Special Specification
Special Specification
Special Specification
SECTION D
SPECIAL SPECIFICATION
Special Specification
PROPOSED IMPROVEMENT WORKS TO THE EXISTING PLANTING SHED AT
NURSERY PETRA JAYA, JALAN DEPO KUCHING
1.01 GENERAL
This is a lump sum contract to which bill of quantities do not form part and calls for the
general supply of labour, materials and equipment for the improvement works to the
existing planting shed at nursery Petra Jaya, Jalan Depo Kuching.
Tenderers are advised to take all reasonable precautions and care to prevent loss or
damages by accident or any other cause to the existing work/finishes including that of
the nominated subcontractors. The Contractor is to maintain the site of the works in
good condition and is to take all precautions to prevent nuisance of any kind on the
premises.
“DBKU” means the Commission of the City of Kuching North or in Bahasa Malaysia
“Dewan Bandaraya Kuching Utara” established under Section 4 of the City of
Kuching North Ordinance, 1988, who for the purpose of this Contract is the Director of
DBKU.
“Schedule of Rates” means the schedule comprising items and rates of works as
stated in the Contract Documents
“Director” means the Director of DBKU appointed under section 8(1) of the City of
Kuching North Ordinance, 1988 who shall carry out the obligations and exercise the
rights and due performance of this Contract.
“Contract” shall mean the Agreement executed between the DBKU and the Contractor
together with the documents forming part thereof.
Words importing the singular also include the plural and vice versa where the context
requires.
This Contract comprises the supply, construct, completion and maintenance of the
Improvement of potting shed at nursery Petra Jaya, Jalan Depo Kuching including
temporary works, demolishing works and other associated works, all in accordance
with drawing and Specifications.
D/1
Special Specification
SECTION 1 - PRELIMINARIES AND GENERAL (Cont’d)
1.05 SITE
The Contractor is to enter a Contract and a performance security amounting to five (5%)
percent of the contract sum.
The Contractor is to refer to the Superintending Officer before the work is carried out,
and of any discrepancy found in or between contracts and site.
Any matter of construction and workmanship which are fairly and obviously intended, but
which may not be definitely referred to in the specification or drawings, and which are
usual in sound building construction practice and essential to the works are to be
considered as included in this Contract.
No part of the existing premises is to be used for any other purposes such as temporary
workers accommodation, cooking and washing or bath without approval from the
Superintending Officer.
D/2
Special Specification
SECTION 1 - PRELIMINARIES AND GENERAL (Cont’d)
1.10 ACCESS TO WORKS
The Contractors will make his own arrangement for the access to the works.
1.11 SECURITY
The Contractor is to provide watchman, temporary cover and adequate security as
necessary or as required by the Superintending Officer to prevent injury to all persons
and property, including the works, the work people and the public.
The Contractor shall submit his/her work programme to DBKU within 1 week after
handing over sites. It shall be the duty of the Contractor to inform DBKU of any changed
thereof. Work programme is important and related with monthly claim. Work programme
shall be approved and verified both party between DBKU and contractor.
The Contractor shall comply with all the safety and health requirement as stated in the
Tender Document including personal protective equipment; temporary traffic warning
signs and lamps; and two (2) set of First Aid Kit completed with all necessary undue
items. DBKU’s enforcement officer shall visit the site to ensure that the safety is
adequately provided on site. Failure to comply with this provision shall be punishable
to a fine of Ringgit Malaysia: Fifty (RM50.00) Only each day and shall be deducted
from the payment Interim Certificate.
Prior to the commencement of the Works, the Contractor shall at their own cost
register the awarded Contract with the JKKP and furnish the evidence of the said
registration to the Superintending Officer.
D/3
Special Specification
SECTION 1 - PRELIMINARIES AND GENERAL (Cont’d)
Where so required the quality of any material is to be approved prior to its use and any
samples required are to be provided free of charge by the Contractor. Any material
rejected is to be removed at the Contractor’s expense.
D/4
Special Specification
The Contractor shall not during the course of the construction cause unnecessary
obstruction or misuse to traffic using that road. The Contractor shall provide necessary
detour or diversion to guide and regulated the traffic flow. Existing traffic shall not be
interrupted for any lengthy period.
