CAT C13 400kW Submittal
CAT C13 400kW Submittal
CAT C13 400kW Submittal
Radiator air flow restriction (system) 0.12 kPa 0.48 in. Water
Radiator air flow 497 m3/min 17551 cfm
Engine coolant capacity 14.2 L 3.8 gal
Radiator coolant capacity 30 L 8 gal
Total coolant capacity 34 L 12 gal
Inlet Air
Combustion air inlet flow rate 24.4 m³/min 966.6 cfm
Max. Allowable Combustion Air Inlet Temp 47 ° C 116 ° F
Exhaust System
Exhaust stack gas temperature 567.4 ° C 1053.4 ° F
Exhaust gas flow rate 82.0 m³/min 2894.9 cfm
Exhaust system backpressure (maximum allowable) 10.0 kPa 40.0 in. water
Heat Rejection
Heat rejection to jacket water 156 kW 8857 Btu/min
Heat rejection to exhaust (total) 398 kW 22607 Btu/min
Heat rejection to aftercooler 71 kW 4023 Btu/min
Heat rejection to atmosphere from engine 52 kW 2945 Btu/min
Heat rejection from alternator 29 kW 1661 Btu/min
LEHE2009-04 1/2
Cat C13 GC ®
DIESEL GENERATOR SETS
1
For ambient and altitude capabilities consult your Cat dealer. Air flow AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70,
restriction (system) is added to existing restriction from factory. NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22, NEMA
MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
2
Emissions data measurement procedures are consistent with those described
in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, Note: Codes may not be available in all model configurations. Please consult your
NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 local Cat Dealer representative for availability.
in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The
nominal emissions data shown is subject to instrumentation, measurement , STANDBY: Output available with varying load for the duration of the interruption
facility and engine to engine variations. Emissions data is based on 100% load of the normal source power. Average power output is 70% of the standby power
and thus cannot be used to compare to EPA regulations which use values based rating. Typical operation is 200 hours per year, with maximum expected usage of
on a weighted cycle. 500 hours per year.
3
UL 2200 Listed packages may have oversized generators with a different RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings
temperature rise and motor starting characteristics. Generator temperature rise also apply at ISO3046 standard conditions.
is based on a 40° C ambient per NEMA MG1-32.
Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of
42 780 kJ/kg (18,390 Btu/lb) when used at 29º C (85º F) and weighing 838.9 g/litre
(7.001 lbs/U.S. gal.). Additional ratings may be available for specific customer
requirements, contact your Caterpillar representative for details. For information
regarding Low Sulfur fuel and Biodiesel capability, please consult your Cat dealer.
LEHE2009-05 (05-20)
www.Cat.com/electricpower
©2020 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International
System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Corporate Yellow”, the
“Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of 2/2
Caterpillar and may not be used without permission.
Cat GC ®
Control Panel
FEATURES
• 4-line back-lit LCD text display
• Multiple display languages
• Five-key menu navigation
• LCD alarm indication
• Customisable power-up text and images
• Data logging facility
• Internal PLC editor
• Protections disable feature
• Fully configurable via PC using USB & RS485 communication
• Front panel configuration with PIN protection
• Power save mode
• 3-phase generator sensing and protection
• Generator current and power monitoring (kW, kvar, kVA, pf)
kW and kvar overload and reverse power alarms
• Over current protection
• Unbalanced load protection
• Breaker control via fascia buttons
• Fuel and start outputs configurable when using
CAN Support for 0 V to 10 V & 4 mA to 20 mA sensors
• 8 configurable digital inputs (3 available for Customer use)
• 8 configurable digital outputs (5 available for Customer use)
• 4 configurable analogue inputs (3 available for Customer Use)
• CAN, MPU and alternator frequency speed sensing in one variant
• Real time clock
• Engine pre-heat and post-heat functions
• Engine run-time scheduler
• Engine idle control for starting &stopping
• Fuel usage monitor and low fuel level alarms
• 3 configurable maintenance alarms
BENEFITS
• Hours counter provides accurate information for monitoring and maintenance periods
• User-friendly set-up and button layout for ease of use
• Multiple parameters are monitored & displayed simultaneously for full visibility
• The module can be configured to suit a wide range of applications for user flexibility
• PLC editor allows user configurable functions to meet user specific application requirements.
