DAT-SS 400 Field Mounted Indicator Manual
DAT-SS 400 Field Mounted Indicator Manual
DAT-SS 400 Field Mounted Indicator Manual
Environmental
Display
Performance
Enclosure
2
Installation
Install the instrument in a location where it will Heavy electrical equipment should not be
not be subjected to excessive heat, humidity or installed close to the weighing equipment.
vibration. For best results, avoid direct sunlight
on the front of the instrument. The unit should Excessive vibration will affect the accuracy of
be installed at eye level so as to allow viewing the weigh system and depending on the severity
the display and access to the front panel keys. can cause damage to electrical and electronic
components.
Cable Types and sizes
The atmosphere should be dust free and not
Use a 6 x 0.5 mm2 shielded cable for the load contain any corrosive gasses or materials which
cell/s connection. Use a 3 x 0.34 mm2 shielded could adversely affect the equipment.
cable for the RS-232 connection, and a 2 x 0.34
mm2 shielded cable for the RS-485 connection. Hazardous areas
3
Introduction Front panel key functions - Setup Mode
This manual provides general information on In setup mode three of the front panel keys are
the installation, configuration, calibration, and used as directional keys to scroll through the
operation of the Precise™ 500 Series Digital / various menus. A label on the lower half of each
Analog Transmitter. The unit features a key identifies the direction provided by the key.
four-button keyboard, 6-digit Red LED display,
The “SET” and “FUN” keys are used to navigate
and four status LED’s. The unit can be
through the main menu and sub-menus. They
configured and calibrated with the front panel
are also used to increment or decrement the
keys, or remotely via the serial port. The
numerical value of a selected digit.
transmitter is packaged in a 1/8 DIN size
ABS plastic panel mounted enclosure. The “O” key is used to move through certain
sub-menu parameters, or to select a specific
All units include the following features:
digit when numerical values are displayed. It is
Drives up to six 350 ohm load cells also used to return to the main menu from any
Supports 4 and 6 wire connections of the sub-menus.
RS-232, RS-422, or RS-485 outputs The “PRG” key switches the unit to the “Basic
(2) Logic inputs Configuration” mode. It is also used to enter the
(2) Logic outputs (setpoints) sub-menus, and store parameter changes.
Isolated analog output 4/20mA, 0-5 Vdc
or 0-10Vdc output utilizing a 16 bit DAC The “PRG” key when used in conjunction with
the “SET” key switches the unit to the “Complete
The Precise™ 500 Series Digital / Analog Configuration” mode. It is also used to enter the
Transmitter has three modes of operation: sub-menus, and store parameter changes.
Operating mode Status LED’s
In this mode the unit displays gross weight, net
There are four status LED’s on the front of the
weight, or peak force readings as required.
unit, one for Motion, one for Net mode, and one
Setup mode for each of the outputs.
This mode is used for configuration and
calibration of the unit. Enabling/Disabling front panel keys.
Test mode In order to prevent any access to the instrument
The test mode enables you to test the inputs, by non-authorized personnel, a procedure to
outputs, and analog output. lock the keyboard is also available.
Front panel key functions - Operating Mode How to LOCK the front panel keys:
Press and hold the “PRG” and “O” keys.
The “SET” key enables you to enter values for The “O” key must be pressed after the “PRG”
Setpoints 1 and 2. Press the “SET” key, Set 1 key.
appears on the display. Press the “PRG” key to Release both keys when the message LOCK
view the current value. To change the current appears on the display.
value, press the “O” key to select a digit, then Press the “PRG” key to confirm.
use the “UP” or “DOWN” keys to increment or Now the keys are disabled.
decrement the value.
Repeat this procedure for the remaining digits, How to UNLOCK the front panel keys:
then press the “PRG” key to enter the new Press and hold the “PRG” and “O” keys.
value. To change the value for Setpoint 2, press The “O” key must be pressed after the “PRG”
the “SET” key again and repeat the above key.
procedure or press the “O” key to exit. Release both keys when the message UNLOCK
The “FUN” key is used to switch the unit from appears on the display.
Gross mode to Net mode, or Peak Hold mode. Press the “PRG” key to confirm.
To switch to Peak Hold mode, press and hold Now the keys are enabled.
the “FUN” key until a ‘P’ appears on the display.
The “O” key is used to zero the unit in Gross Note:
mode, tare the unit in Net mode, and reset the When the keyboard is locked the message
peak value in Peak Hold mode. LOCK appears for a while during the power-on
The “PRG” key is used to send the data to the sequence.
RS-232 serial port for use with a computer.
4
Main Power Connections Logic Input Connections (cont’d)
Use terminal 1 for the (+) input, and terminal 2 for Input (2) functions as a “send data” command,
the (-) input. The supply voltage must be closing the input causes the weight data to be sent
24 Vdc + 15%. The external power supply must to the RS-232 serial port.
have a minimum rating of 10 watts.
Logic Output Connections
Transducer/s Connections Use terminal 13 for Output (1) and terminal 14 for
Attach cable from transducer/s to transmitter Output (2). Terminal 15 is the common for both
(terminals 19 through 24). If using a 4-conductor outputs. The outputs utilize solid-state relays with
cable, (no remote sensing) jumpers must be a maximum load rating of 24 Vdc @ 100mA
installed between the + Excitation and + Sense
leads (terminals 20 to 21) and between Analog Output Connections
the - Excitation and - Sense leads (terminals 19 to Use terminal 3 for the 4/20mA output (300 Ohm load
22) as shown below in Figure 1. max), or terminal 4 for a 0 to 5 Vdc or 0 to 10 Vdc
output (10K Ohm load max). Terminal 5 is used as
Logic Input Connections the common for either output.
Use terminal 16 for Input (1), and terminal 17 for
Input (2). Terminal 18 is the common for both Serial Output Connections
inputs. These are powered inputs, which require The transmitters serial port supports RS-232,
an input voltage of 24 Vdc to activate them. See RS-422 or RS-485 communications.