The Contractor shall provide adequate warning signs, flagmen and watchmen, if
necessary, to regulate traffic flow at hazardous places on the project and at any other
places so directed by the Superintending Officer or his representative. Any cost of
damage due to negligence of these shall be borne by the Contractor.
In the event that the maintenance work not completed as per Schedule of
Maintenance, DBKU shall deduct a sum from the monthly maintenance payment for
the incomplete Maintenance Works based on percentage value of work done.
Special Specification
D/6
SECTION 2 - SITE WORKS (Cont’d)
Prior to blasting, the Contractor shall inform the Superintending Officer or his
Representative and the Police. When blasting is carried out, the Contractor
shall ensure by adherence to proper safety distances and by the use of heavy
blasting mats where necessary to prevent dispersal of materials, so that no
damage is caused to persons or property on the site. Special precaution shall
be taken when blasting in wet ground. Blasting will be such that no building or
structure will be damaged due to the explosion.
D/9
Special Specification
SECTION 3 - EXCAVATOR
3.01 GENERALLY
The Contractor shall provide all labour, plant, equipment and materials for carrying out
all works in connection with excavating, filling and backfilling including removal from
site of all surplus excavated materials and debris from abandoned services and
demolished structures where encountered in strict accordance with the requirement to
the tip as directed by the Superintending Officer.
The Contractor shall make his own investigation as to the nature of the ground to be
excavated. Any existing services, pipes and drains encountered during excavation
shall be diverted as directed or cut off and sealed. Any concrete, brickwork or other
artificial obstructions met with during excavation are to be broken up and got out and
removed from the site.
The Contractor shall excavate or as the case may be, fill with earth available from site
to required levels, prior to actual construction work. Where earth required for filling to
make up the required formation levels is not sufficient, then he must bet the same from
an approved tip.
All excavations shall be square, level and plumb and shall be to such width as may be
necessary to carry out the work safely and properly. The bottoms shall be
consolidated and shall be to the exact levels required.
The Contractor is to give notice to the Superintending Officer and to any other
Authorities when the excavations are ready to receive concrete and these are not to be
laid until the excavations have been approved and the depths noted.
Should any excavation be made without authority to greater depths than shown on the
drawings or as instructed then the Contractor is to fill in to the correct level with
concrete (1:3:6) at the Contractor's expense. However, in the case piles, no such
filling is to be done. The piles are to be driven from the actual excavated level and the
foundation length in concrete of the class specified thereof or to the corrected level.
Additional reinforcement has also to be provided as necessary to the approval of the
Superintending Officer.
D/10
Special Specification
Rates for excavations will include for excavating in hard laterite or shale, but with the
exception of rock which in the opinion of the Superintending Officer requires the use of
compressor drills, explosives or other special methods of removal (i.e. not removable
by changkol, spade, pick or by hand). Such excavations will be measured as "Extra
Over", ordinary excavations and the Superintending Officer will be the sole judge in
deciding what is to be defined as "rock". Materials which can be loosened and
removed by the use of a pick are shall not be classified as Rock.
No explosives are to be used for removal of work or for any other purpose without the
permission of the Superintending Officer in writing. If permission is granted the
Contractor is to be responsible for informing all other interested parties of his intention
and shall take all precautions to prevent damage to any services of statutory
undertakings or local authorities or to adjacent property. The Contractor shall
indemnify the Proprietor against any claim, loss or expense arising from any damage
and make good at his own expense any damage arising from the use of explosives or
similar means of breaking up rock or other obstructions.
The contractor shall store explosives in a licensed store of magazine provided with a
separate compartment for detonators. Explosives shall be handled only by currently
licensed short firers. The Contractor shall ensure that there is no unauthorised issue
or improper use of explosives brought onto the site.
All excavated materials suitable for filling shall be kept in an approved location on the
site. All surplus excavated materials or unsuitable spoils shall be removed from the
site to a tip to be provided by the Contractor at his own expense. Clay or earth
containing any organic matter will not be permitted as fill.