• RS485 Communication port can be used for the Remote Monitoring Communication (Compatible
with Cat PLG)
LEHE2017-02 (09-20)
www.Cat.com/electricpower
©2020 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Corporate
Yellow”, the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
100 Amp Load Center
L1 L2
GFCI 16A (120V) Battery Charger 6A (120V)
Jacket Water Heater 11.25A (240V) Jacket Water Heater 11.25A (240V)
Alternator Heater 1.04A (240V) Alternator Heater 1.04A (240V)
Total Load 28.29A Max Total Load 18.29A Max
www.cat.com/electricpower
©2020 Caterpillar
All rights reserved.
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow,” the “Power Edge”
and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks
LEHE2075-02 (04/20) of Caterpillar and may not be used without permission.
Circuit Breakers
C9 ACERT TM, C13 ACERT, C15 ACERT,
C18 ACERT Circuit Breakers
Manually Operated Circuit Breakers
Current Fram e Num ber Interrupting Ratings (kA rm s)
(A) of Poles Trip (Lugs) Cable Size
Auxiliary Options
240V 480V 600V Units Range / Phase
BUS BAR
3000 R 3 65 35 18
LEHE0942-06 1/18
Circuit Breakers
Single Breaker Options (250 – 3000A)
Model Current (A) Operation
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 600 Manually Operated
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 800 Manually Operated or Electrically Operated
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 1200 Manually Operated or Electrically Operated
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 250 250, 400, 600,
800, or 1200 3rd Breaker:
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 400
250 or 400 (Not
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 600
available if
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 800 1st & 2nd Breaker =
1200A)
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 1200
LEHE0942-06 2/18
Circuit Breakers
Figure 1
L EHE0942-06 3/18
Circuit Breakers
Figure 2
L EHE0942-06 4/18
Circuit Breakers
J-Frame 250 A Typical Peak Let-Through Curves
Figure 3
LEHE0942-06 5/18
Circuit Breakers
J-Frame 150-250 A (JD, JG, JJ, JL, and JR) Thermal-Magnetic
Trip
Figure 4
LEHE0942-06 6/18
Circuit Breakers
Ground Fault Module GFM250JD Trip Curve
Figure 5
LEHE0942-06 7/18
Circuit Breakers
T5 400/ 600 – PR221DS
Figure 6
LEHE0942-05 8/18
Circuit Breakers
T6 600 / 800 -PR221DS
Figure 7
LEHE0942-06 9/18
Circuit Breakers
T6 600 / 800 -PR221DS
Figure 8
LEHE0942-06 10/18
Circuit Breakers
Tmax T7 PR231/P Functions
L-S Functions
Figure 9
LEHE0942-06 11/18
Circuit Breakers
T6 800 - PR222DS and PR222DS/PD-A
Figure 10
LEHE0942-06 12/18
Circuit Breakers
T7 1000/1200 - PR232/P
Figure 11
LEHE0942-06 13/18
Circuit Breakers
T7 1000/1200 - PR332/P
L-S-I Functions
Figure 12
LEHE0942-06 14/18
Circuit Breakers
T8 1600/2000/2500/3000 – PR232/P-T8
L-S-I Functions
Figure - 13
LEHE0942-06 15/18
Circuit Breakers
P, R, NS-Frame Long-Short Trip Curve and NW-Frame Long-
Short Trip Curve
Figure - 14
LEHE0942-06 16/18
Circuit Breakers
P, R, NS-Frame Instant Curve and NW-Frame Instant Trip Curve
Figure 15
LEHE0942-06 17/18
Circuit Breakers
P, R, NS-Frame Ground Curve and NW-Frame Ground Fault Trip Curve
Figure - 16
LEHE0942-06 (05-20)
www.Cat.com/electricpower
© 2020 Caterpillar. All Rights Reserved. CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, "Caterpillar Corporate Yellow", the "Power Edge" and Cat “Modern Hex” trade dress as well
as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission
18/18
Note : The Information on this Document comesfrom a Third Party Sup plier and is not a Caterpillar Material
Attachments
Regulating Safety
Part No Outlet Location Watts Volts Amps Thermostat Thermostat
On 90°F (32°C)
577-1758/578-9355 Right 2700 240 11.25 Off 115°F (46°C) 210°F (98°C)
www.cat.com/electricpower
©2020 Caterpillar
All rights reserved.