Figure 1 for additional information. Serial parameter selections can be found on page
Input (1) is used to zero the unit in Gross mode, tare 18. A detailed description of the serial data formats
the unit in Net mode, and reset the peak value when is provided on pages 20 through 23.
operating in Peak Hold mode. Wiring connections are shown on pages 24 through
25.
Figure 1
Common
Output 2
Output 1
Set Points
POWER SUPPLY
24 Vdc
13 14 15 16 17 18 19 20 21 22 23 24
1
2
Ext. power supply
for Logic Inputs
Current Out
3
(24 Vdc)
Analog
Output
Input 2 Common
5
Common Txd
6
(20m max.)
RS232
- Exc Rxd
7
+ Exc Gnd
8
+ Sense + Tx
9 10 11 12
(1000m max.)
32 unit max.
RS422/485
- Sense - Tx
- Sig + Rx
+ Sig - Rx
LOAD
CELL
5
When no programming procedures are in progress, the display shows the weight value.
In some particular conditions the following ERROR MESSAGES are displayed:
The weight displayed by the instrument is more than 9 divisions over the
“Live” weight value (see “NET” parameter, page 12)
The load cells input signal is lower than - 0,5 (-3,9) mV/V.
O-L The load cells input signal is higher than +3,5 (+3,9) mV/V.
The load cell input signal is missing
The values in brackets refer to the instruments having load cells input signal range from - 3,9 to + 3,9 mV/V (optional)
6
Basic Configuration Menu
Enter total
( O CAPAC ( PRG ) scale ( PRG )
capacity
Enter
( O SENSIT ( PRG ) transducer/s ( PRG )
sensitivity
Enter
( O NET ( PRG ) “LIVE” ( PRG )
weight value
Enter
( O DEAD L ( PRG ) “Dead Load” ( PRG )
weight value
Select display
( O DSPDIV ( PRG ) divisions ( PRG )
0.001 - 50
View input
( O SIGNAL ( PRG ) signal value ( O
mV/V
See calib.
( ( PRG ) procedure on (
O CALIBR
next page
*
Enter FS
( O ANALOG ( PRG ) value for ( PRG )
analog out
Place the unit in “Basic Configuration” mode by then use the “UP” or “DOWN” keys to increment
pressing and holding the “PRG” key until the or decrement the value of the selected digit.
display shows CAPAC. Use either the “UP” or Press the “PRG” key to enter the new value,
“DOWN” keys to scroll through the eight basic then press either the “UP” or “DOWN” keys to
configuration menus shown above. To set one move to the next parameter. To exit the setup
of the following parameters, CAPAC, SENSIT, procedure, press the “O” key when any one of
NET, DEAD L, DSPDIV, or ANALOG, press the the sub-menu parameters are displayed. The
“PRG” key to view the default or previously display will indicate STORE ?, press the “PRG”
selected value for that parameter. To change key to save the changes and return to the
the value, press the “O” key to select a digit, operating mode.
7
Basic Configuration Menu (cont’d)
NOTE: In order to ensure greater stability during the calibration procedure, the digital filter increases
to the maximum value automatically (value 9), therefore the weight indication updates very slowly at
this stage. Once the calibration procedure has been completed, the digital filter will return to the pre-
vious value automatically.
Cont’d from
(
* the previous
page
Sets ZERO
( PRG ) CAL ( O
calibration
Enter the
WT-VALUE actual weight ( PRG )
value (SPAN)
CAL
NOTE:
Input signal from the transducer/s
( PRG ) must be stable when entering the
Back to zero and span values.
“CALIBR”
(Main menu)
The Precise 500 Series Transmitters can be 4. Enter the actual weight value using the “O” key
calibrated via the front panel keys, or with the to select each digit, then use the “UP” or
INOVATION configuration utility. “DOWN” keys to increment or decrement the
value of the selected digit.
Both methods consist of the following steps. 5. Press the “PRG” key to enter the setting (CAL
will be blinking on the display).
Zero calibration
Apply a known load (test weight) 6. Press the “PRG” key, (the display indicates
Edit weight value CALIBR), press either the “UP” or “DOWN”
Span calibration keys to move to the next parameter.
Optional linearization (See page 14) 7. If no additional parameter changes are
required, press the “O” key (the display
2-point calibration via the front panel keys indicates STORE ?), press the “PRG” key to
save the changes and return to the operating
To calibrate the transmitter with the front panel mode.
keys, proceed as follows:
Should it be necessary to erase either of the
1. With the unit in “Basic Configuration” mode, previous calibration entries, proceed as follows:
press the “PRG” key (CAL will be blinking on
the display). When the message CAL is blinking on the display,
to erase the zero calibration, press and hold the
2. With the system unloaded, press the “O” key. “FUN” key, and then press the “O” key. Release
both keys, the previous zero calibration entry has
3. Apply a known load not less than 10% of the been erased. To erase the span calibration, press
net weight value and press the “UP” key. and hold the “FUN” key, and then press the “SET”
key. Release both keys, the previous span
calibration entry has been erased. End the
procedure as described above (points 6 and 7).
8
Complete Configuration via the Front Panel Configuration using INOVATION
In order to perform a complete configuration, the To configure the transmitter with the
unit must be placed in setup mode. To enter the INOVATION program, proceed as follows:
setup mode, press and hold the “PRG” and SET”
keys on the front of the unit. The “SET” key 1. Install INOVATION on an IBM-compatible
must be pressed after the “PRG” key. Release computer running Windows 95, 98, Me or XP.
both keys when the word CONFIG is shown on
the display. The CONFIG menu is the first of six 2. Minimum system requirements are 8MB of
main menus used to completely configure the extended memory and at least 5MB of
instrument. Use either the “UP” or “DOWN” available hard drive space.
keys to navigate through the six main menus
shown below. 3. Remove power from both units, and connect
the PC’s serial port to the RS-232 terminals
on the transmitter. Refer to page 25 for wiring.
