Nothing Special   »   [go: up one dir, main page]

NOJA-7234-03 RC Panel Quick Reference Guide en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

NOJA-7234-03 RC Panel Quick Reference Guide

Local/Remote Control Close Button


One button press toggles between Local and Remote Control. LED Indicates One Button Press to Close.
control mode: LED Indicates switch
 When in Local Control mode all Remote Control functions are inhibited. position.
 When in Remote Control mode all Local Control functions are inhibited. Panel must be turned ON to
 Tripping of the device is allowed regardless of control mode. perform this function.

Open Button
One Button Press to Open.
Panel ON/OFF LED Indicates Switch
Position.
One button press turns
Panel must be turned ON to
panel ON and OFF.
Pressing any button will also perform this function.
turn the panel ON.
Holding the button tests all Scroll Buttons
LCD characters and LED Allow up/down/left/right
indications. movements for screen
cursors for menu selections

Hold To Adjust Escape Button


Adjusts the contrast of the To abort a selected item or
LCD characters on the go back
screen
Enter Button
To enter or accept a change
Fast Keys (6 push buttons)
or menu
are configurable and can
be disabled in software to
prevent operation. Fast Keys (6 push buttons)
are configurable and can
be disabled in software to
prevent operation.

Active Group Hot Line Tag


A one button press will toggle through Group 1 then to The Hot Line Tag (HLT) blocks a close operation
Group 2 then to Group 3 then to Group 4. The LED from any source. The Hot Line Tag LED is lit when
indication will flash to let you know which protection group HLT is active. Protection settings cannot be
you are changing to. changed while Hot Line Tag is active.

The ENTER button must be pressed to then activate that HLT can only be disabled from the source it was
particular protection group. enabled from.

** Please note that the screen will automatically turn itself off after 5 minutes if no buttons are pressed **
** Some parameters are password protected – please refer to OSM manual **
** For single phase devices some of the screens overleaf may be different **
NOJA-7234-03 RC Panel Quick Reference Guide
System Status Alerts (if enabled in the settings)
[Turn Panel ON]  [SYSTEM STATUS] [Turn Panel ON]  [SYSTEM STATUS]

 [ALERTS]

SYSTEM STATUS SYSTEM STATUS

►ALERTS◄ GENERAL WARNING MALFUNCTION


►GENERAL◄ WARNING MALFUNCTION
<Reset Fault Targets>
Date/Time : 15/02/2019, 07:17:40 AM
Open(Prot) Open(OV)
Config : 3 phase, Recloser
Open(PhA) Open(UF)
Status : Closed
Open(PhB) Open(OF)
Open(PhC) Open(Yn)
Measurements Power Quality Open(PhN) VAR1
Input/Output Power Supply Open(OC) VAR12
Protection Communication Ports Open(EF) VAR32
Automation Protocols Open(SEF)
Logic Open(NPS)
Open(UV)

Logs Identification
[Turn Panel ON]  [SYSTEM STATUS]  [ESC] [Turn Panel ON]  [SYSTEM STATUS]  [ESC]
 
[MAIN MENU]  [Logs: CLOSE/OPEN] [MAIN MENU]  [Identification: Relay]

LOGS
►Close/Open◄ Event IDENTIFICATION

►Relay◄ SIM Panel I/O Languages


<13/02/2019 04:42:16 AM Open OC1+>
13/02/2019 04:42:06 AM Close HMI
Model # REL-02
13/02/2019 04:42:03 AM Open HMI
Serial # 0311478523697
Database 25.0.1.0
Software 1.22.0.0
Source: OC1+
Hardware 2.1
State: Lockout
FPGA 0.0.30938

Max (Ib), A=900 Trip (Ia), A=890


Trip (Ib), A=900 Trip (Ic), A=9 U-boot 1.16.0.0
Trip (In), A=845 U-Kernel 1.18.0.0

UPS Status and External Load Output Measurement Screens


[Turn Panel ON]  [SYSTEM STATUS] [Turn Panel ON]  [SYSTEM STATUS]

 [Power Supply]  [Measurements]

POWER SUPPLY STATUS MEASUREMENTS


►Power◄ 1 Phase Energy
Last Power Restart: Other 3 Phase Energy
10:42:03 AM 13/02/2019
Voltages (kV):
AC Input ON A 6.2 B 6.1 C 6.2
Battery Voltage (Ubt) 13.8V R 6.2 S 6.1 T 6.2
Battery Current (Ibt) 0.50A
Battery Capacity (%) 100 AB 10.7 BC 10.7 CA 10.7
External Load Output ►Off◄ RS 10.7 ST 10.7 TR 10.7
Battery Test Initiate
Currents (A):
Battery Test Result: A 52 B 47 C 50
11:43:33 AM 10/02/2019 N 0 I2 0
Battery Test Passed

web: www.nojapower.com.au email: sales@nojapower.com.au ph: +61(7) 3907 8777 fax: +61(7) 3399 6777