Hvac Boq-07082014
Hvac Boq-07082014
Hvac Boq-07082014
Contractors should factor in prices for DG power / water / storage etc. None will be
a
provided for at site.
The minimum quality benchmark will be decided by the Owner / Project management
b
consultant / Architect based on mock up samples before commencing work.
Unless otherwise specified the rates quoted shall be inclusive of the following ~ Cost of
c
material, taxes, transport, labour, overheads and profit, etc.,
d No wastages shall be paid separately. The same shall be factored in the quoted rate.
f Quoted rates to exclude taxes and added separately in grand summary sheet.
2 Pumps BOQ
TOTAL 0
SERVICE TAX
Bill of Quantites
Project: NCSCM
SL
DESCRIPTION OF WORK UNIT QTY RATE (Rs.) AMOUNT (Rs.)
NO
Design, Supply, Installation, Testing & Commissioning of Air-Conditioning system
for NCSCM, Chennai as follows:
Water cooled chiller package suitable for HFC 134a having Multiple compressor of
equal capacity of screw type ( semi/hermetic type) complete with suction and
discharge shut off valves and with Variable speed drive, HP/LP cutouts, oil pressure
failure switch, gague panel, cranckcase heater, automatic capacity
control,microprocessor based control for chiller control,watercooled condenser,
1
DX/Flooded chiller,with multiple circuits, controls such as thermostatic expansion
valve, cooling thermostat antifreeze thermostat, water pressure/flow switch
refrigerant pipes and fittings, strainer, sight glass isolating valves, rubber bellows,
suction line and chiller insulation, first charge of gas and oil, base frames, GI casing,
vibration isolators as per specifications.
a 125 TR Water cooled screw chiller with HFC 134a Refrigerant Nos 2
b Installation, clearance, freight upto site, insurance and commissioning charges Nos 2
Single stage centrifugal coupled horizontal type pumpset with axial suction port and
radial discharge port,with EFF1 drive motor, bronze impeller mechnical seal, three
phase TEFC squirrel cage motor with IP55 protection, class F insulation having a
2
speed of 1440 rpm with inertia base, vibration isolation springs, rubber isolation
bellows, flexible coupling for chilled water circulation having the following duty
conditions as per specifications
a 1136 LPM against a head of 10 m with EFF1 motors - Pumps supply only Nos 3
Single stage centrifugal coupled horizontal type pumpset with axial suction port and
radial discharge port,with EFF1 drive motor, bronze impeller mechnical seal, three
phase TEFC squirrel cage motor with IP55 protection, class F insulation having a
3
speed of 1440 rpm with inertia base, vibration isolation springs, rubber isolation
bellows, flexible coupling for chilled water circulation having the following duty
conditions as per specifications
a 1136 lpm against a head of 20 m with EFF1 motors - Pumps supply only Nos 3
Single stage centrifugal coupled horizontal type pumpset with axial suction port and
radial discharge port,with EFF1 drive motor, bronze impeller mechnical seal, three
phase TEFC squirrel cage motor with IP55 protection, class F insulation having a
4
speed of 1440 rpm with inertia base, vibration isolation springs, rubber isolation
bellows, flexible coupling for chilled water circulation having the following duty
conditions as per specifications
a 1420 lpm against a head of 20 m with EFF1 motors - Pumps supply only Nos 3
Non combustible fibreglass towers having cross flow design, basin, PVC louver, drift
eliminator, low noise fan, ladder, vibration isolators, nozzles TEFC squirrel cage type
5 with variable speed induction motor with IP 55 protection and class F insulation
suitable for chiller capacity of following TR and an approach of 5 deg F as per
specifications
b Installation, clearance, freight upto site, insurance and commissioning charges Nos 2
Microprocessor based pump logic controller with adjustable frequency drive for