Display Main Menu Functions 4. Apply power to the PC and the transmitter,
then start the INOVATION program.
CONFIG Parameters for total scale capacity,
transducer sensitivity, net, dead load 5. Switch the transmitter into remote mode by
weight values, and display divisions. going into complete configuration and then
selecting ‘Remote’ from the serial menu.
CALIBR Zero and full scale calibration. Refer to the serial menu on page 18.
9
Configuration using INOVATION (cont’d) If the operator answers “Yes”, the “Dead load”
value inside the first file folder will change
On this screen you can switch the display automatically according to the new zero.
among net, gross and peak reading, set the se- If the operator answers “No”, the “Dead load”
rial address, enter values for the two setpoints, value inside the first file folder will remain set to
check the two logic inputs status and the the previous value.
software release of the instrument. The third file folder contains the parameter
Click on the SETUP button, seven file folders will selections for digital filtering, zero tracking, etc.
appear on the lower half of the screen. The first The fourth file folder contains the parameter
file folder labeled “Parameters” will be open. selections for configuring the inputs and outputs
The top section in this folder is for entering the The fifth file folder contains the parameter
total scale capacity, sensitivity, net weight, and selections for the serial output.
dead load weight values (required parameters
for performing a data sheet calibration) The sixth folder contains the parameter
selections for the analog output,
The data sheet calibration procedure allows the
transmitter to be calibrated without a transducer The seventh folder provides a means for testing
simulator or test weights. This procedure is the outputs and analog output
based on the capacity and certified, full scale The Main Setup Screen and file folders 1
mV/V output (sensitivity) of the transducer/s. through 6 all have SEND buttons on them for
To perform a data sheet calibration, enter the downloading the various parameter changes.
above values, then click on the SEND button for When configuration and calibration has been
that group of parameters. completed, the data can be saved on a PC or
The next section in this file folder is used to floppy disk or downloaded (sent) to the
select the display resolution. It consists of a transmitter. This method of configuring and
drop down menu and a SEND button. calibrating is very beneficial when several
transmitters with similar configurations are being
The Precise units allow to count by 1’s up to set up, or when a transmitter has to be replaced.
60,000 counts, Yet, for values greater than
10,000, the units automatically select a lower To exit INOVATION , click on the Exit Setup
resolution to ensure greater stability. After se- icon. Now click on Option in the upper left corner
lecting the desired resolution, press the SEND of the screen, from the drop down menu select
button for this parameter. Do not press any of EXIT, a “Save Changes” window will appear,
the other SEND buttons in this folder or the unit click on OK. This will return you to the
will revert back to a default setting of x2, x5, etc. Configuration Utility Screen, click on QUIT.
Changes to the display resolution should
only be done after the unit has already been Figure 2 shows an example of one of the
calibrated using the data sheet or dead load INOVATION configuration screens.
procedure.
The bottom parameter selection in this file folder
is labeled “Operating Mode”. It enables the unit Figure 2
to retain the mode of operation in the event of a
power loss. When the power is re-applied, the
transmitter automatically returns to the mode
that it was operating in prior to the power loss.
Changes to the Operating Mode cause an
automatic power off - power on sequence of the
instrument when the configuration will be saved.
This allows the new Operating Mode to take
effect.
The second file folder enables you to calibrate
the unit with a transducer simulator or actual
weight, (recommended method of calibration).
Inside this 2nd file folder, once the zero
calibration has been performed, the program
asks the operator if the new zero has to modify
the “Data sheet” calibration.
10
Figure 2.1
PRINT CONFIGURATION
The Inovation software also allows the
Date 12/01/2004 Test Procedure for DAT instruments
operator to create new configurations,
Status Instrument
save new files and open existing files wi- Device address 2
thout having any instrument connec- Setpoint 1 value 1500
ted to the computer. Setpoint 2 value 3500
Input 1 status 0
Input 2 status 0
Thanks to this feature, the download of Instrument software version 0.4
a given configuration to the instrument Parameters
can be performed at any time. Total capacity of transducers 10000
Full scale output value (mV/V) 2.0000
To perform the operation mentioned Net weight (value) 8000
Dead load (value) 1500
above click on the “Edit” menu at the left Display resolution 1
end upper corner (See figure 2.1), then Input signal 0.599
enable the function “Edit Configuration Internal counts (Reference only) 155729
Operating mode Net
Offline”.
