Nothing Special   »   [go: up one dir, main page]

AP Specs 2008

Download as pdf or txt
Download as pdf or txt
You are on page 1of 39

GUIDE

SPECIFICATIONS
AQUARIUS II
AP Series Two Stage R-410A
GENERAL
Units shall be performance certified to ISO standard the fan motor.The fan motor shall be an ECM-2 microprocessor controlled
13256-1 for Water Loop Heat Pump, Ground Water Heat Pump and Ground DC type motor with internal programming factory set for the specific unit
Loop Heat Pump applications. Units shall be Underwriter Laboratories and featuring soft start/stop and a delay off feature for maximum effi-
(UL and ULc) listed for safety on all models. Each unit shall be run tested ciency and quiet operation. Air flow rates shall be varied according to the
at the factory. Each unit shall be pallet mounted and stretch wrapped. staging of the unit. There will further be provisions for adjusting the air
The units shall be manufactured in an ISO9001:2000 certified facil- delivery of the motor and blower by +/- 15% from rated air flow.
ity. ELECTRICAL
Controls and safety devices will be factory wired and mounted within the
The units shall be warranted by the manufacturer against
unit. Controls shall include comfort alert module, compressor contactor,
defects in materials and workmanship for a period of i) in the case of
residentially sold units having the last digit of the serial number as a 'T'; 24V transformer, reversing valve coil and solid state lock-out controller
five years on all parts and 10 years on the refrigerant circuit components (UPM). The UPM controller shall include the following features: diagnostic
ii) on all other units; five years on the compressor and one year on all LED's, low pressure bypass time delay (to prevent nuisance low pressure
other parts. lock-outs during operation with low fluid temperatures), anti short cycle
time delay, random start time delay and one time intelligent reset. When the
safety controls are activated the lock-out circuit shall reset itself the first
The units shall be designed to operate with entering fluid
temperatures between 50oF (10oC) and 110oF (43.3oC) in cooling and time. If the safety controls are subsequently activated within one hour,
temperatures between 20oF (-6.6oC) and 80oF (27oC) in heating as manu- then the lock-out circuit shall disable the compressor until it is reset at the
factured by FHP Manufacturing in Fort Lauderdale, Florida. thermostat or main circuit breaker to prevent compressor operation during
fault conditions. A lock-out indicating terminal shall be provided in the low
CASING & CABINET voltage circuit. Safety devices include a low pressure cutout set a 40
The cabinet shall be fabricated from heavy-gauge steel finished with a PSIG (280 kPa) for loss of charge protection (freezestat and/or high dis-
vinyl coated black cabinet and decorative gold anodized aluminum charge gas temperature sensor is not acceptable) and a high pressure
front panel for corrosion protection. The interior shall be insulated cutout control set at 600 PSIG (4100 kPa).
with ½” (12.7mm) thick foil faced glass fiber. All units shall allow sufficient The ECM motor interface board shall provide a screw type terminal block
service access to replace the compressor without unit removal. One for thermostat connection, LED's to indicate thermostat status and air
blower and two compressor compartment access panels shall be re- delivery. It shall also provide a means of changing the motor program to any
movable with supply and return ductwork in place. A duct collar shall be of up to four pre-programmed options. Direct wiring of the motor control
provided on the supply air opening. A filter rack with 2" (50.8 mm) thick harness to the thermostat is not acceptable.
disposable filters and a 1" (25.4mm) return air duct collar shall be pro- A terminal block with screw terminals shall be provided for control wiring.
vided with each unit. Air filters shall be MERV 11 rated. The units shall An optional condensate overflow device shall be factory
have an insulated divider panel between the air handling section and the installed to stop compressor operation if drain pan overflow is
compressor section to minimize the transmission of compressor noise, imminent. An optional energy management relay to allow unit control by an
and to permit service testing without air bypass. Units shall have a stain- external source shall be factory installed.
less steel condensate drain pan. The compressor shall have a floating PIPING
base pan to minimize noise transmissions.
Supply, return water and condensate drain connections shall be brass
REFRIGERATION CIRCUITS female pipe thread fittings and mounted flush to cabinet
All units shall contain a sealed refrigerant circuit including a two stage exterior.
scroll compressor, bi-directional thermal expansion valve INTERNAL ELECTRIC HEAT
metering device, finned tube air-to-refrigerant heat exchanger,
refrigerant reversing valve and service ports. Compressor shall be high 208/230-1-60 volt units shall be equipped with optional factory
efficiency two stage scroll type, designed for heat pump duty, quiet installed internal electric resistance heat for auxiliary and
operation and mounted on rubber vibration isolators. Compressor motors emergency heat. Electric heater must be Underwriter's Laboratories (UL
shall be equipped with overload protection. Refrigerant reversing valves and ULc) approved for safety when installed in the unit. External heater
shall be pilot operated sliding piston type with replaceable encapsulated packages or heater packages not specifically listed for use with the unit
magnetic coils energized only during the cooling cycle. The finned tube are unacceptable. Electric heater packages shall include a heater collar
coil shall be constructed of lanced aluminum fins not exceeding fourteen mounted to the blower outlet, individual thermal overload protected heater
fins per inch bonded to rifled copper tubes in a staggered pattern not less elements no greater than 5kW each and magnetic contactors. Heater
than three rows deep and have a 450 PSIG (3100 kPa) working pres- packages shall have a separate power supply connection from the
sure. Coils shall have a baked polyester enamel coating for protection compressor and this power supply shall also power the unit blower motor
against most airborne chemicals. Coil end plates shall be aluminum. and control transformer for safe operation.
The coaxial water-to-refrigerant heat exchanger shall be constructed of HEAT RECOVERY PACKAGE
a convoluted copper (optional cupronickel) inner tube and steel outer 208/230 volt units shall be equipped with an optional factory
tube with a designed refrigerant working pressure of 450 PSIG (3100 installed internal heat recovery kit for domestic hot water
kPa) and a designed water side working pressure of no less than 400 production. This kit shall include an internally protected pump, double
PSIG (2750 kPa). The water-to-refrigerant heat exchanger shall be insu- walled coaxial water-to-refrigerant heat exchanger, 140oF (60oC) hot wa-
lated to prevent condensation at low fluid temperatures. ter temperature limit switch and an on/off switch/circuit breaker.
FAN MOTOR & ASSEMBLY
The fan shall be direct drive centrifugal forward curved type with a
dynamically balanced wheel. The housing and wheel shall be designed
for quiet low velocity operation. The fan housing shall be removable from
the unit without disconnecting the supply air ductwork for servicing of
APSPECS.P65 REV: 1-08
FHP Manufacturing Co.
601 N.W. 65th Court
Fort Lauderdale, FL 33309
AP Two Sta
Stagge Series
Phone: (954) 776-5471
Fax: (800) 776-5529
http://www.fhp-mfg.com
Ver tical Dimensions
ertical
A B C D E F G H J K M N P Q Condenser Recommended
MODEL R/A Duct R/A Duct Filter Rack Water Replacement
Width Depth Height Flg Width Flg Height Height Connections Nominal Filter Size
AP025 21.50 26.00 47.25 13.75 15.75 6.13 5.25 5.25 8.00 16.25 22.00 22.00 24.00 4.00 3/4" F.P.T. 24 X 24 X 2
AP035 24.00 33.25 47.25 15.75 15.75 8.25 6.37 5.25 8.00 16.25 28.00 22.00 24.00 4.00 3/4" F.P.T. 24 X 30 X 2
AP049 26.00 33.25 51.25 17.75 17.75 8.50 7.25 3.25 10.25 17.25 28.00 30.00 32.00 4.00 1" F.P.T. 16 X 30 X 2 (2)
AP061 26.00 33.25 66.25 17.75 17.75 8.38 6.38 3.25 10.25 17.25 28.00 38.00 40.00 4.00 1" F.P.T. 20 X 30 X 2 (2)
AP071 26.00 33.25 66.25 17.75 17.75 8.38 6.38 3.25 10.25 19.50 28.00 38.00 40.00 4.00 1" F.P.T. 20 X 30 X 2 (2)

Heater
E Knock-out E
F D D F
G Q

Access M
Panel

P
HRP
N
C C
Condenser
Water Out

Condensate
Drain
Condenser
Water In
J K Electrical
Knock-outs

B A A B

H
Left Hand Right Hand
Return Return NOTES: All dimensions within +/- 0.125".
(FLT) (FRT) All condensate drain connections are 3/4" FPT.
All Heat Recovery Kit connections are 1/2" FPT.
Internal electric heat available on 208-230/1/60 top discharge units only
Internal Heat Recovery Kit available on 208-230 volt units only.
Specifications subject to change without notice.
APVTDGIP INT II.P65 REV: 1-08
FHP Manufacturing Co.
601 N.W. 65th Court
AP Two Sta
Stagge Series
Horizontal Dimensions
Fort Lauderdale, FL 33309
Phone: (954) 776-5471
Fax: (800) 776-5529
http://www.fhp-mfg.com
A B C D E F G H J K M N P Q R T Condenser Recommended
MODEL R/A Duct Filter Rack R/A Duct Water Replacement
Width Depth Height Flg Width Height Flg Height Connections Nom. Filter Size
AP025 26.00 54.50 22.00 2.00 30.00 22.50 5.25 16.25 4.50 13.75 3.00 15.75 4.50 3.00 20.00 18.00 3/4" F.P.T. 16 X 20 X 2 (2)
AP035 30.00 68.00 22.00 2.50 34.00 32.00 5.25 16.25 5.81 15.75 3.00 15.75 5.81 3.00 20.00 18.00 3/4" F.P.T. 18 X 20 X 2 (2)
AP049 30.00 68.00 22.00 2.50 34.00 32.00 5.25 19.25 7.66 17.75 2.00 17.75 7.66 2.00 20.00 18.00 1" F.P.T. 18 X 20 X 2 (2)
AP061 30.00 89.00 22.00 2.50 54.00 31.50 3.25 17.25 3.50 17.75 3.75 17.75 7.66 1.00 20.00 18.00 1" F.P.T. 20x28x2 (2)
AP071 30.00 89.00 22.00 2.50 54.00 31.50 3.25 19.50 3.50 17.75 3.75 17.75 7.66 1.00 20.00 18.00 1" F.P.T. 20x28x2 (2)

Left Hand Return


End Blow (FLE)
Left Hand Return
D Return Air Return Air
Straight Through (FLS)
Opening Opening

E
Access C M C Q
Panel Heater
Knock-out
F K K
J N N P
Condensate Condensate
Drain
Left Hand Electrical
Knock-outs
B
Drain
B
Return H A A
G
NOTES: All dimensions within +/- 0.125".
Return Air Return Air
D Opening Opening All condensate drain connections are 3/4" FPT.
E All Heat Recovery connections are 1/2" FPT.
Q Heater C M C Internal electric heat available on 208-230 volt
Knock-out
HRP
F K K units only
Condenser
Water In N J P Internal Loop Pump available on 208-230 volt
Condenser
N
Condensate Condensate
Water Out
Drain Drain
units only.
Access B B Internal Heat Recovery Kit available on 208-230
Panel
A A volt units only.
Units can be field converted between end blow
Right Hand Return Right Hand Return and straight through supply air configurations.
Right Hand End Blow (FRE) Straight Through (FRS) Specifications subject to change without
Return notice.

APHZDGIP.P65 REV: 1-08


FHP Manufacturing Co.
601 N.W. 65th Court
AP Two Sta
Stagge Series
Counterf lo
Counterflo
loww Dimensions
Fort Lauderdale, FL 33309
Phone: (954) 776-5471
Fax: (800) 776-5529
http://www.fhp-mfg.com

A B C D E F G H J K M N P Condenser Recommended
MODEL Blower Blower R/A Duct R/A Duct Filter Rack Water Replacement
Width Depth Height Opening Opening Flg Width Flg Height Height Connections Nominal Filter Size
AP025 21.50 26.00 47.25 9.25 10.25 8.38 5.00 7.50 18.50 10.25 22.00 22.00 24.00 3/4" F.P.T. 24 X 24 X 2
AP035 24.00 33.25 47.25 9.25 10.25 11.13 6.88 7.50 18.50 12.00 28.00 22.00 24.00 3/4" F.P.T. 24 X 30 X 2
AP049 26.00 33.25 51.25 10.50 11.50 10.63 5.00 7.00 20.25 10.50 28.00 30.00 32.00 1" F.P.T. 16 X 30 X 2 (2)
AP061 26.00 33.25 66.25 11.80 12.50 9.75 4.50 7.00 21.00 11.00 28.00 38.00 40.00 1" F.P.T. 20 X 30 X 2 (2)
AP071 26.00 33.25 66.25 12.25 13.50 9.75 4.50 7.00 23.25 11.00 28.00 38.00 40.00 1" F.P.T. 20 X 30 X 2 (2)

Condenser
H Water Out

HRP Compressor
Access Panel
Condenser
J Water In C
C
M
Electrical
Knock-outs

Heater
Knock-out P
Condensate N
Blower & Heater Drain
Access Panel

B A A B

F E E
D D F
G K

NOTES: All dimensions within +/- 0.125".


