Water Bird Continuation Sheet

DOSAGE CALCULATIONS/SIZING CALCULATIONS


CHILLED WATER TREATMENT SYSTEM

Total System Volume : 45 M3

Chemical Quantity Calculation

Cleaning Chemical

Neutral pH cleaner : Accepta 2877

Dosage : 1 kg/m³
Quantity required for 45 m³ : 45 kgs.

Passivation Chemicals

Silicate Based Corrosion Inhibitor : Accepta 894

Dosage : 0.1 kgs/m³


Quantity required for 45 m³ : 4.5 kgs

Initial Treatment Chemicals

Corrosion Inhibitor : Accepta 2337

Dosage : 3 kgs/m³
Quantity required for 45 m³ : 135 kgs

Microbiocide : Accepta 2886

Dosage : 0.1 kg/m³


Quantity required for 45 m³ : 4.5 kgs

Yearly Maintenance Quantity

System Volume : 45 m³
Average loss per month :2%
: 0.9 m³/month
Water Bird Continuation Sheet

Quantity of Accepta 2337 required = 0.9 m³ x 12 (months in a year) x 3 (dosage rate)


= 32.4 kgs. / year
= 0.08876 ltrs/day
= 0.00369 ltrs/hr

Biocide Accepta 2886 addition is once in two months.

Dosage : 4.5 kgs once in two months


Quantity required for one year : 4.5 kgs x 5 times
: 22.5 kgs.

Proposed Items

Automatic dosing tank capacity : 60 ltr


Dosing pump capacity : 1.1 ltrs/hr. @ 16Bar
Max. Working pressure : 16 bar
Manual dosing pot capacity : 25 ltr (Sufficient as per system volume)

Manual Dosing Pot Calculation

Manual dosing pot is used for the periodical dosing of Micro biocide.

System Volume : 45 m³

Microbiocide Requirement : 0.1 kg/m3 of system volume


: Once in 2 months.
: 0.1 x 45
: 4.5 Kgs.

Capacity of Manual Dosing Pot Offered : 25 ltrs.

We have offered a 25 ltrs. Manual Dosing Pot. Proposed Dosing Pot is sufficient to dose one
full shock dosage of Microbiocide at a time.

Dosing Pump Calculation

Dosing pump is used for the dosing of corrosion inhibitor in the chilled water system which
is connected to the automatic dosing system controller. The dosage is done automatically
based on the conductivity measurement. Dosage is calculated based on an average system
loss of 2% per month.

System Volume : 45 m³
Water Bird Continuation Sheet

Dosage rate of Corrosion


Inhibitor (Accepta 2337) : 3 kgs/m³

Yearly Maintenance Quantity

System Volume : 45 m³
Average loss per month :2%
: 0.9 m³/month

Quantity of Accepta 2337 required = 0.9 m³ x 12 (months in a year) x 3 (dosage rate)


= 32.4 kgs. / year
= 0.08876 ltrs/day
= 0.0036 ltrs/hr

Selected Pump : CNPB01601


: 1.1 ltrs/hr. @ 16 Bar

 The dosing pump can deliver a dosage rate of 1.1 Ltrs/hr which is much above the
system requirement of 0.0036 Ltrs/hr.

System Pressure : Up to 16 bar

 The selected / proposed pump can dose chemical at a pressure of 16 bars, which is
enough for the system.

Dosing Tank Calculation:-

System Volume : 45 m³
Dosage rate of Corrosion
Inhibitor (Accepta 2337) : 3 kg’s/m³

Yearly Maintenance Quantity

System Volume : 45 m³
Average loss per month :2%
: 0.9 m³/month

Quantity of Accepta 2337 required = 0.9 m³ x 12 (months in a year) x 3 (dosage rate)


= 32.4 kgs. / year

Selected Dosing Tank : 60 Ltrs.

 Required yearly maintenance chemical is 32.4 kg’s only. Hence we have provided 60
ltrs. Dosing tank, which is more sufficient for more than twelve month chemicals
consumption.