Nothing Special   »   [go: up one dir, main page]

Uss - 3,4,13&5 Rev-0 Schudle PB

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 110

Project :- PROJECT ALPHA - NOON KSA SUMMARY 

OF UNIT SUBSTATIONS Area :-
NOON - KSA
FED From :- ---- D & B Contractor :- Amana Contracting

Max
Rating Amps PVC/XLPE Cable Size Connected Load - KW
assumed
MCCB
length of
Cable ECC Size-1C R-Phase
Sr. Fault
(A)
No Circuit Feeder DB no SP/ TP ISO MCB Duty KA Nos 4C mm 2
(Mtrs) mm2 KVA
Incomer

Outgoing

1 USS-3 (1500 KVA) TP ACB 50 XLPE/SWA/PVC 1 3C 120 20 429.29

2 USS-4 (1500 KVA) TP ACB 50 XLPE/SWA/PVC 1 3C 120 20 502.97

3 USS-13 (1500 KVA) TP ACB 50 XLPE/SWA/PVC 1 3C 120 20 394.44

4 USS-5 (1500 KVA) TP ACB 50 XLPE/SWA/PVC 1 3C 120 20 570.48

Total Connected Load per Phase Total…….. 1897.18

Demand Factor = 0.73 Max. Demand = 4134.96 KVA Total connected load 5637.61 KVA

Amana Contracting
Type of Meter : BMS metering
Area :- IYADH SMDB Ref :- --- Owner :-

Location :- TRANSFORMER RM - SER.BLOCK -2

Connected Load - KW KWH Meter

Y-Phase B-Phase Demand 3 Ph 3 Ph LV/HV

KVA KVA Total KVA Total kW ST BY Load KVA 1 Ph (1) (2) (3) CT (4) Remarks

425.91 426.43 1281.62 1153.46 0.00 957.86 1

497.72 493.07 1493.76 1344.38 50.00 1118.25 1

394.44 394.44 1183.33 1065.00 0.00 863.33 1

571.11 562.08 1678.90 1511.02 0.00 1195.52 1

1889.18 1876.02 5637.61 5073.85 50.00 4134.96 0 4 0 0

Actual Load = 5587.61 KVA Stand By Load = 50.00 KVA


Project SMDB Ref :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
FED From :- USS-3 Owner :- NOON - KSA
:- QRM D & B Contractor :- Amana Contracting

Rating Amps PVC/XLPE Cable Size ECC Size Connected Load - KW


Max

Sr. Circuit Feeder DB no SP/ TP ISO MCCB MCB Fault Duty assumed R-Phase Y-Phase
No KA length of KVA KVA
Nos 4C mm2 Cable (Mtrs) Nos 1C mm2
A

Incomer TP ACB 2500 50 MEDIUM VOLTAGE CABLE 3C 120

Outgoing

1 CHILLER -B2-01 TP ACB 1000 36 XLPE/PVC 3 4C 240 49 3 1C 120 176.30 176.30

2 SMDB-F TP 250 36 XLPE/PVC 1 4C 185 120 1 1C 95 54.77 53.57

3 SMDB-H TP 200 36 XLPE/PVC 1 4C 95 45 1 1C 50 38.26 37.28

4 SMDB-J TP 250 36 XLPE/PVC 1 4C 150 67 1 1C 70 52.55 51.35

5 SPARE TP 400 36 XLPE/PVC 74.07 74.07

6 SPARE TP 200 36 XLPE/PVC 33.33 33.33

7 CAP. BANK (CB-3) TP 800 36 XLPE/PVC 2 4C 240 1 1C 240

8 SPACE TP

Total Connected Load per Phase Total…….. 429.29 425.91

Demand Factor = 0.75 Max. Demand = 957.86 KVA Total connected load 1281.62 KVA Actual Load =

2563.24

Amana Contracting
Type of Meter : BMS metering
Area :- RIYADH
Location :- SERVICE BLOCK -2

Connected Load - KW KWH Meter

B-Phase Demand Demand Demand 3 Ph 3 Ph LV/HV Remarks


KVA Load KVA Factor Load KVA (2) (3) CT (4)
Total KVA Total kW (Down stream) (UP stream) 1 Ph (1)

ST BY
1281.62 1

176.30 528.89 476.00 528.89 0.90 476.00 UVR+TIMER+


CONTACTOR

54.13 162.48 146.23 119.83 0.80 95.86

36.52 112.05 100.85 82.50 0.80 66.00

52.07 155.98 140.38 118.06 0.80 94.44

74.07 222.22 200.00 222.22 0.70 155.56

33.33 100.00 90.00 100.00 0.70 70.00


275KVAR WITH
DETUNED FILTER

426.43 1281.62 1153.46 957.86 0 0 0 0 0.00

Actual Load = 1281.62 KVA Stand By Load = 0.00 KVA

2563.24
Project SMDB Ref :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
FED From :- SMDB-F :- NOON
:- USS-3 Owner :- Amana Contracting
D & B Contractor

ECC Size
Rating Amps PVC/XLPE Cable Size Connected Load - KW

Max
assumed
2/4 x 1C length of
MCCB Cable (Mtrs) Nos 1C mm2
mm2
Sr. (A) Fault Duty R-Phase Y-Phase B-Phase
No Circuit Feeder DB no SP/ TP ISO MCB KA 4C mm2 KVA KVA KVA
Incomer TP 250 36 XLPE/PVC 1 4C 185 120 1 1C 95 54.77 53.57 54.13

Outgoing

1 DB-F-L TP 80 25 XLPE/PVC 1 4C 25 60 1 1C 16 11.70 10.72 11.50

2 DB-F-P TP 80 25 XLPE/PVC 1 4C 16 66 1 1C 16 12.89 12.67 12.44

3 SMDB AC-F TP 160 25 XLPE/PVC 1 4C 70 6 1 1C 35 30.19 30.19 30.19

4 SPARE TP 40

5 SPACE

6 SPACE

Total Connected Load per Phase Total…….. 54.77 53.57 54.13

Total connected load


Demand Factor = 0.74 Max. Demand = 119.83 KVA 162.48 KVA Actual Load =

MD CURRENT + 25%

TCL 162.48
Amana Contracting MD 119.83 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 172.96
Area :- RIYADH
Location :- GF WH -BLOCK F

onnected Load - KW KWH Meter

Demand Load Demand Factor Demand


KVA (Down Load KVA
stream) (UP stream)
3 Ph 3 Ph
ST BY
(2) (3)
LV/HV
Total KVA Total kW 1 Ph (1) CT (4) Remarks
162.48

33.92 30.53 32.64 0.90 29.38

38.00 34.20 19.00 0.90 17.10

90.56 81.50 81.50 0.90 73.35

162.48 146.23 0.00 119.83 0 0 0 0

162.48 KVA Stand By Load = 0.00 KVA

216.21
250
Amana Contracting 

Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand

DB Ref :- DB-F-L Owner :- Al Muhaidib Area :- RIYADH, KSA


FED From :- SMDB-F D & B Contractor :- Amana Contracting Loc :- GF-WAREHOUSE BLOC
STATUS)

Rating of Sr. MCB CKT ECC Connected Loads / Points


ELCB No. RTG in Wire Size Wire Size
Amp mm2 mm2 EX 13A 15A Ceiling FCU/V
CKT No. Room / Area Fan S/O S/O Fan AV
LTG Eqpt. SPUR W/H D/W HD ISO

1 R1 16 6.0 6.0 Warehouse- GF , Block F 9


90
2 Y1 16 6.0 6.0 Warehouse- GF , Block F 9
90
3 B1 16 6.0 6.0 Warehouse- GF , Block F 5
85
4 R2 16 SPARE

5 Y2 16 6.0 6.0 Warehouse- GF , Block F 4


110
6 B2 16 6.0 6.0 Warehouse- GF , Block F 4
110
7 R3 16 6.0 6.0 SPARE

8 Y3 16 6.0 6.0 SPARE

9 B3 16 6.0 6.0 Warehouse- GF , Block F 10


120
10 R4 16 6.0 6.0 Warehouse- GF , Block F 10
115
11 Y4 16 6.0 6.0 Warehouse- GF , Block F 10
105
12 B4 16 6.0 6.0 Warehouse- GF , Block F 10
95
13 R5 16 6.0 6.0 Warehouse- GF , Block F 10
90
14 Y5 16 6.0 6.0 Warehouse- GF , Block F 10
88
15 B5 16 6.0 6.0 Warehouse- GF , Block F 10
120
16 R6 16 6.0 6.0 Warehouse- GF , Block F 10
115
17 Y6 16 6.0 6.0 Warehouse- GF , Block F 10
105
18 B6 16 6.0 6.0 Warehouse- GF , Block F 10
95
19 R7 16 6.0 6.0 Warehouse- GF , Block F 10
90
20 Y7 16 6.0 6.0 Warehouse- GF , Block F 10
80
21 B7 16 6.0 6.0 Warehouse- GF , Block F 10
88
22 R8 16 6.0 6.0 Warehouse- GF , Block F 10
90
23 Y8 16 SPARE

24 B8 16 SPARE

25 R9 10 SPARE FOR EM LIGHT

26 Y9 10 SPARE FOR EM LIGHT

27 B9 10 SPARE FOR EM LIGHT

28 R10 10 SPARE FOR EM LIGHT

29 Y10 16 SPARE

30 B10 16 SPARE

Cable Size :
4C 25 mm2 XLPE/PVC Total Load per Phase
+ 16 mm2 ECC

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of TCL

Load after Diversity

6mm2 R 590 3.87 6


6mm2 Y 578 3.79 6
6mm2 B 595 3.9 6
6mm2 Y/G 18
6mm2 B 18
:- RIYADH, KSA
:- GF-WAREHOUSE BLOCK F Rating of Incomer 80A TP INCOMER TO BE MONITOR BY BMS (POWER ON/OFF/TRIP

Demand Load per circuit Diversity


factor kVA Load
Unit KVA Remarks
R Y B

0.26 1.0 2.30 2.30 CONT WITH MANUAL


OVER RIDE
0.26 1.0 2.30 2.30 CONT WITH MANUAL
OVER RIDE

0.26 1.28 CONT WITH MANUAL


OVER RIDE

0.26 1.0 0.00 0.00

0.26 1.0 1.02 1.02 CONT WITH MANUAL


OVER RIDE

0.26 1.0 1.02 1.02 CONT WITH MANUAL


OVER RIDE

0.26 1.00 0.00 0.00

0.26 1.0 0.00 0.00

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

1.0 0.00 0.00

1.0 0.00 0.00

0.26 1.00 0.20 0.20

0.26 1.00 0.20 0.20

0.26 1.00 0.20 0.20

0.26 1.00 0.20 0.20

1.00 0.00 0.00

1.00 0.00 0.00

Total Load per Phase 11.70 10.72 11.50 32.64

Total connected Load (in kVA) 33.92 kVA

Total connected Load current (A) 48.96 A

r current (A) (TCL current +25% of TCL 61.20 A


Current)
Load after Diversity 32.64 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-F-P Details of Connected Load / Max. Demand
From :- SMDB-F 80A TP Owner :- Al Muhaidib
Rating of Incomer :- D & B Contractor :- Amana Contracting

Rating of ELCB Sr. MCB CKT ECC Connected Loads / Points


No. RTG in Wire Wire Size
EX 13A 13A 15A Ceiling 16A
CKT No. Amp Size mm2 Room / Area Fan S/O D/O S/O Fan IND.
mm2 LTG Eqpt. SPUR W/H D/W
S/O

1 R1 ISOLATOR FOR ROLL UP DOOR+DOCK


LEVELER
2 Y1 20 4.0 4.0 85
3 B1
4 R2 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
5 Y2 20 4.0 4.0 75
6 B2
7 R3 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
8 Y3 20 4.0 4.0 50
9 B3
10 R4 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
11 Y4 20 4.0 4.0 50
12 B4
13 R5 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
14 Y5 20 4.0 4.0 70
15 B5
16 R6
17 Y6 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 50 1
18 B6
19 R7
20 Y7 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 85 1
21 B7
22 R8
23 Y8 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 90 1
24 B8
25 R9

26 Y9 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 80 1


27 B9

28 R10

29 Y10 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 75 1


30 B10

31 R11

32 Y11 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 180 1


33 B11

34 R12

35 Y12 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 180 1


36 B12

37 R13

38 Y13 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER


39 B13
110
40 R14

41 Y14 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER 120


42 B14

43 R15

44 Y15 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER 95


45 B15

46 32 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3


R16 150
47 32 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3
Y16 150
48 32 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3
B16 150
49 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 2
R17 150
50 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 1
Y17 150
51 B17 20 SPARE
52 R18 21 SPARE

53 Y18 22 SPARE

54 B18 23 SPARE

Cable Size :
4C 16 mm2 XLPE/PVC Total Load per Phas
+ 16 mm2 ECC

Total connected Load (in kVA

Total connected Load current

Breaker current (A) (TCL current +25

Load after Diver

4mm2 R 1335 8.76 8


4mm2 Y 1095 7.18 8
4mm2 B 1095 7.18 8
4mm2 Y/G 3285 21.5 24
4mm2 Black 3285 21.5 24
4mm2 Spciall 360
4mm2 Y/G 1080
4mm2 Black 1080
Area Loc :- RIYADH, KSA
:- GF-WAREHOUSE BLOCK F

Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
ISO R Y B

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.44 0.5 1.33 0.67

0.44 0.5 1.33 0.67

0.44 0.5 1.33 0.67

0.22 0.5 0.44 0.22

0.22 0.5 0.22 0.11


Total Load per Phase 12.89 12.67 12.44 19.00

Total connected Load (in kVA) 38.00 kVA

Total connected Load current (A) 54.85 A

Breaker current (A) (TCL current +25% of TCL 68.56 A


Current)
Load after Diversity 19.00 kVA
Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
SMDB Ref :- SMDB-AC-F :- NOON

Owner
FED From :- SMDB-F D & B Contractor :- Amana Contracting

Rating Amps PVC/XLPE Cable Size Max ECC Size Connected Load - KW
Sr. Circuit Feeder DB no SP/ TP Fault Duty KA assumed
MCCB 2/4 x 1C
No length of
mm2 R-Phase Y-Phase
ISO MCB 4C mm2 Cable (Mtrs) Nos 1C mm2
(A) KVA KVA

Incomer TP 160 25 XLPE/PVC 1 4C 70 6 1 1C 35 30.19 30.19

Outgoing

1 CP-FAHU-04 TP 100 25 XLPE/PVC 1 4C 50 229 1 1C 25 14.63 14.63

2 AHU-22 TP 40 25 XLPE/PVC 1 4C 16 206 1 1C 16 5.19 5.19

3 AHU-23 TP 40 25 XLPE/PVC 1 4C 16 179 1 1C 16 5.19 5.19

4 AHU-24 TP 40 25 XLPE/PVC 1 4C 10 162 1 1C 10 5.19 5.19

5 SPARE TP 40 25

6 SPACE

Total Connected Load per Phase Total…….. 30.19 30.19

Total connected load


Demand Factor = 0.90 Max. Demand = 81.50 KVA 90.56 KVA Actual Load =

MD CURRENT + 25%

TCL 90.56
Amana Contracting MD 81.50 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 117.64
Area :- RIYADH

Location :- GF WH -BLOCK F

Connected Load - KW KWH Meter


Remarks
Demand Load
B-Phase KVA 3 Ph 3 Ph LV/HV
Total KVA Total kW Demand Factor 1 Ph (1)
KVA (2) (3) CT (4)
ST.BY
30.19 90.56 1

14.63 43.89 39.50 0.90 39.50 TO C.P.

5.19 15.56 14.00 0.90 14.00 TO C.P.

5.19 15.56 14.00 0.90 14.00 TO C.P.

5.19 15.56 14.00 0.90 14.00 TO C.P.

30.19 90.56 81.50 0.00 81.50 0 0 0 0

Actual Load = 90.56 KVA Stand By Load = 0.00 KVA

MD CURRENT + 25% * BMS Interfacing to be provided


* Fire Alarm Interfacing to be provided

147.05
INCOMER BREAKER
SIZE (A) 160
Project SMDB Ref :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
FED From :- SMDB-H :- NOON
:- USS-3 Owner :- Amana Contracting
D & B Contractor

ECC Size
Rating Amps PVC/XLPE Cable Size Connected Load - KW
Max
MCCB assumed
2/4 x 1C length of
Cable (Mtrs) Nos 1C mm2
mm2
Sr. (A) Fault Duty R-Phase Y-Phase B-Phase
No Circuit Feeder DB no SP/ TP ISO MCB KA 4C mm2 KVA KVA KVA
Incomer TP 200 36 XLPE/PVC 1 4C 95 45 1 1C 50 38.26 37.28 36.52

Outgoing

1 DB-H-L TP 80 25 XLPE/PVC 1 4C 25 54 1 1C 16 11.70 10.72 11.52

2 DB-H-P TP 63 25 XLPE/PVC 1 4C 16 58 1 1C 16 11.00 11.00 9.44

3 SMDB AC-H TP 100 25 XLPE/PVC 1 4C 25 6 1 1C 16 15.56 15.56 15.56

4 SPARE TP 40 25 XLPE/PVC

5 SPACE

6 SPACE

Total Connected Load per Phase Total…….. 38.26 37.28 36.52

Total connected load


Demand Factor = 0.74 Max. Demand = 82.50 KVA 112.05 KVA Actual Load =

MD CURRENT + 25%

TCL 112.05
Amana Contracting MD 82.50 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 119.08
Area :- RIYADH
Location :- GF WH -BLOCK H

onnected Load - KW KWH Meter

Demand Load Demand Factor Demand


KVA (Down Load KVA
stream) (UP stream)

3 Ph 3 Ph LV/HV
Total KVA Total kW ST BY 1 Ph (1) (2) (3) CT (4) Remarks
112.05

33.94 30.55 33.94 0.90 30.55

31.44 28.30 15.72 0.90 14.15

46.67 42.00 42.00 0.90 37.80

112.05 100.85 0.00 82.50 0 0 0 0

112.05 KVA Stand By Load = 0.00 KVA

148.85
200
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand

DB Ref :- DB-H-L Owner :- Al Muhaidib Area :- RIYADH, KSA


FED From :- SMDB-H D & B Contractor :- Amana Contracting Loc :- GF-WAREHOUSE BLOCK
STATUS)

Rating of Sr. MCB CKT ECC Connected Loads / Points


ELCB No. RTG in Wire Size Wire Size
Amp mm2 mm2 EX 13A 15A Ceiling FCU/V
CKT No. Room / Area Fan S/O S/O Fan AV
LTG Eqpt. SPUR W/H D/W HD ISO

1 R1 16 6.0 6.0 Warehouse- GF , Block H 9

2 Y1 16 6.0 6.0 Warehouse- GF , Block H 9

3 B1 16 6.0 6.0 Warehouse- GF , Block H 5

4 R2 16 SPARE

5 Y2 16 6.0 6.0 Warehouse- GF , Block H 4

6 B2 16 6.0 6.0 Warehouse- GF , Block H 4

7 R3 16 SPARE

8 Y3 16 SPARE

9 B3 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

10 R4 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

11 Y4 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

12 B4 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

13 R5 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

14 Y5 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

15 B5 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

16 R6 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

17 Y6 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

18 B6 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

19 R7 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

20 Y7 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

21 B7 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

22 R8 16 6.0 6.0 Warehouse- GF , Block H (RACK AISLES) 10

23 Y8 16 SPARE

24 B8 16 SPARE

25 R9 10 SPARE FOR EM LIGHT

26 Y9 10 SPARE FOR EM LIGHT

27 B9 10 SPARE FOR EM LIGHT

28 R10 10 SPARE FOR EM LIGHT

29 Y10 16 SPARE

30 B10 16 SPARE

Cable Size :
4C 25 mm2 XLPE/PVC Total Load per Phase
+ 16 mm2 ECC

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of TCL

Load after Diversity


6mm2 R 7
6mm2 Y 7
6mm2 B 7
6mm2 Y/G 21
6mm2 Black 21
:- RIYADH, KSA
:- GF-WAREHOUSE BLOCK H Rating of Incomer 80A TP INCOMER TO BE MONITOR BY BMS (POWER ON/OFF/TRIP

