Lembar data produk ATV630D15N4

Karakteristik variable speed drive ATV630 - 15kW/20HP -


380...480V - IP21/UL type 1

Disklaimer: Dokumentasi ini tidak ditujukan sebagai pengganti dan tidak untuk digunakan untuk menentukan kesesuaian atau keandalan produk ini untuk aplikasi pengguna
Main
Range of product Altivar Process ATV600
Product or component type Variable speed drive
Product specific application Process and utilities
Device short name ATV630
Variant Standard version
Product destination Synchronous motors
Asynchronous motors
EMC filter Integrated with 50 m conforming to EN/IEC 61800-3 category C2
Integrated with 150 m conforming to EN/IEC 61800-3 category C3
IP degree of protection IP21 conforming to IEC 61800-5-1
IP21 conforming to IEC 60529
Degree of protection UL type 1 conforming to UL 508C
Type of cooling Forced convection
Supply frequency 50...60 Hz - 5...5 %
[Us] rated supply voltage 380...480 V - 15...10 %
Motor power kW 15 kW (normal duty)
11 kW (heavy duty)
Motor power hp 20 hp normal duty
15 hp heavy duty
Line current 27 A at 380 V (normal duty)
23.3 A at 480 V (normal duty)
20.6 A at 380 V (heavy duty)
18.1 A at 480 V (heavy duty)
Prospective line Isc 50 kA
Apparent power 19.4 kVA at 480 V (normal duty)
15 kVA at 480 V (heavy duty)
Continuous output current 31.7 A at 4 kHz for normal duty
23.5 A at 4 kHz for heavy duty
Maximum transient current 34.9 A during 60 s (normal duty)
35.3 A during 60 s (heavy duty)

09 Mar 21
1
Asynchronous motor control profile Constant torque standard
Variable torque standard
Optimized torque mode
Synchronous motor control profile Permanent magnet motor
Synchronous reluctance motor
Output frequency 0.0001…0.5 kHz
Speed drive output frequency 0.1…599 Hz
Nominal switching frequency 4 kHz
Switching frequency 2...12 kHz adjustable
4...12 kHz with derating factor
Safety function STO (safe torque off) SIL 3
Discrete input logic 16 preset speeds
Communication port protocol Ethernet
Modbus serial
Modbus TCP
Option card Slot A: communication module, Profibus DP V1
Slot A: communication module, Profinet
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink

Complementary
Mounting mode Wall mount
Output voltage <= power supply voltage
Permissible temporary current boost 1.1 x In during 60 s (normal duty)
1.5 x In during 60 s (heavy duty)
Motor slip compensation Can be suppressed
Adjustable
Automatic whatever the load
Not available in permanent magnet motor law
Acceleration and deceleration ramps Linear adjustable separately from 0.01...9999 s
Braking to standstill By DC injection
Protection type Thermal protection: motor
Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Frequency resolution Display unit: 0.1 Hz
Analog input: 0.012/50 Hz
Electrical connection Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16
Line side: screw terminal 10...16 mm²/AWG 8...AWG 6
Motor: screw terminal 10...16 mm²/AWG 8...AWG 6
Connector type RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses 1…247 for Modbus serial
Method of access Slave Modbus TCP

2
Supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-
circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection
type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload
and short-circuit protection
Local signalling 3 LEDs for local diagnostic
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
Width 211 mm
Height 546 mm
Depth 232 mm
Net weight 13.6 kg
Analogue input number 3
Analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA/4...20 mA, impedance: 250 Ohm, resolution 12
bits
Discrete input number 8
Discrete input type DI1...DI6 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm
DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
STOA, STOB safe torque off, 24 V DC (<= 30 V), impedance: > 2.2 kOhm
Input compatibility DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
Discrete input logic Positive logic (source) (DI1...DI6), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI6), > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (DI5, DI6), < 0.6 V (state 0), > 2.5 V (state 1)
Positive logic (source) (STOA, STOB), < 5 V (state 0), > 11 V (state 1)
Analogue output number 2
Analogue output type Software-configurable voltage AO1, AO2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AO1, AO2: 0...20 mA, resolution 10 bits
Sampling duration 2 ms +/- 0.5 ms (DI1...DI4) - discrete input
5 ms +/- 1 ms (DI5, DI6) - discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10 ms +/- 1 ms (AO1) - analog output
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AO1, AO2: +/- 0.2 % for analog output
Relay output number 3
Relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
Maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Isolation Between power and control terminals
Variable speed drive application Building - HVAC Compressor centrifugal
selection Food and beverage processing Other application
Mining mineral and metal Fan
Mining mineral and metal Pump
Oil and gas Fan
Water and waste water Other application
Building - HVAC Screw compressor
Food and beverage processing Pump
Food and beverage processing Fan
Food and beverage processing Atomization
Oil and gas Electro submersible pump (ESP)
Oil and gas Water injection pump
Oil and gas Jet fuel pump
Oil and gas Compressor for refinery
Water and waste water Centrifuge pump

