Nothing Special   »   [go: up one dir, main page]

XLS40e XLS50e XLS60e: Installation Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 46

S Y S T E M

XLS40e
XLS50e Document No. 996-131-001 Issue 01

Installation
XLS60e Manual This manual should not be left with the end user.
XLS40/50/60e Fire Alarm Control Panels

Table of Contents
1 INTRODUCTION ......................................................................................................................... 5
1.1 NOTICE .................................................................................................................................. 5
1.2 WARNINGS AND CAUTIONS ...................................................................................................... 5
1.3 NATIONAL APPROVALS ............................................................................................................ 6
1.4 EN54 INFORMATION ............................................................................................................... 6
2 UNPACKING............................................................................................................................... 8

3 INSTALLATION .......................................................................................................................... 9
3.1 INSTALLING THE ENCLOSURE .................................................................................................. 9
3.1.1 Removing the Chassis .................................................................................................. 9
3.1.2 Mounting the Enclosure to the Wall .............................................................................. 9
3.1.3 Remounting the Chassis............................................................................................... 9
3.2 DIMENSIONS AND FIXING POINTS ........................................................................................... 10
3.3 IDENTIFICATION OF PARTS..................................................................................................... 11
3.3.1 CPU Board .................................................................................................................. 12
3.3.2 Display / Keyboard...................................................................................................... 12
3.3.3 Base Card ................................................................................................................... 12
3.3.4 Zone Extender Card (XLS60e Option Only) ............................................................... 12
3.3.5 Internal Printer (XLS60e Option Only) ........................................................................ 12
3.4 EXTERNAL CONNECTIONS ..................................................................................................... 13
3.4.1 Mains Power Input ...................................................................................................... 13
3.4.1.1 XLS40e / XLS50e Arrangement ............................................................................................13
3.4.1.2 XLS60e Arrangement............................................................................................................ 13
3.4.1.3 Mains Cable Glands .............................................................................................................. 14
3.4.2 Battery Installation ...................................................................................................... 15
3.4.2.1 General Introduction.............................................................................................................. 15
3.4.2.2 XLS40e / XLS50e Arrangement ............................................................................................15
3.4.2.3 XLS60e Arrangement............................................................................................................ 16
3.4.2.4 General Battery Connection .................................................................................................. 16
3.4.3 Detection Loops .......................................................................................................... 17
3.4.3.1 Loop Wiring Installation ......................................................................................................... 18
3.4.3.2 EMC Compliance .................................................................................................................. 19
3.4.3.3 Panel Loop Loading .............................................................................................................. 19
3.4.4 Sounder Circuits.......................................................................................................... 20
3.4.5 Auxiliary Relay Outputs............................................................................................... 22
3.4.6 Auxiliary Supply Output............................................................................................... 23
3.4.7 Panel Networking / Graphics PC Interface ................................................................. 24
3.4.7.1 Local Panel Network ............................................................................................................. 24
3.4.7.2 Master Panel to Superior Master Panel ................................................................................ 24
3.4.7.3 Panel to Graphics PC............................................................................................................ 24
3.4.8 Peripheral Loop........................................................................................................... 25
3.4.9 RS485 Wiring Arrangements ...................................................................................... 26
3.4.9.1 Daisy Chain Style Installation................................................................................................ 26
3.4.9.2 Loop Style Installation ........................................................................................................... 26
3.4.9.3 EMC Compliance .................................................................................................................. 26
3.4.9.4 Cable Screen – Earth Connections ....................................................................................... 27
3.4.10 High Integrity Loop...................................................................................................... 27
3.4.11 Group Disable Input .................................................................................................... 27
3.4.12 Class Change Input .................................................................................................... 27
3.4.13 Recommended Cables ............................................................................................... 28
3.4.14 Base Card Power Supply Connections....................................................................... 28
3.4.15 Cable Routing ............................................................................................................. 29
3.5 INSTALLING ADDITIONAL EQUIPMENT ..................................................................................... 30
3.5.1 General Introduction ................................................................................................... 30
3.5.1.1 XLS40e Arrangement............................................................................................................ 30
3.5.1.2 XLS50e Arrangement............................................................................................................ 31
3.5.1.3 XLS60e Arrangement............................................................................................................ 31

Page 2 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.5.2 Loop Driver Cards........................................................................................................32


3.5.2.1 Voltage Selection .................................................................................................................. 32
3.5.2.1.1 XLS40e / XLS50e Jumper Settings................................................................................. 32
3.5.2.1.2 XLS60e Jumper Settings ................................................................................................ 33
3.5.3 485 / 232 Interface Cards ............................................................................................33
3.5.3.1 Mounting the card directly to the base card........................................................................... 34
3.5.3.2 Mounting the card above the Loop Driver Module................................................................. 34
3.5.4 Printer Module (XLS60e Only).....................................................................................35
4 STANDBY BATTERY CALCULATIONS ..................................................................................36
4.1 SENSOR CURRENT CALCULATIONS .........................................................................................38
4.1.1 Quiescent Load............................................................................................................38
4.1.2 Alarm Load...................................................................................................................38
4.1.3 Adjustment Factors ......................................................................................................38
4.2 LOCAL SYSTEMS AMPERE HOUR CALCULATION ......................................................................38
5 MAINTENANCE.........................................................................................................................39
5.1 MAINTENANCE SCHEDULE ......................................................................................................39
5.1.1 Daily Attention..............................................................................................................39
5.1.2 Monthly Attention .........................................................................................................39
5.1.3 Quarterly Attention .......................................................................................................39
5.1.4 Yearly Attention............................................................................................................39
5.2 REPLACEMENT OF COMPONENTS ...........................................................................................40
5.2.1 Lithium Standby battery ...............................................................................................40
5.2.2 Liquid Crystal Alphanumeric Display ...........................................................................40
5.2.3 Standby Batteries.........................................................................................................40
6 SPECIFICATIONS .....................................................................................................................41
6.1 FUNCTIONAL SPECIFICATIONS ................................................................................................41
6.2 POWER SUPPLY AND CHARGER..............................................................................................43

Installation Manual Document No. 996-131-001, Revision: 01, Page 3 of 46


XLS40/50/60e Fire Alarm Control Panels

Table of Figures
FIGURE 1 – PANEL FIXING CENTRES – XLS40E / XLS50E .................................................................... 10
FIGURE 2 – PANEL FIXING CENTRES - XLS60E .................................................................................... 10
FIGURE 3 – ENCLOSURE ARRANGEMENT - XLS60E .............................................................................. 11
FIGURE 4 – ENCLOSURE ARRANGEMENT – XLS40E / XLS50E ............................................................. 11
FIGURE 5 – MAINS INPUT ARRANGEMENT – XLS40E / XLS50E ............................................................ 13
FIGURE 6 – MAINS INPUT ARRANGEMENT – XLS60E ............................................................................ 14
FIGURE 7 – XLS40E / XLS50E BATTERY INSTALLATION ....................................................................... 15
FIGURE 8 – XLS60E BATTERY INSTALLATION ....................................................................................... 16
FIGURE 9 – SLC CONNECTIONS .......................................................................................................... 18
FIGURE 10 – LOOP WIRING WITHOUT ISOLATORS ................................................................................. 18
FIGURE 11 – LOOP WIRING WITH ISOLATORS– PREFERED ALTERNATIVE ............................................... 19
FIGURE 12 – SLC LOOP – EMC ABSORBER INSTALLATION .................................................................. 19
FIGURE 13 – SOUNDER TERMINAL CONNECTION POINTS – XLS50E...................................................... 20
FIGURE 14 – SOUNDER TERMINAL CONNECTION POINTS – XLS60E...................................................... 20
FIGURE 15 – SOUNDER WIRING ........................................................................................................... 21
FIGURE 16 – RELAY OUTPUT TERMINAL CONNECTION POINTS – XLS40E / XLS50E.............................. 22
FIGURE 17 – RELAY OUTPUT TERMINAL CONNECTION POINTS – XLS60E ............................................. 22
FIGURE 18 – AUXILIARY OUTPUT CONNECTIONS – XLS40E / XLS50E .................................................. 23
FIGURE 19 – AUXILIARY OUTPUT CONNECTIONS – XLS60E .................................................................. 23
FIGURE 20 – AUXILIARY OUTPUT - FERRITE ABSORBER (TYPICAL) ........................................................ 23
FIGURE 21 – TYPICAL RS485 – ‘DAISY CHAIN’ WIRING ........................................................................ 26
FIGURE 22 – TYPICAL RS485 – ‘LOOP’ WIRING ................................................................................... 26
FIGURE 23 – RS485 LOOP – EMC ABSORBER INSTALLATION .............................................................. 26
FIGURE 24 – RS485 SCREEN – EARTH ARRANGEMENT ....................................................................... 27
FIGURE 25 – BASE CARD POWER CONNECTIONS ................................................................................. 28
FIGURE 26 – RECOMMENDED CABLE ROUTING ARRANGEMENT – XLS40E / XLS50E ............................ 29
FIGURE 27 – RECOMMENDED CABLE ROUTING ARRANGEMENT – XLS60E ........................................... 29
FIGURE 28 – POSITIONS FOR ADDITIONAL BOARDS – XLS40E .............................................................. 30
FIGURE 29 – POSITIONS FOR ADDITIONAL BOARDS – XLS50E .............................................................. 31
FIGURE 30 – POSITIONS FOR ADDITIONAL BOARDS – XLS60E .............................................................. 31
FIGURE 31 – MOUNTING THE LOOP DRIVER ......................................................................................... 32
FIGURE 32 – MOUNTING THE RS485 / RS232 MODULE ....................................................................... 34
FIGURE 33 – MOUNTING THE RS485 / RS232 MODULE ....................................................................... 34

