ACB
Air Circuit Breakers
Premium Susol/Metasol ACB meets your demands for high breaking capacity, fully line-up,
and optimized panel size.
Various accessories and connection methods realize user-friendly handling.
Susol/Metasol provides you with total solutions with an advanced trip relay for measurement,
diagnosis, analysis, and communication as well as protective functions for absolute protective
coordination and electric power monitoring system.
Contentsts
▪Overview 4
▪External configuration 22
▪Internal configuration 24
▪Ordering 26
▪Ratings 34
▪Trip relays 42
▪Accessories 72
▪Electrical diagram 110
▪Dimensions 118
▪Technical information
- Insulation voltage 143
- Temperature derating 144
- Operating conditions 145
- Installation recommendation 146
- Protective coordination 152
▪Standards & Approval 160
▪Time chart 161
▪Ordering sheet 165
series
Susol / Smart
Molded Case Circuit Breakers
5
Super solution
Air circuit breaker is to be installed in low voltage distribution line to break the circuit
when over current, short circuit, or ground fault occurs in order to protect user and
other subordinate components.
6
Susol ACB Smart
SUPER SUPER
Optimum
Life span coordination
SUPER SUPER
Brraking
capacity Performance
7
Full line-up & Compact
Up to 6300A, Susol ACB provides fully lined-up 3 frame.
For each frame, there is just one size, which is smaller and more compact.
It makes it possible for you to design the optimized volume panel.
W = 334mm W = 412mm
85kA
AH-06~20D
100kA
AH-06~40E
06 630AF 06 630AF 20 2000AF
08 800AF 08 800AF 25 2500AF
10 1000AF 10 1000AF 32 3200AF
13 1250AF 13 1250AF 40 4000AF
16 1600AF 16 1600AF
20 2000AF
Icu=Ics=100kA/500Vac
Icu=Ics=85kA/500Vac W=412(3p), 527(4p)mm
W=334(3p), 419(4p)mm
8
4000 ~ 6300 AF
D
=
37
5m
m
W = 785mm
9
Trip Relay Trip relays are classified according to function.
Trip relays are classified according to their usages and functions to maximize
customers’ satisfaction. Classified trip relays and easy installation.
• Protection: o
verload, short current, ground fault, earth leakage, under voltage, over
voltage, under frequency, over frequency, reverse power, unbalance, etc
• Measurement: voltage, ampere, power, energy, frequency, power factor, Harmonics, etc.
• Event & fault recording: Max. 256 events & faults
• Communication: Modbus/RS-485, Profibus-DP
Susol ACB Trip Relay functioning world-best protection can be interlocked with mechanism.
It makes the breaking capacity of ACB improved and ACB’s life enhanced, and provides
advanced functions - measurement, diagnosis, analysis, and communication.
10
Susol ACB Trip relay
N A N P A SN P A SN P A S P S
type type type type type type
type type type type
typetype type type type type
11
Meta Solution
Meta Solution
Meta solution
Meta Solution
Meta Solution
Air circuit breaker is to be installed in low voltage distribution line to break the circuit when
over current, short circuit, or ground fault occurs in order to protect user and other
subordinate components.
12
Metasol ACB
Smart
Meta Meta
Optimum
Life span coordination
Meta Meta
Brraking
capacity Performance
W = 334mm W = 412mm
(65kA) (70kA)
70kA
AN-06~16D AS-06~20D
85kA
AS-20~40E
06 630AF 06 630AF 20 2000AF
08 800AF 08 800AF 25 2500AF
10 1000AF 10 1000AF 32 3200AF
13 1250AF 13 1250AF 40 4000AF
16 1600AF 16 1600AF Icu=Ics=85kA/500Vac
Icu=Ics=65kA/500Vac 20 2000AF W=412(3p), 527(4p)mm
W=334(3p), 419(4p)mm Icu=Ics=70kA/500Vac
W=334(3p), 419(4p)mm
14
5000 AF (AS) 4000 ~ 6300 AF (AS)
m
5m
37
=
D
W = 629mm W = 785mm
100kA 120kA
AS-50F AS-40~63G • The highest breaking capacity:
40 4000AF 40 4000AF
150kA (6300AF at 500Vac)
50 5000AF 50 5000AF
Icu=Ics=100kA/500Vac 63 6300AF • 4 ampere frame sizes:
W=629(3p), 799(4p)mm Icu=Ics=120kA/500Vac 2000/4000/5000/6300AF
W=785(3p), 1015(4p)mm
• N phase current conducting capacity: 100%
15
Trip Relay Trip relays are classified according to function.
Trip relays are classified according to their usages and functions to maximize
customers’ satisfaction. Classified trip relays and easy installation.
• Protection: o
verload, short current, ground fault, earth leakage, under voltage, over voltage,
under frequency, over frequency, reverse power, unbalance, etc
• Measurement: voltage, ampere, power, energy, frequency, power factor, Harmonics, etc.
• Event & fault recording: Max. 256 events & faults
• Communication: Modbus/RS-485, Profibus-DP
Metasol ACB Trip Relay functioning world-best protection can be interlocked with mechanism.
It makes the breaking capacity of ACB improved and ACB’s life enhanced, and provides
advanced functions - measurement, diagnosis, analysis, and communication.
16
Metasol ACB Trip relay
N A N P A SN P A SN P A S P S
type type type type type type
type type type type
typetype type type type type
17
Accessories
ACB
Trip Relay Mechanical Interlock (MI)
Motor (M) Auxiliary Switch (AX)
Closing Coil (CC) Key Lock (K1),
Shunt Coil (SHT) Double Key Lock (K3)
Under Voltage Trip Device (UVT) Counter (C)
Door Interlock (DI) On/Off Button Lock (B)
MOC (Mechanical Miss Insertion Preventing Device (MIP)
Operated Cell Switch) Manual Reset Button (MRB)
18
Cradle Other
Safety Shutter (ST) Mechanical Interlock (MI) Condenser Trip Device (CTD)
Manual Connector Miss Insertion Prevent Device (MIP) Door Frame (DF)
Zero Arc Space (ZAS) Body Supporter (BSP) Dust Cover (DC)
Insulation Barrier (IB) Shorting "b" Contact (SBC) i-Tester (IT)
Cell Switch (CEL) Safety Control Cover (SC) ATS Controller (ATS)
Door Interlock (DI) Racking Interlock (RI) Lifting Hook (LM)
MOC (Mechanical Safety Shutter Lock (STL) Dummy ACB
Operated Cell switch) UVT Time Delay Controller (UDC)
Gateway/Data Logger
Profibus-DP
Temperature Alarm
19
Connection
and Installation
Diverisified terminal connection methods of the ACB main circuit for users.
20
Multiple connections
Various installation methods
Standard
connection
Mixed
connection
Horizontal / Vertical type Vertical / Horizontal type Horizontal / Front type Note2)
Vertical / Front type Note2) Front / Horizontal type Note2) Front / Vertical type Note2)
•The Front connection type is suitable for the panel that demands narrow depth for stallation.
•The connection can be modified between vertical type and horizontal type by rotating the
terminals through 90 degrees for the breakers such as AN-06~16D, AS-20E~32E,
AH-06D~20D, AH-06E~32E.
※ AS-20D, AH-20D, AS-40E, AH-40E types are equipped with vertical terminals only.
• Please refer to the rating lists (Page 34~37) because the installation method is various according to the rated current.
Note) 1. If P-type is selected, the ACB is shipped without flat type terminal, and the flat type terminal must be purchased separately.
2. For using the mixed connection type which includes flat type terminals, the mixed terminal kit must be purchased separately.
21
External configuration
❸ OFF button
❸ ❹ ON button
❺ ❺ Series name
❹ ❻ Charge handle
❶ ❻ ❼ Rated name plate
❽ Charge/Discharge indicator
❾ ON/OFF indicator
❼
❿ Corporation logo
❸
❹
❿
❶ ❻
❼
❺
❽
❾
❷
22
Susol / Metasol ACB
Terms
❹
❺
❻ ❶ Safety control cover ❻ Handle inserting hole
❼ ❷ Cradle finger ❼ Pad lock button
❸ Cradle finger ❽ Connecting terminal
❹ Draw-out handle ❾ Connecting terminal
❺ Position indicator
23
Internal configuration
Terms
❶ Arc chute
❷ Aux. switch control terminal
❶
❿ Shunt coil
❺
❻
Closing coil
❼
Motor Ass’y
Aux. switch
❽ ON button
OFF button
MTD base
❾
Trip relay
Front cover
24
Susol / Metasol ACB
Terms
❶ ❶ Control circuit terminal block
❷ ❷ Control terminal
❸ Auxiliary switches
❸ ❹ Closing, Shunt, UVT coil
❺ Trip relay
❹ ❻ Front cover
❺ ❼ Mechanism
❽ Charge handle
❾ Trip spring
❻
❿ Closing spring
Draw-in/out device
❼ Arc chute
❽ Moving contact
Fixed contact
❾
Terminal on line side
Cradle finger
❿ Cradle
Connecting terminal
Power supply CT
Terminal on load side
25
Ordering
AH 10 D 3 10 A
* 2000AF only offers with vertical type mounting terminals 13 1250A Mixed type
(Busbar). M
16 1600A Horizontal
20 2000A Vertical
Mixed type
N Vertical
06 630AF 630~4000AF 3 3P(E) 02 200A
Horizontal
08 800AF E 3P/4P Standard 4 4P(E, X) 04 400A
P Front type
10 1000AF RST(N) 06 630A
13 1250AF 630~4000AF 4P 08 800A
16 1600AF X Reverse phase 10 1000A
20 2000AF type (N)RST 13 1250A
25 2500AF 16 1600A
32 3200AF 20 2000A
40 4000AF 25 2500A
* 4000AF only offers with vertical type mounting terminals 32 3200A
(Busbar).
40 4000A
4000/5000/6300AF
Z 4P Reverse phase
type (N)RST
AT 20 D 3 00 U
* Rated short-circuit withstand current of the protective circuit in earthing product : 60kA/1s * Please contact us to get more detail information of earthing product.
26
Susol / Metasol ACB
M1 D1 D1 AX NG0 U1 AL
Closing coil rated voltage Aux.contact & charging types UVT coil rated voltage
27
Ordering
AS 10 D 3 10 J
AT 20 D 3 00 U
* Rated short-circuit withstand current of the protective circuit in earthing product : 60kA/1s * Please contact us to get more detail information of earthing product.
28
Susol / Metasol ACB
M1 D1 D1 AX NG0 U1 AL
Closing coil rated voltage Aux.contact & charging types UVT coil rated voltage
29
Ordering
Susol cradle
AL H16D 3 A H E S
A S
Connection Mixed type Arc cover
Manual Line: Vertical
J N
Connection Load: Horizontal
(20D inapplicable)
Front type
P (20D, 40E, 50FG, 63G
Note) 1. AH Series: S(with Arc cover) only. inapplicable)
2. AH-20D, AH-40E types are equipped with vertical-only terminals.
3. Front connection terminals should be purchased separately (see Page 68.)
30
Susol / Metasol ACB
Metasol cradle
AL N16D 3 J H E N
Front type
P (20D, 40E, 50FG, 63G
inapplicable)
Note) 1. AS-20D, AS-40E types are equipped with vertical-only terminals.
2. Front connection terminals should be purchased separately (see Page 68.)
31
Ordering
N G 0
Trip relay type Communication & protection Control voltage & frequency
N G 0
000 Without trip relay G Ground fault 0 Self-Power Note) 60Hz
N Normal * L/S/I/G configuration as standard 5 Self-Power Note) 50Hz
- with LED indicators
Note) L/S/I/G(or EL) configuration as standard
- without output contacts (Only. Unable to select ground fault and
* Ground fault system by vector sum earth leakage, simultaneously)
A G 0
A Ammeter G Ground fault 0 Self-Power 60Hz
Z Earth Leakage(External CT, Earth Leakage below 30A) 1 AC/DC 100V~250V 60Hz
E Earth Leakage(External CT, Earth Leakage over 30A) 2 DC 15V~60V 60Hz
C Ground fault + Comm. 5 Self-Power 50Hz
K Earth Leakage(External CT, Earth Leakage below 30A) + Comm. 6 AC/DC 100V~250V 50Hz
X Earth Leakage(External CT, Earth Leakage over 30A) + Comm. 7 DC 15V~60V 50Hz
N** Ground fault (External NCT) + Comm.
* L/S/I/G(or EL) configuration as standard
(Only. Unable to select ground fault and earth leakage, simultaneously)
* Ground fault system by vector sum(G,C)
* Earth leakage system
- Z,K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF)
- E,X: External CT - Private ZCT applied(faullt current >30A, 2000AF)
* Comm. And output contacts DO NOT work under self-power condition.
