12.1.

FEUILLES DES DONNEES DES VANNES DE SECTIONNEMENT A COMMANDE


PNEUMATIQUES POUR LA DESHYDRATATION PRINCIPAL .

ON-OFF VALVE SPECIFICATIONS


1 Tag Number XV701
OUTLET LPG DRYER REGEN 440/6202A
1-GENERAL 2 Function
DATA 3 Quantity 01
4 Line No. 6" D3U 737 FG H50
5 Line Size Schedule 6’’ Sch 40

6 Body Type Ball valve


7 Body Size 6"
8 Rating End Connections. ANSI300 # RF FLG
2-BODY
9 Mounting position vertical
10 Body /Bonnet Material A 216 Gr.WCB
11 Trim Material: Seat Ball/ Disc metal Ball
12 Trim Characteristic ON - OFF
13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
3-ACTUATOR 16 Mounting Type I Supply On Valve I AIR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State LPG Liquid
21 Fluid density kg/m3 501.3
4-SERVICE 22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C OPER Design 250 300
25 Pressure kg/cm2 oper Design 11 16
26 Flow Kg/hr Norm Max
27 Solenoid Valve Yes
28 Filter Reducer Yes
29 Supply 110 VDC 0.1A
5- SOLENOID VALVE 30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
33 Cable Entry 1/2" NPTF for double compression explosionproof gland

34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve

7- Electrical protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum


ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV704
OUTLET LPG DRYER REGEN 440/6202B
1-GENERAL 2 Function
DATA 3 Quantity 01

