ............................ 11

3. System description .............................................................................. 13


3.1 MEDICS® .................................................................................................................... 13
3.2 Features ..................................................................................................................... 14
3.3 Functionality ........................................................................................................... 16
3.3.1 Display/operating elements .............................................................................. 16
3.3.2 Programming .......................................................................................................... 16
3.3.3 History memory ...................................................................................................... 17
3.4 Versions ..................................................................................................................... 17
3.4.1 MK2430-12 ............................................................................................................... 17
3.4.2 MK2430-11 ............................................................................................................... 17
3.4.3 MK2430P-… ............................................................................................................. 17
3.4.4 Interfaces .................................................................................................................. 18
3.4.4.1 BMS bus ............................................................................................................. 18
3.4.4.2 USB interface ................................................................................................... 18

4. Installation and connection ............................................................... 19


4.1 Installation ............................................................................................................... 19
4.1.1 Overview of enclosures ....................................................................................... 19
4.1.2 Dimension diagram flush-mounting enclosure ......................................... 19
4.1.2.1 Flush-mounting .............................................................................................. 20

TGH1389en/08.2012 3
Table of Contents

4.1.2.2 Cavity wall and panel mounting .............................................................. 21


4.1.2.3 Mounting brackets ........................................................................................ 21
4.1.3 Dimension diagram surface-mounting enclosure .................................... 22
4.1.3.1 Installation of the surface-mounting enclosure ................................. 22
4.2 Connections ............................................................................................................. 23
4.2.1 Notes on connection ............................................................................................ 23
4.2.2 Wiring diagram ....................................................................................................... 24
4.2.3 Connection assignment ...................................................................................... 26
4.2.3.1 MK2430-12 ....................................................................................................... 26
4.2.3.2 MK2430-11 ....................................................................................................... 27
4.3 Examples for BMS bus connection and addressing .................................. 27

5. Commissioning and testing ................................................................ 33


5.1 Tests before switching on .................................................................................. 34
5.2 Tests after switching on ...................................................................................... 35
5.3 Make parameter settings .................................................................................... 35
5.3.1 Settings at the MK2430 ....................................................................................... 36
5.3.2 Settings in the software TMK-SET .................................................................... 37
5.3.3 Tests after parameter setting ........................................................................... 38
5.4 Periodic verification and service ...................................................................... 38
5.4.1 Periodic verification .............................................................................................. 38
5.4.2 Service and support .............................................................................................. 40
5.4.3 Maintenance ............................................................................................................ 41

6. Troubleshooting ................................................................................... 43
6.1 Error messages of MK2430 ................................................................................. 43
6.2 Malfunctions ............................................................................................................ 44

7. Operation ............................................................................................... 45
7.1 Operator control and display elements ........................................................ 45
7.2 Quick reference guide .......................................................................................... 47
7.2.1 Display in error-free operation ......................................................................... 47
7.2.2 Display in fault condition .................................................................................... 47
7.2.3 Test function ............................................................................................................ 49

4 TGH1389en/08.2012
Table of Contents

8. Menu mode: Operation and setting ................................................. 51


8.1 Switching on and calling up the main menu ............................................. 51
8.2 Menu overview diagram ..................................................................................... 53
8.3 Main menu functions ........................................................................................... 54
8.4 The main menu ...................................................................................................... 54
8.4.1 Back ............................................................................................................................ 54
8.4.2 Menu 2: Measured values ................................................................................... 54
8.4.3 Menu 3: History ...................................................................................................... 55
8.4.4 Menu 4: Settings .................................................................................................... 57
8.4.4.1 Back ..................................................................................................................... 58
8.4.4.2 Settings menu 2: Alarm addresses .......................................................... 58
8.4.4.3 Settings menu 3: Test addresses .............................................................. 59
8.4.4.4 Settings menu 4: Value addresses ........................................................... 60
8.4.4.5 Settings menu 5: Digital inputs (MK2430-11 only) ............................ 60
8.4.4.6 Settings menu 6: Buzzer .............................................................................. 62
8.4.4.7 Settings menu 7: Common acknowledgement .................................. 62
8.4.4.8 Settings menu 8: Clock ................................................................................ 63
8.4.4.9 Settings menu 9: Language ....................................................................... 64
8.4.4.10 Settings menu 10: Interface ....................................................................... 65
8.4.4.11 Settings menu 11: Relay .............................................................................. 66
8.4.4.12 Settings menu 12: Password ...................................................................... 67
8.4.4.13 Settings menu 13: Service menu .............................................................. 67
8.4.5 Menu 5: Control ...................................................................................................... 68
8.4.5.1 Back ..................................................................................................................... 68
8.4.5.2 Control menu 2: Reset (AlarmClear) ........................................................ 68
8.4.5.3 Control menu 3: EDS start/stop ................................................................ 69
8.4.5.4 Control menu 4: Test communication (MK2430-11 only) ............... 69
8.4.6 Menu 6: External devices .................................................................................... 70
8.4.7 Menu 7: Info ............................................................................................................. 71
8.5 Overview of setting options .............................................................................. 71

TGH1389en/08.2012 5
Table of Contents

9. Technical data ........................................................................................ 73


9.1 Technical data ......................................................................................................... 73
9.1.1 Standards .................................................................................................................. 76
9.2 Ordering information ........................................................................................... 76

INDEX ............................................................................................................ 79

6 TGH1389en/08.2012
1. How to get the most out of this manual

1.1 How to use this manual


This operating manual describes the currently applicable software version of the
MK2430 alarm indicator and test combination. The functions and processes described
may vary from those featured in other versions. It is designed for skilled persons
working in electronics and electrical engineering and in particular for those designing,
installing and operating electrical equipment in the medical sector.

Chapter 7. "Operation" on page 45 can also be used as a quick reference guide by


medical personnel.

Before using the equipment, please read this operating manual, the supplement
entitled “Important safety instructions for Bender Products" and the instruction leaflets
supplied with the individual system components. This document must be kept in an
easily accessible location near to the equipment.

Should you have any further questions, please contact our Technical Sales Department.
We are also happy to provide on-site service. Please contact our Service Department for
more information.

Although great care has been taken in the drafting of this operating manual,. it may
nevertheless contain errors and mistakes. The Bender Group cannot accept any liability
for injury to persons or damage to property resulting from errors or mistakes in this
manual.

TGH1389en/08.2012 7
How to get the most out of this manual

1.2 Explanation of symbols and notes


The following terms and symbols are used to denote hazards and instructions in Bender
documentation:

The warning symbol indicates a potential dangerous situation


that may result in bodily injury and/or damage to property. Observe
the associated safety instructions!

This symbol indicates important information about the correct use of


the equipment purchased.
Failure to observe the associated instructions can result in equipment
malfunctioning or cause problems in the environment in which it is
being used.

This symbol indicates tips for using the equipment and particular use-
ful information. This type of information will help you to optimise
your use of the equipment.

8 TGH1389en/08.2012
2. Safety instructions

2.1 Intended use


The universal MK2430 alarm indicator and test combination is used for visual and
audible indication of operating status and alarm messages from Bender's EDS, RCMS,
ATICS® and MEDICS® systems.
In MEDICS® monitoring systems, the MK2430 meets the requirements of IEC 60364-7-
710:2002-11 and DIN VDE 0100-710:2002-11 in respect of test functions for IT system
monitoring and alarms from changeover devices. The IT system monitoring equipment
can be tested using the programmable test button.

Important display functions:


  Normal operation indicator (green LED)

  Insulation fault

  Overload

  Overtemperature

  Messages from EDS… insulation fault location systems and RCMS… residual cur-

rent monitoring systems


  Interruption of the phase conductor or PE conductor of the ISOMETER®

  Supply line failure

  Power supply fault conditions and changeover system faults

  Device failure

  Test results

  Measured values

The LC text display makes this information easy to understand. The connection
between the MKs and the changeover and monitoring modules is implemented with
bus technology. During normal operation, the MK2430 indicates the readiness for
operation of the system.
The MK2430-11 features 12 digital inputs allowing messages from other technical
equipment to be recorded and displayed on the MK2430, for example from medical
gases or additional battery supported safety power supply systems (BSV systems).

TGH1389en/08.2012 9
Safety instructions

MK2430 come into use in:


  healthcare facilities;

  industrial and office buildings;

  public buildings.

Please heed the limits of the area of application indicated in the technical specifications.
Use which deviates from or is beyond the scope of these technical specifications is
considered non-compliant.

Use for the intended purpose also includes:


  Device-specific settings compliant with local equipment and operating condi-

tions.
  The observation of all information in the operating manual.

  Compliance with test intervals.

2.2 Qualified personnel


Only appropriately qualified personnel may work on Bender devices. Personnel who are
familiar with the installation, commissioning and operation of the equipment and have
undergone appropriate training are considered skilled persons. Such personnel must
have read this operating manual and understood all instructions relating to safety.

10 TGH1389en/08.2012
Safety instructions

2.3 General safety instructions


Bender devices are designed and built in accordance with the state of the art and
accepted rules in respect of technical safety. However, the use of such devices may
introduce risks to the life and limb of the user or third parties and/or result in damage to
Bender devices or other property.
  Only use Bender equipment:

– As intended
– In perfect working order
– in compliance with the accident prevention regulations and guidelines appli-
cable at the location of use
  Eliminate all faults immediately which may endanger safety.

  Do not make any unauthorised changes and only use replacement parts and

optional accessories purchased from or recommended by the manufacturer of


the equipment. Failure to observe this requirement can result in fire, electric
shock and injury.
  Information plates must always be clearly legible. Replace damaged or illegible

plates immediately.
  Make sure that the dimension of the BSV (battery supported safety power supply),

the generator set and the whole wiring is adequate. The applicable national and
international standards must be observed here. Only in this way selective opera-
tion of safety devices can be achieved and a high degree of safety in case of over-
load and short circuit can be ensured.

2.4 Delivery conditions, guarantee, warranty and liability


The conditions of sale and delivery set out by Bender apply. Conditions of sale and
delivery can be obtained from Bender in printed or electronic format.

TGH1389en/08.2012 11
Safety instructions

12 TGH1389en/08.2012
3. System description

3.1 MEDICS®
The MK2430 alarm indicator and test combinations are integral components of the
MEDICS® system. MEDICS® is an intelligent system that guarantees safe power supply in
medical locations.

