Nothing Special   »   [go: up one dir, main page]

PMAC735 Profibus Power Meter Data Sheet V5.0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

PMAC735

Multifunction Power Meter

Feature
 Suit for LV/ HV voltage system
 Compact design with all real-time measurement
 Consist of basic unit and optional modules
 10 years back-up of integrated energy data
 Large LCD, high brightness
 High accuracy, V or I is 0.2%, kWh is class 1
 CT and PT programmable
 Pluggable terminals, easy to install
 Support Modbus / Profibus communication (Optional)
 Panel size: 96 x 96mm
 Password protect
 Standard: IEC62053-21/23, CE

Basic Function Optional Module


PMAC735 provide one RS485 communication,  4 status input + 4 relay output
measures and display real-time parameters:  8 status input + 2 relay output
 Voltage—Ua, Ub, Uc, Uab, Ubc, Uca,  8 status input + 2 pulse output
 Voltage unbalance rate – UL-L unbal, UL-N unbal  Profibus communication module
 Current—Ia, Ib, Ic, In Status input apply to monitoring various kinds of switch status
 Current unbalance rate –I unbal Relay output apply to monitoring over limit alarm with setpoint system
 Active power – Pa, Pb, Pc, ∑P Pulse output apply to exporting pulse signal for active/ reactive energy
 Reactive power –Qa, Qb, Qc, ∑Q Profibus supports high speed bus communication up to 1.5M, and
 Apparent power—Sa, Sb,Sc, ∑S Compatible with SIEMENS Profibus communication system.
 Power factor—PFa, PFb, PFc, ∑PF
 Frequency--F


Active energy—kWh (4 quadrant)
Reactive energy– kvarh (4 quadrant)
Optional Function
 Up to 31st harmonic analysis, K factor, THD
 Demand and Max. record for I, P, Q, S
 SOE (event log)
 Max./ Min. value
 One 4~20mA analog output

Technical Specification
Metering True RMS, 1 sec refresh time Power frequency withstand voltage AC 2KV/minute

Input Rate current: 1A or 5A Insulation resistance ≥50MΩ


Rate voltage: direct 120 ~277Vph-N, (optional)
Impulse withstand voltage 4kV (peak),
PT secondary 57.7/ 100V
1.2/50uS
Frequency: 50/ 60Hz

Overload 120% of rated, continuously Power supply 85~265VAC, 80~300VDC


Instantaneous current: 10 times/ sec Or 24-48VDC (optional)
Instantaneous voltage: 2 times/ sec
Power loss <2VA
Status input ≤8 channels,
(optional) Communication RS485 serial, support Modbus-RTU
provides 30VDC power if it is dry contact
Baudrate: 4800, 9600, 19200, 38400bps
Relay output ≤4 channels, Address: 1~247
(optional) Node capacity: 220VAC/5A, 30VDC/5A
Dimension Panel: 96 x 96 x 18 mm
Analog 1 channel,
output (L x W x H) Cut-out: 89.5 x 89.5 x 65 mm (+0.5mm)
4~20mA, load resistance: 400Ω
(optional)
IP index IP54 (front panel) and IP20 (case)
Pulse output 2 channels, Pulse width: 80ms
(optional) Pulse constant: 1000~40000 programmable Weight Approx. 500gr.
1 pulse = (1÷ pulse constant ×PT ×CT) kWh

http://en.pmac.com.cn
PMAC735 Multifunction Power Meter

Standard (EMC) Environment

Electrostatic discharge immunity test IEC 61000-4-2,Level 4 Operating temperature: -20℃~ +60 ℃
Radiated immunity test IEC 61000-4-3,Level 3 Storage temperature: -30℃~ +70 ℃
Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4
Humidity: 5%~95% non-condensing
Surge immunity test (1, 2/50μs~8/20μs) IEC 61000-4-5,Level 3
Conducted emissions EN 55022,Class B
Radiated emissions EN 55022,Class B

Parameter Accuracy Resolution Measuring Range

Directly: 300Vph-N, 520Vph-ph

Voltage 0.2% 0.01V PT primary: 0~499,999V


PT secondary: 57.7Vph-N, 100Vph-ph
(Note: when PT ratio is non-integer, voltage range is 0~ 49,999V)

CT primary: 0~49,999A
Current 0.2% 0.001A
CT secondary: 1 A or 5A

Power 0.5% 0.1W/ var each phase: 0~100 MW/ Mvar

Power factor 0.5% 0.001 -1.000~+1.000

Frequency 0.01 0.01Hz 35~ 65 Hz

Active energy 1.0% 0.1kWh 0~ 99,999,999.9 kWh

Reactive energy 2.0% 0.1kvarh 0~ 99,999,999.9 kVarh

THD 1.0% 0.001 0~100.0%

Individual harmonic 1.0% 0.001 0~100.0%

Un-balance 1.0% 0.001 0~100.0%

Model PMAC 735N 735A 735B 735E 735P


Feature

U-LL, U-LN, 3I, In, 3P, ∑P, 3Q, ∑Q, 3S, ∑ S, F, ● ● ● ● ●


3PF, ∑PF, kWh, kvarh,
Demand& maximum recording,
Unbalance rate,
Build-in clock,
Max./min. recording,
RS485 communication

4 status input + 4 relay output ●

8 status input + 2 relay output ●

8 status input + 2 pulse output ●

Profibus communication ●

Harmonic analysis, K factor ○ ○ ○ ○ ○

SOE ○ ○ ○

One 4-20mA analog output ○ ○ ○ ○ ○

Remark: ●= standard, ○=optional

http://en.pmac.com.cn
PMAC735 Multifunction Power Meter

Dimension & Installation


unit: mm

PMAC735

Auxiliary
Module

Order Information
PMAC735--①--② --③--④-- ⑤
N Basic Module
A Basic Module + 4 Status Inputs (Dry Contact) + 4 Relay Outputs
B Basic Module + 8 Status Inputs (Dry Contact) + 2 Relay Outputs
E Basic Module + 8 Status Inputs (Dry Contact) + 2 Pulse Outputs
P Basic Module + Profibus Module

H Up to 31st Harmonic Analysis, THD, K Factor


T SOE (Event Log) Function
AO One 4-20mA Analog Output

A AC85-265V~50Hz/60Hz DC80-300V
D DC24 - 48V

V1 57.7/ 100V (via PT), 5A


V2 57.7/ 100V (via PT), 1A
V3 220/ 380V (direct), 5A
V4 220/ 380V (direct), 1A
V5 120/ 208V (direct), 5A
V6 240/ 415V (direct), 5A
V7 277/ 480V (direct), 5A
V8 63.5/ 110V (via PT), 5A

50Hz 50Hz
60Hz 60Hz

Example: Model No. PMAC735-A-H-A-V1-50Hz, which indicates the device provides basic function + 4 status input + 4 relay

output + harmonic analysis, AC85-265V~50Hz/60Hz ,DC80-300V power supply, rated input 57.7/ 100V, 5A, 50Hz

Note:

1. Function H, T, AO can be selected together.

Your representative
ZHUHAI PILOT TECHNOLOGY CO., LTD.
PILOT (HENGQIN) CO., LTD.
Add: No. 15, Keji 6 Road, Chuangxin Haian, Tangjia Hi-tech Zone,
Zhuhai, Guangdong, China
Post Code: 519085
Tel: +86 756 3639029/ 3626166
Fax: +86 756 3629600/ 3629700
Email: overseamarket@pmac.com.cn
http://www.pmac.com.cn

http://en.pmac.com.cn

You might also like