4 Line No. 6" D3U 730 FG H50

5 Line Size Schedule 6" Sch 40

6 Body Type Ball valve

7 Body Size 6"


2-BODY 8 Rating End Connections. 300 # RF FLG

9 Mounting position vertical

10 Body /Bonnet Material A 216 Gr.WCB

11 Trim Material: Seat Ball / Disc metal *

12 Trim Characteristic ON - OFF

13 Required Seat Tightness ANSI Class VI

14 Max Allowable sound Level 85 dBA

15 Type of Actuator Spring Diaphragm or Rack Pinion


3-ACTUATOR Mounting Type I Supply On Valve I AIR
16

17 Failsafe Position Of Valve CLOSE

18 Close At | Open At Barg 0.2 1.0

19 Handwheel Required

20 Fluid Fluid State LPG Liquid

21 Fluid density kg/m3 501.3


4-SERVICE
CONDITIONS 22 Fluid viscosity

23 Fluid Molecular Weight


24 Temperature C° oper Design 250 300
25 Pressure kg/cm2 oper Design 11 16
26 Flow Kg/hr Norm

27 Solenoid Valve Yes

28 Filter Reducer Yes

29 Supply 110 VDC 0.1A

30 Quantity 1
5- SOLENOID VALVE
31 Nb of way 3 Ways

32 Quantity 1

1/2" NPTF for double compression explosion proof


33 Cable Entry gland

34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve

7- Electrical protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum


ON-OFF VALVE SPECIFICATIONS

1 Tag Number XV705


INLET LPG DRYER LPG 440/6202A
1-GENERAL 2 Function
DATA
3 Quantity 01

4 Line No. 10" D3U 702 PX H65

5 Line Size Schedule 10" Sch 40

6 Body Type Ball valve

7 Body Size 10"


2-BODY
8 Rating End Connections. 300 # RF FLG

9 Mounting Position vertical

10 Body /Bonnet Material A 216 Gr.WCB

11 Trim Material: Seat Ball/Disc PTFE 13Cr

12 Trim Characteristic ON - OFF

13 Required Seat Tightness ANSI Class VI

14 Max Allowable sound Level 85 dBA

15 Type of Actuator Spring Diaphragm or Rack Pinion

16 Mounting Type I Supply On Valve I AIR


3-ACTUATOR
17 Failsafe Position Of Valve CLOSE

18 Close At | Open At Barg 0.2 1.0

19 Handwheel Required

20 Fluid Fluid State LPG Liquid

4-SERVICE 21 Fluid density kg/m3 501.3


CONDITIONS
22 Fluid viscosity

23 Fluid Molecular Weight


10 to 38 65
24 Temperature C° OPER Design

Pressure kg/cm2 oper Design


24 39
25

26 Flow Kg/hr Norm

27 Solenoid Valve Yes

28 Filter Reducer Yes

29 Supply 110 VDC 0.1A

30 Quantity 1
5- SOLENOID VALVE
31 Nb of way 3 Ways

32 Quantity 1

1/2" NPTF for double compression explosion proof


33 Cable Entry gland

34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve

7- Electrical protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum


ON-OFF VALVE SPECIFICATIONS

1 Tag Number XV 708


INLET LPG DRYER LPG 440/6202B
1-GENERAL 2 Function
DATA
3 Quantity 01

4 Line No. 10" D3U 703 PX H65

5 Line Size Schedule 10" Sch 40

6 Body Type Ball valve

7 Body Size 10"


2-BODY
8 Rating End Connections. 300 # RF FLG

9 Mounting Position vertical

10 Body /Bonnet Material A 216 Gr.WCB

11 Trim Material: Seat ball/Disc PTFE 13Cr

12 Trim Characteristic ON - OFF

13 Required Seat Tightness ANSI Class VI

14 Max Allowable sound Level 85 dBA

15 Type of Actuator Spring Diaphragm or Rack Pinion

16 Mounting Type I Supply On Valve I AIR


3-ACTUATOR
17 Failsafe Position Of Valve CLOSE

18 Close At | Open At Barg 0.2 1.0

19 Handwheel Required
LPG Liquid
20 Fluid Fluid State

4-SERVICE 21 Fluid density kg/m3 501.3


CONDITIONS
22 Fluid viscosity

23 Fluid Molecular Weight


10 to 38 65
24 Temperature °C oper Max Design

Pressure kg/cm2 oper Max Design


24 39
25

26 Flow Kg/hr Norm Max

27 Solenoid Valve Yes

28 Filter Reducer Yes

29 Supply 110 VDC 0.1A

30 Quantity 1
5- SOLENOID VALVE
31 Nb of way 3 Ways

32 Quantity 1
1/2" NPTF for double compression explosion proof
33 Cable Entry gland

34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve

7- Electrical protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum


ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV 709

OUTLET LPG DRYER LPG 440/6202A


2 Function
1-GENERAL
DATA
3 Quantity 01

4 Line No. 10" D3U 704 PX H65

5 Line Size Schedule 10" Sch 40

6 Body Type Ball valve

7 Body Size 10"

2-BODY 8 Rating End Connections. 300 # RF FLG

9 Mounting position vertical

10 Body /Bonnet Material A 216 Gr.WCB

11 Trim Material: Seat Ball/Disc PTFE *

12 Trim Characteristic ON - OFF

13 Required Seat Tightness ANSI Class VI

14 Max Allowable sound Level 85 dBA

15 Type of Actuator Spring Diaphragm or Rack Pinion


16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE

18 Close At | Open At Barg 0.2 1.0

19 Handwheel Required

Fluid Fluid State LPG Liquid


20

21 Fluid density kg/m3 501.3


4-SERVICE
CONDITIONS 22 Fluid viscosity

23 Fluid Molecular Weight

24 Temperature oper °C 10 to 38 65
Design

25 Pressure kg/cm2 oper Design


24 39

26 Flow Kg/hr
Norm
27 Solenoid Valve Yes

28 Filter Reducer Yes


5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A

30 Quantity 1

31 Nb of way 3 Ways

32 Quantity 1
6- LIMIT 33 Cable Entry 1/2" NPTF for double compression explosion proof
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV 712
2 Function OUTLET LPG DRYER LPG 440/6202B
1-GENERAL 3 Quantity 01
DATA
4 Line No. 10" D3U 705 PX H65
5 Line Size Schedule 10" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Ball Valve
8 Body Size 10"
09 Mounting position vertical
2-BODY
10 Body /Bonnet Material A 216 Gr.WCB
11 Trim Material: Seat Disc PTFE *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State LPG Liquid
21 Fluid density kg/m3 501.3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Température °C oper Design 10 to 38 65
25 Pressure kg/cm2 oper Design 24 39