Demand Load per circuit Diversity


factor kVA Load
Unit KVA Remarks
R Y B

0.26 1.0 2.30 2.30 CONT WITH MANUAL


OVER RIDE

0.26 1.0 2.30 2.30 CONT WITH MANUAL


OVER RIDE
0.26 1.0 1.28 1.28 CONT WITH MANUAL
OVER RIDE

0.26 1.0 0.00 0.00

0.26 1.0 1.02 1.02 CONT WITH MANUAL


OVER RIDE

0.26 1.0 1.04 1.04 CONT WITH MANUAL


OVER RIDE

1.00 0.00 0.00

1.0 0.00 0.00

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

1.0 0.00 0.00

1.0 0.00 0.00

1.00 0.20 0.20 CONT WITH MANUAL


OVER RIDE

1.00 0.20 0.20 CONT WITH MANUAL


OVER RIDE

1.00 0.20 0.20 CONT WITH MANUAL


OVER RIDE

1.00 0.20 0.20 CONT WITH MANUAL


OVER RIDE

1.00 0.00 0.00

1.00 0.00 0.00

Total Load per Phase 11.70 10.72 11.52 33.94

Total connected Load (in kVA) 33.94 kVA

Total connected Load current (A) 48.99 A

r current (A) (TCL current +25% of TCL 61.24 A


Current)
Load after Diversity 33.94 kVA
Amana Contracting 

Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-H-P Details of Connected Load / Max. Demand
From :- SMDB-H 63A TP Owner :- Al Muhaidib
Rating of Incomer :- D & B Contractor :- Amana Contracting

Rating of ELCB Sr. MCB CKT ECC Connected Loads / Points


No. RTG in Wire Wire Size
EX 13A 13A 15A Ceiling
CKT No. Amp Size mm2 Room / Area Fan S/O D/O S/O Fan
mm2 LTG Eqpt. SPUR W/H D/W

1 R1 ISOLATOR FOR ROLL UP DOOR+DOCK LEVELER


2 Y1 20 4.0 4.0 90
3 B1
4 R2 ISOLATOR FOR ROLL UP DOOR+DOCK LEVELER
5 Y2 20 4.0 4.0 110
6 B2
7 R3 ISOLATOR FOR ROLL UP DOOR+DOCK LEVELER
8 Y3 20 4.0 4.0 85
9 B3
10 R4
11 Y4 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 120
12 B4
13 R5
14 Y5 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 95
15 B5
16 R6
17 Y6 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 98
18 B6
19 R7
20 Y7 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 120
21 B7
22 R8
23 Y8 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 125
24 B8
25 R9

26 Y9 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 180


27 B9

28 R10

29 Y10 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 180


30 B10

31 R11

32 Y11 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER 115


33 B11

34 R12
35 Y12 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER 110
36 B12
37 R13

38 Y13 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER 125


39 B13

40 R14 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3


125
41 Y14 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3
160
42 B14 20 SPARE

43 R15 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 1


175
44 Y15 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 1
165
45 B15 20 SPARE

46 R16

47 Y16 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER


48 B16

Cable Size : 4C 16 mm2 XLPE/PVC ECC Total Load per Ph


+ 16 mm2
Cable Size : 4C 16 mm2 XLPE/PVC ECC
+ 16 mm2

Total connected Load (in k

Total connected Load curre

Breaker current (A) (TCL current +

Load after Div

4mm2 R 1383 9.07 10


4mm2 Y 1383 9.07 10
4mm2 B 1383 9.07 10
4mm2 Y/G 4149 27.2 30
4mm2 Black 4149 27.2 30
4mm2 Spciall 360
4mm2 Y/G 1080
4mm2 Black 1080
Area Loc :- RIYADH, KSA
:- GF-WAREHOUSE BLOCK H

s Demand Load per circuit Diversity


factor kVA Load
16A FCU/V
IND. AV Unit KVA Remarks
ISO R Y B
S/O

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 0.56 0.28

1 1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1 1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1 1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1 1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1 1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.44 0.5 1.33 0.67

0.44 0.5 1.33 0.67

0.22 0.5 0.22 0.11

0.22 0.5 0.22 0.11

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

Total Load per Phase 11.00 11.00 9.44 15.72


15.72

Total connected Load (in kVA) 31.44 kVA

Total connected Load current (A) 45.39 A

Breaker current (A) (TCL current +25% of TCL 56.73 A


Current)
Load after Diversity 15.72 kVA
Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand Area :- R
NOON
FED From :- SMDB-H D & B Contractor :- Amana Contracting Location

Max assumed ECC Size


Rating Amps PVC/XLPE Cable Size length of Connected Load - KW
Cable (Mtrs)
Sr.
MCCB Fault Duty KA
No 2/4 x 1C R-Phase Y-Phase
Nos 1C mm2
mm2 KVA KVA
(A)
Circuit Feeder DB no SP/ TP ISO MCB 4C mm2
Incomer TP 100 25 XLPE/PVC 1 4C 25 6 1 1C 16 15.56 15.56

Outgoing

1 AHU-28 TP 40 25 XLPE/PVC 1 4C 10 190 1 1C 10 5.19 5.19

2 AHU-29 TP 40 25 XLPE/PVC 1 4C 10 167 1 1C 10 5.19 5.19

3 AHU-30 TP 40 25 XLPE/PVC 1 4C 10 154 1 1C 10 5.19 5.19

4 SPARE TP 40 25

5 SPARE TP 40 25

6 SPACE

Total Connected Load per Phase Total…….. 15.56 15.56

Demand Factor = 0.90 Total connected 46.67 KVA


Max. Demand = 42.00 KVA load Actual Load = 46.67

MD CURRENT + 25%

TCL 46.67
Amana Contracting MD 42.00 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 60.62
:- RIYADH SMDB Ref :- SMDB-AC-H Owner :-

Location :- GF WH -BLOCK H

Connected Load - KW KWH Meter

B-Phase Demand Load 3 Ph 3 Ph LV/HV


Demand Factor
KVA KVA (2) (3) CT (4)
Total KVA Total kW ST.BY 1 Ph (1) Remarks
15.56 46.67

5.19 15.56 14.00 0.90 14.00 TO C.P.

5.19 15.56 14.00 0.90 14.00 TO C.P.

5.19 15.56 14.00 0.90 14.00 TO C.P.

15.56 46.67 42.00 0.00 42.00 0 0 0 0

Actual Load = 46.67 KVA Stand By Load = 0.00 KVA

MD CURRENT + 25% * BMS Interfacing to be provided


* Fire Alarm Interfacing to be provided

75.78
INCOMER BREAKER
SIZE (A) 100
Project SMDB Ref :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
FED From :- SMDB-J :- NOON
:- USS-3 Owner :- Amana Contracting
D & B Contractor

Rating Amps PVC/XLPE Cable Size Max ECC Size Connected Load - KW
assumed
MCCB 2/4 x 1C length of R-Phase Y-Phase B-Phase
Sr. mm2 Cable (Mtrs) KVA KVA KVA
Circuit Feeder DB no SP/ TP Fault Duty KA
No
ISO MCB 4C mm2 Nos 1C mm2
(A)

Incomer TP 250 36 XLPE/PVC 1 4C 150 67 1 1C 70 52.55 51.35 52.07

Outgoing

1 DB-J-L TP 80 25 XLPE/PVC 1 4C 25 74 1 1C 16 11.70 10.72 11.50

2 DB-J-P TP 63 25 XLPE/PVC 1 4C 16 79 1 1C 16 10.67 10.44 10.39

3 SMDB AC-J TP 160 25 XLPE/PVC 1 4C 70 6 1 1C 35 30.19 30.19 30.19

4 SPARE TP 40 25

5 SPACE

6 SPACE

Total Connected Load per Phase Total…….. 52.55 51.35 52.07

Total connected load


Demand Factor = 0.76 Max. Demand = 118.06 KVA 155.98 KVA Actual Load =

MD CURRENT + 25%
TCL 155.98

Amana Contracting MD 118.06 INCOMER BREAKER


SIZE (A)
Type of Meter : BMS metering MD CURRENT 170.40
Area :- RIYADH
Location :- GF WH -BLOCK J

onnected Load - KW KWH Meter

Demand Load Demand Factor Demand 3 Ph 3 Ph LV/HV


KVA (Down Load KVA (2) (3) CT (4) Remarks
stream) (UP stream)
Total KVA Total kW 1 Ph (1)

ST BY
155.98

33.92 30.53 33.92 0.90 30.53

31.50 28.35 15.75 0.90 14.18

90.56 81.50 81.50 0.90 73.35

155.98 140.38 0.00 118.06 0 0 0 0

155.98 KVA Stand By Load = 0.00 KVA

213.00

250
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand

DB Ref :- DB-J-L Owner :- Al Muhaidib Area :- RIYADH, KSA


FED From :- SMDB-J D & B Contractor :- Amana Contracting Loc :- GF-WAREHOUSE B
STATUS)

Rating of Sr. MCB CKT ECC Connected Loads / Points


ELCB No. RTG in Wire Size Wire Size
Amp mm2 mm2 EX 13A 15A Ceiling
CKT No. Room / Area Fan S/O S/O Fan
LTG Eqpt. SPUR W/H D/W HD ISO

1 R1 16 6.0 6.0 Warehouse- GF , Block J 9

2 Y1 16 6.0 6.0 Warehouse- GF , Block J 9

3 B1 16 6.0 6.0 Warehouse- GF , Block J 5

4 R2 16 SPARE

5 Y2 16 6.0 6.0 Warehouse- GF , Block J 4

6 B2 16 6.0 6.0 Warehouse- GF , Block J 4

7 R3 16 SPARE

8 Y3 16 SPARE

9 B3 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

10 R4 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

11 Y4 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

12 B4 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

13 R5 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

14 Y5 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

15 B5 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

16 R6 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

17 Y6 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

18 B6 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

19 R7 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

20 Y7 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

21 B7 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

22 R8 16 6.0 6.0 Warehouse- GF , Block J (RACK AISLES) 10

23 Y8 16 6.0 6.0 SPARE

24 B8 16 6.0 6.0 SPARE

25 R9 10 SPARE FOR EM LIGHT

26 Y9 10 SPARE FOR EM LIGHT

27 B9 10 SPARE FOR EM LIGHT

28 R10 10 SPARE FOR EM LIGHT

29 Y10 16 SPARE

30 B10 16 SPARE
Cable Size :
4C 25 mm2 XLPE/PVC Total Load per Phase
+ 16 mm2 ECC

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of TCL


+ 16 mm2 ECC

Load after Diversity

6mm2 R 7
6mm2 Y 7
6mm2 B 7
6mm2 Y/G 21
6mm2 Black 21
ea :- RIYADH, KSA
oc :- GF-WAREHOUSE BLOCK J Rating of Incomer 80A TP INCOMER TO BE MONITOR BY BMS (POWER ON/OFF/TRIP

Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
R Y B

0.26 1.0 2.30 2.30 CONT WITH MANUAL


OVER RIDE

0.26 1.0 2.30 2.30 CONT WITH MANUAL


OVER RIDE

0.26 1.0 1.28 1.28 CONT WITH MANUAL


OVER RIDE
0.26 1.0 0.00 0.00

0.26 1.0 1.02 1.02 CONT WITH MANUAL


OVER RIDE

0.26 1.0 1.02 1.02 CONT WITH MANUAL


OVER RIDE

1.00 0.00 0.00

1.0 0.00 0.00

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
0.18 1.0 1.80 1.80 CONT WITH MANUAL
OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE

0.18 1.0 1.80 1.80 CONT WITH MANUAL


OVER RIDE
1.0 0.00 0.00 CONT WITH MANUAL
OVER RIDE

1.0 0.00 0.00 CONT WITH MANUAL


OVER RIDE
0.26 1.00 0.20 0.20 CONT WITH MANUAL
OVER RIDE

0.26 1.00 0.20 0.20 CONT WITH MANUAL


OVER RIDE

0.26 1.00 0.20 0.20 CONT WITH MANUAL


OVER RIDE

0.26 1.00 0.20 0.20 CONT WITH MANUAL


OVER RIDE

0.26 1.00 0.00 0.00

0.26 1.00 0.00 0.00

Total Load per Phase 11.70 10.72 11.50 33.92

Total connected Load (in kVA) 33.92 kVA

Total connected Load current (A) 48.96 A

Breaker current (A) (TCL current +25% of TCL 61.20 A


Current)
Load after Diversity 33.92 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-J-P Details of Connected Load / Max. Demand
From :- SMDB-J 63A TP Owner :- Al Muhaidib
Rating of Incomer :- D & B Contractor :- Amana Contracting

Rating of ELCB Sr. MCB CKT ECC Connected Loads / Points


No. RTG in Wire Wire Size
EX 13A 13A 15A Ceiling 16A
CKT No. Amp Size mm2 Room / Area Fan S/O D/O S/O Fan IND.
mm2 LTG Eqpt. SPUR W/H D/W
S/O

1 R1 ISOLATOR FOR ROLL UP DOOR+DOCK


LEVELER
2 Y1 20 6.0 6.0
3 B1
4 R2 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
5 Y2 20 6.0 6.0
6 B2
7 R3 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
8 Y3 20 6.0 6.0
9 B3
10 R4
11 Y4 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
12 B4
13 R5
14 Y5 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
15 B5
16 R6
17 Y6 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
18 B6
19 R7
20 Y7 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
21 B7
22 R8
23 Y8 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
24 B8
25 R9

26 Y9 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1


27 B9

28 R10

29 Y10 20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1


30 B10

31 R11

32 Y11 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER


33 B11

34 R12

35 Y12 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER


36 B12

37 R13

38 Y13 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER


39 B13

40 R14 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3

41 Y14 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3

42 B14 20 SPARE

43 R15 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 2

44 Y15 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 1

45 B15 20 SPARE

46 R16 20 SPARE

47 Y16 20 SPARE

48 B16 20 SPARE

Cable Size : 4C 16 mm2 XLPE/PVC ECC Total Load per Phas


+ 16 mm2

Total connected Load (in kVA


Cable Size : 4C 16 mm2 XLPE/PVC ECC
+ 16 mm2

Total connected Load current

Breaker current (A) (TCL current +25

Load after Diver

4mm2 R 1335 8.76 8


4mm2 Y 1095 7.18 8
4mm2 B 1095 7.18 8
4mm2 Y/G 3285 21.5 24
4mm2 Black 3285 21.5 24
4mm2 Spciall 360
4mm2 Y/G 1080
4mm2 Black 1080

6mm2 R 152 1 1
6mm2 Y 152 1 1
6mm2 B 152 1 1
6mm2 Y/G 457 3 3
6mm2 Black 457 3 3
Area Loc :- RIYADH, KSA
:- GF-WAREHOUSE BLOCK J

Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
ISO R Y B

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 1.11 0.56

1 3.33 0.5 1.11 0.56


0.5 1.11 0.56
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 0.56 0.28

1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28

1 1.67 0.5 0.56 0.28

0.5 0.56 0.28

0.44 0.5 1.33 0.67

0.44 0.5 1.33 0.67

0.5 1.50 0.75

0.22 0.5 0.44 0.22

0.22 0.5 0.22 0.11

Total Load per Phase 10.67 10.44 10.39 15.75

Total connected Load (in kVA) 31.50 kVA


15.75

Total connected Load current (A) 45.47 A

Breaker current (A) (TCL current +25% of TCL 56.83 A


Current)
Load after Diversity 15.75 kVA
Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand Area :- R
NOON
FED From :- SMDB-J D & B Contractor :- Amana Contracting Location

Max assumed ECC Size


Rating Amps PVC/XLPE Cable Size length of Connected Load - KW
Cable (Mtrs)
Sr.
MCCB Fault Duty KA
No 2/4 x 1C R-Phase Y-Phase
Nos 1C mm2
mm2 KVA KVA
(A)
Circuit Feeder DB no SP/ TP ISO MCB 4C mm2
Incomer TP 160 25 XLPE/PVC 1 4C 70 6 1 1C 35 30.19 30.19

Outgoing

1 CP-FAHU-06 TP 100 25 XLPE/PVC 1 4C 25 168 1 1C 16 14.63 14.63

2 AHU-34 TP 40 25 XLPE/PVC 1 4C 10 173 1 1C 10 5.19 5.19

3 AHU-35 TP 40 25 XLPE/PVC 1 4C 10 197 1 1C 10 5.19 5.19

4 AHU-36 TP 40 25 XLPE/PVC 1 4C 16 214 1 1C 16 5.19 5.19

5 SPARE TP 40 25

6 SPACE

Total Connected Load per Phase Total…….. 30.19 30.19

Demand Factor = 0.90 Total connected 90.56 KVA


Max. Demand = 81.50 KVA load Actual Load = 90.56

MD CURRENT + 25%

TCL 90.56
Amana Contracting MD 81.50 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 117.64
:- RIYADH SMDB Ref :- SMDB -AC-J Owner :-

Location :- GF WH -BLOCK J

Connected Load - KW KWH Meter

B-Phase Demand Load 3 Ph 3 Ph LV/HV


Demand Factor
KVA KVA (2) (3) CT (4)
Total KVA Total kW ST.BY 1 Ph (1) Remarks
30.19 90.56

14.63 43.89 39.50 0.90 39.50 TO C.P.

5.19 15.56 14.00 0.90 14.00 TO C.P.

5.19 15.56 14.00 0.90 14.00 TO C.P.

5.19 15.56 14.00 0.90 14.00 TO C.P.

30.19 90.56 81.50 0.00 81.50 0 0 0 0

Actual Load = 90.56 KVA Stand By Load = 0.00 KVA

MD CURRENT + 25% * BMS Interfacing to be provided


* Fire Alarm Interfacing to be provided

147.05
INCOMER BREAKER
SIZE (A) 160
Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
SMDB Ref :- USS-4 Owner :- NOON - KSA

FED From :- QRM D & B Contractor :- Amana Contracting

Rating Amps PVC/XLPE Cable Size ECC Size Connected Load - KW


Max

Sr. Circuit Feeder DB no SP/ TP ISO MCCB MCB Fault Duty assumed R-Phase Y-Phase
No KA length of KVA KVA
Nos 4C mm2 Cable Nos 1C mm2
(A) (Mtrs)

Incomer TP ACB 2500 50 MEDIUM VOLTAGE CABLE 3C 120

Outgoing

1 CHILLER -B2-02 TP ACB 1000 36 XLPE/PVC 3 4C 240 60 3 1C 120 176.30 176.30

2 SMDB-B2 TP 300 36 XLPE/PVC 1 4C 150 17 1 1C 70 60.43 63.65

3 SMDB-B2-BC TP 125 36 XLPE/PVC 1 4C 35 16 1 1C 16 27.77 27.77

4 ESMDB-B2 TP 400 36 XLPE/PVC 1 4C 240 24 1 1C 120 78.47 70.00


5 CP-B2-CHWP TP 200 36 XLPE/PVC 1 4C 95 20 1 1C 50 50.00 50.00

6 CAP. BANK (CB-4) TP 800 36 XLPE/PVC 2 4C 240 1 1C 240

7 SPARE TP 350 36 60.00 60.00

8 SPARE TP 300 36 50.00 50.00

9 SPACE

10 SPACE

Total Connected Load per Phase Total…….. 502.97 497.72

Demand Factor = 0.75 Max. Demand = 1118.25 KVA Total connected load 1493.76 KVA Actual Load =

Amana Contracting
Type of Meter : BMS metering
Area :- RIYADH

Location :- SERVICE BLOCK -2

Connected Load - KW KWH Meter

B-Phase Demand Demand Demand 3 Ph 3 Ph LV/HV Remarks


KVA Load KVA Factor Load KVA (2) (3) CT (4)
Total KVA Total kW (Down stream) (UP stream) 1 Ph (1)

ST BY
1493.76 1

176.30 528.89 476.00 528.89 0.90 476.00 UVR+TIMER+


CONTACTOR

60.00 184.09 165.68 147.52 0.80 118.01

27.77 83.30 74.97 58.31 0.80 46.65

69.01 217.48 195.73 195.73 0.80 156.59


50.00 150.00 135.00 150.00 50.00 0.90 90.00
250KVAR WITH
DETUNED FILTER

60.00 180.00 162.00 180.00 0.70 126.00

50.00 150.00 135.00 150.00 0.70 105.00

493.07 1493.76 1344.38 50.00 1118.25 0 0 0 0 0.00

Actual Load = 1443.76 KVA Stand By Load = 50.00 KVA


Project SMDB Ref :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
FED From :- SMDB-B2 :- NOON
:- USS-4 :- Amana Contracting
Owner
D & B Contractor