All condensate drain connections are 3/4" FPT.
All Heat Recovery Kit connections are 1/2" FPT.
Left Hand Right Hand Internal electric heat available on 208-230/1/60 bottom discharge units only
Return Return Internal Loop Pump available on 208-230 volt units only.
Internal Heat Recovery Kit available on 208-230 volt units only.
(FLB) (FRB)
APCFDGIP INT II.P65 REV: 1-08 Specifications subject to change without notice.
AP025
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 11.4 52.0 2.8 1/3 - - 18.8 30 Feet Deep O.D. Inch
3.5 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
9 x 7 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 290 lbs 315 lbs
+ 860 FLUID PRESSURE DROP
Norm 750 Fluid Pressure
- 640 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 750 CFM and 8.0 GPM 5.0 2.0 0.9
Water Loop Ground Water Ground Loop 7.0 3.6 1.6
Cooling Heating Cooling Heating Cooling Heating 9.0 5.7 2.5
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 11.0 8.2 3.5
20,000 19.3 23,000 6.5 22,500 32.5 19,500 5.5 22,000 27.8 16,600 4.7 13.0 11.0 4.8

CAPACITY DATA - PART LOAD


EFT Range (Standard) EFT Range (Standard)
COOLING All performance at 750 CFM and 8.0 GPM 50oF to 100oF HEATING 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 19.80 12.73 0.64 0.65 22.03 30.4 50 o 20.98 1.12 17.16 5.5
60 o 70odb 19.09 12.37 0.65 0.77 21.70 24.9 60 o 60 o 22.83 1.12 19.00 6.0
70 o 61 owb 18.37 12.05 0.66 0.88 21.38 20.9 70 o 24.69 1.13 20.83 6.4
85 o 17.30 11.65 0.67 1.05 20.89 16.4 80 o 26.55 1.14 22.67 6.8
100o 16.22 11.31 0.70 1.22 20.40 13.3 50 o 19.84 1.14 15.96 5.1
50 o 21.22 15.24 0.72 0.66 23.46 32.4 60 o 70 o 21.59 1.14 17.69 5.5
60 o 75odb 20.46 14.81 0.72 0.77 23.09 26.6 70 o 23.35 1.15 19.43 6.0
o
70 63 owb 19.69 14.43 0.73 0.89 22.71 22.2 80 o 25.10 1.16 21.16 6.4
85 o 18.54 13.95 0.75 1.06 22.15 17.5 50 o 18.50 1.16 14.54 4.7
100o 17.39 13.55 0.78 1.23 21.59 14.1 60 o 80 o 20.14 1.17 16.15 5.1
50 o 23.30 16.83 0.72 0.66 25.56 35.3 70 o 21.77 1.17 17.77 5.4
60 o 80odb 22.46 16.36 0.73 0.78 25.11 28.9 80 o 23.41 1.18 19.38 5.8
70 o 67 owb 21.62 15.95 0.74 0.89 24.67 24.2
Antifreeze Required
85 o
20.36 15.41 0.76 1.07 24.00 19.1 LOW TEMP HEATING
100o 19.10 14.97 0.78 1.24 23.33 15.4 25 o 16.01 1.10 12.25 4.3
50 o 25.38 18.44 0.73 0.66 27.65 38.2 30 o 60 o 16.92 1.11 13.15 4.5
60 o 85odb 24.47 17.93 0.73 0.78 27.14 31.3 40 o 18.74 1.11 14.95 4.9
70 o 71 owb 23.56 17.47 0.74 0.90 26.62 26.2 25 o 15.15 1.12 11.32 4.0
85 o 22.19 16.89 0.76 1.07 25.85 20.7 30 o 70 o 16.01 1.12 12.17 4.2
100o 20.82 16.41 0.79 1.25 25.08 16.7 40 o 17.73 1.13 13.87 4.6
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 14.13 1.15 10.22 3.6
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 14.93 1.15 11.02 3.8
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 16.54 1.15 12.60 4.2
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP025.1IP60 Rev: 1-08 http://www.fhp-mfg.com
AP025
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 11.4 52.0 2.8 1/3 - - 18.8 30 Feet Deep O.D. Inch
3.5 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
9 x 7 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 290 lbs 315 lbs
+ 1100 FLUID PRESSURE DROP
Norm 950 Fluid Pressure
- 800 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 950 CFM and 8.0 GPM 5.0 2.0 0.9
Water Loop Ground Water Ground Loop 7.0 3.6 1.6
Cooling Heating Cooling Heating Cooling Heating 9.0 5.7 2.5
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 11.0 8.2 3.5
27,000 16.2 32,500 5.3 31,000 25.1 26,500 4.8 28,500 19.2 20,400 4.1 13.0 11.0 4.8

CAPACITY DATA - FULL LOAD


EFT Range (Standard) EFT Range (Standard)
COOLING All performance at 950 CFM and 8.0 GPM 50oF to 100oF HEATING 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 27.31 18.01 0.66 1.19 31.36 23.0 50 o 28.16 1.71 22.32 4.8
60 o 70odb 26.05 17.32 0.67 1.34 30.62 19.5 60 o 60 o 31.67 1.81 25.49 5.1
70 o 61 owb 24.78 16.69 0.67 1.49 29.87 16.6 70 o 35.18 1.91 28.66 5.4
85 o 22.89 15.82 0.69 1.72 28.76 13.3 80 o 38.70 2.01 31.83 5.6
100o 21.00 15.02 0.72 1.95 27.65 10.8 50 o 26.63 1.74 20.69 4.5
50 o 29.26 21.55 0.74 1.19 33.34 24.5 60 o 70 o 29.95 1.84 23.66 4.8
60 o 75odb 27.91 20.73 0.74 1.35 32.51 20.7 70 o 33.27 1.95 26.63 5.0
70 o 63 owb 26.56 19.97 0.75 1.50 31.68 17.7 80 o 36.59 2.05 29.60 5.2
85 o 24.54 18.94 0.77 1.73 30.44 14.2 50 o 24.83 1.78 18.76 4.1
100o 22.51 17.98 0.80 1.96 29.20 11.5 60 o 80 o 27.92 1.88 21.50 4.3
50 o 32.13 23.80 0.74 1.20 36.23 26.7 70 o 31.02 1.99 24.23 4.6
60 o 80odb 30.65 22.89 0.75 1.36 35.28 22.6 80 o 34.11 2.09 26.97 4.8
o
70 67 owb 29.17 22.06 0.76 1.51 34.32 19.3
Antifreeze Required
85 o 26.95 20.92 0.78 1.74 32.90 15.5 LOW TEMP HEATING
100o 24.73 19.87 0.80 1.97 31.47 12.5 25 o 18.99 1.46 14.01 3.8
50 o 34.99 26.07 0.75 1.21 39.12 28.9 30 o 60 o 20.72 1.51 15.56 4.0
60 o 85odb 33.38 25.08 0.75 1.37 38.04 24.4 40 o 24.16 1.61 18.66 4.4
70 o 71 owb 31.77 24.17 0.76 1.52 36.97 20.9 25 o 17.97 1.48 12.90 3.5
85 o 29.36 22.92 0.78 1.76 35.35 16.7 30 o 70 o 19.60 1.54 14.35 3.7
100o 26.94 21.77 0.81 1.99 33.73 13.5 40 o 22.85 1.64 17.26 4.1
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 16.77 1.52 11.59 3.2
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 18.28 1.57 12.93 3.4
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 21.31 1.67 15.60 3.7
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP025.2IP60 Rev: 1-08 http://www.fhp-mfg.com
AP035
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 16.7 82.0 4.3 1/2 - - 27.0 40 Feet Deep O.D. Inch
4.5 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
9 x 7 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
290 lbs 315 lbs
+ 1000 FLUID PRESSURE DROP
Norm 900 Fluid Pressure
- 800 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1000 CFM and 9.0 GPM 5 2.0 0.9
Water Loop Ground Water Ground Loop 7 3.6 1.6
Cooling Heating Cooling Heating Cooling Heating 9 5.7 2.5
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 11 8.2 3.5
25,700 19.8 29,500 6.3 29,500 34.0 24,300 5.3 28,200 28.5 22,000 4.8 13 11.1 4.8

CAPACITY DATA - PART LOAD


EFT Range (Standard) EFT Range (Standard)
COOLING All performance at 1000 CFM and 9.0 GPM 50oF to 100oF HEATING 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 26.07 16.75 0.64 0.81 28.82 32.3 50 o 26.93 1.44 22.01 5.5
60 o 70odb 24.94 16.16 0.65 0.95 28.18 26.3 60 o 60 o 29.10 1.46 24.13 5.9
70 o 61 owb 23.82 15.62 0.66 1.09 27.55 21.8 70 o 31.28 1.47 26.26 6.2
85 o 22.13 14.90 0.67 1.31 26.59 16.9 80 o 33.46 1.49 28.38 6.6
100o 20.44 14.24 0.70 1.52 25.64 13.4 50 o 25.47 1.47 20.46 5.1
50 o 27.94 20.05 0.72 0.81 30.71 34.4 60 o 70 o 27.52 1.48 22.47 5.4
60 o 75odb 26.74 19.35 0.72 0.95 29.99 28.0 70 o 29.58 1.50 24.47 5.8
70 o 63 owb 25.53 18.71 0.73 1.10 29.28 23.2 80 o 31.64 1.51 26.48 6.1
85 o 23.73 17.85 0.75 1.31 28.21 18.1 50 o 23.75 1.50 18.64 4.6
100o 21.92 17.07 0.78 1.53 27.14 14.3 60 o 80 o 25.67 1.51 20.51 5.0
50 o 30.68 22.15 0.72 0.82 33.46 37.6 70 o 27.59 1.53 22.37 5.3
60 o 80odb 29.36 21.38 0.73 0.96 32.64 30.5 80 o 29.50 1.54 24.23 5.6
70 o 67 owb 28.04 20.67 0.74 1.11 31.81 25.3
Antifreeze Required
85 o 26.06 19.72 0.76 1.32 30.58 19.7 LOW TEMP HEATING
100o 24.08 18.86 0.78 1.54 29.34 15.6 25 o 21.06 1.40 16.27 4.4
50 o 33.42 24.28 0.73 0.82 36.22 40.6 30 o 60 o 22.13 1.41 17.31 4.6
60 o 85odb 31.98 23.43 0.73 0.97 35.29 33.0 40 o 24.26 1.43 19.39 5.0
70 o 71 owb 30.55 22.65 0.74 1.11 34.35 27.4 25 o 19.93 1.43 15.05 4.1
85 o 28.39 21.61 0.76 1.33 32.94 21.3 30 o 70 o 20.93 1.44 16.03 4.3
100o 26.24 20.67 0.79 1.55 31.54 16.9 40 o 22.95 1.45 18.00 4.6
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 18.59 1.46 13.62 3.7
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 19.53 1.47 14.53 3.9
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 21.41 1.48 16.35 4.2
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP035.1IP60 Rev: 1-08 http://www.fhp-mfg.com
AP035
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 16.7 82.0 4.3 1/2 - - 27.0 40 Feet Deep O.D. Inch
4.5 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
9 x 7 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 290 lbs 315 lbs
+ 1380 FLUID PRESSURE DROP
Norm 1200 Fluid Pressure
- 1020 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1200 CFM and 9.0 GPM 5 2.0 0.9
Water Loop Ground Water Ground Loop 7 3.6 1.6
Cooling Heating Cooling Heating Cooling Heating 9 5.7 2.5
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 11 8.2 3.5
36,600 16.0 43,000 5.1 41,200 23.5 36,200 4.7 38,200 18.4 28,200 4.1 13 11.1 4.8

CAPACITY DATA - FULL LOAD


EFT Range (Standard) EFT Range (Standard)
COOLING All performance at 1200 CFM and 9.0 GPM 50oF to 100oF HEATING 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 36.10 23.53 0.65 1.67 41.81 21.6 50 o 38.04 2.33 30.08 4.8
60 o 70odb 34.64 22.76 0.66 1.86 41.00 18.6 60 o 60 o 42.34 2.47 33.92 5.0
70 o 61 owb 33.18 22.08 0.67 2.05 40.19 16.2 70 o 46.64 2.60 37.75 5.2
85 o 30.99 21.16 0.68 2.34 38.97 13.3 80 o 50.93 2.74 41.59 5.5
100o 28.80 20.36 0.71 2.62 37.75 11.0 50 o 35.97 2.37 27.87 4.4
50 o 38.68 28.14 0.73 1.68 44.43 23.0 60 o 70 o 40.03 2.51 31.46 4.7
60 o 75odb 37.12 27.23 0.73 1.87 43.52 19.8 70 o 44.09 2.65 35.05 4.9
o
70 63 owb 35.56 26.41 0.74 2.06 42.61 17.2 80 o 48.16 2.79 38.64 5.1
85 o 33.22 25.33 0.76 2.35 41.24 14.1 50 o 33.55 2.42 25.27 4.1
100o 30.87 24.37 0.79 2.64 39.87 11.7 60 o 80 o 37.33 2.57 28.57 4.3
50 o 42.47 31.08 0.73 1.70 48.26 25.0 70 o 41.11 2.71 31.87 4.4
60 o 80odb 40.75 30.08 0.74 1.89 47.20 21.6 80 o 44.89 2.85 35.17 4.6
o
70 67 owb 39.04 29.17 0.75 2.08 46.14 18.8
Antifreeze Required
85 o 36.47 27.98 0.77 2.37 44.56 15.4 LOW TEMP HEATING
100o 33.91 26.92 0.79 2.66 42.97 12.8 25 o 26.76 1.99 19.96 3.9
50 o 46.25 34.05 0.74 1.71 52.08 27.1 30 o 60 o 28.87 2.06 21.83 4.1
60 o 85odb 44.39 32.95 0.74 1.90 50.88 23.3 40 o 33.08 2.20 25.58 4.4
70 o 71 owb 42.52 31.96 0.75 2.10 49.68 20.3 25 o 25.32 2.03 18.39 3.7
85 o 39.73 30.65 0.77 2.39 47.88 16.6 30 o 70 o 27.31 2.10 20.15 3.8
100o 36.94 29.49 0.80 2.68 46.08 13.8 40 o 31.29 2.24 23.66 4.1
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 23.62 2.07 16.55 3.3
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 25.47 2.14 18.16 3.5
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 29.18 2.28 21.39 3.7
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP035.2IP60 Rev: 1-08 http://www.fhp-mfg.com
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS
AP049
A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 21.2 96.0 6.8 3/4 - - 35.1 50 Feet Deep O.D. Inch
6 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
10x 8 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 318 lbs 348 lbs
+ 1490 FLUID PRESSURE DROP
Norm 1300 Fluid Pressure
- 110 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1300 CFM and 12.0 GPM 6.0 2.3 1.0
Water Loop Ground Water Ground Loop 7.0 3.0 1.3
Cooling Heating Cooling Heating Cooling Heating 9.5 5.3 2.3
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 12.0 8.0 3.5
37,000 20 38,500 5.9 41,200 32.5 31,500 5.0 40,200 28.0 28,000 4.6 16.0 13.4 5.8

