Noaa 34984 DS1
Noaa 34984 DS1
Noaa 34984 DS1
MarineRefrigeration
Same
TipsonDesign,
tnstallatian,
andServicing
OregonStateUniversity
ExtensionMarineAdvisoryProgram
A LandGrant/ SeaGrantCooperative
Special Report 488
Reprinted June 1983
50ANCOPY
Ogiy
CIRCIjLATtII8
COI'7
SoaGrantDepository
3. Thermo King Service School Training Manual on Basic
Refrigeration. A limited supply is free and avail-
able in this area by contacting: Don Bachelder or
Bill Pascoe, Standard Parts and Equipment Company,
P. 0. Box 42294, 5251 S.E. McLoughlin Boulevard,
Portland, Oregon 97202 -800-452-8i07!.
~ae
i. ENGINEERING DESIGN
1. Pumps js
Sizing and Selection
16
2. Chillers
Closed Chillers
Open Coil Chillers
Operating Temperatures
~ae
26
I I. MAINTENANCE, TROUBLESHOOTING,AND REPAIR
26
A. System Shutdown
26
B. Refrigerant Shortage
About Troubleshooting
Leak Detection
Making Repairs
Adding Refrigerant
C. Component Servicing 30
Comp re s so r
Lubrication
Head Pressure
Expansion Valve
Condenser
What To Do After It Fails
Filters/Driers
Receiver
Chiller
INDEX 36
z' 12
0
10
0
uJ
R4
U FI GURL 1
0
40 -30 -20 -l 0 0 10 20 30 40
EVAPORATOR TE MP. ' F
jlI
Compressor running at l,7SO RPM, using R- 22, condenser temperature
at 108 'F, liquid is subcooled li' after leaving condenser and
before entering t.-xpansion valve.
As the temperature of the evaporating refrigerant gets lower
and therefore, as the suction pressure goes down!, the system
is able to deliver less and less capacity.
l4
IJJ
~2
Cl
z l0
z
0
z6
0
FIGURE 2
0
-40 -30 -20 -I0 0I 0 20 30 40
EVAPORATOR TEMP. F
H ULL
LANKING
FRAME L
AIR SPACE
EVAPORATOR
FIG
RETURN HEADER
Note that too small a pipe is also bad, because excessive pressure
drops will affect system performance.
to carry oil upwardFigure6!. During periodsof low refriger-
ant flow, the P-trap fills with oil, forcing refrigerant gas up
the right-handriser E!. Because all the gasgoesup oneriser,
the velocity is higher andthe remainingoil droplets are carried
along. Later, whenthe refrigerant gasflow returns to a high
volume,the pressureat point F! increasesto a valuesufficient
to blow the oil out of the P-trap and into the compressor,after
whichgas is returned along both risers at a high velocity. Note
that both legs of the doublesuction riser haveloops at the top
wherethey join the mainreturn line. This preventsoil from
draining into oneof the legs during a period of low flow. In
general,oneP-trap is neededfor every20 feet of rise. If the
rise is only a few feet, a P-trap is not necessary.
F IGUR.
F IG
a. Refrigerant Selection
Compressor
We've already looked at recommendedsystem and compressor
sizing Section 1, "Sizing of the System"!: a boat with 30 tons
of hold capacity would need a compressor of about 10 horsepower,
which, rated at 40 'F suction temperature, would be close to 10
refrigeration tons. Rememberthat compressor speed, refrigerant,
and operating pressures strongly affect its capacity. If you
happen to have a compressor that's too big for the job, just slow
it down. For example, a compressor putting out lS tons at 1,200
RPMwould put out five tons at around 400-S00 RPM. A manufac-
turer will generally give a minimum allowable speed of 600-700
RPM. This is their recommended minimum for adequate lubrication
on compressors with farce-feed oil systems. Usually it's pos-
sible to go below this to, say, 400-500 RPM!without having
any problems.
A previous section " Configuration and Controls" ! discussed.
evaporator temperature control, and how this might influence the
selection of a compressor. For RSW refrigerated seawater! sys-
tems, temperature control is more critical than in brine spray/
freezer systems. There are two ways to go. The cheaper way is
to buy a conventional compressor plus some intricate valves
"gadgets"! such as back pressure regulators' The better way
although more expensive! is to buy a variable capacity compres-
sor* which will unload. cylinders to maintain a constant suction
temperature.
