Temporizador Autonics Modelo Le4sa

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Front panel identification

Output operation mode


Mode Time chart( T:Setting time, T > Ta, Rt:Reset time )
T Rt T T

TIMER

LE4SA
M A N U A L

Time progressing display:It displays the current time. Time setting display:It displays the setting time. Time unit:It displays the time unit. Operation mode:It displays the current operation mode. Output display:It displays the status of output contact. UP/DOWN:It displays time progressing UP(), DOWN(). Key lock display:It displays the status of key lock. ,key:Used for initializing time progressing and output return. *key:Used for advancing to function setting mode, setting time change and output contact status checking <key:Used for advancing to setting time change mode and moving to each digit >key:Used for changing the set value

Operation
POWER

[ OND]
OND

POWER RESET Setting time UP 0 Setting time DOWN 0

T
Time limit contact output

ON Delay

Time limit contact(-) Instantaneous contact (-)

1. Timing operation starts when power is ON. 2. Time limit output will be ON when timing operation is progressed up to the setting time. Display value will be HOLD. 3. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes OFF when power is OFF. 4. If pressing RESET key, display value and time limit output will be reset.

Function Setting Mode Descriptions


Function setting mode
1)Time Range

[ OND.2]
OND II

Rt

POWER RESET Setting time UP 0 Setting time DOWN 0

POWER

Tout

Thank you very much for selecting Autonics products. For your safety, please read the following before using.

[ OND], [ OND.2], [ INT] mode Output operation mode

* key
2)One-Shot output time OND.2 mode T.OFF Time Range

ON Delay 2
(One-Shot Output)

Caution for your safety


Please keep these instructions and review them before using this unit.
Please observe the cautions that follow; RUN mode

*key
T.ON Time Range

Time limit contact output Tout : Output time Time limit contact(-) Instantaneous contact (-)

*key
3 sec

* key

Warning Serious injury may result if instructions are not followed. Caution Product may be damaged, or injury may result if instructions are not followed.
The following is an explanation of the symbols used in the operation manual. caution:Injury or danger may occur under special conditions.

* key
6)Key lock

[ FLK], [ FLK.1] mode T1 Time Range

* key
T2 Time Range

* key

1. Timing operation starts when power is ON. 2. Time limit output will be ON during Tout setting time and goes OFF when timing operation is progressed up to the setting time. Display value will be HOLD. 3. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes OFF when power is OFF. 4. If pressing RESET key, display value and time limit output will be reset. 5. Tout setting range: 0.01 sec~99.99 sec.

[ FLK]
FK
* key
POWER RESET Toff UP Ton 0 Toff DOWN Ton 0

Toff Ton Toff Ton Toff Ta

Rt Toff Ton

Toff Ton

POWER

Warning
1.In case of using this unit with machineries(Nuclear power control, medical equipment,vehicle, train, airplane, combustion apparatus, entertainment or safety device etc), it requires installing fail-safe device or contact us for information on type required. It may result in serious damage, fire or human injury. 2.This unit must be mounted on panel. It may give an electric shock. 3.Do not repair or checkup when power on. It may give an electric shock. 4. Do not disassemble and modify this unit, when it requires. If needs, please contact us. It may give an electric shock and cause a fire.

*key
3 sec
5)Backlight

[ S-D], [ TWN], [ TWN.1] mode

* key

Time limit contact output Toff : OFF Setting time


Ton : ON Setting time

*key
4)Output contact 3)Time Up/Down

Flicker
(Toff operation precedes Ton operation)

*key

* key

Time limit contact(-) Instantaneous contact (-)

1) Time Range
Parameter 9.999S (9.999s) 99.99S (99.99s) 999.9S (999.9s) 9999S (9999s) 99m 59S (99m59s) 999.9m (999.9m) 9999m (9999m) 99h 59m (99h59m) 99.99h (99.99h) 999.9h (999.9h) 9999h (9999h) Time range specification 0.010 sec 0.01 sec 0.1 sec 1 sec 0 min 01 sec 0.1 min 1 min 0 hour 01 min 0.01 hour 0.1 hour 1 hour ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ 9.999 sec 99.99 sec 999.9 sec 9999 sec 99 min 59 sec 999.9 min 9999 min 99 hour 59 min 99.99 hour 999.9 hour 9999 hour

1. Control output will be repeatedly OFF during Toff setting time and will be ON during Ton setting time when power is ON. 2. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes OFF when power is OFF. 3. If pressing RESET key, display value and time limit output will be reset. 4. It is able to set each Toff time and Ton time separately. In [ FLK ] mode, timing operation starts with Toff.