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow,” the “Power Edge”
and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks
of Caterpillar and may not be used without permission.
LEHE2077-01 (10/20)
Attachments
AC SUPPLY
VOLTAGE RANGE 90 V to 305 V (L-N)
FREQUENCY RANGE
48 Hz to 64 Hz (L-N)
DC OUTPUT RATING
10 A DC at 24 V DC
EFFICIENCY
>86%
REGULATION LINE
Image shown might not reflect actual configuration
<0.5%
A comprehensive range of input and output protections ensures a continued safe PROTECTIONS
charging environment also enabling the use of the charger as a power supply. Short Circuit
DC Over Voltage
DC Over Current
Reverse Polarity
FEATURES Over Temperature
• Intelligent two, three and four stage charging profiles AC Under & Over Voltage
• Configurable to suit most battery types (12V/24V)
CHARGE FAILURE RELAY
• Adjustable current limit
3 A at 30 V DC volt free relay
• Can be used as a battery charger, power supply or both at the same time
• Automatic or Manual boost and storage charge functions to help maintain battery condition
DIMENSIONS OVERALL
• Digital Microprocessor Technology
70 mm x200 mm x 130 mm
• Temperature compensation for battery charging 2.7” x 7.9” x 5.1”
• Low Output Ripple and superb line regulation
• Three LED Indicators WEIGHT
• AC input Under voltage 0.75 kg
• AC input Over voltage
• Battery charger output Over voltage OPERATING TEMPERATURE RANGE
• Battery charger output Over current -30 °C to +80 °C
• Optional battery temperature compensation with over temperature protection -22 °F to +176 °F
• Output short circuit and Inversion polarity with auto recovery
• Configurable charge termination STORAGE TEMPERATURE RANGE
• UL1236 /UL1564 Compliant -40 °C to +70 °C
-22 °F to +158 °F
Communication
• Can be integrated into external systems through MODBUS RTU using RS485
• Fully configurable via PC Software
BENEFITS
• Fully flexible to maximise the life of the battery
• Suitable for a wide range of battery types
• Switched mode design
BENEFITS
• Minimum 86% efficiency throughout full operating range
• No external intervention for boost mode
• Multiple chargers can be linked together to provide larger current output
• Can be permanently connected to battery and mains (utility) supply. No need to disconnect
through high load conditions.
LEHE2022-02 (10-20)
©2020 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar corporate
Yellow”, the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
GFCI Receptacles
20A Tamper-Resistant,
Weather-Resistant GFCI
Receptacles
www.Cat-ElectricPower.com
©2016 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” trade dress as well as corporate and product identity used
LEHE1085-00 (5-16) herein, are trademarks of Caterpillar and may not be used without permission.
Cat GC ®
Control Panel Options
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical
Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C BS EN 60068-2-2
Bb/Be Dry Heat+70°C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn
The Panels will be fitted with removable label cards which can be used CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least
to identify the standard NFPA alarms. If desired 10 V before dropout and supply recovers to 5 V. This is
achieved without the need for internal batteries. LEDs and
It includes individual LEDs for each channel and a ‘Power On’ LED that backlight will not be maintained during cranking.
flashes when the link with the host controller is lost. MAXIMUM OPERATING CURRENT
112 mA at 12 V, 53 mA at 24 V
8 mm
LEHE2021-01 (03-21)
www.Cat.com/electricpower
©2021 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Corporate
Yellow”, the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Cat GC ®
Control Panel Options
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical
Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C BS EN 60068-2-2
Bb/Be Dry Heat+70°C
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least
10 V before dropout and supply recovers to 5 V. This is
• achieved without the need for internal batteries. LEDs and
backlight will not be maintained during cranking.