EX PANSION
EVAPORATOR
F I GURE
27 F
13
evaporatorwhere
theliquidportiondisappears, leavingonlygas
at 20'F. Beyondthis point,asmore heatflowsinto therefrig-
erant,its temperature
will beginto rise. It is this temperature
rise that is called "superheat." Sevendegreessuperheat
means
thatbythetimeit getsta thecontrol
bulb,it will have
warmed
up 7', as in Figure 8.
Theexpansion valvewill sense
superheat in theexample,
27'F!. If it falls below,thevalvewill closeslightly, caus-
ingtheevaporator temperature to risebackupto 27'. If the
temperatureincreases,the valvewill openandlet in morere-
frigerant,causingtheevaporator temperature
to coolbackdown
to 27'. Thus,expansion valvessensetemperaturedifference or
hp*h.hd'h~dd
amountanticipatedfor conditionsof start-upwith warm brine,
highersuperheatsare sometimesadjusted. This is not common,
however,
andin general,wetry for the lowestsuperheat pos-
sible without flooding the compressar.
Theperformance of theexpansion valveis shown bythefrost
pointoccurring aroundthecontrolbulb,or thermostat bulb.
Whenseveraldifferent refrigeration circuits or return lines
aredumpedbackinto a common suctionline asin Figure5!, it' s
possible
to seewhichcircuitsarenotrunning properlyand,
therefore,whichexpansion valvesmayneedadjustment! by look-
ing at the frost line for eachcircuit.
Mostvalves, suchas Alco, will modulatethe capacityar
tonnage
avera range
of 25-304.Forexample,
a threetonvalve
will vary fromalmosttwo ta four tons in capacity.
Besure to buy goodquality expansion valves, since they
areveryimportant.It's alsoa good
ideato buythe typeof
valve suchas that made by Alco! that allowsyouto interchange
the valvestems,making it easyto change to a largeror smaller
size withouttakingthe valveout of the line. Forexample, if
a three ton valvewerefoundto be too small, it's better to put
in an orifice capableof makingit a four ton valve, rather than
trying to adjustthe smalleroneto the limit of its capacity.
Finally, buy a valve that canbe silver-solderedin. Stayaway
fromthreadedconnections--incold lines, waterwill follow the
threadsback--alternatefreezingandthawingwill loosenthe
nut.
Evaporator
All comments
related to evaporatarsappearin a later sec-
tion entitled "Chillers."!
Thisfrost point frequentlyextendstwoto five feet beyond
the
bulb, which is o.k.
14
Filters/Driers
Condenser
Piping
200 feet long, consisting of one inch pipe. Using R-22, you
might have no appreciable pressure drop. However, if R-L2 were
put into the same lines and the same capacity were needed, the
pressure drop would be excessive. Therefore, we would have to
either decrease the length of the lines to 125 feet or so! or
increase the diameter to operate without' excessive pressure drop.
l. Pumps
2. Chillers
Closed Chillers
expe
O
B
ed LO t" bt ld e"u b
120 feet. An acceptable design for the evaporator coi s is
use iron pipe on four in.ch center rs with standard elbows. T is
is probabLy the cheapest wa
way to go. 1 f you were to use we
w lded e
return bends, you could space the coils closer, r but ui this is mo re
AEI EY,
E SIDE
SSOVER
Electrolysis is not really a problem, since the brine
temperatures
are generallyquite low. Also not a problemis
freeze-upon the coils due to loss of brine strength or drop
in evaporatorcoil temperature. It is important to.note, how-
ever, that if freeze-updoesoccur in the hold, the brine wash-
ing over ice will not cool as muchas brine washingover re-
frigerated coils--it might get downto about 40 'F.
Onepossible difficulty with installing an opencoil chiller
occurs when the hold has a relatively flat bottom if, for ex-
ample,the engineroomwereaft!, allowingno sump.But the
advantagesover closed.chillers are many--youcan seewhat's
goingon, freeze-upsand.plug-upsare not a problem. In ad-
dition, experiencehas shownthat for boats with a hold capa-
city of about35 tons or less, open-pipesubmerged
coil chillers
are far more economical than closed chillers.