motor, complete by pass starter with IP 55 Enclosure, Required quantity of
6 differential pressure / temperature transmitter, incoming MCCB / ACB with control
wirng for software integration, built in Software integrator suitable for BAS as per
specifications
a For Secondary pumpset( 2 +1 ) with differential pressure transmitter and wiring Set 1
b Installation, clearance, freight upto site, insurance and commissioning charges Set 1
Floor mounted airhandling unit with double skin consturction complete with filter
section with pre filters and fine filters ( MERV13),Variable speed drives with suitable
7 bypass starters, multi row chilled water coils, fan section with backward curved
plugtype/ direct driven drive motor, canvas, supports,commissioning filters,
vibration isolators and outlet damper, fire damper as per specifications
Air Handling unit having a capacity of 17 TR and 7000 cfm against a static pressure
a Nos 1
of 65 mm WG and suitable drive motor - Supply only
Air Handling unit having a capacity of 12 TR and 5000 cfm against a static pressure
c Nos 1
of 65 mm WG and suitable drive motor - Supply only
Ceiling suspended airhandling unit with double skin construction complete with filter
section with filters, multi row chilled water coils, fan section with forward curved
8
centrifugal fan, drive motor, canvas, supports, vibration isolators, commissioning
filters, outlet dampers, drain pan with pump as per specifications
Air Handling unit having a capacity of 15 TR and 5000 cfm against a static pressure
a Nos 1
of 50 mm WG and suitable drive motor - Supply only
Air Handling unit having a capacity of 10 TR and 4000 cfm against a static pressure
c Nos 10
of 40 mm WG and suitable drive motor - Supply only
Air Handling unit having a capacity of 7.5 TR and 3000 cfm against a static pressure
e Nos 7
of 40 mm WG and suitable drive motor - Supply only
Air Handling unit having a capacity of 5 TR and 2000 cfm against a static pressure
g Nos 5
of 40 mm WG and suitable drive motor - Supply only
Air Handling unit having a capacity of 3 TR and 1200 cfm against a static pressure
i Nos 4
of 40 mm WG and suitable drive motor - Supply only
Air Handling unit having a capacity of 2.5 TR and 1000 cfm against a static pressure
k Nos 1
of 40 mm WG and suitable drive motor - Supply only
High Precision Units floor mounted type with chilled water coil, fine filter, heater and
humidifier section, EC fan, drive motor, for evaporator fan, return air louvers, MS /
10
GI powder coated casing, microprocessor control, hardware and software for BAS
hookup, controls as per specifications.
High Precision Units floor mounted type with DX coil, fine filter, heater and
humidifier section, EC fan, drive motor, Variable speed drive for evaporator fan,
11
return air louvers, MS / GI powder coated casing, microprocessor control, hardware
and software for BAS hookup, controls, ref. Piping as per specifications.
Copper refrigerant piping, insulation, drain piping, frame work for indoor and
outdoor and other accessories including Electrical cable/wiring and Clearance,
c Lot 1
Freight upto site Transportation, insurance installation and commissioning(Indoor
and out door units location to be reffered In the drawing)
Chilled water Fan coil unit of double skin construction with compact cooling coil,
multispeed fan motor, the blower shall be dynamicaly balanced and designed for
silent operation, the filters shall be washable synthetic media type arranged for
convenient cleaning and replacement, drain pan with pump .The units as specified in
Schedule of Quantities shall be factory fitted with valve package comprising of 2 way
12
pressure independent valve suitable for variable CHW flow with modulating actuator,
ball with Y strainer valve at inlet & Ball valve at outlet and necessary piping
connections. The actuator of modulating valve shall be provided with interface cards
to receive 0-10V or 4-20 mA signal from Minxon Digital Thermostat.The unit is