DIMENSIONS OVERALL
165 mm x 76 mm x 49 mm
6.5” x 3” x 1.9”
LEHE2020-00 (08-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Cat GC ®
INTEGRAL FUEL TANKS
FEATURES
LEHE2015-01
Cat GC ®
INTEGRAL FUEL TANKS
Integral Fuel Tank Base Useable Capacities with Fuel Tank Dimensions & Weights
Standby Width Width
ekW mm in
250-300 1430 56.3
350-400 1630 64.1
450-500 1630 64.1
550-600 1865 73.4
WIDTH
HEIGHT
LENGTH
The heights listed above do not include lumber used during manufacturing and shipping
Integral FTDW036 2820 744.9 2553 674.4 1165 2568 818.8 32.2 4815 189.5 2584 101.7 2644 104
Tank FTDW037 3671 969.7 3323 877.8 1331 2934 668.2 26.3 4622 181.9 2456 96.7 2644 104
FTDW038 4292 1133.8 3889 1027.3 1657 3653 816.4 32.1 4980 196 2560 100.7 2721 107.1
LEHE2015-02
Cat GC ®
INTEGRAL FUEL TANKS
Tanks with full electrical stub-up area include removable end channel. Tanks with RH stub-up include stubup area directly below the
circuit breaker or power terminal strips.
Fuel tanks and applicable options facilitate compliance with the following United States NFPA Code and Standards:
NFPA 30: Flammable and Combustible Liquids Code
NFPA 37: Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines
NFPA 110: Standard for Emergency and Standby Power Systems
Fuel tanks and applicable options facilitate compliance with the following Canadian Standard and Code:
CSA C282 – Emergency Electrical Power Supply for Buildings
CSA B139-09 – Installation Code for Oil-Burning Equipment
LEHE2015-02 (01-20)
www.Cat.com/electricpower
©2020 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”, the “Power
Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Cat GC ®
ENCLOSURES
FEATURES
Excellent Access
• Large cable entry area for installation ease.
• Accommodates side mounted single or multiple breakers.
• Two doors on both sides.
• Vertically hinged allow 180° opening rotation
• Radiator fill cover.
LEHE2014-02
Cat GC ®
ENCLOSURES
LEHE2014-02
Cat GC ®
ENCLOSURES
Standby
Length, L Width, W Height, H Package Weights
Enclosure Type Ratings,
ekW mm in mm in mm in kg lb
Sound Attenuated Enclosure on 250 2857 6298.6
3958 155.8 1440 56.7 1991 78.4
Skid Base 300 2945 6492.6
350 3983 8781.0
4633 182.4 1630 64.2 2227 87.7
400 4017 8856.0
450 4408 9718.0
4823 189.8 1630 64.2 2777 109.3
500 4457 9826.0
550 4754 10480.8
4980 196.1 1865 73.4 2723 107.2
600 4837 10663.8
Sound Attenuated Enclosure on 250 3497 7709.6
UL Listed Integral Fuel Tank 3958 155.8 1440 56.7 2487 97.9