Operating Temperatures
Assuming
you knowthe freezing temperatureof your brine,
makesure that the operating temperature of the brine flowing
out of the chiller is kept 5-7 F abovethe freezing point.
Also, in cupronickel chillers, don't let the refrigerant suc-
tion temperaturebe any colder than 10' belowthe brine freez-
ing temperature.Ona steel chiller you cango a little lower
because the heat transfer is not as good.
To monitor these temperatures, good gauges are important,
especially for measuring
suctionpressure. A cheapsuction
gaugewhichmightbe off by S psi could throwyour calculations
off, causinga freeze-up of the chiller. A headpressuregauge
is not as important as that for low pressure suction!. Most
of thesepressuregaugeshavethe correspondingsaturation
boiling! temperatures
of both R-1?andR-22printed on the face.
3. Brine Preparation, Circulation, and Spray
Brine Preparation
Sprayseawatersystemsare presentlybeing installed for
the purposesof holdingshrimp. It appearsthat they mightbe
held on the boat longer than the present two- or three-day limit;
also, RSW
systems
appearto eliminatelabor, savetime, andget
aroundthe problemof ice scarcity. But somequestionsremain
to be answered:
How much warm shrimp can be added and over what period
of time?
What is the effect of salt in seawater or brine! on
the product?
F I GVRE l0
FIGHT!; 12
ONTAL
GURZ 13
hosetype arrangement
from the gate valve all the wayback to
the bilge,' this serves to control foamingwhenexcessbrine
is being pumped through the system.
A typical spray systemdesignuses a 2$ x 2 pumpabout
150gal/min! anda 2-inch diameterPVCpipe with 12 or 13 holes
having a diameterof 7/16-inch. Theholes, which could be in
either the top or bottomof the pipe, needto be small enough
to spray out with somevelocity, although this spray action
does create a lot of foam. You will have to raise or lower the
pipe to get the best sprayingpattern andadjust baffles and
holes as appropriate. Thereare two ideas frequently usedfor
deflectors. One is to use engine block soft plugs {around two
inches in diameter! fastened to the ceiling of the hold with a
screw or nail. This is placed directly over the hole in the
top of the brine spraypipe Figure 1S!. Thesecondidea is
shownin Figure 16. A tablespoonis bent at right anglesand
fastened to the PVCspray pipe with tape or a hose clamp. The
difficulty with tablespoonsis that they frequently bendout of
shape, and it is hard to get at them to adjusts
TABLESPOON
CLAMPED
F IGURE 15
Pvc PIPE FIGURE 16
C. Installation of E ui ment
Materials
Piping
Figure 17 showsa through-bulkhead
piping designdiscussed
earlier--steel pipe in the fish hold, copper in the engine room.
The riser in the fish hold is frequently installed as a matter of
convenience--the engine room is often too crowded. to go in very
low. Oil return is no problem as long as the copper pipe for
that particular circuit drops downinto the top of the suction
line before it rises back up into the compressor. Make sure
24
Expansion Valve
Buy an expansionvalve with soldered connections--in and.out.
Install it in the engine room, not in the hold. This is to avoid
having.copper materials in the fish hold, and to makeit easier
to service in case of a problem.
Condenser
REFRIGERANT
REF R IGERANT
FIGURE l8
26
A. S stem Shutdown
Whenyou' re through using the sys tem for a while, it's a good
idea to close the king valve just downstream of the receiver!
and pump the system partially down. That is, pump most of the
refrigerant liquid into the receiver. You don't have to pump
it all back.! The reason for doing this is to prevent a slug
of Txquid entering the compressor crankcase on start-up, causing
oil to be blown out.
Once the system has been pumpeddown, chances are the com-
pressor valves will leak a little and eventually pressurize the
suction side. This is o.k., since pressure is better than va-
cuum in the event of system leaks. However, if the shutdown
is to be for an extended period of time, you should also close
the service valves to isolate the low side as much as possible.
