B3 - 206 - 2006-Substation Design Using Phase To Phase Insulation
B3 - 206 - 2006-Substation Design Using Phase To Phase Insulation
B3 - 206 - 2006-Substation Design Using Phase To Phase Insulation
http : //www.cigre.org
A Renton
Maunsell Ltd
New Zealand
SUMMARY
The use of phase to phase insulation on Transmission Systems appears to have been limited
to use as conductor spacers to prevent line clashing on transmission circuits. Further
applications within transmission systems and in particular switchyards, do not appear to have
been pursued. While investigating expansion options for a 220 kV substation, we found that
by using a higher voltage class composite insulator to separate the main and transverse bus
sections, a number of advantages over current designs are possible. These ideas can be
used for both the redevelopment of existing and the construction of new substations.
Work was carried out to investigate expansion options at a 220 kV substation. The brief for
this review involved examining the existing switchyard designs and suggesting possible
options that would meet the following key design criteria;
One design option that evolved made use of a rigid aluminium main busbar separated from
the flexible (stranded conductor) transverse bus by phase to phase insulation, made up of a
standard 400 kV composite line suspension insulator hung from the main bus.
This approach enabled the design criteria objectives to be met primarily by reducing the
number of components used. By changing the design of the main bus supports, savings in
foundations and structures were also realised. With the use of a larger diameter main bus,
the requirement for rigid transverse buswork and associated support posts, foundations and
insulators was removed as the suspended composite insulator strings support the transverse
bus conductor. As an added advantage this arrangement enabled the physical spacing of
the transverse bus and the main bus support structures to be reduced without affecting
electrical clearances, resulting in a shorter and narrower bay size.
andrew.renton@maunsell.com
Taken together this arrangement has enabled the following;
• Fewer components to be utilised, with no special or one supplier only parts being
required as the flexible transverse bus acts as both transverse bus and equipment
connector
• Reduced number of structures to be installed and maintained
• Improved access to the switchyard through the removal of clutter and extraneous
structures
• Reduced construction time & cost savings of approximately 55-80% per bus section
• Improved environmental effects by reducing the station footprint and visual impact
with fewer structures being present
• Improved equipment maintenance access
This paper describes the design of this alternative approach, and compares and contrasts
technical and financial attributes with more traditional designs.
KEYWORDS
andrew.renton@maunsell.com
INTRODUCTION
The owner of the New Zealand National Grid, wished to investigate possible expansion
options at a 220 kV substation. The work involved reviewing the existing switchyard design
and formulating alternative switchyard bus configurations, which complied with both the
National Grid Operators standards for the design and layout of substation and buswork, as
well as meeting a number of key design criteria. These criteria were;
Outlined below are the significant electrical, mechanical & environmental design parameters
that formed the basis for the design of the proposed substation expansion.
2 DESIGN REQUIRMENTS
2.1.2 Environmental
• Maximum Ambient Temperature 30°C
• Maximum Continuous Conductor Temperature 80°C
• Maximum Short Time Conductor Temperature 250°C
• Minimum Wind Velocity 0.6 m/s
• Relative Conductor Emissivity 0.5
• Pollution Level Heavy/Very Heavy
• Creepage 25 mm/kV
• Seismic Loads to AS/NZS:1170
• Line Pull <=1 kN
3
3 BUS DESIGN
The following sections demonstrate the proposed designs evolution by contrasting the
existing, an interim and the proposed busbar configuration, before going on to detail a series
of calculations used to verify the design.
3.1 Configurations
Figure 1 Existing Rigid Post Mounted Main - Rigid Post Mounted Transverse Bus
Figure 2 Rigid Post Mounted Main - Flexible Post Mounted Transverse Bus
4
The use of flexible conductor for the transverse bus has construction, access and cost
advantages when only one switchgear bay is installed, however these benefits reduce when
additional bays are required, because it requires the same number of insulators, steel posts
& foundations as its rigid equivalent. As multiple switchgear bays are a possibility, it was
decided to investigate the feasibility of removing the additional transverse support posts
while retaining the flexible stranded conductor.
With these conflicts resolved, the disconnector could be repositioned closer to the main bus,
removing the requirement for any yellow phase bus supports while leaving the challenge of
the outer blue phase flexible connections. The design criteria specified in Section 2.1, limited
the load applied to equipment terminals by flexible connections to less than 1 kN. After
consideration it was proposed that suspension insulators, used in a similar manner to how
transmission line phase spacers are used, could support the flexible transverse bus.
