DATA SHEET FOR LV SWITCHGEAR

XX DD-MM-YYYY XXX XXX XXX Issued for EBOK

REV. DATE ORIGINATOR REVIEWED APPROVED APPROVED DESCRIPTION

THIS DOCUMENT IS INTENDED FOR USE BY ITS NOMINATED CONSULTANTS, CONTRACTORS, MANUFACTURERS AND SUPPLIERS.

COMPANY: XXXXXXXXXXXXXXXXXXXXX

ORIGINATOR:

Page: 1 of 6
DATA SHEET FOR LV SWITCHGEAR
0 0

0 Page : 2 of 6

The table below is a brief summary of the most recent revisions to this document. Details of all revisions are held on
document by the issuing department.

Sr. No. Rev. No. Issue No. Date of issue Description of revision
1 A 1 DD-MM-YYYY Issued for EBOK
DATA SHEET FOR LV SWITCHGEAR
0 0

0 Page : 3 of 6

1 SCOPE
THIS DOCUMENT COVERS THE TECHNICAL AND DESIGN REQUIREMENTS IN A FORM OF DATASHEET FOR THE LV SWITCHGEAR
INSTALLED IN PROJECT FACILITIES OF FERRUKA-HARARE PIPELINE SERIES OPERATION.

2 GENERAL NOTES

1) * - DATA BY VENDOR
2) THE SWITCHGEAR SHALL BE RATED TO OPERATE SATISFACTORILY UNDER AN AMBIENT TEMPERATURE OF 37°C AND SHALL BE
CAPABLE OF OPERATING AT 50°C FOR A PERIOD OF FOUR (4) HOURS, DURING THE FAILURE OF AIR-CONDITIONING WITHOUT
AFFECTING ITS LIFE SPAN AS WELL AS ITS PERFORMANCE.
3) CT, PT BURDEN & ACCURACY CLASS TO BE VERIFIED AND SELECTED BY VENDOR INCLUDING BASIS OF CALCULATION.
4) VENDOR TO FURNISH CATALOG DETAILS OF CIRCUIT BREAKER, RELAY ETC.
5) VENDOR TO FURNISH INSPECTION AND TEST PLAN, FACTORY ACCEPTANCE TEST PROCEDURE.
6) VENDOR TO SUBMIT TYPE TEST CERTIFICATES FOR SWITCHGEAR, FOR PURCHASER'S REVIEW.
7) UNIT RATES FOR ADDITION / DELETION OF VARIOUS FEEDERS SUCH AS INCOMER, OUTGOING MOTOR FEEDERS ETC. FOR DIFFERENT
CONTINUOUS AND SHORT CIRCUIT RATING SHALL BE PROVIDED.
8) ALL STATUS SIGNAL CONTACTS SHALL BE VOLT- FREE CONTACTS. COMMANDS AND STATUS SIGNALS SHALL BE WIRED UPTO
MARSHALLING CABINET PROVIDED IN EACH SHIPPING SECTION. INTERPANEL WIRING SHALL BE DONE BY VENDOR.
9) EMERGENCY TRIPPING FACILITY FROM ESD SYSTEM SHALL BE INCORPORATED IN THE WIRING DIAGRAM.
10) LANGUAGE OF DOCUMENTS AND LANGUAGE ON EQUIPMENT SHALL BE ENGLISH.
11) VENDOR SHALL FURNISH 230V AC NON UPS POWER REQUIREMENT FOR PANEL / MOTOR SPACE HEATER ALONG WITH BID.
12) VENDOR SHALL FURNISH 110V AC UPS POWER REQUIREMENT FOR CLOSING COIL, TRIPPING COIL, SPRING CHARGING MOTOR,
RELAYS, BREAKER CONTROL SUPPLY, ETC.
13) NORMAL IDENTIFICATION LABELS SHALL BE IN WHITE BACKGROUND WITH ENGRAVED BLACK LETTER.
14) WARNING & DANGER LABELS SHALL BE IN RED BACKGROUND WITHENGRAVED WHITE LETTER IN ENGLISH.
15) RATINGS SHALL BE UPDATED BY THE CONTRACTOR BASED ON FINAL VENDOR DATA DURING DETAILED ENGINEERING.
16) MANUAL CHARGING HANDLE SHALL BE PROVIDED FOR MANUALLY CHARGING THE SPRING.
17) VENDOR SHALL PROVIDE SUITABLE SURGE ARRESTORS IN ALL CIRCUITS WHERE REQUIRED.
18) FOR UNIT PROTECTION (TRANSFORMER DIFFERENTIAL AND RESTRICTED EARTH FAULT) SCHEMES, SWITCHGEAR VENDOR SHALL
CO-ORDINATE WITH EQUIPMENT SUPPLIER FOR PROPER MATCHING OF CURRENT TRANSFORMER
19) MIMIC DIAGRAM SHALL BE SHOWN ON EACH SWITCHGEAR PANEL.
20) VENDOR SHALL INDICATE HEAT LOAD OF THE SWITCHGEAR IN THE BID.