D/11
Special Specification
SECTION 4 - CONCRETOR
4.01 GENERAL
The work required under section comprises the supply and construction of structural
masonry walls in the drawing and in accordance with the provisions of BS 5628 part 1,
2 and 3.
4.03 REINFORCEMENT
Bar reinforcement shall be rolled mild steel bars of a manufacture approved by
Superintending Officer and shall comply with B.S. 4449. All reinforcement shall be
cleared free from loose mild-scales, loose rust, oil, grease, earth and other harmful
matter before being placed in the forms and shall be free from these at the time the
concrete is placed.
D/12
Special Specification
SECTION 4 - CONCRETOR ( cont’d )
4.09 REINFORCEMENT
The reinforcement shall comply with the requirements of the relevant BS for the
reinforcing bars specified in the drawings.
4.11 TESTING
Independent testing of masonry units shall be carried out in accordance with BS 6073 :
Park 1 : 1981
D/13
Special Specification
SECTION 4 - CONCRETOR ( cont’d )
Binding wire shall be 1.6 mm diameter soft annealed steel wire complying with the
requirements of B.S. 1052.
The Contractor shall, on request, furnish the Superintending Officer with samples of
reinforcement brought onto the Site, not withstanding any previous acceptance on the
manufacturer’s test certificates. The reinforcement represented by the sample may be
rejected by the Superintending Officer and shall, if it fails to meet the Specification,
require its removal from the Works Site.
Steel reinforcement shall be stored in clean and dry conditions. When placed in the
Works it shall be clean and free from loose rust, mill scale, oil grease, paint, dirt or
anything which may reduce its bond with concrete.
Bars shall be of their correct lengths and bent to the exact shapes required
before being fixed in the work.
Bars shall be cut and bent cold by the application of slow, steady pressure of in
an approved bar-bending machine. Bending at temperatures in excess of
100C may only be carried out with the Superintending Officer’s approval and
under his supervision. Except where otherwise indicated on the Drawings, bars
shall be bent and measured in accordance with B.S. 4466.
D/14
SECTION 4 - CONCRETOR ( cont’d )
Special Specification
Cold worked and hot rolled bars shall not be straightened or bent again once
having been bent. Where it is necessary to bend mild steel reinforcement
already cast in the concrete, the internal radius of bend shall be not less than
twice the diameter of the bar.
Special care shall be taken that the overall length of bars with multiple bends is
accurate and that after bending and fixing in position the bars remain in place
without wrap or twist.
The number, size, length, form and position of all reinforcing bars, links,
stirrups, spacer bars and other parts of the steel reinforcement, shall be in
accordance with the Drawings.
The Contractor shall be take particular care that the reinforcement is laid out
correctly in every respect and temporarily suspended by annealed wire or
supported on concrete blocks or other approved spacers in the forms to
prevent displacement before or during the placing and compacting of concrete.
Stirrups and distance pieces shall be kept tight to the bars they embrace or
support and all reinforcement shall be kept away from the face of the concrete
at the distances shown on the Drawings.
No concrete shall be placed until the reinforcement has been inspected and
approved by the Superintending Officer.
4.12.8 SPLICING
Laps and joints including lapping bars, sleeving, threading and other
mechanical connections shall be made strictly in accordance with the method
specified and at the positions shown on the Drawings or as otherwise approved
by the Superintending Officer.
D/15
SECTION 4 - CONCRETOR ( cont’d )
Special Specification
Supporting and spacer blocks required for ensuring that the reinforcement is
correctly positioned shall be as small as possible consistent with their purpose,
of a shape acceptable to the Superintending Officer, and designed so that they
will not overturn when the concrete is placed. They shall be made of concrete
with 10 mm maximum aggregate size and they shall be of at least the same
strength and material source as the adjacent concrete. Wire cast in the block
for the purpose of tying it to the reinforcement shall be as described in Sub-
Section 6.12.2. Other types of spacers may be used only with the approval of
the Superintending Officer.