Table of Tables
TABLE 1 – PACKING CONTENTS LIST ...................................................................................................... 8
TABLE 2 – MAXIMUM LOOP LENGTHS ................................................................................................... 17
TABLE 3 – LIST OF COMPATIBLE PERIPHERAL DEVICES ......................................................................... 25
TABLE 4 – JUMPER SETTING FOR LOOP VOLTAGE ................................................................................. 32
TABLE 5 – JUMPER SETTING FOR LOOP VOLTAGE ................................................................................ 33
TABLE 6 – CURRENT RATING CHART – XLS40E / XLS50E ................................................................... 36
TABLE 7 – CURRENT RATING CHART - XLS60E .................................................................................... 37
TABLE 8 – XLS40E / XLS50E FUNCTIONAL SPECIFICATIONS ................................................................ 41
TABLE 9 – XLS60E FUNCTIONAL SPECIFICATIONS ................................................................................ 42
TABLE 10 – XLS40E / XLS50E POWER SUPPLY AND CHARGER SPECIFICATIONS .................................. 43
TABLE 11 – XLS60E POWER SUPPLY AND CHARGER SPECIFICATIONS .................................................. 44

Page 4 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

1 Introduction
1.1 Notice
• The material and instructions covered in this manual have been carefully checked for accuracy and are
presumed to be correct. However, the manufacturer assumes no responsibility for inaccuracies and
reserves the right to modify and revise this document without notice.
• These instructions cover the installation of the Fire Alarm Control Panels. For use with software
Refer to the User Manual (P/N 996-130-001) for details of how to operate
version 800 onwards
the system and refer to the Commissioning Manual (P/N 996-132-001) for
information on programming and Level 3 functions.
• The XLS40e, XLS50e and XLS60e Fire Alarm Control Panels are 1, 1-2 and 1-5 loop panels for use with
analogue addressable devices from the following detector manufacturer ranges: -

Honeywell

Apollo
S90

Hochiki

Nittan

System Sensor

• The XLS40e, XLS50e & XLS60e Fire Alarm Control Panels are not
EN54-2 EN54 approved for use with the Nittan range of signalling
EN54 devices.
! Nittan.
If the Nittan loop driver card is installed, the LPCB logo MUST be
removed.

1.2 Warnings and Cautions

These instructions contain procedures to follow in order to avoid injury and damage to
equipment. It is assumed that the user of this manual is a suitably trained installer who is
familiar with the relevant regulations.

Electro-static Sensitive Devices.


Take suitable ESD precautions when removing or installing printed circuit boards.

This panel is CE Marked to show that it conforms to the requirements of the following
European Community Directives:
• Electromagnetic Compatibility Directive 89/336/EEC (and the amending directive
92/23/EEC)
• Low Voltage Directive 73/23/EEC

Installation Manual Document No. 996-131-001, Revision: 01, Page 5 of 46


XLS40/50/60e Fire Alarm Control Panels

• This panel has been tested and found to comply with the Year 2000 requirements.
• NOTE: The end date for all date functions is 31/12/2079.
• In the year prior to reaching the calendar end date, consult the Original Equipment
Supplier/ Current Maintenance Contractor for advice.

CAUTION: A Lithium Battery is used for Data Retention.


Replace only with the same or equivalent type. Contact the Service Organisation for
Replacement CPU Card.

EN54-2 13.7 • The XLS40e, XLS50e & XLS60e range of panels has many features,
EN54 which if used inappropriately, may contravene the requirements of
! Maximum of 512 EN54. Where such a possibility may arise, a suitable warning is given
sensors / manual with brief details of the EN54 requirement and the relevant section it
call points per pertains to. A typical EN54 non-compliance warning is illustrated.
panel.

1.3 National Approvals


This equipment must be installed in accordance with these instructions and the appropriate
national, regional and local fire systems installation regulations specific to the country and location
of the installation. Consult with the appropriate Authority Having Jurisdiction (AHJ) for confirmation
of the requirements.

All equipment is to be installed in accordance with the appropriate standards for the
country and area of installation.

This equipment must be installed in accordance with these instructions and the appropriate
national, regional and local wiring regulations. In the UK the wiring must conform to the
requirements of the IEE Wiring Regulations – Sixteenth Edition.

1.4 EN54 Information

• This Fire Control Panel complies with the requirements of EN54-2/4 1997. In addition
EN54 to the basic requirements of EN54, the panel conforms to the following optional
9 functions.

Option EN54-2 Clause


Indication: Fault signals from points 8.3
Controls: Coincidence Detection 7.12
Delays of Actioning Outputs 7.11
Disablement of each address point. 9.5
Test condition 10
Outputs: Outputs to fire alarm devices 7.8

Page 6 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

EN54 • The power supplies for the XLS40e, XLS50e and XLS60e range of panels complies
9 with the following clauses of EN54-4.

XLS50e & XLS60e Power Supply Functions EN54-4 Clause


Derive power supply from main power source 5.1
Derive power supply from a standby battery source 5.2
Charge and monitor the standby battery source 5.3
Detect & signal power supply faults 5.4

• In addition to the functions required by EN54-2, the panel supports a number of


EN54 ancillary functions that are not required by EN54. These are outlined below:-
N/A
Ancillary Function Manual Section
Auxiliary supply output 3.4.6
Panel network output ports (Port C) 3.4.7, 3.5.1.1 & 3.5.1.3
Master panel to superior master panel output port 3.4.7.2, 3.5.1.1 & 3.5.1.3
connections (Port B - XLS60e only)
Panel to graphics PC output port connections (Port B – 3.4.7.3, 3.5.1.1 & 3.5.1.3
XLS60e only)
Peripheral loop output & supported devices (Port D) 3.4.8, 3.5.1.1 & 3.5.1.3
High integrity 485 Loop 3.4.10 & Hi485 Installation
Guide (996-065)
Auxiliary relay outputs 3.4.5
Printer option (XLS60e only) 3.5.4
Class Change Input 3.4.12
Group Disable 3.4.11

Installation Manual Document No. 996-131-001, Revision: 01, Page 7 of 46


XLS40/50/60e Fire Alarm Control Panels

2 Unpacking
• The XLS40e, XLS50e and XLS60e Fire Alarm Control Panels are simple to install if the recommended
procedures described in this manual are followed. Refer to the Commissioning Manual for details of how
to program the system operation.
• Before installing the XLS40e, XLS50e or XLS60e Fire Alarm Control Panels, first ensure that all the
equipment has been received. The packing box should contain the following items.

Item Component Part Number Quantity


XLS40e XLS50e XLS60e
1 XLS60e Fire Alarm Control Panel or - - 1
XLS50e Fire Alarm Control Panel or - 1 -
XLS40e Fire Alarm Control Panel 1 - -
2 Installation Manual 996-131-001 1 1 1
3 Commissioning Manual 996-132-001 1 1 1
4 Operator’ Manual 996-130-001 1 1 1
5 Reference Guide – XLS60e 996-135-001 - - 1
Reference Guide - XLS50e 996-134-001 - 1 -
Reference Guide – XLS40e 996-133-001 1 - -
6 Front Door Keys 797-021 2 2 2
7 Ferrite Absorber Small 538-143 1 1 1
8 Ferrite Absorber Large 684-353 1 1 -
9 Battery Cables Kit 082-073 1 1 1
10 EOL Resistor 627-682 2 2 4

Table 1 – Packing Contents List

• Frame and mount the supplied Reference Guide, on the wall, adjacent to the Panel.

NOTE:
The EOL resistors supplied are standard resistors. If EOL resistor assemblies with 150 mm flying leads are
required, please order these separately under part number 170-073-682.

Page 8 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3 Installation
3.1 Installing the Enclosure
• Unlock the front door and remove the battery cable, ferrite absorber and EOL resistor kits. Store these in
a secure place for re-use later.

3.1.1 Removing the Chassis


• Unplug the ribbon cable between the CPU Board and the Display Board at the CPU Board end.
• Remove the nuts and spring washers holding the chassis to the back box. (There are six of each for
XLS60e, and four of each for XLS40e / XLS50e). Store these in a secure place for re-use later.
• Carefully remove the chassis assembly. Store in a secure place where it will not be damaged and where it
will be kept dry and clean.

Handle the chassis by holding the metalwork only. DO NOT lift it by holding the printed
circuit boards or any parts on the circuit boards.

3.1.2 Mounting the Enclosure to the Wall


The XLS60e Fire Alarm Control Panel can weigh in excess of 38kg (XLS60e) and 18kg
(XLS40e / XLS50e) once the batteries are fitted. When attaching the enclosure to a surface,
use mounting hardware capable of supporting this weight and reinforce the wall if
necessary.

• Remove the necessary knockouts for the installation cabling.


• Mount the enclosure in the desired location using all four mounting holes.
• Use a drill bit diameter 7.0 mm and a suitable 40 mm long expansion plug. Fix the panel to the wall with
No. 10 screws length 1½” or M5 screws length 40 mm.
• Install the external wiring into the enclosure using the appropriate glands / conduit fittings. Sufficient
knockouts are provided at the top of the enclosure. If you punch other holes, be sure that they do not
interfere with any component mounting positions.
• Use a brush to clean any dust and swarf from inside the enclosure before attempting to remount the
chassis assembly.