Example of a section of a hospital with the MEDICS® system:

TGH1389en/08.2012 13
System description

Legend to example
MK2430 Alarm indicator and test combination
RCMS Residual current monitoring system for TN-S systems
SMI472 Signal converter for third-party systems (e.g. med. gases, BSV sys-
tems)
TM Alarm indicator and operator panel
UFC107E… Changeover and monitoring module for IT systems with EDS… in-
sulation fault location system
UMC107E… Changeover and monitoring module for IT systems
UMC710D… Changeover module for main distribution boards
USC710D… Control module for changeover modules (preferably in main distri-
bution boards)

MEDICS® includes:
  Display and operating units such as TM…operator panels or MK… alarm indicator

and test combinations


  Single and three-phase monitoring modules. Examples of modules in the

MEDICS® system include UMC…, USC…, UFC… and EDS…. insulation fault loca-
tion systems
  Communication between these components via the BMS bus (two-wire connec-

tion).
  The connection of third-party technical systems by means of protocol converters

(gateways) or via digital inputs and relay outputs.


The real strength of MEDICS® is to be found in communication between all involved
components and the resulting information provided to the user. The functionality of
the equipment is continuously monitored. Operating states, irregularities, faults and
equipment failures are displayed. This means high operational reliability of the instal-
lation for the user.

3.2 Features
On its backlit LC display (4 x 20 characters), the MK2430 displays messages from all BMS
bus devices assigned via alarm addresses. As well as being used as a standalone
indicator, the MK2430 also supports parallel indication in different rooms.
In the event of an alarm message the yellow "WARNING“ LED or the red "ALARM" LED
lights up and the message appears on the LC display in plain text format. At the same
time there is an audible signal (acknowledgeable/can be switched to mute). If a second
message is received whilst the first is still pending, the audible signal will sound again

14 TGH1389en/08.2012
System description

and the messages will flash up alternately on the LC display. The address of the device
triggering the alarm can also be called up. The audible signal sounds again once a
configurable period of time has elapsed (repetition can be deactivated).

Internal device parameters (alarm addresses, test addresses,…) and the parameter
setting for EDS and RCM systems can be accessed via the menu system. As a master, the
MK2430 can also be used as master device in installations with a number of IT and EDS
systems.
The test button can be used to check the operation of the associated devices (e.g.
insulation monitoring devices, LIM (Line Isolation Monitors) or GFCI (Ground Fault
Circuit Interrupters). A message is output only on the MK2430 on which the test button
"TEST" was pressed. The test and its individual evaluations are carried out sequentially.
Once the process is complete, a message indicating that the test has been successful or
a fault message is output.

MK2430 features:
  Display of operating status, warning and alarm messages in accordance with

IEC 60364-7-710:2002-11, DIN VDE 0100-710:2002-11 and other standards


  Backlit clear LC text display (4 x 20 characters)

  Standard texts for messages in 20 languages

  200 freely programmable message texts (with TMK-SET PC software)

  Bus technology for easy installation and reduced fire load

  Audible alarm (can be acknowledged or set to mute)

  Menu-based parameter setting (German/English): MK2430 basic parameters and

EDS46x, EDS47x, EDS49x, RCMS460, RCMS470, RCMS490 via BMS bus


  Types available for flush and surface mounting

  Easy commissioning due to predefined alarm text messages

  12 Digital inputs (MK2430-11 only)

  History memory with real-time clock to store 250 warnings and alarms

  Replaces the MK2418

TGH1389en/08.2012 15
System description

3.3 Functionality
3.3.1 Display/operating elements
The backlit display features four lines of 20 characters. It supplies medical and technical
personnel with information that is always clear and unambiguous, in order to help them
to make decisions. Every alarm message comprises three lines which appear spontane-
ously and three additional lines which can be displayed at the touch of a button. The
fourth line contains status information (number of messages, test procedures, menu
information). Three LEDs are located above the text display. They indicate:
Normal operation (green), warnings (yellow) or alarms (red).
Five buttons are available for acknowledging or setting alarms to mute and warnings,
for testing the associated devices and for the menu system.

3.3.2 Programming
Standard message texts can be activated by enabling alarm addresses. These texts are
available in 20 languages. Alarm addresses can be enabled via the device menu system
(without PC). Individual message texts, each comprising 6 lines of 20 characters can be
programmed with the TMK-SET software.
An LED (yellow or red) and an audible signal can be assigned to each message. For this
purpose, the PC is connected to the USB interface or BMS bus (RS-485).

16 TGH1389en/08.2012
System description

3.3.3 History memory


Warnings and alarms are written to the history memory automatically with date and
time stamp. 250 text messages can be saved. After this, each subsequent message then
overwrites the oldest message in the history memory (message 251 will overwrite
message 1 etc.). The history memory can be read out via the operating menu or the
TMK-HISTORY PC software.

3.4 Versions
3.4.1 MK2430-12
The MK2430-12 is used for visual and audible indication of alarms from Bender's EDS,
RCMS and MEDICS® systems and for testing assigned devices (e.g. insulation monitoring
devices, LIM, GFCI). Furthermore, the MK2430-12 can also be used as parallel indication
in conjunction with MK2430-11 resp. SMI472-12. The programmed message texts are
displayed on the LCD in the selected language.

3.4.2 MK2430-11
The MK2430-11 features all the functions of the MK2430-12 plus 12 digital inputs and a
programmable relay output. All digital inputs are electrically isolated in three groups of
4. The input voltage is AC/DC 10…30 V / 2…5 mA (HIGH = 10…30 V; LOW = 0…2 V). In
practice, these digital inputs (IN1… IN12) are controlled via potential-free contacts
(N/C or N/O operation configurable). The voltage required for these inputs is provided
via the power supply unit, which also supplies power to the MK2430. Any message text
can be assigned to the inputs.

3.4.3 MK2430P-…
The MK2430P-… contains the programming of the standard display and the factory
activation of up to 20 alarm addresses. A line containing a note about the assigned
equipment can be programmed individually for each alarm address. This line appears
as the first line in an alarm.
For many applications with medical IT systems, this programming scope is sufficient. A
programming template in the shape of a form is available for customer-specific
programming.

Furthermore, up to 200 individual alarms can be programmed in the factory subject to


an additional fee. This type of programming is recommended for EDS, RCMS, medical
gases or BSV systems.

TGH1389en/08.2012 17
System description

3.4.4 Interfaces
MK2430 feature a BMS bus and USB interface.

3.4.4.1 BMS bus


The internal BMS bus is used for communication with MEDICS® components,
– e.g. modules such as UMC…, UMA…, UFA…, UFC…, LFC..
– or devices like RCMS…, EDS…, SMI…, SMO…, ATICS®, alarm indicator and
operator panels.
The MK2430 is the master whenever the address is set to 1. An address setting of 2…150
denotes operation as a slave.

The Master is responsible for specific tasks:


– As a "master clock", it synchronises the time of all devices on the internal BMS
bus
– It controls data traffic on the BMS bus.

In order to program the MK2430, a PC must be connected


– to the BMS bus either via an RS-232/RS-485 adapter
– or to a USB/RS-485 adapter.

3.4.4.2 USB interface


A PC can also be connected to the MK2430 via the USB interface with a USB cable (Type
A plug onto Type B plug). The interface can only be accessed when the MK2430 has
been removed.

Only the connected MK2430 can be read out and set via the USB interface.

Optional software
  You can use the the TMK-SET PC software to display and change the MK2430

settings.
  You can use the PC software TMK-HISTORY to read out the MK2430 history

memory.

18 TGH1389en/08.2012
4. Installation and connection

4.1 Installation
4.1.1 Overview of enclosures
– The MK2430 in flush-mounting enclosure (with a special mounting kit) also
suitable for installation in a panel or cavity wall
– MK2430A in surface-mounting enclosure

4.1.2 Dimension diagram flush-mounting enclosure

Fig. 4.1: MK2430 in flush-mounting enclosure


front panel cut-out: 161 x 77 mm

The MK2430 is mounted in its enclosure by means of clips. In addi-


tion, the MK2430 can be secured in its enclosure with screws. For this
purpose, markings for the drilling holes are prepared at the rear of
the front plate: drilling hole: 3 mm ∅ , counterboring: 6 mm ∅).

TGH1389en/08.2012 19
Installation and connection

4.1.2.1 Flush-mounting
The flush-mounting enclosure is already enclosed in the scope of delivery of MK2430.
1. Insert the supplied cardboard into the flush-mounting enclosure to improve
the shape stability and to provide protection against pollution.
2. Insert the enclosure so that it is flush with the wall surface.

1 2

The flush-mounting enclosure must not be installed lopsidedly or warped, and must
not be installed too deep below the surface.

20 TGH1389en/08.2012
Installation and connection

4.1.2.2 Cavity wall and panel mounting


For cavity wall or panel mounting you will need a "Complete mounting kit" (Art. No.
B95101000).

9...50 mm 2...50 mm

Cavity wall mounting Panel mounting

4.1.2.3 Mounting brackets


Use the laterally attached mounting clips to snap the MK2430 into the flush-mounting
enclosure. Two mounting brackets (M) are used for additional support. They are needed in
particular if the MK2430 is to be fixed into an existing flush-mounting enclosure (e.g.
MK2418) which is not intended for snap-on mounting. This requires "Complete mounting
kit" (Art. No. B95101000)“.

TGH1389en/08.2012 21
Installation and connection

4.1.3 Dimension diagram surface-mounting enclosure

MK2430A MK2430

Fig. 4.2: MK2430 in surface-mounting enclosure

4.1.3.1 Installation of the surface-mounting enclosure

A smooth and even surface is a precondition for installation. Only


use fastening screws of the size specified below. Failure to observe
this can result in deformation or damage to the enclosure.

  Use the empty enclosure as a template for marking the drilling holes
  Maximum diameter of the screws:
Thread of screw 3 mm, bolt head 7 mm

22 TGH1389en/08.2012
Installation and connection

4.2 Connections
Risk of electric shock!
Before fitting the enclosure and working on the device connections,
make sure that the power supply has been disconnected and the sys-
tem is dead.
Failure to comply with this requirement will expose personnel to the
risk of electric shock. Furthermore, the electrical installation may sus-
tain damage and the device may be destroyed beyond repair.
You must only connect the MK2430 as illustrated in the diagram in
this chapter. Do not make any changes to the internal wiring.
Non-compliant connection or arbitrary changes can lead to serious
malfunctions or even the complete failure of the MK2430.
The device contains components that can be damaged by electro-
static discharges (ESD). When work activities are carried out at the
opened device, the safety precautions for the dissipation of electro-
static electricity have to be observed..