Welding shall be carried out in accordance with B.S. 5135 and B.S. 638. Butt
welds shall be of the double V type and two (2) butt weld bond tests shall be
carried out on a specimen prepared to represent each form of butt welded joint
used in welding the reinforcement and for each position of welding. The method
of making butt weld tests shall be that laid down in B.S. 709. The specimen
shall pass the test to the satisfaction of the Superintending Officer before
approval is accorded to use the joint which the specimen represents.
4.13.1.1 DESCRIPTION
D/16
Special Specification
SECTION 4 - CONCRETOR ( cont’d )
D/17
Special Specification
SECTION 4 - CONCRETOR ( cont’d )
D/18
Special Specification
SECTION 4 - CONCRETOR ( cont’d )
4.13.2 FINISHES
Formed concrete surfaces shall have one (1) of the following classes of
finish. Unless otherwise specified, all exposed concrete surfaces shall
be of Class F2, all unexposed surfaces shall be of Class F1 and Class
F3 finish shall be used only where shown on the Drawings.
(a) Class F1
(b) Class F2
(c) Class F3
This finish shall be obtained by the use of properly designed steel forms
or plastic coated plywood or wrought boards or other approved material.
The surface shall be improved by carefully removing all fins and other
projections, thoroughly washing down and then filling the most
noticeable surface blemishes with a cement and fine aggregate paste to
match the colour of the original concrete. Form release agent shall be
carefully chosen to ensure that the surface shall not be stained or
discoloured.
After the concrete has been properly cured, the surface shall be rubbed
down where necessary, to produce a smooth and even surface.
D/19
Special Specification
(a) Class U1
(b) Class U2
(c) Class U3
When the moisture film has disappeared and the concrete has
hardened sufficiently to prevent laitance from being worked to the
surface, a Class U1 surface shall be steeltrowelled under firm pressure
to produce a dense, smooth uniform surface free from trowel marks.
Any concrete, the surface of which has been treated before being
inspected by the Superintending Officer, shall be liable to rejection.
Before concreting, all forms shall be thoroughly cleaned out, free from sawdust
shavings, dust, mud or other debris.
The inside surfaces of forms shall, except for permanent formwork, or unless
otherwise agreed by the Superintending Officer, be coated with an approved
non-staining form oil or other approved material to prevent adhesion of the
concrete. Such release agents shall be applied strictly in accordance with the
manufacturer’s instructions and shall not come into contact with the
reinforcement or prestressing tendons and anchorages. For any exposed
surface only one release agent shall be used throughout the entire area.
D/20
Special Specification
SECTION 4 - CONCRETOR ( cont’d )
The Contractor shall inform the Superintending Officer and obtain his approval
before striking any formwork, but such approval shall not relieve the Contractor
of his responsibilities for the safety of the work.
The removal shall be done in such a manner as not to damage the concrete,
and shall take place at times to suit the requirements for its curing.
The periods stated above are based on the use of ordinary Portland cement.
They may be changed if other types of cement are used, subject to the
Superintending Officer’s agreement.
For prestressed in situ decks, temporary supports shall not be removed until
the deck is stressed to the satisfaction of the Superintending Officer.
D/21
Special Specification
SECTION 5 – CARPENTER AND JOINER
5.01 GENERALLY
The quality of timber and workmanship in all joinery work shall confirm to the relevant
requirement of B. S. 1186.
All joinery timber, unless otherwise specified, shall be wrot on all faces exposed to
view and shall be slightly rounded on all exposed arises.
All joinery is to be put on hand immediately upon receipt of details and kept in the
drying room as soon as possible.
Joinery must not be fixed until plaster, etc., has completed dried out and should it be
necessary for any tucking in or pointing to be undertaking after joinery is in position,
this should be kept to a minimum.
Any joinery that splits, shrinks or warps from want of seasoning, unsoundness of bad
workmanship shall be removed and replaced without charge.
5.02 TIMBER
All timber is to be sawn die square with the slope of the grain not exceeding one in
eight and is to be free from sapwood, twist, splits, cracks, large, loose or dead knots,
large resin pockets, waney edges, live or extensive insect attack or other defects
except to such extent as may be permitted by the Superintending Officer where the
strength, durability or appearance of the work will not be affected.