Caution
1.This unit shall not be used outdoors. It may give an electric shock. 2.When wire connection, No.20AWG(0.50mm2) should be used and screw bolt on terminal block with 0.74Nm to 0.90Nm strength. It may result in malfunction or fire due to contact failure. 3.Please observe specification rating. It might shorten the life cycle of the product and cause a fire. 4.Do not use the load beyond rated switching capacity of Relay contact. It may cause insulation failure, contact melt, contact failure, relay broken, fire etc. 5.In cleaning the unit, do not use water or an oil-based detergent. It might cause an electric shock or a fire. 6.Do not use this unit at place where there are flammable or explosive gas, humidity, direct ray of the sun, radiant heat, vibration, impact etc. It may cause explosion or a fire. 7.Do not inflow dust or wire dregs into inside of this unit. It may cause a fire or mechanical trouble.

[ FLK.1]
FK I Flicker 1
(Ton operation precedes Toff operation)

Ton Toff Ton Toff Ton Ta

Rt Ton Toff

Ton Toff

POWER RESET Toff UP Ton 0 Toff DOWN Ton 0

POWER

Time limit contact output Toff : OFF Setting time


Ton : ON Setting time

Time limit contact(-) Instantaneous contact (-)

1. Control output will be repeatedly ON during Ton setting time and will be OFF during Toff setting time when power is ON. 2. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes OFF when power is OFF. 3. If pressing RESET key, display value and time limit output will be reset. 4. It is able to set each Ton time and Toff time separately. In [ FLK.1] mode, timing operation starts with Ton.

2) One-Shot output time setting


It will be activated when selecting ON Delay 2[ OND.2] output operation mode (One-Shot-output mode).(Time setting: 0.01 sec ~ 99.99 sec)

[ INT]
INT

Rt

POWER RESET Setting time UP 0 Setting time DOWN 0

POWER

T
Time limit contact output Time limit contact(-) Instantaneous contact (-)

Ordering information
L E 4 S A
Output A Size Digit Item Display Time limit contact 1c Time limit contact 2c, Instantaneous contact 1c + Time limit contact 1c(Selectable)

Interval

3) Time progress UP/DOWN setting


>key <key

UP[ UP]: Time progressed from 0 to setting time. DOWN[ DN]: Time progressed from setting time to 0.

S DIN W48mmH48mm 4 9999(4 Digit type)

4) Output contact setting


Set the relay contact (No.1, 3, 4 pin) to Instantaneous or Time limit. [ 1C.1C] : Instantaneous 1c, Time limit 1c , [ 2C] : Time limit 2c. <key It is fixed to Time limit 2c in star-delta, Twin and Twin 1 modes. If *key press on RUN mode, [ 1C.1C] or [ 2C] will be displayed depend on the status of output contact on time setting display.
>key

1. Time limit output will be ON when power is ON and Timing operation starts. 2. Time limit output will be OFF when timing operation is progressed up to the setting time. Display value will be HOLD. 3. If selecting time limit 1c + instantaneous 1c mode, instantaneous output will be ON when power is ON and goes OFF when power is OFF. 4. If pressing RESET key, display value and time limit output will be reset.

[ S-D]
POWER RESET T1 (Output will be UP T2 set automatically 0 as Time limit 2c) T1 DOWN T2 0

T1

T2

Rt

T1

T2

POWER

T1 T2

E Timer L LCD Display


8 Pin socket(PG-08, PS-08): Sold separately

contact contact
T1 : Setting time T2 : Return time ( Return time) contact(-) contact(-)

Star-Delta

Dimensions
55 48 76 6 56 14

5) Backlight setting
(Unit:mm)
>key <key

Set Backlight (ON[ ON], OFF[ OFF]).