For details of knockout positions, refer to section 3.4.15. Cables must be megger tested
before any active devices are fitted and before the connections are made to the terminal
blocks.

3.1.3 Remounting the Chassis


• Carefully mount the chassis onto the mounting threaded studs.
• Secure the chassis to the back box using the nuts and spring washers that were originally removed.
• Plug the ribbon cable between the CPU Board and the Display board back into the CPU Board. The plug
and socket are polarised to ensure correct insertion.

Handle the chassis by holding the metalwork only. DO NOT lift it by holding the printed
circuit boards or any parts on the circuit boards.

Installation Manual Document No. 996-131-001, Revision: 01, Page 9 of 46


XLS40/50/60e Fire Alarm Control Panels

3.2 Dimensions and Fixing Points


400mm

280mm 60mm

140mm

357mm

400mm
FIXING HOLES Ø5.0mm

Figure 1 – Panel Fixing Centres – XLS40e / XLS50e 18mm

Figure 2 – Panel Fixing Centres - XLS60e

Page 10 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.3 Identification of Parts


Transformer and AC Mains Terminal Block
Filter Assembly with Integral Fuse

Display /
Keyboard CPU Card

Base Card
Zone Expander
Card (Option)

Printer
Mounting
Plate

Power Supply
Card

Figure 3 – Enclosure Arrangement - XLS60e

AC Mains
Terminal
Block

FUSE

Transformer
and Filter
Assembly

Base
Card
CPU
Display / Card
Keyboard
Power
Supply Card

Figure 4 – Enclosure Arrangement – XLS40e / XLS50e

Installation Manual Document No. 996-131-001, Revision: 01, Page 11 of 46


XLS40/50/60e Fire Alarm Control Panels

3.3.1 CPU Board


• The CPU Board controls the operation of the XLS40e, XLS50e and XLS60e Fire Alarm Control Panels.
The operating program is stored in EPROM mounted in sockets on the board.

3.3.2 Display / Keyboard


• The Display / Keyboard provides the user access to view alarms and control operation of the system.

3.3.3 Base Card


• The base card provides control and wiring of all external connections to the system.
• The base card will be augmented with one (XLS40e), one to two (XLS50e) or one to five (XLS60e) plug-in
loop driver modules for connection to the signalling detectors.
• The system can support addressable smoke detectors and loop devices using different loop driver boards.
The options are as follows:

1. Honeywell 795-070 XLS60/LIB


2. System Sensor 795-068
3. Hochiki 795-058-005
4. Apollo XP95 / Discovery 795-066
5. Nittan 795-044

EN54-2
EN54
The panel is not EN54 approved for use with Nittan.
! Nittan If the Nittan option is fitted, the LPCB logo insert label MUST be removed.

• For details of the compatible signalling devices, refer to the relevant installation guide supplied with the
loop driver module. At least one loop driver board MUST be installed for the unit to operate as a Fire
Alarm Control Panel.
• The base card may be augmented by one (XLS40e), one or two (XLS50e) or by one, two or three
(XLS60e) plug-in serial interface cards. The serial interface cards provide for networking of panels and for
connection of peripheral devices. The XLS40e cannot be installed as part of a network.

3.3.4 Zone Extender Card (XLS60e Option Only)


• The XLS60e FACP may be augmented with an additional Zone LED Indicator card. This Zone Expander
Card provides FIRE ALARM and FAULT LED indicators.
• It is available in two options providing, a further 20 zones (40 zones in total) or a further 60 zones (80
zones in total). The model numbers of the units are as follows:
1. 795-077-020 20 Zone LED Expander
2. 795-077-060 60 Zone LED Expander
• Refer to the Zone Expander Installation Guide (P/N 996-137) for further information.

3.3.5 Internal Printer (XLS60e Option Only)


• The XLS60e FACP may be augmented by the addition of a printer module. This provides printed records
of FIRE ALARMS, FAULTS and EVENT LOG.
• Refer to Section 3.5.4 and to the Commissioning Manual for further information.

Page 12 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.4 External Connections


BEFORE INSTALLATION: Refer to Ratings / Type label located on the inside of the panel.

3.4.1 Mains Power Input

3.4.1.1 XLS40e / XLS50e Arrangement


• The XLS40e and XLS50e Fire Alarm Control Panels receive power from either a 230V, 50Hz (or 120V,
1
60Hz-power supply ). The current flows through an EMI filter to the transformer. The transformer converts
the input mains voltage to 24V AC. All of these components are mounted to the chassis.
• The incoming power feed cable Ground or Earth (Green or Green/Yellow) wire should be connected to the
terminal block earth connection – middle terminal.
• Connect the neutral (Blue/Black) wire to the top terminal and connect the Phase or Live (Brown/Red) wire
to the bottom terminal. The terminal block contains an integral fuse.

Open and lock out the circuit


breaker before connecting
any wiring. Do not power the
system until the installation is
complete. Ferrite
Large

Maintain separation between ISOLATE

the 120/230V and the low ELSEWHERE

N Afiix cable tie


voltage wiring. Do not route in around wires
below ferrite
the same trunking and keep
Blue L
apart in the enclosure. F1: T 2A H 250V

Green / Yellow
Brown
Fuse
For EMC Compliance, fit the ISOLATE
supplied Ferrite Absorber ELSEWHERE

(large) as shown in the N


diagram.
L
F1: T 2A H 250V

Figure 5 – Mains Input Arrangement – XLS40e / XLS50e

The panel shall be supplied with AC mains power via a readily accessible disconnect device
(‘isolation’ switch) to facilitate servicing and be provided with suitable earth fault protection
incorporated in the building installation wiring. The minimum cross sectional area of the
mains cable should be 0.75mm and the supply should be fused with a 5A HRC anti-surge
fuse.

3.4.1.2 XLS60e Arrangement


• The XLS60e Fire Alarm Control Panel receives power from a 230V, 50Hz (or a 120V, 60Hz power
1
supply ). The current flows through an EMI filter and a chassis mounted fuse, to the transformer. The
transformer converts the input mains voltage to 24V AC. All of these components are mounted to the
chassis.
• The incoming power feed cable Ground or Earth (Green or Green/Yellow) wire should be connected to the
terminal block earth connection – middle terminal.

1
With the appropriate transformer fitted.

Installation Manual Document No. 996-131-001, Revision: 01, Page 13 of 46


XLS40/50/60e Fire Alarm Control Panels

• Connect the neutral (Blue/Black) wire to the left-hand terminal and connect the Phase or Live
(Brown/Red) wire to the right hand terminal.

Open and lock out the circuit


breaker before connecting
any wiring. Do not power the
system until the installation is
complete.

Blue
ISOLATE
Brown
Maintain separation between Green
ELSEWHERE
F1 T 3.15A H 250V

the 120/230V and the low N L


voltage wiring. Do not route in
ISOLATE
same trunking and keep apart ELSEWHERE FUSE

in the enclosure.
F1 T 3.15A H 250V

N L

Chassis
Replace the cover, supplied,
over the terminal block.

Figure 6 – Mains Input Arrangement – XLS60e

The panel shall be supplied with AC mains power via a readily accessible disconnect device
(‘isolation’ switch) to facilitate servicing and be provided with suitable earth fault protection
incorporated in the building installation wiring. The minimum cross sectional area of the
mains cable should be 0.75mm and the supply should be fused with a 5A HRC anti-surge
fuse.

3.4.1.3 Mains Cable Glands

The cable gland and cord anchorage bushing used to route the mains cable through the
20mm knockout MUST have a minimum flame retardant rating of 94HB.
• Typical glands / bushings are: -
Type Manufacturer Supplier / Part No.
Gland IP68 – Nylon 66 M20 Black, Rating UL94V-2 Multicomp Farnell 927-739
Gland IP65 – Brass M20, EExd / Eexe Lappcable A2F20S
Bushing Nylon 66 M20 Black, Rating UL94V-2 Multicomp Farnell 303-0751

Page 14 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.4.2 Battery Installation

3.4.2.1 General Introduction


• Refer to the Standby Battery Calculations (section 4) for the size of the batteries required for a particular
installation.
• Refer to Section 5.2.3 for a list of recommended batteries.

Do not make the final battery connections until the installation is complete.
Battery Lead Connections are not power limited.

Before installation.
New Batteries require ‘top charging’ prior to being put into service. For further information
and for a list of recommended batteries, refer to Section 5.2.3.

3.4.2.2 XLS40e / XLS50e Arrangement

• Included in the packing is a battery cable kit. Use


the cable included in this kit to connect the
negative terminal of battery No.1 to the positive
terminal of battery No.2.
• Connect the red wire from terminal (7) on the
Power Supply to the positive terminal of battery
No.1.
• Connect the black wire from terminal (6) on the
Power Supply to the negative terminal of battery
No.2.
• The standby batteries should be located in the 7AH 7AH
#2 #1
enclosure as shown in the diagrams opposite.

Battery Stops

• For battery sizes greater than 12Ah, these


should be installed in a separate enclosure
suitable for Fire Protection Use, such as Battery
Box 797-025-001, with wiring connected to the
panel through conduit.