Filters / z-track
The message “Edit” will appear on the Digital filter value (0 to 9: 0 = no filter; 9 = max filter; default 5) 5
display, showing this particular condition. Motion band value (0 to 4: 0 = minimum; 4 = maximum; default 2) 1
Auto zero range setting at power up (0 to 10.0% of net weight: 0 = disble) 0.0
Another useful function concern the Zero tracking (0 to 4: default 2) 2
possibility to print out a report in which Output config. Out 1
Operating mode Net
all the parameters of a given Contact status below setpoint value N. Open
configuration are included. Positive / Negative weight comparison Positive
Immediate activation / activation after stabilization Immediate
The “Print” command can be performed Hysteresis (default 2) 2
by clicking on “Print Configuration”. Setpoint activation time length (in 1/10 sec.) (0 = disable) 0
Time delay for activating setpoint (in 1/10 sec.) (0 = disable) 0
Besides, the command “Report Notes” Output config. Out 2
allows the operator to include a heading Operating mode Gross
Contact status below setpoint value N. Closed
in the report, in order to identify the plant, Positive / Negative weight comparison Positive
the customer name or any other Immediate activation / activation after stabilization Immediate
useful information. Hysteresis (default 2) 50
Setpoint activation time length (in 1/10 sec.) (0 = disable) 0
Time delay for activating setpoint (in 1/10 sec.) (0 = disable) 0
An example of a printed report is given
Serial
on the right side of this page: Baud Rate (default 9600) 9600
Serial port mode (default Continuous transmission) Slave
Serial address (ID Code) (from 01 to 32) 2
Response delay (Demand or Modbus mode) (in 1/100 sec. Max 1 sec.) 25
Data Format (N-8-2 / E-8-1 / O-8-1 for MODBUS mode) N-8-1
Com2 Protocol (None for MODBUS mode) None
Com2 Address (Profibus/DeviceNet Address from 1 to 126) 001
Com2 Baud Rate (Only DeviceNet) 250
Ana. Output
Full scale value (default = Net weight value) 8000
Analog output source (Net Gross Peak H) Net
Analog output selection 0-20mA
No load zero input value 0
11
Complete Configuration Menu
( PRG )
Enter total
( O CAPAC ( PRG ) scale ( PRG )
capacity
Enter
( O SENSIT ( PRG ) transducer/s ( PRG )
sensitivity
Enter
( O NET ( PRG ) “LIVE” ( PRG )
weight value
Enter
( ( PRG ) “Dead Load” ( PRG )
O DEAD L
weight value
Select display
( O DSPDIV ( PRG ) divisions ( PRG )
0.001 - 50
View input
( O SIGNAL ( PRG ) signal value ( O
mV/V
View the
( O COUNTS ( PRG ) Raw ( O
A/D counts
( O OPMODE
Operating
( PRG ) GROSS NET PEAK H mode @
power up
( PRG )
Place the unit in complete configuration To change the value, press the “O” key to select
mode by pressing and holding the “PRG” a digit, then use the “UP” or “DOWN” keys to
and SET” keys on the front of the unit. The increment or decrement the value of the
“SET” key must be pressed after the “PRG” selected digit. Press the “PRG” key to enter
key. Release both keys when CONFIG is dis- the new value, then press either the “UP” or
played. “DOWN” keys to move to the next sub-menu
parameter or press the “O” key to return to the
Press the “PRG” key to enter the sub-menu, main menu.
then use either the “UP” or “DOWN” keys to se- To exit the configuration procedure, return to the
lect one of the sub-menu parameters. Press the main menu and press the “O” key, (the display
“PRG” key to view the default or previously se- will indicate STORE ?), press the “PRG” key to
lected value for that parameter. save the changes and return to the operating
mode.
12
Complete Configuration Menu (cont’d)
NOTE: In order to ensure greater stability during the calibration procedure, the digital filter increases
to the maximum value automatically (value 9), therefore the weight indication updates very slowly at
this stage. Once the calibration procedure has been completed, the digital filter will return to the pre-
vious value automatically.
( PRG )
Sets ZERO
( PRG ) CAL ( O
calibration
Enter the
WT-VALUE actual weight ( PRG )
value (SPAN)
( PRG ) CAL
NOTE:
Input signal from the transducer/s
must be stable when entering the
zero and span values.
NOTE: Prior to calibration, the transmitter must 5. Enter the actual weight value using the “O” key
be configured, thus giving it a set of operating to select each digit, then use the “UP” or
parameters. “DOWN” keys to increment or decrement the
value of the digit. Press the “PRG” key to enter
The unit can be calibrated using the 2-point the setting (CAL will be blinking on the display).
method or the optional multi-point (linearity
compensation) method. See page 14 for a 6. Press the “PRG” key, (the display indicates
detailed description of the multi-point calibration CALIBR), press either the “UP” or “DOWN
procedure. keys to move to the next parameter.
2-Point calibration via the front panel keys 7. If no additional parameter changes are
required, press the “O” key (the display
To calibrate the transmitter using the front panel indicates STORE ?), press the “PRG” key to
keys, proceed as follows: save the changes and return to the operating
mode.
1. With the unit in “Complete Configuration”
mode, press either the “UP” or “DOWN” Should it be necessary to erase either of the
keys until CALIBR is shown on the display. previous calibration entries, proceed as follows:
2. Press the “PRG” key (CAL will be blinking on To erase the zero calibration, press and hold the
the display). “FUN” key, and then press the “O” key.
Release both keys, the previous zero calibration
3. With the system unloaded, press the “O” key. entry has been erased. To erase the span
calibration, press and hold the “FUN” key, and
4. Apply a known weight not less than 10% of then press the “SET” key. Release both keys, the
the net weight value and press the “UP” key. previous span calibration entry has been erased.
13
Basic Configuration Menu (cont’d)
Apply a known
Lin P1 weight on the
scale
( PRG )
Display and
WT VALUE edit test ( PRG )
weight value
( O
The Precise™ 500 Series Digital / Analog 5. Press the “PRG” key. The unit will increment
Transmitters feature a 10-point linearization to the next linearization point (Lin P2).
option (available only with the front panel keys).
Any number of points up to 10 may be used, 6. Repeat steps 3 through 5 for additional points.
however, the last point must always be the full 7. If all 10 points will be linearized, follow the 1st.
scale value of the weighing system. procedure. For linearization correction using
Example: A one point linearization correction less than 10 points, follow the 2nd. procedure.
would require a total of two points, one point 1st Procedure (10-point linearization)
within the range, and one point for full scale.
7a. Enter the weight value for linearization point
Prior to performing the linearization correction, Lin P9, and press the “PRG” key (CAL will be
at least the zero of the unit must have already blinking on the display). Press the “PRG” key
been calibrated, while the full scale value is not again, (the display indicates CALIBR).
mandatory. The unit must be in CALIBR mode,
and you should have known weights available 7b. Press the “O” key (the display will indicate
equal to the points being set. STORE ?), press the “PRG” to save the
changes and return to the operating mode.
Multi-point Calibration via Front Panel Keys
2nd. Procedure (less than 10-point linearization)
1. With the unit in either “Basic or Complete
Configuration” mode, press the “PRG” key 7a. The last linearization point must be the full
(CAL will be blinking on the display). scale value. Press the “O” key, (CAL will be
blinking on the display).
2. Press and hold the “SET” key until Lin P1 is
blinking on the display. 7b. Press the “PRG” key (the display will show
CALIBR). Press the “O” key (the display will
3. Apply a known weight for the first linearization indicate STORE ?).
point, and press the “PRG” key.