CAPACITY DATA - PART LOAD


COOLING All performance at 1300 CFM and 12.0 GPM EFT Range (Standard)
50 F to 100 F o o HEATING EFT Range (Standard)
25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 37.65 28.42 0.75 1.17 41.65 32.1 50 o 36.30 1.93 29.72 5.5
60 o 70odb 36.39 27.70 0.76 1.37 41.06 26.6 60 o 60 o 39.48 1.97 32.75 5.9
70 o 61 owb 35.12 27.08 0.77 1.57 40.47 22.4 70 o 42.66 2.02 35.78 6.2
85 o 33.23 26.30 0.79 1.86 39.58 17.9 80 o 45.84 2.06 38.82 6.5
100o 31.34 25.67 0.82 2.15 38.69 14.6 50 o 34.33 1.96 27.64 5.1
50 o 40.35 33.98 0.84 1.18 44.37 34.2 60 o 70 o 37.34 2.01 30.49 5.5
60 o 75odb 39.00 33.12 0.85 1.38 43.69 28.3 70 o 40.34 2.05 33.35 5.8
70 o 63 owb 37.65 32.38 0.86 1.57 43.02 23.9 80 o 43.35 2.10 36.20 6.1
85 o 35.62 31.45 0.88 1.87 42.00 19.1 50 o 32.02 2.00 25.19 4.7
100o 33.59 30.71 0.91 2.16 40.98 15.5 60 o 80 o 34.82 2.05 27.83 5.0
50 o 44.30 37.52 0.85 1.19 48.35 37.3 70 o 37.62 2.09 30.47 5.3
60 o 80odb 42.81 36.57 0.85 1.39 47.55 30.9 80 o 40.42 2.14 33.11 5.5
70 o 67 owb 41.33 35.76 0.87 1.59 46.74 26.1
Antifreeze Required
85 o 39.11 34.73 0.89 1.88 45.54 20.8 LOW TEMP HEATING
100o 36.89 33.91 0.92 2.18 44.33 16.9 25 o 27.79 1.82 21.59 4.5
50 o 48.24 41.10 0.85 1.20 52.32 40.3 30 o 60 o 29.35 1.84 23.08 4.7
60 o 85odb 46.63 40.06 0.86 1.40 51.40 33.4 40 o 32.47 1.88 26.04 5.1
70 o 71 owb 45.02 39.16 0.87 1.60 50.47 28.2 25 o 26.29 1.85 19.99 4.2
85 o 42.60 38.05 0.89 1.90 49.08 22.5 30 o 70 o 27.77 1.87 21.38 4.4
100o 40.19 37.15 0.92 2.20 47.69 18.3 40 o 30.71 1.92 24.18 4.7
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 24.53 1.89 18.09 3.8
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 25.90 1.91 19.39 4.0
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 28.65 1.96 21.97 4.3
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP049.1IP60 Rev: 1-08 http://www.fhp-mfg.com
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS
AP049
A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 21.2 96.0 6.8 3/4 - - 35.1 50 Feet Deep O.D. Inch
6.0 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
10x 8 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 318 lbs 348 lbs
+ 1950 FLUID PRESSURE DROP
Norm 1700 Fluid Pressure
- 1450 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1700 CFM and 12.0 GPM 6.0 2.3 1.0
Water Loop Ground Water Ground Loop 7.0 3.0 1.3
Cooling Heating Cooling Heating Cooling Heating 9.5 5.3 2.3
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 12.0 8.0 3.5
50,000 16.9 53,000 5.2 56,000 24.0 45,500 4.8 52,000 19.0 38,000 4.1 16.0 13.4 5.8

CAPACITY DATA - FULL LOAD


COOLING All performance at 1700 CFM and 12.0 GPM EFT Range (Standard)
50oF to 100oF HEATING EFT Range (Standard)
25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 48.95 31.89 0.65 2.28 56.74 21.4 50 o 48.44 2.96 38.32 4.8
60 o 70odb 47.04 30.90 0.66 2.51 55.59 18.8 60 o 60 o 52.79 3.05 42.38 5.1
70 o 61 owb 45.13 30.01 0.67 2.73 54.45 16.5 70 o 57.15 3.14 46.43 5.3
85 o 42.27 28.85 0.68 3.06 52.72 13.8 80 o 61.50 3.23 50.48 5.6
100o 39.40 27.84 0.71 3.40 51.00 11.6 50 o 45.81 3.02 35.52 4.5
50 o 52.46 38.15 0.73 2.30 60.29 22.9 60 o 70 o 49.92 3.11 39.32 4.7
60 o 75odb 50.41 36.97 0.73 2.52 59.01 20.0 70 o 54.04 3.20 43.13 5.0
o
70 63 owb 48.37 35.92 0.74 2.74 57.74 17.6 80 o 58.15 3.29 46.94 5.2
85 o 45.31 34.54 0.76 3.08 55.82 14.7 50 o 42.72 3.08 32.21 4.1
100o 42.24 33.33 0.79 3.42 53.90 12.4 60 o 80 o 46.55 3.17 35.73 4.3
50 o 57.59 42.14 0.73 2.31 65.48 24.9 70 o 50.39 3.26 39.25 4.5
60 o 80odb 55.35 40.84 0.74 2.54 64.01 21.8 80 o 54.22 3.36 42.76 4.7
70 o 67 owb 53.11 39.68 0.75 2.76 62.55 19.2
Antifreeze Required
85 o 49.75 38.15 0.77 3.10 60.35 16.0 LOW TEMP HEATING
100o 46.39 36.82 0.79 3.44 58.14 13.5 25 o 36.81 2.74 27.45 3.9
50 o 62.72 46.16 0.74 2.33 70.67 26.9 30 o 60 o 38.95 2.79 29.44 4.1
60 o 85odb 60.29 44.74 0.74 2.56 69.01 23.6 40 o 43.22 2.87 33.41 4.4
70 o 71 owb 57.85 43.47 0.75 2.79 67.36 20.8 25 o 34.83 2.79 25.31 3.7
85 o 54.20 41.80 0.77 3.13 64.87 17.3 30 o 70 o 36.84 2.83 27.17 3.8
100o 50.54 40.35 0.80 3.47 62.38 14.6 40 o 40.88 2.93 30.89 4.1
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 32.49 2.85 22.77 3.3
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 34.37 2.89 24.49 3.5
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 38.13 2.99 27.93 3.7
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP049.2IP60 Rev: 1-08 http://www.fhp-mfg.com
AP061
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 25.7 118.0 6.8 3/4 - - 41.0 60 Feet Deep O.D. Inch
7.5 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
11x 9 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 390 lbs 415 lbs
+ 1725 FLUID PRESSURE DROP
Norm 1500 Fluid Pressure
- 1275 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1500 CFM and 14.0 GPM 8 3.5 1.5
Water Loop Ground Water Ground Loop 12 7.2 3.1
Cooling Heating Cooling Heating Cooling Heating 16 12.1 5.3
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 18 15.0 6.5
47,000 19.0 56,500 6.2 53,000 33.0 45,000 5.2 51,000 27.7 39,000 4.6 22 21.5 9.3

CAPACITY DATA - PART LOAD


COOLING All performance at 1500 CFM and 14.0 GPM EFT Range (Standard)
50 F to 100 F o o HEATING EFT Range (Standard)
25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 47.18 30.54 0.65 1.27 51.51 37.3 50 o 49.27 2.53 40.63 5.7
60 o 70odb 45.41 29.64 0.65 1.55 50.71 29.2 60 o 60 o 54.35 2.59 45.50 6.1
70 o 61 owb 43.64 28.84 0.66 1.84 49.92 23.7 70 o 59.43 2.66 50.36 6.6
85 o 40.98 27.79 0.68 2.27 48.73 18.0 80 o 64.51 2.72 55.22 6.9
100o 38.32 26.89 0.70 2.70 47.55 14.2 50 o 46.56 2.58 37.77 5.3
50 o 50.53 36.44 0.72 1.27 54.87 39.7 60 o 70 o 51.36 2.64 42.35 5.7
60 o 75odb 48.63 35.37 0.73 1.56 53.96 31.1 70 o 56.16 2.71 46.92 6.1
70 o 63 owb 46.73 34.41 0.74 1.85 53.05 25.2 80 o 60.97 2.77 51.50 6.4
85 o 43.89 33.17 0.76 2.28 51.69 19.2 50 o 43.39 2.63 34.39 4.8
100o 41.04 32.10 0.78 2.72 50.32 15.1 60 o 80 o 47.86 2.70 38.64 5.2
50 o 55.42 40.19 0.73 1.28 59.80 43.2 70 o 52.33 2.77 42.88 5.5
60 o 80odb 53.34 39.01 0.73 1.57 58.72 33.9 80 o 56.80 2.83 47.12 5.9
70 o 67 owb 51.26 37.96 0.74 1.87 57.63 27.5
Antifreeze Required
85 o 48.14 36.59 0.76 2.30 56.00 20.9 LOW TEMP HEATING
100o 45.02 35.40 0.79 2.74 54.38 16.4 25 o 35.85 2.37 27.76 4.4
50 o 60.31 43.98 0.73 1.29 64.73 46.6 30 o 60 o 38.34 2.40 30.14 4.7
60 o 85odb 58.05 42.69 0.74 1.59 63.47 36.6 40 o 43.32 2.47 34.91 5.1
70 o 71 owb 55.79 41.54 0.74 1.88 62.21 29.7 25 o 33.88 2.41 25.65 4.1
85 o 52.40 40.04 0.76 2.32 60.32 22.6 30 o 70 o 36.24 2.45 27.89 4.3
100o 49.00 38.75 0.79 2.76 58.43 17.7 40 o 40.94 2.51 32.37 4.8
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 31.58 2.47 23.16 3.8
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 33.77 2.50 25.23 4.0
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 38.15 2.57 29.39 4.4
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP061.1IP60 Rev: 1-08 http://www.fhp-mfg.com
AP061
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 25.7 118.0 6.8 3/4 - - 41.0 60 Feet Deep O.D. Inch
7.5 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
11x 9 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 390 lbs 415 lbs
+ 2200 FLUID PRESSURE DROP
Norm 2000 Fluid Pressure
- 1700 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 2000 CFM and 14.0 GPM 8 3.5 1.5
Water Loop Ground Water Ground Loop 12 7.2 3.1
Cooling Heating Cooling Heating Cooling Heating 16 12.1 5.3
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 18 15.0 6.5
64,000 16.2 78,500 5.4 71,000 23.8 65,000 5.0 67,000 18.5 49,000 4.1 22 21.5 9.3

CAPACITY DATA - FULL LOAD


COOLING All performance at 2000 CFM and 14.0 GPM EFT Range (Standard)
50oF to 100oF HEATING EFT Range (Standard)
25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
o
50 62.67 40.56 0.65 2.66 71.76 23.5 50 o 67.49 3.83 54.43 5.2
60o 70odb 60.48 39.48 0.65 3.01 70.76 20.1 60o 60o 76.05 4.05 62.22 5.5
70o 61owb 58.30 38.53 0.66 3.36 69.77 17.4 70o 84.62 4.28 70.01 5.8
85o 55.03 37.33 0.68 3.88 68.27 14.2 80o 93.19 4.51 77.81 6.1
100o 51.76 36.33 0.70 4.40 66.78 11.8 50o 63.78 3.90 50.48 4.8
50o 67.11 48.40 0.72 2.68 76.25 25.0 60o 70o 71.88 4.13 57.78 5.1
60o 75odb 64.77 47.11 0.73 3.03 75.11 21.4 70o 79.97 4.36 65.09 5.4
70o 63owb 62.44 45.98 0.74 3.38 73.97 18.5 80o 88.06 4.59 72.40 5.6
o
85 58.94 44.54 0.76 3.90 72.25 15.1 50o 59.43 3.99 45.82 4.4
100o 55.43 43.35 0.78 4.43 70.54 12.5 60o 80o 66.97 4.22 52.56 4.6
50o 73.61 53.38 0.73 2.70 82.82 27.3 70o 74.50 4.46 59.29 4.9
60o 80odb 71.05 51.96 0.73 3.05 81.47 23.3 80o 82.04 4.69 66.02 5.1
70o 67owb 68.49 50.71 0.74 3.41 80.11 20.1
Antifreeze Required
85o 64.65 49.13 0.76 3.93 78.08 16.4 LOW TEMP HEATING
100o 60.81 47.82 0.79 4.46 76.04 13.6 25o 45.17 3.26 34.04 4.1
50o 80.11 58.42 0.73 2.72 89.40 29.4 30o 60o 49.37 3.38 37.85 4.3
60o 85odb 77.32 56.86 0.74 3.08 87.82 25.1 40o 57.77 3.60 45.48 4.7
70o 71owb 74.54 55.50 0.74 3.43 86.25 21.7 25o 42.70 3.32 31.36 3.8
o
85 70.36 53.77 0.76 3.97 83.90 17.7 30o 70o 46.66 3.44 34.93 4.0
100o 66.19 52.33 0.79 4.50 81.54 14.7 40o 54.60 3.67 42.08 4.4
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25o 39.79 3.40 28.20 3.4
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30o 80o 43.49 3.52 31.49 3.6
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40o 50.88 3.75 38.07 4.0
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP061.2IP60 Rev: 1-08 http://www.fhp-mfg.com
AP071
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol Square Rows Tube Fins/
RLA LRA FLA HP FLA HP Amps Breaker
208/230-1-60 -1 29.9 138.4 7.0 1 - - 46.2 70 Feet Deep O.D. Inch
7.5 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
12 x 9 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 450 lbs 495 lbs
Speed
+ 1600 FLUID PRESSURE DROP
Norm 1500 Fluid Pressure
- 1200 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1500 CFM and 18.0 GPM 8 2.5 1.1
Water Loop Ground Water Ground Loop 12 3.6 1.6
Cooling Heating Cooling Heating Cooling Heating 16 4.3 1.9
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 18 6.9 3.0
53,000 18.2 65,800 5.2 59,000 28.8 53,700 4.6 57,500 25.2 47,000 4.1 22 8.2 3.6