300 3585 7903.6
Base 350 4765 10505.0
4633 182.4 1630 64.2 2644 104.1
400 4799 10580.0
450 5345 11783.7
4823 189.8 1630 64.2 2777 109.3
500 5394 11891.7
550 5973 13168.2
4980 196.1 1865 73.4 2723 107.2
600 6056 13351.2
LEHE2014-02 (09-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos,
“Caterpillar Yellow”, the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L L
6310 CONTROLLER
J J
I I
H H
B B
M
A
T
NOTE A: FACTORY WIRING NOT PROVIDED AS STANDARD. REFER TO MANUFACTURER INSTALLATION INSTRUCTIONS. L
HT
TR
DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 2X3
- 02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L
CONTROL SCHEMATIC (DSE 6310) L
ADEM A4:E4
A-C3
ECM 160-7689
23 ECU + (J1939)
A-S3
24 ECU - (J1939)
A-S4 CAN+
J1-PIN34 CAN A- 34 Y798-A3 WH-18 A-T13
1 1
120R
CBL-A2:Y798-A1 BK-18 A-T14 1 1
CAN-
Resistor_As_3_Nodes_1 A-T15
1 1 A-T17
134-2540 A-C2
155-2267
J J
A Y797-A20 WH-18 A-C1
265-4123
B Y798-A44 WH-18
CBL-A4:Y798-A1 BK-18 F
C REF [16,F] 208-A22 WH-18 A-T61
1 DC SUPPLY (-)
120 CBL-A4:Y797-A2 WH-18 G
ENGINE SERVICE E-STOP_PANEL REF [10,D] 108-A25 WH-18 A-T62
DC SUPPLY (+)
2
CBL-A4:Y799-A3 CU-20 C CONNECTOR 390--1209
J 22 21
A-T20 A-T22
8 OUTPUT D (SPARE)
A-T7
12 OUTPUT H (SPARE)
CUSTOMER TERMINALS
A-S2
1 1
A-T4
G-T
1
1 1
18 ANALOG INPUT C (SPARE)
F4 SPARE ANALOG INPUT
208-A19 BK-8 422-6095 1 1 (NOTE A) 19 ANALOG INPUT D (SPARE)
BATT+
10A
A-S6
26 DSENET B
REF [3,J] 108-A25 WH-18 EXPANSION DATALINK 27 DSENET A
(NOTE A) 28 DSENET SCR
REF [7,I] 108-A55 WH-18
ALT
A-T41
B+ A-T40
101-A43 WH-10
A A 108-A6 WH-18
B B 208-A18 WH-18 REF [15,G]
C C Y983-A5 WH-18 REF [5,F]
M
A
A-C8 T
L
FUEL LEVEL SENSOR 247-8195 HT
TR
1 1 1E5167A INT-PROP
1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
2 2 P733-A60 WH-18 REF [9,G] 1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
3 3 229-A58 WH-18 REF [5,E] T
E Caterpillar: Confidential Yellow
PROD X OTHER
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY X
A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 2 OF 6
PROJECTION
DWG CONTROL W591
DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L
POWER SCHEMATIC L
CB SHUNT TRIP
STR
352--2951
21 24
22
11 14
A-T70
12
3 PHASE STAR
(6 WIRE) 1200A HARNESS
C2 C1
L1 (U)
L2 (V)
UF-T2
P854-A62 WH-18
K CB1_Y0 CB1_ST+ K
T2
UG-T2
T1
EXCITER
UH-T2
T5
VF-T2
CB2_Y0 CB2_ST-
T4
VG-T2
T6
VH-T2
CONNECT TO CONNECT TO
ALTERNATOR
WF-T2
BREAKER
WG-T2
J T3 J
NF-T2
N-NF1 BK-0
NF-T1
L3 (W) NG-T2
N-NG1 BK-0
NG-T1
NH-T2
OPTIONAL OPTIONAL