4.2.1 Notes on connection


  Connect the MK2430 to the supply voltage (terminals U2/V2).

– If you are connecting the MK2430 to a DC 24 V supply: take the line voltage
drop into account if you are using long supply cables for the supply voltage.
– Consider the maximum permissible cable lengths for the supply voltage U2/V2
when using an AN450 or AN410 power supply unit (refer to "Technical data" ).
  The connection to the internal BMS bus is made via the terminals A/B. Connect

the BMS bus as described on the "BMS bus" instruction leaflet. Use a shielded
cable of at least mm or 0.8 mm cross section for the interface line (e.g. J-Y(St)Y n x
2 x 0.8). Connect the shield to PE at one end. When wiring the bus connection,
please note that a 4-wire cable (2 x BUS, 2 x US) with suitable cross section is
required when routing the supply voltage Us.
  Set the terminating resistor for the BMS bus on the "Term" DIP switch. Factory set-

ting: off.
  MK2430-11 only: Use cables with a cross section of at least 0.75 mm
2 when con-

necting the digital inputs and the relay output. The maximum cable length per
connection is 500 m.

TGH1389en/08.2012 23
Installation and connection

4.2.2 Wiring diagram

6
7
1

56
4

3
isoMED. . .
2

ATICS. . .
1

24 TGH1389en/08.2012
Installation and connection

Legend to wiring diagram

Terminating resistor:
If two or more devices are connected to each other via the BMS bus, each bus
1 line must be terminated with a resistor (R = 120 Ω) at the start and end of the
BMS bus (can be connected via DIP switch on the MK2430 and alarm indicator
and operator panel.

BMS bus connection:


A variety of Bender devices with a BMS bus can be connected to the BMS bus.
2
These may include: 107TD47 insulation monitoring devices, PRC487 control
devices, RCMS470 residual current evaluators and many more.

Power supply unit in the MEDICS® module, sufficient for supplying power to at
3
least three MK2430.

Cable between the MEDICS® module and MK2430. Please observe the permissi-
4 ble cable lengths and cross sections when using the AN450 power supply unit
in MEDICS® modules.

Digital inputs. The digital inputs may be controlled either via internal or exter-
nal voltage or potential-free contacts. If the inputs are controlled via an exter-
5 nal voltage, the common 0(-) is applied to terminal "0" and the 1(+) signal to
the relevant input IN1 … IN12. In this case, the connections between the termi-
nals 0 and V2 and the common connections and U2 are not required.

USB interface. For PC connection. The TMK-SET PC software is used to pro-


6 gramme the MK2430. You can use the PC software TMK-HISTORY to read out
the MK2430 history memory.

MK2430-11 only: Relay output. Programmable contact for device errors, test of
7
assigned devices*, device failure and common alarm message.

* Devices without BMS bus connection, but with test input (e.g. ISOMETER®)

TGH1389en/08.2012 25
Installation and connection

4.2.3 Connection assignment


The connections are located on the rear of the devices.

4.2.3.1 MK2430-12
The MK2430-12 features a single terminal strip as it receives all messages via the BMS
bus. It receives these messages for example from the 107TD47, an MK2430-11, the
signal converter SMI47x, the EDS… or the RCMS…

Supply voltage US :
looped through connection for the supply voltage US. Note:.
U2, V2 Note: Make sure that the power supply of MK2430 is isolated against PE. If
this is not taken into consideration and if a PC is connected to the USB
interface, the MK 2430 device and the PC may sustain damage

USB USB connection. Cable: Type A plug on type B plug.

S BMS bus and USB interface shield.

A, B BMS bus

Term BMS bus terminating resistor, switchable

26 TGH1389en/08.2012
Installation and connection

4.2.3.2 MK2430-11
The MK2430-11 alarm indicator and test combination provides additional terminal
strips for the 12 digital inputs and one optional relay output.

IN1…IN12 Digital inputs 1…12

0 (IN1…4) Common connection"0" for the digital inputs 1…4

0 (IN5…8) Common connection"0" for the digital inputs 5…8

0 (IN9…12) Common connection"0" for the digital inputs 9…12

21, 22, 24 Relay output (option)

NC no function (not connected)

Also refer to “Settings menu 5: Digital inputs (MK2430-11 only)” auf Seite 60.

4.3 Examples for BMS bus connection and addressing

Missing or incorrectly installed terminating resistors (e.g. in the mid-


dle of the bus) will cause bus instability. Please also note the informa-
tion on the "BMS-Bus" operating manual.

TGH1389en/08.2012 27
Installation and connection

Example 1: Operating theatre or intensive care unit with two IT systems and
three rooms

med. gases
Device Parameters Address settings

First changeover and monitoring module UMC107E

107TD47 Bus address 3

PRC487 Bus address 4

Second changeover and monitoring module UMC107E

107TD47 Bus address 5

PRC487 Bus address 6

Alarm indicator and test combinations


Bus address 1
First
Test address 3, 5
MK2430…
Alarm address 2, 3, 4, 5, 6, 7
Bus address 2
Second
Test address 3, 5
MK2430…
Alarm address 1, 3, 4, 5, 6, 7
Bus address 7
Third
Test address 3, 5
MK2430…
Alarm address 1, 2, 3, 4, 5, 6

28 TGH1389en/08.2012
Installation and connection

Example 2: Intensive care unit with two IT systems and four rooms

UFC107E UFC107E

107TD47 107TD47 MK MK MK MK
PRC487 PRC487 2430 2430 2430 2430
PGH474 PGH474
EDS474 EDS474

Device Parameters Address settings

First UFC107E switchover and monitoring module

107TD47 Bus address 3

PRC487 Bus address 4

PGH474 Bus address 111

EDS474-12 Bus address 61

Second UFC107E switchover and monitoring module

107TD47 Bus address 5

PRC487 Bus address 6

PGH474 Bus address 112

EDS474-12 Bus address 62

Alarm indicator and test combinations


Bus address 1
First
Test address 3, 5
MK2430…
Alarm address 2, 3, 4, 5, 6, 7, 8, 61, 62, 111, 112

TGH1389en/08.2012 29
Installation and connection

Device Parameters Address settings


Bus address 2
Second
Test address 3, 5
MK2430…
Alarm address 1, 3, 4, 5, 6, 7, 8, 61, 62, 111, 112
Bus address 7
Third
Test address 3, 5
MK2430…
Alarm address 1, 2, 3, 4, 5, 6, 8, 61, 62, 111, 112
Bus address 8
Fourth
Test address 3, 5
MK2430…
Alarm address 1, 2, 3, 4, 5, 6, 7, 61, 62, 111, 112

30 TGH1389en/08.2012
Installation and connection

Example 3: Intensive care unit with two IT systems and four rooms

„A“ „B“
ATICS ATICS
EDS151 EDS151

Device Parameters Address settings

First switchover and monitoring module

ATICS "A" Bus address 3

EDS151 "A" Bus address 4

Second switchover and monitoring module

ATICS "B" Bus address 5

EDS151 "B" Bus address 6

Alarm indicator and test combinations


Bus address 1
First MK2430… Test address 3, 5
Alarm address 2, 3, 4, 5, 6, 7, 8
Bus address 2
Second
Test address 3, 5
MK2430…
Alarm address 1, 3, 4, 5, 6, 7, 8
Bus address 7
Third
Test address 3, 5
MK2430…
Alarm address 1, 2, 3, 4, 5, 6, 8
Bus address 8
Fourth
Test address 3, 5
MK2430…
Alarm address 1, 2, 3, 4, 5, 6, 7

TGH1389en/08.2012 31
Installation and connection

Example 4: System with 3 RCMS, one MK2430 and one MK800

messages
up to 16
Device Parameters Address settings

Residual current evaluators

1. RCMS460 Bus address 3

2. RCMS460 Bus address 4

3. RCMS460 Bus address 5

Alarm indicator and test combinations


Bus address 2
MK2430… Test address -
Alarm address 1, 3, 4, 5
Bus address 1
MK800… Test address -
Alarm address 2, 3, 4, 5,

32 TGH1389en/08.2012
5. Commissioning and testing
Accomplish start-up according to the following start-up patterns:
1. Tests before switching on
2. Tests after switching on
3. Make parameter settings
– Settings at the MK2430
– Settings in the software TMK-SET
4. Tests after parameter setting

Please note down all settings and attach these to the equipment or
installation documentation.

TGH1389en/08.2012 33
Commissioning and testing

5.1 Tests before switching on

Does the supply voltage no Provide the appropriate


match the information on operating voltage.
the MK2430 nameplate?
yes
no
Is the supply voltage Connect the supply voltage
properly connected? properly.
yes
no
Is the BMS bus properly Connect the BMS bus
connected? properly and check polarity
yes of the terminals A/B!
no
Are terminating resistors Install the terminating
built-in correctly at the resistors properly or switch
beginning and end of the them on (use the DIP switch
BMS bus and switched on? at MK2430 "Term" on/off)
yes
no
MK2430-11 only: Do the Make corrections
digital inputs have the
appropriate voltage?
yes
no
MK2430-11 only: Are the Make corrections
digital inputs connected
properly?
yes
no
Are the other devices Make corrections
connected correctly?
yes
no
Are the addresses on all Make corrections, possibly
devices correctly set you first have to switch
according to the plan? supply voltage on.
yes
no
Are the rules specified in Make corrections
the "BMS bus" instruction
leaflet adhered to ?
yes
no
Are all devices in the Update the respective
system up to date? device.
yes
Switch voltage supply on.
Then proceed with "tests
after switching on"."