supplied with corded remote controller of approved as per specifications
Fan Coil Unit having a capacity of 1 TR and 400 cfm against a static pressure of 15
a Nos 18
mm WG and suitable drive motor - Supply only
Chilled water Cassette type indoor units with compact cooling coil, multispeed fan
motor, the blower shall be dynamicaly balanced and designed for silent operation, the
filters shall be washable synthetic media type arranged for convenient cleaning and
replacement and inbuilt drain pump.The units as specified in Schedule of Quantities
shall be factory fitted with valve package comprising of 2 way pressure independent
13
valve suitable for variable CHW flow with modulating actuator, ball with Y strainer
valve at inlet & Ball valve at outlet and necessary piping connections. The actuator of
modulating valve shall be provided with interface cards to receive 0-10V or 4-20 mA
signal from Minxon Digital Thermostat.The unit is supplied with corded remote
controller of approved as per specifications
Cassette Unit having a capacity of 3.0 TR and 1200 cfm against a static pressure of
a Nos 1
15 mm WG and suitable drive motor - Supply only
Cassette Unit having a capacity of 2.5 TR and 1000 cfm against a static pressure of
c Nos 3
15 mm WG and suitable drive motor - Supply only
Cassette Unit having a capacity of 2.0 TR and 800 cfm against a static pressure of 15
e Nos 5
mm WG and suitable drive motor - Supply only
Chilled water High wall mounted indoor units with compact cooling coil, multispeed
fan motor, the blower shall be dynamicaly balanced and designed for silent operation,
the filters shall be washable synthetic media type arranged for convenient cleaning
and replacement and drain pan.The units as specified in Schedule of Quantities shall
be factory fitted with valve package comprising of 2 way pressure independent valve
13
suitable for variable CHW flow with modulating actuator, ball with Y strainer valve
at inlet & Ball valve at outlet and necessary piping connections. The actuator of
modulating valve shall be provided with interface cards to receive 0-10V or 4-20 mA
signal from Minxon Digital Thermostat.The unit is supplied with corded remote
controller of approved as per specifications
Hiwall Unit having a capacity of 1.0 TR and 400 cfm against a static pressure of 15
a Nos 5
mm WG and suitable drive motor - Supply only
Supply, installation testing & commissioning of Hi wall Split air conditioner of 1.0
TR /400 cfm capacity with Scroll compressors with matching condensers MS Frame
14 Nos 1
for mouting the units to be provided with rubber pads, the frame should be painted
with two coats for ATM ground floor.
Copper refrigerant piping, insulation, drain piping, frame work for indoor and
outdoor and other accessories including Electrical cable/wiring and Clearance,
a Lot 1
Freight upto site Transportation, insurance installation and commissioning(Indoor
and out door units location to be reffered In the drawing)
Supply, Installation, Testing and commisioning of Double skin outdoor mounted type
Heat recovery unit made of 50mm thick panels consisting of GI casing of thickness
0.63mm outside layer and 0.63mm inside layer with factory injected PUF insulation,
Supply & Return air Centrifugal blower(Forward curved/backward curved)sections
with aerofoil constructions, Heat recovery wheel section, belt drive packages with
TEFC motor suitable for operation on 415 +/- 10% volts, 50 Hz, 3 phase, A.C. power
15 supply, Fresh air Pre-filter section, Heat recovery descicant wheel, Fresh air, return
air & exhaust air dampers with suitable actuator with a provision for CO2 signal
sensing,CO2 sensors with wiring to be included for each unit and all the necessary
accessories, necessary vibration isolators and complete as per specifications. The
duties of equipments listed below and accessories shall be as per equipment schedule.
