Output Ratings
Generating Set Model P135 P150E
Prime* Standby*
380-415V, 50 Hz 135 kVA 150 kVA
108 kW 120 kW
480V, 60 Hz 150 kVA 165 kVA
120 kW 132 kW
* Refer to ratings definitions on page 4.
Ratings at 0.8 pf
Technical Data
Engine Make & Model Perkins 1006TAG
Alternator Model LL3014F
Base Frame Type Heavy Duty Fabricated Steel
Frequency 50 Hz 60Hz
Engine Speed 1500 1800
Fuel Tank Capacity: Litres (US Gal) 290 (76.6)
Fuel Consump, P135: L/hr (US Gal/hr) 31.2 (8.2) 38.2 (10.1)
Fuel Consump, P150E: L/hr (US Gal/hr) 34.4 (9.1) 41.5 (11.0)
abcde
FG Wilson (Engineering) Ltd
Old Glenarm Road, Larne, County Antrim BT40 1EJ
Northern Ireland, United Kingdom
Tel: 44 (0) 28 2826 1000 Fax: 44 (0) 28 2826 1111
www.FGWilson.com
P135/P150E
2
P135/P150E
Motor Starting
Capability* kVA 329 309 283 362 360 241 283 264 311
Short Circuit
300 300 300 300 300 300 300 300 300
Capacity** %
Reactances:
Per Unit
Xd 2.64 2.85 3.15 2.18 2.64 4.20 3.51 3.79 3.14
X’d 0.09 0.10 0.11 0.08 0.09 0.15 0.12 0.13 0.11
X”d 0.055 0.059 0.065 0.045 0.055 0.087 0.073 0.079 0.065
Winding Pitch Code: 2/3- (No. 6) Total Harmonic Content LL/LN <4%
Suppression is in line with European
Wires: 12 Radio Interference Standard EN61000-6
3
P135/P150E
Technical Data
3 Phase Ratings and Performance at 50 Hz, 1500 RPM 3 Phase Ratings and Performance at 60 Hz, 1800 RPM
Model: P135 Model: P150E Model: P135 Model: P150E
Voltage Voltage
Prime Standby Prime Standby
kVA kW kVA kW kVA kW kVA kW
415/240 135.0 108.0 150.0 120.0 480/277 150.0 120.0 165.0 132.0
400/230 135.0 108.0 150.0 120.0 440/254 150.0 120.0 165.0 132.0
380/220 135.0 108.0 150.0 120.0 380/220 150.0 120.0 165.0 132.0
230/115 135.0 108.0 150.0 120.0 240/120 150.0 120.0 165.0 132.0
220/127 125.0 100.0 138.0 110.4 230/115 150.0 120.0 165.0 132.0
220/110 135.0 108.0 150.0 120.0 220/127 150.0 120.0 165.0 132.0
200/115 135.0 108.0 150.0 120.0 220/110 150.0 120.0 165.0 132.0
208/120 150.0 120.0 165.0 132.0
240/139 150.0 120.0 165.0 132.0
Definitions
Standby Rating Prime Rating Standard Reference Conditions
These ratings are applicable for supplying con- These ratings are applicable for supplying Note: Standard reference conditions 27˚C
tinuous electrical power (at variable load) in continuous electrical power (at variable load) (80˚F) Air Inlet Temp, 152.4m (500ft) A.S.L.
the event of a utility power failure. No overload in lieu of commercially purchased power. 60% relative humidity. All engine performance
is permitted on these ratings. The alternator There is no limitation to the annual hours of data based on the above mentioned maximum
on this model is peak continuous rated (as operation and this model can supply 10% continuous ratings. Fuel consumption data at
defined in ISO8528-3). overload power for 1 hour in 12 hours. full load with diesel fuel with specific gravity of
0.85 and conforming to BS2869: 1998,
Class A2.
L W
General Data
Documents Generating Set Standards Warranty
A full set of operation and maintenance The equipment meets the following standards: All equipment carries full manufacturer's
manuals, circuit wiring diagrams, and BS5000, ISO 8528, warranty. Extended warranty terms available.
commissioning/fault finding instruction leaflets. ISO 3046, IEC 60034, VDE 0530, NEMA For details on warranty cover please contact
MG-1.22. your local dealer, or visit our website,
www.FGWilson.com
FG Wilson is a fully accredited ISO9001
company.
955-731 In line with our policy of continuous product development, we reserve the right to change specification without notice. P135-P150E/TECHDATA/FGW/0604