(Only checking LED available)
** A
N provide the function to detect and protect the ground fault current by applying the
NCT (Neutral CT) in the neutral wire when 3pole circuit breaker is used in 3-phase 4-wire
system. Please use NCT with the secondary output of 5A rating. (NCT is not provided)
P S 1
Trip unit type Relay function / Communtation fuction(Default) Frequency Control power
Communication
P Power meter S L,S,I,G + PTA (Main Circuit) voltage
S S 1
Trip unit type Relay function / Communtation fuction(Default) Frequency Control power
Communication
(Main Circuit) voltage
S Supreme meter S L,S,I,G + PTA
1 60Hz AC/DC 100V~250V Bluetooth/NFC
J L,S,I,Gext + ZCT
6 50Hz AC/DC 100V~250V Bluetooth/NFC
Y L,S,I,Gext + Ground wire CT
O L,S,I,G + Neutral CT
* Self-power is Default (Automatic power supply to the Trip Unit without additional control power) Item Description Features Remark
* L,S,I: Long time delay trip, Short time delay trip, Instantaneous trip
TOTAL ASS'Y,VDM(Shield Cable), Separate
* G: Ground fault (Residual earth fault protection) 72313460708 Accessory
EXTERNAL, STU purchasing
* Gext + ZCT: Earth leakage protection (Earth Fault Current: 0.5A ~ 30A) – Only suitable for under 1600A
products and cables * I f you want to apply external VDM separately, please order the code above.
* Gext + Ground wire CT: Source return Type * PTA: Pre-trip alarm Function
* Customers must purchase their own Ground wire CT (Secondary output: 5A, accuracy 1%)
* Customers must purchase their own Neutral CT (Primary output: same as ACB's Rated Current / Secondary
output: 5A, accuracy 1%)
* The STU acceptable voltage range is 100 to 250V.
* If you want an external VDM, please insert '(-V)' at the end of the full ordering.
32
Susol / Metasol ACB
33
Ratings
D 300×300×295
4P 300×385×295
W
34
Susol / Metasol ACB
AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G
630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
200, 400, 630, 630, 800, 1000, 1250, 1600, 2000, 2000, 2500, 3200,
400, 630 800, 800, 1000, 1250, 1600, 2000, 2500, 2500, 3200, 4000,
630 800, 1000 1000, 1250, 1600, 2000, 2500, 3200, 3200, 4000, 5000,
(800) 1250 1600, (1600) 2000 2500 3200 4000, (3200) 4000 5000 6300
0.4 ~ 1.0
630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
1,000 1,000
690 690
12 12
50/60 50/60
3/4 3/4
100 150
100 150
85 100
100% 100%
220 330
220 330
187 220
85 100
75 85
65 75
Less than 25ms under Icw/Less than 75ms over Icw Less than 25ms under Icw/Less than 75ms over Icw
80ms under 90ms under
15,000 10,000
5,000 2,000
-
- -
- -
87/103 107/139 181/223 186/230
85/101 102/145 179/221 184/228
44/55 65/85 97/117 102/124
44/55 61/81 98/123 103/130
42/53 60/80 96/121 101/128
430×412×375 460×785×375
430×527×375 460×1015×375
300×378×295 300×751×295
300×493×295 300×981×295
N, A, P, S type N, A, P, S type
KS / KEMA / KERI / GOST / CCC KS / KEMA / KERI / GOST / CCC
LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK
※ Derating of the rated current is required according to the ambient temperature around the breaker in a panel if it is higher than
the reference value. (See pages 123 to 126)
※ It is possible to connect power and load side reversely, but please use it for normal connection for maintenance and safety.
35
Ratings
Susol Switch-Disconnector
Rated current of neutral pole (A) 630 800 1000 1250 1600 2000
4P 300×385×295
W
36
Susol / Metasol ACB
1,000
690
12
50/60
3/4
187
85
75
65
Under 40ms
Under 80ms
15,000
5,000
-
-
-
87/103 107/139
85/101 102/145
44/55 65/85
44/55 61/81
42/53 60/80
430×412×375
430×527×375
300×378×295
300×493×295
※ Derating of the rated current is required according to the ambient temperature around the breaker in a panel
if it is higher than the reference value. (See pages 123 to 126)
37
Ratings
4P 300×385×295
W
38
Susol / Metasol ACB
AS-06D AS-08D AS-10D AS-13D AS-16D AS-20D AS-20E AS-25E AS-32E AS-40E AS-40F AS-50F AS-40G AS-50G AS-63G
630 800 1000 1250 1600 2000 2000 2500 3200 4000 4000 5000 4000 5000 6300
200, 200, 630, 630, 800, 1000, 200, 400, 1250, 1600, 2000, 2000, 2500, 2000, 2500, 3200,
400, 400, 800, 800, 1000, 1250, 630, 800, 1600, 2000, 2500, 2500, 3200, 2500, 3200, 4000,
630 630, 1000 1000, 1250, 1600, 1000, 1250, 2000, 2500, 3200, 3200, 4000 4000, 3200, 4000, 5000,
800 1250 1600 2000 1600, 2000 2500 3200 4000 (3200, 4000) 5000 4000 5000 6300
0.4 ~ 1.0 0.4 ~ 1.0 0.4 ~ 1.0 0.4 ~ 1.0
630 800 1000 1250 1600 2000 2000 2500 3200 4000 4000 5000 4000 5000 6300
※ Derating of the rated current is required according to the ambient temperature around the breaker in a panel if it is higher than
the reference value. (See pages 123 to 126)
※ It is possible to connect power and load side reversely, but please use it for normal connection for maintenance and safety.
39
Ratings
Metasol Switch-Disconnector
Fixed type
D
4P 300×385×295
W
40
Susol / Metasol ACB
DS-06D DS-08D DS-10D DS-13D DS-16D DS-20D DS-20E DS-25E DS-32E DS-40E
630 800 1000 1250 1600 2000 2000 2500 3200 4000
200, 400, 630, 630, 800, 1000, 200, 400, 630, 1250, 1600, 2000,
400, 630, 800, 800, 1000, 1250, 800, 1000, 1600, 2000, 2500,
630 800 1000 1000, 1250, 1600, 1250, 1600, 2000, 2500, 3200,
1250 1600 2000 2000 2500 3200 4000
0.4~1.0 0.4~1.0
630 800 1000 1250 1600 2000 2000 2500 3200 4000
1000 1000
690 690
12 12
50/60 50/60
3/4 3/4
143 187
65 85
50 75
42 65
Under 40ms Under 40ms
Under 80ms Under 80ms
20000 15000
5000 5000
- -
- -
- -
63/74 70/85 87/103 107/139
61/72 68/83 85/101 102/145
29/32 33/40 44/50 65/85
34/44 38/47 44/55 61/81
32/42 36/45 42/53 60/80
430×334×375 430×412×375
430×419×375 430×527×375
300×300×295 300×378×295
300×385×295 300×493×295
※ Derating of the rated current is required according to the ambient temperature around the breaker in a panel
if it is higher than the reference value. (See pages 123 to 126)
41
Trip relay
The trip relay of Susol ACB provides the additional protection
functions for voltage, frequency, unbalance, and others in
addition to main protection functions for over current, short-
circuit, ground fault. It supports the advanced measurement
functions for voltage, current, power, electric energy,
harmonics, communication function, and others.
Analog trip function interlocked with mechanism enhanced a
durability of devices as well as the breaking capacity of ACB.
Zone selective interlocking function makes the protective
coordination more simple and thermal memory can be
applied to various loads.
Contents
Trip relay types 43
N type:「Normal」 type 44
A type:「Ammeter」 type 46
P type:「Power meter」 type 48
S type:「Supreme meter」 type 50
Operation characteristic 52
Measurement function 54
Man machine interface 55
Protection element setting 56
Measurement element display 57
Characteristic curves 58
ZSI - Zone Selective Interlocking 63
Remote reset and digital I/O 64
Communication 65
Event & fault recording 66
System information 66
System block diagram 67
42
42
Trip relays Susol / Metasol ACB
Externals
•L / S / I / G / Thermal •L / S / I / G(or EL) • L (N), S, I, G, PTA, Gext • L (N), S1, S2, I, G, PTA, Gext
Current •Thermal • D, S (V), IU • D, S (V) 1, S (V) 2
protection •ZSI (Protective coordination)
• Over/Under voltage • Over/Under voltage
• Over/Under frequency • Over/Under frequency
Other protection - - • Unbalance (Voltage/Current) • Unbalance (Voltage/Current)
• Reverse power • Reverse power
• Current (R / S / T / N) • 3 phase voltage, line - to - line voltage • 3 phase voltage, line - to - line voltage
• Current [R/S/T/N] • Current [R/S/T/N]
• Frequency • Frequency
• External CT current • External CT current
• Voltage/Current phase (A phase • Voltage/Current phase (A phase
voltage standard) voltage standard)
• Total/Each phase power [P, Q, S] • Total/Each phase power [P, Q, S]
• Total/Each phase power factor • Total/Each phase power factor
Measurement • Positive/Negative, Effective/ • Positive/Negative, Effective/
- Reactive/Apparent energy Reactive/Apparent energy
function • Vector Sum zero sequence voltage • Vector Sum zero sequence voltage
• Vector Sum zero sequence current • Vector Sum zero sequence current
• Positive, Negative sequence voltage • Positive, Negative sequence voltage
• Steady, Negative sequence current • Steady, Negative sequence current
• Imbalance negative sequence voltage • Imbalance negative sequence voltage
• Imbalance negative sequence current • Imbalance negative sequence current
• Previous current demand for each phase • Previous current demand for each phase
•P revious apparent, reactiveand active •P revious apparent, reactiveand active
power demand power demand
Fine adjustment - - • L, S, I Pickup Current • Can be set by touch
Pre Trip Alarm - - - -
• 3DO (Fixed)
Digital Output - • L, S/I, G Alarm - -
• Supports L relay element • Supports L relay element
IDMTL setting - - Thermal (N type) Thermal (N type)
• Modbus / RS-485 • USB[For site operator] • USB[For site operator]
• Profibus-DP • RS485 / Modbus • RS485 / Modbus
Communication - • BLE(bluetooth, option) • BLE(Bluetooth)
• Ethernet(Option) • NFC(Near Field Communication)
• Ethernet(Option)
•Self Power •Self Power • AC/DC 100~250V • AC/DC 100~250V
- Power source works over 20% - Power source works over 20% * Basic
protection function * Basic
protection function
of load current. of load current. (L / S / I / G) is still under normal (L / S / I / G) is still under normal
Power supply - External power source are operation without control operation without control
required for comm. power. power.