34 TGH1389en/08.2012
Commissioning and testing

5.2 Tests after switching on

Check the supply voltage no Make corrections. If


of MK2430 (terminals U2, required, connect another
V2). Voltage OK? or different power supply
unit for MK2430 supply.
yes
Fix the MK2430 to the
enclosure.

no Did the supply voltage or


Does anything appear on
the MK2430 display? the MK2430 fail?- Remove
the fault.
yes
Does the MK2430 display yes Make a note of the
a fault message? message. Adapt the
indicating device to the
no system or remove the fault.
Connect a PC utilizing TMK-
SET software. Activate the no
TMK-SET function "Bus Make corrections
scanning". Are addresses
and software versions of
connected devices OK?
yes
Set MK2430 parameters

5.3 Make parameter settings

All settings can be carried out via the TMK-SET software.


Alternatively, some settings can be carried out via the MK2430 menu
(see diagrams).

TGH1389en/08.2012 35
Commissioning and testing

5.3.1 Settings at the MK2430

36 TGH1389en/08.2012
Commissioning and testing

5.3.2 Settings in the software TMK-SET

BSV

TGH1389en/08.2012 37
Commissioning and testing

5.3.3 Tests after parameter setting

no
Select "Test mode" from the make corrections
menu "External devices".
Are all external device
settings OK?
yes
no
Simulate fault messages make corrections
(e.g. device failure,
insulation fault). Generate
a fault directly or select the
"Test communication"
function. Is the fault
correctly signalled by the
MK2430?

no
Does the MK2430 react make corrections
properly to signals at the
digital inputs?
yes
MK2430 is ready for
operation.

5.4 Periodic verification and service


5.4.1 Periodic verification
The following periodic verification must be performed on electrical installations in com-
pliance with the local or national regulations that apply. We recommend for your
Bender products:

38 TGH1389en/08.2012
Commissioning and testing

To be
Test performed Interval
by
Functional test of the IT system monitoring (insulation, load cur- Once
rent, transformer temperature and connection monitoring) by Medical every
pressing the "TEST" button on the alarm indicator and test combi- personnel working
nation or on the alarm indicator and operator panel day
Functional test of the changeover module*:
Electrically
Functional test of the automatic changeover modules. Every six
skilled per-
Please observe the information in the chapter "Testing the change- months
son
over module" (operating manual of the changeover module)!
Functional test of the IT system monitoring (insulation, load cur- Electrically
Every six
rent, transformer temperature and connection monitoring) on the skilled per-
months
insulation monitoring device son
Electrically
Every 12
Checking the setting values and changeover periods skilled per-
months
son
Test the transfer switching device, the IT system monitoring, and Bender Every 24
the connection to the SCADA system (Supervisory Control and Data Service months
Acquisition) (if applicable) and the interaction between the compo-
nents on the system.
The test encompasses the following:
- Inspection: Marking, display elements, mechanical components,
wiring, parameterisation, connection of third-party systems, eval-
uation of fault memory
- Measurement: Internal/external supply voltages/potentials,
bus voltage, bus protocol, bus scan
- Testing: Device function, device communication
- Documentation: Test results, recommendations for eliminating
defects
* This test must only be performed by an electrically skilled person who has been appoint-
ed to do so in agreement with the medical locations concerned.

Before carrying out the tests, please refer to the instructions relating to the functional tests
in the check list. If no national directives apply, you should perform the tests recommended
by IEC 60364-7-710 :2002-11, section 710.62 and DIN VDE 0100-710 (VDE 0100 Part 710):
2002-11, section 710.62.

TGH1389en/08.2012 39
Commissioning and testing

5.4.2 Service and support


Bender would be delighted to provide service for commissioning, troubleshooting and
periodic verification:

First Level Support


Technical support by phone or e-mail for all Bender products
  All questions about customer applications

  Commissioning

  Troubleshooting

Tel.: +49 6401 807-760*


Fax: +49 6401 807-259
only available in Germany: 0700BenderHelp (Tel. and Fax)
E-mail: support@bender-service.com

Repair Service
Repair, calibration, update and replacement service for all Bender products
  Repair, calibration, testing and analysing Bender products

  Hardware and software update for Bender devices

  Delivery of replacement devices for faulty or incorrectly delivered Bender devices

  Extended warranty for Bender devices with in-house repair service resp. replace-

ment devices at no extra cost

Tel.: +49 6401 807-780** (technical issues)


+49 6401 807-784**, -785** (commercial matters)
Fax: +49 6401 807-789
E-mail: repair@bender-service.com

Please send the devices for repair to the following address:


Bender GmbH, Repair Service, Londorfer Strasse 65, 35305 Gruenberg, Germany

40 TGH1389en/08.2012
Commissioning and testing

Field Service
On-site service for all Bender products
  Commissioning, parameter setting, maintenance, trouble shooting for Bender

products
  Analysis of the electrical installation in the building (power quality test, EMC test,

thermography)
  Practical training courses for customers

Tel.: +49 6401 807-752**, -762 **(technical issues)


+49 6401 807-753** (commercial matters)
Fax: +49 6401 807-759
E-mail: fieldservice@bender-service.com

*Available from 7.00 a.m. to 8.00 p.m.on 365 days of the year (CET/UTC+1)
**Mo-Thu 7.00 a.m. - 8.00 p.m., Fr 7.00 a.m. - 13.00 p.m

Internet: www.bender-de.com

5.4.3 Maintenance
MK2430 does not contain any parts that require maintenance. Despite this, the intervals
specified for periodic verification should be adhered to.

TGH1389en/08.2012 41
Commissioning and testing

42 TGH1389en/08.2012
6. Troubleshooting

6.1 Error messages of MK2430


The following errors are recognised by the MK2430 and indicated on the display. In
addition, the buzzer emits a beep code every 10 seconds corresponding to the number
of the error.
MK2430..-11 only: "Settings menu 11: Relay": if the function "device error" has been set,
also the alarm relay switches.
No. Displays Description Actions
1 DISPLAY ERROR Display defective Replace the MK2430*
switch off the device for 10
minutes, switch on again; if
2 I2C-BUS ERROR(X) Fault I2C bus unsuccessful: Replace the
MK2430*
3 RTC ERROR Clock chip defective Replace the MK2430*
Replace memory chip D15
4 FLASH ERROR Assignment chip defective
(socketed) or replace MK2430*
Address of the MK2430 on the
Change the MK2430 address in
5 Address ERROR (XXX) internal BNS bus is already in
the menu
use (XXX = current address)
More than 80 alarm messages
6 Overflow ERROR (03) Reduce number of messages
are present at the same time
More than 200 device failure
Overflow ERROR (05) Reduce number of messages
messages are present
More than 99 text messages
Overflow ERROR (07) Reduce number of messages
are present
Automatic correction of the
history memory is carried out
Overflow ERROR (08) none
because of voltage interrup-
tion.
Make a note of the error code
Overflow ERROR (11) Stack Error and
contact Bender Service.
7 Checksum ERROR Program memory defective Replace the MK2430*
* Please make a note of the cause of error, the error number and if applicable the error
code. This information facilitates the diagnosis and repair of the equipment.
X Error code

TGH1389en/08.2012 43
Troubleshooting

6.2 Malfunctions
List of possible errors and proposals for the correction of the faults. This error list does
not claim to be exhaustive.
Possible error codes occurring during a test are listed in the chapter "Test function" on
page 49f.

Errors Possible cause / Actions

MK2430 display blank Check AC/DC 24 V power supply.

Display is lit up
Replace the MK2430
but no characters on the screen.

Function buttons not working. Replace the MK2430

LEDs not working Replace the MK2430

Character matrix visible on display,


Processor does not start; replace MK2430
but firmware does not start.

Time of day gets lost in case of short-


Replace the MK2430
term voltage failure.

MK2430 address not properly set (menu); MK2430


Error during transfer of the assign-
address does not match setting of TMK-SET configu-
ments or basic settings via the USB
ration software; USB cable defective; wrong serial
interface.
interface (com port) set in TMK-SET.

Device addresses not properly set on the internal


bus; interface cables A/B mixed up; network incor-
Error on internal BMS bus.
rectly terminated or not at all; incorrect parameter
setting with TMK-SET.

Digital inputs not correctly set with TMK-SET. Defec-


Error relating function of digital
tive connection (does not match pre-assignment).
inputs.
Incorrect setting "neutral/medical".

44 TGH1389en/08.2012
7. Operation
This chapter can also be used as a quick reference guide by medical operating
personnel.

7.1 Operator control and display elements

2
1 3

5 8
6
9
7

LED and LCD

LED "NORMAL": Power On indicator, green (only lights up if no warnings or alarms


1
are pending)

2 LED "WARNING": Warnings, yellow

3 LED "ALARM": Alarm messages, red

4 LCD: Display of operating status and alarm messages as well as menu functions

TGH1389en/08.2012 45
Operation

The buttons have the following functions:

No. In operating mode In menu mode

"ESC" button
"Mute" button Exit function (without saving)
5 Set buzzer to mute following alarm / resp. go up one menu level.
acknowledge alarm When the buzzer is sounding, you can
press ESC to set it to mute.

Button " " (additional text) Down button "▼"


6 Switch between display text and possi-
Down in menu
ble additional text for message

Scroll button " "


7 Scroll through the warnings and alarms Up button "▲"
if there is more than one message pend- Up in the menu
ing

"TEST" button
Press and release: LED test
8 Press and hold down: Initiate testing of No function
assigned devices (insulation monitoring
devices, LIM, GFCI)

"MENU" button
Starts menu mode in order to make "ENTER" button "↵"
9
MK2430 settings; Confirm menu option selection
for display and control functions

46 TGH1389en/08.2012
Operation

7.2 Quick reference guide


The following images have been provided by way of example only.

7.2.1 Display in error-free operation


There are no warnings or alarms pending.
  The green "Normal" LED is lit.

  The programmed standard information appears on the LC display.

  A maximum of 3 measuring values can be indicated in the lines 1…3.

Power supply:OK
Med. gases: OK

09:50

– Line 1…3: user-definable standard display text


– Line 4 status bar, indicates the time of day (can be switched off)

7.2.2 Display in fault condition


A warning or an alarm message is pending.
  Depending on the type of fault, either the yellow LED "Warning" or the red LED

"Alarm" will light up. The green LED "Normal" goes out.
  The buzzer sounds at the same time. If the cause of the message cannot be reme-

died immediately, the buzzer can be deactivated by pressing "Mute" ( 5).


  Information about the message appears on the LC display.