Without oil sloshing against the compressor shaft seal, it' ll
tend to dry out and leak. If the service valves weren't shut off,
you might then find yourself out of refrigerant when you go to
start-up at the beginning of the season.
How do you check whether the system is performing well at
the beginning of the season? Oneway is to have a curve of tem-
perature versus time, madewhenthe systemwas working well--then
comparethe new curve with that of the original system. It
might be only necessary to see how manyhours it takes to get
down to the proper temperature. For this, you would need to have
a thermometer on the brine pump discharge. If you have a chiller,
it's easy to look at the temperature difference across the chil-
ler--for example, S' might indicate it is working properly. For
an open coil chiller, obviously this is difficult.
B. Refri erant Shorta e
For the case of oil shortage, this means that you shouldn' t--
add oil, tear down a compressor, change a drier, adjust an ex-
pansion valve--before thinking the situation over. Check for
an oil leak. If there isn't one, and if the compressor is
short, the oil m~u
t be in the systemsomewhere--probably
in the
evaporator coils. The cause might be a shortage of refriger-
ant. Check the sight glasses. Frequently, the receiver will
have sight glasses in the side, showing whether or not the level
of liquid is adequate. If it doesn' t, there are two ways to
determine the position of the liquid level in the receiver. One
way is to briefly turn off the water to the condenser while
the system is in operation. Hot gas will heat up the non-liquid
area of the receiver, which you can feel with your hand; below
the liquid level, the walls of the receiver will be cold. The
second way of determining liquid level is to pour boiling water
on the receiver. Again, the metal below the level of the liquid
will be cold."*
Check the liquid-line sight glass. If bubbles are seen, it' s
usually a good. ind.ication of a shortage of refrigerant; and
this means a leak somewhere.*** If you' re at sea, the best
solution is usually to add some refrigerant and worry about the
leak when you get home. Adding more refrigerant--whether you' re
using R-12 or R-ZZ--will return the oil from the coils.
Leaks can mean losing refrigerant or "gaining" air and mois-
ture if the low side were to be in a vacuum!. Loss of refrig-
erant can be. detected in several ways. With R-12 systems, watch
for any signs of oil accumulating on a joint or fitting. This
is a sign of a leak--enough refrigerant gas has leaked out to
One refrigeration serviceman removed 27 gallons of oil from
coils on a SO-ton boat.
**Howmuchliquid should be in. the receiver? Xou actually need
only just enough to cover the outlet. The receiver should be
no more than one- fourth full.
It's difficult to identify a refrigerant shortage by merely
observing the frost line on the coils. Often, this frost line
is some distance downstream of the actual BP, due to cold gas
creating frost.
28
EXPANSION
LVE L COILS
F I GU RF. 19
30
Compressor
will usually be too hot to allow you to hold your hand against
it. However, the 1 ine should be below 212 'F. Check this by
splashing water or spitting on it. If the water sizzles, causing
steam, the line is over 212' and you have compressor problems.
A possible cause is that the discharge valve isn't closing tight-
ly. Therefore, gas would be sucked back in, causing too much to
be compressed during the compression cyc1e, resulting in. discharge
gas which is too hot.
Expansion Valve
it alone. If, for some reason, the valve doesn't hold its ad-
>ustment, it should go back to the factory. There is no reason
to take the cap off. If you occasionally detect inadequate flow
through the valve, the difficulty is usually elsewhere. This is
especially true of a valve that has been working for six months
or more. There might be dirt or moisture causing a problem, but
it ' s not the valve ' s f ault. Very f ew valves f ail.
As stated previously, expansion valves sense temperature
differen e, that is, the amount of superheat. So in order to
check that the valve is operating properly, it's necessary to
use two temperature sensors or a temperature sensor and a
pressure gauge!.* Expansion valves are usually set for about
7' superheat. If frost is seen on the compressor,it meansthat
the expaiis'oil salve is either set wrong or it's bad."" The genera1
solution to this problem is to buy a new valve. If you are using
a Sporlen or Alco valve, you can merely change the seat or the
inside of the valve.
Condenser
PLIED
OSE:BUD
R-I2
ED FROM
H~O.
LvE
ER
FIGURE 20
Receiver
Chiller
INDEX