Date Test Protocol

Operational Qualification

Page: 1 of: 1
AFGUARD® installation with ………..

Location:

Test protocol for AFGUARD® installation with ……………………..


ok

Requirements: System must be switched on, loop tester installed instead of AFGUARD®

Pre-test (no button pressed)

Function test for 4 mA base signal of AFGUARD® sensor


No further interaction (do not press any function button)
Output 4 mA or 0 ppm

Test 1: Fail safe test AFGUARD® -> signal output << 4 mA – blue lamp off
Function test for NAMUR 1
Press F1:
Output: Immediate reply (LED F1 constantly on) – blue lamp should be off (no blinking)

Test 2: Warning level -> signal output representing > 15 ppm – slow blinking blue lamp
Function test for warning level
Press F2 for warning level (15 ppm < water level < 30 ppm)
Output: LED blinking -> after _10__ seconds LED constantly on - blue lamp blinking slowly

Test 3: Alarm level -> signal output representing > 30 ppm – fast blinking blue lamp
Function test for alarm level
Press F3 for alarm level (water level > 30 ppm)
Output: LED blinking -> after _10__ seconds LED constantly on

Test 4: Water slug indication -> signal output >> 20 mA – fast blinking blue lamp
Function test for water slug indication
Press F4 for water slug (water level >> 50 ppm)
Output: LED blinking -> after _5__ seconds LED constantly on

Test 5: AFGUARD® broken wire -> no mA signal – blue lamp off


Disconnect the AFGUARD® cable – blue lamp should be off (no blinking)

Remarks:

___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________

Operation Manager Inspector

Name Name

FAUDI Aviation GmbH Loop Test Protocol Rev.03