D/22
Special Specification
SECTION 6 – PAINTER
6.01 MATERIAL
All paints, distempers and other materials are to be of “ICI” or other approved
equivalent in good conditions, delivered to site in unopened drums or packages, and
are to be used strictly in accordance with the Manufacture’s instructions. All materials
for successive coats of the same process, including primers and sealers, are to be
obtained from the same Manufacturer.
All painting or decoration is to be carried out by skilled workmen according to the best
current practice and in accordance with the Manufacturer’s instructions.
All materials are to be thoroughly stirred before use after the removal of any skin and
are to be strained as necessary to remove all lumps. Opened cans are to be resealed
when not in use.
Each coat of paint shall be thoroughly dry before the next is applied and successive
coats of paint are to slightly differ in tints.
Each coat of oil paint is to be lightly rubbed down with glass paper and dusted off
before the next is applied. Where two finishing coats are applied, the first is to be
rubbed down sufficiently to remove the gloss.
No finishing coats are to be applied until all dust and rubbish has been removed from
the area.
All finished paint work and decoration is to be of uniform finish and colour, free from
blemishes, brush marks and tackiness.
D/23
Special Specification
SECTION 6 – PAINTER (Cont’d)
b) All rust, scale or loose priming paint is to be removed back to bare metal by
wire brushing or chipping as required.
d) Bare patches in metalwork delivered primed are to be brought forward with the
appropriate primer before receiving the treatment specified.
All steel and ironwork to be painted, except plumbing pipe-work and electrical conduit,
is to be primed before assembly or fixing, including laps, ends for building in, and other
concealed parts.
D/24
Special Specification
SECTION 7 MAINTENANCE AND ALTERATIONS
GENERALLY
7.01 APPLICATION
This section applies to all repairs, maintenance works, alterations and additions, and
other works affecting existing buildings or works. The previous sections of this
Specification apply also to such works where appropriate.
7.02 MATCH EXISTING
Unless otherwise specified or required all new work is to match existing as far as
possible, using similar materials, workmanship and finish.
7.03 USE OF EXISTING PREMISES
Existing premises are not to be used for storage, canteen, sanitary or other purposes
unless so specified or permitted by the Superintending Officer.
7.04 MAKING GOOD
All work affected by repairs, alterations, etc. is to be made good whether or not so
particularly specified.
7.05 MATERIALS ARISING FROM WORKS
Unless otherwise specified, all material and fixtures arising from alterations, repairs or
demolitions are to become the property of the Contractor for the purposes of this
Contract if complying with the specified requirements for the material, but the
Superintending Officer approval is to be obtained before such materials are removed
from the site.
D/25
Special Specification
8.01 GENERAL
The structural steel framework is designed with the requirement of B.S. 449 (1970).
This specification is based on the requirement of B.S. 449 and Materials and
Workmanship shall be in accordance with that standard unless specifically varied.
8.02 STEELWORKS
All members, including flats and bars, are to be accurately fabricated and perfectly
straight and free from winding, and except where otherwise shown are to be in one
length.
Holes in steelworks for bolts etc. are to be drilled or reamed to the exact diameter
required and punching will not be permitted.
Exposed steel members are to be neatly finished, with cut surfaces filed smooth.
The weight of all steal section is exclusion of rolling margins, which are not to exceed
2½ % under theoretical weight.
8.03 WELDING
Electrodes for manual welding shall comply with B.S. 639.
Weld metal deposited by an automatic or semi-automatic process shall have
mechanical properties not less than the minimum specified for the weld metal
deposited by electrodes complying with B.S. 639 and B.S. 4165. All weld metal shall
have the minimum tensile strength of the parent metal and notch-ductility to Grade II,
B.S. 639 and B.S. 4165 and relevant.
All electrodes shall be classified, coded and marked in accordance with B.S. 1719.
Electrodes of Classes 2, 3 and 6 may be used for welding steels to B.S. 4360 in
thickness up to 50 mm. For greater thickness Class 6 electrodes shall be used.