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A
30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
6- LIMIT 1/2" NPTF for double compression explosion proof
33 Cable Entry
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV 713
2 Function INLET LPG DRYER REGEN 440/6202A
1-GENERAL 3 Quantity 01
DATA 6" D3U 727 FG H50
4 Line No.
5 Line Size Schedule 6" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Ball Valve
8 Body Size 6"
09 Mounting position vertical
2-BODY
10 Body /Bonnet Material A 216 Gr.WCB
11 Trim Material: Seat Disc metal *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State LPG Liquid
21 Fluid density kg/m3 501.3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 250 300
25 Pressure kg/cm2 oper Design 11 16
26 Flow Kg/hr Norm
27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A
30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
6- LIMIT 1/2" NPTF for double compression explosion proof
33 Cable Entry
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV 715

2 Function DRAIN DRYER 440/6202A


1-GENERAL
DATA 3 Quantity 01
4 Line No. 4" D3U 708 PX H45
5 Line Size Schedule 4" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Ball Valve
8 Body Size 4"
09 Mounting position Vertical
2-BODY
10 Body /Bonnet Material A 216 Gr.WCB
11 Trim Material: Seat Disc PTFE *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State LPG Liquid
21 Fluid density kg/m3 501.3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 10 to 38 65
25 Pressure kg/cm2 oper Design 24 39

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A
30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
6- LIMIT 1/2" NPTF for double compression explosion proof
33 Cable Entry
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV 716
INLET LPG DRYER REGEN 440/6202B
2 Function
1-GENERAL
3 Quantity 01
DATA
4 Line No. 6" D3U 728 FG H50
5 Line Size Schedule 6" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Ball Valve
8 Body Size 6"
09 Mounting position vertical
2-BODY
10 Body /Bonnet Material A 216 Gr.WCB
11 Trim Material: Seat Disc metal *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State LPG Liquid
21 Fluid density kg/m3 501.3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 250 300
25 Pressure kg/cm2 oper Design 11 16

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A
30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
6- LIMIT 1/2" NPTF for double compression explosion proof
33 Cable Entry
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV 720
2 Function DRAIN DRYER 440/6202B
1-GENERAL 3 Quantity 01
DATA 4" D3U 709 PX H45
4 Line No.
5 Line Size Schedule 4" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Ball Valve
8 Body Size 4"
09 Mounting position vertical
2-BODY
10 Body /Bonnet Material A 216 Gr.WCB
11 Trim Material: Seat Disc PTFE *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State LPG Liquid
21 Fluid density kg/m3 501.3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 10 to 38 65
25 Pressure kg/cm2 Oper Design 24 39

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A
30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
6- LIMIT 1/2" NPTF for double compression explosion proof
33 Cable Entry
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV 721
2 Function FILL LINE DRYER 440/6202A
1-GENERAL 3 Quantity 01
DATA 4 Line No. 3’’ D3U 1018 PX
5 Line Size Schedule 3" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Ball Valve
8 Body Size 3"
09 Mounting position vertical
2-BODY
10 Body /Bonnet Material A 216 Gr.WCC CAST STEEL
11 Trim Material: Seat Disc PTFE *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State GPL Liquid
21 Fluid density kg/m3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 10 to 38 65

25 Pressure kg/cm2 oper Design 24 39

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A
30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
6- LIMIT 1/2" NPTF for double compression explosion proof
33 Cable Entry
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number XV 722

2 Function FILL LINE DRYER 440/6202B


1-GENERAL
DATA 3 Quantity 01
4 Line No. 3’’ D3U 1019 PX
5 Line Size Schedule 3" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Ball Valve
8 Body Size 3"
09 Mounting position VERTICAL
2-BODY
10 Body /Bonnet Material A 216 Gr.WCC CAST STEEL
11 Trim Material: Seat Disc P¨TFE *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State GPL Liquid
21 Fluid density kg/m3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 10 to 38 65