Heat recovery wheel efficiency should not be less than 75%. Unit shall be with VFD
and with suitable bypass starter and BMS compatible and as per specifications
900 Cfm Fresh air and Exhaust against a static pressure of 50 mm WG having
a Nos 2
suitable drive motors
Cabinet type Exhaust air handling unit with double skin construction complete with
damper gravity louver, cengrifugal blower, 3 phase drive motor, anti vibration
18
mounts suitable for floor mounting with commissioning filters having capacities as
follows as per specifications:
a 4500 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1
b 2800 cfm against a static pressure of 40mm WG having suitable drive motor Nos 2
b 2200 cfm against a static pressure of 40mm WG having suitable drive motor Nos 3
c 1650 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1
Cabinet type Fresh air handling unit with double skin construction complete with
damper gravity louver, cengrifugal blower, 3 phase drive motor, anti vibration
18
mounts suitable for floor mounting with commissioning filters having capacities as
follows as per specifications:
a 2450 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1
b 2250 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1
c 1870 cfm against a static pressure of 40mm WG having suitable drive motor Nos 2
d 1400 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1
e 1150 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1
Inline type Fresh air fan with double skin construction complete with damper gravity
19 louver, centrifugal blower, 3 phase/1 Phase drive motor, anti vibration mounts
suitable for floor mounting having capacities as follows as per specifications
a 500 cfm against a static pressure of 20mm WG having suitable drive motor Nos 1
b 350 cfm against a static pressure of 20mm WG having suitable drive motor Nos 1
Cabinet type Exhaust air handling unit( Kitchen area ) with double skin construction
complete with damper gravity louver, cengrifugal blower, 3 phase drive motor, anti
20
vibration mounts suitable for floor mounting with commissioning filters having
capacities as follows as per specifications:
a 4600 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1
Cabinet type Fresh air handling unit( Kitchen area ) with double skin construction
complete with damper gravity louver, cengrifugal blower, 3 phase drive motor, anti
21
vibration mounts suitable for floor mounting with commissioning filters having
capacities as follows as per specifications:
a 3700 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1
Machine made GSS Ducting with flanges, neoprene gaskets, factory made supports,
22
with black painting as per specifications (factory made with ductmate flanges)
a 24 G Sqm 2150
b 22 G Sqm 650
c 20 G Sqm 5
Aluminium volume control dampers with PVC gear and opposed blades with handle
24
as per specs.(Shall be suitable for motorised actuation)
GSS Fire Dampers with 90 min fire rating with temperature sensor, alarm panel with
25 motorised actuator, provision for receipt of external fire signal, wiring as per
specifications.
Floor grilles with extruded aluminium louvres, 4 quadrant with independent volume
30 Nos 6
control dampers and frame work having a size of 600 x 600 mm as per specifications
32 Aluminium powder coated continous grilles with 0/15 deg. Deflection as follows
Aluminium powder coated Spot grille/Stoke discreate grille with 0/15 deg.Deflection
33
as follows
a 1000x100 Nos 9
34 Aluminium powder coated Supply/exhaust air Disc valve with opposed blade
PVC flexible duct with worm drive clamps having the following sizes as per
35 specifications as follows:(alternatively single skin aluminium flexible shall be
offered)
Acoustic lining of ducting with 15mm thick open cell nitrile rubber insulation with
36 Sqm 500
aluminium tape as per specifications
Duct insulation with 15 mm thick close cell nitrile rubber insulation factory
37 Sqm 1300
laminated aluminium foil and aluminium tape as per specs
Chilled water piping with black steel pipes, fittings, RCC Sleepers, factory made
supports, sand cushioning including digging and refilling of earth for buried pipes
38
along with Thermal insulation of buried chilled water pipes with TF Quality EPS
insulation, finished with sand cement plaster and tarfelt as per specifications:
MS pipes for chilled water applications above ground with 19 mm thick nitrile
39 rubber which bonds to the pipe, the outer casing material shall be galvanized,
stainless steel or high density polyethylene tubes with vapour barrier, comply to class
O fire rating standards with comprehensive strength upto 275 kPa, the PU Foam shall
be CFC Free agent finished with supports/hangers as per specifications
ABOVE GROUND
MS 'C' Class pipe with insulation as per specifications,
MS B Class
All valves are to be considered with nitrile rubber insulation finished with polyshied
as per specifications
Two way motorised valve with actuator and transformer as per specifications having
43
the following water flow, clearance, installation and with insulation as follows,
46 100 mm dia Dial type pressure gauges with thermo port Nos 112
Drain piping using CPVC pipe SDR11 with CPVC fittngs and insulated with 6mm
48 thick nitrile rubber insulation finished with polyshield. The pipe goes below ground
should be rapped with polythene sheet as follows:
UNDER GROUND
Above GROUND
b 50 mm dia Rmt 45
c 40 mm dia Rmt 30
d 32 mm dia Rmt 50
e 25 mm dia Rmt 350
Membrane type automatic expansion tank having a capacity of 1000 litres as per
49 Nos 1
specifications
50 Condenser water pipes with black steel fittings, factory made supports as follows:
ABOVE GROUND
MS 'C' Class pipe with insulation as per specifications,
52 100 mm dia Dial type pressure gauges with thermo port Nos 10
The air seperator with Dirt seperator fabricated with Steel finished with dirt chamber,
air chamber, vent units, automatic valve, drain valve, suitable for flushing even when
54
in operation, suitable for threaded or flanged connections as per specifications of the
following sizes
TOTAL
Supply and fixing of modular 6/16A,5 pin single phase switch socket outlet fixied in
a suitable size metal sheet box suitable for switches and sockets,including supply of
fixing materials interconnections complete as required and approved by the
consultant/client.