Intensive care unit 03


Insulation fault
Measured value 43 kΩ
xx/yy zzz 09:50

– Line 1: Standard display: "System"


User-defined text here: "Intensive care unit 03"
– Line 2…3: message text, may contain measured value

TGH1389en/08.2012 47
Operation

– Line 4 Status line


xx = Consecutive number of message displayed
yy = Number of pending messages
= Message text page, in this case page 1
zzz = Insulation fault location or test in progress
(see table)
09:50 = Time of day (example)
Possible displays during insulation fault location or testing:

zzz Meaning

EDSa EDS insulation fault location in progress (automatic)

EDSp Continuous EDS insulation fault location in progress

EDSs Single-pass EDS fault location in progress

EDS insulation fault location was deactivated, the current measur-


EDS
ing sequence is still running

Test in progress. "TEST" flashes if the message on the display is asso-


TEST
ciated with the test.

noMA No MASTER

MAST Device is currently "substitute master".

  Press the " " button (6) for detailed information.

Since: 01.05.12 16:52


Device: ISOMETER
Addr/channel: 003/00
xx/yy [ ] 17:30

– Line 1: date and time the message occurred


– Line 2 device triggering the message
– Line 3: Address of the device sending the message
– Line 4 xx = consecutive number of the message displayed
yy = number of pending messages
= message text page, in this case page 2
17:30 = time of day (example)

48 TGH1389en/08.2012
Operation

The display may deviate accordingly in case of user-defined


messages.
If messages are pending and one of the arrow buttons is pressed, the
current message will appear on the display. If no further button is
pressed, this indication will be displayed for 15 seconds.

7.2.3 Test function


Press and hold down the "TEST" button for at least one second to check the function of
the assigned insulation monitoring devices (e.g. 107TD47, IRDH…), LIM (Line Isolation
Monitors) and GFCI (Ground Fault Circuit interrupters). A message is output only on the
MK2430 on which the test button "TEST" was pressed.

1.Test all devices 1.Test all devices


2.Test single device 2.Test single device
Addr.: 3 (01/02)
107TD47

1. Test all devices Test of all devices set in the "Test addresses" menu.
2. Test single device Select a device using the arrow buttons and press "↵ "
button.

During the test, the text "TEST" will appear in the status bar. "TEST" flashes if the
message on the display is associated with the test.

The assigned devices are tested one after the other. The MK2430 automatically
evaluates the messages that appear. Once the process is complete, either a common
message indicating that the test has been successful or an error message is output.

If more than one device has been tested, a separate error code will be displayed for each
device failing the test.

TGH1389en/08.2012 49
Operation

The following error codes are displayed in the event of an ISOMETER® failing the
test:
Error Meaning for the 107TD47 Meaning for the IRDH…
Note
code (hospital ISOMETER®) (Industrial ISOMETER®)
No messages received from ISO- No messages received from ISO-
0 METER® despite it confirming the METER® despite it confirming the
test command. test command.
Only insulation fault message Only insulation fault message
1 Channel 1
received received from channel 1
Only overload fault message Only insulation fault message
2 Channel 2
received received from channel 2
Only insulation fault message and Channel 1
3
overload message received and 2
Only overtemperature message
4 Channel 3
received
Only insulation fault message and
Channel 1
5 overtemperature message
and 3
received
Only overload message and over- Channel 2
6
temperature message received and 3
Unable to send test command as Unable to send test command as
14 Slave only
request not received (slave). request not received (slave).
ISOMETER® did not confirm the ISOMETER® did not confirm the
15
test (no response). test (no response).

Notes about error codes


  For MK2430 operating as "slaves" on the BMS bus, a time-out of 50 seconds is

applicable for error codes 0 and 14.


  Error code 14 is displayed if the test has been requested on a slave but the test

command cannot be sent because the MK2430 was not scanned. This can be the
case if the address gap upstream of the MK2430 is so large that the master does
not scan the MK2430 (refer to "BMS bus" operating manual). This error code is less
of an indicator that an ISOMETER® is faulty and much more of an indicator of a
fault on the BMS bus system.

50 TGH1389en/08.2012
8. Menu mode: Operation and setting

8.1 Switching on and calling up the main menu


When the MK2430 is connected to the power supply, the following information appears
on the display for approx. 3 seconds. It indicates the address and firmware version of the
device. This information can also be accessed in the "Info" menu.

MK2430-11 Addr.:001
Software 4.02 D228
Date: 02.05.12
www.bender-de.com

If the MK2430 was not supplied with voltage for several days, a long-
er time may be required for start-up (approx. 30 seconds). In this
case, time and date have to be entered again.

If there are no messages pending, the standard display will appear after the start.

SYSTEM READY!

09:50

The standard display and the message texts can be modified in the TMK-SET software.

TGH1389en/08.2012 51
Menu mode: Operation and setting

Press the "Menu" button for approximately two seconds to open the main menu.

1.Exit
2.Values
3.History
4.Settings

5.Control
6.External devices
7.Info

The following buttons are used on the main menu:


ESC Exit function or go up one menu level.

▲, ▼ Select menu items

↵ Confirm selected menu item (Enter)

If no buttons are pressed in a menu for a period of more than five


minutes, menu mode is exited automatically (exception: "test com-
munication" in the "Control" menu and "position mode" in the "Exter-
nal devices" menu).

Some menus are password-protected. Password protection is only


effective if the password has been enabled (switched on).
When an attempt is made to open one of these menus, the password
entry screen appears automatically:
Enter
password
0 0 0

Once a valid password has been entered, full access will be granted
to all menus (except the Service menu) until menu mode is exited.

52 TGH1389en/08.2012
Menu mode: Operation and setting

8.2 Menu overview diagram


The following diagram will help you to familiarise yourself with the menu:

1.Exit

2. Values

1.Exit
3.History
2.Alarm addresses

4.Settings 3.Test addresses

4.Value addresses

5.Digital inputs

6.Buzzer

7.Common reset

8.Clock

9.Language

10.Interface

11.Relay

12.Password

13.Service menu

1.Exit

2.Reset (AlarmClear)
5.Control
3.EDS Start/Stop

4.Test communication

6.External devices

7.Info

TGH1389en/08.2012 53
Menu mode: Operation and setting

8.3 Main menu functions

Menu item Mode Page

1. Back Exit menu mode

2. Measured values No function

Displays history with information about messages, acknowl-


3. History 55
edgements and associated times.

4. Settings Various settings for this MK2430 57

This menu offers various options for controlling the overall


5.Control 68
system.

Settings on the connected evaluators (e.g. EDS4xx and


6. External devices 70
RCMS4xx).

Information about the device type, the firmware version


7. Info 71
and the last time the assignments were transmitted.

8.4 The main menu


8.4.1 Back
Exits menu mode.

1.Exit
2.Values
3.History
4.Settings

8.4.2 Menu 2: Measured values


This menu has no function.

54 TGH1389en/08.2012
Menu mode: Operation and setting

8.4.3 Menu 3: History


The MK2430 can store up to 250 messages in the history memory (ring buffer). Once the
MK2430 reaches the limit of 250 messages, message 251 will overwrite message 1.
The "History" menu provides information about messages, acknowledgements and
associated times. It also indicates whether an alarm is still pending or when it was
acknowledged / set to mute with the " Mute" button. The complete content of the
history memory with additional texts and address of the device sending the message
can be displayed on a PC and printed out using the TMK-HISTORY software version V3
or higher. All interfaces of MK2430 can be used for connection.
1. Use the arrow buttons to select the entry you require.
The most recent entry appears first on the display. Older messages can be
selected using the arrow buttons.

Entry No.: 003/003


From: 21.05.11 16:00
Ack.: 21.05.11 16:00
To: 22.05.11 11:15

2. Press "↵ " to call up the message text for the selected entry. The path the
message took to reach MK2430 appears in the last line. In this case an insula-
tion fault was received via the internal BMS bus from address 003, channel 01.
The table on the following page contains information about other possible
displays.

System: 01
Insulation fault
Meas. value:
Address: 003/01

3. As shown in the example above, the min. and max. values display can be
called up by pressing "▲".
4. Press "↵" again to go back to the entry selection screen.

Repeat this process for all required messages. Then press "ESC" to exit the menu.

TGH1389en/08.2012 55
Menu mode: Operation and setting

Possible displays in the last line of the history memory message text display:

Text Meaning

Address: Address of the device triggering the message (aaa= device address, kk=
aaa/kk channel no. of the message)

Digital Inp
Number (kk) of digital input on this MK which triggered the message.
Nr.: kk

Note that the current history entry was created as the result of a test initi-
TESTex
ated on this MK.

Note that the current history entry was created as the result of a test and
TESTin was triggered on the device assigned to it (insulation monitoring device,
LIM, GFCI)

56 TGH1389en/08.2012
Menu mode: Operation and setting

8.4.4 Menu 4: Settings


The following menu options are available for configuring the MK2430:

Menu item Mode Page


1. Back Exit "Settings" menu; go up one menu level
2. Alarm Setting of bus addresses for devices whose alarm messages
58
addresses are to be displayed on this MK2430
Setting of bus addresses for devices which are to carry out a
3. Test addresses 59
test when the "TEST" button is pressed.
4. Measured value
No function 60
addresses
5. Digital MK2430-11 only: Setting of the operational characteristics
60
inputs of digital inputs.
Setting of the frequency and repetition rate of buzzer sig-
6. Buzzer 62
nal.
Setting whether this MK2430 should respond to a common
7. Common
acknowledgement initiated via the reset button on an exter- 62
acknowledgement
nal device
Setting of the date and time on the real-time clock on this
MK2430. At the same time this setting is sent via BMS bus
8. Clock and all other devices are synchronised. The device with 63
address 1 (MK2430 or alarm indicator and operator panel)
synchronises all other devices every hour
Selection of operating language for the MK2430 (German or
9. Language 64
English)
10. Interface Setting of the device address and baud rate for this MK2430 65
Mode of operation and function of the common alarm relay
11. Relay 66
(alarm relay) on the MK2430-11
12. Password Change password, activate/deactivate password. 67
Reserved for settings to be made by authorised Bender
Service personnel. Call up information about the device sta-
13. Service menu 67
tus, make settings for specific operating conditions and run
firmware update.