N-NH1 BK-0
NH-T1
41 95
41-AX1 WH-16 AX-T7
1 1 95-BK ABB-T21
1 1
44
1
98
1
98
1
UNTRIPPED CB TRIPPED/
(12 WIRE) 44-AX2 WH-16 1 1 98-BK 1 1
AX-T1 AX-T6 ABB-T30 ABB-T25
(SY) 41 UNTRIPPED 95
UC-T1
EXCITER T1 T8
VC-T1
11 11
11-AX4 WH-16 AX-T2
1 1 11-BK ABB-T24
1 1
T10 T5
VE-T1
CONNECT TO CONNECT TO 1 1 1 1
14 14 14 14
CB OPEN/CLOSED
T4 T11 ALTERNATOR WC-T1
T12 T6
12 12 12 12
12-AX6 WH-16 AX-T3
1 1 12-BK ABB-T26
1 1
NC-T1
NE-T1
E T9 T3
H H
L3 (W)
400A HARNESS
1 2
L1-UA1 BK-0 UA-T14
L1
A-T42
A-T43
G G
SERIES STAR 1 2
L2-VA1 BK-0 VA-T2
L2 CUSTOMER LOAD
A-T44
A-T45
(12 WIRE)
1 2
L3-WA1 BK-0 WA-T1
L3
A-T49
A-T46
A-T47
UA-
T6
T2
VA-
T4
A-T50
T1 T5
EXCITER
5+ T4
T8 N-NA1 BK-0 NA-T3
N
T7 T11
E494-A36 WH-18
E495-A35 WH-18
E496-A34 WH-18
E498-A37 WH-18
E498-A38 WH-18
E498-A39 WH-18
200-A63 GN-YL-16 A-T65
F T10
NA-T5
F
A-T
51
T12
GENERATOR GROUND
-6 T9 6310 CONTROLLER
200-A61 GN-YL-16 A-T75
T6
E 41 N/C
T3
CONTROL PANEL DOOR GROUND
E498-A33 WH-16 40 CURRENT SENSING COMMON
A-S1
WA-T3
A-T30
A-T48
39 CURRENT SENSING L3
E E
E495-A35 WH-18 A-T32
38 CURRENT SENSING L2
NE LINK CABLE
E494-A36 WH-18 A-T33
37 CURRENT SENSING L1
F1
GN/YL GN/YL 7W-0482
E486-A66 WH-18
A-T57
29 VOLTAGE SENSING L1
30 VOLTAGE SENSING L2
D D
BASEFRAME
F3
GROUND 7W-0482
31 VOLTAGE SENSING L3
32 VOLTAGE SENSING N
C C
STANDARD
SHUNT EXCITATION
D350 AVR
6- 3 F-
0V
5+ 6 F+
AI1
CONNECT TO T7 9 4 X1
0V
B CONNECT TO T12 10 2 X2 B
RTD
5 Z1
0V
1 Z2
DI1
0V M
A
T
L
D02 HT
TR
D01
1E5167A INT-PROP
1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
CONNECT TO T1 U 1 U T
E Caterpillar: Confidential Yellow
PROD X OTHER
CONNECT TO T2 V 2 V S1
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY
A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
SHEET 3 OF 6
CONNECT TO T3 W 3 W S2
THIRD ANGLE
PROJECTION
DWG CONTROL W591
DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L L
ADDITIONAL OPTIONS
OPTIONAL
VFC FOR GENSET RUNNING AND GENERAL FAULT
K K
14 11
12
24 21
22
I I
OPTIONAL
REMOTE ANNUNCIATOR
2548 CONTROLLER
G G
120R
2548 CONTROLLER
BATT+
1 1
F F
1 1
AN-T7
CUSTOMER CONNECTIONS: 1 1
AN-T8
TO BE CONNECTED IN SERIES 1 1
AN-T9
1 1
AN-T10
E E
D D
C C
B B
M
A
T
L
HT
TR
1E5167A INT-PROP
1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
T
E Caterpillar: Confidential Yellow
PROD X OTHER
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY
A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 4 OF 6
PROJECTION
DWG CONTROL W591
DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L L