3 ABBREVIATIONS
AC ALTERNATING CURRENT
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
API AMERICAN PETROLEUM INSTITUTE
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ATEX ATMOSPHERES EXPLOSIVE
BS BRITISH STANDARDS
BSEN BRITISH STANDARDS EURO NORMES
CT CURRENT TRANSFORMER
DC DIRECT CURRENT
EMC ELECTRO-MAGNETIC COMPATIBILITY
EMI ELECTROMAGNETIC INTERFERENCE
EN EURO NORM
ESD EMERGENCY SHUT DOWN
FAT FACTORY ACCEPTANCE TEST
FO FIBER OPTIC
HAZOP HAZARD AND OPERABILITY
HFI HIGH FLASH INTERFACE
MV HIGH VOLTAGE
IAC INTERNAL ARC CLASSIFICATION
ICS INSTRUMENT CONTROL SYSTEM
IEC INTERNATIONAL ELECTROTECHNICAL COMMISSION
IMCS INTEGRATED MACHINE CONTROL SYSTEM
IP INGRESS PROTECTION
ISO INTERNATIONAL ORGANIZATION FOR STANDARDIZATION
LFI LOW FLASH INTERFACE
LV LOW VOLTAGE
MCB MINIATURE CIRCUIT BREAKER
MCCB MOULDED CASE CIRCUIT BREAKER
NEMA THE NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
OEM ORIGINAL EQUIPMENT MANUFACTURER
PFD PROCESS FLOW DIAGRAM
PM PARTITION OF METAL
PTC POSITIVE TEMPERATURE COEFFICIENT
PVC POLY VINYL CHLORIDE
RTD RESISTANCE TEMPERATURE DETECTOR
SAT SITE ACCEPTANCE TEST
SCADA SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM
SCPD SHORT CIRCUIT PROTECTIVE DEVICE
SF6 SULFUR HEXAFLUORIDE
SLD SINGLE LINE DIAGRAM
TCP/IP TRANSFER CONTROL PROTOCOL / INTERNET PROTOCOL
TRV TRANSIENT RECOVERY VOLTAGE
UPS UNINTERRUPTED POWER SUPPLY
VCB VACUUM CIRCUIT BREAKER
VSC VARIABLE SPEED COUPLING
VSD VARIABLE SPEED DRIVE
XLPE CROSS-LINKED POLYETHYLENE
ZESA ZIMBABWE ELECTRICITY SUPPLY AUTHORITY
DATA SHEET FOR LV SWITCHGEAR
0 0