7c. Press the “PRG” key to save the changes
4. Enter the actual weight value using the “O” and return to the operating mode.
key to select each digit, then use the “UP”
and “DOWN” keys to increment or decrement
the value of the selected digit.
14
Complete Configuration Menu (cont’d)
( PRG )
Enter value
( O FILTER ( PRG ) 0 to 9 ( PRG )
Default = 5
Enter value
( O MOTION ( PRG ) 0 to 4 ( PRG )
Default = 2
Enter value
( O AUTO 0 ( PRG ) 0.0 to 10.0% ( PRG )
0 = Disabled
Enter value
( O 0 TRAC ( PRG ) 0 to 4 ( PRG )
Default = 2
Enter value
( O 0 BAND ( PRG ) 0 to 200 ( PRG )
Default = 100
1. With the unit in “Complete Configuration” 5. Press the “PRG” key to enter the new value,
mode, press either the “UP” or “DOWN” then press either the “UP” or “DOWN” keys to
keys until PARAM is shown on the display. move to the next sub-menu parameter or
press the “O” key to return to the main menu.
2. Press the “PRG” key to enter the sub-menu,
then use either the “UP” or “DOWN” keys to 6. To exit the configuration procedure, return to
select one of the sub-menu parameters. the main menu and press the “O” key, (the
display indicates STORE ?), press the “PRG”
3. Press the “PRG” key to view the default or key to save the changes and return to the
previously selected value for that parameter. operating mode.
See Table 2 on page 26 for a detailed explanation of the “PARAM” parameter selections
15
Complete Configuration Menu (cont’d)
( PRG )
( O MODE 1 ( PRG )
( PRG ) NET
( PRG ) GROSS
on page 28
( PRG ) PEAK H
( O HYST 1 ( PRG ) ( PRG )
Default = 2
( PRG ) N.O.
Enter value
( O TIMER 1 ( PRG ) 0.00 - 100.0 ( PRG ) ( PRG ) N.C.
Default = 0
See notes
( O HYST 2 ( PRG ) on page 28 ( PRG )
Default = 2
Enter value
( O TIMER 2 ( PRG ) 0.00 - 100.0 ( PRG )
Default = 0
Enter value
( O DELAY 2 ( PRG ) 0.00 - 100.0 ( PRG )
Default = 0
16
Complete Configuration Menu (cont’d)
Closing Input 1 = 10
Closing Input 2 = 02
( O TEST IN ( PRG ) IN 0 0 ( O
( O OUT 00
( O OUT 10 See
( O OUT 02 Table 1
( O OUT 12
Table 1
OUT 10 ON OFF
OUT 02 OFF ON
OUT 12 ON ON
See Table 6 on page 28 for a detailed explanation of the “IN - OUT” parameter selections
17
SERIAL ANALOG CONFIG CALIBR PARAM IN-OUT
( PRG )
( O BAUD R ( PRG )
( PRG ) 2400
( PRG ) 9600
( O PROT-1 ( PRG ) ( PRG ) 19200
( PRG ) CONTIN ( PRG ) 38400
( PRG ) DEMAND ( PRG ) 115200
( PRG ) AUTOM
( PRG ) SLAVE
MODBUS ( PRG )
( PRG ) BCD
( PRG ) NONE
( PRG ) E 8 1
( PRG ) o 8 1
( O PROT-2 ( PRG )
( PRG ) NONE
( O DATA F ( PRG )
( PRG ) n 8 2
( PRG ) E 8 1
( PRG ) o 8 1
( PRG ) n 7 2
( PRG ) E 7 1
( PRG ) E 7 2
See Tables 3 through 5 for ( PRG ) o 7 1
a detailed explanation of the
“SERIAL” parameter selections
18
Complete Configuration Menu (cont’d)
( PRG )
( O MODE ( PRG )
( PRG ) NET
( O TEST ( PRG )
( O OUT 0
( O RANGE ( PRG )
( O OUT 100
( PRG ) 0-20 mA
( PRG ) 4-20 mA
( PRG ) 0-10 V
( PRG ) 0-5 V
( O OFFSET ( PRG )
1. With the unit in “Complete Configuration” 5. To edit numerical values, use the “O” key to
mode, press either the “UP” or “DOWN” select the digit, then use either the “UP” or
keys until ANALOG is shown on the display. “DOWN” keys to increment or decrement the
value of the selected digit.
2. Press the “PRG” key to enter the sub-menu,
then use either the “UP” or “DOWN” keys to 6. Press the “PRG” key to enter the new value,
select one of the sub-menu parameters. then press either the “UP” or “DOWN” keys to
move to the next sub-menu parameter or
3. Press the “PRG” key to view the default or
press the “O” key to return to the main menu.
previously selected value for that parameter.
The “ANZERO” parameter is a negative weight
4. To change a parameter, press either the “UP”
value to which the zero offset of the analog out-
or “DOWN” keys to view the choices for that
put can be referred.
parameter.
When the desired selection appears on the Example: If the selected range is 4/20 mA and
display, press the “PRG” key to enter the the “ANZERO” value is “10”, the analog output
selection and move to the next parameter. value will be 4 mA when the weight will be “–10”
19
Serial Communication
Baud Rates
2400, 9600, 19200, 38400, and 115200
Data Formats
All serial characters are in ASCII format, and consist of the following.
1 Start Bit, 7 or 8 Data Bits, 1 or 2 Stop Bit, Parity No, Even or Odd.
The above data depend on the selection made in the “SERIAL” menu (see Table 3 on page 26)
Transmission of the serial data can be initiated in several ways as described below.
Automatic mode
The “Automatic” mode is used to interface with printers or other data acquisition devices. The serial
data is transmitted automatically, upon stabilization whenever the weight value has increased or
decreased more than 20 divisions.
This function is not performable when the “MOTION” parameter is set to 0 (weight stability check
disabled).