CAPACITY DATA - PART LOAD


COOLING All performance at 1500 CFM and 18.0 GPM EFT Range (Standard)
50oF to 100oF HEATING EFT Range (Standard)
25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 51.94 33.47 0.64 1.74 57.88 29.8 50 o 58.79 3.48 46.91 4.9
60 o 70odb 50.20 32.62 0.65 2.03 57.11 24.8 60 o 60 o 64.25 3.59 51.98 5.2
70 o 61 owb 48.46 31.88 0.66 2.31 56.35 21.0 70 o 69.71 3.71 57.05 5.5
o
85 45.85 30.96 0.68 2.74 55.20 16.7 80 o 75.17 3.82 62.13 5.8
100o 43.25 30.23 0.70 3.17 54.05 13.7 50 o 55.58 3.54 43.49 4.6
50 o 55.65 40.01 0.72 1.75 61.62 31.8 60 o 70 o 60.74 3.66 48.25 4.9
60 o 75odb 53.79 39.00 0.73 2.04 60.74 26.4 70 o 65.90 3.77 53.02 5.1
70 o 63 owb 51.93 38.13 0.73 2.32 59.86 22.4 80 o 71.06 3.89 57.78 5.4
85 o 49.14 37.03 0.75 2.75 58.54 17.8 50 o 51.82 3.62 39.46 4.2
100o 46.35 36.15 0.78 3.18 57.21 14.6 60 o 80 o 56.62 3.74 43.86 4.4
50 o 61.08 44.18 0.72 1.76 67.09 34.7 70 o 61.43 3.86 48.26 4.7
60 o 80odb 59.04 43.06 0.73 2.05 66.04 28.8 80 o 66.23 3.98 52.66 4.9
70 o 67 owb 57.00 42.10 0.74 2.34 64.99 24.4
Antifreeze Required
85 o 53.94 40.89 0.76 2.77 63.41 19.4 LOW TEMP HEATING
100o 50.88 39.92 0.78 3.21 61.83 15.9 25 o 44.26 3.20 33.35 4.1
50 o 66.51 48.39 0.73 1.78 72.57 37.5 30 o 60 o 46.93 3.25 35.83 4.2
60 o 85odb 64.29 47.16 0.73 2.07 71.35 31.1 40 o 52.28 3.37 40.79 4.5
70 o 71 owb 62.07 46.11 0.74 2.36 70.12 26.3 25 o 41.85 3.25 30.75 3.8
85 o 58.75 44.79 0.76 2.80 68.29 21.0 30 o 70 o 44.38 3.31 33.08 3.9
100o 55.42 43.73 0.79 3.23 66.45 17.1 40 o 49.44 3.43 37.74 4.2
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 39.03 3.32 27.68 3.4
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 41.39 3.38 29.84 3.6
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 46.09 3.50 34.14 3.9
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP071.1IP60 Rev: 1-08 http://www.fhp-mfg.com
AP071
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS A QU ARIUS II
QUARIUS
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Electrical Elect.
Circuit Fuse/ Air Coil
Characteristics Symbol
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 29.9 138.4 7.0 1 - - 46.2 70 Feet Deep O.D. Inch
7.5 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
12x 9 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
Speed
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 450 lbs 495 lbs
+ FLUID PRESSURE DROP
Norm 2300 Fluid Pressure
- 1900 Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 2300 CFM and 18.0 GPM 8 2.5 1.1
Water Loop Ground Water Ground Loop 12 3.6 1.6
Cooling Heating Cooling Heating Cooling Heating 16 4.3 1.9
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 18 6.9 3.0
72,000 16.0 89,000 5.2 78,000 21.8 73,000 4.7 74,000 18.0 58,000 4.1 22 8.2 3.6

CAPACITY DATA - FULL LOAD


COOLING All performance at 2300 CFM and 18.0 GPM EFT Range (Standard)
50oF to 100oF HEATING EFT Range (Standard)
25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 67.02 42.08 0.63 3.45 78.78 19.4 50 o 77.31 4.74 61.12 4.8
60 o 70odb 65.13 41.23 0.63 3.77 77.99 17.3 60 o 60 o 86.25 5.00 69.17 5.0
70 o 61 owb 63.23 40.53 0.64 4.09 77.20 15.5 70 o 95.20 5.27 77.22 5.3
85 o 60.40 39.74 0.66 4.58 76.01 13.2 80 o 104.14 5.53 85.28 5.5
100o 57.56 39.20 0.68 5.06 74.82 11.4 50 o 73.10 4.83 56.62 4.4
50 o 71.82 50.34 0.70 3.46 83.65 20.7 60 o 70 o 81.55 5.09 64.16 4.7
60 o 75odb 69.79 49.33 0.71 3.79 82.73 18.4 70 o 90.00 5.36 71.70 4.9
o
70 63 owb 67.77 48.50 0.72 4.11 81.81 16.5 80 o 98.45 5.63 79.25 5.1
85 o 64.73 47.55 0.73 4.60 80.43 14.1 50 o 68.15 4.93 51.32 4.0
100o 61.69 46.91 0.76 5.09 79.05 12.1 60 o 80 o 76.02 5.21 58.26 4.3
50 o 78.84 55.59 0.71 3.49 90.76 22.6 70 o 83.89 5.48 65.20 4.5
60 o 80odb 76.62 54.48 0.71 3.82 89.65 20.1 80 o 91.76 5.75 72.14 4.7
70 o 67 owb 74.40 53.57 0.72 4.15 88.55 17.9 Antifreeze Required
85 o 71.07 52.52 0.74 4.64 86.89 15.3 LOW TEMP HEATING
100o 67.74 51.82 0.76 5.13 85.24 13.2 25 o 53.87 4.09 39.91 3.9
50 o 85.86 60.90 0.71 3.52 97.87 24.4 30 o 60 o 58.25 4.22 43.85 4.0
60 o 85odb 83.45 59.68 0.72 3.85 96.58 21.7 40 o 67.02 4.48 51.72 4.4
70 o 71 owb 81.03 58.68 0.72 4.18 95.29 19.4 25 o 50.95 4.16 36.74 3.6
85 o 77.41 57.55 0.74 4.67 93.35 16.6 30 o 70 o 55.10 4.30 40.43 3.8
100o 73.78 56.77 0.77 5.17 91.42 14.3 40 o 63.38 4.56 47.81 4.1
Units are complete packages containing compressor, reversing valve, expansion valve metering device, ECM fan motor 25 o 47.53 4.25 33.02 3.3
and heat exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant
pressure switches and solid state lock-out circuit. Optional UL approved internal electric heater, factory installed with 30 o 80 o 51.39 4.39 36.41 3.4
primary thermal overload protection and magnetic contactors (208/230-1-60 only) optional UL approved internal Heat
Recovery Package and/or Ground Loop Pump with purge connections available
40 o 59.10 4.66 43.20 3.7
FHP MANUFACTURING COMPANY
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP
EAD selection software. Due to variations in installation actual performance may vary marginally from tabulated values. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
Phone: (954) 776-5471 - Fax: (800) 776-5529
As a result of continuing research and development, specifications are subject to change without notice.
AP071.2IP60 Rev: 1-08 http://www.fhp-mfg.com
AP SERIES

AP SERIES
INSTALLATION TABLE OF CONTENTS
Model Nomenclature .................................................................................................1
Initial Inspection .........................................................................................................2
General Description ...................................................................................................2
Moving and Storage ..................................................................................................2
Safety Considerations ................................................................................................2
Location.....................................................................................................................2
Installation..................................................................................................................2
Condensate Drain......................................................................................................3
Duct System..............................................................................................................3
Piping ........................................................................................................................3
Electrical ....................................................................................................................4
Thermostat Connections............................................................................................4
Safety Devices & the UPM Controller.........................................................................5
Electric Heater Package Option .................................................................................7
Sequence of Operation Single Stage Units ................................................................7
Sequence of Operation Two-Stage Units...................................................................7
Well Water Systems...................................................................................................7
Installation of Pressure Regulating Valves ..................................................................7
Cooling Tower / Boiler Application .............................................................................7
Earth Coupled Systems .............................................................................................8
System Checkout ......................................................................................................8
Unit Start-Up .............................................................................................................8
Maintenance ..............................................................................................................8
AND MAINTENANCE MANUAL

Wiring Diagrams ........................................................................................................9


Trouble Shooting .....................................................................................................13
Unit Check Out ........................................................................................................14
Operating Pressures & Temperatures ......................................................................15

MODEL NOMENCLATURE
AP 049 -1 VT C - F L T
SERIES:
AP-AQUARIUS II

SUPPLY AIR LOCATION:


NOMINAL CAPACITY: T - TOP (VT ONLY)
E - END BLOW (HZ ONLY)
VOLTAGE DESIGNATION: B - BOTTOM (CF ONLY)
1 - 208/1/60 & 230/1/60

RETURN AIR LOCATION:


L - LEFT
R - RIGHT
CABINET CONFIGURATION: B - BACK
VT - VERTICAL F - FRONT
HZ - HORIZONTAL
CF - COUNTERFLOW
WATER CONNECTION
LOCATION:
HEAT EXCHANGER MATERIAL: F - FRONT
C - COPPER
N - CUPRO-NICKEL
2 AP SERIES