• AC/DC 100~250V
• DC 15~60V
•Available •RTC embedded
RTC timer - (Back up with battery) -
• Long time delay • Long time delay • L, S, I, G/Gext/PTA, SP • L, S, I, G/Gext/PTA, SP
LED for • Short time delay/Instantaneous • Short time delay/Instantaneous
trip info. • Ground fault • Ground fault
•10 records •Display of 127 incident •Display of 127 incident
Screen (Fault/Current/Date and Time) events [Incident zero events [Incident zero
sequence/current/time] sequence/current/time]
Fault -
recording •Saves 127 incident events •Saves 127 incident events
•Saves 6 incident waveforms •Saves 6 incident waveforms
Memory [In case of operation by Self [In case of operation by Self
Power, incident] Power, incident]
•2
55 kinds including change •2
55 kinds including change
Event recording - - of device status [Information, of device status [Information,
status, date and time) status, date and time)
•Reset button • Reset, Menu •R
eset button •R
eset button
Operating button Up/Down, Tap, Enter •L
CD Touch •L
CD Touch
Each OCR type has Battery in itself. * L/S/I/G(or EL)configuration as standard
1. Battery lifespan 2. The display minimum range of OCR current (Only. Unable to select ground fault and
1) When turned off: 14~28years 1) A type: When more 15% than rated current (In) earth leakage, simultaneously)
2) When using 1 LED consecutively or turned off: 7~14days 2) P/S type: When more 12% than rated current (In)
43
Trip relays
Isd
Alarm SP Ir Ii Ig
② ③ Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting
⑥ Ig: Ground fault current setting, tg: Ground fault tripping delay setting
③
⑦ Test terminal: OCR test terminal (Connected with OCR tester)
④
⑤
⑥
⑦
44
Susol / Metasol ACB
Protection
Long time
Current setting (A) Iu = In×... 0.5 0.6 0.7 0.8 0.9 1.0
Ir = Iu×... 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1.0
Time delay (s) tr@(1.5×lr) 12.5 25 50 100 200 300 400 500 Off
Accuracy: ±15% or tr@(6.0×lr) 0.5 1 2 4 8 12 16 20 Off
below 100ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 Off
Short time
Current setting (A) Isd = Ir×... 1.5 2 3 4 5 6 8 10 Off
Time delay (s) I2t Off 0.05 0.1 0.2 0.3 0.4
tsd
Accuracy: ±15% or I2t On @(10×Ir) 0.1 0.2 0.3 0.4
below 50ms Min. Trip
20 80 160 260 360
Time(ms)
(I t Off)
2
Max. Trip
80 140 240 340 440
Time(ms)
Instantaneous
Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 Off
Tripping time below 50ms
Ground fault
Pick-up (A) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 Off
Time delay (s) I t Off
2
0.05 0.1 0.2 0.3 0.4
tg
Accuracy: ±10%(Ig≥0.4In) I2t On @(10×Ir) 0.1 0.2 0.3 0.4
±20%(Ig≺0.4In) Min. Trip
20 80 160 260 360
or below 50ms Time(ms)
(I2t Off)
Max. Trip
80 140 240 340 440
Time(ms)
45
Trip relays
Isd
Alarm SP Ir Ii Ig Comm
②
Reset
Esc
③
Reset/ESC: Fault reset or ESC from menu
Enter: Enter into secondary menu or setting input
④ Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting
⑦
⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting
⑧
⑥ Ii: Instantaneous current setting
⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting
46
Susol / Metasol ACB
Protection
Long time
Current setting (A) Iu = In×... 0.5 0.6 0.7 0.8 0.9 1.0
Ir = Iu×... 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1.0
Time delay (s) tr@(1.5×lr) 12.5 25 50 100 200 300 400 500 Off
Accuracy: ±15% or tr@(6.0×lr) 0.5 1 2 4 8 12 16 20 Off
below 100ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 Off
Short time
Current setting (A) Isd = Ir×... 1.5 2 3 4 5 6 8 10 Off
Time delay (s) I2t Off 0.05 0.1 0.2 0.3 0.4
tsd
Accuracy: ±15% or I2t On @(10×Ir) 0.1 0.2 0.3 0.4
below 50ms Min. Trip
20 80 160 260 360
Time(ms)
(I2t Off)
Max. Trip
80 140 240 340 440
Time(ms)
Instantaneous
Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 Off
Tripping time below 50ms
Ground fault
Pick-up (A) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 Off
Time delay (s) I t Off
2
0.05 0.1 0.2 0.3 0.4
tg
Accuracy: ±10%(Ig≥0.4In) I2t On @(10×Ir) 0.1 0.2 0.3 0.4
±20%(Ig≺0.4In) Min. Trip
20 80 160 260 360
or below 50ms Time(ms)
(I2t Off)
Max. Trip
80 140 240 340 440
Time(ms)
47
Trip relays
1) RUN/AL
- RUN: Indicating the operation(Blinking blue LED during turn on)
① - AL: Indicating an overload(Turn on above 90%, Blink above 105%)
- Self diagnose error: Blinking blue and red LED
2) SP/ERMS
- Override/MCR operation: Red LED
- ERMS operation: Blue LED
3) COMM: Communication display LED(green)
4) Ir: LED Display for long-time over current relay operation
5) Isd/Ii: LED Display for short-time/INSTANTANEOUS OVER CURRENT Relay Operation
6) G/PTA: LED displaying operation for Ground/Leakage fault protection relay, PTA
②
④ Fault Reset/Esc Key: Fault/LED reset, Return to menu, Battery tes
⑥ ⑧ Rating plug
⑩ ⑪
48
Susol / Metasol ACB
Long time
Threshold (A) Ir = Iu×... 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Trip between 1.05 and 1.2 Ir
Time delay (s) tr@(1.5×lr) 12.5 25 50 100 200 300 400 500 Off
Accuracy : ±10% (Ir < 6In), tr@(6.0×lr) 0.5 1 2 4 8 12 16 20 Off
±20% (Ir ≥ 6In),
or ±40ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 Off
Note) 1. See manual for checking IDTML and equations. 2. Time tolerance should add +40ms for L/S/I/G, if power does not supply to the trip unit.
3. Threshold(A) value can be adjusted in 1A by touch LCD.
Short time
Threshold (A) Tolerance: ±10% Isd = Ir×... 1.5 2 3 4 5 6 8 10 Off
If time delay (s) I²t Off 0.05 0.1 0.2 0.3 0.4
Accuracy I2t On:chose largest tsd
I²t On@(10×Ir) 0.1 0.2 0.3 0.4
value between, ±15% (Is ≤
6In), ±20% (Is > 6In), Min. Trip Time (ms) 20 80 160 260 360
(I²t Off)
or ±40ms Max. Trip Time (ms) 80 140 240 340 440
ZSI ZSI Time (s) 0.04 ~ 0.2 (0.01s steps), OFF
Start up Pick up (A) Above 1.2×Isd (10A steps)
Time delay (s) 0.1 ~ 30 (0.01s steps), OFF
Note) Threshold(A) value can be adjusted in 1A by touch LCD.
Instantaneous
Threshold (A) Tolerance: ±10% Ii = In×... 2 3 4 6 8 10 12 15 Off
Trip time Under 50ms
Start up Pick up (A) Above 1.2×Isd (10A steps)
Time delay (s) 0.1 ~ 30 (0.01s steps), OFF
Note) Threshold(A) value can be adjusted in 1A by touch LCD.
Ground fault
Threshold (A) Tolerance: ±10% Ig = In×... 0.2 ~1.0 (1A steps), OFF
If time delay (ms)
Accuracy I2t Off: chose largest
value between, ±10% or ±40ms I2t can choose On/Off
tg
If I2t On (@30 A): chose largest 0.05 ~ 3.0 (0.01s steps)
value between, ±25% or
±40ms
ZSI ZSI Time (s) 0.04 ~ 0.2 (0.01s steps), OFF
Start up Pick up (A) Above 1.2×Isd (10A steps)
Time delay (s) 0.1 ~ 30 (0.01s steps), OFF
Note) 1. Ig cannot adjust over 1200A. 2. Time tolerance should add +20ms for relaying if power does not supply to the trip unit. 3. Ground fault should be adjusted by touch LCD.
Earth leakage(option)
Threshold (A) Tolerance: ±10% I△n 0.1 ~ 30 (1A steps), OFF
If time delay(ms) Accuracy I2t Off: chose
largest value between, ±10%(Ig_ext ≥ I2t can choose On/Off
5A), ±20% (Ig_ext < 5A), or ±40ms t△n
If I2t On (@30 A): chose largest value 0.1 ~ 1.0 (0.01s steps)
between, ±25% or ±40ms
ZSI ZSI Time (s) 0.04 ~ 0.2 (0.01s steps), OFF
Start up Pick up (A) Above 1.2×Isd (0.1A steps)
Time delay (s) 0.1 ~ 30 (0.01s steps), OFF
Note) 1. It is impossible to use both ground fault and earth leakage at same time. 2. CT accuracy can be changed by applying CT. 3. Earth leakage should be adjusted by touch LCD .
49
Trip relays
1) RUN/AL
- RUN: Indicating the operation(Blinking blue LED during turn on)
- AL: Indicating an overload(Turn on above 90%, Blink above 105%)
②
- Self diagnose error: Blinking blue and red LED
2) SP/ERMS
- Override/MCR operation: Red LED
- ERMS operation: Blue LED
3) COMM: Communication display LED(green)
4) Ir: LED Display for long-time over current relay operation
5) Isd/Ii: LED Display for short-time/INSTANTANEOUS OVER CURRENT Relay Operation
6) G/PTA: LED displaying operation for Ground/Leakage fault protection relay, PTA
⑧ ⑨
50
Susol / Metasol ACB
Long time
Threshold (A) Ir = Iu×... 0.4 ~ 1.0 (1A steps), OFF
Trip between 1.05 and 1.2 Ir
If time delay(s): chose largest
value between, tr@(1.5×lr) 0.5 ~ 24 (0.01s steps)
Accuracy: ±10% (Is ≤ 6In),
±20% (Is > 6In), or ±40ms
Note) 1. See manual for checking IDTML and equations. 2. Time tolerance should add +40ms for L/S/I/G, if power does not supply to the trip unit.
3. S-Type should be adjusted by touch LCD.
Short time
Threshold (A) Tolerance: ±10% Isd = Ir×... 1.5 ~ 10 (1A steps), OFF
Earth leakage(option)
Threshold (A) Tolerance: ±10% I△n 0.1 ~ 30 (1A steps), OFF
If time delay(ms) Accuracy I2t Off: chose
largest value between, ±10%(Ig_ext ≥ I2t can choose On/Off
5A), ±20% (Ig_ext < 5A), or ±40ms, t△n
If I2t On (@30 A): chose largest value between, 0.1 ~ 1.0 (0.01s steps)
±25% or ±40ms
ZSI ZSI Time (s) 0.04 ~ 0.2 (0.01s steps), OFF
Start up Pick up (A) Above 1.2 X I△n (0.1A steps)
Time delay (s) 0.1 ~ 30 (0.01s steps), OFF
Note) 1. It is impossible to use both ground fault and earth leakage at same time. 2. CT accuracy can be changed by applying CT.
51
Trip relays
Operation characteristics
- Iu: (0.5-0.6-0.7-0.8-0.9-1.0)×In
.5 1 20
t .4 .5 off
- Ir: (0.8-0.83-0.85-0.88-0.9-0.93-0.95-0.98-1.0)×Iu
Iong time
Ir ×In @6 Ir
Instantaneous (I)
The function for breaking fault current above the setting value within
the shortest time to protect the circuit from short-circuit.
52
Susol / Metasol ACB
53
Trip relays
Measurement function
39
101
4-Ø5.5
87.5
25
82
54
Susol / Metasol ACB
Max Power
Demand
Energy
CB Count
Run Time
8. DO Setup
9. Language
Ir adjustment
knob
tg adjustment
knob
Displayed screen when changing
tg value into 0.2
(After 3sec, return to initial display)
55
Trip relays
PASSWORD 1.OCR
2.OCGR
3.OVR/UVR
XXXX 4.Unbal
5.rP/OPR
56
Susol / Metasol ACB
100%
50%
Q+
S : 360 1080 S : 0 0
607 kVarh
T : 360 T : 0
Reverse Energy Forward Q [kVarh] Reverse Q [kVarh]
P- 0 kWh R : 210 Total R : 0 Total
Q-
S : 210 630 S : 0 0
0 kVarh
T : 210 T : 0
Voltage/Current Volt Wave & FFT [%] S Volt Harmonics [V] S Volt Harmonics [V] S Volt Harmonics [V]
THD[S] : 25.0 H1 220 H8 0 H15 0 H22 0 H57 0
harmonics
H2 0 H9 0 H16 0 H23 0 H58 0
Curr Wave & FFT [%] R Curr Harmonics [A] R Curr Harmonics [A] R Curr Harmonics [A] TDD 3Phase
THD[R] : 3.0 H1 1000 H8 0 H15 1 H22 0 H57 0 R : 0.1 %
H2 0 H9 3 H16 0 H23 1 H58 0 S : 0.1 %
H3 15 H10 0 H17 1 H24 0 H59 0 T : 0.1 %
H4 0 H11 1 H18 0 H25 1 H60 0 Current K - Factor
T
H5 20 H12 0 H19 1 H26 0 H61 0 R : 1.2
R
H6 0 H13 1 H20 0 H27 1 H62 0 S : 1.2
S
H7 0 H14 0 H21 1 H28 0 H63 0 T : 1.3
57
Trip relays
Screen transition
Return
Cancel
Enter
Main menu
■ ERMS display
H/W SET display
Measurement
display
Measurement -
Load Current/
Metering
Overview
58
Susol / Metasol ACB
Measurement –
Voltage &
Current
Measurement –
Power & Energy
Measurement -
Demand
Measurement -
Harmonics
•••••
Measurement –
Oscilloscope
EVENT display
System info
display
59
Trip relays
Characteristics curves
Ir = 0.4...1 In
1000
500
200
100
50
40 tr = 0.5...20s
30
20
20
12
10
8
t(s) 5 4
4
3
2
2
1
1
0.5
0.4
0.3
0.2
0.1
0.05
0.02
0.01
0.5
0.7
10
20
× Ir
60
Susol / Metasol ACB
1000
200
100
50
40
30
20
10
t(s) 5
4
3
2
0.05
0.05
0.02
0.01
0.5
0.7
10
20
× Ir
61
Trip relays
Characteristics curves
20
Ig = 0.2...1 In
10
5
4
3
t(s) 1
I2t ON
0.3
0.3 0.3
I2t OFF
0.1 0.1 0.1
0.05
0.05
Ii = 2...15 In
0.02
0.01
0.05
0.07
0.1
0.2
0.3
0.4
0.5
0.7
3
4
5
10
× In
62
Susol / Metasol ACB
IDMTL 10000
5000
2000
EIT
1000
500
VIT
200
100
SIT
t(s)
50
20
DT
10
0.05
0.5
0.7
10
20
× Ir
63
Trip relays
Characteristics curves
200
100
50
40 35
30
20
15
10
5
5
4
3
t(s) 2
1
1
0.4
0.3
0.2
0.1
0.05
0.02
0.01
0.5
0.7
10
20
30
× Ip
64
Susol / Metasol ACB
Zone-selective interlocking drops delay time that eliminates faults for breakers.