12AH 12AH
#2 #1

Battery Stops

Figure 7 – XLS40e / XLS50e Battery Installation

Installation Manual Document No. 996-131-001, Revision: 01, Page 15 of 46


XLS40/50/60e Fire Alarm Control Panels

3.4.2.3 XLS60e Arrangement


• Included in the packing is a battery cable kit. Use
the cable included in this kit to connect the
negative terminal of battery No.1 to the positive
terminal of battery No.2.
• Connect the red wire from terminal (6) on the
Power Supply to the positive terminal of battery
No.1.
• Connect the black wire from terminal (7) on the
Power Supply to the negative terminal of battery
No.2.
• The standby batteries should be located in the
enclosure as shown in the diagrams opposite. 12Ah 12Ah
The chassis provides fixing points to allow a #2 #1
strap to be fitted.
Battery Stop

• For battery sizes greater then 12Ah, it is


necessary to cut off the spade terminals
connected to the battery cables. These should be
replaced by connector fixings appropriate to the 17Ah 17Ah
installed batteries #2 #1

• For battery sizes greater than 25Ah, these


should be installed in a separate enclosure
suitable for Fire Protection Use, such as Battery
Box 797-025-001, with wiring connected to the 24Ah
24Ah
panel through conduit. #1 #2

Figure 8 – XLS60e Battery Installation

3.4.2.4 General Battery Connection

- Charger
+
Black Output Red
Wire Wire

Link Wire

- + - +
2 1

Page 16 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.4.3 Detection Loops


• The control panel supports analogue detectors with a digital, data transmission system. It provides power
and communicates with the initiating devices over a two-wire circuit.

• Depending on protocol, it is possible for up to 1000 addressable input


EN54-2 13.7 points to be connected to the panel.
EN54
! Maximum of 512 • To comply with EN54-2 requirements, a maximum of 512 sensors /
sensors / MCP’s MCP’s (input points) only should be connected to the control panel
per panel. across all analogue detection loops. This limit includes any
conventional detectors / call points connected to the system via zone
monitors.

The detection circuit should be separated from other cable runs to minimize the risk of
external interference. Under extremely noisy conditions, twisted pair wire is
recommended to reduce interference.
The Detection Loop Circuits are supervised and power limited.

• Shielded cable should be used for all detection (SLC) circuits. It is important that the shield is always
terminated to a good earth connection at both ends of the loop. Mineral insulated copper cable (MICC) is
recommended for the best screening purposes. However, most of the established brands of fire related
screened cables are suitable. Refer to Section 3.4.13 for a list of recommended cables.
• The core size, length of wiring run and detection circuit loading will produce a voltage drop along the
length of the cable. To determine if the installed loop driver can fully support the planned loop
configuration, use the detector manufacturers’ calculations for voltage and capacitance.

ALWAYS check that conductors of appropriate diameter are used so that the voltage at
the detectors is within the detector manufacturer’s specification.
The maximum permitted impedance for the SLC Loop is 40 ohms. This must be reduced if
loop powered sounders are installed.

• The following table lists the maximum recommended cable loop lengths for each detection loop type.
Wiring to external devices should follow the appropriate manufacturer’s instructions.

Loop Driver Maximum Loop Length


MICC 18 AWG 16 AWG 14 AWG
1.5mm
Honeywell 2 km 1 km 1.5 km 2 km
System Sensor 2 km 1 km 1.5 km 2 km
Apollo 2 km 1 km 1.5 km 2 km
Hochiki 2 km 1 km 1.5 km 2 km
Nittan 1 km 0.8km 1 km 1 km

Table 2 – Maximum Loop Lengths

• NOTE 1: Cable runs in excess of 2km are not recommended. Otherwise, cable capacitance (Max. 0.5uF
per loop) and inductance may start to interfere with data transmission. Refer to the manufacturers’ quoted
figures for maximum cable capacitance.
• The SLC (detector) circuits should be installed as loops with or without isolator modules. The wiring
details are as described below.

Installation Manual Document No. 996-131-001, Revision: 01, Page 17 of 46


XLS40/50/60e Fire Alarm Control Panels

EN54-2 12.5.2 For best results and system integrity:


EN54 The detection loop circuit should be wired as a loop with short
! Maximum of 32
sensors / MCP’s circuit isolators. This will allow the system to still function, even if a
between Isolator. section of the cable becomes open circuited. It is recommended that
Short circuit isolators be fitted to the detection loop to prevent an
external short circuit from removing more than 32 addressable
points from the system.

• The detection loop connections are made on the terminal blocks at the top of the base card.

3.4.3.1 Loop Wiring Installation

(+) RETURN
• Form the loop by taking wires from the positive and Data / Power (+) OUT
Data / Power (-) OUT
(-) RETURN

negative terminals, at one side of the connector on the


base card – see opposite.
• Proceed with installing wiring, around the loop,
connecting all devices – see below.
• Return the wiring to the positive and negative
terminals at the other side of the connector on the
base card.
• Ensure that all devices connected to the loop are
correctly oriented for positive and negative
connections.
• Refer to the detector manufacturers’ data sheet
supplied with the signalling device.

Figure 9 – SLC Connections

FACP Connections
Data / Power (+) OUT

Data / Power (-) OUT

Data / Power (+) RETURN

Data / Power (-) RETURN

Figure 10 – Loop Wiring without Isolators

DO NOT loop wiring under any terminals. Break wire run to maintain supervision.

Page 18 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

• It is recommended that Short Circuit Isolators be installed. Install the isolators at strategic points in the
loop (i.e. zonal boundaries) to prevent an external short circuit from removing more than 32 addressable
points from the system. Note: The loop driver modules have built-in isolators so it is not required to place
isolator modules on the outputs of the FACP.
• Refer to the following diagram for information.

FACP Connections
Data / Power (+) OUT

Data / Power (-) OUT

ISOLATORS

Data / Power (+) RETURN

Data / Power (-) RETURN

Figure 11 – Loop Wiring with Isolators– Prefered Alternative

3.4.3.2 EMC Compliance

For EMC Compliance, fit the


Ferrite Absorbers supplied
with the loop driver board
around the SLC Loop cables. Connect Earth Absorber
drain wire of Large
cable to gland
The figure opposite shows the earth
typical arrangement for a
typical installation.
Affix cable tie
around wires
below ferrite
+-E+-
LOOP 1

Figure 12 – SLC Loop – EMC Absorber Installation

3.4.3.3 Panel Loop Loading


• Care must be taken to ensure that the number of signalling loop devices (inputs and outputs) installed
does not exceed the power supply ratings of each individual loop driver board and of the panel (all loops)
in both quiescent and alarm conditions.
1. Loop Driver Board Load (Refer to the documentation supplied with the loop driver)
2. Overall Panel Load (Refer to Specification Tables – Section 6).

Installation Manual Document No. 996-131-001, Revision: 01, Page 19 of 46


XLS40/50/60e Fire Alarm Control Panels

3.4.4 Sounder Circuits


• The XLS40e and XLS50e Fire Alarm Control Panels have two power limited and supervised sounder
circuits, identified as sounder circuits A and B.
• The XLS60e Fire Alarm Control Panel has four power limited and supervised sounder circuits, identified
as sounder circuits A, B, C and D.
• Each circuit has a maximum rating of 1 Amp.
• Each sounder output is monitored for open and short circuits. An end-of-line (EOL) resistor (6.8KΩ, 0.5W
minimum, P/N 170-073-682) must be fitted to the last sounder on the circuit.
• Each sounder should have an integral blocking diode that prevents the sounder from consuming any
power in the normal monitoring position. The polarity of the sounder output is reversed when the sounder
circuit is energised. This allows the sounder to turn on.

Sounder Circuits

Figure 13 – Sounder Terminal Connection Points – XLS50e

N/O N/C COM N/O N/C COM A- A+ B- B+ C- C+ D- D+ 0V 24V


TB10 TB7 TB8 TB9 TB6

SOUNDER CIRCUITS

Figure 14 – Sounder Terminal Connection Points – XLS60e

• Any other devices connected to sounder outputs must be suppressed and polarized.
• Refer to Section 3.4.13 for a list of recommended cables.

Page 20 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

FACP Connections

SOUNDER A (+)
EOL (6800Ω)

SOUNDER A (-) Typical


Arrangement
SOUNDER B (+)
EOL (6800Ω)

SOUNDER B (-)

Figure 15 – Sounder Wiring

DO NOT loop wiring under any terminals. Break wire run to maintain supervision.

• Cable runs in excess of 1km (3200’) are not recommended. Otherwise, the capacitance and inductance of
the cable may affect the performance of the system. For systems with Nittan detectors, cable runs should
not exceed ½ km (1600’).
• Always check that conductors of appropriate diameter are used so that the voltage of all sounders is
within the manufacturers specification when the panel is operating under AC Mains failure and minimum
battery voltage conditions (Refer to Table 10 & Table 11 for minimum panel output voltage).

Installation Manual Document No. 996-131-001, Revision: 01, Page 21 of 46


XLS40/50/60e Fire Alarm Control Panels

3.4.5 Auxiliary Relay Outputs

• The XLS40e, XLS50e and XLS60e Fire Alarm Control Panels


EN54-2 8.8 have two unsupervised, programmable relay outputs, with volt
EN54
Fault Output: free (dry contact) changeover contacts.
!
Relay 1 is configured • Each output is rated at 30V AC/DC, 1 Amp.
for failsafe operation • Relay 1 is normally held in an energized state. It will de-energize
as standard. under fault conditions.