ECC Size
Rating Amps PVC/XLPE Cable Size Connected Load - KW

Max
assumed
2/4 x 1C length of R-Phase Y-Phase B-Phase
MCCB Cable (Mtrs) Nos 1C mm2
mm2 KVA KVA KVA
Sr. (A) Fault Duty
No Circuit Feeder DB no SP/ TP ISO MCB KA 4C mm2
Incomer TP 300 50 XLPE/PVC 1 4C 150 17 1 1C 70 60.43 63.65 60.00

Outgoing

1 DB-B2-L TP 40 25 XLPE/PVC 1 4C 10 15 1 1C 10 2.40 2.03 1.67

2 DB-B2-P TP 40 25 XLPE/PVC 1 4C 16 14 1 1C 16 6.64 8.19 7.09

3 DB-B2-AC TP 63 25 XLPE/PVC 1 4C 16 14 1 1C 16 8.89 8.40 8.43

4 DB-B2-LP TP 63 25 XLPE/PVC 1 4C 16 35 1 1C 16 9.08 11.43 9.89

5 BOOSTER PUMP TP 32 25 XLPE/PVC 1 4C 6 57 1 1C 6 2.96 2.96 2.96

6 PRESURIZATION PUMP TP 20 25 XLPE/PVC 1 4C 4 60 1 1C 4 1.48 1.48 1.48

7 DB-EXT-2 TP 40 25 XLPE/SWA/PVC 1 4C 10 15 1 1C 10 3.42 3.60 2.92

8 CP-FAHU-B2-01 TP 63 25 XLPE/PVC 1 4C 16 15 1 1C 16 6.67 6.67 6.67

9 FAHU-B2-02 TP 20 25 XLPE/PVC 1 4C 4 15 1 1C 4 0.74 0.74 0.74

10 CP-FAHU-B2-01 - HEATER TP 100 25 XLPE/PVC 1 4C 25 15 1 1C 16 18.15 18.15 18.15

11 SPARE TP 40 25

12 SPACE

Total Connected Load per Phase Total…….. 60.43 63.65 60.00

Total connected load


Demand Factor = 0.80 Max. Demand = 147.52 KVA 184.09 KVA Actual Load =

TCL 184.09 MD CURRENT + 25%


Amana Contracting MD 147.52 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 212.929056
Area :- RIYADH
Location :- GF SERVICE BLOCK 2 (ELECT RM)

nected Load - KW KWH Meter

Demand Demand Load


Load KVA KVA (UP
(Down stream) stream)
3 Ph 3 Ph LV/HV
Demand Factor
(2) (3) CT (4)

Total KVA Total kW ST BY 1 Ph (1) Remarks


184.09 1

6.10 5.49 6.10 0.90 5.49

21.93 19.73 10.96 0.90 9.87

25.72 23.15 23.15 0.90 23.15

30.41 27.37 23.29 0.90 27.37

8.89 8.00 8.89 4.40 0.70 3.14 1D+1ST.BY

4.44 4.00 4.44 2.22 0.70 1.55 1D+1ST.BY

9.94 8.95 9.94 0.80 7.95

20.00 18.00 20.00 0.90 18.00

2.22 2.00 2.22 0.90 2.00

54.44 49.00 54.44 0.90 49.00

184.09 165.68 6.62 147.52 0 0 0 0

177.47 KVA Stand By Load = 6.62 KVA

266.16132
300
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-B2-L Details of Connected Load / Max. Demand
From :- SMDB-B2 40A TP Owner :- Al Muhaidib
Rating of Incomer :- D & B Contractor :- Amana Contracting

Rating of Sr. MCB CKT ECC Connected Loads / Points


ELCB No. RTG in Wire Size Wire Size
EX 13A 15A Ceiling
CKT No. Amp mm2 mm2 Room / Area Fan S/O S/O Fan
LTG Eqpt. SPUR W/H D/W HD

RCBO 30mA 1 R1 10 2.5 2.5 SUPPORT TOILETS 3,2


RCBO 30mA 2 Y1 10 2.5 2.5 JANITOR, JANITOR STORAGE, FEMALE 8,4
TOILET

RCBO 30mA 3 B1 10 2.5 2.5 TOILET 4,5


4 R2 10 2.5 2.5 ENTRANCE 9
5 Y2 10 2.5 2.5 MHE SERVICE & BATTERY CHARGER 12
6 B2 10 2.5 2.5 OFFICE AREA 8
7 R3 10 2.5 2.5 OFFICE,OFFICE -01. OFFICE-02 18
8 Y3 10 2.5 2.5 TRAINING ROOM 6
9 B3 10 2.5 2.5 DRIVER'S WAITING AREA, PRAYER ROOM 4
10 R4 10 2.5 2.5 MALE LOCKERS 12
11 Y4 10 2.5 2.5 CORRIDOR 7
12 B4 10 2.5 2.5 CORRIDOR 5
13 R5 10 2.5 2.5 FEMALE LOCKERS 3
14 Y5 10 2.5 2.5 FEMALE DINING ROOM, RECEIVING 7
15 B5 10 2.5 2.5 SECURITY & CCTV ROOM, IDF ROOM 5
16 R6 10 2.5 2.5 ENTRANCE 12
17 Y6 10 2.5 2.5 SPARE for EM light 32,4
18 B6 10 2.5 2.5 SPARE for EM light 26,8
19 R7 10 2.5 2.5 GENERATOR 4

20 Y7 10 2.5 2.5 ELECTRICAL PANEL ROOM 4

21 B7 10 2.5 2.5 TRANSFORMER 8

22 R8 10 2.5 2.5 STAIRCASE 6

23 Y8 10 Spare

24 B8 10 Spare

Cable Size : 4C 10 mm2 XLPE/PVC ECC Total Load per Phase


Spare load + 10 mm2

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of

Load after Diversity

2.5mm2 R 7
2.5mm2 Y 7
2.5mm2 B 7
2.5mm2 Y/G 21
2.5mm2 Black 21
Area Loc :- RIYADH, KSA
:- SERVICE BLOCK- 2 GF ELECTRICAL ROOM

Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
ISO R Y B

0.03,0.02 1.0 0.12 0.12


0.03,0.02 1.0 0.30 0.30

0.03,0.02 1.0 0.22 0.22


0.03 1.0 0.24 0.24
0.05 1.0 0.62 0.62
0.04 1.0 0.32 0.32
0.04 1.0 0.72 0.72
0.04 1.0 0.24 0.24
0.04 1.0 0.16 0.16
0.04 1.0 0.48 0.48
0.03 1.0 0.18 0.18
0.03 1.0 0.13 0.13
0.04 1.0 0.12 0.12
0.04 1.0 0.28 0.28
0.05 1.0 0.26 0.26
0.03 1.0 0.31 0.31
0.0062/0.0011 1.0 0.20 0.20
0.0062/0.0011 1.0 0.17 0.17
0.05 1.0 0.21 0.21

0.05 1.0 0.21 0.21

0.05 1.0 0.41 0.41

0.03 1.0 0.20 0.20

Total Load per Phase 2.40 2.03 1.67 6.10

Total connected Load (in kVA) 6.10 kVA

Total connected Load current (A) 8.80 A

Breaker current (A) (TCL current +25% of TCL 11.00 A


Current)
Load after Diversity 6.10 kVA
Amana Contracting 
Project DB Ref FED From :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-B2-P Details of Connected Load / Max. Demand
Rating of Incomer :- SMDB-B2 40A TP Owner :- Al Muhaidib
:- D & B Contractor :- Amana Contracting

Sr. MCB RTG CKT ECC Connected Loads / Points


No. in Amp Wire Size Wire Size
mm2 mm2 EX 13A 13A 15A Ceiling
Rating of ELCB CKT No. Room / Area
LTG Eqpt. Fan S/O D/O S/O SPUR W/H Fan

1 R1 20 4.0 4.0 TRANSFORMER, GENERATOR,STORE, ELEC.PANEL ROOM 6

2 Y1 20 4.0 4.0 CORRIDOR,RECEIVING, FEMALE LOCKERS 4

3 B1 20 4.0 4.0 SPARE


4 R2 20 4.0 4.0 ENTRANCE, IDF ROOM 4
5 Y2 20 4.0 4.0 TRAINING ROOM 2
6 B2 20 4.0 4.0 CORRIDOR,DRIVER'S WAITING AREA, PRAYER ROOM 6

7 R3 20 4.0 4.0 OFFICE-01, OFFICE-02 4


8 Y3 20 4.0 4.0 OFFICE 4
9 B3 20 4.0 4.0 OFFICE AREA 3
10 R4 20 4.0 4.0 MALE LOCKERS 3
11 Y4 20 4.0 4.0 FEMALE DINING ROOM 3 2
12 B4 20 4.0 4.0 OFFICE AREA 1 2
RCBO 30mA 13 R5 20 4.0 4.0 FEMALE TOILET 1
RCBO 30mA 14 Y5 20 4.0 4.0 TOILET 1
RCBO 30mA 15 B5 20 4.0 4.0 SUPPORT TOILETS 1
16 R6 20 4.0 4.0 GENERATOR BATTERY
RCBO 30mA 17 Y6 20 4.0 4.0 SUPPORT TOILETS
RCBO 30mA 18 B6 20 4.0 4.0 MALE TOI 1
19 R7 20 SPARE

20 Y7 20 4.0 4.0 TRAINING ROOM 1 1

21 B7 20 SPARE

22 R8 20 SPARE

23 Y8 20 SPARE

24 B8 20 SPARE

Cable Size : 4C 16 mm2 XLPE/PVC ECC


+ 16 mm2

4mm2 R 950 6
4mm2 Y 950 6
4mm2 B 950 6
4mm2 Y/G 2850 19
4mm2 Black 2850 19
Area Loc :- RIYADH, KSA
:- SERVICE BLOCK- 2 GF ELECTRICAL ROOM

ads / Points Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
D/W HD ISO R Y B

0.22 0.5 1.33 0.67

0.22 0.5 0.89 0.44

0.22 0.5 0.89 0.44


0.44 0.5 0.88 0.44
0.22 0.5 1.33 0.67

0.22 0.5 0.89 0.44


0.22 0.5 0.89 0.44
0.44 0.5 1.32 0.66
0.22 0.5 0.67 0.33
0.22,0.44 0.5 1.54 0.77
0.22,0.44 0.5 1.10 0.55
1.67 0.5 1.67 0.83
1.67 0.5 1.67 0.83
1.67 0.5 1.67 0.83
1 1.20 0.5 1.20 0.60
1 1.67 0.5 1.67 0.83
1.67 0.5 1.67 0.84

0.22,0.44 0.5 0.66 0.33

Total Load per Phase 6.64 8.19 7.09 10.96

Total connected Load (in kVA) 21.93 kVA

Total connected Load current (A) 31.65 A

Breaker current (A) (TCL current +25% of TCL 39.56 A


Current)
Load after Diversity 10.96 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 EDB-H Details of Connected Load / Max. Demand
From :- ESMDB-B2 Owner :- Al Muhaidib
Rating of Incomer :- 63A TP D & B Contractor :- Amana Contracting

Rating of Sr. CKT MCB CKT ECC Connected Loads / Points


ELCB No. No. RTG in Wire Size Wire Size
Amp EX 13A 13A 15A Ceiling
mm2 mm2 Room / Area Fan S/O D/O S/O Fan
LTG Eqpt. SPUR W/H D/W

1 R1 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-H 5

2 Y1 16 SPARE

3 B1 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-H 5

4 R2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-H 5

5 Y2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-H 4

6 B2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-H 5

7 R3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-H 5

8 Y3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-H 4

9 B3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-H 3

10 R4 16 SPARE

11 Y4 16 SPARE

12 B4 20 SPARE

13 R5 4C-4mm2 XLPE/FR
+1C-
14 Y5 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER 60
15 B5

16 R6 4C-4mm2 XLPE/FR
+1C-
17 Y6 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER
18 B6
60
19 R7 4C-4mm2 XLPE/FR
+1C-
20 Y7 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER
21 B7
90
22 R8 20 4.0 4.0 13A D/O FOR ICT RACK 1

23 Y8 20 4.0 4.0 13A D/O FOR ICT RACK 1

24 B8 20 4.0 4.0 13A D/O FOR CCTV RACK 1

25 R9 20 4.0 4.0 SVCP-H-1

26 Y9 20 4.0 4.0 SVCP-H-2

27 B9 20 4.0 4.0 SVCP-H-3

Total Load pe

Cable Size : 4C 16 mm2 CU/FR/XLPE/LSOH

+ 16 mm2 ECC Total connected Load (

Total connected Load curr

Breaker current (A) (TCL current +25% o

Load after Di

To be ordered
4mm2 R 1217 7.98 8
4mm2 Y 1105 7.25 8
4mm2 B 1215 7.97 8
4mm2 Y/G 24
4mm2 Black 24
4C-4mm2 XLPE/FR +1C- 210
4mm ECC
Area Loc :- RIYADH, KSA
:- GF-WAREHOUSE BLOCK H

Demand Load per circuit Diversity


factor kVA Load
16A FCU/V
IND. AV Unit KVA Remarks
S/O ISO R Y B

0.26 1.0 1.28 1.28

1.0 0.00 0.00

0.18 1.0 0.90 0.90

0.18 1.0 0.90 0.90

0.18 1.0 0.72 0.72

0.18 1.0 0.90 0.90

0.18 1.0 0.90 0.90

0.18 1.0 0.72 0.72

0.26 1.0 0.77 0.77

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56

0.5 1.11 0.56

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56

0.5 1.11 0.56

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56

0.5 1.11 0.56

0.44 1.0 0.44 0.44

0.44 1.0 0.44 0.44

0.44 1.0 0.44 0.44

1 0.66 1.0 0.66 0.66 FP-200 CABLE

1 0.66 1.0 0.66 0.66 FP-200 CABLE

1 0.66 1.0 0.66 0.66 FP-200 CABLE

Total Load per Phase 7.52 5.88 7.00

15.40

Total connected Load (in kVA) 20.40 kVA

Total connected Load current (A) 29.44 A

Breaker current (A) (TCL current +25% of TCL 36.80 A


Current)
Load after Diversity 15.40 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-B2-AC Details of Connected Load / Max. Demand
From :- SMDB-B2 63A TP Owner :- Al Muhaidib
Rating of Incomer :- D & B Contractor :- Amana Contracting

Rating of Sr. MCB RTG CKT Wire ECC Wire Connected Loads / Points
ELCB No. in Amp Size mm2 Size mm2
EX 13A 13A 15A Ceiling
CKT No. Room / Area Fan S/O D/O S/O Fan
LTG Eqpt. SPUR W/H D/W

1 R1 20 4.0 4.0 FCU-B2-4

2 Y1 20 4.0 4.0 FCU-B2-11

3 B1 20 4.0 4.0 FCU-B2-7


4 R2 20 4.0 4.0 FCU-B2-6
5 Y2 20 4.0 4.0 FCU-B2-5
6 B2 20 4.0 4.0 FCU-B2-8

7 R3 20 4.0 4.0 FCU-B2-9


8 Y3 20 4.0 4.0 FCU-B2-10
9 B3 20 4.0 4.0 FCU-B2-12
10 R4 20 4.0 4.0 FCU-B2-13
11 Y4 20 4.0 4.0 FCU-B2-14
12 B4 20 4.0 4.0 FCU-B2-15
13 R5 20 4.0 4.0 FCU-B2-16
14 Y5 20 SPARE
15 B5 20 4.0 4.0 FCU-B2-2
16 R6 20 4.0 4.0 FCU-B2-3
17 Y6 20 4.0 4.0 FCU-B2-1
18 B6 20 SPARE
19 R7 20 4.0 4.0 AIRCURTAIN -1

20 Y7 40 3C-10mm2 ODU - B02-02(IELECT ROOM) (In Roof)


XLPE/PVC

21 B7 40 3C-10mm2 ODU - B02-02(IELECT ROOM) (In Roof)


XLPE/PVC

22 R8 20 4.0 4.0 EXHAUST FAN BATTERY CHARGING ROOM

23 Y8 20 4.0 4.0 EXHAUST FAN TRANSFORMER ROOM

24 B8 20 4.0 4.0 EXHAUST FAN TRANSFORMER ROOM

25 R9 20 4.0 4.0 AIRCURTAIN -1

26 Y9 20 SPARE

27 B9 20 SPARE

28 R10 20 SPARE

29 Y10 20 SPARE

30 B10 20 SPARE

Cable Size : 4C 16 mm2 XLPE/PVC Total L


+ 16 mm2 ECC

Total connected

Total connected Lo

Breaker current (A) (TCL c

Load a

4mm2 R 1200 7.9


4mm2 Y 1200 7.9
4mm2 B 1200 7.9
4mm2 Y/G 3600 24
4mm2 Blk 3600 24
3x10mm2 250
Area Loc :- RIYADH, KSA
:- SERVICE BLOCK- 2 GF ELECTRICAL ROOM

Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
HD ISO R Y B

1 1.50 0.9 1.50 1.35

1 0.94 0.9 0.94 0.85

1 0.72 0.9 0.72 0.65


1 0.72 0.9 0.72 0.65
1 0.83 0.9 0.83 0.75
1 0.83 0.9 0.83 0.75

1 0.76 0.9 0.76 0.68


1 0.91 0.9 0.91 0.82
1 0.72 0.9 0.72 0.65
1 1.28 0.9 1.28 1.15
1 1.06 0.9 1.06 0.95
1 0.83 0.9 0.83 0.75
1 1.83 0.9 1.83 1.65

1 0.67 0.9 0.67 0.60


1 0.80 0.9 0.80 0.72
0.72 0.9 0.00 0.00

1 0.67 0.9 0.67 0.60

1 4.44 0.9 4.44 4.00 UVR+TIMER +CONT

1 4.44 0.9 4.44 4.00 UVR+TIMER +CONT

1 0.66 0.9 0.66 0.59

1 0.22 0.9 0.22 0.20

1 0.22 0.9 0.22 0.20

1 0.67 0.9 0.67 0.60

Total Load per Phase 8.89 8.40 8.43 23.15

Total connected Load (in kVA) 25.72 kVA

Total connected Load current (A) 37.12 A

Breaker current (A) (TCL current +25% of TCL 46.41 A


Current)
Load after Diversity 23.15 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-B2-LP Details of Connected Load / Max. Demand
From :- SMDB-B2 63A TP Owner :- Al Muhaidib
Rating of Incomer :- D & B Contractor :- Amana Contracting

Sr. MCB RTG CKT ECC Connected Loads / Points


No. in Amp Wire Size Wire Size
mm2 mm2 EX 13A 13A 15A
Rating of ELCB CKT No. Room / Area Fan S/O D/O S/O
LTG Eqpt. SPUR W/H D/W HD ISO

1 R1 10 2.5 2.5 PRAYER ROOM 5

RCBO 30mA 2 Y1 10 2.5 2.5 ABLUTION, PASSAGE 2,5

RCBO 30mA 3 B1 10 2.5 2.5 MALE TOILET, JANITOR, CORRIDOR 9,7

4 R2 10 2.5 2.5 MALE DINING HALL 12

5 Y2 10 2.5 2.5 MALE DINING HALL 12

6 B2 10 2.5 2.5 MALE DINING HALL 12

7 R3 10 2.5 2.5 MALE DINING HALL 6

8 Y3 10 2.5 2.5 PREPARATION AREA, RECEIVING, DUMP 6


WAITER

9 B3 10 2.5 2.5 SERVING AREA 8

RCBO 30mA 10 R4 10 2.5 2.5 ROOF LIGHTS 11

11 Y4 10 2.5 2.5 SPARE for EM light 30,3

12 B4 10 SPARE

13 R5 20 4.0 4.0 JANITOR,CORRIDOR,PRAYER ROOM 4

14 Y5 20 4.0 4.0 MALE DINING HALL 3

15 B5 20 4.0 4.0 PREPARATION AREA, RECEIVING 2 2

RCBO 30mA 16 R6 20 4.0 4.0 MALE TOILET 1

RCBO 30mA 17 Y6 20 4.0 4.0 TOILET CORRIDOR 1

RCBO 30mA 18 B6 20 4.0 4.0 ROOF POWER 2

19 R7 20 SPARE

20 Y7 20 4.0 4.0 MALE DINING HALL 5

21 B7 20 SPARE

22 R8 20 4.0 4.0 FCU-B1-17A

23 Y8 20 4.0 4.0 SPARE

24 B8 20 4.0 4.0 FCU-B1-17C

25 R9 20 4.0 4.0 FCU-B1-17D

26 Y9 20 4.0 4.0 FCU-B1-17E

27 B9 20 4.0 4.0 FCU-B1-17B

28 R10 20 4.0 4.0 SPARE

29 Y10 20 4.0 4.0 FCU-B1-22

30 B10 20 4.0 4.0 FCU-B1-21

31 R11 20 4.0 4.0 FCU-B1-20

32 Y11 32 6.0 6.0 FCU-B1-19

33 B11 20 4.0 4.0 FCU-B1-18

34 R12

35 Y12 20 4.0 4.0 ISOLATOR FOR DUMP WAITER 1


36 B12

Cable Size : 4C 16 mm2 XLPE/PVC Total Load per Phase


+ 16 mm2 ECC

Total connected Load (in kVA)