0 Page : 4 of 6

4 REFERENCE STANDARDS

2014/34/EU DIRECTIVE 2014/34/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL OF 26 FEBRUARY 2014 ON THE LAWS OF THE MEMBER
STATES RELATING TO EQUIPMENT AND PROTECTIVE SYSTEMS INTENDED FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES
(RECAST) TEXT WITH EEA RELEVANCE.
The International Electrotechnical Commission Standards
IEC 60038 IEC Standard Voltages
IEC 60050 International electrotechnical vocabulary
IEC 60051 Direct acting indicating analogue electrical measuring instruments and their accessories
IEC 60060 High-Voltage Test Techniques
IEC 60071 Insulation coordination
IEC 60073 Basic and Safety Principles for Man-Machine Interface, Marking and Identification - Coding Principles for Indication Devices and
IEC 60255 Measuring relay and protection equipment.
IEC 60269 Low-voltage fuses.
IEC 60417 Graphical Symbols for Use on Equipment
IEC 60445 Basic and Safety Principles for Man-Machine Interface, Marking and Identification - Identification of Equipment Terminals and of
IEC 60470 High-Voltage Alternating Current Contactors and Contactor-Based Motor-Starters
IEC 60529 Degrees of protection provided by enclosures (IP code)
IEC 60617 Graphical Symbols for Diagrams
IEC 60644 Specification for High-Voltage Fuse-Links for Motor Circuit Applications
IEC 60909, short-circuit current calculations
IEC 60947 Low-voltage switchgear and control gear
IEC 61000 Electromagnetic Compatibility (EMC)
IEC 61850 Communications Networks and Systems in Substations
IEC 61869-1 Instrument transformers – General requirements
IEC 61869-2 Instrument transformers – Additional requirements for current Transformers.
IEC 61869-3 Instrument transformers – Additional requirements for inductive voltage Transformers.
IEC 62208 Empty enclosures for low-voltage switchgear and control gear assemblies –General Requirements
IEC 62271 High-Voltage Switchgear and Control gear
IEC/TR 61641 Enclosed low-voltage switchgear and control gear assemblies - Guide for testing under conditions of arcing due to internal fault
IEEE C37.20.7 Guide for Testing Metal-Enclosed Switchgear Rated Up to 38 kV for Internal Arcing Faults
International Organization for Standardization
ISO 9001 Quality management systems-Requirements
S.No DESCRIPTION DESIGN DATA VENDOR DATA
GENERAL
1 MANUFACTURER NAME *
2 COUNTRY OF ORIGIN *
3 GOVERNING MANUFACTURING STANDARD *
4 SWIITCHGEAR SERIES NAME *
5 TYPE TESTED SWITCHBOARD ( YES / NO) Yes
6 LIST OF TYPE TEST WITH DATE OF VALIDITY *
7 NAME OF TESTING AUTHORITY *
8 APPLICABLE REFERENCE DOCS
9 SPECIFICATION SPECIFICATIONFOR LV SWITCHGEAR Doc. No. XXXXX
10 MANUFACTURING STANDARD IEC 60947
11 SWITCHGEAR SLD REFER SLD
12 SWITCHGEAR TAG REFER SLD
13 SERVICE / SITE CONDITIONS
14 SERVICE/APPLICATION ELECTRICAL LOADS
15 ALTITUDE IF > 1000 m XXX
16 MAXIMUM AMBIENT TEMPERATURE XXX°C
17 DESIGN AMBIENT TEMPERATURE XXX°C
18 MAXIMUM HUMIDITY XX% APPROX.
19 SPECIAL CONDITIONS (TROPICALISATION, etc.) TROPICALISATION
20 AREA CLASSIFICATION
21 SAFE / HAZARDOUS SAFE
22 INDOOR / OUTDOOR INDOOR
23 SYSTEM CHARACTERISTICS
24 TYPE SINGLE FRONT
ASSEMBLY EXTERNAL DESIGN (ENCLOSED, CUBICLE, MULTI-
25 ENCLOSED MULTICUBICLE
CUBICLE, BOX, MULTI-BOX)
26 INTERNAL SEPARATION (FORM 1, FORM 2, …) & TYPE FORM 3A
27 WITHDRAWABLE / PLUG-IN FIXED / ... WITHDRAWABLE
28 MOUNTING FLOOR MOUNTED
29 ACCESS FRONT
30 CABLES ENTRY BOTTOM
31 FOOT PLINTH YES
32 NETWORK
33 VOLTAGE 400 V ± 10 %
34 FREQUENCY 50 Hz ± 1 %
35 VOLTAGE VARIATION +10% /-10%
36 SHORT CIRCUIT RATING 50kA / 1Sec
37 NEUTRAL EARTHING SYSTEM TN-S
38 SWITCHGEAR
39 RATED OPERATIONAL VOLTAGE 400 V± 10 %
40 RATED CURRENT 600 A (HOLD)
41 RATED SHORT-TIME WITHSTAND CURRENT FOR 1 SECONDS 50kA / 1Sec
Approximately 1.6 to 1.8 times the Rated Short time withstand
42 RATED PEAK WITHSTAND CURRENT
current (IEC 60909)
INTERNAL ARC FAULT PROTECTION FOR 0.3 SECONDS
43 YES
(Y / N) FOR RATED SHORT CIRCUIT CURRENT
44 VECTOR ROTATION Clockwise
45 COLOUR RAL 7035
46 MAIN BUSBAR
47 RATING AT SITE CONDITION 800A (HOLD)
48 BUSBAR SYSTEM SINGLE & INSULATED
49 BUSBAR CONFIGURATION 3Ph + N
50 EARTH BUSBAR
51 CONDUCTOR BARE OR TINNED COPPER
52 BUSBAR SYSTEM THROUGHOUT THE SWITCHGEAR LENGTH
53 AUXILIARY VOLTAGES
54 INTERNAL (I) / EXTERNAL (E) VOLTAGE SUPPLY INTERNAL 240 V AC / EXTERNAL 110 V AC
55 CONTROL SYSTEM 110V AC ± 10 %
56 CIRCUIT BREAKER COILS 110V AC ± 10 %
57 PROTECTION RELAYS 110V AC ± 10 %
58 AUXILIARY RELAYS 110V AC ± 10 %
59 SIGNALISATION 110V AC ± 10 %
60 CONTACTOR COILS 240V AC
61 INCOMER CUBICLE TECHNICAL CHARACTERISTICS
62 BREAKING DEVICE
63 ISOLATING DEVICE & BREAKING DEVICE MOTORIZED MCCB
64 RATINGS OF BREAKING DEVICES 600A (HOLD)
65 MEASUREMENT
Y / (MIN. A, V, W, VA, VAr, f, PF, kWh,
66 SEPARATE DIGITAL MULTIFUNCTIONAL METER (DMM)
KVArh)
67 REMOTE MONITORING FROM DCS YES
68 CURRENT TRANSFORMER FOR MEASUREMENTS AND PROTECTION
69 RATIO / QTY *
70 CLASS *
71 BURDEN *
72 SWITCHGEAR STATUS (AS A MINIMUM)
73 CIRCUIT BREAKER OPEN/CLOSED YES
74 CIRCUIT BREAKER READY FOR CLOSE YES
75 CIRCUIT BREAKER SERVICE / TEST / ISOLATATED YES
76 LOCAL/REMOTE YES
77 SWITCHGEAR ALARM AND TRIP (AS A MINIMUM)
78 INST OVERCURRENT TRIP YES
79 INST EARTHFAULT TRIP YES
80 IDMT OVER CURRENT YES
81 TRIP CIRCUIT FAULTY YES
82 CIRCUIT BREAKER LOCKOUT YES
83 UNDER VOLTAGE ALARM YES
84 INTER-TRIP RECEIVE YES
85 TRANSFORMER TRIP STATUS SIGNAL YES
86 VOLTAGE TRANSFORMERS
87 RATIO / QTY *
88 DRAWOUT FIXED TYPE DRAWOUT
89 SWITCHBOARDS CONTROLS
90 CLOSED / OPEN (Y / N) YES
91 TRIPPED (Y / N) YES