Relay Circuits

Figure 16 – Relay Output Terminal Connection Points – XLS40e / XLS50e

N/O N/C COM N/O N/C COM A- A+ B- B+ C- C+ D- D+ 0V 24V


TB10 TB7 TB8 TB9 TB6

_____ _____
#1 #2
RELAY CIRCUITS

Figure 17 – Relay Output Terminal Connection Points – XLS60e

Do not connect any wiring to the relay contacts that is not power limited.

Page 22 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.4.6 Auxiliary Supply Output


• The XLS40e, XLS50e and XLS60e Fire Alarm Control Panels have a power-limited, unsupervised
auxiliary (AUX O/P) 24V-output supply rated at 340mA maximum.
• This supply can be used to power Remote Annunciator (Repeater) units and other peripheral loop units or
other signalling loop units.

Auxiliary Output

Figure 18 – Auxiliary Output Connections – XLS40e / XLS50e

N/O N/C COM N/O N/C COM A- A+ B- B+ C- C+ D- D+ 0V 24V


TB10 TB7 TB8 TB9 TB6

AUXILIARY OUTPUT

Figure 19 – Auxiliary Output Connections – XLS60e

0V (Gnd) 24V DC
The total current loading of all
detection loops, sounder circuits and
auxiliary supply must not exceed the
rated output capability of the panel –
refer to specification tables.
Absorber
Small

For EMC Compliance, fit the supplied Afiix cable tie


around wires
Ferrite Absorber (small) as shown in below ferrite

the diagram.
Figure 20 – Auxiliary Output - Ferrite Absorber
(Typical)

Installation Manual Document No. 996-131-001, Revision: 01, Page 23 of 46


XLS40/50/60e Fire Alarm Control Panels

3.4.7 Panel Networking / Graphics PC Interface


EN54-2 12.5
• The Panel Network (Master to Slave panel) interface uses Port ‘C’
Integrity of position on the base card.
transmission paths:
• A Master Panel (XLS60e Only) can also be connected either to a
EN54 The network does Superior Master or to a Graphics PC using the Port ‘B’ position on
! not provide the the base card.
required
• The XLS40e cannot be installed in a network or to a Graphics PC.
transmission path
integrity.

3.4.7.1 Local Panel Network


• The XLS50e and XLS60e Fire Alarm Control Panels can be
EN54-2 12.5 connected in a network of panels either with other XLS60e panels
EN54 or with XLS50e panels.
! Integrity of
transmission paths: • The panels can be connected in two types of configuration. These
The network does are, a Shared Zone Network in which panels share common zones
not provide the and function as one system, a Report and Control Network in which
required individual panels or subsystems are networked for reporting and
transmission path control purposes only.
integrity. • A panel network requires the installation of an Isolated RS485
Interface card in each panel, using Port ‘C’ interface position.
• For detailed information on networking and wiring installation for a
panel network, refer to document P/N 996-089.

3.4.7.2 Master Panel to Superior Master Panel


EN54-2 12.5 • The network can be further extended, by connecting Network
EN54
Integrity of Master Panels to a Superior Master Panel (XLS60e Only).
!
transmission paths: • The network master panels are connected via an Isolated RS485
The network does Interface Card in Port ‘B’ position to the Superior Master panel
not provide the containing an Isolated RS485 Interface Card in Port ‘C’ position.
required • For detailed information on networking and wiring installation for a
transmission path panel network, refer to document P/N 996-089.
integrity.

3.4.7.3 Panel to Graphics PC


• A Network Master panel or a Superior Master Panel may be
EN54-2 12.5 connected to a Graphics PC for additional reporting and control
EN54 purposes (XLS60e Only).
! Integrity of
transmission paths: • The Graphics PC interface requires the installation of either an
The network does Isolated RS232 interface or an Isolated RS485 interface card using
not provide the Port ‘B’ position.
required • The XLS50e panel may be connected to a Graphics PC but may
transmission path then not be connected in a network of panels.
integrity. • For detailed information on connecting and using a Graphics PC,
refer to documents P/N 996-046 and 996-047.

Page 24 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.4.8 Peripheral Loop


• The XLS40e, XLS50e and XLS60e Fire Alarm Control Panels can
EN54-2 12.5 be connected to a range of serial interface devices connected to
EN54 the panel via the peripheral loop.
! Integrity of
transmission paths: • The peripheral loop interface uses Port D position on the base
The network does card.
not provide the • A peripheral loop requires the installation of an Isolated RS485
required Interface card in the panel.
transmission path • The RS485 peripheral communications link should be installed in a
integrity. ‘daisy chain’ or ‘loop’ type wiring arrangement. For further details,
refer to the Installation Guide supplied with the RS485 Interface
Card.
• Each supervised peripheral device must be given an address. The
address can be in the range 1 – 126. Refer to the Installation Guide
for each peripheral type for details on the allowed address range.
• The maximum number of physical devices that can be connected
to the peripheral loop is 31.

Part Number Device Description Supervised


709-011 XLS60/FR Active Remote Annunciator (Repeater) YES
709-111 XLS60/BR Passive Remote Annunciator (Repeater) NO
795-015 EXP-015 4-Way Sounder Module YES
795-065 EXP-065 40-Way Remote Mimic (LED Driver) YES
795-015 EXP-014 4-Way Relay Module YES
795-029 EXP-029 8-Way Input Module YES
795-057-001 XLS60/MBUS Modbus Interface YES

Table 3 – List of Compatible Peripheral Devices

Installation Manual Document No. 996-131-001, Revision: 01, Page 25 of 46


XLS40/50/60e Fire Alarm Control Panels

3.4.9 RS485 Wiring Arrangements


EN54-2 12.5
EN54
! Integrity of
• The following diagrams show the wiring arrangements for ‘daisy
transmission paths:
chain’ and ‘loop’ installations of the panel network and peripheral
The network does data bus interfaces.
not provide the • Refer to Section 3.4.13 for a list of recommended cables.
required
transmission path
integrity.

3.4.9.1 Daisy Chain Style Installation


• Form the peripheral or panel
RS485 link by taking wires from
EOL EOL
the A and B terminals at one side
of the interface board connector to
the A and B terminals of the next
device on the link.
• Continue wiring to all the units to
be connected to the link –
connecting A to A and B to B.
• Install EOL (150Ω, 0.5W minimum,
P/N 170-073-151) resistors in the BABA
spare terminals in both the first
and last units on the link. Figure 21 – Typical RS485 – ‘Daisy Chain’ Wiring
• The maximum allowed length of
the link is 1.2km (4000’).

3.4.9.2 Loop Style Installation


• Form the peripheral or panel RS485 link
by taking wires from the A and B
terminals at one side of the interface
board connector to the A and B
terminals of the next device on the link.
• Continue wiring to all the units to be
connected to the link – connecting A to
A and B to B. BABA

• Install return wiring from the spare


terminals on the last unit to the spare
terminals on the first unit. Figure 22 – Typical RS485 – ‘Loop’ Wiring
• The maximum allowed length of the
complete loop is 1.2km (4000’).

3.4.9.3 EMC Compliance


For EMC Compliance, fit the
Ferrite Absorber supplied with
the RS485 Interface board
around the Peripheral (or Connect Earth
drain wire of
Absorber

Panel) Link cables. cable to gland


earth

The figure opposite shows the


typical arrangement for a Afiix cable tie
around wires

typical installation. below ferrite

Figure 23 – RS485 Loop – EMC Absorber Installation

Page 26 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.4.9.4 Cable Screen – Earth Connections


• During installation of a panel
network the consequences of
connecting remote grounds
together must be considered.
• When wiring between RS485
cards and/or peripherals if a
drain earth wire is available it Connect Earth
drain wire of
should not be bonded to the cable to gland
earth
chassis at both ends of the Capacitor
link. Absorber

• The drain earth wire should


only be bonded to one of the
panel chassis at the cable
gland. The other end should
not be bonded directly to the Figure 24 – RS485 Screen – Earth Arrangement
chassis but should be
connected through a non-
polarised 2.2uFcapacitor.
This is shown opposite.

3.4.10 High Integrity Loop


• Hi485 Interface Modules can be used to create a ‘High Integrity’ RS485 Communications Loop for use on
the Panel Network and Peripheral interface links.
• The ‘High Integrity’ Loop provides open and short circuit protection to ensure that information can still be
passed around the loop if a single fault occurs. The loop can be extended to provide a communications
network of up to 12km (39000’) in distance.
• Refer to the Hi485 Installation Guide (996-065) for further information.

3.4.11 Group Disable Input


• The panel can be configured for an input device (loop call point / switch monitor or peripheral input) to act
as a group-disable function. Refer to the commissioning manual for programming information.

EN54-2 • The operation of a “Group Disable” input MUST be restricted to


EN54
Level 2 access only. Install accordingly using a key switch to
! Group Disable activate.

3.4.12 Class Change Input


• A call point / switch monitor unit or peripheral input can be configured to activate as a class change input
(refer to commissioning manual for programming information).

EN54-2 • The operation of a “Class Change” input MUST be restricted to


EN54 Level 2 access only. Install accordingly using a key switch to
! Class Change activate or locate in a restricted area.
Input

Installation Manual Document No. 996-131-001, Revision: 01, Page 27 of 46


XLS40/50/60e Fire Alarm Control Panels

3.4.13 Recommended Cables

All cables connected to the XLS40e, XLS50e or XLS60e Fire Alarm Control Panels should be
fire resistant cables. The drain earth wire, where available, should be connected to the earth
tag on the cable entry gland and to a suitable earth point at the remote end of the cable.