Total connected Load current (A)

Breaker current (A) (TCL current +25% of TC


Current

Load after Diversity

4mm2 R 1300 8.5


4mm2 Y 1300 8.5
4mm2 B 1300 8.5
4mm2 Y/G 3600 24
4mm2 Blk 3600 24
Area Loc :- RIYADH, KSA
:- SERVICE BLOCK-2

MEZZ.FLOOR PASSAGE
Demand Load per circuit Diversity
factor kVA Load
FCU/V
AV Unit KVA Remarks
R Y B

0.04 1.0 0.20 0.20

0.03,0.05 1.0 0.28 0.28

0.03,0.02 1.0 0.38 0.38

0.04 1.0 0.48 0.48

0.04 1.0 0.48 0.48

0.04 1.0 0.48 0.48

0.04 1.0 0.24 0.24

0.04 1.0 0.24 0.24

0.04 1.0 0.32 0.32

0.03 1.0 0.37 0.37

0.0062/0.0011 1.0 0.20 0.20

0.20 0.5 0.80 0.40

0.44 0.5 1.32 0.66

0.22,0.44 0.5 1.33 0.67

1.66 0.5 1.66 0.83

1.66 0.5 1.66 0.83

0.22 0.5 0.44 0.22

0.22 0.5 1.10 0.55

1 1.67 0.9 1.67 1.50

1 0.9 0.00 0.00

1 1.67 0.9 1.67 1.50

1 1.67 0.9 1.67 1.50

1 1.67 0.9 1.67 1.50

1 1.67 0.9 1.67 1.50

1 0.9 0.00 0.00

1 0.72 0.9 0.72 0.65

1 0.83 0.9 0.83 0.75

1 1.06 0.9 1.06 0.95

1 2.83 0.9 2.83 2.55

1 1.83 0.9 1.83 1.65

0.5 0.93 0.47

2.80 0.5 0.93 0.47

0.5 0.93 0.47

Total Load per Phase 9.08 11.43 9.89 23.29

Total connected Load (in kVA) 30.41 kVA


Total connected Load current (A) 43.89 A

Breaker current (A) (TCL current +25% of TCL 54.86 A


Current)

Load after Diversity 23.29 kVA


Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand
DB Ref FED From :- DB-EXT-2 SMDB-B2 40A TP Owner :- Al Muhaidib
D & B Contractor :- Amana Contracting
Rating of Incomer :-

Rating of Sr. MCB CKT Wire Size ECC Wire Size Connected Loads / Points
ELCB No. RTG in mm2 mm2
Amp EX 13A 13A 15A Ceiling
CKT No. Room / Area Fan S/O D/O S/O Fan
LTG Eqpt. SPUR W/H

1 R1 External Lighting
16 4.0 4.0 7 190
2 Y1 3C-6mm2 XLPE/SWA/PVC External Lighting
16 6 275
3 B1 3C-6mm2 XLPE/SWA/PVC External Lighting
Section-1, 4P 16 6 265
40A
30mA 4 R2 External Lighting
16 4.0 4.0 3 155
5 Y2 3C-6mm2 XLPE/SWA/PVC External Lighting
16 6 190
6 B2 3C-6mm2 XLPE/SWA/PVC External Lighting
16 5 150
7 R3 3C-6mm2 XLPE/SWA/PVC External Lighting
16 6 135
8 Y3 3C-6mm2 XLPE/SWA/PVC External Lighting
16 6 190
Section-2, 4P 9 B3 16 3C-6mm2 XLPE/SWA/PVC External Lighting
40A 4 190
30mA
10 R4 16 3C-6mm2 XLPE/SWA/PVC CAR SHED LIGHT 4
120
11 Y4 16 SPARE
12 B4 16 SPARE
13 R5 SPACE
14 Y5 SPACE

Cable Size : 4C 10 mm2 XLPE/PVC


+ 10 mm2 ECC

3C-6mm2 XLPE/SWA/PVC 1515


4mm2 R 345 2.26 3
4mm2 Y/G 345 3
4mm2 Black 345 3
Area Loc :- RIYADH, KSA
:- SERVICE BLOCK-2, GF ELECTRICAL ROOM

ds / Points Demand Load per circuit Diversity


factor kVA Load
16A FCU/V
IND. AV Unit KVA Remarks
D/W ISO R Y B
S/O

1.0 1.40 1.40


0.20

1.0 1.20 1.20


0.200

1.0 1.20 1.20


0.20

1.0 0.60 0.60


0.20

1.0 1.20 1.20


0.200 P.CELL +TIMER
+CONTACTOR WITH MANUAL
1.0 1.00 1.00 OVERRIDE
0.20

0.20 1.0 1.20 1.20

0.20 1.0 1.20 1.20

0.18 1.0 0.72 0.72

0.06 1.0 0.22 0.22

Total Load per Phase 3.42 3.60 2.92


9.94
Total connected Load (in kVA) 9.94 kVA
Total connected Load current (A) 14.35 A
Breaker current (A) (TCL current +25% of TCL 17.93 A
Current)
Load after Diversity 9.94 kVA
Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
SMDB Ref :- SMDB-B2-BC :- NOON

Owner
FED From :- USS-4 D & B Contractor :- Amana Contracting

Max ECC Size


Rating Amps PVC/XLPE Cable Size assumed Connected Load - KW
length of
Cable (Mtrs)

MCCB 2/4 x 1C R-Phase Y-Phase B-Phase


Nos 1C mm2
mm2 KVA KVA KVA

Sr. (A)
No Circuit Feeder DB no SP/ TP ISO MCB Fault Duty KA 4C mm2
Incomer TP 125 36 XLPE/PVC 1 4C 35 16 1 1C 16 27.77 27.77 27.77

Outgoing

1 BATTERY CHARGER-1 TP 32 25 XLPE/PVC 1 4C 6 31 1 1C 6 2.78 2.78 2.78

2 BATTERY CHARGER-2 TP 32 25 XLPE/PVC 1 4C 6 30 1 1C 6 2.78 2.78 2.78

3 BATTERY CHARGER-3 TP 32 25 XLPE/PVC 1 4C 6 29 1 1C 6 2.78 2.78 2.78

4 BATTERY CHARGER-4 TP 32 25 XLPE/PVC 1 4C 6 27 1 1C 6 2.78 2.78 2.78

5 BATTERY CHARGER-5 TP 32 25 XLPE/PVC 1 4C 6 26 1 1C 6 2.78 2.78 2.78

6 BATTERY CHARGER-6 TP 32 25 XLPE/PVC 1 4C 6 25 1 1C 6 2.78 2.78 2.78

7 BATTERY CHARGER-7 TP 32 25 XLPE/PVC 1 4C 6 23 1 1C 6 2.78 2.78 2.78

8 BATTERY CHARGER-8 TP 32 25 XLPE/PVC 1 4C 6 21 1 1C 6 2.78 2.78 2.78

9 BATTERY CHARGER-9 TP 32 25 XLPE/PVC 1 4C 6 25 1 1C 6 2.78 2.78 2.78

10 BATTERY CHARGER-10 TP 32 25 XLPE/PVC 1 4C 6 25 1 1C 6 2.78 2.78 2.78

11 SPARE TP 32 25

12 SPACE

Total Connected Load per Phase Total…….. 27.77 27.77 27.77

Total connected load


Demand Factor = 0.70 Max. Demand = 58.31 KVA 83.30 KVA Actual Load =

MD CURRENT + 25%

TCL 83.30
Amana Contracting MD 58.31 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 84.17
Area :- RIYADH

Location :- GF SERVICE BLOCK 2 (ELECT RM)

onnected Load - KW KWH Meter

Demand Demand
Load KVA Load KVA
(Down stream) (UP stream)
LV/HV
Demand Factor
CT (4)

3 Ph 3 Ph
Total KVA Total kW ST BY 1 Ph (1) (2) (3) Remarks
83.30

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

8.33 7.50 8.33 0.70 5.83

83.30 74.97 0.00 58.31 0 0 0 0

83.30 KVA Stand By Load = 0.00 KVA

105.21
125
Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand

SMDB Ref :- ESMDB-B2 Owner :- NOON


FED From :- USS-4 & 250kva GENERATOR D & B Contractor :- Amana Contracting

ECC Size
Rating Amps PVC/XLPE Cable Size Connected Load - KW
Max
MCCB assumed
2/4 x 1C length of
Cable (Mtrs) Nos 1C mm2
mm2
Sr. (A) R-Phase Y-Phase B-Phase
No Circuit Feeder DB no SP/ TP ISO MCB Fault Duty KA 4C mm2 KVA KVA KVA
Incomer (From USS-4) 4P 400 36 CU//XLPE/PVC 1 4C 240 24 1 1C 120 78.47 70.00 69.01

Incomer (From GEN-B2) 4P 400 36 CU/FR/XLPE/LSOH 1 4C 240 24 1 1C 120

Outgoing

1 EDB-F TP 63 25 CU/FR/XLPE/LSOH 1 4C 16 150 1 1C 16 8.63 6.99 7.67

2 EDB-H TP 63 25 CU/FR/XLPE/LSOH 1 4C 16 74 1 1C 16 7.52 5.88 7.00

3 EDB-J TP 63 25 CU/FR/XLPE/LSOH 1 4C 16 115 1 1C 16 7.47 5.83 6.56

4 EDB-B2 TP 40 25 CU/FR/XLPE/LSOH 1 4C 10 15 1 1C 10 5.74 5.51 9.73

5 EDB-SERVER TP 160 25 CU/FR/XLPE/LSOH 1 4C 120 340 1 1C 70 25.94 26.82 20.94

6 EDB-AD TP 40 25 CU/FR/XLPE/LSOH 1 4C 25 362 1 1C 16 9.10 4.89 3.02

7 CCU-2 TP 80 25 CU/FR/XLPE/LSOH 1 4C 50 350 1 1C 25 14.08 14.08 14.08

8 SPARE TP 40 25

9 SPACE

Total Connected Load per Phase Total…….. 78.47 70.00 69.01

Total connected load


Demand Factor = 0.90 Max. Demand = 195.73 KVA 217.48 KVA Actual Load =

MD CURRENT + 25%

TCL 217.48
Amana Contracting MD 195.73 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 282.5230947
Area :- RIYADH

Location :- GF ELECT ROOM SERVICE BLOCK 2

onnected Load - KW KWH Meter

Demand Load Demand Factor Demand Load


KVA (Down KVA (UP
stream) stream)

3 Ph 3 Ph LV/HV
Total KVA Total kW ST BY 1 Ph (1) (2) (3) CT (4) Remarks
217.48 AUTO TRANSFER
and E/M Interlock

23.29 20.96 16.18 0.90 20.96

20.40 18.36 15.40 0.90 18.36

19.86 17.88 14.86 0.90 17.88

20.98 18.88 17.80 0.90 18.88

73.70 66.33 72.55 0.90 66.33

17.01 15.31 17.01 0.90 15.31

42.24 38.02 42.24 0.90 38.02 ELCB 100mA

217.48 195.73 0.00 195.73 0 0 0 0 0.00

217.48 KVA Stand By Load = 0.00 KVA

353.153868
400
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 EDB-F Details of Connected Load / Max. Demand
From :- ESMDB-B2 63A TP Owner :- Al Muhaidib
Rating of Incomer :- D & B Contractor :- Amana Contracting

Rating of Sr. MCB CKT ECC Connected Loads / Points


ELCB No. RTG in Wire Wire Size
Amp Size mm2 EX 13A 13A 15A Ceiling 16A
CKT No. Room / Area Fan S/O D/O S/O Fan IND.
mm2 LTG Eqpt. SPUR W/H D/W ISO
S/O

1 R1 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-F 5


2 Y1 16 SPARE
3 B1 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-F 5
4 R2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-F 5
5 Y2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-F 4
6 B2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-F 5
7 R3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-F 5
8 Y3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-F 4
9 B3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-F 3
10 R4 16 SPARE
11 Y4 20 SPARE
12 B4 20 SPARE
FR WIRING 13 R5 4C-4mm2 XLPE/FR
+1C-
14 Y5 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER 1
15 B5
FR WIRING 16 R6 4C-4mm2 XLPE/FR
+1C-
17 Y6 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER 1
18 B6
FR WIRING 19 R7 4C-4mm2 XLPE/FR
+1C-
20 Y7 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER 1
21 B7
FR WIRING 22 R8 4C-4mm2 XLPE/FR
+1C-
23 Y8 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER 1
24 B8
25 R9 20 4.0 4.0 13A D/O FOR ICT RACK 1

26 Y9 20 4.0 4.0 13A D/O FOR ICT RACK 1

27 B9 20 SPARE

28 R10 20 4.0 4.0 SVCP-F-1 1

29 Y10 20 4.0 4.0 SVCP-F-2 1

30 B10 20 4.0 4.0 SVCP-F-3 1

Cable Size : 4C 16 mm2 CU/FR/XLPE/LSOH ECC Total Load per Phase


+ 16 mm2

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of TCL

Load after Diversity

To be ordered
4mm2 R 1217 7.98 8
4mm2 Y 1105 7.25 8
4mm2 B 1215 7.97 8
4mm2 Y/G 24
4mm2 Black 24
4C-4mm2 XLPE/FR 210
+1C-
4mm ECC
Area Loc :- RIYADH, KSA
:- GF-WAREHOUSE BLOCK F

Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
R Y B

0.26 1.0 1.28 1.28


1.0 0.00 0.00
0.18 1.0 0.90 0.90
0.18 1.0 0.90 0.90
0.18 1.0 0.72 0.72
0.18 1.0 0.90 0.90
0.18 1.0 0.90 0.90
0.18 1.0 0.72 0.72
0.26 1.0 0.77 0.77

0.5 1.11 0.56


3.33 0.5 1.11 0.56
0.5 1.11 0.56
0.5 1.11 0.56
3.33 0.5 1.11 0.56
0.5 1.11 0.56
0.5 1.11 0.56
3.33 0.5 1.11 0.56
0.5 1.11 0.56
0.5 1.11 0.56
3.33 0.5 1.11 0.56
0.5 1.11 0.56
0.44 0.5 0.44 0.22

0.44 0.5 0.44 0.22

0.66 1.0 0.66 0.66 FP-200 CABLE

0.66 1.0 0.66 0.66 FP-200 CABLE

0.66 1.0 0.66 0.66 FP-200 CABLE

Total Load per Phase 8.63 6.99 7.67 16.18

Total connected Load (in kVA) 23.29 kVA

Total connected Load current (A) 33.61 A

Breaker current (A) (TCL current +25% of TCL 42.02 A


Current)
Load after Diversity 16.18 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 EDB-J Details of Connected Load / Max. Demand
From :- ESMDB-B2 Owner :- Al Muhaidib
Rating of Incomer :- 63A TP D & B Contractor :- Amana Contracting

Rating of Sr. CKT MCB CKT ECC Connected Loads / Points


ELCB No. No. RTG in Wire Size Wire Size
Amp EX 13A 13A 15A Ceiling
mm2 mm2 Room / Area Fan S/O D/O S/O Fan
LTG Eqpt. SPUR W/H D/W

1 R1 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-J 5

2 Y1 16 SPARE

3 B1 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-J 5

4 R2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-J 5

5 Y2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-J 4

6 B2 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-J 5

7 R3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-J 5

8 Y3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-J 4

9 B3 16 4.0 4.0 WH.LIGHTING-GF.BLOCK-J 3

10 R4 16 SPARE

11 Y4 16 SPARE

12 B4 20 SPARE

13 R5 4C-4mm2 XLPE/FR
FR WIRING +1C-
FR WIRING 14 Y5 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER
FR WIRING
15 B5

16 R6 4C-4mm2 XLPE/FR
+1C-
17 Y6 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER
18 B6

19 R7 4C-4mm2 XLPE/FR
+1C-
20 Y7 20 4mm ECC 20A TP ISO.FOR DOCK LEVELER
21 B7

22 R8 20 4.0 4.0 13A D/O FOR ICT RACK 1

23 Y8 20 4.0 4.0 13A D/O FOR ICT RACK 1

24 B8 20 SPARE

25 R9 20 4.0 4.0 SVCP-J-1

26 Y9 20 4.0 4.0 SVCP-J-2

27 B9 20 4.0 4.0 SVCP-J-3

Total Load pe

Cable Size : 4C 16 mm2 CU/FR/XLPE/LSOH

+ 16 mm2 ECC Total connected Load (

Total connected Load curr

Breaker current (A) (TCL current +25% o

Load after Di

To be ordered
4mm2 R 1217 7.98 8
4mm2 Y 1105 7.25 8
4mm2 B 1215 7.97 8
4mm2 Y/G 24
4mm2 Black 24
4C-4mm2 XLPE/FR +1C- 210
4mm ECC
Area Loc :- RIYADH, KSA
:- GF-WAREHOUSE BLOCK H

Demand Load per circuit Diversity


factor kVA Load
16A FCU/V
IND. AV Unit KVA Remarks
S/O ISO R Y B

0.26 1.0 1.28 1.28

1.0 0.00 0.00

0.18 1.0 0.90 0.90

0.18 1.0 0.90 0.90

0.18 1.0 0.72 0.72

0.18 1.0 0.90 0.90

0.18 1.0 0.90 0.90

0.18 1.0 0.72 0.72

0.26 1.0 0.77 0.77

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56

0.5 1.11 0.56

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56

0.5 1.11 0.56

0.5 1.11 0.56

1 3.33 0.5 1.11 0.56

0.5 1.11 0.56

0.44 1.0 0.40 0.40

0.44 1.0 0.40 0.40

1 0.66 1.0 0.66 0.66 FP-200 CABLE

1 0.66 1.0 0.66 0.66 FP-200 CABLE

1 0.66 1.0 0.66 0.66 FP-200 CABLE

Total Load per Phase 7.47 5.83 6.56

14.86

Total connected Load (in kVA) 19.86 kVA

Total connected Load current (A) 28.67 A

Breaker current (A) (TCL current +25% of TCL 35.84 A


Current)
Load after Diversity 14.86 kVA
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1
DB Ref :- EDB-B2 Owner :- Al Muhaidib
D & B Contractor :- Amana Contracting
FED From :- ESMDB-B2
Rating of Incomer 40A TP

Rating of Sr. MCB CKT ECC Connected Loads / Points


ELCB No. RTG in Wire Wire EX 13A 13A 15A Ceiling
CKT No. Amp Size Size Room / Area Fan S/O D/O S/O Fan
mm2 mm2 LTG Eqpt. SPUR W/H D/W

