CONNECTING COMPETENCE.

w DATA SHEET: MONITORING RELAYS UR6U1052

• AC/DC voltage monitoring in 1-phase mains


• Multifunction
• 16.6 to 400 Hz
• Fault latch
• Zoom voltage 24 to 240V AC/DC
• 2 change-over contacts
• Width 22.5 mm
• Industrial design

w TECHNICAL DATA

1. Functions 5. Versorgungskreis
AC/DC voltage monitoring in 1-phase mains with adjustable Supply voltage:
thresholds, timing for start-up suppression and tripping delay 24 to 240V AC/DC terminals A1-A2 (galvanically
separately adjustable and the following functions (selectable by separated)
means of rotary switch) Tolerance:
OVER Overvoltage monitoring 24 to 240V DC -20% to +25%
OVER+LATCH Overvoltage monitoring with 24 to 240V AC -15% to +10%
fault latch Rated frequency:
UNDER Undervoltage monitoring 24 to 240V AC 48 to 400Hz
UNDER+LATCH Undervoltage monitoring with 48 to 240V AC 16 to 48Hz
fault latch Rated consumption: 4.5VA (1W)
WIN Monitoring the window Duration of operation: 100%
between Min and Max Reset time: 500ms
WIN+LATCH Monitoring the window Wave form for AC: Sinus
between Min and Max with Residual ripple for DC: 10%
fault latch Drop-out voltage: >15% of the supply voltage
Overvoltage category: III (in accordance with
2. Time ranges IEC 60661-1)
Adjustment range Rated surge voltage: 4kV
Start-up suppression time: 0s 10s
Tripping delay: 0.1s 10s 6. Output circuit
2 potential free change-over contacts
3. Indicators Rated voltage: 250V AC
Green LED ON: indication of supply voltage Switching capacity (distance <5 mm): 750VA (3A / 250V AC)
Green LED flashes: indication of start-up Switching capacity (distance >5 mm): 1250VA (5A / 250V AC)
suppression time Fusing: 5A fast acting
Yellow LED ON/OFF: indication of relay output Mechanical life: 20 x 106 operations
Red LED ON/OFF: indication of failure of the Electrical life: 2 x 105 operations
corresponding threshold at 1000VA resistive load
Red LED flashes: indication of tripping delay of Switching frequency: max. 60/min at 100VA
the corresponding threshold resistive load
max. 6/min at 1000VA
4. Mechanical design resistive load (in accordance
Self-extinguishing plastic housing, IP rating IP40 with IEC 60947-5-1)
Mounted on DIN-Rail TS 35 according to EN 60715 Overvoltage category: III (in accordance with
Mounting position: any IEC 60664-1)
Shockproof terminal connection according to VBG 4 Rated surge voltage: 4kV
(PZ1 required),IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 bis 2.5 mm² with/without multicore cable end
1 x 4 mm² without multicore cable end
2 x 0.5 bis 1.5 mm² with/without multicore cable end
2 x 2.5 mm² flexible without multicore cable end

SCHRACK TECHNIK GMBH PAGE 1/4

Seybelgasse 13, A - 1230 Vienna, PHONE +43 1/866 85-0 DATA SHEET: UR6U1052-E / 08-2009
E-MAIL info@schrack.com, INTERNET www.schrack.com Errors and omissions excepted.
CONNECTING COMPETENCE.

7. Measuring circuit 8. Accuracy


Fusing: max. 20A Base accuracy: ±5% (of maximum scale value)
(in accordance with UL 508) Frequency response: -10% to +5%
Measured variable: DC or AC Sinus (at 16.6 to 400Hz)
(16.6 to 400Hz) Adjustment accuracy: ≤5% (of maximum scale value)
Input: Repetition accuracy: ≤2%
30V AC/DC terminals E-F1(+) Voltage influence: ≤0.5%
60V AC/DC terminals E-F2(+) Temperature influence: ≤0.1% / °C
300V AC/DC terminals E-F3(+)
Overload capacity: 9. Ambient conditions
30V AC/DC 100Veff Ambient temperature: -25 to +55°C (in accordance
60V AC/DC 150Veff with IEC 60068-1)
300V AC/DC 440Veff -25 to +40°C
Input resistance: (in accordance with UL 508)
30V AC/DC 47Ω Storage temperature: -25 to +70°C
60V AC/DC 100Ω Transport temperature: -25 to +70°C
300V AC/DC 470Ω Relative humidity: 15% to 85% (in accordance
Switching threshold: with IEC 60721-3-3 class 3K3)
Max 10% to 100% von UN Pollution degree: 3 (in accordance with
Min 5% to 95% von UN IEC 60664-1)
Overvoltage category: III (in accordance with Vibration resistance: 10 to 55Hz 0.35 mm (in
IEC 60664-1) accordance with IEC 60068-2-6)
Rated surge voltage: 4kV Shock resistance: 15g 11ms (in accordance with
IEC 60068-2-27)

w FUNCTIONS

When the supply voltage U is applied, the output relays switch


into on-position (yellow LED illuminated) and the set interval of
the start-up suppression (START) begins (green LED U flashes).
Changes of the measured voltage during this period do not affect
the state of the output relay. After the interval has expired the
green LED is illumi-nated steadily.For all the functions the LEDs
MIN and MAX are flashing alternating, when the minimum value
for the measured voltage was chosen to be greater than the max-
imum value.