Continuous mode
The “Continuous” mode is used to interface with computers, remote displays, or other types of
devices that require constant data updating.
Demand mode
The “Demand” mode is used to interface with printers and requires a manual print command from the
front panel keys (Model 400) or a remote contact closure to initiate the output.
In the above modes, the transmitter sends serial data using the format shown below:
STX <status> <net weight> <gross weight> <peak value> ETX <chksum> EOT
STX (start of text) = 02h ETX (end of text) = 03h EOT (end of transmission) = 04h
NOTE: The brackets “<“ “>“ are not sent, they are only shown for clarification.
The result of the above calculation equals 1 character, which can be a numerical value of 0 to 9 or
A to F (Hexadecimal)
20
Serial Communication (cont’d)
Slave mode
The slave mode is used for interfacing with distributed control systems (DCS) or programmable logic
controllers (PLC). This mode requires a data request from the master to initiate the output.
In this mode the host sends serial data to the transmitter using the formats shown below:
<addr> “N” EOT
After receiving the request, the transmitter responds with the following data string.
<addr> “N” <status> <net weight> <gross weight> <peak value> ETX <chksum> EOT
In case of an error, the transmitter will respond with the following data string.
Character strings
NOTE: The brackets “<“ ”>“ are not sent, they are only shown for clarification.
The checksum control value is obtained by performing the XOR operation.
It is expressed with 2 Hexadecimal digits. Example: 25 = 1D
The result of the above calculation equals 1 character, which can be a numerical value of 0 to 9 or
A to F (Hexadecimal)
In case of an error, the transmitter will respond with the following data string.
The programmed values are stored in RAM, however, they are not retained if the power is removed.
There is no limit on the number of times that these commands can be performed.
21
Store set-point values in Eeprom
In case of an error, the transmitter will respond with the following data string.
In case of an error, the transmitter will respond with the following data string.
In case of an error, the transmitter will respond with the following data string.
22
Switch to Net weight mode
In case of an error, the transmitter will respond with the following data string.
In case of an error, the transmitter will respond with the following data string.
Modbus mode
The Modbus mode is used to communicate with Modicon Programmable Controllers using a unique
message structure that the controllers can understand regardless of the type of networks being used.
Please refer to the tables on pages 29 through 39 for information regarding the “MODBUS” RTU
Protocol Specifications.
Modbus® and Modicon® are registered trademarks of the Schneider Automation Group.
23
Serial Output Wiring Connections
RS-232 serial connections to a computer, remote serial display or other data acquisition device.
See Figure 3
Figure 3
Rx
Tx
Gnd
5 6 7 8 9 10 11 12
+ Rx
+ Tx
Gnd
- Rx
Rxd
- Tx
Txd
Common
Gnd
+ Rxd
- Rxd
+ Txd
- Txd
Transmitter # 32 Transmitter # 1
8 9 10 11 12 8 9 10 11 12
+ Rx
+ Rx
+ Tx
+ Tx
Gnd
Gnd
- Rx
- Rx
- Tx
- Tx
24
Figure 5 RS485 Connection
Gnd
RS485 +
RS485
Transmitter # 32 Transmitter # 1
8 9 10 11 12 8 9 10 11 12
+ Rx
+ Rx
+ Tx
+ Tx
Gnd
Gnd
- Rx
- Rx
- Tx
- Tx
RS-422 or RS-485 RS-422 or RS-485
Rx (Pin 2) Rx (Pin 3)
Tx (Pin 3) Tx (Pin 2)
5 6 7 8 9 10 11 12
+ Rx
+ Tx
Gnd
- Rx
Rxd
- Tx
Txd
Common
Not only the RS232, but also the RS422 or RS485 can be used for the communication with the
Inovation software. Refer to Figures 3, 4, 5 depending on the desired connection.
25
Sub-menu parameter selections
Digital filtering affects the update rate and speed of the unit. 0 BAND:
Filter setting =0 Update rate = 25 Hz this parameter defines the operating
Filter setting =1 Update rate = 10 Hz
Filter setting =2 Update rate = 5 Hz
range of the “Zero” key (and Input 1),
Filter setting =3 Update rate = 2.5 Hz used to zero the unit in Gross mode.
Filter setting =4 Update rate = 1.5 Hz
Filter setting =5 Update rate = 1 Hz
Filter setting =6 Update rate = 0.7 Hz
Filter setting =7 Update rate = 0.4 Hz
Filter setting =8 Update rate = 0.2 Hz
Filter setting =9 Update rate = 0.1 Hz
26
Sub-menu parameter selections (cont’d)
Continuous transmission:
The transmission speed depends on the digital filter setting and the baud rate value selected.
See Table 4 below for additional information.
Table 4
BAUD RATE
2400 9600 19,200 38,400 115,200
D 0 6 Hz 25 Hz 50 Hz 50 Hz 50 Hz
I 1 6 Hz 25 Hz 50 Hz 50 Hz 50 Hz
G
I 2 6 Hz 25 Hz 50 Hz 50 Hz 50 Hz
T 3 6 Hz 25 Hz 25 Hz 25 Hz 25 Hz
A
L 4 6 Hz 25 Hz 25 Hz 25 Hz 25 Hz
F 5 6 Hz 12 Hz 12 Hz 12 Hz 12 Hz
I 6 6 Hz 12 Hz 12 Hz 12 Hz 12 Hz
L
T 7 6 Hz 12 Hz 12 Hz 12 Hz 12 Hz
E
8 6 Hz 6 Hz 6 Hz 6 Hz 6 Hz
R
9 6 Hz 6 Hz 6 Hz 6 Hz 6 Hz
Table 5
BAUD RATE
2400 9600
D 0 12 Hz 50 Hz
I 1 12 Hz 50 Hz
G
I 2 12 Hz 50 Hz
T 3 12 Hz 25 Hz
A
L 4 12 Hz 25 Hz
F 5 12 Hz 12 Hz
I 6 12 Hz 12 Hz
L
T 7 12 Hz 12 Hz
E
8 6 Hz 6 Hz
R
9 6 Hz 6 Hz
27
Sub-menu parameter selections (cont’d)
Table 6
NOTES:
1. The hysteresis setting must be less than it’s respective setpoint value.
Entering a hysteresis setting greater than the setpoint value will automatically
be replaced with a default setting of (2) counts.