It minimizes the shock that all kinds of electric machineries get under fault conditions.
1. In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at
accident site sends ZSI signal to halt upstream breaker’s operation.
2. To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay.
3. The upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time-
delay for protective coordination in the system.
However upstream breaker that did not receive its signal will trip instantaneously.
4. For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit
breakers will react before upstream ones under overcurrent/short time delay/ ground fault situations.
① Z4
Z3
Z2
ZSI input
Z1
Fault A
②
Z4
ZSI output
Z3
Z2
ZSI input
Z1
Fault B
Z4 Z4 Z4
Z3 Z3 Z3
Z2 Z2 Z2
Z1 Z1 Z1
1) Occurrence of fault A
- Only breaker ① performs instantaneous trip operation.
2) Occurrence of fault B
- Breaker ② performs instantaneous trip operation,
breaker ① performs trip operation after prearranged delay time
- But if breaker ② did not break the fault normally,
breaker ① performs instantaneous trip operation to protect system.
65
Trip relays
In case of that ACB operates due to accidents or over current, Trip relay indicates the information of
the accident through the LED and LCD.
Trip relay A, P and S type is possible to perform the remote reset by digital input, and have 3
DO(Digital output).
1. Methods to reset Trip relay is to push the Reset button on the frontal side and to use the remote reset.
2. Digital input
- [R11-R22] input: Remote reset
- [Z1-Z2] Input: ZSI input
- [E1-E2] Input: ZCT for earth leakage detection or external CT input
※ All DI are dry contact that has 3.3V of recognition voltage. When inputting close by SSR(Solid State
Relay) or open-collector, connect collector(Drain) to R11.
Voltage module
ZSI output
Common
ZSI input
Power supply
Reset
ZCT
V1 V2 V3 Vn E1 Z3 Z1 485+ R11 R22 513 R2 R1
Trip relay
LTD
S/I
66
Susol / Metasol ACB
Communication
Modbus/RS-485
• Operation mode: Differential
• Distance: Max. 1.2km
• Cable :
General RS-485 shielded twist
2-pair cable
• Baud rate :
9600bps, 19200bps, 38400bps
• Transmission method: Half-Duplex
• Termination: 100Ω
※ RS485 communication precautions
1) Operation mode and maximum communication distance:
Support up to 1.2km in differential mode.
2) Communication line and cable specification:
Use universal AWG22, twisted shield par cable.
3) Please make sure to ground the shield of the communication line.
Profibus-DP
communication module
(Option)
67
ACB/MCCB/MCB panel configuration
ACB/MCCB/MCB panelpanel
ACB/MCCB/MCB configuration
ACB/MCCB/MCB configuration
panel configuration
Upper system
Upper system
GridSol CAREGridSol
Monitoring
CARES/W
Monitoring
(Cloud) S/W (Cloud) GridSol CAREGridSol
Operation
CARE
S/W
Operation S/W
Communication
Communication
device device
1 1 2 2
Accessory device
Accessory device
Thermal CAM
Thermal CAM TRIO TRIO
Circuit breaker
Circuit
& breaker &
measurement measurement
device device
i-Tester i-Tester
Portable Portable
Smart ACB Smart ACB Battery & Battery &
Trip Module Trip Module
Main panel
Main panel
※ Please use one of the communication devices ① (Gateway) or ② (Ethernet Converter). ※ Coamtipble devices : GIMAC1000, GIMAC-B, MMP, DMPi
※ RSTP (Rapid Spanning Tree Protocol) supported devices : Data Logger, Gateway, Ethernet Converter, E COLLECTOR
68
Susol / Metasol ACB
Internet Internet
Ethernet Ethernet
RS485 RS485
USB USB
GridSol CAREGridSol
Maintenance
CARE Maintenance
S/W S/W Tester Cable
Tester Cable
Hardwire Hardwire
1 1 2 2
Gateway Gateway
Ethernet Converter
Ethernet Converter Gateway Gateway E COLLECTOR
E COLLECTOR
Feeder panel
Feeder panel Panel board
Panel board
69
Trip relays
70
Susol / Metasol ACB
A B C N A B C
CT CT
Main
PCB
CN2-7 Ass'y CN2-7
Setting
CN2-14 Part CN2-14
GND 24V
CN2-4 CN2-4
Vcc
Self
power
+24V
RY0 (K1)
POWER POWER
CN9-2
LTD contact
GND
CT CT
+5 V RY0 (K2) CN9-4
Main STD/INST contact
PCB
Ass'y
CN2-2 RY0 (K3) CN2-2
CN9-6
GTD contact
J1-1 J1-1
Power PCB CN9-8
J1-2 Common contact J1-2
Voltage Voltage
VDM Ass'y
J1-3 Module J1-3
Input J1-4
Input J1-4
FG
CN5-1
ZSI output+
CN9-9 CN5-2 CN9-9
External ZSI output- External Source
SMPS
Source CN9-10 Power CN5-3 AC/DC 110~220V CN9-10
AC/DC ZSI input+ DC 24~48V
PCB
110~220V CN9-7 CN5-4 CN9-7
FG Ass'y ZSI input- FG
DC 24~48V
CN5-7 CN5-7
CN5-5
CN5-8 Remote reset + CN5-8
CN5-6
Remote reset -
ZCT ZCT
(Earth leakage) CN5-9 Group DI or
(Earth leakage)
CN4-2 ERMS DI + CN4-2
Current Signal(A) CN5-10 Group DI or Current Signal(A)
CN4-4 CN4-4
Current Signal(B) Test ERMS DI - Current Signal(B)
CN4-6 Port CN4-6
Current Signal(C) Current Signal(C)
CN4-8 CN4-8
Current Signal(N) Current Signal(N)
i-Tester DC 24V
CN4-5
Comm.
CN9-1
RS485+ i-Tester DC 24V
CN4-5
CN4-1
CN4-1 Main
TTL TX CN9-3 TTL TX
CN4-3 PCB PCB Ass'y RS485- CN4-3
TTL RX TTL RX
CN4-9 Ass'y CN9-5 CN4-9
GND Comm. GND GND
AD GND CN4-10 AD GND CN4-10
71
Accessories
AH AS AN
Mounting Accessories Remark Page
Standard Option Standard Option Standard Option
CC Closing Coil ● ○ ● ○ ● ○ * 76
M Motor ● ○ ● ○ ● ○ * 77
C Counter ● ○ ○ * 87
AX Auxiliary Switch ○ ○ ○ * 81
MI Mechanical Interlock ○ ○ ○ * 89
K1 Key Lock ○ ○ ○ * 82
LH Lifting Hook ○ ○ ○ 84
DC Dust Cover ○ ○ ○ 87
DF Door Frame ○ ○ ○ 92
J Manual Connector ○ ○ ● * -
A Automatic Connector ● ● ○ * -
72
Susol / Metasol ACB
AH AS AN
Mounting Accessories Remark Page
Standard Option Standard Option Standard Option
N N type ○ ○ ○ * 44
A A type ○ ○ * 46
P P type ○ ○ ○ * 48
Trip relay
S S type ○ ○ ○ * 50
VM Voltage Module ○ ○ ○ ** 54
ST Safety Shutter ○ ○ ○ * 91
DI Door Interlock ○ ○ ○ 90
RI Racking Interlock ○ ○ ○ 97
IB Interphase Barrier ● ○ ○ * 92
73
Accessories
74
Susol / Metasol ACB
Wiring Diagram
• Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30V
or DC / AC 48~60V of rated voltage.
75
Accessories
Wiring Diagram
• Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30V
or DC / AC 48~60V of rated voltage.
76
Susol / Metasol ACB
Motor [M]
Main
axis
AC/DC AC/DC
Input voltage (V) DC 24~30V AC/DC 48~60V AC 380V AC 440~480V
100~130V 200~250V
Load current (max.) 5A 3A 1A 0.5A 0.3A 0.3A
Starting current (Max.) 5 times of load current
Load rpm (Motor) 15000 ~ 19000 rpm
Charge time Less than 5sec.
Dielectric strength 2kV/min
Using temperature range -20°~ 60°
Using humidity range Max. RH 80% (No dew condensation)
Charge switch 10A at 250VAC
Susol Metasol
Type AH-D AH-E AH-G AN, AS-D AN, AS-E AS-F AS-G
Endurance 20,000 15,000 10,000 20,000 15,000 10,000 10,000
* Unit: Cycle (Frequency 2 cycles/ min)
77
Accessories
24~30 -
48~60 48
Less than
100~130 100~130 0.65~0.85 Vn 0.4~0.6 Vn 200 5
50ms
200~250 200~250
- 380~480
Note) Operating voltage range is the min. rated standard for each rated voltage (Vn).
78
Susol / Metasol ACB
• When a circuit breaker is tripped by OCR which operates against the fault current (Over Current Relay), Trip
AL1, 1a
Alarm switch provides the information regarding the trip of circuit breaker by sending the electrical signal from
AL2, 1a
the mechanical indicator on front cover of main circuit breaker or internal auxiliary switch. (Installed at the
inside of circuit breaker)
• When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops
out from the front cover and the switch (AL) which sends control signal electrically is conducted to output the
information occurred from fault circuit breaker.
• MRB and AL can be operated only when tripping by OCR, but doesn’t be operated by Off button and OFF
operation of trip coil.
• To re-close a circuit breaker after a trip, press MRB to reset it for closing.
• 2pcs of electrical trip switch (AL1, AL2, 1a) are provided (Option)
• Trip alarm contact and MRB(Manual reset bottom) need to be purchased together.
• It is a function which resets a circuit breaker manually when a circuit breaker is tripped by OCR.
• When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops
out from the front cover and the switch (AL) which sends control signal electrically is conducted to output the
information occurred from fault circuit breaker.
• MRB can be operated only by OCR but not by OFF operation of circuit breaker. To re-close a circuit breaker after
a trip, press MRB to reset it for closing.
79
Accessories
• Following tripping, this function resets the "fault trip" alarm contacts (AL) and the mechanical indicator (MRB)
and enables circuit breaker closing.
Push button switch: AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load
Connect to inner
RES
micro switch
184
Connect to
* The dotted line to AL2 / RES
be made by the
customer
Wiring Diagram
80
Susol / Metasol ACB
Standard classification
Standard High capacity
2000, 5000AF 4000, 6300AF 2000, 5000AF 4000, 6300AF
81
Accessories
K1
Wiring
•3 circuit breakers can be arranged for the
continuous power supply to the load side and
be interlocked mutually by using Key Lock
embedded in each circuit breaker.
* How to order: 3 breakers must be ordered as a set, and K2
description must be added to the additional
breakers. (2 keys are provided per 3 breakers.)
Status
ACB-1 ACB-2 ACB-3
LOAD1 LOAD2
● ● ● OFF OFF
ACB1 ACB2 ● ○ ○ ON ON
○ ● ○ ON ON
○ ○ ● ON ON
● ● ○ OFF OFF
● ○ ● OFF ON
ACB3 ○ ● ● ON OFF
○: Release ●: Lock
Load 1 Load 2
82
Susol / Metasol ACB
<B2>
83
Accessories
•It is a device to
make an ACB easy to shift.
•Please hang it to both handles
of the arc cover.
External dimension
Range of Input voltage (%) 85~110 85~111
Unit (mm)
Condenser capacity 1000㎌ 560㎌
150
Circuit diagram
88
75
C1 C6
Side view
15
50 2-Ø6.5
AC input Condenser AC output
15.5
8 M3.5
1 2 3 4 5 6
12.8
112
C3 C5
User wiring
7 8 9 10 11 12
110.5 80
84
Susol / Metasol ACB
Ratings
Model type ATSC-110 ATSC-220
Rated voltage AC 110V AC 220V
Voltage range AC 93.5 (±5%) ~126.5V (±5%) AC 187 (±5%) ~ 253V (±5%)
Frequency 50Hz/60Hz
Power consumption (apparent power) 15.4W
4-location switch (stop, N, R, Auto)
Time setting (t1~t4)
Fault function (OCR/Circuit breaker trouble)
Output contact (Auto, Load burden)
• t1: The delayed time from when UN (power supply of electric company) is tripped to when generator start-up
signal contact is closed. (t1: 0.2, 0.5, 1, 2, 4, 8, 15, 30, 40, 50secs)
• t2: The delayed time from when UN is closed to when ACB2 is tripped.
(t2: 0.2, 1, 2, 4, 8, 15, 30, 60, 120, 240secs)
• t3: The delayed time from when ACB1 is tripped to when ACB2 is closed.
(t3: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs)
• t4: The delayed time from when ACB2 is tripped to when ACB1 is closed.