INITIAL INSPECTION: When working on equipment, always observe


precautions described in the literature, tags, and labels
Be certain to inspect all cartons or crates on each unit
attached to the unit. Follow all safety codes. Wear
as received at the job site before signing the freight bill.
safety glasses and work gloves. Use a quenching cloth
Verify that all items have been received and that there
for brazing, and place a fire extinguisher close to the
are no visible damages; note any shortages or
work area.
damages on all copies of the freight bill. In the event of
damage or shortage, remember that the purchaser is
responsible for filing the necessary claims with the LOCATION:
carrier. Concealed damages not discovered until after Locate the unit in an indoor area that allows easy
removing the units from the packaging must be removal of the filter and access panels, and has
reported to the carrier within 24 hours of receipt. enough room for service personnel to perform
maintenance or repair. Provide sufficient room to make
GENERAL DESCRIPTION: fluid, electrical, and duct connection(s). If the unit is
located in a confined space such as a closet,
These Water-to-Air Heat Pumps provide the best
provisions must be made for return air to freely enter
combination of performance and efficiency available.
the space. On horizontal units, allow adequate room
Safety devices are built into each unit to provide the
below the unit for a condensate drain trap and do not
maximum system protection possible when properly
locate the unit above supply piping. These units are not
installed and maintained.
approved for outdoor installation; therefore, they must
The AP Water-to-Air Heat Pumps are Underwriters be installed inside the structure being conditioned. Do
Laboratories (UL) and (cUL) listed for safety. The water- not locate in areas that are subject to freezing.
to-Air Heat Pumps are designed to operate with
entering fluid temperature between 20°F to 80°F in the INSTALLATION:
heating mode and between 50°F to 110°F in the
cooling mode. NOTE: Remove all shipping blocks under blower
housing. Loosen compressor mounting bolts.
NOTE: 50°F Min. EWT for well water applications with
sufficient water flow to prevent freezing. Antifreeze
solution is required for all closed loop applications. MOUNTING VERTICAL UNITS:
Cooling Tower/Boiler and Earth Coupled (Geo Thermal)
applications should have sufficient antifreeze solution Vertical units up to
(Figure #1)
to protect against extreme conditions and equipment six tons are available
failure. Frozen water coils are not covered under in left, right, front, or
warranty. rear air return
configurations.
NOTE: This product should not be used for Vertical units should
temporarily heating/cooling during construction. Doing be mounted level on
so may effect the units warranty. a vibration absorbing
pad slightly larger
MOVING AND STORAGE: than the base to
minimize vibration
If the equipment is not needed for immediate transmission to the
installation upon its arrival at the job site, it should be building structure. It
left in its shipping carton and stored in a clean, dry VIBRATION
is not necessary to PAD
area. Units must only be stored or moved in the normal anchor the unit to the FULL SIZE
upright position as indicated by the "UP" arrows on floor. (See Figure #1).
each carton at all times. If unit stacking is required,
stack units as follows: Vertical units less than 6 tons,
no more than two high. Horizontal units less than 6 MOUNTING HORIZONTAL UNITS:
tons, no more than three high. "Do not stack units While horizontal units may be installed on any level
larger than 6 tons." surface strong enough to hold their weight, they are
typically suspended above a ceiling by threaded rods.
SAFETY CONSIDERATIONS: The rods are usually attached to the unit corners by
Installation and servicing of this equipment can be hanger bracket kits
hazardous due to system pressure and electrical (P/N 930-004, 006).
components. Only trained and qualified personnel (See Figure #2). The
should install, repair, or service the equipment. rods must be securely
Untrained personnel can perform basic functions of anchored to the ceiling.
maintenance such as cleaning coils and replacing Refer to the hanging
filters. bracket assembly and
installation instructions
WARNING: Before performing service or (Figure #2) for details. Models
maintenance operations on the system, turn off main AP035 and up require
power to the unit. Electrical shock could cause six brackets (930-006).(See unit horizontal detail
personal injury or death. drawing). Horizontal units installed above the ceiling
must conform to all local codes. An auxiliary drain pan
AP SERIES 3
if required by code, should be at least four inches The horizontal unit should be pitched approximately
larger than the bottom of the heat pump. Plumbing 1/4" towards the drain in both directions, to facilitate
connected to the heat pump must not come in direct condensate removal. (See Figure #4)
contact with joists, trusses, walls, etc.
DUCT SYSTEM:
Some applications require an attic floor installation of
the horizontal unit. In this case the unit should be set A supply air outlet collar and return air duct flange are
in a full size secondary drain pan on top of a vibration provided on all units to facilitate duct connections.
absorbing mesh. The secondary drain pan prevents Refer to the FHP individual data specification sheet for
possible condensate overflow or water leakage physical dimensions of the collar and flange.
damage to the ceiling. The secondary drain pan is
usually placed on a plywood base isolated from the A flexible connector is recommended for supply and
ceiling joists by additional layers of vibration absorbing return air duct connections on metal duct systems. All
mesh. In both cases, a 3/4" drain connected to this metal ducting should be insulated with a minimum of
secondary pan should be run to an eave at a location one inch duct insulation to avoid heat loss or gain and
that will be noticeable. If the unit is located in a crawl prevent condensate forming during the cooling
space, the bottom of the unit must be at least 4" above operation. Application of the unit to uninsulated duct
grade to prevent flooding of the electrical parts due to work is not recommended as the unit’s performance
heavy rains. will be adversely affected. Do not connect discharge
ducts directly to the blower outlet. The factory
provided air filter must be removed when using a filter
CONDENSATE DRAIN: back return air grill.The factory filter should be left in
NOTE: If equipped with float style condensate place on a free return system.
overflow switch, final adjustment must be made in the
field. If the unit will be installed in a new installation which
includes new duct work, the installation should be
A drain line must be connected to the heat pump and designed using current ASHRAE procedures for duct
sizing. If the unit is to be connected to existing
ductwork, a check should be made to assure that the
duct system has the capacity to handle the air required
for the unit application. If the duct system is too small,
larger ductwork should be installed. Check for existing
leaks and repair.
The duct system and all diffusers should be sized to
handle the designed air flow quietly. To maximize
sound attenuation of the unit blower, the supply and
return air plenums should be insulated. There should
be no direct straight air path thru the return air grille
(Figure #3)
into the heat pump. The return air inlet to the heat
pump must have at least one 90 degree turn away from
pitched away from the unit a minimum of 1/8" per foot the space return air grille. If air noise or excessive air
to allow the condensate to flow away from the unit. flow are a problem, the blower speed can be changed
to a lower speed to reduce air flow. (Refer to ECM
This connection must be in conformance with local motor interface board section in this manual and Figure
plumbing codes. A trap must be installed in the #7)
condensate line to insure free condensate flow. (Heat
Pumps are not internally trapped). A vertical air vent is PIPING:
sometimes required to avoid air pockets. (See Figure
Supply and return piping must be as large as the unit
#3). The length of the trap depends on the amount of
connections on the heat pump (larger on long runs).
positive or negative pressure on the drain pan. A
Never use flexible hoses of a smaller inside diameter
second trap must not be included.
than that of the fluid connections on the unit. AP units
are supplied with either a copper or optional cupro-
nickel condenser. Copper is adequate for ground water
that is not high in mineral content. Should your well
driller express concern regarding the quality of the well
water available or should any known hazards exist in
your area, we recommend proper testing to assure the
well water quality is suitable for use with water source
equipment. In conditions anticipating moderate scale
formation or in brackish water a cupro-nickel heat
exchanger is recommended.
Both the supply and discharge water lines will sweat if
subjected to low water temperature. These lines should
(Figure #4) be insulated to prevent damage from condensation.
4 AP SERIES

All manual flow valves used in the system must be ball Properly sized fuses or HACR circuit breakers must be
valves. Globe and gate valves must not be used due to installed for branch circuit protection. See unit
high pressure drop and poor throttling characteristics. nameplate for maximum fuse or breaker size.
Never exceed the recommended water flow rates as
serious damage or erosion of the water to refrigerant The unit is provided with a concentric knock-out in the
heat exchanger could occur. front left corner post for attaching common trade sizes
of conduit, route power supply wiring through this
Always check carefully for water leaks and repair opening. Always connect the ground lead to the
appropriately. Units are equipped with female pipe grounding lug provided in the control box and power
thread fittings. Consult the specification sheets for leads to the power supply terminal block as indicated
sizes. Teflon tape sealer should be used when on the wiring diagram and Figure #5.
connecting water piping connections to the units to
insure against leaks and possible heat exchanger
fouling. Do not overtighten the connections. Flexible NOTE: Units supplied with internal electric heat
hoses should be used between the unit and the rigid require two (2) separate power supplies: one for the
system to avoid possible vibration. Ball valves should unit compressor and one for the electric heater
be installed in the supply and return lines for unit elements, blower motor and control circuit. Refer to the
isolation and unit water flow balancing. ELECTRIC HEATER PACKAGE OPTION section and
Figure #9 for wiring instructions, minimum circuit
ampacities and maximum fuse/breaker sizing.
ELECTRICAL:
(Refer to electrical component box layout, Figure #5)
Field wiring must comply with local and national
electric codes. Power to the unit must be within the
operating voltage range indicated on the unit
nameplate or on the performance data sheet. On three
phase units (single stage units only) phases must be
balanced within 2%.
CAUTION: Operation of unit on improper line voltage
or with excessive phase imbalance will be hazardous to
the unit, constitutes abuse and may void the warranty.

(Figure #5)
Electrical Box Component Layout

(Figure #6)

ECM INTERFACE BOARD:

THERMOSTAT CONNECTIONS:
Thermostat wiring is connected to the 10 pin screw
type terminal block on the lower center portion of the
ECM Interface Board. In addition to providing a
connecting point for thermostat wiring, the interface
board also translates thermostat inputs into control
commands for the variable speed programmable ECM
DC fan motor and displays an LED indication of
operating status. The thermostat connections and their
functions are as follows:

Y2 Second Stage Compressor Operation


Y1 First Stage Compressor Operation
G Fan
O Reversing Valve (energized in cooling)
W1 Auxiliary Electric Heat
(runs in conjunction with compressor)
EM/W2 Emergency Heat (electric heat only)
NC Transformer 24 VAC Common
(extra connection)
C1 Transformer 24 VAC Common
(primary connection)
R Transformer 24 VAC Hot
Single & Two Step HUM Dehumidification Mode
AP SERIES 5
If the unit is being connected to a thermostat with a TEST position and energize G on the thermostat
malfunction light, this connection is made at the unit connection block. If the motor ramps up to 100%
malfunction output or relay. power, then the motor itself is functioning normally.
Always remember to replace the jumper to NORM, (+)
NOTE: If the thermostat is provided with a malfunction or (-) after testing and reset the unit thermostat to
light powered off of the common (C) side of the restore normal operation.
transformer, the unit must be provided with a
malfunction relay (FHP option # 660-006) to properly NOTE: Do not set the ADJ jumper to the (-) setting
energize the light. The relay coil will be wired across when electric heaters are installed. Doing so may
the (ALR) and (C) contacts on the unit’s UPM board cause the heaters to cycle on their thermal overload
and the relay’s normally open contacts across (ALR) switches, potentially shortening the life of the switches.
and the malfunction light connection on the
thermostat. If the thermostat is provided with a The other three sets of jumper pins are used to select
malfunction light powered off of the hot (R) side of the the proper program in the ECM motor for the unit.
transformer, then the thermostat malfunction light Refer to Figure #7 for the proper jumper placement.
connection should be connected directly to the (ALR)
contact on the unit’s UPM board. NOTE: Always disconnect power before changing
jumper positions on the interface board and reset the
unit afterward.
MOTOR PROFILE AIR FLOW TABLE CFM
TWO STAGE UNITS To the left of the red and green status LED’s is
FAN Y1 Y2 AUX. EMERG. PLUS MINUS TAP a row of 1/4” male quick connects. These are
MODEL ONLY COOL/HEAT COOL/HEAT HEAT HEAT ADJ ADJ COOL/HEAT/DELAY used to pass thermostat inputs on to the rest
AP025 600 750 950 950 950 1090 800 A
of the control circuit. Remember to always turn
off unit power at the circuit breaker before
AP035 900 1000 1200 1200 1200 1400 1000 A
attaching or disconnecting any wiring from
AP049 1200 1300 1700 1700 1700 1950 1450 B these connections to avoid accidental short
AP061 1300 1500 2000 2000 2000 2100 1900 A circuits that can damage unit control
AP071 1300 1500 2100 2100 2100 2300 1900 A components.

To the left of the thermostat connection block are a


row of 2 red and 4 green LED’s. These LED’s indicate SAFETY DEVICES AND THE UPM
the operating status of the unit. They are labeled as CONTROLLER
follows:
Each unit is factory provided with a Unit Protection
EM (red) Emergency Heat On Module (UPM) that controls the compressor operation
W1 (red) Auxiliary Heat On and monitors the safety controls that protect the unit.
O (green) Reversing Valve Energized, unit is
in cooling mode Safety controls include the following:
Y2 (green) Second Stage Compressor On
Y1 (green) First Stage Compressor On • High pressure switch located in the refrigerant
G (green) Fan On discharge line and wired across the HPC terminals on
the UPM
Just above the connector block is a single red LED
labeled CFM that will blink intermittently when the unit • Low pressure switch located in the unit refrigerant
is running and may flicker when the unit is off. This LED suction line and wired across terminals LPC1 and LPC2
indicates the air delivery of the blower at any given on the UPM.
time. Each blink of the LED represent 100 CFM of air
delivery so if the LED blinks 12 times, pauses, blinks 12 • Optional freeze protection sensor located on the leaving
times, etc. the blower is delivering 1200 CFM. Refer to side of the water coil prevents unit operation below 35º
Figure #7 for factory programmed air delivery settings F. A freeze stat pin located on the board may be put in
for the ES Series. the YES or NO position depending whether the freeze
stat is ordered.
To the right of the thermostat connection block is a
green LED labeled dehumidify. NOTE: The factory default is in the YES position. If the
freeze stat option is not ordered the pin must be
Just above and to the right of the thermostat relocated to the NO position.
connection block are four sets of jumper pins labeled
ADJ, DELAY, HEAT and COOL. The ADJ set of pins are • Optional Condensate overflow protection sensor
labeled NORM, (+), (-) and TEST. ES units will all be set located in the drain pan of the unit and connected to
on the NORM position from the factory, however, the ‘cond’ terminal on the UPM board.
airflow can be increased (+) or decreased
(-) by 15% from the pre-programmed setting by
relocating the jumper in this section. The TEST position The UPM includes the following features:
is used to verify proper motor operation. If a motor • ANTI-SHORT CYCLE TIMER – 5 minute delay on
problem is suspected, move the ADJ jumper to the break timer to prevent compressor short cycling.
6 AP SERIES

• RANDOM START – Each controller has a unique thermostat with a fault indication LED (24v) and will
random start delay ranging from 270 to 300 seconds. display the fault code on the thermostat.
• LOW PRESSURE BYPASS TIMER - The low • INTELLIGENT RESET - If a fault condition is initiated
pressure switch is bypassed for 120 seconds after the 5 minute delay on break time period and the
compressor start-up to prevent nuisance low pressure random start timer are initiated and the unit will restart
lockouts during cold start-up in the heating mode. after these delays expire. During this period the fault
LED will indicate the cause of the fault. If the fault
• BROWNOUT/SURGE/POWER INTERRUPTION condition still exists or reoccurs before 60 minutes, the
PROTECTION – a 20 millisecond window is monitored
unit will go into a hard lockout and requires a manual
for the above condition. Should any of these conditions
lockout reset. A condensate overflow fault will cause
be detected, the 5-minute delay on break timer and the
the unit to go into a hard lockout immediately.
random start timer delay are initiated.
• LOCKOUT RESET - A hard lockout can be reset by
• MALFUNCTION OUTPUT – The controller has a set of
turning the unit thermostat off and then back on or by
wet contacts for remote fault indication.
shutting off unit power at the circuit breaker.
• TEST SERVICE PIN – A jumper pin is provided to
reduce all time delay settings to 5 seconds during NOTE: The blower motor will remain active during a
troubleshooting or verification of unit operation. Note lockout condition.
that operation of the unit in test mode can lead to
accelerated wear and premature failure of the unit. ELECTRIC HEATER PACKAGE OPTION:

• L.E.D. FAULT INDICATION – Two L.E.D. indicators Factory or field installed internal electric heater
are provided: packages are available for all Aquarius II series units.
Two power supplies are required when heater
• GREEN: Power L.E.D. indicates 18 – 30 VAC present packages are utilized. The power supply for the heater
at the board. package (located in the electric heater package control
box) provides power for the heater elements, the
• RED: Fault indicator with blink codes as follows: blower motor and the control circuit for the unit. The
• ONE BLINK High pressure lockout power supply for the unit provides power for the
compressor. This allows the electric heaters to
• TWO BLINKS Low pressure lockout continue to operate along with the blower motor in the
case of unit compressor and/or compressor power
• THREE BLINKS Freeze sensor lockout
supply failure. See HP Series Heater Kit Instructions for
• FOUR BLINKS Condensate overflow field installation.
• FIVE BLINKS Brown out Each Aquarius II model has a number of heater sizes
available. Refer to Figure #9 for heater package
The fault pulse code may be sent to the ALR fault
compatibility with specific Aquarius II units, model
terminal by placing the Alarm Output pin in the
nomenclature and electrical data.
pulse position. The pulse signal may be sent to a