ADDITIONAL OPTIONS
OPTIONAL
ALTERNATOR HEATER
AHR
352-2951
K K
REF [16,I] 208-RC36 WH-18 RC-T2 RC-T1
11 14
1 AH_L1 12
RC-T10
AC719-RC39 WH-18 RC-T5
6A CF-T4
AC104-CF2 WH-14
1 1
2
F8
1 1 190-2558
AH_L2
HTR-H2 1 1 RC-T13
AC720-RC40 WH-18 RC-T6
6A CF-T3
AC103-CF1 WH-14
J J
OPTIONAL
BATTERY CHARGER
1 1 572-0792
BATTERY_CHARGER
BATT+
1 1 ER-T13
108-ER1 WH-14 ER-T1
OP+
1 1 ER-T12
208-ER2 WH-14 ER-T2
OP-
I BATT- I
REF [16,K] 208-RC36 WH-18 RC-T4
1 1
NC
COM
NO
NTC
NTC_1
6310 CONTROLLER
120R
8 OUTPUT D (GENSET RUNNING) RC-T3
A309-RC35 WH-18 REF [13,K] LK1
H NOTE C LK1_1 H
26 DSENET B ER-T16
CBL-ER1:B-1 GN-18 ER-T6
B
27 DSENET A ER-T17
CBL-ER1:A-2 YL-18 ER-T7
A
28 DSENET SCR ER-T18
CBL-ER1:SCR-3 CU-18 ER-T8
SCR
GND_1
AC199-ER45 WH-14 ER-T20
N
1 1 F9 AC102-ER44 WH-14 ER-T21
L
GND 422-6095
G 200-CE3 GN-YL-14 CE-T8
1 1 ER-T26
G
ER-T23
10A ER-T22
1 1
1 1
BC_L1
AC101-CE1 WH-14 CE-T6
1 1 ER-T24
AC101-ER43 WH-14
F F
E OPTIONAL E
LOAD CENTER BOX
CE-T13
CD-T3
NEUTRAL
BATT_CHRG_BREAKER
508-6697
20A CE-T18
AC101-CE1 WH-14
ALT_HTRG_BREAKER
577-8557
AC103-CF1 WH-14
L1 CF-T2
CUSTOMER 15A
CF-T1
AC104-CF2 WH-14
D CONNECTION GFCI_RECEPTACLE D
240V 3WIRES 423-7031
GFCI_BREAKER
508-6697
BK (LINE)
L2 20A CD-T2
AC101-CD1 WH-12 CD-T4
WH (N) CD-T5
AC199-CD3 WH-12 REF [14,E]
JWH_BREAKER
577-8557
CONNECT
JACKET WATER GND
CD-T6
15A
HEATER WIRES
200-CE3 GN-YL-14 200-CD2 GN-YL-10
CE-T11
CD-T1
C C
200-CD4 GN-YL-10
CD-T7
MAIN CUSTOMER
GROUND
B B
M
A
T
L
HT
TR
1E5167A INT-PROP
1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
T
E Caterpillar: Confidential Yellow
PROD X OTHER
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY
A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 5 OF 6
PROJECTION
DWG CONTROL W591
DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
DC FUSES
J J
GROUND FAULT
REM_STRT
CLN_GND
ESTOP_A
ESTOP_B
CAN_SH
BATT +
BATT +
CB2_95
CB2_96
CB2_98
BATT -
BATT -
BATT -
CB1_14
CB2_11
CB2_12
CB2_14
CB1_11
CB1_12
CB1_95
CB1_41
CB1_96
CB1_42
CB1_98
CB1_44
CAN +
CAN -
C1 C1 C2 C2
I I
H H
F F
D D
F7 F8 F9
AHR
BC_L1
AH_L1
AH_L2
BC_N
GND
C C
B COMPONENT DESCRIPTION B
AHR ALTERNATOR SPACE HEATER RELAY
AH_L1 ALTERNATOR HEATER AC SUPPLY L1
AH_L2 ALTERNATOR HEATER AC SUPPLY L2
F7 ALTERNATOR HEATER FUSE L1 (6A)
F8 ALTERNATOR HEATER FUSE L2 (6A) M
A
GND SHORE POWER GROUND T
L
HT
F9 BATTERY CHARGR FUSE L1 (10A) TR
A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 6 OF 6
PROJECTION
DWG CONTROL W591
DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1