(t4: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs)
• Stop-mode: T
his mode is for compulsory trip of ACB1(electric power company) or ACB2 (power station) when
UN (power supply of electric power company) or UR (power supply of power station) is available.
*UN or UR should be kept in ON position
• R-mode: This mode is for compulsory closing of ACB2 during the use of UR regardless of that UN is available or not.
• Auto-mode: This mode is for transferring a circuit breaker automatically to available power supply of UN or UR.
In short, it trips the circuit breaker where power supply is not available and it close the circuit
breaker where power supply is available.
85
Accessories
• Status
ACB 1 ACB 2
OFF OFF
ON OFF
OFF ON
• Wire type
It is possible to interlock between devices without ampere frame and
Number of Poles.
The standard type(2 ACBs) provides 2m wire. In case of special type(3 ACBs)
provides 2.3m wires.
• Status
ACB 1 ACB 2 ACB 3
86
Susol / Metasol ACB
Panel door
Counter [C]
Counter
87
Accessories
a1 a2 a3 a4 a5 b1 b2 b3 b4 b5 a1 a2 a3 a4 a5 b1 b2 b3 b4 b5
13 23 33 43 53 11 21 31 41 51 13 23 33 43 53 11 21 31 41 51
14 24 34 44 54 12 22 32 42 52 14 24 34 44 54 12 22 32 42 52
• When MOC link is installed to cradle, MOC can be equipped with the inside of panel.
88
Susol / Metasol ACB
• It is used to interlock closing and trip between two or three breakers mechanically so as to prevent unintended
operation at the same time.
• Wire type interlock can be applied upto 3 breakers
89
Accessories
Catch type 1. The panel door will not be open when the circuit break 2. The panel door will be open when the circuit break in
Frame ① ② ③ ④
D 15 60 113 min 60
E 15 60 113 min 60
F 15 60 143 min 90
G 15 60 143 min 90
90
Susol / Metasol ACB
91
Accessories
Fixed type
• Interphase barrier prevents the arc which may arise and result in short-circuit between phases in advance
• As “C” stands for “CRADLE”, install the Interphase barrier in the direction of “C” in case of Draw-out type.
• As “A” stands for “ACB main frame”, install the Interphase barrier in the direction of “A” in case of Fixed type.
92
Susol / Metasol ACB
<Contact configuration>
4C: 1Disconnected +1Test +2Connected
8C: 2Disconnected +2Test +4Connected
Cell switch
CL-C ON
(Connected) OFF
Contact CL-T ON
operation (Test) OFF
CL-D ON
(Disconnected) OFF
4C attached to the right side of cradle 4C attached to the left side of cradle
93
Accessories
Connected position
(Shorting b contact : OFF)
Test position
(Shorting b contact : ON)
94
Susol / Metasol ACB
95
Accessories
Body supporter
Draw-in button
Pad lock
ACB is subject to restriction regarding moving in connected, test, disconnected when drawing in or out.
If main body of ACB is placed in 3 positions, it is locked and stopped when drawing in or out.
• As shown in the figure, if draw-in / out button pops out, it means locking is operating.
• To continue Draw-in / out operation, release lock by pushing Draw-in / out button
•In case it is locked as shown in the figure above, main body of ACB can not be drawn in orout into the cradle.
• For the lock device, user has to purchase it. (Ø5 ~ Ø6)
96
Susol / Metasol ACB
Door plate
97
Accessories
1
A
2
B 3
C 4
D 5
E
F 6
G 7
• When the main body of ACB is inserted to the cradle, if the ratings of ACB does not match with cradle,
it mechanically prevents ACB from being inserted into cradle of ACB.
98
Susol / Metasol ACB
■ Wiring
99
Accessories
The NCT(Neutral CT) allows to use following protecting functions when using 3-pole circuit breaker in WYE
connection(3-phase, 4-line Y-line).
PO L,S, I, G + Neutral CT
SO L,S, I, G + Neutral CT
How to wire
See wiring diagram(page 79) before wiring.
The ACB may malfunction when the NCT wires incorrectly.
CT spec.
Standard Code
CT ratio Burden Frequency Part size
100
Susol / Metasol ACB
S10 S61
210×85 102×35
102
92
SEC.
310 Terminal(M5) 55
210 28 SEC.
170 Terminal(M5) 65
102 35
190
85
123
35
68
50
S91
153×95
102
SEC.
245 Terminal(M5) 65
153 35
Bolt specification
• S10: Hex cross flange bolt (M6 L65)
• S61: Hex cross bolt (M6 L45)
190
NCT installation
circuit diagram L1
L2
L3
N V1
V2
V3 Voltage Module
VN (External)
V1 V2 V3 VN VG
Local/Remote DI
or
Comm. Group DI
or
ground ERMS DI Power supply
Reset
GD GD
FG CG /EM(+) /EM(-) V1 V2 V3 VN VG R11 R22 513 R2 R1
H2
NCT
x1
STD/inst
GTD
RS485
LTD
Comm.
x2
H1
PE
101
Accessories
i-Tester
The i-Tester (Intelligent Tester) is an accessory to test-drive ACB/MCCB. As a stand-alone type, it not only
performs various relay tests such as manual/auto/user tests, but also has various functions such as self-
calibration function, device information setting, relay setting, and device status checking. In addition, it
supports 256×128 graphic LCD and supports not only English but also Chinese and Russian languages.
It has the function to output the test and test results in the same way using the upper Manager S/W.
Key functions ‧Device information checking function (information, DI, DO, self-diagnosis)
‧Relay and H/W information setting function
‧Device control and reset function
‧Relay test function
- Manual/auto/user test function
‧Test history storage (up to 255) and output (PDF) function
102
Smart
SmartLVLV
Solution
Solution
Smart
SmartLVLV
Solution 부속
Solution 부속기기 기기
외관
외관설명
설명 ④④
④⑤ ⑤
⑤⑥⑥
⑥
Exterior
➍➎ ➏
description
②②
②
항목
항목
항목 내용
내용
내용
①①
①
➋ ① 전원스위치
① 전원스위치
① 전원스위치 전원
전원
전원ON/OFF 기능
ON/OFF
ON/OFF 기능
기능
③③ ② LCD
② LCD
LCD 256256
x 128
256 그래픽 LCDLCD
③ ② xx 128
128 그래픽
그래픽 LCD
Type Details
➊ ③ KEY
③ PAD
③ KEY
KEY PAD
PAD 메뉴 메뉴이동, 설정 및
메뉴 이동, 설정 및 조작
이동, 설정 조작
및 조작 버튼 버튼
버튼
➊ Power switch Power On/Off function
④ 어댑터
④
④➋어댑터 단자단자
단자 DC24V
DC24V
DC24V 전원 전원 입력입력
전원 입력 단자단자 단자
LCD 256×128 graphic LCD
➌ ⑤ USB
⑤ 단자
USB 단자
⑤ USB 단자 USB 통신
USB
USB 통신
통신연결 단자(USB2.0)
연결
연결 단자(USB2.0)
단자(USB2.0)
Menu navigation, setting and
⑦⑦ ➌ KEY PAD
⑦ operation buttons
⑥⑥신호
⑥ 신호
신호 포트 포트
포트 기기 기기
기기테스트를
테스트를
테스트를 위한위한
위한신호 단자
신호
신호 단자
단자
➍ Adapter terminal DC24V power input terminal
⑦ 배터리
⑦ 배터리
⑦ 배터리 9V 9V
알카라인
9V 알카라인
알카라인 건전지건전지
건전지 장착( x 3ea)
장착(
장착( xx 3ea)
3ea)
USB communication connection
➎ USB terminal
terminal (USB2.0)
➐ ➏ Signal port Signal terminals for device testing
Equipped with 9V alkaline batteries
➐ Battery
(×3ea)
제품
제품사용
사용예예
Device usage
example
Smart
Smart ACB
ACB
Smart
Smart ACB
ACB Manager
Manager
Manager
Manager S/W
S/W
S/W
S/W
1.1.Perform
계전
1.
1. 계전
계전테스트
relay
테스트
테스트 수행
test수행
수행 1.
1.계전1. 테스트
Perform
1. 계전
계전 테스트
테스트 수행
relay test
수행
수행
2.2.Device
기기 monitoring,
모니터링,
2. 기기 모니터링, 2.기기
2. Device
2. 기기monitoring,
모니터링,
모니터링,
2. 기기 모니터링, 2. 기기 모니터링,
relay
계전계전 setting
설정 및and
제어 relay설정
계전 setting and
및 제어
계전 설정
설정 및
및 제어
제어 계전
계전 설정
설정 및
및 제어
제어
Smart
Smart MCCB
MCCB
Smart MCCB control control +24V
+24V
+24V Adapter
Adapter
+24V Adapter
Adapter
Smart MCCB
Susol
Susol //ACB
Susol
Susol 선박용 forACB
// 선박용
선박용ship
ACB
ACB 9V9V
9V
9V Battery×3EA
Battery *3EA
Battery
Battery *3EA
*3EA
전원 전원
Power connection
전원연결선 연결선
line연결선
통신 통신
통신연결선 연결선 line
연결선
*IPOT : Intelligent
*IPOT
*IPOT
* IPOT : Intelligent
Potable
:: Intelligent
Intelligent OCROCR
Potable
Potable
Potable
TESTER
OCR
TESTER
OCRTESTER
TESTER Communication connection
Target device Circuit breaker Smart ACB(STU), Susol/Metasol ACB(OCR), Smart MCCB, TS1600
LSIS Co.,Ltd.85 85
Co.,Ltd.
LSIS
103
Accessories
Smart LV Solution 부속 기기
TRIO
TRIO
This device is a device used to monitor ACB status, remote open/close operation control
and temperature measurement by being installed on the LV panel or distribution panel.
It본is제품은 저압 판넬of
also capable 또는 분전반에 설치하여
expanding DI/DO through communicating with DTR.
ACB상태 감시, 원격 개폐 동작 제어 및 온도 측정을 수행하기 위한 장치입니다.
STU와 통신 연계하여 DI/DO 확장이 가능합니다.
주요 특징 TRIO 모듈은 별도의 온도센서 부착을 통해 온도감시가 가능하며, DI/DO 확장 기능을 내장하고 있어 차단기 감시 및 제어가
Characteristic •가능합니다.
Monitoring
기존theTRIO에
temperature
비해 DI/DOby접점
using external
개수가 temperature
증가하였으며, 온도표시가 sensor.
7-Segment 수준으로 향상되었습니다.
• Monitoring the ACB status through the built-in function of DI/DO expansion.
• Compare with old TRIO, the number of DI/DO contact increased.
• Temperature display improved to 7S-egment level.
제품 사양 항목 내용 비고
Rating 모델명 Item TRIO Description Remark
정격전압
Rating voltage DC24V (±10%)
DC24V (±10%) 21.6~26.4Vdc 21.6~26.4Vdc
소비전력
Power consumption 6W Up
이하to 6W
4ea 측정 범위 : 0~150 ℃
• Range: 0~150℃ 오차범위 : 접촉식 ±3 ℃, 비접촉식 5 ℃
온도센서 4EA 알람 온도 : 55 ℃, 65 ℃, 70 ℃, 80 ℃
• Tollerence
디지털 출력 연계 가능
Temperature - Contact type: ±3℃ 온도센서 별매 Separate sale
monitoring sensor - Non-contact type: 5℃
일반• Alarming
: 4EA temperature Cradle 상태 접점 감시 및
DI
CB용-2EA55℃, 65℃, 70℃, 80℃ Spring charge 상태 감시 가능
• DO link available
일반 : 3EA LATCH, 500ms 설정 가능
DO
CB용 2EA
• Normal: 4ea (CB 제어 가능) • Cradle status monitoring
DI
Power LED 2ea
• CB type: • Closing spring status monitoring
Comm. LED 온도표시 7-Segment• LATCH
CB •LED
Normal:
3개, 3ea : 100 ℃ 미만 : 소수점 1자리까지 표시
DO
LED •S
: 100 ℃ 이상 : 1의 et 500ms available(CB control
DI LED
• CB4개type: 2ea 자리까지 표시
DO LED 3개 available)
온도센서 LED 4개
• Power LED
프로토콜 • Comm.