(Figure #9)
ENVIROSAVER HEATER KW HEATER CIRCUIT MCA MAX AWG
MODEL MODEL AMPS FUSE MIN

208V 240V 208V 240V 208V 240V

m AP025 thru 035 HP050-1XS 4.8 17.3 20.0 L1/L2 27.1 30.4 30 30 8

m AP049 thru 071 HP050-1XM 4.8 17.3 20.0 L1/L2 27.1 30.4 30 30 8

m AP025 thru 035 HP075-1XS 7.2 23.6 30.0 L1/L2 34.9 42.9 40 45 8

m AP049 thru 071 HP075-1XM 7.2 23.6 30.0 L1/L2 35.7 43.8 40 45 8

m AP025 thru 035 HP100-1XS 9.6 34.7 40.0 L1/L2 48.8 55.4 50 60 6

m AP049 thru 071 HP100-1XM 9.6 34.7 40.0 L1/L2 49.5 56.3 50 60 6

m AP049 thru 071 HP150-1XM 14.4 52.0 60.0 SINGLE 71.2 81.3 80 90 4
HP150-1XM 14.4 34.7 40.0 L1/L2 49.5 56.3 60 60 6
17.3 20.0 L3/L4 21.7 25.0 25 25 10

m AP049 thru 071 HP200-1XM 19.2 69.3 80.0 SINGLE 92.9 106.3 100 110 2
HP200-1XM 19.2 34.7 40.0 L1/L2 49.5 56.3 50 60 6
34.7 40.0 L3/L4 43.4 50.0 45 50 6

All heaters rated single phase 60 Hz, and include unit fan load. All fuses type “D” time delay or HACR type breaker or HRC FORM 1
Wire size based on 60 deg. C copper conductors.
AP SERIES 7
SEQUENCE OF OPERATION-TWO STAGE UNITS: control valve or a bladder type expansion tank. When
(Figure #13 Wire Schematic) using a single water well to supply both domestic water
and the heat pump care must be taken to insure that
the well can provide sufficient flow for both. In well
COOLING MODE:
water applications a slow closing solenoid valve must
Energizing the “O” terminal energizes the unit reversing be used to prevent water hammer.
valve in the cooling mode. The fan motor starts when
the “G” terminal is energized. Note that the fan motor Solenoid valves should be connected across Y1 and
will take 30 seconds to ramp up to operating speed C1 on the interface board for all. Make sure that the VA
and will run at fan only rated air flow as long as there is draw of the valve does not exceed the contact rating of
no call for compressor or heater operation. the thermostat.

When the thermostat calls for first stage cooling (Y1) INSTALLATION OF PRESSURE
the loop pump or solenoid valve if present is energized REGULATING VALVES:
and the first stage of compressor capacity starts. The
fan ramps up to first stage cooling air flow in 30 Pressure regulating valves are used to increase or
seconds. decrease water flow through the heat pump in
response to refrigerant pressure. In some cases more
When the thermostat calls for second stage cooling water may be required in heating than in cooling, or
(Y2) the second stage (or full compressor capacity) is vice versa. With the Aquarius II heat pumps these
initiated. The fan ramps up to full cooling air flow. valves are not required. However, if installed, a pair of
valves are required for proper operation, one valve for
Once the thermostat is satisfied, the compressor shuts cooling (direct acting) and another valve for heating
down accordingly and the fan ramps down to either fan (indirect acting). A refrigerant tap is provided in the
only mode or off over a span of 30 seconds. refrigerant line located between the reversing valve and
the water-to-refrigerant heat exchanger for proper
Note that a fault condition initiating a lockout will de-
monitoring of the refrigerant pressures.
energize the compressor irrespective of which stage is
engaged. The discharge water from the heat pump is not
contaminated in any manner and can be disposed of in
HEATING MODE: various ways depending on local building codes (i.e.
The first two stages of heating (Y1 & Y2) operate in the discharge well, dry well, storm sewer, drain field,
same manner as cooling, but with the reversing valve stream or pond, etc.) Most local codes forbid the use
de-energized. On a call for auxiliary heat (W1), the fan of a sanitary sewer for disposal. Consult your local
ramps up to auxiliary heat air flow immediately and the building and zoning department to insure compliance
electric heater package is energized along with the in your area.
compressor. As the thermostat is satisfied, the heaters
will shut off as soon as W1 is de-energized, and the COOLING TOWER/BOILER SYSTEMS:
compressors will remain on until the thermostat stages (Figure #11)
are satisfied. Note that if the unit compressor lock out
for any reason at this time, the electric heaters will The cooling tower and boiler water loop temperature is
continue to function normally. usually maintained between 50˚ F to 100 ˚ F to assure
adequate cooling and heating performance.
Once the thermostat is satisfied, the compressor shuts
down and the fan ramps down either fan only mode or In the cooling mode, heat is rejected from the FHP unit
off over a span of 30 seconds. If emergency heat into the water loop. A cooling tower provides
(W2/EM) is called for, the fan will ramp up to evaporative cooling to the loop water thus maintaining
emergency heat air flow immediately and the heater a constant supply temperature to the unit. When
package will energize in emergency heat mode, all utilizing open cooling towers, chemical water treatment
heater elements coming on. On shut down the fan will is mandatory to ensure the water is free from corrosive
ramp down over a period of 30 seconds. elements. A secondary heat exchanger (plate frame)
between the unit and the open cooling tower may also
WELL WATER SYSTEMS: be used. It is imperative that all air be eliminated from
(Figure #10) the closed loop side of the heat exchanger to insure
against fouling.
Copper is adequate for ground water that is not high in
mineral content. Should your well driller express In the heating mode, heat is absorbed from the water
concern regarding the quality of the well water loop. A boiler can be utilized to maintain the loop at the
available or should any known hazards exist in your desired temperature.
area, we recommend proper testing to assure the well CAUTION: Water piping exposed to extreme low
water quality is suitable for use with water source ambient temperatures is subject to freezing.
equipment. In conditions anticipating moderate scale
formation or in brackish water a cupro-nickel heat Consult the specification sheets for piping sizes. Teflon
exchanger is recommended. In well water applications tape sealer should be used when connecting to the unit
water pressure must always be maintained in the heat to insure against leaks and possible heat exchanger
exchanger. This can be accomplished with either fouling. Do not overtighten the connections. Flexible
8 AP SERIES

hoses should be used between the unit and the rigid 5. Turn the thermostat system switch to the "OFF"
system to avoid possible vibration. Ball valves should position. The unit should stop running and the reversing
be installed in the supply and return lines for unit valve should deenergize.
isolation and unit water flow balancing.
Pressure/temperature ports are recommended in both 6. Leave the unit off for approximately (5) minutes to allow
supply and return lines for system flow balancing. for system equalization.
Water flow can be accurately set by measuring the
7. Turn the thermostat to the lowest setting.
water-to-refrigerant heat exchangers water side
pressure drop. See specification sheets for water flow 8. Set the thermostat switch to "HEAT".
vs. pressure drop information.
9. Increase the thermostat setting approximately 5
No unit should be connected to the supply or return degrees above the room temperature.
piping until the water system has been completely
cleaned and flushed to remove any dirt, piping chips or 10. Verify the heat pump is operating in the heating mode.
other foreign material. Supply and return hoses should
be connected together during this process to ensure 11. Set the thermostat to maintain the desired space
the entire system is properly flushed. After the cleaning temperature.
and flushing has taken place the unit may be 12. Check for vibrations, leaks, etc...
connected to the water loop and should have all valves
wide open.
MAINTENANCE:
EARTH COUPLED SYSTEMS: 1. Filter changes or cleanings are required at regular
intervals. The time period between filter changes will
(Figure #12) depend upon type of environment the equipment is
Closed loop and pond applications require specialized used in. In a single family home, that is not under
design knowledge.No attempt at these installations construction, changing or cleaning the filter every 60
should be made unless the dealer has received days is sufficient. In other applications such as motels,
specialized training. Utilizing FHP’s Ground Loop where daily vacuuming produces a large amount of lint,
Pumping Package (GLP), makes the installation easy. filter changes may be need to be as frequent as
Anti-freeze solutions are utilized when low evaporating biweekly.
conditions are expected to occur. Refer to the GLP WARNING: Equipment should never be used during
installation manuals for more specific instructions. construction due to likelihood of wall board dust
SYSTEM CHECKOUT: accumulation in the air coil of the equipment which
permanently affects the performance and may
• After completing the installation, and before energizing shorten the life of the equipment.
the unit, the following system checks should be made:
2. An annual “checkup” is recommended by a licensed
• Verify that the supply voltage to the heat pump is in
refrigeration mechanic. Recording the performance
accordance with the nameplate ratings.
measurements of volts, amps, and water temperature
• Make sure that all electrical connections are tight and differences (both heating and cooling) is recommended.
secure. This data should be compared to the information on the
• Check the electrical fusing and wiring for the correct unit’s data plate and the data taken at the original
size. startup of the equipment.
• Verify that the low voltage wiring between the
thermostat and the unit is correct. 3. Lubrication of the blower motor is not required,
however may be performed on some motors to extend
• Verify that the water piping is complete and correct.
motor life. Use SAE-20 non-detergent electric motor oil.
• Check that the water flow is correct, and adjust if
necessary. 4. The condensate drain should be checked annually by
• Check the blower for free rotation, and that it is secured cleaning and flushing to insure proper drainage.
to the shaft.
5. Periodic lockouts almost always are caused by air or
• Verify that vibration isolation has been provided. water flow problems. The lockout (shutdown) of the unit
• Unit is serviceable. Be certain that all access panels are is a normal protective measure in the design of the
secured in place. equipment. If continual lockouts occur call a mechanic
immediately and have them check for: water flow
UNIT START-UP:
problems, water temperature problems, air flow
1. Set the thermostat to the highest setting. problems or air temperature problems. Use of the
pressure and temperature charts for the unit may be
2. Set the thermostat system switch to "COOL", and the required to properly determine the cause.
fan switch to the "AUTO" position. The reversing valve
solenoid should energize. The compressor and fan
should not run.
3. Reduce the thermostat setting approximately 5 degrees
below the room temperature.
4. Verify the heat pump is operating in the cooling mode.
AP SERIES

WELL WATER APPLICATIONS (50°F EWT MIN.)

1. LINE VOLTAGE DISCONNECT (UNIT)


2. FLEX DUCT CONNECTION
3. LOW VOLTAGE CONTROL CONNECTION
4. LINE VOLTAGE CONNECTION
5. VIBRATION PAD
6. P/T PORTS
7. HOSE KITS (Optional)
8. BALL VALVES
9. SOLENOID VALVE SLOW CLOSING
10. CONDENSATE DRAIN CONNECTION
11. PRESSURE TANK (Optional)
12. LINE VOLTAGE DISCONNECT (ELECTRIC HEATER)

NOTE: SEE FIGURE #3 FOR CONDENSATE DRAIN CONNECTION


9

(Figure #10)
10

COOLING TOWER/BOILER APPLICATION

1. LINE VOLTAGE DISCONNECT (UNIT)


2. LOW VOLTAGE CONTROL CONNECTION
3. P/T PLUGS (Optional)
4. HOSE KITS (Optional)
5. BALL VALVES
6. SUPPLY AND RETURN LINES OF CENTRAL SYSTEM
7. FLEX DUCT CONNECTION
8. HANGING BRACKETS ASSEMBLY
9. THREADED ROD
10. HANGING BRACKET ASSEMBLY AP035 and up #930-006

NOTE: SEE FIGURE #3 FOR CONDENSATE DRAIN CONNECTION


(Figure #11)
AP SERIES
AP SERIES 11

EARTH COUPLED APPLICATION

1. LINE VOLTAGE DISCONNECT (UNIT)


2. FLEX DUCT CONNECTION
3. LOW VOLTAGE CONTROL CONNECTION
4. LINE VOLTAGE CONNECTION (UNIT)
5. P/T PORTS
6. VIBRATION PAD
7. CONDENSATE DRAIN
8. GROUND LOOP CONNECTION KIT (555-000,001)
9. GROUND LOOP PUMPING PACKAGE (GL001-1 or 002-1)
10. POLYETHELENE WITH INSULATION
11. LINE VOLTAGE DISCONNECT (ELECTRIC HEATER)

NOTE: SEE FIGURE #3 FOR CONDENSATE DRAIN CONNECTION

(Figure #12)
12 AP SERIES

(Figure #13)
AP SERIES 13

TROUBLE SHOOTING

PROBLEM POSSIBLE CAUSE CHECKS AND CORRECTIONS

ENTIRE UNIT DOES Power supply off Apply power, close disconnect
NOT RUN Blown fuse Replace fuse or reset circuit breaker. Check for correct fuses.
Voltage supply low If voltage is below minimum voltage specified on unit data plate, contact local power company.

Thermostat Set the fan to "ON", the fan should run. Set thermostat to "COOL" and lowest temperature
setting, the unit should run in the cooling mode (reversing valve energized). Set unit to "HEAT"
and the highest temperature setting, the unit should run in the heating mode. If neither the
blower or compressor run in all three cases, the thermostat could be miswired or faulty.To
ensure miswired or faulty thermostat verify 24 volts is available on the condensing section low
voltage terminal strip between "R" and "C", "Y" and "C", and "O" and "C". If the blower does
not operate, verify 24 volts between terminals "G" and "C" in the air handler. Replace the
thermostat if defective.

BLOWER OPERATES Thermostat Check setting, calibration, and wiring.


BUT COMPRESSOR Wiring Check for loose or broken wires at compressor, capacitor, or contactor.
DOES NOT
Safety controls Check UPM board red default L.E.D. for Blink Code

Compressor overload open If the compressor is cool and the overload will not reset, replace compressor.
Compressor motor grounded Internal winding grounded to the compressor shell. Replace compressor. If compressor
burnout, install suction filter dryer.
Compressor windings open After compressor has cooled, check continuity of the compressor windings. If the windings are
open, replace the compressor.