1 R1 20 4.0 4.0 IDF RACK 1

2 Y1 20 4.0 4.0 IDF RACK 1

3 B1 20 4.0 4.0 IDF RACK 1

4 R2 20 4.0 4.0 IDF RACK 1

5 Y2 20 4.0 4.0 IT RACK 1

6 B2 20 4.0 4.0 CCTV ROOM 1 2

7 R3 16 4.0 4.0 CCTV RACK 1

8 Y3 16 4.0 4.0 CCTV MONITOR 4

9 B3 16 SPARE

10 R4 20 4.0 4.0 ENTRANCE-TURNSTILES 7

11 Y4 20 4.0 4.0 ENTRANCE SCANNER 4

12 B4 20 4.0 4.0 FACP 1

13 R5 20 4.0 4.0 MIMIC PANEL 1

14 Y5 20 4.0 4.0 DDC-05 1

FR WIRING FR 15 B5 20 4.0 4.0 DDC-06 1


WIRING
16 R6 20 SPARE

17 Y6 20 4.0 4.0 DDC-07 1

18 B6 20 4.0 4.0 DDC-08 1

19 R7 20 3C-4mm2 CCTV EXTERNAL 4


XLPE/SWA/PVC

20 Y7 20 3C-4mm2 CCTV EXTERNAL 5


XLPE/SWA/PVC

21 B7 20 4.0 4.0 DDC-15 1

22 R8 20 3C-4mm2 CCTV EXTERNAL 5


XLPE/SWA/PVC

23 Y8 20 3C-4mm2 CCTV EXTERNAL 2


XLPE/SWA/PVC

24 B8 40 3C-10mm2 ODU - B02-01 (IDF ROOM) (In Roof)


XLPE/PVC

25 R9 20 4.0 4.0 SPARE

26 Y9 20 4.0 4.0 SPARE

27 B9 20 4.0 4.0 SPARE

Total Load

Cable Size : 4C 10 mm2 CU/FR/XLPE/LSOH

+ 10 mm2 ECC Total connected Load

Total connected Load cu

Breaker current (A) (TCL current +25%

Load after

4mm2 R 5
4mm2 Y 5
4mm2 B 5
4mm2 Y/G 15
4mm2 Balck 15
3C-10mm2 75
XLPE/PVC
3C-4mm2 150
XLPE/PVC
Details of Connected Load / Max. Demand
dib Area :-
ontracting Loc :- RIYADH, KSA
GF ELECT ROOM SERVICE BLOCK 2

Demand Load per circuit Diversity


16A IND. FCU/V factor kVA Load
S/O AV Unit KVA Remarks
ISO R Y B

1.66 0.7 1.66 1.16

1.66 0.7 1.66 1.16

1.66 0.7 1.66 1.16

1.66 0.7 1.66 1.16

0.44 0.7 0.44 0.31

0.22,0.44 0.5 1.11 0.56

0.44 1.0 0.44 0.44

0.22 1.0 0.88 0.88

1.0 0.20 0.20

0.11 1.0 0.77 0.77

0.22 1.0 0.88 0.88

0.44 1.0 0.44 0.44

0.22 1.0 0.22 0.22

0.44 1.0 0.44 0.44

0.44 1.0 0.44 0.44

0.44 1.0 0.44 0.44

0.44 1.0 0.44 0.44

0.11 1.0 0.44 0.44

0.11 1.0 0.55 0.55

0.44 1.0 0.44 0.44

0.11 1.0 0.55 0.55

0.11 1.0 0.22 0.22

1 5.00 0.9 5.00 4.50 UVR+TIMER


+CONT

Total Load per Phase 5.74 5.51 9.73

17.80

Total connected Load (in kVA) 20.98 kVA

Total connected Load current (A) 30.28 A

Breaker current (A) (TCL current +25% of TCL 37.86 A


Current)
Load after Diversity 17.80 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 EDB-SERVER Details of Connected Load / Max. Demand
From :- ESMDB-B2 160A TP Owner :- Al Muhaidib Area
Rating of Incomer :- D & B Contractor :- Amana Contracting Loc

Rating of Sr. MCB RTG CKT ECC Connected Loads / Points


ELCB No. in Amp Wire Size Wire Size
mm2 mm2 EX 13A 13A 15A Ceiling
CKT No. Room / Area
LTG Eqpt. Fan S/O D/O S/O SPUR W/H Fan D/W 32A I.S

1 R1 32 6.0 6.0 SERVER RACK 1 1


150
2 Y1 32 6.0 6.0 SERVER RACK 2 135 1
3 B1 32 6.0 6.0 SERVER RACK 3 160 1
4 R2 32 6.0 6.0 SERVER RACK 4 190 1
5 Y2 32 6.0 6.0 SERVER RACK 5 145 1
6 B2 32 6.0 6.0 SERVER RACK 6 160 1
7 R3 32 6.0 6.0 SERVER RACK 7 1
170
8 Y3 32 6.0 6.0 SERVER RACK 8 150 1
9 B3 32 6.0 6.0 SERVER RACK 9 1
150
10 R4 32 6.0 6.0 SERVER RACK 10 160 1
11 Y4 32 6.0 6.0 SERVER RACK 11 175 1
12 B4 32 6.0 6.0 SERVER RACK 12 190 1
13 R5 32 6.0 6.0 SERVER RACK 13 175 1
14 Y5 32 6.0 6.0 SERVER RACK 14 150 1
15 B5 32 4.0 4.0 SERVER ROOM 150 2 1
16 R6 20 4.0 4.0 IT RACK 1 175
17 Y6 20 4.0 4.0 IT RACK 2 190
18 B6 20 4.0 4.0 IT RACK 3 175
19 R7 20 4.0 4.0 12u RACK 1
185
20 Y7 20 4.0 4.0 IT ROOM 3
190
21 B7 20 4.0 4.0 IT RACK 4
175
22 R8 32 6.0 6.0 CCCTV RACK 1
185
23 Y8 32 6.0 6.0 CCCTV RACK 1
190
24 B8 32 SPARE

25 R9 SPACE

26 Y9 SPACE

27 B9 SPACE

28 R10 SPACE

Cable Size : 4C 120 mm2 CU/FR/XLPE/LSOH ECC


+ 70 mm2

Total connected Load (in


kVA)
Total connected Load curren
(A)
Breaker current (A) (TCL current +25% of T

4mm2 R 750 5
4mm2 Y 750 5
4mm2 B 750 5
4mm2 Y/G 2250 15
4mm2 Balck 2250 15
6mm2 R 753 5
6mm2 Y 753 5
6mm2 B 753 5
6mm2 Y/G 2259 15
6mm2 Balck 6777 15
:- RIYADH, KSA
Area :- SERVER ROOM - MZ ADMIN
Loc

Demand Load per circuit Diversity


factor kVA Load
FCU/V
Unit KVA Remarks
16A I.S AV R Y B

3.88 1.0 3.88 3.88

3.88 1.0 3.88 3.88


3.88 1.0 3.88 3.88
3.88 1.0 3.88 3.88
3.88 1.0 3.88 3.88
3.88 1.0 3.88 3.88
3.88 1.0 3.88 3.88

3.88 1.0 3.88 3.88


3.88 1.0 3.88 3.88

3.88 1.0 3.88 3.88


3.88 1.0 3.88 3.88
3.88 1.0 3.88 3.88
3.88 1.0 3.88 3.88
3.88 1.0 3.88 3.88
1 0.44/0.22 0.5 0.98 0.49
1 2.22 1.0 2.22 2.22
1 2.22 1.0 2.22 2.22
1 2.22 1.0 2.22 2.22
0.44 1.0 0.44 0.44

0.44 0.5 1.32 0.66

1 2.22 1.0 2.22 2.22

3.88 1.0 3.88 3.88

3.88 1.0 3.88 3.88

Total Load per 25.94 26.82 20.94 72.55


Phase

Total connected Load (in 73.70 kVA


kVA)
Total connected Load current 106.38 A
(A)
Breaker current (A) (TCL current +25% of TCL 132.97 A
Current)
Load after 72.55 kVA
Diversity
Amana Contracting 
Project DB Ref FED From :- ALPHA NOON LOGISTICS HUB - PHASE 1 EDB-AD Details of Connected Load / Max. Demand
Rating of Incomer :- ESMDB-B2 40A TP Owner :- Al Muhaidib
:- D & B Contractor :- Amana Contracting

Sr. MCB RTG in CKT ECC Connected Loads / Points


No. Amp Wire Size Wire Size
EX 13A 13A 15A Ceiling
Rating of ELCB CKT No. mm2 mm2 Room / Area Fan S/O D/O S/O Fan
LTG Eqpt. SPUR W/H

1 R1 20 4.0 4.0 4
CCTV MONITOR 150
2 Y1 20 4.0 4.0 CCTV ROOM WORK STATION 135 4
3 B1 20 4.0 4.0 IT RACK 160 1
FR WIRING 4 R2 20 4.0 4.0 FACP 125 1
FR WIRING 5 Y2 20 4.0 4.0 MIMIC PANEL 145 1
FR WIRING 6 B2 20 4.0 4.0 TURNSTILE 150 4
7 R3 20 4.0 4.0 4
WALK THROUGH SCANNER 175
FR WIRING 8 Y3 20 4.0 4.0 FACP 120 1
FR WIRING 9 B3 20 4.0 4.0 2
TURNSTILE 145
10 R4 20 4.0 4.0 DDC-10 95 1
11 Y4 20 4.0 4.0 DDC-11 120 1
12 B4 20 4.0 4.0 DDC-12 175 1
13 R5 20 4.0 4.0 ACCESS CONTROL PANEL GF 95 4

14 Y5 20 4.0 4.0 ACCESS CONTROL PANEL MEZZ 78 3

15 B5 20 DDC-09 125 1
16 R6 32 6.0 6.0 IDU-A-01 165
17 Y6 20 3C-4mm2 2
XLPE/SWA/PVC
CCTV EXTERNAL 295
18 B6 20 3C-4mm2 2
XLPE/SWA/PVC
CCTV EXTERNAL 350
19 R7 20 3C-4mm2 2
XLPE/SWA/PVC
CCTV EXTERNAL 320
20 Y7 20 3C-4mm2 4
XLPE/SWA/PVC
CCTV EXTERNAL 320
21 B7 20 4.0 4.0 MSFD 120 2
22 R8 20 4.0 4.0 MSFD 120 2
23 Y8 20 4.0 4.0 MSFD 130 2

24 B8 SPACE

Cable Size : 4C 25 mm2 CU/FR/XLPE/LSOH


+ 16 mm2 ECC

3c-4mm2 XLPE/SWA/PVC 1285 Hold subject to cctv selections


4mm2 R 950 6
4mm2 Y 950
4mm2 B 950
4mm2 Y/G 2850
4mm2 Black 2850
Area :- RIYADH, KSA
Loc :- ADMIN BLOCK - GF ELECTRICAL ROOM

ads / Points Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
D/W 32A I.S ISO R Y B

0.22 1.0 0.88 0.88

0.44 1.0 1.76 1.76


0.60 1.0 0.60 0.60
0.88 1.0 0.88 0.88
0.44 1.0 0.44 0.44
0.11 1.0 0.44 0.44
0.22 1.0 0.88 0.88

0.88 1.0 0.88 0.88


0.11 1.0 0.22 0.22

0.44 1.0 0.44 0.44


0.44 1.0 0.44 0.44
0.44 1.0 0.44 0.44
0.09 1.0 0.36 0.36

0.09 1.0 0.27 0.27

0.44 1.0 0.44 0.44


1 5.00 1.0 5.00 5.00
0.11 1.0 0.22 0.22

0.11 1.0 0.44 0.44

0.11 1.0 0.22 0.22

0.11 1.0 0.44 0.44

0.22 1.0 0.44 0.44


0.22 1.0 0.44 0.44
0.22 1.0 0.44 0.44

1.0 0.00

Total Load per Phase 9.10 4.89 3.02


17.01
Total connected Load (in kVA) 17.01 kVA
Total connected Load current (A) 24.55 A
Breaker current (A) (TCL current +25% of TCL 30.69 A
Current)
Load after Diversity 17.01 kVA
Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand Area :-
NOON
FED From :- USS-4 D & B Contractor :- Amana Contracting Location

Max assumed ECC Size


Rating Amps PVC/XLPE Cable Size length of Cable Connected Load - KW
(Mtrs)
Sr.
MCCB Fault Duty KA
No 2/4 x 1C R-Phase
Nos 1C mm2
mm2 KVA
(A)
Circuit Feeder DB no SP/ TP ISO MCB 4C mm2
Incomer TP 200 36 XLPE/PVC 1 4C 95 20 1 1C 50 50.00

Outgoing

1 CHWP - 01 TP 100 25 XLPE/PVC 1 4C. 25 10 1 1C 16 16.67

2 CHWP - 02 TP 100 25 XLPE/PVC 1 4C. 25 10 1 1C 16 16.67

3 CHWP - 03 (ST.BY) TP 100 25 XLPE/PVC 1 4C. 25 10 1 1C 16 16.67

Total Connected Load per Phase Total…….. 50.00

Demand Factor = 0.60 Total connected 150.00 KVA

Max. Demand = 90.00 KVA load

Amana Contracting TCL 150.00

Type of Meter : MD 90.00


MD CURRENT 129.91

4c-25mm2 xlpe-pvc 60
a :- RIYADH SMDB Ref :- CP-B2-CHWP Owner :-

Location :- ROOF SERVICE BLOCK 2

Connected Load - KW KWH Meter

Y-Phase B-Phase Demand Load 3 Ph 3 Ph LV/HV


Demand Factor
KVA KVA KVA (2) (3) CT (4)
Total KVA Total kW ST.BY 1 Ph (1) Remarks
50.00 50.00 150.00

16.67 16.67 50.00 45.00 0.90 45.00


ELCB + VFD

16.67 16.67 50.00 45.00 0.90 45.00


ELCB + VFD

16.67 16.67 50.00 45.00 50.00 0.90 0.00 ELCB + VFD

50.00 50.00 150.00 135.00 50.00 90.00 0 0 0 0

Actual Load = 100.00 KVA Stand By Load = 50.00 KVA

MD CURRENT + * BMS Interfacing to be provided


25% 162.38 * Fire Alarm Interfacing to be provided

INCOMER BREAKER 200


SIZE (A)
Project SMDB Ref :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
FED From :- USS-13 Owner :- NOON - KSA
:- QRM D & B Contractor :- Amana Contracting

Rating Amps PVC/XLPE Cable Size ECC Size Connected Load - KW


Max

Sr. Circuit Feeder DB no SP/ TP ISO MCCB MCB Fault Duty assumed R-Phase Y-Phase
No KA length of KVA KVA
Nos 4C mm2 Cable (Mtrs) Nos 1C mm2
A

Incomer TP ACB 2500 50 MEDIUM VOLTAGE CABLE 3C 120

Outgoing

1 ISO - FOR CONVEYOR ( TP 300 36 XLPE/PVC 1 4C 150 59 1 1C 70 55.56 55.56


BLOCK-H)
2 ISO -5 TP 300 36 XLPE/PVC 1 4C 240 160 1 1C 120 55.56 55.56

3 ISO-4 TP 630 36 XLPE/PVC 3 4C 185 172 3 1C 95 111.11 111.11

4 ISO - FOR CONVEYOR TP 300 36 XLPE/PVC 1 4C 150 55 1 1C 150 55.56 55.56


( BLOCK-J)
5 SPARE TP 400 36 66.67 66.67

6 SPARE TP 300 36 50.00 50.00

7 CAP. BANK (CB-13) TP 800 36 XLPE/PVC 2 4C 240 1 240

8 SPACE TP

Total Connected Load per Phase Total…….. 394.44 394.44

Demand Factor = 0.73 Max. Demand = 863.33 KVA Total connected load 1183.33 KVA Actual Load =

Amana Contracting
Type of Meter : BMS metering

4c-150mm2+70mm2G 60
4c240mm2+120mm2G 160
4c-185mm2+95mm2g 285
4c-150mm2+70mm2G 150
4c-240mm2 50
Area :- RIYADH
Location :- SERVICE BLOCK -2

Connected Load - KW KWH Meter

B-Phase Demand Demand Demand 3 Ph 3 Ph LV/HV Remarks


KVA Load KVA Factor Load KVA (2) (3) CT (4)
Total KVA Total kW (Down stream) (UP stream) 1 Ph (1)

ST BY
1183.33 1

55.56 166.67 150.00 166.67 0.70 116.67

55.56 166.67 150.00 166.67 0.70 116.67

111.11 333.33 300.00 333.33 0.70 233.33

55.56 166.67 150.00 166.67 0.70 116.67

66.67 200.00 180.00 200.00 0.80 160.00

50.00 150.00 200.00 150.00 0.80 120.00


250KVAR WITH
DETUNED FILTER

394.44 1183.33 1065.00 863.33 0 0 0 0 0.00

Actual Load = 1183.33 KVA Stand By Load = 0.00 KVA


Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
SMDB Ref :- USS-5 Owner :- NOON - KSA

FED From :- QRM D & B Contractor :- Amana Contracting

Max ECC Size


Rating Amps PVC/XLPE Cable Size assumed Connected Load - KW
length of
Cable (Mtrs) Nos 1C mm2
MCCB
R-Phase Y-Phase B-Phase
KVA KVA KVA
Sr. (A) Fault Duty
No Circuit Feeder DB no SP/ TP ISO MCB KA Nos 4C mm2
Incomer TP ACB 2500 50 MEDIUM VOLTAGE CABLE 3C 120

Outgoing

1 SMDB-WH-2 TP 160 36 XLPE/PVC 1 4C 120 90 1 1C 70 49.10 51.10 31.07

2 ISO-3 TP 630 36 XLPE/PVC 2 4C 150 34 1 1C 150 94.44 94.44 94.44

3 ISO- 9 (PROVISION FOR MT) TP 630 36 XLPE/PVC 2 4C 150 35 1 1C 150 111.11 111.11 111.11

4 ISO-10 (PROVISION FOR MT) TP 630 36 XLPE/PVC 2 4C 150 36 1 1C 150 111.11 111.11 111.11

5 SMDB-ADMIN TP 800 36 XLPE/PVC 2 4C 240 80 1 1C 240 176.94 175.57 186.56

6 SPARE TP 160 36 27.78 27.78 27.78

7 CAP. BANK (CB-5) TP 800 36 XLPE/PVC 2 4C 240 1 240

8 SPACE TP

Total Connected Load per Phase Total…….. 570.48 571.11 562.08

Demand Factor = 0.71 Max. Demand = 1195.52 KVA Total connected load 1678.90 KVA Actual Load =

Amana Contracting

Type of Meter : BMS metering


Area :- RIYADH

Location :- SERVICE BLOCK -2

Connected Load - KW KWH Meter

Demand Load Demand Factor Demand Load


KVA (Down KVA (UP
stream) stream) 3 Ph 3 Ph LV/HV
(2) (3) CT (4)
Total KVA Total kW ST BY 1 Ph (1) Remarks
1678.90 1

106.50 95.85 74.80 0.90 67.32

283.33 255.00 283.33 0.70 198.33

333.33 300.00 333.33 0.80 266.67

333.33 300.00 333.33 0.80 266.67

539.06 485.17 375.77 0.90 338.20

83.33 75.00 83.33 0.70 58.33

250KVAR WITH DETUNED


FILTER

1678.90 1511.02 1195.52 0 0 0 0 0.00

1678.90 KVA Stand By Load = 0.00 KVA


Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
SMDB Ref :- SMDB-WH-2 :- NOON

Owner
FED From :- USS-5 D & B Contractor :- Amana Contracting

ECC Size
Rating Amps PVC/XLPE Cable Size Connected Load - KW
Max
MCCB assumed
2/4 x 1C length of
Cable (Mtrs) Nos 1C mm2
mm2
Sr. A R-Phase Y-Phase B-Phase
No Circuit Feeder DB no SP/ TP ISO MCB Fault Duty KA 4C mm2 KVA KVA KVA
Incomer TP 160 36 XLPE/PVC 1 4C 120 90 1 1C 70 49.10 51.10 49.20

Outgoing

1 DB-WH-L3 TP 80 25 XLPE/PVC 1 4C 25 6 1 1C 16 9.27 11.29 10.52

2 DB-WH-L4 TP 80 25 XLPE/PVC 1 4C 95 175 1 1C 50 9.60 9.40 9.66

3 DB-WH-P1 TP 100 25 XLPE/PVC 1 4C 35 121 1 1C 16 30.23 30.42 29.02

4 SPARE TP 63 25

5 SPACE

6 SPACE

Total Connected Load per Phase Total…….. 49.10 51.10 49.20

Total connected load


Demand Factor = 0.70 Max. Demand = 74.80 KVA 106.50 KVA Actual Load =

TCL 106.50 MD CURRENT + 25%


Amana Contracting MD 74.80 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 107.9734411
TOTAL Spare LOAD 0.00 KVA
Area :- RIYADH

Location :- GF ADMIN BLOCK(ELECT RM)

nected Load - KW KWH Meter

Demand Demand Factor Demand


Load KVA Load KVA
(Down stream) (UP stream)