Modbus RTULED Temperature display – 7 segment
• CB LED: 3ea -U nder 100℃ : display to 1 decimal
LED
통신방식 RS485 STU 연계 가능
• DI LED: 4ea place
설치 타입 • DO LED:
DIN-Rail, 3ea
Screw - Over 100℃ : display to 1 digit place
• Temperature sensor: 4ea
사이즈 72 (W) × 81 (H) × 65 (D), 단위 mm
Protocol Modbus RTU
사용 온도 -25 ℃ ~ +60 ℃
Communication RS485 Link with STU
보관 온도 -30 ℃ ~ +70 ℃
• Din-rail
Attachment
주위 습도 method 85%• Screw
이하 (이슬이 맺히지 않을 것)
Dimension(W×H×D) 72mm×81mm×65mm
104
76
Susol / Metasol ACB
Smart
Smart LV Solution
LV Solution
Smart
Smart LV LV 부속
Solution
Solution 부속
기기 기기
Exterior
외관
외관 설명
설명
Communication / Power terminal
Digital output (DO)
(RJ12)
통신,통신, 전원단자
전원단자 (RJ12)
(RJ12) 디지털출력(DO)(DO)
Temperature
디지털출력 alarm/
Operating switch
온도온도
알람알람
/ /
동작동작
모드모드
설정설정
스위치스위치
제품 사용예예
Example
제품 사용
DC Power DC Power
DC Power
DC Power TRIO DC Power
DC Power TRIO
Module
Module TRIOTRIO Module
Module TRIOTRIO
Module Module
Sole
단독단독usage
사용사용예 예 RS485
RS485
STU
STUSTU
Use
STUSTU
사용with
예 STU
사용 예
대상
대상 기기
기기 차단기
차단기 Susol
Susol ACBACB
STU,STU, Metasol
Metasol ACBACB
STUSTU
Device Circuit breaker
※ 단독 사용 가능
Susol/Metasol ACB with STU
※ 단독 사용 가능
※ Can be used alone
77 77
105
Accessories
TRIO
5V Ø9.75 39
24V+ 5V GND O1
5V ISO1
C1
SPD 5V ISO1 GND
Power 5V ISO2 O2
5V ISO2 GND
24V –
3.3V C2
3.3V GND
O3
176.67
192.27
157.95
87.75
66
C3
RJ12A CC+
CC –
SH+
RJ12B
SH –
39 99.4
T1
139.62 127.92
S1+ ADC
RS-485
S1–
T2
I1
ADC
G
I2 T3
ADC
C
I3 T4
ADC
G
I4
C
USB USB2.0
A+
A–
B+ S2+
RS-485
B– S2–
106
Susol / Metasol ACB
24V G S2+S2-G T1 T2 G T3 T4
CC+CC-SH+SH- A+A-B+B- C I1 I2 C I3 I4
24V G S2+S2-G T1 T2 G T3 T4
CC+CC-SH+SH- A+A-B+B- C I1 I2 C I3 I4
24V G S2+S2-G T1 T2 G T3 T4
CC+CC-SH+SH- A+A-B+B- C I1 I2 C I3 I4
13 23 33 43 53 11 21 31 41 51
14 24 34 44 54 12 22 32 42 52
107
Accessories
GATEWAY and DATA LOGGER are system communication devices within the Smart LV solution.
GATEWAY performs a role of sending the data of serially connected RS-485 communication type devices.
GATEWAY and DATA LOGGER provide their independent web page for users to use the connected device
settings/status and the monitoring service through this page.
108
Smart LV Solution
Smart LVSusol 부속 기기
/ Metasol
Solution ACB
Web
Web 서비스
service ▪Provides
▪기기 device 기능
등록, 모니터링 registration
제공 and monitoring functions
▪Provides
▪원격 펌웨어 remote
업그레이드 firmware
기능 제공upgrade function
▪Provides
▪Wave wave
Viewer 기능 viewer
제공 function
ACB 전압,
ACB voltage, 전류 파형
current waveform Trip Trip
Wavewave
외관 설명
Exterior
description
Antenna EthernetPort
Ethernet Port (WAN)
(WAN)
Antenna
EthernetPort
Ethernet Port (RSTP)
(RSTP)
Status LED
상태표시 LED
Power
전원 단자 terminal (24Vdc)
(24Vdc)
USB2.0
USB2.0
RS485 communication RESET switch
RESET 스위치
terminal
RS485 통신 (RJ12)
단자 (RJ12)
Digital
디지털 output (DO)
출력 (DO)
RS485 communication
terminal
RS485 통신 (2 Pin)
단자 (2 Pin) Digital
디지털input (DI)
입력 (DI)
Circuit breaker Susol ACB STU, Metasol ACB STU, Susol Smart MCCB
대상 기기
Target device
차단기 Susol ACB STU, Metasol ACB STU, Susol Smart MCCB
Measurement device GIMAC1000, GIMAC-B, E TAG, MMP, DMPi, Energy Meter
계측기기 GIMAC1000, GIMAC-B, E TAG, MMP, DMPi, Energy Meter
Accessory device M LINK, TRIO, Thermal CAM
부속기기 M LINK, TRIO, Thermal CAM
109
73
Electrical diagram
Note) 1. The diagram is shown with circuits de-energized, all devices open, connected and charged and relays in normal position
2. Relay is normal condition and charging type is "OFF-Charging"
3. T
he standard of auxiliary contact is 3a3b. The auxiliary switch in above diagram is composed of 5a5b. See 66 page for more detail on auxiliary switches.
4. Option
- Ready to close contact, Trip alarm contact, UVT coil, Fully charged contact, secondary trip coil
- Cell switch, Temperature module, Voltage module, Remote close-open module, ZCT, ZSI
5. Please consult us for the use of ZSI (Zone selective Interlocking).
6. Refer to the page 47 for the connection of Trip relay and the page 61 for UVT.
7. For connecting RS-485 verify if the polarity is correct
110
Susol / Metasol ACB
This diagram is based on “CONNECTED” position of a circuit breaker and Opening, Motor charging, Releasing of locking plate
should be normal condition.
111
Electrical diagram
Power supply
CG GD
/EM(+)
GD
/EM(-) Z4 Z3 Z2 Z1 R11 R22 513 R2 R1
STU
ZCT
RS485
Wiring Diagram for External type VDM Wiring Diagram for Internal type VDM
112
Susol / Metasol ACB
183
251 83 /RES(+) D1 C11 C1 A1 U1 413 423 51 41 31 21 21 53 43 33 23 13
or
252 84
184
/RES(-) D2 C12 C2 A2 U2 414 424 52 42 32 22 12 54 44 34 24 14
Electrical Charge
operation circuit completion Auxiliary switch
contact
Secondary SBC
trip coil (Shorting b-contact)
113
Electrical diagram
ATS controller
to R’s relay
Trip relays
114
Susol / Metasol ACB
115
to N’s ACV to R’s ACV
Input terminal Output terminal Input terminal Output terminal
N, R wiring terminal
* For working the trip coil monitoring contact, see page 114~115.
Trip relays
to N’s relay
Electrical diagram
TC(TCS ON-charge)
'5a5b'
116
Susol / Metasol ACB
TC(TCS OFF-charge)
'4a4b'
117
Dimensions
Front view
3P 4P
Vertical type
3P 4P
<Conductor>
165 165
(73)
Cradle bottom
118
Susol / Metasol ACB
[Unit: mm]
Horizontal type
3P 4P
<Conductor>
Front
connection
type
3P 4P
<Conductor>
119
Dimensions
Front view
3P 4P
Vertical type
3P 4P
<Conductor>
Door Frame: DF
(AH/AN/AS-D/E)
<Mounting hole> <Side hole> <Panel cutting >
Dim. "W"
Rear Panel D3 330
Operating panel center D4 415
276 10-Ø9 315(Panel cutting size) Door frame E3 408
E4 523
W
4-Ø6
120
is installed)
265
128
266
388
352
280
304
2
39 21.5
120
6.5
109
11.5
120
Susol / Metasol ACB
[Unit: mm]
Horizontal type
3P 4P
<Conductor>
Front
connection
type
3P 4P
<Conductor>
121
Dimensions
Front view
3P 4P
Vertical type
3P 4P
<Conductor>
122
Susol / Metasol ACB
Front view
3P 4P
Vertical type
3P 4P
<Conductor>
123
Dimensions
Front view
3P 4P
45
25
25
165
165
20
20
4- 14 4- 14
Mounting hole Mounting hole
408 523
432 547
3P 4P
90
15
30
15
75
270
25
75
133
58
25
75
3- 13
67
35
65 20 165 45 <Conductor>
29.5
295 32.5
124
Susol / Metasol ACB
[Unit: mm]
Horizontal type
3P 4P
<Conductor>
Front
connection
type
3P 4P
<Conductor>
125
Dimensions
Front view
3P 4P
Vertical type
3P 4P
<Conductor>
126
Susol / Metasol ACB
[Unit: mm]
Horizontal type
3P 4P
<Conductor>
Front
connection
type
3P 4P
<Conductor>
127
Dimensions
Front view
3P 4P
Vertical type
3P 4P
<Conductor>
128
Susol / Metasol ACB
Front view
3P
4P
Vertical type
3P 4P
<Conductor>
129
Dimensions
Front view
3P 4P
Vertical type
3P 4P
<Conductor>
130
Susol / Metasol ACB
[Unit: mm]
Horizontal
type
3P 4P
<Conductor>
Door Frame: DF
(AH-G, AS-F)
<Mounting hole> <Side hole>
Panel Door
Door Frame
10-Ø9 315(Panel cutting size)
100
165 165
(73)
Cradle bottom
131
Dimensions
Front view
3P 4P
Vertical
type
3P 4P
<Conductor>
132
Susol / Metasol ACB
[Unit: mm]
Horizontal
type
3P 4P
<Conductor>
Door Frame: DF
(AH-G, AS-F) <Mounting hole> <Side hole> <Panel cutting >
Dim. "W"
F3 625
F4 795
10-Ø9 315(Panel cutting size) G3 781
G4 1011
4-Ø6
(If dust cover
120
is installed)
353(Panel cutting size)
280
265
128
2
120
23.5
16
7.5
165 165 5
Cradle bottom
133
Dimensions
Front view
3P 4P
Vertical type
3P 4P
4000A~5000A 6300A
<Conductor>
<Conductor>
134
Susol / Metasol ACB
[Unit: mm]
Horizontal type
4000A~5000A
3P 4P
6300A
3P 4P
4000A~5000A 6300A
<Conductor>
<Conductor>
135
Dimensions
Front view
3P 4P
Vertical type
3P 4P
4000A~5000A 6300A
<Conductor> <Conductor>
136
Susol / Metasol ACB
[Unit: mm]
Horizontal type
4000A~5000A
3P 4P
6300A
3P 4P
4000A~5000A
<Conductor>
6300A
<Conductor>
137
Dimensions
D-3/4P
138
Susol / Metasol ACB
139
Dimensions
140
Susol / Metasol ACB
141
Dimensions
4000~6300A, G4 (W1200)
G-4P
[Unit: mm]
142
Technical information Susol / Metasol ACB
Insulation voltage
You should keep the isolation distance between ACB and panel as below table.
Type A B
AN/AS 50 150
Fixed
AH 50 150
AN/AS 50 150
Draw out
AH 50 0
Note) When drawing the distribution panel, it is available to use regardless of the distance between
ACB and the wall of the panel because Susol ACB(draw-in/out type) extinguishes the arc
in the Arc Chute and Arc Cover clearly.
40-50Nm
Nut
Busher
25
Tightening torque
Screw type
Standard(kgf·cm) Tolerance Standard(N.m) Tolerance
M8 135 ±16 13.3 ±1.6
M10 270 ±32 26.5 ±3.2
M12 480 ±57 46.6 ±5.6
143
Technical information
Temperature derating
The table below indicates the maximum current rating, for each connection type, as a function of the ambient temperature around the circuit
breaker and the busbars.
Circuit breakers with mixed connections have the same derating as horizontally connected breakers.
For ambient temperatures greater than 60°C, consult us.
Temperature inside the switchboard around the circuit breaker and its connection: Ti (IEC 60947-2)
Rated Applicable
Frame ACB terminal
current busbar size
144
Susol / Metasol ACB
Operating conditions
Ambient temperature
ACB devices can operate under the following temperature conditions
- The electrical and mechanical characteristics are stipulated for an ambient temperature of -5°C to +40°C
- The average temperature should be within + 35°C
- Reduce the continuous conducting current when the temperature is over 45°C (refer to temperature derating)
- Storage condition : -20°C to + 60°C is recommended.
Altitude
ACB is designed for operation at altitudes under 2000m. At altitudes higher than 2000m, emitting heat is lowered
and operating voltage, continuous current capacity, and breaking capacity will be reduced. Durability of the
insulation is also reduced according to the atmosphere pressure.
According to the below table, change the ratings upon a service condition.
Altitude [m] 2000m 3000m 4000m 5000m
Item
Withstand voltage [V] 3500 3150 2500 2100
Average insulating voltage [V] 1000 900 700 600
Max. using voltage [V] 690 620 540 470
Current compensation constant 1×In 0.98×In 0.96×In 0.94×In
Environment
Under clean air;
Maximum temperature + 40°C (relative humidity should be under 85%)
Maximum temperature + 20°C (relative humidity should be under 90%)
Do not apply under corrosive or ammonia gas circumstances
(H2S ≤ 0.01ppm, SO2 ≤ 0.01ppm, NH3 ≤ a few ppm)
* Extreme atmosphere conditions
Under high temperature and/or high humidity, the insulation durability, electrical and mechanical features could
be deteriorated. At this conditions, increasing corrosion-resistant dealing needs. Corrosion-resistant parts need
under this conditions.