UNIT OFF ON In "COOLING" mode: Lack of or inadequate water flow. Entering water temperature too warm.
HIGH PRESSURE Discharge pressure too high Scaled or plugged condenser.
CONTROL In "HEATING" mode: Lack of or inadequate air flow. Blower inoperative, clogged filter or
restrictions in ductwork.

Refrigerant charge The unit is overcharged with refrigerant. Reclaim refrigerant, evacuate and recharge with
factory recommended charge.

High pressure Check for defective or improperly calibrated high pressure switch.

UNIT OFF ON Suction pressure too low In "COOLING" mode: Lack of or inadequate air flow. Entering air temperature too cold. Blower
LOW PRESSURE inoperative, clogged filter, or restrictions in ductwork.
In "HEATING" mode: Lack of or inadequate water flow. Entering water temperature too cold.
CONTROL
Scaled or plugged condenser.
Refrigerant charge The unit is low on refrigerant. Check for refrigerant leak, repair, evacuate and recharge with
factory recommended charge.
Low pressure switch Check for defective or improperly calibrated low pressure switch.

UNIT SHORT Unit oversized Recalculate heating and or cooling loads.


CYCLES

Thermostat Thermostat installed near a supply air grill, relocate thermostat. Readjust heat anticipator.

Wiring and controls Loose connections in the wiring or a defective compressor contactor.

INSUFFICIENT Unit undersized Recalculate heating and or cooling loads. If excessive, possibly adding insulation and shading
COOLING OR will rectify the problem.
HEATING Loss of conditioned air Check for leaks in duct work or introduction of ambient air through doors or windows.
by leaks
Airflow Lack of adequate air flow or improper distribution of air. Replace dirty filter.
Refrigerant charge Low on refrigerant charge causing inefficient operation.
Compressor Check for defective compressor. If discharge is too low and suction pressure is too high,
compressor is not pumping properly. Replace compressor.
Reversing valve Defective reversing valve creating bypass of refrigerant from discharge to suction side of
compressor. Replace reversing valve.
Operating pressures Compare unit operating pressures to the pressure / temperature chart for the unit.
TXV Check TXV for possible restriction or defect. Replace if necessary.

Moisture, noncondensables The refrigerant system may be contaminated with moisture or noncondensables. Reclaim
refrigerant, evacuate and recharge with factory recommended charge. Note: a liquid line dryer
may be required.
14 AP SERIES

UNIT CHECK-OUT
SHEET
Customer Data
Customer Name _____________________________________________ Date _________________________________
Address ____________________________________________________
_____________________________________________________
Phone ______________________________________________________ Unit Number__________________________

Unit Nameplate Data


Unit Make ________________________________________
Model Number ____________________________________ Serial Number ________________________________
Refrigerant Charge (oz) _______
Compressor: RLA____________ LRA _____________
Blower Motor: FLA (or NPA)__________ HP ______________
Mximum Fuse Size (Amps) __________
Minimum Circuit Ampacity (Amps) ____________

Operating Conditions
Cooling Mode Heating Mode
Entering / Leaving Air Temp _______________ /_______________ _______________ /_______________
Entering Air Measured at: _______________________________ _______________________________
Leaving Air Measured at: _______________________________ _______________________________
Entering / Leaving Fluid Temp _______________ /_______________ _______________ /_______________
Fluid Flow (gpm) _______________________________ _______________________________
Fluid Side Pressure Drop _______________________________ _______________________________
Suction / Discharge Pressure (psig) _______________ /_______________ _______________ /_______________
Suction / Discharge Temp _______________ /_______________ _______________ /_______________
Suction Superheat _______________________________ _______________________________
Entering TXV / Cap Tube Temp _______________________________ _______________________________
Liquid Subcooling _______________________________ _______________________________
Compressor Volts / Amps _______________ /_______________ _______________ /_______________
Blower Motor Volts / Amps _______________ /_______________ _______________ /_______________

Auxiliary Heat
Unit Make ________________________________________
Model Number ____________________________________ Serial Number _______________________________
Max Fuse Size (Amps) _____________________________
Volts / Amps_____________________ /____________________
Entering Air Temperature ___________________________
Leaving Air Temperature ___________________________
AP SERIES 15

Operating Pressures & Temperatures


Environmentally Safe R-410A Refrigerant

OPERATING DATA
COOLING HEATING
ENTERING WATER SUCTION DISCHARGE WATER AIR SUCTION DISCHARGE WATER AIR
MODEL WATER FLOW PRESSURE PRESSURE TEMP TEMP PRESSURE PRESSURE TEMP TEMP
TEMP. ˚F GPM PSIG PSIG RISE ˚F DROP ˚F PSIG PSIG DROP ˚F RISE ˚F

4 75-91 264-322 5-6 15-17


30˚
8 79-96 270-331 3-4 16-18
40˚ 4 120-146 186-228 14-17 18-21 88-107 277-339 6-7 17-20
8 115-140 175-214 8-9 19-23 92-112 284-348 4-5 18-21
50˚ 4 129-157 218-267 14-17 18-20 98-122 291-356 7-8 20-23
8 124-151 204-250 8-9 19-22 110-130 298-364 5-6 21-24
AP025 60˚ 4 134-163 249-305 13-16 17-20 112-136 304-372 8-10 22-26
Part 8 128-156 233-287 8-9 18-21 117-143 312-381 6-7 23-28
Load 70˚ 4 138-168 281-341 13-16 17-19 124-152 318-389 9-11 24-29
8 133-161 263-323 7-9 18-21 131-159 325-398 6-8 26-31
80˚ 4 143-174 317-388 13-16 16-19 136-166 331-405 11-13 27-32
8 137-167 297-366 7-9 17-20 143-174 339-415 7-9 28-33
90˚ 4 147-179 357-437 13-16 16-18 149-181 345-422 12-14 29-35
8 141-172 335-411 7-9 17-20 156-190 352-432 8-10 31-37
100˚ 4 151-185 402-492 13-15 15-18
8 146-177 378-459 7-9 16-19
30˚ 4 76-92 242-297 3-4 13-14
8 80-97 249-304 2-3 13-15
40˚ 4 125-151 180-221 14-18 19-22 89-108 255-312 4-5 15-17
8 120-146 169-207 8-10 20-23 93-113 261-320 3-3 16-18
50˚ 4 134-163 211-258 14-18 18-21 106-118 267-327 5-6 17-19
8 129-157 198-242 8-10 19-23 104-112 274-335 3-4 18-21
60˚ 4 139-169 241-295 14-17 18-21 113-138 280-342 6-7 19-22
AP025
8 134-163 227-278 8-10 19-22 119-145 287-351 4-5 20-23
Full
Load 70˚ 4 144-175 272-333 14-17 17-20 126-155 292-358 7-8 21-24
8 138-168 255-313 8-10 18-21 133-162 300-367 5-6 22-26
80˚ 4 148-181 307-375 14-17 17-19 138-168 305-373 8-9 23-27
8 143-174 288-353 8-10 18-21 145-177 312-382 5-6 24-29
90˚ 4 153-186 346-423 14-17 16-19 151-184 317-388 8-10 25-29
8 147-179 325-398 8-9 17-20 158-193 325-398 6-7 26-31
100˚ 4 158-191 389-477 13-16 16-18
8 152-185 366-448 8-9 17-20
30˚ 4.5 73-89 266-325 5-6 15-18
9.0 77-94 272-333 3-4 16-19
40˚ 4.5 117-143 189-231 14-17 18-22 86-105 279-341 6-7 17-21
9.0 112-137 178-217 8-9 19-24 90-110 286-350 4-5 18-22
50˚ 4.5 126-154 221-270 14-17 18-21 105-125 293-358 7-8 20-24
9.0 121-148 207-253 8-9 19-23 170-208 300-366 5-6 21-25
60˚ 4.5 131-160 252-308 13-16 17-21 110-134 306-374 8-10 22-27
AP035
9.0 125-153 237-290 8-9 18-22 115-141 314-383 6-7 23-29
Part
70˚ 4.5 135-165 284-347 13-16 17-20 122-150 320-391 9-11 24-30
Load
9.0 130-158 266-326 7-9 18-22 129-157 327-400 6-8 26-32
80˚ 4.5 140-171 320-391 13-16 16-20 134-164 333-407 11-13 27-33
9.0 134-164 300-367 7-9 17-21 141-172 341-417 7-9 28-35
90˚ 4.5 144-176 360-440 13-16 16-19 147-179 347-424 12-14 29-36
9.0 138-169 338-414 7-9 17-21 154-188 355-434 8-10 31-38
100˚ 4.5 149-182 405-495 13-15 15-19
9.0 143-174 381-465 7-9 16-20

This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate
system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data
at entering fluid temperatures below 50º assumes the use of antifreeze.

As a result of continuing research and development, specifications are subject to change without notice.
16 AP SERIES
Operating Pressures & Temperatures
Environmentally Safe R-410A Refrigerant

OPERATING DATA
COOLING HEATING
ENTERING WATER SUCTION DISCHARGE WATER AIR SUCTION DISCHARGE WATER AIR
MODEL WATER FLOW PRESSURE PRESSURE TEMP TEMP PRESSURE PRESSURE TEMP TEMP
TEMP. ˚F GPM PSIG PSIG RISE ˚F DROP ˚F PSIG PSIG DROP ˚F RISE ˚F

4.5 74-90 244-299 3-4 13-15


30˚
9.0 78-95 251-306 2-3 13-16
40˚ 4.5 122-149 183-224 14-18 19-23 87-106 257-314 4-5 15-18
9.0 117-143 172-210 8-10 20-24 91-111 263-322 3-3 16-19
50˚ 4.5 131-160 214-261 14-18 18-22 95-105 269-329 5-6 17-20
9.0 126-154 201-245 8-10 19-24 100-125 276-337 3-4 18-22
AP035 60˚ 4.5 136-166 244-298 14-17 18-22 111-136 282-344 6-7 19-23
Full 9.0 131-160 230-281 8-10 19-23 117-143 289-353 4-5 20-24
Load 70˚ 4.5 141-172 275-336 14-17 17-21 124-152 294-360 7-8 21-25
9.0 135-165 258-316 8-10 18-22 131-160 302-369 5-6 22-27
80˚ 4.5 145-178 310-378 14-17 17-20 136-166 307-375 8-9 23-28
9.0 140-171 291-356 8-10 18-22 143-175 314-384 5-6 24-30
90˚ 4.5 150-183 349-426 14-17 16-20 149-182 319-390 8-10 25-30
9.0 144-176 328-401 8-9 17-21 156-191 327-400 6-7 26-32
100˚ 4.5 155-189 392-480 13-16 16-19
9.0 149-182 369-451 8-9 17-21
30˚ 6.0 64-78 248-303 5-6 15-18
12.0 67-82 254-311 3-4 16-19
40˚ 6.0 109-134 183-224 18-22 19-23 75-91 261-319 6-8 17-21
12.0 105-128 172-210 10-12 20-25 79-96 267-327 4-5 18-23
50˚ 6.0 118-144 214-261 18-22 19-23 78-90 273-334 8-10 20-24
12.0 113-138 201-245 10-12 20-24 82-95 280-342 5-7 21-26
60˚ 6.0 122-149 244-298 17-21 18-22 96-117 286-349 9-11 22-27
AP049
12.0 117-143 230-281 10-12 19-24 101-123 293-358 6-8 24-29
Part
Load 70˚ 6.0 126-154 275-336 17-21 18-22 107-131 299-365 11-13 25-30
12.0 121-148 258-316 10-12 19-23 113-138 306-374 7-9 26-32
80˚ 6.0 130-159 310-378 17-21 17-21 117-143 311-380 12-15 27-33
12.0 132-153 291-356 10-12 18-22 123-151 319-390 8-10 29-35
90˚ 6.0 134-164 349-426 17-20 17-20 128-157 324-396 13-16 29-36
12.0 129-158 328-401 9-12 18-22 135-165 332-406 9-11 31-38
100˚ 6.0 139-170 392-480 16-20 16-20
12.0 133-163 369-451 9-11 17-21
30˚ 6.0 71-87 277-339 6-7 15-19
12.0 75-92 284-347 4-5 16-20
40˚ 6.0 118-144 194-237 21-25 19-23 84-102 291-356 7-9 18-22
12.0 113-138 182-223 12-14 20-24 88-108 299-365 5-6 19-23
50˚ 6.0 127-155 226-276 21-25 18-22 92-110 305-373 9-11 20-25
12.0 122-149 213-260 12-14 19-24 98-120 313-383 6-7 21-26
60˚ 6.0 131-160 259-316 21-25 18-22 108-132 320-391 10-13 23-28
AP049
12.0 126-154 243-297 12-14 19-23 113-138 328-400 7-9 24-29
Full
70˚ 6.0 136-166 291-355 20-25 17-21 120-147 334-408 12-15 25-31
Load
12.0 130-159 273-334 12-14 18-22 126-154 342-418 8-10 27-32
80˚ 6.0 140-171 328-401 20-24 17-20 131-161 348-425 14-17 27-34
12.0 135-165 308-377 11-14 18-22 138-169 356-436 9-11 29-36
90˚ 6.0 145-177 369-451 20-24 16-20 144-176 362-442 15-18 30-37
12.0 139-170 347-424 11-14 17-21 151-185 371-453 10-12 32-39
100˚ 6.0 149-183 415-508 19-24 16-19
12.0 143-175 391-477 11-14 17-21

This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate
system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data
at entering fluid temperatures below 50º assumes the use of antifreeze.