Research aimed at identifying where phase to phase insulation was used on transmission
systems other than line phase spacers and how it had been used within substations met with
only limited success. Therefore a number of arrangements using phase to phase insulation,
some examples are shown in Figure 3, were proposed before the final design of two
insulators arranged in a “V” configuration was settled on.
The final configuration utilises the standard main bus support post insulators, a larger
diameter rigid tubular aluminium busbar and standard 400 kV composite suspension
insulators. These suspension insulators along with the hardware are hung from the main
bus, supporting the flexible conductor transverse bus. When viewed from above the
suspension insulators are diagonally offset to one another to prevent significant sideways
displacement under fault conditions.
5
Having established that this arrangement met the design criteria without major drawbacks,
further detailed design checks where undertaken to confirm the design concept.
Where
It should be noted that this short circuit force is twice the value given by the CIGRE Formula,
which specifies a maximum service load.
The calculated results demonstrated that for a conductor length of 3.9 m and a fault level of
25 kA, the maximum short circuit current force experienced by the conductor equated to
277 N/m. As the conductor’s displacement during a fault would result in a tangential force
6
being applied to the insulator, the maximum line pull applied by the conductor to the attached
equipment is less than the specified maximum of 1 kN. During a fault the side ways
deflection of a single phase stranded conductor is less than 0.66 m. With a transverse bus
spacing of 3.6 m this deflection does not compromise either the phase to phase (3.6 m – 2 x
0.66 m = 2.28 m) or phase to earth clearances.
4.1 Disadvantages
• Failure of phase to phase insulation results in the loss of a busbar or bus section
• Composite insulators may require earlier replacement than traditional ceramics
• Larger and heavier main bus support posts are not as easy to handle on site
4.2 Advantages
• Use of standard substation & transmission line components
• No reduction in required clearances and spacings
• Better access for maintenance due to fewer obstructions
• Lower visual impact due to fewer structures
• Reduced construction time and cost
• Smaller land area, and therefore lower associated land and civil costs
7
4.3 Costings
Although the proposed design requires a larger diameter main bus bar and heavier main bus
support posts, it is a more cost effective arrangement than conventional designs as,
Figure 5 below indicates where the savings have predominately been made.
100%
% Versus Two SwGr Bay Rigid Main Rigid Transverse
Foundations
90%
Insualtors
80%
Support Posts
70% Buswork & Conductors
60%
50%
40%
30%
20%
10%
0%
Rigid Rigid Rigid Rigid Rigid Rigid
Main/Rigid Main/Strung Main/Strung Main/Rigid Main/Strung Main/Strung
Transverse Transverse Transverse Transverse Transverse Transverse
Post Suspension Post Suspension
No Sw Gr Bays Per Bus Tw o Sw Gr Bays Per Bus
It should be noted that in preparing these costings, only obvious and direct savings were
accounted for, such as number of insulators, reduced busbar length, bus fittings, and fewer
support posts, foundations and earth connections. No allowance has been made for
additional cost savings resulting from smaller space requirements such as those associated
with earth works, earthgrid, control cables, land purchase and fencing.
The reduction in land area is assumed to be only the area directly under a single bus and a
single switchgear bay as far as the line/transformer CT position. This approach ignores the
benefits of easier vehicle access to the main bus that the increased height of the busbar
enables. Based on the dimensions given in Figure 4 above (Proposed 13 x 17 m =221 m2
Vs Existing12.2 x 23.7 m = 290 m2) it is estimated that a substation’s area may be reduced
by between 15% and 25% depending upon issues such as vehicle access, and number of
switchgear bays connected to a given bus section.
8
Overall, conservative estimates of the proposed design suggest that construction costs per
two switchgear bay bus section could be reduced by approximately 55%, when compared to
a more traditional arrangement. This total is likely to be closer to 80% per bus section once
savings related to reduced space, land purchase, civil works, cabling etc are taken into
account.
This proposed design offers a number of potential benefits in addition to cost savings of
between 55-80% per bus section, without appearing to have any significant disadvantages.
BIBLIOGRAPHY
[1] “The thermal behaviour of overhead conductors Section 1 and 2 Mathematical model for
evaluation of conductor temperature in the steady state and the application thereof” (Working
Group SC 22-12 CIGRE, Electra number 144 October 1992 pages 107-125)
[2] Transmission Line Reference Book, 115-138 kV Compact Line Design, EPRI, 1978, pages 12-
24 & 147-143.
[3] AS/NZS:1170 Parts 1 -5 Structural Design Actions (NZ Loadings Code)
[4] IEC60865-1 Short-circuit currents - Calculation of effects - Part 1: Definitions and calculation
methods