• Suitable cable types are listed below:


• Fire Rated Cables for Signalling Loops and Sounder Circuits
1. AEI type Firetec Multicore Ref. F1C1 (1mm2) to F1C2.5 (2.5mm2) in 2 core.
2. AEI type Firetec Armoured Ref. F2C1 (1.5mm2) to F2C2.5 (2.5mm2) in 2 core.
3. AEI type Mineral Insulated Cable (all types up to 2.5mm2).
4. BICC types Mineral Insulated twin twisted conductor cables, Ref. CCM2T1RG and CCM2T1.5RG.
5. BICC type Mineral Insulated Pyrotenax (all types up to 2.5mm2)
6. CALFLEX type Calflam CWZ 2 core type up to 2.5mm2 maximum.
7. PIRELLI type FP200 Gold 2 core type from 1mm2 to 2.5mm2
8. FIRETUF (OHLS) FTZ up to 2.5mm2. Manufactured by Draka
• Signal Cables for RS485 Communications Links (twisted pair)
9. 12 AWG Signal 88202 Belden 9583 WPW999
10. 14 AWG Signal 88402 Belden 9581 WPW995
11. 16 AWG Signal 88602 Belden 9575 WPW991
12. 18 AWG Signal 88802 Belden 9574 WPW975
13. FIRETUF FDZ1000 by Draka 2 core.
14. PIRELLI type FP200 Gold 2 core.

3.4.14 Base Card Power Supply Connections

• Panel upgrades and modifications may require the


removal of the base card from the panel enclosure.
• The correct wire connections to on the base card
are shown opposite. These are identical for the
XLS40e, XLS50e and XLS60e panels.

Grey Red
Blue Black
Orange

Figure 25 – Base Card Power Connections

Page 28 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.4.15 Cable Routing


• Cables should be routed within the enclosure in accordance with the following diagram. Ensure that
power-limited cables are routed separately from AC Mains and non power-limited cables.

RS485/RS232 SLC Circuits AC Mains


Power Limited Power Limited Input
Sounder and
AUX Power
Power Limited

XLS50e
Only
XLS50e
Only

Route cables
behind chassis

Use this knockout for


wiring to external battery
Relay Outputs box.
Not Power Limited

Figure 26 – Recommended Cable Routing Arrangement – XLS40e / XLS50e

AC MAINS RS485 / RS232 SLC Circuits


Power-Limited Power-Limited

Sounder and
AUX Power
Power-Limited

Relay Outputs
Non Power-Limited

Use this knockout for


wiring to external battery
box.

Figure 27 – Recommended Cable Routing Arrangement – XLS60e

Installation Manual Document No. 996-131-001, Revision: 01, Page 29 of 46


XLS40/50/60e Fire Alarm Control Panels

3.5 Installing Additional Equipment

3.5.1 General Introduction

Always ensure that the mains and battery power supplies have been isolated before
plugging or unplugging any of the internal circuit boards.

Follow the specific instructions supplied with each item of additional equipment.

At least one loop driver board MUST be installed for the unit to operate as a Fire Alarm
Control Panel.

• The following diagrams show the locations for installing additional equipment onto the base card.

3.5.1.1 XLS40e Arrangement

RS485
Interface
Card

Loop Driver
Module

Figure 28 – Positions for Additional Boards – XLS40e

Page 30 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.5.1.2 XLS50e Arrangement

RS485 RS485 or RS232


Interface Interface Card
Card

Loop Driver
Modules

Figure 29 – Positions for Additional Boards – XLS50e

3.5.1.3 XLS60e Arrangement

LOOP 5 LOOP 4 LOOP 3 LOOP 2 LOOP 1

Loop Driver
Modules

Port Port Port


D C B

Serial Interface
Cards
J1

J2
N/O N/C COM N/O N/C COM A- A+ B- B+ C- C+ D- D+ 0V 24V
TB10 TB7 TB8 TB9 TB6

Figure 30 – Positions for Additional Boards – XLS60e

Installation Manual Document No. 996-131-001, Revision: 01, Page 31 of 46


XLS40/50/60e Fire Alarm Control Panels

3.5.2 Loop Driver Cards


• Adding loop driver cards to the base unit expands the system. There are expansion slots for one loop
driver card in XLS40e, up to two loop driver cards in XLS50e (designated Loop 1 and Loop 2) and up to
five loop drivers in XLS60e (designated Loop 1 to Loop 5).
• Note that the first loop, designated ‘loop 1’ is situated at the top right hand side of the base card.
• Each card is secured with the four M3x6 screws supplied.

Check that both the 10-way and 4-way TOP


connectors are correctly aligned and
pushed fully home onto the pin headers. 4-way header

When removing a loop driver, the latch


Base Card
on the 4-way header must be pushed Loop Driver
away from the connector before
attempting to pull the connector out.

10-way
The XLS40e, XLS50e and XLS60e Fire header
Alarm Control Panels only support one
manufacturer loop type at a time.
DO NOT install loop drivers of different
types in the panel. Figure 31 – Mounting the Loop Driver

3.5.2.1 Voltage Selection


• The installation of each loop driver card requires the setting of a link or links to adjust the loop driver
power supply for compliance with the different manufacturers’ protocols.

3.5.2.1.1 XLS40e / XLS50e Jumper Settings


• The loop voltage for each loop driver type is selected using the jumper link J1. The following table defines
the position of J1 for each loop driver.

Loop Driver J1 Position


Honeywell B
System Sensor B
Apollo A
Hochiki A
Nittan B

Table 4 – Jumper Setting for Loop Voltage

Ensure that the Jumper setting is in the correct position for the installed loop driver
module before applying any power to the panel.

Page 32 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.5.2.1.2 XLS60e Jumper Settings


• The loop voltage for each loop driver type is selected using the jumper links J1 and J2. The following table
defines the position of J1 for each loop driver.

Loop Driver J1 Position J2 Position


Honeywell Open Linked
System Sensor Open Linked
Apollo Linked Open
Hochiki Linked Open
Nittan Open Linked

Table 5 – Jumper Setting for Loop Voltage

Ensure that the Jumper setting is in the correct position for the installed loop driver
module before applying any power to the panel.

3.5.3 485 / 232 Interface Cards

• The system can be expanded to provide a data interface between


EN54-2 12.5 the panel and control centres, peripheral devices, repeaters and
EN54 annunciators and to network with other panels.
! Integrity of
transmission paths: • The XLS40e base card is provided with one serial port (port D) to
Use of these which an isolated RS485 serial interface card can be fitted.
interface cards will • The XLS50e base card is provided with two serial ports (labelled C
not give the and D) to which isolated RS485 and RS232 serial interface cards
required can be fitted.
transmission path • The XLS60e base card is provided with three serial ports B, C and
integrity. D (labelled PL2, PL3 and PL4) to which isolated RS485 and RS232
serial interface cards can be fitted.
• Port D supports up to 31 peripheral devices on an RS485
communications bus. These devices can be active XLS60/FR or
passive ZXR4B remote annunciators (repeaters), 4-way sounder
modules, 4-way relay modules, 8-way input modules, 40-way Event
Mimic (LED driver) modules and Hi485 modules.
• Port C supports a panel network connection using an RS485
communications bus or a panel to graphic PC data link using either
an RS232 or an RS485 communications link.
• Port B (XLS60e Only) supports a network connection to a superior
master panel using an RS485 communications bus or a panel to
graphic PC data link using either an RS232 or an RS485
communications link.

Installation Manual Document No. 996-131-001, Revision: 01, Page 33 of 46


XLS40/50/60e Fire Alarm Control Panels

3.5.3.1 Mounting the card directly to the base


card TOP

• Use either the four fixing screws (M3 x 6mm) or the four 4-way
nylon spacers (M3 x 30mm), supplied with the module, connector
to mount the card onto the nylon spacers on the base
card.
Base Card
• Plug the 8-way ribbon cable connector into the 8-way RS485/232
socket (S-PORT-D on XLS40e, S-PORT-C and S- Interface Module
PORT-D on XLS50e, PL2, PL3, PL4 on XLS60e) on the
base card. Ensure the connector is fully inserted and
that there is no misalignment. 10-way
connector
Ensure that the 8-way ribbon cable
connector IS NOT inserted into the 10- 8-way
way connector on the XLS60e base connector
card. Figure 32 – Mounting the RS485 / RS232
Module

3.5.3.2 Mounting the card above the Loop Driver TOP


Module Loop
Driver 4-way
• The three serial interfaces may require to be installed on Module connector
top of the loop driver boards (loops 3 – 5) in the XLS60e
panel.
Base Card
• Use the four nylon spacers (M3 x 30mm), supplied with
RS485/232
the RS485 module, to mount the loop driver card to the Interface
base card. Module

• Use the four fixing screws (M3 x 6mm), supplied with


the module, to mount the RS485 card onto the nylon 10-way
spacers on the loop driver card. connector

• Plug the 10-way and 4-way ribbon cable connectors of 8-way


connector
the loop driver card into the appropriate sockets on the
base card.
Figure 33 – Mounting the RS485 / RS232
• Plug the 8-way ribbon cable connector from the Module
interface card into the 8-way socket (PL2, PL3, or PL4)
on the base card. Ensure the connector is fully inserted
and that there is no misalignment.