3
Water and waste water Positive displacement pump
Water and waste water Electro submersible pump (ESP)
Water and waste water Screw pump
Water and waste water Lobe compressor
Water and waste water Screw compressor
Water and waste water Compressor centrifugal
Water and waste water Fan
Water and waste water Conveyor
Water and waste water Mixer
Motor power range AC-3 15…25 kW at 380…440 V 3 phases
15…25 kW at 480…500 V 3 phases

Environment
Insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
Noise level 59.5 dB conforming to 86/188/EEC
Power dissipation in W Natural convection: 59 W at 380 V, switching frequency 4 kHz
Forced convection: 366 W at 380 V, switching frequency 4 kHz
Volume of cooling air 215 m3/h
Operating position Vertical +/- 10 degree
Maximum THDI <48 % from 80...100 % of load conforming to IEC 61000-3-12
Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Pollution degree 2 conforming to EN/IEC 61800-5-1
Vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation -15…50 °C (without derating)
50…60 °C (with derating factor)
Ambient air temperature for storage -40…70 °C
Operating altitude <= 1000 m without derating
1000...4800 m with current derating 1 % per 100 m
Standards UL 508C
EN/IEC 61800-3
Environment 1 category C2 EN/IEC 61800-3
Environment 2 category C3 EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
Product certifications ATEX zone 2/22
TÜV
ATEX INERIS
CSA
UL
DNV-GL
Marking CE

Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 17.493 kg
Package 1 Height 25.5 cm
Package 1 width 34 cm
Package 1 Length 73.5 cm

4
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
Upgradeability Upgraded components available

5
Lembar data produk ATV630D15N4
Dimensions Drawings

Dimensions

Drives with IP21 Top Cover


Front and Left Views

Drives Without IP21 Top Cover


Left and Rear Views

6
7
Lembar data produk ATV630D15N4
Mounting and Clearance

Clearances

X1 X2 X3

≥ 100 mm (3.94 in.) ≥ 100 mm (3.94 in.) ≥ 10 mm (0.39 in.)

8
Lembar data produk ATV630D15N4
Mounting and Clearance

Mounting Types

Mounting Type A: Individual IP21

a≥ 100 mm (3.94 in.)

Mounting Type B: Side by Side IP20

Mounting Type C: Individual IP20

a≥ 0

9
Lembar data produk ATV630D15N4
Connections and Schema

Three-Phase Power Supply with Upstream Breaking via Line Contactor

Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 6

(1) Line choke if used


(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 : Line Contactor
Q2, Q3 : Circuit breakers
S1, S2 : Pushbuttons
T1 : Transformer for control part

10
Lembar data produk ATV630D15N4
Connections and Schema

Three-Phase Power Supply with Downstream Breaking via Contactor

Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN

(1) Line choke if used


(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 : Contactor

11
Lembar data produk ATV630D15N4
Connections and Schema

Control Block Wiring Diagram

(1) Safe Torque Off


(2) Analog Output
(3) Digital Input
(4) Reference potentiometer
(5) Analog Input
R1A, R1B,Fault
R1Crelay
:
R2A, R2CSequence
: relay
R3A, R3CSequence
: relay

Sensor Connection
It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.

12
Lembar data produk ATV630D15N4
Connections and Schema

Sink / Source Switch Configuration

The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
● Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
● Set the switch to Ext if using PLC outputs with NPN transistors.

Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs

Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs

Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs

Switch Set to EXT Position Using an External Power Supply for the DIs

13
Lembar data produk ATV630D15N4
Performance Curves

Derating Curves

40 °C (104 °F) - Mounting type A, B and C


50 °C (122 °F) - Mounting type A, B and C
60 °C (140 °F) - Mounting type B and C
In : Nominal Drive Current
SF : Switching Frequency