Class 6 electrodes shall be used for welding steels to B.S. 4360 Grade 50 in all
thickness.
Electrodes shall be stored and protected from weather effects in accordance with the
conditions specified by the Manufacturer.
Welding procedure shall comply with B.S. 4360 Grade 43. Before any welding is
accepted, test specimen must be made and tested as indicated by Superintending
Officer. Costs of all tests are deem to be included in the tender.
Surface preparations and welding conditions shall comply with B.S. 1856:1964, Part 5,
Section 3 or B.S. 2642:1965, Part 5, Section 3 as appropriate.
Tack welds shall conform to B.S. 1856:1964, Clause 34 or B.S. 2642:1965, Clause 30
as appropriate, except that in no case shall the minimum length of weld be less than
50 mm.
The Contractor shall not place any welds not shown on drawings on any steelworks,
even for temporary attachment, or to repair faulty plates by welding, unless the
contractor has submitted his proposals to obtain the approval of the Superintending
Officer.
D/26
Special Specification
SECTION 8 - STEEL AND IRON WORKS (Cont’d)
8.07 FABRICATION
Work off site shall conform with the appropriate clauses of the current B.S. 449 and
shall be carried out in such a way that the erected structure can conform to the
requirement of Clause 12 of this specification.
Where High Strength Friction Grip Bolts are used the holes shall be drilled full size to a
diameter of the bolt and all burrs shall be removed.
Where HSFG Bolts are used, the method and procedure for tightening shall be in
accordance with Clause 13 of this specification.
Individual member marking shall be visible when members have been stacked
together. All painted or metal coated steelworks shall be kept off the ground.
The positions of all foundations and points of support for structural steelworks shall be
set out so that the distance between any two points jointed by a shop fabricated
component of structural steel are within 3 mm of the required dimension. Individual
fabricate members shall conform to a degree of accuracy compatible with all the
tolerances laid down in this clause.
D/27
Special Specification
The Contractor shall notify the Superintending Officer at least two (2) weeks in
advance of his commencing work on site of the method by which he proposes to erect
the steelworks, and the type of lifting device he intend to employ. All fixing or
temporary steelworks required for erection or bracing must be provided by the
Contractor and details submitted with the shop fabrication drawings.
If the Contractor intends to make individual site connections in more than one stage by
developing initially only a proportion of the joint strength indicated on the drawings
before continuing with further erection work, he shall firstly obtain the Superintending
Officer’s written permission to do so.
The Superintending Officer’s written authority shall be obtained for the use of burning
equipment on site.
The site bolting of permanent connections shall conform to Clause 62 of B.S. 49:1959.
Where high strength friction grip bolts are specified they shall be of the loading
indicating type such that the achievement of the proof tensile load can be directly
related to feeler gauge measurement of gap closures on the bolt head or on the
washer. The Contractor is to submit to the Superintending Officer for his approval the
type of load indication system he wishes to use and also the name of the load
indicating bolt or load indicating washer Manufacturer. Washers shall be of harden
steel conforming to B.S. 3139 and shall be provided under the head of the bolt.
During the tightening operation the bolt head shall be prevented from rotating.
Immediately prior to assembly the surfaces to be match shall be lightly sand blasted to
the Superintending Officer’s approval.
No painting of the bolts or washers shall be carried until the Superintending Officer has
given the Contractor permission to do so. In all other respects the relevant clauses of
B.S. 3294, Part I shall be adhered to.
Where applicable, paint shall conform to the current B.S. code of practice C.P. 2008.
Treatment and coatings must be executed in an enclosed building under rigid control.
D/28
Special Specification
SECTION 8 - STEEL AND IRON WORKS (Cont’d)
Scrape and wire brush to remove loose mill-scale and rust immediately prior to
painting or encasement.
All matching surfaces to be connected using high strength friction grip bolts are to be
lightly sand blasted to a standard agreed with the Superintending Officer.
8.13 COATINGS
The steel work, where applicable, is to be coated with two (2) coats each 0.00015” of
quick-drying red lead.
All exposed steelworks shall be painted with at least two (2) coats of good quality paint
to be specified by the Superintending Officer.
D/29