3 Ph 3 Ph LV/HV
Total KVA Total kW ST BY 1 Ph (1) (2) (3) CT (4) Remarks
106.50

31.07 27.96 31.07 0.90 27.96

28.66 25.79 28.66 0.90 25.79

46.78 42.10 23.39 0.90 21.05

106.50 95.85 0.00 74.80 0 0 0 0

106.50 KVA Stand By Load = 0.00 KVA

134.966801
160
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand

DB Ref :- DB-WH-L3 Owner :- Al Muhaidib Area :- RIYADH, KSA


FED From :- SMDB-WH-2 D & B Contractor :- Amana Contracting Loc :- GF-WAREHOUSE Ratin

Rating of Sr. MCB CKT ECC Connected Loads / Points


ELCB No. RTG in Wire Size Wire Size
Amp mm2 mm2 EX 13A 15A Ceiling FCU/V
CKT No. Room / Area Fan S/O S/O Fan AV
LTG Eqpt. SPUR W/H D/W HD ISO

1 R1 16 6.0 6.0 Warehouse- GF 4

2 Y1 16 6.0 6.0 Warehouse- GF 8

3 B1 16 6.0 6.0 Warehouse- GF 5

4 R2 16 6.0 6.0 Warehouse- GF 8

5 Y2 16 6.0 6.0 PERFUME STORE 12

6 B2 16 6.0 6.0 PERFUME STORE 12

7 R3 16 6.0 6.0 PERFUME STORE 6

8 Y3 16 6.0 6.0 Warehouse- GF 8

9 B3 16 6.0 6.0 Warehouse- GF 8

10 R4 16 6.0 6.0 Warehouse- GF 8

11 Y4 16 6.0 6.0 Warehouse- GF 8

12 B4 16 6.0 6.0 Warehouse- GF 8

13 R5 16 6.0 6.0 Warehouse- GF 8

14 Y5 16 6.0 6.0 Warehouse- GF 8

15 B5 16 6.0 6.0 Warehouse- GF 8

16 R6 16 6.0 6.0 Warehouse- GF 5

17 Y6 16 6.0 6.0 Warehouse- GF 8

18 B6 16 6.0 6.0 Warehouse- GF 8

19 R7 10 SPARE FOR EM LIGHT

20 Y7 10 SPARE FOR EM LIGHT

21 B7 10 SPARE FOR EM LIGHT

22 R8 10 SPARE FOR EM LIGHT

23 Y8 16 SPARE

24 B8 16 SPARE

Cable Size :
4C 25 mm2 XLPE/PVC Total Load per Phase
+ 16 mm2 ECC

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of TCL

Load after Diversity

6mm2 R 6
6mm2 Y 6
6mm2 B 6
6mm2 Y/G 18
6mm2 Black 18
:- RIYADH, KSA
:- GF-WAREHOUSE Rating of Incomer 80A TP INCOMER TO BE MONITOR BY BMS (POWER ON/OFF/TRIP STATUS)

Demand Load per circuit Diversity


factor kVA Load
Unit KVA Remarks
R Y B

0.26 1.0 1.02 1.02

0.26 1.0 2.04 2.04

0.26 1.0 1.28 1.28

0.26 1.0 2.04 2.04

0.07 1.0 0.86 0.86

0.07 1.0 0.86 0.86

0.07 1.0 0.43 0.43

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04

0.26 1.0 1.28 1.28

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04

1.00 0.20 0.20

1.00 0.20 0.20

1.00 0.20 0.20

1.0 0.20 0.20

1.0 0.00 0.00

1.0 0.00 0.00

Total Load per Phase 9.27 11.29 10.52 31.07

Total connected Load (in kVA) 31.07 kVA

Total connected Load current (A) 44.85 A

r current (A) (TCL current +25% of TCL 56.06 A


Current)
Load after Diversity 31.07 kVA
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand

DB Ref :- DB-WH-L4 Owner :- Al Muhaidib Area :- RIYADH, KSA


FED From :- SMDB-WH-2 D & B Contractor :- Amana Contracting Loc :- GF-WAREHOUSE Rati

Rating of Sr. MCB CKT ECC Connected Loads / Points


ELCB No. RTG in Wire Size Wire Size
Amp mm2 mm2 EX 13A 15A Ceiling FCU/V
CKT No. Room / Area Fan S/O S/O Fan AV
LTG Eqpt. SPUR W/H D/W HD ISO

1 R1 16 6.0 6.0 Warehouse- GF 7

2 Y1 16 6.0 6.0 Warehouse- GF 7

3 B1 16 6.0 6.0 Warehouse- GF 5

4 R2 16 6.0 6.0 Warehouse- GF 5

5 Y2 16 6.0 6.0 Warehouse- GF 5

6 B2 16 6.0 6.0 MT Warehouse 8

7 R3 16 6.0 6.0 MT Warehouse 8


8 Y3 16 6.0 6.0 MT Warehouse 8
9 B3 16 6.0 6.0 MT Warehouse 8
10 R4 16 6.0 6.0 MT Warehouse 8
11 Y4 16 6.0 6.0 MT Warehouse 8
12 B4 16 6.0 6.0 MT Warehouse 8
13 R5 16 6.0 6.0 MT Warehouse 8
14 Y5 16 6.0 6.0 MT Warehouse 8
15 B5 16 6.0 6.0 MT Warehouse 8
16 R6 16 SPARE
17 Y6 16 SPARE
18 B6 16 SPARE
19 R7 10 SPARE FOR EM LIGHT

20 Y7 10 SPARE FOR EM LIGHT

21 B7 10 SPARE FOR EM LIGHT

22 R8 10 SPARE FOR EM LIGHT

23 Y8 16 SPARE

24 B8 16 SPARE

Cable Size :
4C 95 mm2 XLPE/PVC Total Load per Phase
+ 50 mm2 ECC

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of TCL

Load after Diversity

6mm2 R 5
6mm2 Y 5
6mm2 B 5
6mm2 Y/G 15
6mm2 Black 15
:- RIYADH, KSA
:- GF-WAREHOUSE Rating of Incomer 80A INCOMER TO BE MONITOR BY BMS (POWER ON/OFF/TRIP STATUS)

Demand Load per circuit Diversity


factor kVA Load
Unit KVA Remarks
R Y B

0.26 1.0 1.79 1.79

0.26 1.0 1.79 1.79

0.26 1.0 1.28 1.28

0.26 1.0 1.28 1.28

0.26 1.0 1.28 1.28

0.26 1.0 2.04 2.04

0.26 1.0 2.04 2.04


0.26 1.0 2.04 2.04
0.26 1.0 2.04 2.04
0.26 1.0 2.04 2.04
0.26 1.0 2.04 2.04
0.26 1.0 2.04 2.04
0.26 1.0 2.04 2.04
0.26 1.0 2.04 2.04
0.26 1.0 2.04 2.04
0.26 1.0 0.00 0.00
0.26 1.0 0.00 0.00
1.0 0.00 0.00
1.0 0.20 0.20

1.0 0.20 0.20

1.0 0.20 0.20

1.0 0.20 0.20

1.0 0.00 0.00

1.0 0.00 0.00

Total Load per Phase 9.60 9.40 9.66 28.66

Total connected Load (in kVA) 28.66 kVA

Total connected Load current (A) 41.36 A

r current (A) (TCL current +25% of TCL 51.70 A


Current)
Load after Diversity 28.66 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Dema
From :- DB-WH-P1 SMDB-WH-2 100A TP Owner :- Al Muhaidib Area
Rating of Incomer :- D & B Contractor :- Amana Contracting Loc

Rating of ELCB Sr. CKT No. MCB CKT Wire ECC Room / Area Connected Loads / Points
No. RTG in Size mm2 Wire Size
Amp mm2 EX 13A 13A 15A Ceiling 16A FCU/V
LTG Eqpt. Fan S/O D/O S/O SPUR W/H Fan D/W IND. ISO AV
S/O

1 R1 ISOLATOR FOR ROLL UP DOOR+DOCK


LEVELER
2 Y1 20 4.0 4.0 1
3 B1
4 R2 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
5 Y2 20 4.0 4.0 1
6 B2
7 R3 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
8 Y3 20 4.0 4.0 1
9 B3
10 R4
11 Y4 20 4.0 4.0 ISOLATOR FOR ROLLER SHUTTER 1
12 B4
13 R5 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
14 Y5 20 4.0 4.0 1
15 B5
16 R6 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
17 Y6 20 4.0 4.0 1
18 B6
19 R7 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
20 Y7 20 4.0 4.0 1
21 B7
22 R8 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
23 Y8 20 4.0 4.0 1
24 B8
25 R9 ISOLATOR FOR ROLL UP DOOR+DOCK
LEVELER
26 Y9
20 4.0 4.0 1
27 B9

28 R10 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3

29 Y10 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3

30 B10 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3

31 R11 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 4

32 Y11 20 4.0 4.0 13A SOCKET IN WAREHOUSE AREA 3

33 B11 20 SPARE

34 R12

35 Y12
20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
36 B12

37 R13

38 Y13
20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
39 B13

40 R14

41 Y14
20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
42 B14

43 R15 ISOLATOR FOR ROLL UP DOOR+DOCK


LEVELER
44 Y15
20 4.0 4.0 1
45 B15

46 R16

47 Y16
20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1

48 B16

49 R17

50 Y17
20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
51 B17

52 R18

20 4.0 4.0 16A TP INDUSTRIAL SOCKET 250 1


53 Y18
20 4.0 4.0 16A TP INDUSTRIAL SOCKET 250 1
54 B18

55 R19

56 Y19
20 4.0 4.0 16A TP INDUSTRIAL SOCKET 1
57 B19

58 R20 20 SPARE

59 Y20 20 SPARE

60 B20 20 SPARE

Cable Size : 4C 35 mm2 mm2 XLPE/PVC ECC Total Load per Phase
+ 16

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of TCL


Current)
Load after Diversity

4mm2 R 10
4mm2 Y 10
4mm2 B 10
4mm2 Y/G 30
4mm2 Black 30
Special 4mm2 250
Details of Connected Load / Max. Demand RIYADH, KSA
Area :- GF-WAREHOUSE
Loc :-

Unit KVA Demand Load per circuit Diversity Remarks


factor kVA Load

R Y B

0.5 1.00 0.50

3.00 0.5 1.00 0.50


0.5 1.00 0.50
0.5 1.00 0.50

3.00 0.5 1.00 0.50


0.5 1.00 0.50
0.5 1.00 0.50

3.00 0.5 1.00 0.50


0.5 1.00 0.50
0.5 0.56 0.28

1.67 0.5 0.56 0.28


0.5 0.56 0.28
0.5 1.00 0.50

3.00 0.5 1.00 0.50


0.5 1.00 0.50
0.5 1.00 0.50

3.00 0.5 1.00 0.50


0.5 1.00 0.50
0.5 1.00 0.50

3.00 0.5 1.00 0.50


0.5 1.00 0.50
0.5 1.00 0.50

3.00 0.5 1.00 0.50


0.5 1.00 0.50
0.5 1.00 0.50

0.5 1.00 0.50


3.00
0.5 1.00 0.50

0.44 0.5 1.33 0.67

0.44 0.5 1.33 0.67

0.44 0.5 1.33 0.67

0.44 0.5 1.78 0.89

0.22 0.5 0.67 0.33

0.5 0.56 0.28

0.5 0.56 0.28


1.67
0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28


1.67
0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28


1.67
0.5 0.56 0.28

0.5 1.00 0.50

0.5 1.00 0.50


3.00
0.5 1.00 0.50

0.5 0.56 0.28

0.5 0.56 0.28


1.67

0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28


1.67
0.5 0.56 0.28

0.5 0.56 0.28

1.67
0.5 0.56 0.28
1.67
0.5 0.56 0.28

0.5 0.56 0.28

0.5 0.56 0.28


1.67
0.5 0.56 0.28

Total Load per Phase 16.56 15.44 14.78 23.39

Total connected Load (in kVA) 46.78 kVA

Total connected Load current (A) 67.52 A

ker current (A) (TCL current +25% of TCL 84.40 A


Current)
Load after Diversity 23.39 kVA
Project :- PROJECT ALPHA - NOON KSA Details of Connected Load / Max. Demand
SMDB Ref :- SMDB-ADMIN :- NOON

Owner
FED From :- USS-5 D & B Contractor :- Amana Contracting

ECC Size
Rating Amps PVC/XLPE Cable Size Connected Load - KW
Max
assumed
MCCB length of
2/4 x 1C Cable Nos 1C mm2
(A) mm2 (Mtrs)
Sr. R-Phase Y-Phase B-Phase
No Circuit Feeder DB no SP/ TP ISO MCB Fault Duty KA 4C mm2 KVA KVA KVA
Incomer TP 800 36 XLPE/PVC 2 4C 240 80 1 1C 240 176.94 175.57 186.56

Outgoing

1 DB-GF-AD-L TP 40 25 XLPE/PVC 1 4C 10 10 1 1C 10 6.19 8.37 3.99

2 DB-MZ-AD-L TP 40 25 XLPE/PVC 1 4C 10 15 1 1C 10 4.28 4.07 3.88

3 DB-GF-AD-P TP 160 25 XLPE/PVC 1 4C 50 10 1 1C 25 30.23 30.42 29.02

4 DB-MZ-AD-P1 TP 100 25 XLPE/PVC 1 4C 25 15 1 1C 16 16.52 17.10 18.99

5 DB-MZ-AD-P2 TP 125 25 XLPE/PVC 1 4C 35 15 1 1C 16 19.26 19.80 20.70

6 DB-GF-AD-AC TP 63 25 XLPE/PVC 1 4C 16 10 1 1C 16 8.79 11.64 9.32

7 DB-MZ-AD-AC TP 160 25 XLPE/PVC 1 4C 70 15 1 1C 35 26.44 21.25 36.76

8 CCU-1 TP 80 25 XLPE/PVC 1 4C 25 45 1 1C 16 14.08 14.08 14.08

9 CP-FAHU-A-01 (HEATER) TP 125 25 XLPE/PVC 1 4C 35 45 1 1C 16 22.96 22.96 22.96

10 CP-FAHU-A-01 TP 63 25 XLPE/PVC 1 4C 16 20 1 1C 16 9.26 9.26 9.26

11 DB-EXT-3 TP 40 25 XLPE/PVC 1 4C 10 10 1 1C 10 3.90 4.53 4.28

12 DB-GR-2 TP 40 25 XLPE/SWA/PVC 1 4C 16 123 1 1C 16 6.14 3.21 4.43

13 LIFT-1 TP 40 25 XLPE/PVC 1 4C 10 40 1 1C 10 4.44 4.44 4.44

14 LIFT-2 TP 40 25 XLPE/PVC 1 4C 10 40 1 1C 10 4.44 4.44 4.44

15 SPARE TP 40 25

16 SPACE

Total Connected Load per Phase Total…….. 176.94 175.57 186.56

Total connected load


Demand Factor = 0.70 Max. Demand = 375.77 KVA 539.06 KVA Actual Load =

TCL 539.06 MD CURRENT + 25%


Amana Contracting MD 375.77 INCOMER BREAKER
SIZE (A)
Type of Meter : BMS metering MD CURRENT 542.398244
TOTAL Spare LOAD 0.00 KVA
Area :- RIYADH

Location :- GF ADMIN BLOCK(ELECT RM)

nected Load - KW KWH Meter

Demand Load Demand Factor Demand Load


KVA (Down KVA (UP
stream) stream)
3 Ph 3 Ph LV/HV
Total KVA Total kW ST BY 1 Ph (1) (2) (3) CT (4) Remarks
539.06

18.56 16.70 18.56 0.95 17.63

12.23 11.00 12.23 0.95 11.62

89.67 80.70 44.61 0.90 40.15

52.60 47.34 26.30 0.90 23.67

59.77 53.79 29.88 0.90 26.90

29.75 26.78 26.78 0.95 25.44

84.45 76.01 67.30 0.90 60.57

42.24 38.02 42.24 0.90 38.02 UVR+TIMER+CONT

68.88 62.00 68.88 0.90 61.99

27.78 25.00 27.78 0.90 25.00

12.71 11.44 12.71 0.90 11.44

13.78 12.40 10.40 0.90 9.36

13.33 12.00 13.33 0.90 12.00 ELCB 300mA

13.33 12.00 13.33 0.90 12.00 ELCB 300mA

539.06 485.17 0.00 375.77 0 0 0 0

539.06 KVA Stand By Load = 0.00 KVA

677.997805
800
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand

DB Ref :- DB-GF-AD-L Owner :- Al Muhaidib Area :- RIYADH, KSA


FED From :- SMDB-ADMIN D & B Contractor :- Amana Contracting Loc :- ADMIN BLOC

Rating of Sr. MCB CKT Wire ECC Connected Loads / Points


ELCB No. RTG in Size mm2 Wire Size
EX 13A 15A Ceiling
CKT No. Amp mm2 Room / Area Fan S/O S/O Fan
LTG Eqpt. SPUR W/H D/W HD

1 R1 10 2.5 2.5 SERVING AREA, FOOD PREP, RECEIVING 10


2 Y1 10 2.5 2.5 MALE DINING HALL 12
3 B1 10 2.5 2.5 MALE DINING HALL 18
4 R2 10 2.5 2.5 FEMALE DINING HALL 12
5 Y2 10 2.5 2.5 OFFICE AREA 10
6 B2 10 2.5 2.5 OFFICE AREA 10
7 R3 10 2.5 2.5 ENTRANCE 8
8 Y3 10 2.5 2.5 ENTRANCE 12
9 B3 10 2.5 2.5 ABLUTION, MALE PRAYER AREA, FEMALE 4,8
PRAYER AREA

10 R4 10 2.5 2.5 WHITE COLLAR ENTRANCE 8


11 Y4 10 2.5 2.5 TRAINING ROOM 6
12 B4 10
RCBO 30mA 13 R5 10 2.5 2.5 FEMALE TOILET 3,1,3

RCBO 30mA 14 Y5 10 2.5 2.5 MALE TOILET, FEMALE TOILET 1,6,6


RCBO 30mA 15 B5 10 2.5 2.5 JANITOR, MALE TOILET 6,6,1,1
16 R6 10 2.5 2.5 SUPPORT TOILETS 4,3
17 Y6 10 2.5 2.5 TRAINING ROOM 4
18 B6 10 2.5 2.5 STAIRCASE 6
19 R7 10 2.5 2.5 STORE, CORRIDOR 2,7

20 Y7 10 2.5 2.5 ELECTRICAL ROOM 3

21 B7 10 2.5 2.5 CORRIDOR 7

22 R8 10 2.5 2.5 OFFICE AREA 14

23 Y8 10 2.5 2.5 OFFICE AREA 14

24 B8 10 2.5 2.5 OFFICE AREA 14

25 R9 10 2.5 2.5 OFFICE AREA 13

26 Y9 10 2.5 2.5 BLUE COLLAR ENTRANCE 9

27 B9 10 2.5 2.5 BLUE COLLAR ENTRANCE 9

28 R10 10 2.5 2.5 SECURITY & CCTV MONITOR 4

29 Y10 10 2.5 2.5 MALE LOCKER 15

30 B10 10 2.5 2.5 TRANSFORMER ROOM 4

31 R11 10 2.5 2.5 STAIRCASE 6

32 Y11 10 2.5 2.5 STAIRCASE 4

33 B11 10 2.5 2.5 STAIRCASE 8

34 R12 10 SPARE

35 Y12 10 SPARE

36 B12 10 SPARE

37 R13 10 2.5 2.5 EM LIGHT 25,5

38 Y13 10 2.5 2.5 EM LIGHT 21,3,2

39 B13 10 2.5 2.5 EM LIGHT 18,5,1

40 R14 10 2.5 2.5 EM LIGHT 17,3,3,1,1

41 Y14 SPACE

42 B14 SPACE
Cable Size :
4C 10 mm2 XLPE/PVC Total Load per Phase
+ 10 mm2 ECC

Total connected Load (in kVA)

Total connected Load current (A)

Breaker current (A) (TCL current +25% of

Load after Diversity


2.5mm2 R 10
2.5mm2 Y 10
2.5mm2 B 10
2.5mm2 Y/G 30
2.5mm2 Black 30
Area :- RIYADH, KSA
Loc :- ADMIN BLOCK -GF ELECTRICAL ROOM Rating of Incomer 40A TP

Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
ISO R Y B

0.04 1.0 0.40 0.40


0.04 1.0 0.48 0.48
0.04 1.0 0.72 0.72
0.04 1.0 0.48 0.48
0.04 1.0 0.40 0.40
0.04 1.0 0.40 0.40
0.33 1.0 2.67 2.67
0.40 1.0 4.80 4.80
.03, .05 1.0 0.47 0.47