6) Key Lock selection


44.8 48

1. contact will be ON when power is ON and Timing operation starts. 2. contact will be OFF when timing operation is progressed up to the T1 setting time. Timing operation will be reset and started again. 3. contact will be ON when timing operation is progressed up to the T2 switching time. Display value will be HOLD. 4. If pressing RESET key, display value and contacts will be reset. 5. It is able to set each T1 and T2 time separately.

>key <key

[ TWN]
T
>key <key

T1

T2

Rt

T1

T2

T1

>key <key

>key <key

POWER RESET

POWER T1 contact T2 contact

T1 T2
T1,T2 = Setting time T1 contact(-) T2 contact(-)

Panel cut-out
Min.65 45+0.6 -0

Product mounting

Turns off the Lock mode.

,key cannot
be used.

<,>key cannot be used.

,,<,>key
cannot be used.

Twin T1 (Output will be UP T2 set automatically 0 T1 as Time limit 2c) DOWN T2 0

Time setting

Min.65

Output operation mode : OND, OND II , INT

1. T1 contact will be ON when power is ON and Timing operation starts. 2. T1 contact will be OFF and T2 contact will be ON when timing operation is progressed up to the T1 setting time. Timing operation will be reset and started again. T2 contact will be OFF when timing operation is progressed up to the T2 setting time. Display value will be HOLD. 3. If pressing RESET key, display value and T1, T2 contacts will be reset. 4. It is able to set each T1 and T2 time separately.
POWER RESET Twin 1 T1 (Output will be UP T2 set automatically 0 as Time limit 2c) T1 DOWN T2 0

45+0.6 -0

[ TWN.1]
TI

T1

T2

Ta

Rt

T1

T2

POWER

T1
T1 contact

Insert product into a panel, fasten braket by pushing with tools as shown above.

T2
T2 contact

Specifications
Model Power supply Display method Allowable voltage range Power consumption Return time Control Con- Type output tact Capacity RepeatSettingVoltage Temperature error Ambient temperature Storage temperature Ambient humidity Insulation resistance Dielectric strength Mechanical Vibration Malfunction Shock Mechanical Malfunction

[Fig. 1]

[Fig. 2]

[Fig. 3]

[Fig. 4]

[Fig. 5]

T1,T2 = Setting time T1 contact(-) T2 contact(-)

LE4SA
24-240VAC 50/60Hz, 24-240VDC LCD Display(Backlight) 90 ~ 110% of rated voltage 24-240VAC: Max. 4VA, 24-240VDC: Max. 1.6W Max. 100ms Time limit DPDT(2c), Time limit SPDT(1c)+Instantaneous contact SPDT(1c): Selectable 250VAC 3A resistive load Max. 0.01% 0.05 sec -10 ~ 55(at non-freezing status) -25 ~ 65(at non-freezing status) 35 ~ 85%RH Min. 100M(500VDC megger) 2,000VAC 50/60 for 1 minute 0.75mm amplitude at frequency of 10 ~ 55 in each of X, Y, Z directions for 1hour 0.5mm amplitude at frequency of 10 ~ 55 in each of X, Y, Z directions for 10 minutes 300m/s(30G) X, Y, Z directions for 3 times 100m/s(10G) X, Y, Z directions for 3 times Min. 10,000,000 times Min. 100,000 times(250VAC 3A resistive load) Approx. 98g

Press <key in RUN mode, time set digits will flash.[Fig. 1] Change setting time by press < or >keys.[Fig. 2,3,4] -<key:Shift the setting digits. ->key:Shift the flashing position value. As press >key once, it will increase by 1digit, number will increase faster by press >key for over 2sec. When the setting is completed, it will be saved and return to RUN mode by pressing *key.[Fig. 5]

1. Timing operation starts when power is ON. 2. T1 contact will be ON when timing operation is progressed up to the T1 setting time. Timing operation will be reset and started again. 3. T2 contact will be ON when timing operation is progressed up to the T2 setting time. Display value will be HOLD. 4. If pressing RESET key, display value and T1 and T2 contacts will be reset. 5. It is able to set each T1 and T2 time separately.