Inspection and Maintenance should be performed periodically which referred to inspection and replacement period in
maintenance manual. The recommended product replacement cycle is 10 years from manufacturing date.
145
Technical information
Installation recommendation
BUS-BAR Connection
Cables connections
Make sure that no excessive mechanical force put on the rear terminals for cable connection.
Extension terminal is fixed such as B, C and cable is to fixed to the frame such as E
Bus-bar connection
For busbar connection, connect access parts with a provided torque and fix with parallel installing the support not to apply terminal weight to
circuit breaker.
In order to prevent the spread safety or secondary accidents, secure maximum safe distance A (Table 1) from the access area to withstand the
electrical force during the short circuit faults.
A2
A A1
A=A1+A2
146
Susol / Metasol ACB
Installation recommendation
147
Technical information
Installation recommendation
Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)
Switchboard compsition
4
(2300×800×900)
3
2
1
Connection type
148
Susol / Metasol ACB
Installation recommendation
Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)
Switchboard compsition
4
(2300×800×900)
3
2
1
Connection type
149
Technical information
Installation recommendation
Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)
Switchboard compsition 4 4 4 4
(2300×800×900)
3 3 3 3
2 2 2 2
1 1 1 1
Connection type
Area of outlet vents: 350cm2 2 2000 2000 2000 2200 2300 2700 2900 3300
Area of intlet vents: 350cm2 1
Ta=35℃ 4
Non Ventilated switchboard(IP41/54) 3 2000
2 2000 2000 2000 2115 2275 2650 2850 3320
1
Ta=45℃ 4
3 1900
2 1900 1960 1960 2000 2150 2550 2700 3120
1
Ta=55℃ 4
3 1780
2 1800 1920 1920 1900 2020 2370 2530 2960
1
150
Susol / Metasol ACB
Installation recommendation
Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)
Switchboard compsition
4 4 4 4 4
(2300×800×900)
3 3 3 3 3
2 2 2 2 2
1 1 1 1 1
Connection type
151
Technical information
AC 220/240V
Rated voltage: AC 220/240V
Main breaker(Main ACB): Susol ACB
Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series
Below protective coordination table is based on ACB equipped with OCR
Susol MCCB
under arrangement of short time delay trip current as 10 times of rated current.
Susol AH series
Upstream Product type AH-D,W
breaker AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D
Rated current [A] 200 400 630 400 630 800 1000 1250 1600 2000
Downstream Short time delay
breaker trip current
2 4 6.3 4 6.3 8 10 12.5 16 20
(Max. 10In)
Is [kA]
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker’s rated short breaking capacity.
152
Susol / Metasol ACB
AC 220/240V
Rated voltage: AC 220/240V
Main breaker(Main ACB): Susol ACB
Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series
Below protective coordination table is based on ACB equipped with OCR
Susol MCCB
under arrangement of short time delay trip current as 10 times of rated current.
Susol AH series
Upstream Product type AH-E,X AH-G,Z
breaker AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G
Rated current [A] 400 630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
Downstream Short time delay
breaker trip current
4 6.3 8 10 12.5 16 20 25 32 40 40 50 63
(Max. 10In)
Is [kA]
Rated Ultimate breaking
Model current capacity Icu 100 150
[A] [kA]
TD100N 100 85 T T T T T T T T T T T T T
TD100H 100 100 T T T T T T T T T T T T T
TD100L 100 200 T T T T T T T T T T T T T
TD160N 160 85 T T T T T T T T T T T T T
TD160H 160 100 T T T T T T T T T T T T T
TD160L 160 200 T T T T T T T T T T T T T
TS100N 100 100 T T T T T T T T T T T T T
TS100H 100 120 T T T T T T T T T T T T T
TS100L 100 200 T T T T T T T T T T T T T
TS160N 160 100 T T T T T T T T T T T T T
TS160H 160 120 T T T T T T T T T T T T T
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker’s rated short breaking capacity.
153
Technical information
AC 380/415V
Rated voltage: AC 380/415V
Main breaker(Main ACB): Susol ACB
Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series
Below protective coordination table is based on ACB equipped with OCR
Susol MCCB
under arrangement of short time delay trip current as 10 times of rated current.
Susol AH series
Upstream Product type AH-D,W
breaker AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D
Rated current [A] 200 400 630 400 630 800 1000 1250 1600 2000
Downstream Short time delay
breaker trip current
2 4 6.3 4 6.3 8 10 12.5 16 20
(Max. 10In)
Is [kA]
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker’s rated short breaking capacity.
154
Susol / Metasol ACB
AC 380/415V
Rated voltage: AC 380/415V
Main breaker(Main ACB): Susol ACB
Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series
Below protective coordination table is based on ACB equipped with OCR
Susol MCCB
under arrangement of short time delay trip current as 10 times of rated current.
Susol AH series
Upstream Product type AH-E,X AH-G,Z
breaker AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G
Rated current [A] 400 630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
Downstream Short time delay
breaker trip current
4 6.3 8 10 12.5 16 20 25 32 40 40 50 63
(Max. 10In)
Is [kA]
Rated Ultimate breaking
Model current capacity Icu 100 150
[A] [kA]
TD100N 100 50 T T T T T T T T T T T T T
TD100H 100 85 T T T T T T T T T T T T T
TD100L 100 150 T T T T T T T T T T T T T
TD160N 160 50 T T T T T T T T T T T T T
TD160H 160 85 T T T T T T T T T T T T T
TD160L 160 150 T T T T T T T T T T T T T
TS100N 100 50 T T T T T T T T T T T T T
TS100H 100 85 T T T T T T T T T T T T T
TS100L 100 150 T T T T T T T T T T T T T
TS160N 160 50 T T T T T T T T T T T T T
TS160H 160 85 T T T T T T T T T T T T T
155
Technical information
AC 480/500V
Rated voltage: AC 480/500V
Main breaker(Main ACB): Susol ACB
Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series
Below protective coordination table is based on ACB equipped with OCR
Susol MCCB
under arrangement of short time delay trip current as 10 times of rated current.
Susol AH series
Upstream Product type AH-D,W
breaker AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D
Rated current [A] 200 400 630 400 630 800 1000 1250 1600 2000
Downstream Short time delay
breaker trip current
2 4 6.3 4 6.3 8 10 12.5 16 20
(Max. 10In)
Is [kA]
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker’s rated short breaking capacity.
156
Susol / Metasol ACB
AC 480/500V
Rated voltage: AC 480/500V
Main breaker(Main ACB): Susol ACB
Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series
Below protective coordination table is based on ACB equipped with OCR
Susol MCCB
under arrangement of short time delay trip current as 10 times of rated current.
Susol AH series
Upstream Product type AH-E,X AH-G,Z
breaker AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G
Rated current [A] 400 630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
Downstream Short time delay
breaker trip current
4 6.3 8 10 12.5 16 20 25 32 40 40 50 63
(Max. 10In)
Is [kA]
Rated Ultimate breaking
Model current capacity Icu 100 150
[A] [kA]
TD100N 100 30 T T T T T T T T T T T T T
TD100H 100 50 T T T T T T T T T T T T T
TD100L 100 65 T T T T T T T T T T T T T
TD160N 160 30 T T T T T T T T T T T T T
TD160H 160 50 T T T T T T T T T T T T T
TD160L 160 65 T T T T T T T T T T T T T
TS100N 100 42 T T T T T T T T T T T T T
TS100H 100 65 T T T T T T T T T T T T T
TS100L 100 85 T T T T T T T T T T T T T
TS160N 160 42 T T T T T T T T T T T T T
TS160H 160 65 T T T T T T T T T T T T T
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker’s rated short breaking capacity.
157
Technical information
AC 220~500V
Rated voltage: AC 220~500V
Main breaker(Main ACB): Metasol ACB
Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series
Below protective coordination table is based on ACB equipped with OCR
Susol MCCB
under arrangement of short time delay trip current as 10 times of rated current.
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker’s rated short breaking capacity.
158
Susol / Metasol ACB
AC 220~500V
Rated voltage: AC 220~500V
Main breaker(Main ACB): Metasol ACB
Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series
Below protective coordination table is based on ACB equipped with OCR
Susol MCCB
under arrangement of short time delay trip current as 10 times of rated current.
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker’s rated short breaking capacity.
159
Standards & Approval
IEC 60947-2
Low-voltage switchgear and controlgear
- Part 2: Circuit-breakers
CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the manufacturer, as
regards his products, by virtue of the European Community directives providing for the affixing of the CE marking.
When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of his authorized
representative that the product in question conforms to all the applicable provisions including the conformity
assessment procedures. This prevents the Member States from limiting the marketing and putting into service of
products bearing the CE marking, unless this measure is justified by the proved non-conformity of the product.
IECEE CB SCHEME
The IECEE CB Scheme is the world's first truly international system for acceptance of test reports dealing with the
safety of electrical and electronic products. It is a multilateral agreement among participating countries and
certification organizations. A manufacturer utilizing a CB test report issued by one of these organizations can
obtain national certification in all other member countries of the CB Scheme.
The Scheme is based on the use of international (IEC) Standards. If some members' national standards are not
yet completely harmonized with IEC Standards, national differences are permitted if clearly declared to all other
members. The CB Scheme utilizes CB Test Certificates to attest that product samples have successfully passed
the appropriate tests and are in compliance with the requirements of the relevant IEC Standard and with the
declared national differences of various member countries.
The main objective of the Scheme, is to facilitate trade by promoting harmonization of the national standards
with international Standards and cooperation among product certifiers worldwide in order to bring product
manufacturers a step closer to the ideal concept of "one product, one test, one mark, where applicable".