0.03 1.0 0.24 0.24


0.04 1.0 0.24 0.24

.02,0.03,0.03 1.0 0.17 0.17

0.03,0.03,0.02 1.0 0.31 0.31


0.03,0.02,0.03 1.0 0.39 0.39
0.03,0.02 1.0 0.17 0.17
0.04 1.0 0.16 0.16
0.033 1.0 0.20 0.20
0.05,.03 1.0 0.30 0.30

0.05 1.0 0.16 0.16

0.03 1.0 0.18 0.18

0.04 1.0 0.56 0.56

0.04 1.0 0.56 0.56

0.04 1.0 0.56 0.56

0.04 1.0 0.52 0.52

0.04 1.0 0.36 0.36

0.04 1.0 0.36 0.36

0.04 1.0 0.16 0.16

0.04 1.0 0.60 0.60

0.08 1.0 0.31 0.31

0.03 1.0 0.20 0.20

0.03 1.0 0.13 0.13

0.03 1.0 0.27 0.27

0.007, 0.001 1.0 0.18 0.18

0.007, 0.001 1.0 0.17 0.17

0.007, 0.001 1.0 0.14 0.14

0.007, 0.001 1.0 0.15 0.15

Total Load per Phase 6.19 8.37 3.99 18.56

Total connected Load (in kVA) 18.56 kVA

Total connected Load current (A) 26.78 A

Breaker current (A) (TCL current +25% of TCL 33.48 A


Current)
Load after Diversity 18.56 kVA
Amana Contracting 
Project DB Ref FED From :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-MZ-AD-L Details of Connected Load / Max. Demand
Rating of Incomer :- SMDB-ADMIN 40A TP Owner :- Al Muhaidib
:- D & B Contractor :- Amana Contracting

Sr. MCB CKT ECC Connected Loads / Points


No. RTG in Wire Size Wire Size
EX 13A 15A Ceiling
Rating of ELCB CKT No. Amp mm2 mm2 Room / Area Fan S/O S/O Fan
LTG Eqpt. SPUR W/H D/W HD

1 R1 10 2.5 2.5 ELECTRICAL ROOM, CORRIDOR 3,3


2 Y1 10 2.5 2.5 TRAINING ROOM 8
3 B1 10 2.5 2.5 TRAINING ROOMS 10
4 R2 10 2.5 2.5 STOCK ROOM, CORRIDOR 3,2
5 Y2 10 2.5 2.5 PANTRY 5
6 B2 10 2.5 2.5 TRAINING ROOM 6
7 R3 10 2.5 2.5 SERVER ROOM 12
8 Y3 10 2.5 2.5 IT ROOM 4
9 B3 10 2.5 2.5 PREPARATIOIN AREA, DUMP WAITER, 7
RECEIVING

RCBO 30mA 10 R4 10 2.5 2.5 MALE TOILET, FEMALE TOILET 1,9,9


RCBO 30mA 11 Y4 10 2.5 2.5 MALE TOILET, FEMALE TOILET 1,6,6
RCBO 30mA 12 B4 10 2.5 2.5 MALE TOILET 6,6
13 R5 10 2.5 2.5 CCTV CONTROL ROOM 9
14 Y5 10 2.5 2.5 CCTV CONTROL ROOM 9
15 B5 10 2.5 2.5 OFFICE AREA 7
16 R6 10 2.5 2.5 OFFICE AREA 14
17 Y6 10 2.5 2.5 OFFICE AREA 14
18 B6 10 2.5 2.5 OFFICE AREA 14
19 R7 10 2.5 2.5 OFFICE AREA 12

20 Y7 10 2.5 2.5 OFFICE AREA 12

21 B7 10 2.5 2.5 OFFICE AREA 12

22 R8 10 2.5 2.5 OFFICE AREA 12

23 Y8 10 2.5 2.5 MALE DINING, SERVING AREA 14

24 B8 10 2.5 2.5 MALE DINING, SERVING AREA 11

25 R9 10 2.5 2.5 PRAYER ROOM, ABLUTION 2,2,2

26 Y9 10 2.5 2.5 OFFICE AREA 14

27 B9 10 2.5 2.5 OFFICE AREA 10

28 R10 10 SPARE

29 Y10 10 SPARE

30 B10 10 SPARE

31 R11 10 2.5 2.5 EM LIGHT 24,2

32 Y11 10 2.5 2.5 EM LIGHT 19,3,2,1

33 B11 10 2.5 2.5 EM LIGHT 16,2,4,1,1

34 R12 10 2.5 2.5 EM LIGHT 26,1

35 Y12 SPACE

36 B12 SPACE

Cable Size : 4C 10 mm2 XLPE/PVC ECC Total Load per Pha


+ 10 mm2

Total connected Load (in kVA

Total connected Load current (A

Breaker current (A) (TCL current +25%

Load after Diversity

2.5mm2 R 10
2.5mm2 Y 10
2.5mm2 B 10
2.5mm2 Y/G 30
2.5mm2 Black 30
Area Loc :- RIYADH, KSA
:- ADMIN BLOCK -MEZZ. ELECTRICAL ROOM

Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
ISO R Y B

.06,.03 1.0 0.26 0.26


0.05 1.0 0.36 0.36
0.05 1.0 0.45 0.45
0.05,0.03 1.0 0.19 0.19
0.05 1.0 0.23 0.23
0.05 1.0 0.27 0.27
0.06 1.0 0.70 0.70
0.05 1.0 0.18 0.18
0.05 1.0 0.32 0.32

.03,.03,.02 1.0 0.45 0.45


.03,.03,.02 1.0 0.31 0.31
.03,.02 1.0 0.28 0.28
0.05 1.0 0.41 0.41
0.05 1.0 0.41 0.41
0.05 1.0 0.32 0.32
0.05 1.0 0.63 0.63
0.05 1.0 0.63 0.63
0.05 1.0 0.63 0.63
0.05 1.0 0.54 0.54

0.05 1.0 0.54 0.54

0.05 1.0 0.54 0.54

0.05 1.0 0.54 0.54

0.05 1.0 0.63 0.63

0.05 1.0 0.50 0.50

.05,.03,.03 1.0 0.21 0.21

0.05 1.0 0.63 0.63

0.05 1.0 0.45 0.45

0.007, 0.001 1.0 0.17 0.17

0.007, 0.001 1.0 0.16 0.16

0.007, 0.001 1.0 0.13 0.13

0.007, 0.001 1.0 0.18 0.18

Total Load per Phase 4.28 4.07 3.88 12.23

Total connected Load (in kVA) 12.23 kVA

Total connected Load current (A) 17.65 A

Breaker current (A) (TCL current +25% of TCL 22.06 A


Current)
Load after Diversity 12.23 kVA
Amana Contracting 
Project DB Ref FED :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand
From :- DB-GF-AD-P SMDB-ADMIN 160A TP Owner :- Al Muhaidib
Rating of Incomer :- D & B Contractor :- Amana Contracting

Rating of ELCB Sr. CKT No. MCB CKT Wire ECC Room / Area Connected Loads / Points
No. RTG in Size mm2 Wire
Amp Size EX 13A 13A 15A Ceiling
mm2 LTG Eqpt. Fan S/O D/O S/O SPUR W/H Fan D/W HD

1 R1 20 4.0 4.0 RECEIVING, FOOD PREPARATION 2 2


2 Y1 20 4.0 4.0 MALE DINING HALL 1 2
3 B1 20 4.0 4.0 FEMALE DINING HALL 3 2
4 R2 20 4.0 4.0 OFFICE AREA 4
5 Y2 20 4.0 4.0 OFFICE AREA 4
6 B2 20 4.0 4.0 OFFICE AREA 4
7 R3 20 4.0 4.0 OFFICE AREA 4
8 Y3 20 4.0 4.0 OFFICE AREA 4
9 B3 20 4.0 4.0 OFFICE AREA 4
10 R4 20 4.0 4.0 OFFICE AREA 4
11 Y4 20 4.0 4.0 ELEC. ROOM, CORRIDOR,FEMALE PRAYER AREA,MALE PRAYER 5
AREA,

12 B4 20 4.0 4.0 ENTRANCE 2


13 R5 20 4.0 4.0 ENTRANCE 3
14 Y5 20 4.0 4.0 TRAINING ROOM 4
RCBO 30mA 15 B5 20 4.0 4.0 ABLUTION 1
16 R6 20 4.0 4.0 OFFICE AREA 4
17 Y6 20 4.0 4.0 OFFICE AREA 4
18 B6 20 4.0 4.0 OFFICE AREA 4
19 R7 20 4.0 4.0 OFFICE AREA 4
20 Y7 20 4.0 4.0 OFFICE AREA 4
21 B7 20 4.0 4.0 OFFICE AREA 4
22 R8 20 4.0 4.0 OFFICE AREA 4
23 Y8 20 4.0 4.0 OFFICE AREA 4
24 B8 20 4.0 4.0 OFFICE AREA 4
25 R9 20 4.0 4.0 OFFICE AREA 4
26 Y9 20 4.0 4.0 OFFICE AREA 4
27 B9 20 4.0 4.0 OFFICE AREA 4
28 R10 20 4.0 4.0 OFFICE AREA 4

29 Y10 20 4.0 4.0 OFFICE AREA 4

30 B10 20 4.0 4.0 OFFICE AREA 4

31 R11 20 4.0 4.0 OFFICE AREA 4

32 Y11 20 4.0 4.0 OFFICE AREA 4

33 B11 20 4.0 4.0 OFFICE AREA 4

34 R12 20 4.0 4.0 OFFICE AREA 4

35 Y12 20 4.0 4.0 OFFICE AREA 4

36 B12 20 4.0 4.0 OFFICE AREA 4

37 R13 20 4.0 4.0 OFFICE AREA 4

38 Y13 20 4.0 4.0 OFFICE AREA 4

39 B13 20 4.0 4.0 OFFICE AREA 4

40 R14 20 4.0 4.0 STORE/ JANITOR 3 1

41 Y14 20 4.0 4.0 TRAINING ROOM 4

42 B14 20 4.0 4.0 ENTRANCE 3

43 R15 20 SPARE

44 Y15 20 4.0 4.0 MALE LOCKER, SECURITY & CCTV MONITOR 4

45 B15 20 4.0 4.0 CORRIDOR, RECIVING, DUMP WAITER 4

RCBO 30mA 46 R16 20 4.0 4.0 MALE TOILET 1

RCBO 30mA 47 Y16 20 4.0 4.0 MALE TOILET 1

RCBO 30mA 48 B16 20 4.0 4.0 FEMALE TOILET 1

RCBO 30mA 49 R17 20 4.0 4.0 FEMALE TOILET 1

50 Y17 20 4.0 4.0 WHITE COLLAR ENTRANCE (FOR SLIDING DOOR) 1

RCBO 30mA 51 B17 20 4.0 4.0 FEMALE TOILET 1

RCBO 30mA 52 R18 20 4.0 4.0 MALE TOILET 1

RCBO 30mA 53 Y18 20 4.0 4.0 FEMALE TOILET 1

54 B18 20 SPARE
55 R19 20 4.0 4.0 CORRIDOR/ STAIR 2

56 Y19 20 4.0 4.0 TRAINING ROOM 1 1

RCBO 30mA 57 B19 20 4.0 4.0 SUPPORT TOILETS 1

RCBO 30mA 58 R20 20 4.0 4.0 SUPPORT TOILETS 1

59 Y20 20 4.0 4.0 TRAINING ROOM 1 1

60 B20 20 4.0 4.0 FEMALE DINING HALL 3

61 R21 20 4.0 4.0 ENTRANCE WHITE COLLAR 2

62 Y21 20 4.0 4.0 MALE DINING HALL 5

63 B21 20 4.0 4.0 ENTRANCE BLUE COLLAR 2

64 R22 SPACE

65 Y22 SPACE

66 B22 SPACE

Cable Size : 4C 50 mm2 XLPE/PVC ECC Total Load per Phas


+ 25 mm2

Total connected Load (in kVA)

Total connected Load current

Breaker current (A) (TCL current +25%


Cu
Load after Diversity

4mm2 R 10
4mm2 Y 10
4mm2 B 10
4mm2 Y/G 30
4mm2 Black 30
Area Loc :- RIYADH, KSA
:- SERVICE BLOCK-1, 2, 4,5 (TYPICAL) - GF ELECTRICAL
ROOM

Unit KVA Demand Load per circuit Diversity Remarks


factor kVA Load
FCU/V
ISO AV R Y B

0.22,0.44 0.5 1.33 0.67


0.22,0.44 0.5 1.11 0.56
0.22,0.44 0.5 1.56 0.78
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.22,0.44 0.5 1.11 0.56

0.22 0.5 0.44 0.22


0.44 0.5 1.33 0.67
0.44 0.5 1.78 0.89
1.67 0.5 1.67 0.83
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.22 0.5 0.88 0.44

0.44 0.5 1.76 0.88

0.22 0.5 0.67 0.33

0.22 0.5 0.89 0.44

0.22 0.5 0.89 0.44

1.67 0.5 1.67 0.83

1.67 0.5 1.67 0.83

1.67 0.5 1.67 0.83

1.67 0.5 1.67 0.83

0.22 0.5 0.22 0.11

1.67 0.5 1.67 0.83

1.67 0.5 1.67 0.83

1.67 0.5 1.67 0.83

0.22 1.0 0.00 0.00


0.22 0.44 0.00

0.22,0.44 0.5 0.66 0.33

1.67 0.5 1.67 0.83

1.33 0.5 1.33 0.67

0.22,0.44 0.5 0.66 0.33

0.22 0.5 0.66 0.33

0.18 0.5 0.36 0.18

0.22 0.5 1.12 0.56

0.18 0.5 0.36 0.18

Total Load per Phase 30.23 30.42 29.02 44.61

Total connected Load (in kVA) 89.67 kVA

Total connected Load current (A) 129.43 A

Breaker current (A) (TCL current +25% of TCL 161.79 A


Current)
Load after Diversity 44.61 kVA
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand

DB Ref :- DB-MZ-AD-P1 Owner :- Al Muhaidib Area :-


FED From :- SMDB-ADMIN D & B Contractor :- Amana Contracting Loc :-
MEZZ.FLOOR ELECTRICAL ROOM

Rating of Sr. MCB CKT Wire ECC Connected Loads / Points


ELCB No. RTG in Size mm2 Wire Size
EX 13A 13A 15A Ceiling
CKT No. Amp mm2 Room / Area
LTG Eqpt. Fan S/O D/O S/O SPUR W/H Fan

1 R1 20 4.0 4.0 OFFICE AREA 4


2 Y1 20 4.0 4.0 OFFICE AREA 4
3 B1 20 4.0 4.0 OFFICE AREA 4
4 R2 20 4.0 4.0 OFFICE AREA 4
5 Y2 20 4.0 4.0 OFFICE AREA 4
6 B2 20 4.0 4.0 OFFICE AREA 4
7 R3 20 4.0 4.0 OFFICE AREA 4
8 Y3 20 4.0 4.0 OFFICE AREA 4
9 B3 20 4.0 4.0 OFFICE AREA 4
10 R4 20 4.0 4.0 ELEC. ROOM,CORRIDOR,STOCK ROOM 5 1
11 Y4 20 4.0 4.0 TRAINING ROOM 3
12 B4 20 4.0 4.0 TRAINING ROOM 4
13 R5 20 4.0 4.0 SPARE
14 Y5 20 4.0 4.0 TRAINING ROOM 4
15 B5 20 4.0 4.0 TRAINING ROOM 2 2
16 R6 20 4.0 4.0 OFFICE AREA 4
17 Y6 20 4.0 4.0 OFFICE AREA 4
18 B6 20 4.0 4.0 OFFICE AREA 4
19 R7 20 4.0 4.0 OFFICE AREA 4
20 Y7 20 4.0 4.0 OFFICE AREA 4
21 B7 20 4.0 4.0 OFFICE AREA 4
22 R8 20 4.0 4.0 OFFICE AREA 4
23 Y8 20 4.0 4.0 OFFICE AREA 4
24 B8 20 4.0 4.0 OFFICE AREA 4
25 R9 20 4.0 4.0 OFFICE AREA 4
26 Y9 20 4.0 4.0 OFFICE AREA 4
27 B9 20 4.0 4.0 OFFICE AREA 4
RCBO 30mA 28 R10 20 4.0 4.0 MALE TOILET

29 Y10 20 4.0 4.0 TRAINING ROOM 1 1

RCBO 30mA 30 B10 20 4.0 4.0 MALE TOILET 1

31 R11 20 4.0 4.0 CCTV ROOM 2

32 Y11 20 4.0 4.0 CCTV ROOM 2

33 B11 20 4.0 4.0 TRAINING ROOM 4

34 R12 20 4.0 4.0 SPARE

35 Y12 20 4.0 4.0 SPARE

36 B12 20 4.0 4.0 SPARE

Cable Size :
4C 25 mm2 XLPE/PVC
+ 16 mm2 ECC

4mm2 R 15
4mm2 Y 15
4mm2 B 15
4mm2 Y/G 45
4mm2 Black 45
Area :- RIYADH, KSA
Loc :- SERVICE BLOCK-1, 2, 4,5 (TYPICAL) - Rating of Incomer 100A TP
LECTRICAL ROOM

oads / Points Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
D/W HD ISO R Y B

0.44 0.5 1.78 0.89


0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.22/0.44 0.5 1.54 0.77
0.44 0.5 1.33 0.67
0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89


0.22/0.44 0.5 1.32 0.66
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.76 0.88
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
1 1.67 0.5 1.67 0.83

0.22/0.44 0.5 0.66 0.33

1.67 0.5 1.67 0.83

0.44 0.5 0.89 0.44

0.44 0.5 0.88 0.44

0.44 0.5 1.78 0.89

Total Load per Phase 16.52 17.10 18.99 26.30

Total connected Load (in kVA) 52.60 kVA

Total connected Load current (A) 75.93 A

Breaker current (A) (TCL current +25% of TCL 94.91 A


Current)
Load after Diversity 26.30 kVA
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand

DB Ref :- DB-MZ-AD-P2 Owner :- Al Muhaidib Area :-


FED From :- SMDB-ADMIN D & B Contractor :- Amana Contracting Loc :-
MEZZ.FLOOR ELECTRICAL ROOM

Sr. MCB CKT Wire ECC Connected Loads / Points


No. RTG in Size mm2 Wire Size
EX 13A 13A 15A Ceiling
Rating of ELCB CKT No. Amp mm2 Room / Area
LTG Eqpt. Fan S/O D/O S/O SPUR W/H Fan

1 R1 20 4.0 4.0 OFFICE AREA 4


2 Y1 20 4.0 4.0 OFFICE AREA 4
3 B1 20 4.0 4.0 OFFICE AREA 4
4 R2 20 4.0 4.0 OFFICE AREA 4
5 Y2 20 4.0 4.0 OFFICE AREA 4
6 B2 20 4.0 4.0 OFFICE AREA 4
7 R3 20 4.0 4.0 OFFICE AREA 4
8 Y3 20 4.0 4.0 OFFICE AREA 4
9 B3 20 4.0 4.0 OFFICE AREA 4
10 R4 20 4.0 4.0 OFFICE AREA 4
11 Y4 20 4.0 4.0 OFFICE AREA 4
12 B4 20 4.0 4.0 OFFICE AREA 4
13 R5 20 4.0 4.0 OFFICE AREA 4
14 Y5 20 4.0 4.0 OFFICE AREA 4
15 B5 20 4.0 4.0 OFFICE AREA 4
16 R6 20 4.0 4.0 OFFICE AREA 4
17 Y6 20 4.0 4.0 OFFICE AREA 4
18 B6 20 4.0 4.0 OFFICE AREA 4
19 R7 20 4.0 4.0 OFFICE AREA 2
20 Y7 20 4.0 4.0 OFFICE AREA 4
21 B7 20 4.0 4.0 OFFICE AREA 4
22 R8 20 4.0 4.0 OFFICE AREA 2
23 Y8 20 4.0 4.0 PANTRY 1 2
24 B8 20 4.0 4.0 TRAINING ROOM 4
RCBO 30mA 25 R9 20 4.0 4.0 FEMALE TOILET
RCBO 30mA 26 Y9 20 4.0 4.0 FEMALE TOILET 1
RCBO 30mA 27 B9 20 4.0 4.0 MALE TOILET
28 R10 20 4.0 4.0 CORRIDOR/ PRAYER ROOM 3