Supply and installation of following TPN/SPN MCB DBs of CRCA sheet steel
enclosure,dust and vermin proof ,rated for 440V/230V. 3/1 phase,50 HZ AC supply,
operation(doubledoor type )inclusive of busbar of suitable capacity,neutral link with
required outgoings,DIN bar,and earthing terminals and with silicon based fire/ Heat
resistant coating appiled inside the DB and painted with approved shade of paint
suitable for incorporating SP/DP/TP MCB as specified below with all materials
required including supply and fixing of MCBs/ ELMCBs / Isolators/ SFUs and fixed
in flush with wall along with all materials required including all associated civil
works and earthing as per specifications and the SLD, The MCB & MCCB' S have
the Ka Rating-10kA
Supply Each 9
Installation Each 9
4 LT XLPE Cables
Supply of 1.1 KV grade, 2C/3C/3.5C/4C, XLPE insulated, and PVC overall sheathed,
stranded aluminium/Copper conductor, flat steel strip/ wire armoured cables
conforming to IS:1554/ Part I (with latest amendments)and of following sizes.The
cable shall bear ISI certification mark. Laying of the cable in ground/existing cable
tray/duct/shaft including transportation of cable to site,excavation of earth, laying the
cable and covering with sand and placing the bricks on sides and top,refilling with
earth and providing cable route/ joint markers complete as required. (the laying of
cable in trench shall include removing the trench cover, reclosing it after laying cable
in good condition and fixing it to the cable suupports on wall with suitable clamps
including supply of clamps complete as required)
4.2 4C X 25 Sq.mm AR. AL Cable (for Primary pumps, secondary pumps and cooling
towers,DB )
Supply Mtrs 500
Laying Mtrs 500
4.3 4C X 6Sq.mm AR. AL Cable (AHU )
Supply Mtrs 200
Laying Mtrs 200
5 LT XLPE Cables End termination
(Tinned copper lugs, long barrel )
5.1 3.5C X 150 Sq.mm AR. AL Cable (for CHILLERS) Nos 4
5.2 4C X 25 Sq.mm AR. AL Cable (for Primary pumps, secondary pumps and cooling Nos 24
towers) )
Supply and instllation of 2mm thick GI perforated/ ladder type cable tray with side
rail using suitable revets, washers, bolts,supporting brackets of same make and all
other accessories required for fixing the cable tray complete as required and as
directed by the Engineer-in-charge.
Supply and Laying and fixing of FRLS PVC conduits of 2mm thick of the following
sizes in slab or external with necessary fixing accessories for PA system, home
automation and bms integaration as required with necessary accessories such as
bends, collars, junction boxes and pull boxes and with covering covering plate as
required as per the site condition and as approved by the client/ consultants.
8 EARTHING STRIP
8.1 25x6mm GI strip (body earthing for Fencing, SUB- panels and DBs) Mtrs 200
8.2
8 Guage CU. strip (body earthing for Primary,Secondary,Cooling Towers,Chillers) Mtrs 50
8.3 DANGER BOARDS :
Supplying & fixing of 0.415KV danger boards with the word "DANGER" written in Nos. 5
English & Kannada as per EB/LOCAL EB AUTHORITIES requirement.
8.4.3
Danger Boards on subpanels, In English, HINDI & LOCAL LANGUAGE. Nos. 20
8.4.4
Artificial Respiration Charts-In English, HINDI & LOCAL LANGUAGE Nos. 1
TOTAL
GRAND TOTAL