160
Time chart Susol / Metasol ACB
Long time
tr tr
×Ir 0.5 1 2 4 8 12 16 20 ×Ir 0.5 1 2 4 8 12 16 20
1.11 58806 117611 235223 470445 940890 1411335 1881780 2352225 3.95 1181 2361 4722 9445 18889 28334 37779 47223
1.15 36041 72082 144163 288326 576652 864978 1153305 1441631 4.00 1150 2300 4600 9201 18401 27602 36802 46003
1.20 26827 53654 107308 214615 429231 643846 858461 1073077 4.05 1121 2241 4483 8966 17932 26898 35864 44830
1.25 21777 43553 87106 174212 348424 522636 696848 871060 4.10 1093 2185 4370 8740 17481 26221 34961 43701
1.30 18408 36817 73634 147268 294535 441803 589071 736338 4.15 1065 2131 4262 8523 17046 25569 34092 42615
1.35 15947 31895 63789 127579 255157 382736 510314 637893 4.20 1039 2079 4157 8314 16628 24942 33256 41570
1.40 14049 28098 56197 112393 224787 337180 449573 561967 4.25 1014 2028 4056 8113 16225 24338 32451 40563
1.45 12532 25063 50126 100252 200504 300756 401009 501261 4.30 990 1980 3959 7919 15837 23756 31674 39593
1.50 11286 22573 45145 90290 180580 270870 361160 451450 4.35 966 1933 3866 7731 15463 23194 30926 38657
1.55 10244 20488 40977 81954 163907 245861 327814 409768 4.40 944 1888 3776 7551 15102 22653 30204 37755
1.60 9359 18717 37434 74869 149737 224606 299474 374343 4.45 922 1844 3688 7377 14754 22131 29507 36884
1.65 8596 17193 34386 68771 137542 206313 275084 343855 4.50 901 1802 3604 7209 14417 21626 28835 36043
1.70 7934 15867 31734 63468 126936 190404 253873 317341 4.55 881 1762 3523 7046 14093 21139 28185 35231
1.75 7352 14704 29408 58815 117631 176446 235261 294077 4.60 861 1722 3445 6889 13779 20668 27557 34447
1.80 6838 13675 27351 54702 109404 164106 218808 273509 4.65 842 1684 3369 6738 13475 20213 26951 33688
1.85 6380 12760 25521 51041 102082 153123 204164 255205 4.70 824 1648 3295 6591 13182 19773 26364 32955
1.90 5970 11941 23882 47764 95528 143292 191056 238820 4.75 806 1612 3225 6449 12898 19347 25796 32245
1.95 5602 11204 22408 44815 89630 134446 179261 224076 4.80 789 1578 3156 6312 12624 18935 25247 31559
2.00 5269 10537 21075 42150 84299 126449 168598 210748 4.85 772 1545 3089 6179 12358 18536 24715 30894
2.05 4966 9932 19865 39730 79459 119189 158919 198649 4.90 756 1513 3025 6050 12100 18150 24200 30250
2.10 4691 9381 18762 37525 75049 112574 150099 187623 4.95 741 1481 2963 5925 11851 17776 23701 29627
2.15 4439 8877 17754 35508 71017 106525 142034 177542 5.00 726 1451 2902 5804 11609 17413 23218 29022
2.20 4207 8415 16829 33659 67318 100976 134635 168294 5.05 711 1422 2844 5687 11374 17062 22749 28436
2.25 3995 7989 15979 31957 63914 95871 127829 159786 5.10 697 1393 2787 5574 11147 16721 22294 27868
2.30 3798 7597 15194 30387 60775 91162 121550 151937 5.15 683 1366 2732 5463 10927 16390 21853 27317
2.35 3617 7234 14468 28936 57871 86807 115742 144678 5.20 670 1339 2678 5356 10713 16069 21425 26782
2.40 3449 6897 13795 27590 55180 82769 110359 137949 5.25 657 1313 2626 5252 10505 15757 21010 26262
2.45 3292 6585 13170 26339 52679 79018 105358 131697 5.30 644 1288 2576 5152 10303 15455 20607 25758
2.50 3147 6294 12588 25176 50351 75527 100702 125878 5.35 632 1263 2527 5054 10107 15161 20215 25268
2.55 3011 6022 12045 24090 48180 72269 96359 120449 5.40 620 1240 2479 4959 9917 14876 19834 24793
2.60 2884 5769 11538 23075 46151 69226 92301 115377 5.45 608 1217 2433 4866 9732 14598 19464 24330
2.65 2766 5531 11063 22126 44251 66377 88503 110628 5.50 597 1194 2388 4776 9552 14329 19105 23881
2.70 2654 5309 10618 21235 42471 63706 84941 106177 5.55 586 1172 2344 4689 9378 14066 18755 23444
2.75 2550 5100 10200 20399 40799 61198 81597 101997 5.60 575 1151 2302 4604 9207 13811 18415 23019
2.80 2452 4903 9807 19613 39226 58840 78453 98066 5.65 565 1130 2261 4521 9042 13563 18084 22605
2.85 2359 4718 9436 18873 37746 56619 75491 94364 5.70 555 1110 2220 4441 8881 13322 17762 22203
2.90 2272 4544 9087 18175 36350 54524 72699 90874 5.75 545 1091 2181 4362 8724 13087 17449 21811
2.95 2189 4379 8758 17516 35032 52547 70063 87579 5.80 536 1071 2143 4286 8572 12858 17144 21430
3.00 2112 4223 8446 16893 33786 50679 67572 84464 5.85 526 1053 2106 4212 8423 12635 16847 21058
3.05 2038 4076 8152 16303 32607 48910 65214 81517 5.90 517 1035 2070 4139 8279 12418 16557 20697
3.10 1968 3936 7872 15745 31490 47235 62980 78725 5.95 509 1017 2034 4069 8138 12206 16275 20344
3.15 1902 3804 7608 15215 30431 45646 60862 76077 6.00 500 1000 2000 4000 8000 12000 16000 20001
3.20 1839 3678 7356 14713 29425 44138 58851 73563 6.05 492 983 1967 3933 7866 11799 15733 19666
3.25 1779 3559 7117 14235 28470 42705 56940 71175 6.10 483 967 1934 3868 7736 11604 15471 19339
3.30 1723 3445 6890 13781 27561 41342 55122 68903 6.15 476 951 1902 3804 7608 11413 15217 19021
3.35 1669 3337 6674 13348 26696 40044 53392 66741 6.20 468 936 1871 3742 7484 11226 14968 18710
3.40 1617 3234 6468 12936 25872 38808 51744 64680 6.25 460 920 1841 3682 7363 11045 14726 18408
3.45 1568 3136 6272 12543 25086 37629 50172 62715 6.30 453 906 1811 3622 7245 10867 14490 18112
3.50 1521 3042 6084 12168 24336 36504 48672 60841 6.35 446 891 1782 3565 7129 10694 14259 17823
3.55 1476 2952 5905 11810 23620 35430 47240 59050 6.40 439 877 1754 3508 7017 10525 14034 17542
3.60 1433 2867 5734 11468 22935 34403 45871 57338 6.45 432 863 1727 3453 6907 10360 13814 17267
3.65 1393 2785 5570 11140 22281 33421 44561 55702 6.50 425 850 1700 3400 6799 10199 13599 16998
3.70 1353 2707 5413 10827 21654 32481 43308 54135 6.55 418 837 1674 3347 6694 10042 13389 16736
3.75 1316 2632 5263 10527 21054 31581 42108 52634 6.60 412 824 1648 3296 6592 9888 13184 16480
3.80 1280 2560 5120 10239 20479 30718 40957 51196 6.65 406 811 1623 3246 6492 9738 12984 16230
3.85 1245 2491 4982 9963 19927 29890 39854 49817 6.70 400 799 1598 3197 6394 9591 12788 15985
3.90 1212 2425 4849 9699 19398 29096 38795 48494 6.75 394 787 1575 3149 6298 9447 12597 15746
161
Time chart
Long time
tr tr
×Ir 0.5 1 2 4 8 12 16 20 ×Ir 0.5 1 2 4 8 12 16 20
6.80 388 776 1551 3102 6205 9307 12410 15512 9.65 191 383 765 1530 3060 4591 6121 7651
6.85 382 764 1528 3057 6113 9170 12227 15283 9.70 189 379 757 1514 3029 4543 6058 7572
6.90 376 753 1506 3012 6024 9036 12048 15060 9.75 187 375 749 1499 2998 4496 5995 7494
6.95 371 742 1484 2968 5936 8905 11873 14841 9.80 185 371 742 1483 2967 4450 5934 7417
7.00 366 731 1463 2925 5851 8776 11702 14627 9.85 184 367 734 1468 2937 4405 5873 7342
7.05 360 721 1442 2884 5767 8651 11534 14418 9.90 182 363 727 1453 2907 4360 5814 7267
7.10 355 711 1421 2843 5685 8528 11371 14213 9.95 180 360 719 1439 2878 4316 5755 7194
7.15 350 701 1401 2803 5605 8408 11210 14013 10.00 178 356 712 1424 2849 4273 5697 7122
7.20 345 691 1382 2763 5527 8290 11053 13816
7.25 341 681 1362 2725 5450 8175 10899 13624
7.30 336 672 1344 2687 5374 8062 10749 13436
7.35 331 663 1325 2650 5301 7951 10601 13252
7.40 327 654 1307 2614 5229 7843 10457 13071
7.45 322 645 1289 2579 5158 7737 10316 12895
7.50 318 636 1272 2544 5089 7633 10177 12721
Short time
7.55 314 628 1255 2510 5021 7531 10041 12552
tsd tsd
7.60 310 619 1239 2477 4954 7431 9908 12385 ×Ir 0.1 0.2 0.3 0.4 ×Ir 0.1 0.2 0.3 0.4
7.65 306 611 1222 2444 4889 7333 9778 12222 1.40 5102 10204 15306 20408 3.40 865 1730 2595 3460
7.70 302 603 1206 2412 4825 7237 9650 12062 1.45 4756 9512 14269 19025 3.45 840 1680 2520 3361
7.75 298 595 1191 2381 4762 7143 9524 11906 1.50 4444 8889 13333 17778 3.50 816 1633 2449 3265
7.80 294 588 1175 2350 4701 7051 9401 11752 1.55 4162 8325 12487 16649 3.55 793 1587 2380 3174
7.85 290 580 1160 2320 4640 6961 9281 11601 1.60 3906 7813 11719 15625 3.60 772 1543 2315 3086
7.90 286 573 1145 2291 4581 6872 9163 11453 1.65 3673 7346 11019 14692 3.65 751 1501 2252 3002
7.95 283 565 1131 2262 4523 6785 9047 11308 1.70 3460 6920 10381 13841 3.70 730 1461 2191 2922
8.00 279 558 1117 2233 4466 6700 8933 11166 1.75 3265 6531 9796 13061 3.75 711 1422 2133 2844
8.05 276 551 1103 2205 4411 6616 8821 11026 1.80 3086 6173 9259 12346 3.80 693 1385 2078 2770
8.10 272 544 1089 2178 4356 6534 8712 10889 1.85 2922 5844 8766 11687 3.85 675 1349 2024 2699
8.15 269 538 1076 2151 4302 6453 8604 10755 1.90 2770 5540 8310 11080 3.90 657 1315 1972 2630
8.20 266 531 1062 2125 4249 6374 8498 10623 1.95 2630 5260 7890 10519 3.95 641 1282 1923 2564
8.25 262 525 1049 2099 4197 6296 8395 10494 2.00 2500 5000 7500 10000 4.00 625 1250 1875 2500
8.30 259 518 1037 2073 4147 6220 8293 10366 2.05 2380 4759 7139 9518 4.05 610 1219 1829 2439
8.35 256 512 1024 2048 4097 6145 8193 10242 2.10 2268 4535 6803 9070 4.10 595 1190 1785 2380
8.40 253 506 1012 2024 4048 6071 8095 10119 2.15 2163 4327 6490 8653 4.15 581 1161 1742 2323
8.45 250 500 1000 2000 3999 5999 7999 9998 2.20 2066 4132 6198 8264 4.20 567 1134 1701 2268
8.50 247 494 988 1976 3952 5928 7904 9880 2.25 1975 3951 5926 7901 4.25 554 1107 1661 2215
8.55 244 488 976 1953 3906 5858 7811 9764 2.30 1890 3781 5671 7561 4.30 541 1082 1622 2163
8.60 241 482 965 1930 3860 5790 7720 9650 2.35 1811 3622 5432 7243 4.35 528 1057 1585 2114
8.65 238 477 954 1908 3815 5723 7630 9538 2.40 1736 3472 5208 6944 4.40 517 1033 1550 2066
8.70 236 471 943 1886 3771 5657 7542 9428 2.45 1666 3332 4998 6664 4.45 505 1010 1515 2020
8.75 233 466 932 1864 3728 5592 7455 9319 2.50 1600 3200 4800 6400 4.50 494 988 1481 1975
8.80 230 461 921 1843 3685 5528 7370 9213 2.55 1538 3076 4614 6151 4.55 483 966 1449 1932
8.85 228 455 911 1822 3643 5465 7287 9108 2.60 1479 2959 4438 5917 4.60 473 945 1418 1890
8.90 225 450 901 1801 3602 5403 7204 9005 2.65 1424 2848 4272 5696 4.65 462 925 1387 1850
8.95 223 445 890 1781 3562 5343 7123 8904 2.70 1372 2743 4115 5487 4.70 453 905 1358 1811
9.00 220 440 880 1761 3522 5283 7044 8805 2.75 1322 2645 3967 5289 4.75 443 886 1330 1773
9.05 218 435 871 1741 3483 5224 6966 8707 2.80 1276 2551 3827 5102 4.80 434 868 1302 1736
9.10 215 431 861 1722 3444 5167 6889 8611 2.85 1231 2462 3693 4925 4.85 425 850 1275 1700
9.15 213 426 852 1703 3407 5110 6813 8516 2.90 1189 2378 3567 4756 4.90 416 833 1249 1666
9.20 211 421 842 1685 3369 5054 6739 8423 2.95 1149 2298 3447 4596 4.95 408 816 1224 1632
9.25 208 417 833 1666 3333 4999 6666 8332 3.00 1111 2222 3333 4444 5.00 400 800 1200 1600
9.30 206 412 824 1648 3297 4945 6594 8242 3.05 1075 2150 3225 4300 5.05 392 784 1176 1568
9.35 204 408 815 1631 3261 4892 6523 8153 3.10 1041 2081 3122 4162 5.10 384 769 1153 1538
9.40 202 403 807 1613 3227 4840 6453 8066 3.15 1008 2016 3023 4031 5.15 377 754 1131 1508
9.45 200 399 798 1596 3192 4788 6384 7981 3.20 977 1953 2930 3906 5.20 370 740 1109 1479
9.50 197 395 790 1579 3159 4738 6317 7896 3.25 947 1893 2840 3787 5.25 363 726 1088 1451
9.55 195 391 781 1563 3125 4688 6251 7813 3.30 918 1837 2755 3673 5.30 356 712 1068 1424
9.60 193 387 773 1546 3093 4639 6185 7732 3.35 891 1782 2673 3564 5.35 349 699 1048 1398
162
Susol / Metasol ACB
163
Memo
164
Susol / Metasol ACB
165
Memo
166
Ordering sheet
For faster quote processing, please use the following request for ordering sheet. For each section, check the applicable box or enter value cerresponding to your choice.
Note) 1. In case of D type of Metasol (AN), frame size is in the range of 630~1600AF
2. The standard accessory for Susol (AH).
3. Aux. contact with extended/high capacity type adopts the rapid auto-reclosing method and available up to 6a6b.
www.ls-electric.com