Setpoint 1 is used to fill a vessel with 5,000 lbs. of product, and setpoint 2 will be
used as a high weight alarm. When the weight in the vessel reaches 5,000 lbs.,
relay # 1 de-energizes stopping the flow, feed, etc. The product is drawn from the
vessel as required, when the weight in the vessel reaches 10 lbs., setpoint # 1’s
relay re-energizes and automatically refills the vessel to 5,000 lbs.
28
MODBUS RTU PROTOCOL SPECIFICATIONS
1. PRECAUTIONS
The Modbus protocol writes directly into the memory of the instrument.
Use caution when sending data to the instrument:
The data being sent must be within the specified ranges given in the tables on the following pages.
Some of the data is written into the E2prom’s memory (refer to the column in the tables “Stored in
E2prom”) for additional information. This memory can only be written to 100,000 times, therefore,
you should avoid writing continuously into this memory.
To confirm the storage of a new value in the E2prom, perform the MAKE - BACKUP function.
If this function is not performed, all of the newly stored data will be lost when power is removed from
the instrument.
The “Set point” setting does not require the MAKE - BACKUP function to be performed.
The set point values are expressed as number of divisions
This means that any set point value (temporary or permanent) has to be multiplied by the “Display
division” data, in order to obtain the actual value of the set point.
E.G. Assuming that the “display division” value is 0.2; if the PLC asks for a set point value and get
the data “3949” from the instrument, this means that the actual value of the set point is 789.8
(3949 x 0.2 = 789.8)
Even the other weight values are given as number of divisions, except for the “Net weight” and
“Gross weight”.
“Net weight” and “Gross weight” (Modbus addresses 40006 and 40007) are given as absolute
values
Note:
The numeric values on the following pages for (addresses, codes, and data) are represented as
decimal values.
The addresses given in the following tables refer to the standards provided in the Modicon Modbus
Protocol Reference Guide PI-MBUS-300 Rev J.
2. DATA FORMAT
Start Bit : 1
Data Bits : 8, the Least Significant Bit (LSB) is sent first.
Parity : No, Even, Odd
Stop Bits : 1, 2
Possible Data Format Selection: N-8-2 E-8-1 O-8-1
Function Description
01 (01) READ COIL STATUS
29
Each single function is explained in detail on pages 32, 33 and 34 of the operator’s manual.
Each function is composed by a Query (request master instrument) and a Response
(answer instrument master). Queries and responses are composed by a sequence of data that
are briefly explained here below (***), please note that the code “0x” before any value indicates that
the value is represented as hexadecimal value.
Besides, all the Modbus addresses (the ones mentioned in the left end column on pages 36 and
37) have to be represented as hexadecimal values, but, only for these addresses, there is an im-
portant rule to be taken into consideration:
Before converting the address into an hexadecimal value, the 1st digit on the left has not to
be considered and the remaining 4 digits have to be decremented by “1”.
1st Example:
To represent the address 40150 (“display division” on page 36) as hexadecimal value, exclude the
digit “4” (remains “0150”), then decrement by 1 the number “0150”. The result is “0149”, now perform
the conversion into hexadecimal. The result is “00 95”. This is the value to be used in the query.
2nd Example:
To represent the address 40102 (“load cells sensitivity” on page 36) as hexadecimal value, exclude
the digit “4” (remains “0102”), then decrement by 1 the number “0102”. The result is “0101”, now per-
form the conversion into hexadecimal. The result is “00 65”. This is the value to be used in the query.
(***)
Address: is the number of the instrument’s address, represented as hexadecimal value
(in this case do not decrement by 1 the number).
Function: is the number of the function to be performed (see the table above)
1st Output address: is the address number where the reading of the outputs status has to start
Number of outputs: is the number of the outputs to be read
1st Input address: is the address number where the reading of the inputs has to start
Number of inputs: is the number of the inputs to be read
Number of bytes: represents the number of bytes which compose a data
2 byte CRC: “Cyclical Redundancy Check”. It’s an algorithm used as checksum.
Total byte: Total number of bytes transmitted. This data is not included in the strings.
Exceptions:
Query Master to slave 01 Response time slave 01 Response slave 01 20 mSec delay Query Master to slave 02
Query Master to slave 01 Response time slave 01 Response slave 01 delay Query Master to slave 02
30
Scheme of the communication time in a Master-Slave RS-485 system, using a double twisted pair.
Tx PC
Tx Slave 01
Tx Slave 01
Tx PC
Tx Slave 01
Tx Slave 01
15 mSec
31
5. LIST OF TRANSMISSION STRINGS
QUERY
Address Function 1st. Output address Number of outputs 2 byte Total byte
RESPONSE
A 0 x 01 0 x 01 0 x 00 CRC 6
QUERY
Address Function 1st. Register address Number of register 2 byte Total byte
RESPONSE
Address Function Number of bytes 1st. Register 2nd. Register 2 byte Total byte
QUERY
Address Function 1st. Register address Number of register 2 byte Total byte
RESPONSE
32
5.5. FUNCTION 5: FORCE SINGLE COIL
QUERY
RESPONSE
QUERY
RESPONSE
QUERY
Address Function 1st. Output address Nº of outputs Nº of bytes Status of outputs 2 byte Total byte
RESPONSE
Number of outputs: Number of the output to be written, starting from the address.
Number of bytes: Number of bytes transmitted as status of outputs (8 outputs each byte)
Status of outputs: 1 output each bit (1 = On, 0 = Off); the 1st. Output coincides with the least significant bit (LSB) of the 1st.
Byte. Non-significant bits are set to zero.
The response includes the identification of the modified outputs.