As a result of continuing research and development, specifications are subject to change without notice.
AP SERIES 17
Operating Pressures & Temperatures
Environmentally Safe R-410A Refrigerant

OPERATING DATA
COOLING HEATING
ENTERING WATER SUCTION DISCHARGE WATER AIR SUCTION DISCHARGE WATER AIR
MODEL WATER FLOW PRESSURE PRESSURE TEMP TEMP PRESSURE PRESSURE TEMP TEMP
TEMP. ˚F GPM PSIG PSIG RISE ˚F DROP˚ F PSIG PSIG DROP ˚F RISE ˚F

7.0 68-84 256-313 5-7 19-23


30˚
14.0 73-89 261-319 4-5 20-25
40˚ 7.0 113-138 172-210 18-22 19-23 81-99 277-339 7-8 22-26
14.0 110-134 161-196 12-14 20-24 86-105 283-346 5-6 23-28
50˚ 7.0 116-142 206-252 17-21 19-23 93-114 299-365 8-9 24-29
14.0 112-137 193-236 12-14 19-24 99-121 305-373 6-7 25-31
AP061 60˚ 7.0 118-145 241-294 17-21 18-23 106-129 321-392 9-11 26-32
Part 14.0 115-140 225-275 11-14 19-23 113-138 327-400 7-8 28-34
Load 70˚ 7.0 121-148 275-336 17-21 18-22 118-145 342-418 10-12 29-35
14.0 117-143 257-314 11-14 19-23 126-154 349-427 8-9 30-37
80˚ 7.0 123-151 309-378 16-20 18-22 131-160 364-444 11-14 31-38
14.0 120-146 289-353 11-13 19-23 139-170 371-454 8-10 33-40
90˚ 7.0 126-154 344-420 16-20 18-22 143-175 385-471 12-15 33-41
14.0 122-149 321-392 11-13 18-22 152-186 393-480 9-11 35-43
100˚ 7.0 128-157 378-462 16-19 17-21
14.0 125-152 353-432 11-13 18-22
30˚ 7.0 68-84 256-313 5-7 19-23
14.0 73-89 261-319 4-5 20-25
40˚ 7.0 117-143 182-222 15-19 21-26 81-99 277-339 7-8 22-26
14.0 114-139 170-208 11-14 22-27 86-105 283-346 5-6 23-28
50˚ 7.0 120-147 215-263 15-18 20-25 93-114 299-365 8-9 24-29
14.0 117-143 201-246 11-14 21-26 99-121 305-373 6-7 25-31
60˚ 7.0 123-150 248-304 14-17 20-24 106-129 321-392 9-11 26-32
AP061
14.0 119-146 232-284 11-13 21-25 113-138 327-400 7-8 28-34
Full
Load 70˚ 7.0 126-154 282-344 14-17 19-24 118-145 342-418 10-12 29-35
14.0 122-149 263-322 10-13 20-25 126-154 349-427 8-9 30-37
80˚ 7.0 129-157 315-385 13-16 19-23 131-160 364-444 11-14 31-38
14.0 125-153 294-360 10-12 19-24 139-170 371-454 8-10 33-40
90˚ 7.0 132-161 348-426 13-16 18-22 143-175 385-471 12-15 33-41
14.0 128-156 326-398 10-12 19-23 152-186 393-480 9-11 35-43
100˚ 7.0 134-164 382-466 12-15 17-21
14.0 131-160 357-436 9-11 18-22
30˚ 9.0 71-87 259-316 5-7 19-23
18.0 76-92 264-322 4-5 20-25
40˚ 9.0 116-141 175-213 18-22 19-23 84-102 280-342 7-8 22-26
18.0 113-137 164-199 12-14 20-24 89-108 286-349 5-6 23-28
50˚ 9.0 119-145 209-255 17-21 19-23 96-117 302-368 8-9 24-29
18.0 115-140 196-239 12-14 19-24 102-124 308-376 6-7 25-31
60˚ 9.0 121-148 244-297 17-21 18-23 109-132 324-395 9-11 26-32
AP071
18.0 118-143 228-278 11-14 19-23 116-141 330-403 7-8 28-34
Part
70˚ 9.0 124-151 278-339 17-21 18-22 121-148 345-421 10-12 29-35
Load
18.0 120-146 260-317 11-14 19-23 129-157 352-430 8-9 30-37
80˚ 9.0 126-154 312-381 16-20 18-22 134-163 367-447 11-14 31-38
18.0 123-149 292-356 11-13 19-23 142-173 374-457 8-10 33-40
90˚ 9.0 129-157 347-423 16-20 18-22 146-178 388-474 12-15 33-41
18.0 125-152 324-395 11-13 18-22 155-189 396-483 9-11 35-43
100˚ 9.0 131-160 381-465 16-19 17-21
18.0 128-155 356-435 11-13 18-22

This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate
system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data
at entering fluid temperatures below 50º assumes the use of antifreeze.

As a result of continuing research and development, specifications are subject to change without notice.
18 AP SERIES
Operating Pressures & Temperatures
Environmentally Safe R-410A Refrigerant

OPERATING DATA
COOLING HEATING
ENTERING WATER SUCTION DISCHARGE WATER AIR SUCTION DISCHARGE WATER AIR
MODEL WATER FLOW PRESSURE PRESSURE TEMP TEMP PRESSURE PRESSURE TEMP TEMP
TEMP. ˚F GPM PSIG PSIG RISE ˚F DROP ˚F PSIG PSIG DROP ˚F RISE ˚F

30˚ 9.0 71-87 259-316 5-7 19-23


18.0 76-92 264-322 4-5 20-25
40˚ 9.0 120-146 185-225 15-19 21-26 84-102 280-342 7-8 22-26
18.0 117-142 173-211 11-14 22-27 89-108 286-349 5-6 23-28
50˚ 9.0 123-150 218-266 15-18 20-25 96-117 302-368 8-9 24-29
18.0 120-146 204-249 11-14 21-26 102-124 308-376 6-7 25-31
AP071 60˚ 9.0 126-153 251-307 14-17 20-24 109-132 324-395 9-11 26-32
Full 18.0 122-149 235-287 11-13 21-25 116-141 330-403 7-8 28-34
Load 70˚ 9.0 129-157 285-347 14-17 19-24 121-148 345-421 10-12 29-35
18.0 125-152 266-325 10-13 20-25 129-157 352-430 8-9 30-37
80˚ 9.0 132-160 318-388 13-16 19-23 134-163 367-447 11-14 31-38
18.0 128-156 297-363 10-12 19-24 142-173 374-457 8-10 33-40
90˚ 9.0 135-164 351-429 13-16 18-22 146-178 388-474 12-15 33-41
18.0 131-159 329-401 10-12 19-23 155-189 396-483 9-11 35-43
100˚ 9.0 137-167 385-469 12-15 17-21
18.0 134-163 360-439 9-11 18-22

This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate
system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data
at entering fluid temperatures below 50º assumes the use of antifreeze.

As a result of continuing research and development, specifications are subject to change without notice.
AP SERIES 19

NOTES
AP SERIES

REV. 2/08
FHP MANUFACTURING

PARTS PRICE LIST

All models in this price sheet reflect our current vintage. For discontinued models please contact the
factory. To ensure you receive the correct part please have the full model and serial number available.

Prices contained herein are to be used with parts multipliers only . These price sheets should be used solely for parts prices
only. Do not use this price sheet for installed cost for any of the items contained. Consult equipment price sheets or contact
FHP customer service for installed costs.

While every effort has been made to ensure the accuracy of this parts list changes in our vendors may
necessitate part substitutions. Please check with FHP Customer Service for the latest information.

REV 2/08
Page 1
EFFECTIVE 1/2006
MODEL NOMENCLATURE

VERTICAL, HORIZONTAL, SPLITS, AND WATER TO WATER UNITS

1 2 3 4 5 6 7 8 9 10 11 12 13 14
E M 0 3 1 - 1 V T C - F L T

SERIES:
SUPPLY AIR LOCATION:
AP - AQUARIUS II R-410A
EC- AQUARIUS R-410A T - TOP
EM- ENERGY MISER r-22 F - FRONT
ES - ENVIROSAVER r-410a R - REAR
EV- ENVIROMISER r-410a S - STRAIGHT THRU
GS- GEO-SAVER R-22 E - END BLOW
GT- GEO-THERMAL R-22 B - BOTTOM
MB- MODULAR AIR R-22
WP- WATER TO WATER R-22
WW- WATER TO WATER - 410A
NOMINAL CAPACITY:
RETURN AIR LOCATION:
THOUSANDS OF BTUH
L - LEFT
R - RIGHT
ELECTRICAL CONFIGURATIONS B - BACK ("VT" CABINET ONLY)
0 - 115/1/60 F - FRONT ("VT" CABINET ONLY)
1 - 208-230/1/60
2 - 277(265)/1/60 WATER CONNECTION LOCATION:
3 - 208-230/3/60
4 - 460/3/60 F - FRONT
5 - 575/3/60 S - SIDE
8 - 220-240/1/50
A - 380-415/3/50 WATER COIL OPTIONS:
CABINET CONFIGURATIONS:
C - COPPER
VT - VERTICAL N - CUPRO-NICKEL
HZ - HORIZONTAL
CF - COUNTERFLOW
CS - CONDENSING SECTION OR WATER TO WATER UNIT
AH - HORIZONTAL AIR HANDLER
AV - VERTICAL AIR HANDLER

CONSOLE SERIES MODEL NOMENCLATURE


1 2 3 4 5 6 7 8 9 10 11 12 13 14
C A 0 0 9 - 1 U L C - X X X

SERIES: NOT USED:


CA - CONSOLE SERIES R-410A SLOPE TOP
CS - CONSOLE SERIES R-22 SLOPE TOP WATER COIL OPTIONS:

NOMINAL CAPACITY: C - COPPER


N - CUPRO-NICKEL
THOUSANDS OF BTUH

ELECTRICAL CONFIGURATIONS: WATER CONNECTION


0 - 115/1/60 L - LEFT
1 - 208-230/1/60 R - RIGHT
2 - 277(265)/1/60
8 - 220-240/1/50
CONTROL OPTIONS:
U - CONSOLE UNIT CONTROLLER (CUC) UNIT MOUNTED
R - REMOTE THERMOSTAT
S - MASTER/SLAVE OPERATION
REV 2/08 Page 4
FHP WARRANTY CODE / SERIAL NUMBER IDENTIFICATION

FIRST LETTER IS THE YEAR

1994 1995 1996 1997 1998 1999 2000 2001 2002


A B C D E F G H J
1971 1972 1973 1974 1975 1976 1977 1978 1979

2003 2004 2005 2006 2007 2008 2009 2010 2011


K L M N P R S T U
1980 1981 1982 1983 1984 1985 1986 1987 1988

2012 2013 2014 2015 2016


V W X Y Z
1989 1990 1991 1992 1993

SECOND LETTER IS THE MONTH

A JANUARY G JULY
B FEBRUARY H AUGUST
C MARCH J SEPTEMBER
D APRIL K OCTOBER
E MAY L NOVEMBER
F JUNE M DECEMBER

EXAMPLE: DC0123456 where D = 1997 OR 1974 & C = MARCH

IF THERE IS DOUBT IN THE YEAR THAT A UNIT WAS BUILT PLEASE CONTACT FHP CUSTOMER SERVICE FOR VERIFICATION

REV 2/08 Page 3


FHP Manufacturing Co.
Parts Price List
While every effort has been made to ensure the accuracy of this parts list changes in our vendors may necessitate part substitutions.
Please check with FHP Customer Service for latest information.

Index:

INDEX……………………………………… 2 ES018 - ES071, AU025 - AU071………………………… 18


FHP WARRANTY CODE………………… 3 EV018 - EV070…………………………………………… 19
NOMENCLATURE……………………… 4 GS018 - GS070…………………………………………… 20
AP025 - AP071 …………………………… 5 GT010 - GT070…………………………………………… 21
CA009 - CA018…………………………… 6 MB360 - MB720………………………………………...… 22
CS009 - CS018…………………………… 7 MB-Components Per Unit………………………………… 23
EC007 - EC042…………………………… 8 WP018, 036 - WP420…………………………………… 24
EC048 - EC070…………………………… 9 WH / WP-Components Per Unit………………………… 25
EC072 - EC360…………………………… 10 WW024 - WW420………………………………………… 26
EC-Components Per Unit………………… 11 WW-Components Per Unit……………………………… 27
EM007 - EM042…………………………… 12 Compressors…………………………………….. 28
EM048 - EM070…………………………… 13 Air Evaporators, Water Condensers…………………… 29
EM072 - EM168…………………………… 14 Blowers, Motors…………………………………………… 30
EM170 - EM360…………………………… 15 Reversing Valves, Cap Tubes, TXV's…………………… 31
EM-Components Per Unit……………… 16 Contactors, Transformers, Capacitors………………… 32
EM-Components Per Unit (2)…………… 17 Common Parts………………………………………… 33

REV 2/08
Page 2
Comp. Comp. Air Water Reversing
Model Compressor Blower Motor Transformer TXV
Capacitor Contactor Evaporator Condenser Valve
VT 200-040 CU 300-133 * 850-009
AP025-1 105-489 700-018 601-040 410-021 450-143 500-003 603-022
HZ 200-029 CN 300-132 ** 850-040
AP035-1 105-413 700-025 601-040 VT 200-031 410-021 450-119 CU 300-128 500-003 603-022 * 850-009
VT 200-043 CU 300-130 * 850-033
AP049-1 105-414 700-027 601-007 410-031 450-120 500-006 603-022
HZ 200-030 CN 300-131 ** 850-042
VT 200-063 CU 300-160 * 850-008
AP061-1 105-415 700-047 601-007 410-026 450-120 500-005 603-022
HZ 200-064 CN 300-162 ** 850-055
VT 200-063 CU 300-161 * 850-008
AP071-1 105-490 700-047 601-007 410-023 450-142 500-005 603-022
HZ 200-064 CN 300-163 ** 850-055
* REPRESENTS DISTRIBUTOR
** REPRESENTS TXV

REV 2/08
Page 5

You might also like