Page 34 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

3.5.4 Printer Module (XLS60e Only)


• The printer module is mounted to the 11 way
reverse of the front panel door on the ribbon
cable Printer Interface
printer mounting plate. Card
• Working from the rear of the panel Control 12mm Nylon spacers
mounting plate, carefully cut a slot in Panel Door
the front panel label using the slot in M3 x 20mm with
nylock nuts
the metal plate as a guide. Remove
any sharp edges around the Printer
periphery of the slot. Affix the self- Mechanism
adhesive tear-off guide, centrally over
the slot, to the front of the panel. Printer
Bracket
• Screw down two of the supplied M3
nuts on to the metals studs on the
printer mounting plate to act as Door panel
spacers. stud

• Mount the printer assembly to the


metal studs and secure in position with the remaining two M3 nuts, spring and plain washers. Ensure that
the paper feeds through the slot.
• Connect the supplied 4-way ribbon cable between the printer driver board and the connector on the CPU
Board. Fasten down the cable along the inner lid using tie-wraps and adhesive bases.
• Connect the transformer 8-volt secondary winding leads to the 2-way connector on the printer driver
board. Fasten the leads to the chassis using cable ties and adhesive bases.
• After re-applying power, press the ‘FEED’ button on the printer assembly and ensure that the printer
correctly feeds paper and the paper does not jam in the exit slot.

Installation Manual Document No. 996-131-001, Revision: 01, Page 35 of 46


XLS40/50/60e Fire Alarm Control Panels

4 Standby Battery Calculations


Quiescent Condition Alarm Condition
A B
Item Qty Each Unit Total (A) Each Unit Total (A)
(Units x Qty) (Units x Qty)
XLS50e Panel 1 0.090 0.090 0.250 0.250
RS485 Module (EXP-004) 0.059 0.059

RS485 Module (EXP-004B) 0.025 0.025

RS232 Module (EXP-005) 0.059 0.059

Zone LED Expander (EXP-077-020 0r 0.014 0.014 + 0.0005 per


EXP-077-060) LED lit

Loop Driver Modules


System Sensor (EXP-068) 0.020 0.020

Apollo (EXP-066) 0.040 0.040

Hochiki (EXP-058-V5) 0.042 0.042

Nittan (EXP-044) 0.030 0.030

Peripheral Units (Maximum 0.340 Amps total auxiliary 24V (Maximum 0.340 Amps total auxiliary 24V
DC supply) 4 DC supply) 4

XLS60/FR 0.1252 0.1503

XLS60/BR 0.1252 0.1503

4-Way Relay (EXP-014) 0.0802 0.1603


2
8-Way Input (EXP-029) 0.065 0.0652

4-way sounder (EXP-015) 0.1202 0.2203

40-way Event / Mimic LED (EXP-065) 0.0302 0.2803


2
Hi485 (EXP-038) or (EXP-038B) 0.125 / 0.040 0.125 / 0.0402
1
Sensor Current

Sounder A Load

Sounder B Load

Other devices connected to the system but not listed above.

Total A Total B
Standby Period Total A x 24 = Alarm Period Total B x 0.5 =

Total C Total D
Battery Ah ( C + D ) x 1.2 =
Table 6 – Current Rating Chart – XLS40e / XLS50e
1: Refer to Section –4.1 below.
2: Typical Quiescent currents quoted. Refer to data sheet for supply current range in all conditions.
3: Maximum Alarm Load quoted. Refer to data sheet for supply current range in all conditions.
4: Ensure total load of peripherals under all alarm and operating or fault conditions does not exceed maximum rating quoted.

Page 36 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

Quiescent Condition Alarm Condition


A B
Item Qty Each Unit Total (A) Each Unit Total (A)
(Units x Qty) (Units x Qty)
XLS60e Panel 1 0.225 0.225 0.375 0.375
RS485 Module (EXP-004) 0.059 0.059

RS485 Module (EXP-004B) 0.025 0.025

RS232 Module (EXP-005) 0.059 0.059

Zone LED Expander (EXP-077-020 0r 0.014 0.014 + 0.0005 per


EXP-077-060) LED lit

Loop Driver Modules


System Sensor (EXP-068) 0.020 0.020

Apollo (EXP-066) 0.040 0.040

Hochiki (EXP-058-V5) 0.042 0.042

Nittan (EXP-044) 0.030 0.030

Peripheral Units (Maximum 0.340 Amps total auxiliary 24V (Maximum 0.340 Amps total auxiliary 24V
DC supply) 4 DC supply) 4

XLS60/FR 0.1252 0.1503

XLS60/BR 0.1252 0.1503

4-Way Relay (EXP-014) 0.0802 0.1603


2
8-Way Input (EXP-029) 0.065 0.0652

4-way sounder (EXP-015) 0.1202 0.2203

40-way Event / Mimic LED (EXP-065) 0.0302 0.2803


2
Hi485 (EXP-038) or (EXP-038B) 0.125 / 0.040 0.125 / 0.0402
1
Sensor Current

Sounder A Load

Sounder B Load

Sounder C Load

Sounder D Load

Other devices connected to the system but not listed above.

Total A Total B
Standby Period Total A x 24 = Alarm Period Total B x 0.5 =

Total C Total D
Battery Ah ( C + D ) x 1.2 =
Table 7 – Current Rating Chart - XLS60e
1: Refer to Section –4.1 below.
2: Typical Quiescent currents quoted. Refer to data sheet for supply current range in all conditions.
3: Maximum Alarm Load quoted. Refer to data sheet for supply current range in all conditions.
4: Ensure total load of peripherals under all alarm and operating or fault conditions does not exceed maximum rating quoted.

Installation Manual Document No. 996-131-001, Revision: 01, Page 37 of 46


XLS40/50/60e Fire Alarm Control Panels

• The XLS60e Fire Alarm Control Panel supervises and charges the two 12-volt batteries that make up the
standby power source. Batteries are available commercially and should be of the sealed lead acid type.
Suggested suppliers for the Batteries are Yuasa and Powersonic.
• Use the current rating chart, along with the following formulae, to determine the size of the batteries to
satisfy the specific installation conditions.
• Batteries with capacity greater than 24Ah should be installed in a separate enclosure that is suitable for
Fire Protection Use such as Battery Box – 797-025-001, with wiring connected to the panel through
conduit.

4.1 Sensor Current Calculations

4.1.1 Quiescent Load


• Refer to the manufacturers’ published data sheets for the supply current required by each sensor type in
normal mode. Take into account the figures quoted for whether the detector LED flashes when the
signalling device is addressed – refer to the Commissioning manual for details of the Setup parameter to
turn this blinking on / off.
• Calculate the total current required by the sensors connected to all signalling loops. This should be based
on the quantity of each device installed and the supply current required for the device.

4.1.2 Alarm Load


• Refer to the manufacturers’ published data sheets for the supply current required by each sensor type.
• Calculate the total current required by the sensors connected to all signalling loops. This should be based
on the quantity of each device installed and the supply current required for the device as above.
• When a fire alarm condition is registered, the panel will turn on the sensor LED indicators for the first four
sensors that register an alarm. Refer to the manufacturers’ data sheet for the current supply required for
these LED indicators.
• Calculate the total current required by any loop driven sounders or output modules active in alarm
conditions. NOTE: The LED of all activated System Sensor output modules will be turned ON.

4.1.3 Adjustment Factors


• The figures calculated for sensor current, above, should be multiplied by the following adjustment factors
before being used in the Current Rating Chart.
1. For Apollo and Hochiki devices: multiply by 1.5
2. For Honeywell, System Sensor and Nittan devices: multiply by 1.25

4.2 Local Systems Ampere Hour Calculation


• Use the following formula to calculate the size of
batteries required for the installation. C = Total A * 24 hours
• These installations require a standby period of 24 hours D = Total B * 0.5 hours
plus thirty minutes of alarm operation at the end of the
standby period. Battery Ah = 1.2 * (C + D)

Page 38 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

5 Maintenance
5.1 Maintenance Schedule
• The following Maintenance routine as recommended in EN54-14 should be adopted.

5.1.1 Daily Attention


• The user should check the following:
1. The panel should indicate normal operation & if not the fault should be recorded in a logbook &
reported to the servicing organization.
2. Any faults previously reported have received attention.

5.1.2 Monthly Attention


• The user should check the following:
1. Any stand-by generators should be started and fuel levels checked.
2. At least one call point or detector (from different zones each month) should be operated to test the
fire panel and any connected alarm/ warning devices.
3. Where permissible, any link to the fire brigade or remote manned centre should be operated.
• Any faults should be recorded in the log book & corrective action taken as soon as possible.

5.1.3 Quarterly Attention


• The service organization should arrange to test the following:
1. Check entries in the logbook & inspect the panel’s log, taking appropriate remedial action where
necessary.
2. Examine all battery connections.
3. Check the alarm, fault and ancillary functions of the control and indicating equipment.
4. Visually inspect the control and indicating equipment for any moisture ingress or other
deterioration.
5. Enquire if any structural alterations have been made which could affect the operation of call points,
detectors or sounders, if so carry out a visual inspection.
• Any defects should be recorded in the logbook and corrective action taken as soon as possible.

5.1.4 Yearly Attention


• The service organization should arrange to test the following:
1. Carry out the test & inspection routines recommended daily, monthly & quarterly.
2. “Walk Test” the system and check that each detector operates in accordance with the
manufacturers recommendations.
3. Visually inspect all cable fittings and ensure equipment is secure, undamaged and adequately
protected.
4. Examine and test all batteries NB: Note the expected operating life shown in section E.
• Any defects should be recorded in the logbook and corrective action taken as soon as possible.