TGH1389en/08.2012 57
Menu mode: Operation and setting

8.4.4.1 Back
Exit menu mode.
1.Exit
2.Alarm addresses
3.Test addresses
4.Value addresses

8.4.4.2 Settings menu 2: Alarm addresses


Setting of bus addresses for devices whose alarm messages are to be displayed as
standard messages on this MK2430.
The address of this MK2430 is automatically set to "On". All other alarm addresses are
set to: "Off".
Set the addresses of devices whose messages are to be displayed on this MK2430 to
"On". Only these addresses are monitored for presence on the BMS bus. If a device
cannot be found on the bus, an alarm message will appear.
The text of individual messages can be modified using the TMK-SET software.
If a number of systems or areas (e.g. several operating theatres) are connected to the
MK2430, the system numbers 1…4 can be assigned to them.

1.Exit 1.Exit
2.Edit table 2.Address: 002 On
3.Clear table System-No.: nn
---Alarm addresses---

1. Exit Back to the main menu.


2. Edit table Use the arrow buttons to select the address on the internal
BMS bus and confirm your selection by pressing "↵".
Use the arrow buttons to select "On" and activate this address
("Off" = deactivate). Press "↵" to accept the entry.
Use the arrow buttons to select System no.: "nn" and confirm
your selection by pressing "↵".
Repeat the procedure to activate more alarm addresses.
3. Clear table Deactivate all addresses (off). "Clear table" is only possible
when there are no test addresses activated (see setting
menu 3 "Test addresses".

58 TGH1389en/08.2012
Menu mode: Operation and setting

Possible system number settings:

nn Meaning

00 No text appears in line 1 of the alarm message.

01…04 Texts "System 01" to "System 04" are displayed.

T Programmed text is displayed.

8.4.4.3 Settings menu 3: Test addresses


Setting of bus addresses for insulation monitoring devices (e.g. 107TD47, IRDH…),
transfer switching devices with monitoring functions (ATICS®), LIM (Line Isolation
Monitors) and GFCI (Ground Fault Circuit interrupters) which are to carry out a test
when the "TEST" button is pressed. The setting can only be made for devices which have
also been activated in the "Alarm addresses" menu and/or programmed for individual
alarm texts. Individual alarm texts are a minimum requirement for:
  Channel 1…3 (setting "107TD47")
  Channel 1 (setting "IRDHxxx")

1.Exit 1.Exit
2.Edit table 2.Address: 002
3.Clear table Gerätetyp: MED-Iso
---Test addresses---

1. Exit Back to the main menu.


2. Edit table Use the arrow buttons to select the internal BMS bus ad-
dress and confirm your selection by pressing "↵ ".
Use the arrow buttons to select the device type:
LIM Line Isolation Monitors
GFCI Ground Fault Circuit interrupter
IND-Iso Industrial Insulation monitoring device
MED-Iso Medical insulation monitoring device
Off Address deactivated
Press "↵" to accept the entry.
Repeat the procedure to activate more addresses.
3. Clear table Deactivate all addresses (off).

TGH1389en/08.2012 59
Menu mode: Operation and setting

8.4.4.4 Settings menu 4: Value addresses


Currently has no function.

8.4.4.5 Settings menu 5: Digital inputs (MK2430-11 only)


Setting of the operational characteristics of digital inputs IN01…IN12. The following
setting can be made individually for each input: "24V" (high) or "0V" (low).
If "24V" is set for an input, an alarm message will be output if 24 Volt exists there. If "0V"
is set for an input, an alarm message will be output if 0 V exists there. It is for this reason
that you should always set unused digital inputs to "24V".

1.Exit 1.Exit
2.Operation mode 2.Input: IN01: 24V
3.Function: general Alarm at 24V
---Digital inputs---

1. Exit Back to the main menu.


2. Operation mode Use the arrow buttons to select the digital input and
confirm your selection by pressing "↵". Use the arrow
buttons to select "24 V" or "0 V". Press "↵" to accept the
entry.
Repeat the procedure to set more digital inputs.
3. . Function Set the message text category "neutral" or "medical",
see "neutral and specific alarm messages" on page 61

Digital input alarm texts


A neutral or specific alarm message can be assigned to all digital inputs. A neutral alarm
message indicates the alarm, the channel and the address of the device triggering the
alarm. In comparison, specific alarm messages (medical) signal non-modifiable pre-
programmed alarms, e.g. "oxygen".
Assign the inputs in accordance with table "neutral and specific alarm messages" on
page 61.

Other messages can be assigned to individual or all digital inputs with the TMK-SET PC
software.
If freely programmable alarm messages need to be displayed on a different MK2430 or
an alarm indicator and operator panel, the same alarm messages must have been
programmed in the displaying device.
The alarm messages in the following table are sent to other MK… or alarm indicator and
operator panels via BMS bus and displayed there in plain text format.

60 TGH1389en/08.2012
Menu mode: Operation and setting

Specific alarm messages


These messages contain instructions for medical gases and UPS systems.

Alarm messages for medical gases are signalled by the red "ALARM"
LED and the buzzer sounding. The buzzer can be set to mute (ac-
knowledged). It will sound again after 15 minutes by way of remind-
er.
Non-standard settings can only be made using the TMK-SET soft-
ware.

neutral and specific alarm messages

Neutral alarm messages Specific alarm messages


Inputs
"Function: Neutral" "Function: Medical"

IN1 Alarm: Address/channel XXX/01 Alarm: Oxygen

IN2 Alarm: Address/channel XXX/02 Alarm: Vacuum

IN3 Alarm: Address/channel XXX/03 Alarm: Nitrous oxide

IN4 Alarm: Address/channel XXX/04 Alarm: Compressed air 5 bar

IN5 Alarm: Address/channel XXX/05 Alarm: Compressed air 8 bar

IN6 Alarm: Address/channel XXX/06 Alarm: Nitrogen

IN7 Alarm: Address/channel XXX/07 Alarm: CO2

IN8 Alarm: Address/channel XXX/08 Alarm: BSV battery operation

IN9 Alarm: Address/channel XXX/09 Alarm: BSV overload

IN10 Alarm: Address/channel XXX/10 Alarm: BSV converter failure

IN11 Alarm: Address/channel XXX/11 Alarm: BSV fault

IN12 Alarm: Address/channel XXX/12 Alarm: BSV test run

TGH1389en/08.2012 61
Menu mode: Operation and setting

8.4.4.6 Settings menu 6: Buzzer


The buzzer will sound in the event of a warning or an alarm message. Setting the
frequency and repetition rate to distinguish the two buzzer tones.

1.Exit
2.Warning: 5
3.Alarm: 2

1. Exit Back to the main menu.


2. Warning
3. Alarm Various standard signals can be selected for "Warning" and "Alarm".
An individual buzzer sound can be selected via TMK-SET.
During setting the selected buzzer signal will sound and the LED will light up or flash.

8.4.4.7 Settings menu 7: Common acknowledgement


Setting indicating whether this MK2430 should respond to the acknowledgement of
the buzzer/buzzer mute initiated by pressing Buzzer mute button" " on another
MK… or TM… operator panel ("On") or "Off".
Activating the common acknowledgement function can for example make it possible to
acknowledge (mute) an alarm (buzzer tone) on an MK… or a TM… located in a neigh-
bouring building from an MK2430 in a central location.
The alarm message itself will remain visible on the display until its cause has been
rectified.

1.Exit
2.Common ack: On

1. Exit Back to the main menu.


2. Common ack.: Setting of the common acknowledgement for the internal
bus.
On Buzzer can be acknowledged (muted) externally
Off Buzzer cannot be acknowledged (muted) externally

62 TGH1389en/08.2012
Menu mode: Operation and setting

8.4.4.8 Settings menu 8: Clock


This menu is used to set the time of day, date and date format display. These settings
remain stored for approx. 5 days following a power supply failure.
The clock switches automatically to central European summer time (CEST) and winter
time (CET). Reset the clock if the time of day no longer matches your local time following
automatic switchover.
Automatic switchover can be deactivated (see 5. "Daylight sav.").

1.Exit (CEST)
2. Time 17:45
3.Date 21.09.11
4.Format: dd.mm.yy

1. Exit Back to the main menu


2. Time Set time of day (hours and minutes)
3. Date Set date (according to the format indicated in line 4)
4. Format Select German (dd. mm. yy) or
American (mm/ dd/yy)
5. Daylight sav. Setting for automatic switchover to Central European Sum-
mer Time:
Auto automatic switchover
Off no switchover

You can set the system time of day and date on any MK2430 or alarm
indicator and operator panel. The settings are transferred via the
BMS bus to the master device (address 1), which transfers the settings
to all other MK2430 or alarm indicator and operator panels.

TGH1389en/08.2012 63
Menu mode: Operation and setting

8.4.4.9 Settings menu 9: Language


Selection of the language for using the menus and displaying messages (alarm and
operational status messages) on the MK2430. Changes take effect immediately.
1.Exit
2.Menu: English
3.Mess.: English

1. Exit Back to the main menu.


2. Menu Set the operating language for the menu:
English or Deutsch
3. Message Set the display language for the messages. You may select:

English English French Italian

Portuguese
Spanish Portuguese Dutch
(Brazilian)

Norwegian Swedish Finnish Danish

Polish Hungarian Czech Slovenian

Croatian Serbian Turkish Indonesian

The language setting activates the language-specific special charac-


ters. However, user-defined alarm texts remain unchanged.
Therefore do not program or transfer the individual alarm texts until
the language settings are configured.

64 TGH1389en/08.2012
Menu mode: Operation and setting

8.4.4.10 Settings menu 10: Interface


Setting of the device address of this MK2430 and indication of the transmission speed
(baud rate) for the connection to the internal BMS bus (RS-485).

1.Exit
2.Addr. RS485: 001
3.Baud RS485: 09600

1. Exit Back to the main menu.


2. Addr. Device address setting of this MK2430.
Any address can be selected within the range of 1…150, the
addresses 100 to 110 are intended for special applications (e.g. PC,
OPC) and cannot be used for devices.
Factory setting is address 001 (master).
3. Baud The fixed pre-assigned baud rate is 9600 Bit/s

Change the corresponding device address if a number of MK2430 are connected to one
internal BMS bus. One MK2430 must have the address 1 (master). All other MK2430 are
addressed in consecutive order: 2,3,4… There should be no gaps between addresses to
ensure smooth system functioning (also refer to the "BMS bus operating manual").
Data exchange will only work between devices with the same baud rate.