29 Y10 20 4.0 4.0 MALE DINING 2 1

RCBO 30mA 30 B10 20 4.0 4.0 MALE TOILET 1

31 R11 20 4.0 4.0 OFFICE AREA 4

32 Y11 20 4.0 4.0 MALE DINING 2 1

33 B11 20 4.0 4.0 PREPARATION AREA, RECEIVING 3 2

34 R12

35 Y12 20 4.0 4.0 ISOLATOR FOR DUMP WAITER


36 B12

37 R13 20 4.0 4.0 OFFICE AREA 4

38 Y13 20 4.0 4.0 OFFICE AREA 4

39 B13 20 4.0 4.0 TRAINING ROOM 1 1

40 R14 20 SPARE

41 Y14 20 SPARE

42 B14 20 SPARE

Cable Size :
4C 35 mm2 XLPE/PVC
+ 16 mm2 ECC

4mm2 R 15
4mm2 Y 15
4mm2 B 15
4mm2 Y/G 45
4mm2 Black 45
Area :- RIYADH, KSA
Loc :- SERVICE BLOCK-1, 2, 4,5 (TYPICAL) - Rating of Incomer 125A TP
LECTRICAL ROOM

ads / Points Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
D/W HD ISO R Y B

0.44 0.5 1.78 0.89


0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 0.89 0.44
0.44 0.5 1.78 0.89
0.44 0.5 1.78 0.89
0.44 0.5 0.89 0.44
0.44, 0.22 0.5 1.22 0.61
0.44 0.5 1.78 0.89
1 1.67 0.5 1.67 0.83
1.67 0.5 1.67 0.83
1 1.67 0.5 1.67 0.83
0.22 0.5 0.66 0.33

0.22,0.44 0.5 0.88 0.44

1.67 0.5 1.67 0.83

0.44 0.5 1.78 0.89

0.22,0.44 0.5 0.88 0.44

0.22,0.44 0.5 1.56 0.78

0.5 0.93 0.47

1 2.80 0.5 0.93 0.47

0.5 0.93 0.47

0.44 0.5 1.78 0.89

0.44 0.5 1.78 0.89

0.22,0.44 0.5 0.66 0.33

Total Load per Phase 19.26 19.80 20.70 29.88

Total connected Load (in kVA) 59.77 kVA

Total connected Load current (A) 86.27 A

Breaker current (A) (TCL current +25% of TCL 107.84 A


Current)
Load after Diversity 29.88 kVA
Amana Contracting 
Project DB Ref :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-GF-AD-AC Details of Connected Load / Max. Demand Owner
FED From :- SMDB-ADMIN :- Al Muhaidib
:- D & B Contractor :- Amana Contracting

Rating of Incomer 63A TP

Rating of Sr. CKT MCB CKT Wire ECC Connected Loads / Points
ELCB No. No. RTG in Size mm2 Wire Size
Amp EX 13A 13A 15A Ceiling
mm2 Room / Area Fan S/O D/O S/O Fan
LTG Eqpt. SPUR W/H

1 R1 20 4.0 4.0 FOOD PREPARATION-FCU-A-02


2 Y1 20 4.0 4.0 SERVING AREA-FCU-A-01
3 B1 20 4.0 4.0 CORRIDOR-FCU-A-03
4 R2 20 4.0 4.0 MALE DINING HALL -FCU-A-05A
5 Y2 20 4.0 4.0 MALE DINING HALL-FCU-A-05B
6 B2 20 SPARE
7 R3 20 4.0 4.0 ABLUTION-FCU-A-07
8 Y3 20 4.0 4.0 MALE TOILET-FCU-A-06
9 B3 20 4.0 4.0 STORE-FCU-A-04
10 R4 20 4.0 4.0 FEMALE DINING HALL-FCU-A-08
11 Y4 20 4.0 4.0 CORRIDOR-FCU-A-10A

12 B4 20 4.0 4.0 CORRIDOR-FCU-A-10B


13 R5 20 4.0 4.0 CORRIDOR-FCU-A-11
14 Y5 20 4.0 4.0 ABLUTION-FCU-A-09
15 B5 20 4.0 4.0 CORRIDOR-FCU-A-12-A
16 R6 20 4.0 4.0 CORRIDOR-FCU-A-12-B
17 Y6 20 4.0 4.0 CORRIDOR-FCU-A-13
18 B6 20 4.0 4.0 CORRIDOR-FCU-A-12C
19 R7 20 4.0 4.0 CORRIDOR-FCU-A-14
20 Y7 20 SPARE
21 B7 20 4.0 4.0 RECEIVING AREA-FCU-A-19
22 R8 20 SPARE
23 Y8 20 4.0 4.0 MALE LOCKER-FCU-A-15
24 B8 20 4.0 4.0 TRANSFORMER ROOM-EAF-A1-01
25 R9 20 SPARE
26 Y9 20 4.0 4.0 MALE LOCKER-FCU-A-17
27 B9 20 4.0 4.0 CORRIDOR-FCU-A-12D
28 R10 20 SPARE
29 Y10 20 4.0 4.0 MALE LOCKER-FCU-A-16
30 B10 20 SPARE

Cable Size : 4C 16 mm2 XLPE/PVC


+ 16 mm2 ECC

4mm2 R 13
4mm2 Y 13
4mm2 B 13
4mm2 Y/G 39
4mm2 Black 39
Area Loc
:- RIYADH, KSA
:- ADMIN BUILDING-GF ELECTRICAL ROOM

ads / Points Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
D/W HD ISO R Y B

1 0.78 0.9 0.78 0.70


1 1.47 0.9 1.47 1.32
1 0.72 0.9 0.72 0.65
1 2.22 0.9 2.22 2.00
1 2.22 0.9 2.22 2.00

1 0.89 0.9 0.89 0.80


1 1.11 0.9 1.11 1.00
1 0.72 0.9 0.72 0.65
1 1.78 0.9 1.78 1.60
1 1.72 0.9 1.72 1.55

1 1.72 0.9 1.72 1.55


1 0.78 0.9 0.78 0.70
1 0.78 0.9 0.78 0.70
1 1.56 0.9 1.56 1.40
1 1.56 0.9 1.56 1.40
1 0.78 0.9 0.78 0.70
1 1.56 0.9 1.56 1.40
1 0.78 0.9 0.78 0.70

1 1.28 0.9 1.28 1.15

1 1.56 0.9 1.56 1.40


1 0.20 0.9 0.20 0.18

1 1.11 0.9 1.11 1.00


1 1.56 0.9 1.56 1.40

1 0.89 0.9 0.89 0.80

Total Load per Phase 8.79 11.64 9.32


26.78
Total connected Load (in kVA) 29.75 kVA
Total connected Load current (A) 42.94 A

Breaker current (A) (TCL current +25% of TCL 53.68 A


Current)
Load after Diversity 26.78 kVA
Amana Contracting 
Project DB Ref :- ALPHA NOON LOGISTICS HUB - PHASE 1 DB-MZ-AD-AC Details of Connected Load / Max. Demand
FED From :- SMDB-ADMIN Owner :- Al Muhaidib
:- D & B Contractor :- Amana Contracting

Rating of Incomer 160A TP

Rating of Sr. MCB RTG CKT Wire ECC Connected Loads / Points
ELCB No. in Amp Size mm2 Wire Size
mm2 EX 13A 13A 15A Ceiling
CKT No. Room / Area Fan S/O D/O S/O Fan
LTG Eqpt. SPUR W/H

1 R1 20 4.0 4.0 SMALL ITEMS STOCK RM-FCU-A-21 85


2 Y1 32 6.0 6.0 CORRIDOR-FCU-A-22 90
3 B1 40 10.0 10.0 CORRIDOR-FCU-A-23A 100
4 R2 20 4.0 4.0 CORRIDOR-FCU-A-24 75
5 Y2 32 6.0 6.0 CORRIDOR-FCU-A-20 90
6 B2 40 10.0 10.0 CORRIDOR-FCU-A-23B 90
7 R3 20 4.0 4.0 CORRIDOR-FCU-A-25 85
8 Y3 20 4.0 4.0 STAIR CASE-FCU-A-29 75
9 B3 20 4.0 4.0 CORRIDOR-FCU-A-26 90
10 R4 40 10.0 10.0 CORRIDOR-FCU-A-23C 75
11 Y4 20 SPARE

12 B4 20 4.0 4.0 CORRIDOR-FCU-A-27 85


13 R5 40 10.0 10.0 CORRIDOR-FCU-A-28A 85
14 Y5 40 10.0 10.0 CORRIDOR-FCU-A-28B 85
15 B5 40 10.0 10.0 CORRIDOR-FCU-A-30A 75
16 R6 20 4.0 4.0 CORRIDOR-FCU-A-31 90
17 Y6 20 4.0 4.0 ABLUTION-FCU-A-34 78
18 B6 40 10.0 10.0 OFFICE AREA CORRIDOR-FCU-A-30B 90
19 R7 20 SPARE

20 Y7 32 6.0 6.0 MALE DINING-FCU-A-33B 90


21 B7 20 4.0 4.0 PREPARATION ARE-FCU-A-37 70
22 R8 20 4.0 4.0 OFFICE AREA OFFICE AREA-FCU-A-32 90
23 Y8 32 6.0 6.0 MALE DINING-FCU-A-33A 100
24 B8 20 4.0 4.0 PREPARATION ARE-FCU-A-36 100
25 R9 40 10.0 10.0 OFFICE AREA-FCU-A-30D 100
26 Y9 20 4.0 4.0 MALE DINING-FCU-A-35 90
27 B9 40 10.0 10.0 OFFICE AREA-FCU-A-30C 100
28 R10 32 6.0 6.0 IT ROOM DX- UNIT 100
29 Y10 32 SPARE

30 B10 20 SPARE

31 R11 20 SPARE

32 Y11 20 SPARE

33 B11 40 10.0 10.0 OFFICE AREA-FCU-A-23D 100

Cable Size : 4C 70 mm2 XLPE/PVC


+ 35 mm2 ECC

10mm2 R 200 200


10mm2 Y 0
10mm2 B 600 600
10mm2 Y/G 800 800
10mm2 Black 800 800
6mm2 R 350 2.3 3
6mm2 Y 350 2.3 3
6mm2 B 350 2.3 3
6mm2 Y/G 1050 6.9 7
6mm2 Black 1050 6.9 7
4mm2 R 367 2.4 3
4mm2 Y 367 2.4 3
4mm2 B 367 2.4 3
4mm2 Y/G 1101 7.2 9
4mm2 Black 1101 7.2 9
Area Loc
:- RIYADH, KSA
:- ADMIN BUILDING-MZ ELECTRICAL ROOM

nts Demand Load per circuit Diversity


factor kVA Load
FCU/V
AV Unit KVA Remarks
D/W HD ISO R Y B

1 0.78 0.9 0.78 0.70

1 2.67 0.9 2.67 2.40

1 4.67 0.9 4.67 4.20

1 0.80 0.9 0.80 0.72

1 2.89 0.9 2.89 2.60

1 4.67 0.9 4.67 4.20

1 0.80 0.9 0.80 0.72

1 0.80 0.9 0.80 0.72

1 1.02 0.9 1.02 0.92

1 4.67 0.9 4.67 4.20

1 0.78 0.9 0.78 0.70

1 6.67 0.9 6.67 6.00

1 6.67 0.9 6.67 6.00

1 6.11 0.9 6.11 5.50

1 0.80 0.9 0.80 0.72

1 1.44 0.9 1.44 1.30

1 6.67 0.9 6.67 6.00

1 2.67 0.9 2.67 2.40

1 1.28 0.9 1.28 1.15

1 0.81 0.9 0.81 0.73

1 2.67 0.9 2.67 2.40

1 0.78 0.9 0.78 0.70

1 6.11 0.9 6.11 5.50

1 1.44 0.9 1.44 1.30

1 6.11 0.9 6.11 5.50

1 5.00 0.9 5.00 4.50 UVR+TIMER+CONT

1 4.67 0.9 4.67 4.20

Total Load per Phase 26.44 21.25 36.76


67.30
Total connected Load (in kVA) 84.45 kVA
Total connected Load current (A) 121.90 A

Breaker current (A) (TCL current +25% of TCL 152.37 A


Current)
Load after Diversity 67.30 kVA
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand
DB Ref FED From :- DB-EXT-3 SMDB-ADMIN 40A TP Owner :- Al Muhaidib
D & B Contractor :- Amana Contracting
Rating of Incomer :-

Rating of Sr. MCB CKT Wire Size ECC Wire Size Connected Loads / Points
ELCB No. RTG in mm2 mm2
Amp EX 13A 13A 15A
CKT No. Room / Area Fan S/O D/O S/O
LTG Eqpt. SPUR W/H

1 R1 External Lighting
16 4.0 4.0 6 185
2 Y1 3C-6mm2 XLPE/SWA/PVC External Lighting
16 6 260
3 B1 External Lighting
16 4.0 4.0 4 195
4 R2 External Lighting
16 4.0 4.0 4 175
Section-1, 4P
40A 5 Y2 3C-6mm2 XLPE/SWA/PVC External Lighting
100mA 16 6 310
6 B2 3C-6mm2 XLPE/SWA/PVC External Lighting
16 3 295
7 R3 3C-6mm2 XLPE/SWA/PVC External Lighting
16 4 275
8 Y3 3C-6mm2 XLPE/SWA/PVC External Lighting
16 6 265
9 B3 16 3C-6mm2 XLPE/SWA/PVC External Lighting 6 190
10 R4 16 3C-6mm2 XLPE/SWA/PVC External Lighting 6 210
11 Y4 16 4.0 4.0 External Lighting 5 245
12 B4 16 4.0 4.0 External Lighting 4 260
Section-2, 4P
13 R5 16 3C-6mm2 XLPE/SWA/PVC CAR PARK SHED LIGHT 9 190
40A
100mA
14 Y5 16 3C-6mm2 XLPE/SWA/PVC CAR PARK SHED LIGHT 6 175
15 B5 16 3C-6mm2 XLPE/SWA/PVC CAR PARK SHED LIGHT 11 165
16 R6 16 spare
17 Y6 16 spare
18 B6 16 spare

Cable Size : 4C 10 mm2 XLPE/PVC


+ 10 mm2 ECC

3C-6mm2 XLPE/SWA/PVC 2335


4mm2 R 400 2.6 3
4mm2 Y 400 2.6 3
4mm2 B 400 2.6 3
4mm2 Y/G 1200 7.9 9
4mm2 Black 1200 7.9 9
cting 

Area Loc :- RIYADH, KSA


:- SERVICE BLOCK-1, ELECT ROOM

ected Loads / Points Demand Load per circuit Diversity


factor kVA Load
Ceiling 16A FCU/V
Fan IND. AV Unit KVA Remarks
D/W ISO R Y B
S/O

1.0 1.20 1.20


0.20

1.0 1.20 1.20


0.20

1.0 0.98 0.98


0.24

1.0 0.80 0.80


0.20

1.0 1.20 1.20


0.20

1.0 0.72 0.72


0.24

0.20 1.0 0.80 0.80

0.20 1.0 1.20 1.20

0.20 1.0 1.20 1.20


0.20 1.0 0.60 0.60
0.20 1.0 0.60 0.60
0.20 1.0 0.78 0.78

0.06 1.0 0.50 0.50

0.06 1.0 0.33 0.33

0.06 1.0 0.61 0.61


P.CELL +TIMER +CONTACTOR

Total Load per Phase 3.90 4.53 4.28


12.71
Total connected Load (in kVA) 12.71 kVA
Total connected Load current (A) 18.34 A
Breaker current (A) (TCL current +25% of TCL 22.93 A
Current)
Load after Diversity 12.71 kVA
Amana Contracting 
Project :- ALPHA NOON LOGISTICS HUB - PHASE 1 Details of Connected Load / Max. Demand
DB Ref FED From :- DB-GR-2 SMDB-AD 40A TP Owner :- Al Muhaidib
D & B Contractor :- Amana Contracting
Rating of Incomer :-

Rating of Sr. MCB CKT Wire Size ECC Wire Size mm2 Connected Loads / Points
ELCB No. RTG in mm2
EX 13A 13A
CKT No. Amp Room / Area Fan S/O D/O
LTG Eqpt.

1 R1 Guard Rm & Pantry


10 2.5 2.5 5 95 1

2 Y1 Guard Rm toilet
RCBO 30mA 10 2.5 2.5 2 95 1

3 B1 Spare
10 3

4 R2 ODU
32 6.0 6.0 50
5 Y2 SPARE
20

6 B2 ODU
32 6.0 6.0 50
7 R3 Guard Rm
32 4.0 4.0 90 1 2

8 Y3 PANTRY
32 4.0 4.0 90 1 2

9 B3 20 4.0 4.0 Guard Rm 90 1 1

10 R4 20 4.0 4.0 IT RACK 90 1

11 Y4 20 4.0 4.0 PANTRY 90


12 B4 20 4.0 4.0 CCTV RACK 90 1

13 R5 20 4.0 4.0 FARP 90


14 Y5 20 SPARE
15 B5 20 SPARE
RCBO 30mA 16 R6 20 3C-4mm2 XLPE/SWA/PVC SLIDING GATE 75
RCBO 30mA 17 Y6 20 3C-4mm2 XLPE/SWA/PVC SLIDING GATE 75
18 B6 20 SPARE

Cable Size : 4C 16 mm2 XLPE/SWA/PVC


+ 16 mm2 ECC

3C-4mm2 XLPE/SWA/PVC 150


4mm2 R 210 1.4 2
4mm2 Y 210 1.4 2
4mm2 B 210 1.4 2
4mm2 Y/G 630 4.1 6
4mm2 Black 630 4.1 6
Amana Contracting 
Details of Connected Load / Max. Demand
Owner :- Al Muhaidib
D & B Contractor :- Amana Contracting Area Loc :- RIYADH, KSA
:- GUARD ROOM -1

Connected Loads / Points Demand Load per circuit Diversity


factor kVA Load
15A Ceiling 16A FCU/V
S/O Fan IND. AV Unit KVA Remarks
SPUR W/H D/W ISO R Y B
S/O

1.0 0.22 0.22


0.06

1.0 0.17 0.17


0.055

0.9 3.33 3.00


1 3.33 UVR+TIMER+CONT

0.9 3.33 3.00


1 3.330 UVR+TIMER+CONT

0.22/0.44 0.5 1.11 0.56

0.22/0.44 0.5 1.11 0.56

0.22/0.44 0.5 0.66 0.33

0.44 1.0 0.44 0.44

1 1.33 0.5 1.33 0.67

0.44 1.0 0.44 0.44

1 0.44 1.0 0.44 0.44

1 0.60 0.5 0.60 0.30

1 0.60 0.5 0.60 0.30

Total Load per Phase 6.14 3.21 4.43


10.40
Total connected Load (in kVA) 13.78 kVA
Total connected Load current (A) 19.88 A
Breaker current (A) (TCL current +25% of TCL 24.85 A
Current)
Load after Diversity 10.40 kVA
Summary 20.7.2022 -USS 3,4,13,5
R Y B Y/G Black
2.5mm2 27 27 27 81 81
4.0 mm2 145 145 145 435 435
6mm2 40 40 40 120 120
4mm2 ( special length wires ) RYB 720
4mm2 ( Special length wires ) Y/G 720
4mm2 ( Special length wires ) Black 720
3c-10mm2+10mm2g 0
4c-10mm2 +10mm2g-SWA
3x6mm2 /SWA 3750
4c-70mm2 +35mm2G PVC
4c-70mm2 +35mm2GFR
4c-4mm2 FR+4mm2G
3c-4mm2 SAWA 150
4c-25mm2 +16mm2G 0
10mm2 R 200
10mm2 Y 0
10mm2 B 600
10mm2 Y/G 800
10mm2 Black 800
4c-150mm2+70mm2G 0
4c240mm2+120mm2G 0
4c-185mm2+95mm2g 0
4c-150mm2+70mm2G 0
4c-240mm2 0
3c-4mm2 XLPE/SWA/PVC 0
3C-10mm2 525
XLPE/PVC
3C-4mm2 0
XLPE/PVC
4C-4mm2 XLPE/FR +1C- 630
4mm ECC
3C-6mm2 XLPE/SWA/PVC

You might also like