Installation Manual Document No. 996-131-001, Revision: 01, Page 39 of 46


XLS40/50/60e Fire Alarm Control Panels

5.2 Replacement of Components


• All components used in the control panel have been chosen for high reliability and long life. The
manufacturers’ data on the following items indicates that they may have a life expectancy of less than 15
years and so may need to be replaced in the future.

5.2.1 Lithium Standby battery

CAUTION: A Lithium Battery is used for Data Retention.


Replace only with the same or equivalent type. Contact the Service Organisation for
Replacement CPU Card.

Manufactures expected life - In excess of 10 Years

Recommended replacement - 10 years for panels in continuous service. 4 years for CPU cards
held as spares and not powered up.

5.2.2 Liquid Crystal Alphanumeric Display

Manufactures expected life - In excess of 10 Years.

Recommended replacement - When the display becomes difficult to read.

• The LED backlit liquid crystal display gives a life that is significantly better than most other display
technologies. The contrast of the LCD will gradually deteriorate as this part ages. This item can therefore
be changed when normal contrast starts to fade.

5.2.3 Standby Batteries

Manufacturers expected life - 3-5 years at an ambient temperature of 20 Celsius, NB life decreases
approximately 50% for every 10° Celsius increase in temperature.

Recommended service - Contact Battery manufacturer / supplier

Recommended Suppliers - Yuasa


Types - 7AH Model#: NP7-12
- 12AH Model#: NP12-12
- 17AH Model#: NP18-12
- 24AH Model#: NP24-12B

Before installation.
New Batteries require ‘top charging’ prior to being put into service.
Yuasa recommend top charging at 28.8V DC for 15 – 20 hours for batteries up to 6 months
old from data of manufacture.

It is normal for lead-acid type batteries to discharge hydrogen whilst being charged. The
panel is adequately ventilated to dissipate this hydrogen.
DO NOT seal the panel enclosure or mount the panel in a sealed enclosure or cavity.

Dispose of batteries in a responsible manner and in accordance with any local


regulations.

Page 40 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

6 Specifications
6.1 Functional Specifications

Specification Item Values


Enclosure 400mm wide, 400mm high, 135 mm deep
Sealed to IP30.

Weight 10 kg without batteries.


18.5 kg with 12AHr batteries fitted.
Operating Temperature 0°C to +40°C
Relative Humidity 85% (non-condensing)
Knockouts (20mm) 14 (Top), 2 (Bottom)
Sounder (NAC) Output 2 programmable outputs.
Open and short circuit monitored.
6K8, EOL resistors (P/N 170-073-682).
1A maximum output current.
Minimum switched current – 1mA
Auxiliary Relay 2 programmable volt-free, changeover outputs.
Contacts rated at 24V AC/DC, 1 Ampere, 0.6PF
maximum.
Minimum switched load – 1mA @ 5V
Sensor Circuit XLS40e – 1 plug-in loop driver module per panel.
XLS50e – 1 to 2 plug-in loop driver modules per panel.
Supports Analogue Addressable devices over a 2 wire
combined power and digital data transmission loop.
Loop Output Voltage and Signalling depends on the
loop driver installed – refer to documentation supplied
with the loop driver.
Maximum Loop Loading is 0.5A for all loops.
Monitoring zones Up to 20 zones with individual LED indicators.
Maximum 120 zones – up to 100 software zones (no
LED indicators).

Table 8 – XLS40e / XLS50e Functional Specifications

Installation Manual Document No. 996-131-001, Revision: 01, Page 41 of 46


XLS40/50/60e Fire Alarm Control Panels

Specification Item Values


Enclosure 500mm wide, 500mm high, 180 mm deep.
Sealed to IP30
Weight 19 kg without batteries
38.2 kg with 25AHr batteries fitted
Operating Temperature 0°C to +40°C
Relative Humidity 85% (non-condensing)
Knockouts (20mm) 24 (Top), 24 (Bottom)
Sounder Output 4 programmable outputs
Open and short circuit monitored.
6K8, EOL resistors (P/N 170-073-682).
1A maximum output current.
Minimum switched current – 1mA
Auxilliary Relay 2 programmable volt free changeover outputs
Contacts rated at 30V AC/DC, 1 Ampere maximum
Minimum switched load – 1mA @ 5V
Sensor Circuit 1 to 5 plug-in loop driver modules per panel
Supports Analogue Addressable devices over a 2 wire
combined power and digital data transmission loop.
Loop Output Voltage and Signalling depends on the
loop driver installed – refer to documentation supplied
with the loop driver.
Maximum Loop Loading is 1.25A for all loops.
Monitoring zones Up to 20 zones with individual LED indicators,
expandable to 40 / 80 zones with optional LED indicator
boards.
Maximum 120 zones – up to 40 software zones (no LED
indicators).

Table 9 – XLS60e Functional Specifications

Page 42 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

6.2 Power Supply and Charger

Specification Item Values


Operating Voltage 230V 50Hz AC
(or 120V 60Hz AC1)
Voltage tolerance + 10% - 15%
Incoming mains fuse F1 2A 20mm HRC anti-surge fuse in AC Mains TB
Power supply card input 24V & 7V AC from integral mains transformer
Power supply card fuses FS1 3.15A 20 mm HRC anti-surge
FS2 1.6A 20 mm HRC anti-surge
FS3 5A 20 mm HRC anti-surge
Max. Power supply output 2.7 Amps total maximum, comprising
(short term 10 min. rating) 0.7A temperature compensated lead acid battery charger
2A external load including the control panels quiescent current
(i.e. sounder current + aux. supply current + loop current)
Continuous Power supply 2.5 Amps total, comprising
Output Rating
0.7A battery charging
0.5A Internal circuit boards (2x485 cards + 2x loop driver
cards)
1.3A external load2
D. C. Output Voltage 26.5V Maximum & 19.5V Minimum3
Max. Ripple Voltage 1.7V peak-peak @ Maximum Output loading
Battery Charger Output 27.4 V nom at 20°C (temperature compensated)
Quiescent current 90mA. + Loop driver / option card current + external circuits
Alarm current 250mA. + Loop driver / option card current + external circuits
4
Standby Batteries 24V sealed lead acid
Minimum Capacity - 6 Ah (Internally Fitted)
Maximum Capacity - 12 Ah (Internally Fitted)
Maximum Capacity - 17 Ah (Externally Fitted)

Table 10 – XLS40e / XLS50e Power Supply and Charger Specifications

1
With appropriate transformer fitted.
2
If loop sounders are used, the maximum output from the two loop driver cards will be 400mA maximum. This will have to
be deducted from the 1.3A external load.
3
At V battery = 21V and mains supply disconnected.
4
Refer to Section 5.2.3 for a list of recommended batteries and suppliers.

Installation Manual Document No. 996-131-001, Revision: 01, Page 43 of 46


XLS40/50/60e Fire Alarm Control Panels

Specification Item Values


Operating Voltage 230V 50Hz AC
(or 120V 60Hz AC1)
Voltage tolerance + 10% - 15%
Incoming mains fuse FS1 3.15A 20mm HRC anti-surge fuse - Chassis mounted
Power supply card input 24V AC from integral mains transformer
Power supply card fuses F1 5A 20mm HRC anti-surge fuse
F2 5A 20 mm HRC anti-surge
Max. Power supply output 3.75 Amps total maximum, comprising
(Short term 10 min. rating) 1.00 Amps temperature compensated lead acid battery
charger
0.75 Amps internal circuitry
2.00 A external load including the control panels quiescent
current (i.e. sounder current + aux. supply current + loop
current)
Continuous Power supply 3.25 Amps total, comprising
Output Rating
1.00 Amps battery charging
0.75 Amps Internal circuit
1.50 Amps external load2
D. C. Output Voltage 25.5V Max & 20V Min3
Maximum Ripple Voltage 1.9V peak-peak.
Battery Charger Output 27.4 V nom at 20°C (temperature compensated)
Quiescent current 225mA + loop driver / option card current + external circuits
Alarm current 375mA + loop driver / option card current + external circuits
4
Standby Batteries 24V sealed lead acid
Maximum Capacity - 25 Ah
Minimum Capacity - 12 Ah
Printer Supply 8V AC from integral mains transformer for optional panel
mounted printer

Table 11 – XLS60e Power Supply and Charger Specifications

1
With appropriate transformer fitted.
2
If loop sounders are used, the maximum output from the five loop driver cards will be 1000mA maximum. This will have to
be deducted from the 1.5A external load.
3
Output = Battery voltage – 1.0 volts under AC Mains power failure conditions.
4
Refer to Section 5.2.3 for a list of recommended batteries and suppliers.

Page 44 of 46 Document No. 996-131-001, Revision: 01, Installation Manual


XLS40/50/60e Fire Alarm Control Panels

NOTES

Installation Manual Document No. 996-131-001, Revision: 01, Page 45 of 46


XLS40/50/60e Fire Alarm Control Panels

EUROPEAN FIRE GROUP


BRACKNELL, UK
S Y S T E M TEL. 01344 655084/655265
FAX. 01344 655085

© MORLEY-IAS. All rights reserved.

Page 46 of 46 Document No. 996-131-001, Revision: 01, Installation Manual

You might also like