Datasheet for LV Switchgear 5 of 6


S.No DESCRIPTION DESIGN DATA VENDOR DATA
92 MECHANICAL (Y / N) / ELECTRICAL (Y / N) YES / YES
93 REMOTE CONTROL (Y / N) FROM DCS (CLOSE AND OPEN) YES (HARDWIRED)
94 INTELLIGENT PROTECTION RELAYS
95 FEEDING DIRECT, BY CT OR VT BY CT & VT
96 LIST OF ANSI DEVICE CODE NUMBERS AS PER SLD
MICROPROCESSOR BASED WITH SELF DIAGNOSTIC
97 TYPE
FACILITIES & SERIAL COMMUNICATION DRAWOUT
VOLTAGE / CURRENT TEST TERMINAL, BOXES AND SOCKETS (Y /
98 YES
N)
99 OUTGOING FEEDER (REFER SLD)
100 OUTGOING CUBICLE TECHNICAL CHARACTERISTICS
101 ISOLATING DEVICE & BREAKING DEVICE RATING AS PER SLD
102 DISCONNECTING SWITCH (Y / N) YES
103 FUSES (Y / N) NO
104 START/STOP FROM DCS NO
105 MOTOR STARTER FEEDERS
106 ISOLATING DEVICE & BREAKING DEVICE MCCB OR ACB (NOTE-8)
107 PLUG BUSHING CONTACTS (Y / N) ***
108 DISCONNECTING SWITCH (Y / N) NO
109 SWITCH (Y / N) NO
110 CONTACTOR (Y / N) YES
111 FUSES (Y / N) NO
112 CIRCUIT BREAKER (Y / N) YES
113 START/STOP FROM IMCS & DCS YES
114 TRIP COMMAND FROM ESD YES
115 MOTOR RUNNING INDICATION IMCS & DCS YES
116 FOR CRITICAL & NON-CRITICAL MOTOR YES
117 LABELS
118 LANGUAGE ON DOCUMENTS ENGLISH
119 LANGUAGE ON LABELS/EQUIPMENT DUTCH
120 MAIN LABEL (FRONT / BACK) FRONT
121 FUNCTIONAL UNIT LABELS (FRONT / BACK) FRONT
122 COLOUR WHITE BACKGROUND BLACK LETTERING
123 SWITCHGEAR ARRANGEMENT
124 LENGTH / WIDTH / HEIGHT *
125 TOTAL WEIGHT *
126 HEAT LOSS *
127 NUMBER & SIZE OF UNITS *
128 ACCESSORIES AND MISCELLANOUS
129 MOUNTING CHANNELS & FIXING ACCESSORIES (Y / N) YES
130 LIFTING EYEBOLTS (Y / N) YES
131 HANDLING TRUCK (Y / N) NO
132 SET OF SAFETY DEVICES (Y / N) NO
133 DOOR LOCKING YES
134 PADLOCKING FACILITIES YES
135 GLAND PLATE YES
136 INTERNAL MAINTENANCE LIGHT WITH DOOR SWITCH YES
137 SPACE HEATER WITH THERMOSTAT YES

Datasheet for LV Switchgear 6 of 6