Overvoltage monitoring (OVER, OVER+LATCH)


When the measured voltage exceeds the value adjusted at the
MAX-regulator, the set interval of the tripping delay (DELAY) Undervoltage monitoring (UNDER, UNDER+LATCH)
begins (red LED MAX flashes). After the interval has expired (red When the measured voltage falls below the value adjusted at the
LED MAX illuminated), the output relays switch into off-position MIN-regulator, the set interval of the tripping delay (DELAY) begins
(yellow LED not illuminated). The output relays again switch into (red LED MIN flashes). After the interval has expired (red LED MIN
on-position (yellow LED illuminated), when the measured voltage illuminated), the output relays switch into off-position (yellow LED
falls below the value adjusted at the MIN-regulator (red LED MAX not illuminated). The output relays again switch into on-position
not illuminated). If the fault latch is activated (OVER+LATCH) and (yellow LED illuminated), when the measured voltage exceeds the
the measured voltage remains above the MAX-value longer than value adjusted at the MAX-regulator.If the fault latch is activated
the set interval of the tripping delay, the output relays remain in (UNDER+LATCH) and the measured volt-age remains below the
the off-position even if the measured voltage falls below the value MIN-value longer than the set interval of the tripping delay, the
adjusted at the MIN-regulator. After resetting the failure (inter- output relays remain in the off-position even if the measured volt-
rupting and re-applying the supply voltage), the output relays age exceeds the value adjusted at the MAX-regulator. After reset-
switch into on-position and a new measuring cycle begins with the ting the failure (interrupting and re-applying the supply voltage),
set interval of the start-up suppression (START). the output relays switch into on-position and a new measuring
cycle begins with the set interval of the start-up suppression
(START).

SCHRACK TECHNIK GMBH PAGE 2/4

Seybelgasse 13, A - 1230 Vienna, PHONE +43 1/866 85-0 DATA SHEET: UR6U1052-E / 08-2009
E-MAIL info@schrack.com, INTERNET www.schrack.com Errors and omissions excepted.
CONNECTING COMPETENCE.

If the fault latch is activated (WIN+LATCH) and the measured volt-


age remains below the MIN-value longer than the set interval of
the tripping delay, the output relays remain in the off-position even
if the measured voltage exceeds the value adjusted at the MIN-reg-
ulator. If the measured voltage remains above the MAX-value
longer than the set interval of the tripping delay, the output relays
remain in the off-position even if the measured voltage falls below
the value adjusted at the MAX-regulator. After resetting the failure
(interrupting and re-applying the supply voltage), the output relays
switch into on-position and a new measuring cycle begins with the
set interval of the start-up suppression (START).

Window function (WIN, WIN+LATCH)


The output relays switch into on-position (yellow LED illuminated)
when the measured voltage exceeds the value adjusted at the
MIN-regulator. When the measured voltage exceeds the value
adjusted at the MAX-regulator, the set interval of the tripping
delay (DELAY) begins (red LED MAX flashes). After the interval has
expired (red LED MAX illuminated), the output relays switch into
off-position (yellow LED not illuminated). The output relays again
switch into on-position (yellow LED illuminated) when the meas-
ured voltage falls below the value adjusted at the MAX-regulator
(red LED MAX not illuminated). When the measured voltage falls
below the value adjusted at the MIN-regulator, the set interval of
the tripping delay (DELAY) begins again (red LED MIN flashes).
After the interval has expired (red LED MIN illuminated), the out-
put relays switch into off-position (yellow LED not illuminated).

SCHRACK TECHNIK GMBH PAGE 3/4

Seybelgasse 13, A - 1230 Vienna, PHONE +43 1/866 85-0 DATA SHEET: UR6U1052-E / 08-2009
E-MAIL info@schrack.com, INTERNET www.schrack.com Errors and omissions excepted.
CONNECTING COMPETENCE.

w CONNECTIONS

Range 30V, supply voltage 24V AC/DC and fault latch Range 60V, supply voltage 230V AC and fault latch

Umax=30V AC/DC Umax=60V AC/DC

24VAC/DC
L1
0V
N

max. max.
20A 20A

Reset
Reset

15 25
15 25

16 18 26 28
16 18 26 28

Range 300V, supply voltage 24V AC/DC and fault latch

Umax=300V AC/DC

24VAC/DC
0V

max.
20A

Reset

15 25

16 18 26 28

w DIMENSIONS

SCHRACK TECHNIK GMBH PAGE 4/4

Seybelgasse 13, A - 1230 Vienna, PHONE +43 1/866 85-0 DATA SHEET: UR6U1052-E / 08-2009