TGH1389en/08.2012 65
Menu mode: Operation and setting

8.4.4.11 Settings menu 11: Relay


Set the mode of operation and function of the optional alarm relay on the alarm
indicator and test combination. This menu only exists on the MK2430…-11.

1.Exit
2.Operation mode: N/O
3.Function:
Device error

1. Exit Back to the main menu.


2. Relay mode Set the mode of operation:
N/O N/O operation
N/C N/C operation
3. Mode Alarm relay switches in the event of:

Setting Description

Device error Relay switches in case of an internal fault on the MK2430-11.

Common alarm Relay switches in case of any warning or alarm message.

Relay switches as soon as the MK2430 recognises a device


Device failure
failure.

Relay switches for approx. 3 seconds once a test is started


ISOMETER
via the "TEST“ button at the assigned devices (insulation
test
monitoring devices, LIM, GFCI).

The relay switches as soon as the buzzer sounds. Also other


Buzzer function signalling devices can be installed to indicate pending mes-
sages on the MK2430.

Programming via TMK-SET -> individual alarms or operating


Programmable
messages

66 TGH1389en/08.2012
Menu mode: Operation and setting

8.4.4.12 Settings menu 12: Password


Change, activate/deactivate password.

1.Exit
2.Password: X X X
3.Status: off

1. Exit Back to the main menu.


2. Password Change password. Factory setting: 807
3. Status: Activate or deactivate password protection.

Some menus are password-protected. Password protection is only


effective if the password has been enabled (switched on).
When an attempt is made to open a window, the entry screen for en-
tering the password appears automatically:
Enter
password
0 0 0

Once a valid password has been entered, full access will be granted
to all menus (except the Service menu) until menu mode is exited.

8.4.4.13 Settings menu 13: Service menu


The Service menu is reserved for settings made by authorised Bender Service
personnel. It can only be accessed subject to the entry of a master password.
In the Service menu, information about the device status can be called up and settings
for specific operating conditions can be made.

TGH1389en/08.2012 67
Menu mode: Operation and setting

8.4.5 Menu 5: Control


This menu offers various options for controlling individual devices or the overall system:

Menu item Mode Page

1. Back Exit "Control" menu; go up one menu level

2. Reset
Resetting all fault messages pending on the BMS bus 68
(AlarmClear)

3. EDS start/stop Manual starting/stopping of test procedures on EDS system 69

4. Test Testing of communication via the BMS bus (MK2430-11


69
Communication only).

8.4.5.1 Back
Exit menu mode.

1.Exit
2.Reset (AlarmClear)
3.EDS start/stop
4.Test Communication

8.4.5.2 Control menu 2: Reset (AlarmClear)


Press "↵ " to reset all pending fault messages on the BMS bus. "Reset done!" will then
appear in the last line displayed.

1.Exit
2.Reset (AlarmClear)
3.EDS Start/Stop
Reset done!

This reset command is sent via the BMS bus. Note that some devices (e.g. PRC470) do
not react to this reset.

68 TGH1389en/08.2012
Menu mode: Operation and setting

8.4.5.3 Control menu 3: EDS start/stop


Press "↵ " to start and stop the test procedure manually on the EDS system. This
function can only be activated for the master. The current status appears in the last line.

1.Exit 1.Exit
2.Reset (AlarmClear) 2.Reset (AlarmClear)
3.EDS start/stop 3.EDS start/stop
EDS system running EDS system stop

EDS system running Once started, EDS4xx-12 and PGH47x run continuously. If
you exit the menu, the standard display "EDSp" will appear
in the last line in order to indicate continuous running*.
EDS system stop Stops the continuous pass of EDS4xx-12 and PGH47x. If
you exit the menu, the standard display "EDS" will appear
in the last line until the current test pass finishes.

*
Other abbreviations that might appear in the last line of the display:
EDSa Automatic mode: Insulation fault location has been
started by e.g. ISOMETER®, ATICS® or isoMED427P on
PGH47x .
EDSs Single mode: A single pass has been started by IN2 on
PGH471.

8.4.5.4 Control menu 4: Test communication (MK2430-11 only)


Testing communication via the BMS bus. For this purpose, an error message is
simulated on a digital input. This fault message is sent to evaluator devices (e.g. alarm
indicator and test combinations MK2430, SMO…etc.) via BMS bus. Check that these
devices are responding to the fault message as requested.

1.Exit
2.Channel: 003

-Test communication-

Channel 003 Setting of the channel whose message is to be activated.

TGH1389en/08.2012 69
Menu mode: Operation and setting

8.4.6 Menu 6: External devices


This menu is used to set and control external devices. Functions include for example
displaying information about connected devices (address, software version, device
type) or continuous displaying a channel on a connected evaluator.

After calling the menu, select the address of the external device to be displayed (e.g.
EDS4xx-12 or RCMS4xx-12).

1. Back
001: MK2430 V4.02
002: EDS151 V1.00
003: ATICS2-ISO V1.08

Address, type and version of the connected device are indicated. When no device is
detected under this address, the character "?" appears. Use the arrow buttons to select
the address of the external device and confirm your selection with the "↵" button.

If the device has been recognised, the MK2430 will read the current settings of the
connected device. The device type is displayed in the first line of the display.
Use the Up/Down buttons to select the appropriate function or device setting. Confirm
with the "↵“ button. Example:

1. Exit (107TD47) 1. Exit (107TD47)


2. Position mode 2. Chan.: 1
Re= 20 KΩ

Numerous setting options are available in the EDS or RCMS menu. These are described
in more detail in the operating manuals for the corresponding systems.

1. Exit (EDS470)
2. General
3. Channel
4. Relay

70 TGH1389en/08.2012
Menu mode: Operation and setting

8.4.7 Menu 7: Info

MK2430-11 Addr.:001
Software 4.02 D228
Date: 02.09.11
www.bender-de.com

Information about the device type, the firmware version and the last time the assign-
ments were transmitted. Assignments are settings carried out via the PC software TMK-
SET:
  Enter standard texts

  Assign texts and functions to alarm messages and digital inputs of the MK2430

  Set parameters

Select:

ESC Exit menu mode


▲ Show date of last assignment transmission.
Assignments are settings carried out via PC software (e.g. TMK-
SET):
- Enter standard texts
- Assign texts and functions to the alarm messages and digital
inputs of
the MK2430
- Set parameters
▼ Show version of standard texts
and number of
- activated alarm addresses
- activated test addresses
- individually programmed messages
↵ Go back to the main menu

8.5 Overview of setting options


Die MK2430 supports various setting modes. The table below shows where the
individual parameters can be set.

TGH1389en/08.2012 71
Parameter Set in

72
Name Range Factory User MK2430 MK2430 TMK-SET Note
setting setting menu Service Parameter
menu menu
History entries -- -- -- -- clear clear Data records
Clear history
Power-down watchdog -- -- -- -- clear clear Reset counter
Time-out int. 42…200 ms 60 ms M13 x x Change only for test
purposes!
ALMI idle time 1…2 s 1s M13 x x Time between two
ALMI queries on the
internal BMS
Backlight autom./cont. autom. M13 x x
S/W time autom./OFF autom. M8 -- x Automat.
summer/winter time
Buzzer ON/OFF for ON -- M13 x -- e.g. for
1...9 hrs commissioning
Password prompt Y/N Y M12 -- x Activate password
prompt
Password 000...999 807 M12 -- x Change password
Language (for menu only) English/ German M9 -- x
German
Language (for message 20 German M9 -- x
only) languages
Time/message 3…8 s 5s M13 x x Message interval
Buzzer settings Duration/ 2 M6 -- x
interval 1…5
frequency
Common acknowledge Y/N Y M7 -- x Response to "buzzer
int. OFF" via BMS bus
Time of day/date M8 x
RS-485 settings address 1…150 1 M7 -- x Int. BMS bus
address
Time display Y/N Y M13 x x Time in the standard
display
Display ATICS Y/N N M13 x x
maintenance messages
Menu mode: Operation and setting

TGH1389en/08.2012
Menu mode: Operation and setting

TGH1389en/08.2012 73
Menu mode: Operation and setting

74 TGH1389en/08.2012
Technical data

9. Technical data

9.1 Technical data


Insulation coordination acc. to IEC 60664-1
Rated insulation voltage...............................................................................................................AC 250 V
Rated impulse voltage/pollution degree ....................................................................................... 4 kV/3
Supply voltage
Supply voltage Us ...................................................................................................................AC / DC 24 V
Frequency range Us ............................................................................................................0 / 40…60 Hz
Operating range Us .......................................................................................AC 18…28 / DC 18…30 V
Power consumption......................................................................................................................... ≤3 VA
Voltage failure without reset.......................................................................................................... ≤ 15 s
Displays and LEDs
Display, characters .......................................................................................... four lines, 4 x 20 characters
Standard message texts in.....................................................................................................20 languages
Alarm addresses................................................................................................................................ ≤ 150
Programmable text messages...............................................................................................................200
History memory (messages) .................................................................................................................250
Standard text message .................................................................................................... 3 x 20 characters
Additional text message (press button to access) ......................................................... 3 x 20 characters
Alarm LEDs (a set of LEDs) .................................... NORMAL (green), WARNING (yellow), ALARM (red)
Menu texts ....................................................................................................................... German/ English
Buttons.....................................................5 (ISOMETER test, buzzer mute, additional text, scroll, menu)
Buzzer
Buzzer message ....................................can be acknowledged, adoption of characteristics of new value
Buzzer interval ........................................................................................................................ configurable
Buzzer frequency .................................................................................................................... configurable
Buzzer repetition .................................................................................................................... configurable
Inputs (MK2430…-11 only)
Digital inputs.....................................................................................................................12 (IN1…IN12)
Galvanic separation.................................................................................................................................yes
Activation of the digital inputs......................................via potential-free contacts / extraneous voltage
Operating principle ....................................... N/O / N/C operation individually selectable for each input
Factory setting ......................................................................................................................N/O operation
Voltage range (high) ...................................................................................................AC / DC 10…30 V

TGH1389en/08.2012 75
Technical data

Voltage range (low) ......................................................................................................... AC / DC 0…2 V


