FBs-2ATC4

2 Channel A/D Input Module /4 Channel Thermo


-Couple Temperature Input Module

Analog Input Thermo-Couple


Specification Specification
Channels-2CH Channels-4CH
Resolution-14 or 12 bits Resolution-0.1℃ or 1℃
Signal Resolution- I/O Points Occupied-
0.3mV(Voltage), 0.61uA(Current) 2 IR(Input Register)
I/O Points Occupied- 8 DO(Discrete Output)
2 IR(Input Register) Conversion Time-2 or 4 Sec.
Conversion Time-Updated each Accuracy-±(1%+1℃)
scan Sensor Type-J,K,R,S,E,T,B
Accuracy-±1 % ,N
Max. Absolute Input Rating- Software Filter-Moving average
Introduction ±15V,30mA Average Samples-1~16
FBs-2ATC4 is one of the Analog and Temperature Software Filter-Moving average configurable
mixed input modules of FATEK FBs series PLC. For Average Samples-1~16 Compensation-Built in cold
analog input it provides 2 channels A/D input with 12 configurable junction compensation
or 14 bit effective resolution. Base on the different Input Impedance- Measurement Range-
jumper settings it can measure the varieties of current 63.2kΩ(Voltage)、 J:-200~900℃; K:-190~1300℃
or voltage signal. The reading value is represented by 250Ω(Current) R:0~1800℃; S:0~1700℃
a 14 bit value no matter the effective resolution is set Measurement Range--10~+10V, E:-190~1000℃; T:-190~380℃
to 12 or 14 bit The output code also can be configured -5~+5V B:350~1800℃; N:-200~1000℃
as unipolar or bipolar which makes the relation of ,0~10V, 0~5V, -20~+20mA,
input code and real input signal more intuitive.. In -10~+10mA, 0~20mA, 0~10mA
order to filter out the field noise imposed on the signal,
it also provides the average of sample input function.
For temperature measure it provides 4 channels of
Comm. Specification
thermo-couple temperature measurement input with Isolation-Transformer(Power) and photo-coupler(Signal)
0.1 ℃ or 1 ℃ resolution. The scan rate for 0.1 ℃
Indicator(s)-5V PWR LED
resolution is 4 seconds, while the scan rate for 1 ℃
Supply Power-24V-15%/+20%,2VA
resolution is 2 seconds. The cold junction
Internal Power Consumption--5V, 100mA
compensation is carried out inside the module, also it
Operating Temperature-0 ~ 60 ℃
provides wire broken detection feature. To give the
Storage Temperature--20~ 80 ℃
user more choices for the selection of thermo-couple
Dimensions-40(W) X 90(H) X 80(D)mm
type and in order to enhance the noise immunity, the
isolation scheme is per channel basis. All the optional
features of this module are software configurable,
there are no hardware jumpers or switches for user to
setup.

Dimensions

1/4
FBs-2ATC4
2 Channel A/D Input Module /4 Channel Thermo
-Couple Temperature Input Module

Wiring Diagram

Inputs
FBs-2ATC4

+15V 24V+ + 24VDC


External power supply
15V 24V

+ V I0+
CH0 Input
V
I0 (Voltage source)
I

+ V I1+
CH1 Input
I
I1 (Current source)
I

AG

J(K) extension cable


+
+ TC0+
J(K) type
TC0 thermocouple

+
+ TC1+
J(K) type
TC1 thermocouple
Thermocouple
Input

+
+ TC3+
J(K) type
TC3 thermocouple

Multiplexer
J(K) extension cable
(Shielding must be connected to FG)

If it's FBs-TC6, n is 5
If it's FBs-TC16, n is 15

2/4
FBs-2ATC4
2 Channel A/D Input Module /4 Channel Thermo
-Couple Temperature Input Module

A/D Jumper Setup


Input Code Format Selection
There are two input data formats can be selected which are bipolar and unipolar. The range of input value is 0~16383 for
unipolar format while bipolar is -8192~8191. The two extreme values of each range corresponding to the minimal and maximal
input signal. For example, if chose the -10V~+10V type signal, for 10V input signal the input value is 16383 for unipolar format
while the bipolar format is 8191. Normally the input code format setting is consistent with input signal type (bipolar coded for
bipolar input signal, unipolar coded for unipolar input signal). Only when use the FUN32 for offset conversion should set the
bipolar code for unipolar input signal (Please refer the FUN32 description). The code format of all input channels are set by the
same JP1 jumper. The location and the setting of jumper of JP1 are shown at below

Corresponding Input JP1 Setup Code Format

U
-10V~10V(-20mA~ 20mA) JP1 -8192~8191
B

-5V~5V(-20mA~20mA)
0~16383

0V~10V(0mA~20mA) U
JP1 -8192~8191
B

0V~5V(0mA~10mA)
0~16383

JP3
JP4

JP5
JP6

JP1

3/4
FBs-2ATC4
2 Channel A/D Input Module /4 Channel Thermo
-Couple Temperature Input Module

Voltage/Current input signal type setting

Signal Type JP3 ~ JP4

Voltage

Current

A/D Signal Type selection

Signal Type Polarity Setting (JP5) Range Setting (JP6)


0~10V
or
0~20mA

0~5V
or
0~10mA

-10~+10V
or
-20~+20mA

-5~+5V
or
-10mA~+10mA

The default factory settings of 2ATC4 analogue input/output module are


Input code format – Bipolar(-8192~+8191)
Input signal type and range – Bipolar(-10V ~ +10V)
Output code format – Bipolar(-8192~+8191)
Output signal type and range – Bipolar(-10V ~ +10V)
For those applications that require the setting differ than the above default setting should make some modifications of jumper
position according to above tables.
While application, besides the setting of jumper should be conducted, the AI module configuration of Winproladder also need to
be performed.