25 Pressure kg/cm2 oper Design 24 39

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A
30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
6- LIMIT 1/2" NPTF for double compression explosion proof
33 Cable Entry
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number HV 701
2 Function FOR LEVEL CONTROL 440/6203 SUMP OUTLET
1-GENERAL 3 Quantity 01
DATA 2" D1Z 723 OS
4 Line No.
5 Line Size Schedule 2" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type ball Valve
8 Body Size 2"
09 Mounting position horizontal
2-BODY
10 Body /Bonnet Material WCB
11 Trim Material: Seat Disc PTFE *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State LPG Liquid
21 Fluid density kg/m3 501.3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 10 to 38 65

25 Pressure kg/cm2 Norm Design atm atm

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID
VALVE 29 Supply 110 VDC 0.1A
30 Quantity 1
31 Nb of way 3 Ways
32 Quantity 1
6- LIMIT 1/2" NPTF for double compression explosion proof
33 Cable Entry
SWITCHES gland
34 Quantity of contacts 2 (ZSO & ZSC)/ For Valve
7- Electrical
protection 35 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number HV 705
2 Function FILL LINE DRYER LPG 440/6202A
1-GENERAL 3 Quantity 01
DATA 2" D3U 739 FG
4 Line No.
5 Line Size Schedule 2" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Gate Valve
8 Body Size 1"
09 Mounting position horizontal
2-BODY
10 Body /Bonnet Material WCB
11 Trim Material: Seat Disc PTFE *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State FG GAS
21 Fluid density kg/m3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 10 to 38 65

25 Pressure kg/cm2 oper Design 24 39

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID 29 Supply 110 VDC 0.1A
VALVE
30 Quantity 1
31 Nb of way 3 Ways
32 1/2" NPTF for double compression explosion proof
Cable Entry
gland
33 Quantity 1
34 1/2" NPTF for double compression explosion proof
FEEDBACK Cable Entry
gland
35
Positioner Out put 4-20ma
7- Electrical
protection 36 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum
ON-OFF VALVE SPECIFICATIONS
1 Tag Number HV 706
2 Function FILL LINE DRYER LPG 440/6202B
1-GENERAL 3 Quantity 01
DATA 2" D3U 740 FG
4 Line No.
5 Line Size Schedule 2" Sch 40

6 Rating End Connections. 300 # RF FLG


7 Body Type Gate Valve
8 Body Size 1"
09 Mounting position horizontal
2-BODY
10 Body /Bonnet Material WCB
11 Trim Material: Seat Disc PTFE *

12 Trim Characteristic ON - OFF


13 Required Seat Tightness ANSI Class VI
14 Max Allowable sound Level 85 dBA
15 Type of Actuator Spring Diaphragm or Rack Pinion
16 Mounting Type I Supply On Valve I AIR
3-ACTUATOR
17 Failsafe Position Of Valve CLOSE
18 Close At | Open At Barg 0.2 1.0
19 Handwheel Required
20 Fluid Fluid State FG GAS
21 Fluid density kg/m3
4-SERVICE
22 Fluid viscosity
CONDITIONS
23 Fluid Molecular Weight
24 Temperature °C oper Design 10 to 38 65

25 Pressure kg/cm2 oper Design 24 39

26 Flow Kg/hr Norm


27 Solenoid Valve Yes
28 Filter Reducer Yes
5- SOLENOID 29 Supply 110 VDC 0.1A
VALVE
30 Quantity 1
31 Nb of way 3 Ways
32 1/2" NPTF for double compression explosion proof
Cable Entry
gland
33 Quantity 1
34 1/2" NPTF for double compression explosion proof
FEEDBACK Cable Entry
gland
35
Positioner Out put 4-20ma
7- Electrical
protection 36 Solenoid Valve/ Limit Switches EEx d IIA T4 / IP 65 minimum