Recommended cable.......................................................................................................min. J-Y(St)Y 0.8
Cable length.................................................................................................................................. ≤ 500 m
Interfaces
Interfaces.......................................................................................................RS-485 and USB (V2.0/V1.1)
Technical data for the RS-485 interface:
Protocol ............................................................................................................................................... BMS
Baud rate ..................................................................................................................................... 9.6 kbit/s
Cable length............................................................................................................................... ≤ 1200 m
Recommended cable: twisted pair, one end of shield connected to PE: J-Y(St)Y min. 2x0.8
Terminating resistor ..................................................120 Ω (0.25 W) can be connected via DIP switch
Device address, BMS bus.............................................................................................DIP switch 1…150
Factory setting device address ...................................................................................................1 (master)
Programming
Interfaces........................................RS-485 or USB (V2.0/V1.1), USB cable: Type A plug on type B plug.
Software............................................................................................................TMK-SET V 3.0 and higher
Factory setting password ............................................................................................................ activated
Max. cable length in case of power supply of 1/2/3 MK24…from one AN450
0.28 mm2 (z.B. J-Y(St)Y n x 0.6) .......................................................................................160 / 40 / -- m
0.5 mm2 (z.B. J-Y(St)Y n x 0.8) .........................................................................................250 / 70 / -- m
0.75 mm2..........................................................................................................................400 / 100 / -- m
1.5 mm2 ........................................................................................................................... 800 / 210 / 10 m
2.5 mm2 .........................................................................................................................1300 / 360 / 20 m
Max. cable length in case of power supply of 1/2/3 MK24…from one AN410
0.28 mm2 (z.B. J-Y(St)Y n x 0.6) ...................................................................................300 /150 / 100 m
0.5 mm2 (z.B. J-Y(St)Y n x 0.8) ....................................................................................500 / 250 / 150 m
0.75 mm2.......................................................................................................................750 / 375 / 250 m
1.5 mm2 .......................................................................................................................1500 / 750 / 500 m
2.5 mm2 .....................................................................................................................2500 / 1200 / 750 m
Colours
Front foil........................................................................... RAL 7035 (light grey); RAL 7040 (basalt grey)
Marking........................................................................................................ RAL 5005 (ultramarine blue)
Front plate ................................................................................................................RAL 7035 (light grey)

76 TGH1389en/08.2012
Technical data

Switching elements (MK2430…-11 only)


Number .....................................................................................................................1 changeover contact
Function ............................................................................................................................. programmable
Operating principle ...................................................................... N/C or N/O operation (programmable)
Electrical service life under rated operating conditions...............................10.000 switching operations
Contact data acc. to IEC 60947-5-1
Utilisation category..............................................................AC-13...................... AC-14 .................DC-12
Rated operational voltage ......................................................24 V......................... 24 V ....................24 V
Rated operational current.........................................................5 A........................... 3 A ......................1 A
Minimum contact rating.......................................................................................1 mA at AC / DC > 10 V
General data
EMC immunity ......................................................................................... acc. to EN 61000-6-2:2002-08
EMC emission ........................................................................................... acc. to EN 61000-6-6:2007-09
Classification of climatic conditions acc. to IEC 60721:
Stationary use ........................................................................................................................................3K5
Transport ...............................................................................................................................................2K3
Long-term storage.................................................................................................................................1K4
Operating temperature......................................................................................................... -5…+55 °C
Classification of mechanical conditions acc. to IEC 60721:
Stationary use ...................................................................................................................................... 3M4
Transport ............................................................................................................................................. 2M2
Long-term storage............................................................................................................................... 1M3
Operating mode .......................................................................................................continuous operation
Mounting ..........................................................................................................................display-oriented
Connection pluggable screw terminals
Connection properties (supply voltage, BMS bus):
Connection of single conductors
rigid/flexible/conductor sizes............................................................0.2…0,2…2.5 mm2/AWG 24-12
flexible with ferrules, without/with plastic sleeve .................................. 0.25…2.5 / 0.25…2.5 mm2
Multi-conductor connection (2 conductors with the same cross section)
rigid / flexible.................................................................................................... 0.2…1 / 0.2…1.5 mm2
flexible with ferrule without plastic sleeve ........................................................................ 0.25…1 mm2
flexible with TWIN ferrule with plastic sleeve ................................................................. 0.5 …1.5 mm2

TGH1389en/08.2012 77
Technical data

Connection properties (inputs):


Connection of single conductors
rigid/flexible/conductor sizes .............................................. 0.08…1.5 / 0.08…1.5 mm2/AWG 28-16
flexible with ferrules, without/with plastic sleeve ..................................0.25…1.5 / 0.25…0.5 mm2
Multi-conductor connection (2 conductors with the same cross section):
rigid / flexible........................................................................................... 0.08…0.5 / 0.08…0.75 mm2
flexible with ferrule without plastic sleeve................................................................... 0.25…0.34 mm2
flexible with TWIN ferrule with plastic sleeve ..............................................................................0.5 mm2

Stripping length................................................................................................................................. 7 mm
Tightening torque................................................................................................................ 0.5…0.6 Nm
Degree of protection, internal components (DIN EN 60529)...........IP50 (surface-mounting type: IP54)
Degree of protection, terminals (DIN EN 60529).................................................................................IP20
Flammability class........................................................................................................................ UL94V-0
Weight ...................................................................flush-mounting < 210 g, surface-mounting< 400 g

9.1.1 Standards
The MK2430 alarm indicator and test combination meets the requirements of the
regulations for installation IEC 60364-7-710:2002-11 and DIN VDE 0100-710 (VDE 0100
Teil 710): IEC 60364-7-710 2002-11.

9.2 Ordering information

Type Description Art. No.

Alarm indicator and test combination according to IEC


60364-7-710:2002-11 / DIN VDE 0100-710,
featuring a BMS bus and a USB interface , 12 digital inputs,
MK2430-11 B 9510 0001
one relay output, alarm texts programmable via interfaces
and PC, standard text display. Version: Flush-mounting
enclosure

Alarm indicator and test combination according to IEC


60364-7-710:2002-11 / DIN VDE 0100-710,
MK2430-12 featuring a BMS bus and a USB interface, B 9510 0002
alarm texts can be programmed via interfaces and PC,
standard text display. Version: Flush-mounting enclosure

78 TGH1389en/08.2012
Technical data

Type Description Art. No.

MK2430P-11 As MK2430-11, but programmed in the factory. B 9510 0003

MK2430P-12 As MK2430-12 but programmed in the factory. B 9510 0004

MK2430A-11 As MK2430-11, but with surface-mounting enclosure B 9510 0005

MK2430A-12 As MK2430-12, but with surface-mounting enclosure B 9510 0006

As MK2430A-11, but programmed in the factory and with


MK2430PA-11 B 9510 0007
surface mounting enclosure.

As MK2430A-12, but programmed in the factory and with


MK2430PA-12 B 9510 0008
surface mounting enclosure.

MK2430S-11 As 2430-11, but front plate with screw fixing B 9510 0011

MK2430S-12 As 2430-12, but front plate with screw fixing B 9510 0012

MK2430- Mounting bracket kit for flash-mounting enclosure for snap


mounting kit, on mounting of the MK2430 Mounting kits for cavity wall B 9510 1000
complete mounting, panel mounting or DIN rail mounting

Flush-mount- Flush mounting enclosure included in the scope of delivery


B 923 710
ing enclosure of MK2430

- TMK-SET V 4.x parameterisation software for


MK2430, MK800, TM800
- TMK-HISTORY V 3.x for MK2430, MK800, TM800,
MEDICS soft-
TM1000 and PRC1470 B 9602 0087
ware
- USB driver software for MK2430, MK800 and TM800
- MEDISET V1.x parameterisation software for TM1000 and
PRC1470

TGH1389en/08.2012 79
Technical data

80 TGH1389en/08.2012
INDEX D
Date 63
Date format 63
A device address 65
Acknowledgement 62 Diagram 53
Additional text 48 Digital inputs 25, 60
Address settings 28, 32 Display 16
Alarm addresses 16, 58 drill holes 19
Alarm message 16
- neutral 60
E
- specific 60
Alarm relay 43, 66 Error codes 50
Assignments 71 Error list 44
Automatic mode 69 Evaluators 70
External devices 70
B
F
Baud rate 65
Beep code 43 Features 15
Bender Service personnel 67 Firmware version 51, 71
BMS bus 18 Flush-mounting enclosure 20
Buzzer 47, 62, 66 frequency 62
Functional test 39
C
G
Cable length 23
Cavity wall mounting 21 Gases
CEST 63 - medical 61
Changeover periods 39
Commissioning 33 H
Common acknowledgement 62 History memory 17, 55
Communication 69
Connection 23 I
Control 68
Intended use 9
Interfaces 18

TGH1389en/08.2012 81
INDEX

L R
Language 16, 64 Regulations for erection and installation 78
LEDs 16 Relay mode 66
Relay output 27
M Reset 68
Main menu 52
Master password 67 S
Measured value addresses 60 Selective operation 11
medical gases 61 Service 40
MEDICS® 13 Setting 57
MK2430-11 17 Setting possibilities 71
MK2430-12 17 Setting values 39
MK2430P-… 17 Shape stability 20
Mounting brackets 21 Single mode 69
Snap-on mounting 21
O Software 16, 18
Standard display 47, 51
Operation 45
Status line 48, 49
- condition 47
Switching on 34, 35
- fault-free 47
System components 7
Ordering information 78
Overview of enclosures 19
T
P Terminating resistor 23, 25, 26, 27
TEST 49
Panel mounting 21
Test procedure 69
parallel indication 14, 17
Text messages 17
Password 52, 67
Time 63
Periodic verification 38
TMK-SET 58, 60, 61
Personnel 10
Transmission speed 65
Potential free contacts 17
Programming 17
U
Q USB interface 18
Quick reference guide 45

82 TGH1389en/08.2012
Bender Inc.
USA:
700 Fox Chase
Coatesville, PA 19320
Toll Free: 800-356-4266
Phone: 610-383-9200
Fax: 610-383-7100
E-mail: info@bender.org

Canada:
5810 Ambler Drive, Unit 1
Mississauga, ON L4W 4J5
Toll Free: 800-243-2438
Phone: 905-602-9990
Fax: 905-602-9960
E-mail: info@bender-ca.com

Web: http://www.bender.org

You might also like