Output operation mode : FK, FK I

, . Reset: Up mode -> Display value is0 Output isOFF DOWN mode -> Display value issetting time Output isOFF , .

Caution for using


1. Power connection (1) AC Power : It is able to connect power to the terminals(2 to 7) without distinguish the polarity. DC Power : Be sure the polarity of <->, <+>. (2) It can be operating stably due to free power voltage type.(Please connect the power lind seperate from high voltage line in order to avoid inductive noise) 2. Input signal line (1) Shorten the cable distance between the sensor and this product. (2) Please shielded wire for input signal needed to be long. (3) Please wire input signal line separated from power line. 3. When test dielectric voltage and insulation resistance of the control panel with this unit installed. (1) Please isolate this unit from the circuit of control panel. (2) Please make all terminals of this unit short-circuited. 4. Do not use this unit at below places because of product damage. (1) Place where there are severe vibration or impact (2) Place where strong alkalis or acids are used (3) Place where there are direct ray of the sun (4) Place where strong magnetic field or electric noise are generated 5. Installation environment (1) It shall be used indoor (2) Altitude Max. 2000m (3) Pollution Degree 2 (4) Installation Category II

RUN mode

T.off Time

<

Setting of <> Setting the time

Setting of <> Setting T.on Time the time

RUN mode

Output operation mode :

, T, T I

Mechanical Relay life cycle Electrical Approval Weight

RUN mode

<

Setting of <> Setting T1 Time the time

Setting of <> Setting T2 Time the time

RUN mode

Connection

OND, OND II, FK, FK I, INT, T, T I


CONTACT OUT 250VAC 3A RESISTIVE LOAD

CONTACT OUT 250VAC 3A RESISTIVE LOAD


Contact Contact
(Time limit contact1a)

Setting time changes can be made during timing operation. Make sure that timing operation is continuously progressed while changing the setting time. If pressing *key while setting time is shorter than min. setting time, setting value will be flickering three times and it will be returned to setting mode again, not to RUN mode. If there is no additional key operations after entering into setting mode, it will be return to RUN mode.(Setting value is not saved.) Min. Setting time: 0.01 sec.(In case of OND and OND modes, it is able to set 0 since no min. setting time is applied.)

It may cause malfunction if above instructions are not followed.

Major products
Proximity sensors Counters Pressure sensors Timers http://www.autonics.com Rotary encoders Area sensors Satisfiable Partner For Factory Automation Fiber optic sensors Display units HEAD QUARTERS : Photoelectric sensors Panel meters Graphic/Logic panels Sensor controllers 41-5. Yongdang-dong, Yangsan-si, Gyeongnam, 626-847, Korea Field network devices Power controllers OVERSEAS SALES : Door/Door side sensors Bldg. 402 3rd FL., Bucheon Techno Park, 193, Yakdae-dong, Temperature controllers Wonmi-gu, Bucheon-si, Gyeonggi-do, 420-734, Korea TEL : 82-32-610-2730 / FAX : 82-32-329-0728 Tachometer/Pulse(Rate) meters E-mail : sales@autonics.com Temperature/Humidity transducers Switching power supplies The proposal of a product improvement Stepping motors/drivers/motion controllers and development :product@autonics.com Laser marking system(CO Nd:YAG) , Laser welding/soldering system EP-KE-02-058A

Factory Default
NO.

(Time limit contact1a) (Instantaneous (Time contact1c) limit contact 1c) (Time limit contact1c)

Parameter Output operation mode Time Range Time Up/Down Output contact Backlight Key Lock Setting time

Default

1 2
SOURCE

SOURCE

3 4 5 6 7

Instantaneous contact 1c + Time limit contact 1c or Time limit contact 2c (Selectable) T, T I : Time limit 2c(Only)

The above specifications are subject to change without notice.

OUT.M T.RNG U-D CONT BLU LOCK -

OND 99.99s UP 1C.1C ON LOC.1 50.00s