33
5.16 FUNCTION 16: PRESET MULTIPLE REGISTERS
QUERY
Address Function 1st. Number of Number of 1st. 2nd. 2 byte Total byte
Register output register bytes Register Register
value value
RESPONSE
Number of registers: Number of the registers to be written, starting from the address.
Number of bytes: Number of bytes transmitted as registers value (2 bytes each register)
Registers value: Content of the registers, starting from the 1st.
The response includes the identification of the modified registers.
6 BROADCAST MODE
The communication strings are controlled by the CRC (Cyclical Redundancy Check). If a communication error occurs, the
slave unit doesn’t answer. The master unit controls a timeout when waiting for the response from the slave. If the slave
doesn’t answer during this timeout, it means that a communication error has occurred.
If the string is received correctly but is not executable, the slave answers the master with an EXCEPTION RESPONSE.
The field “function” is transmitted having the most significant digit (MSD) set to 1.
EXCEPTION RESPONSE
Code Description
1 ILLEGAL FUNCTION (The function is not valid or not supported)
34
6 BROADCAST MODE
The communication strings are controlled by the CRC (Cyclical Redundancy Check). If a communication error occurs, the
slave unit doesn’t answer. The master unit controls a timeout when waiting for the response from the slave. If the slave
doesn’t answer during this timeout, it means that a communication error has occurred.
If the string is received correctly but is not executable, the slave answers the master with an EXCEPTION RESPONSE.
The field “function” is transmitted having the most significant digit (MSD) set to 1.
EXCEPTION RESPONSE
Code Description
35
List of the Holding Registers (4x)
Peak Value
Basic Configuration
40100 Load cell/s total capacity (kg) H CAPAC 0-500000 (1) YES
40101 Load cell/s total capacity (kg) L
40103 Net weight of the weighing system (H) NET 0 to full scale (1) YES
40104 Net weight of the weighing system (L)
40105 Dead load of the weighing system (H) DEAD L 0 to full scale (1) YES
40106 Dead load of the weighing system (L)
Weighing Parameters
36
List of the Holding Registers (4x) cont’d
Analog Output
(1) The combined theoretical net and tare weight values must not exceed the total capacity value.
(2) Refer to the 15 values from 0.001 to 50
(3) For the list of values please refer to the user manual.
(4) They are stored in the E2prom if writing the function 0000 in the status register.
(5) When setting these values the decimal point has not to be included.
Once the “serial address” and “response delay” have been modified, they take effect immediately.
The serial port mode can’t be modified via Modbus.
When setting a new baud rate value, the power to the instrument must be removed and re-applied in order for the
changes to take effect.
TABLE “A”
IDENTIFICATION CODES
0 (00) 0.001
1 (01) 0.002
2 (02) 0.005
3 (03) 0.01
4 (04) 0.02
5 (05) 0.05
6 (06) 0.1
7 (07) 0.2
8 (08) 0.5
9 (09) 1
10 (0A) 2
11 (0B) 5
12 (0C) 10
13 (0D) 20
14 (0E) 50
37
Table of the Input Status bytes
(*) The scale is considered unloaded (empty) when the weight value is within the “0 Band”
range (see “Table 2”, page 26)
Modbus Description
Address
Modbus address 30007 = 00 01: the weight value is shown on the display. The instrument is “On-line”
Modbus address 30007 = 00 00: one of the error conditions (underload, overload, offrange) occurs, or any
programming procedure is underway. The instrument is “Off-line”.
Bit’s meaning
Modbus Description Range value Stored in
Address E2prom
0 1
38
List of the functions “Command register”
0004 (04 Hex) Analog output full scale offset adjustment - YES
For additional information regarding the Modbus protocol, please refer to the Modbus Protocol Manual PI-MBUS-300 Rev J.
39
Intrinsic Safety Barriers
+ Signal + Signal
1 7761 3 + Sen 1
- Exc. 13 - Signal - Signal 1 - Sig - Sen 2
2 4
+ Exc. 14 2 + Sig + Exc 3
+ Sens 15 + Exc. + Exc. 3 - Exc - Exc 4
- Sens 16 3 4 - Sens + Sig 5
+ Sig 5
- Sig 6
Shield 7
TB2
+ Sen 1
FUNCTION BARRIER TYPE QTY 1 + Exc - Sen 2
2 - Exc + Exc 3
+/- Signal 7761 Pac 1 3 + Sig - Exc 4
FUNCTION COLOR - Sig
4 + Sig 5
+/- Exc. 7766 Pac 1 5 Shield - Sig 6
+ Exc. Green Shield 7
- Exc. Black
- Sense Yellow
+ Signal Red
- Signal White
Shield Bare
Options
Precise™
24 Volt Power Supply
Installation
Make sure the installation complies with local regulations and electrical codes.
Connect AC voltage to the terminals marked “L” and “N”.
The DC voltage is available on the terminals marked “+” and “-”. The second set of terminals
are used when powering two transmitters from a single power supply (See notes).
A red LED is illuminated when the power supply is “ON”.
Notes: The power supply should be used to power two transmitters only when a single load cell is
connected to each transmitter. For multiple load cell applications it is recommended that an
individual power supply be used for each transmitter. This enables the power supply to
compensate for any fluctuations in the incoming line voltage. Recent field experiences have
shown that voltage drops of greater than 10% can cause the transmitters to drift and become
unstable.
Fuse
L N LED + -
Mains in 24 Vdc
Fuse Replacement
The following procedures require work inside the power supply enclosure and should be
performed by qualified service personnel.
Before opening the unit, disconnect the AC voltage.
Remove the front cover from the power supply.
Press down gently on the cover of the fuse holder, and turn counter-clockwise.
Pull out the cover and fuse as an assembly, replace fuse with a new one.
Re-install fuse and cover as an assembly, press down gently and turn clockwise.
Replace the front cover on the power supply.
Re-apply AC voltage to the unit.
In the event of a malfunction, please contact the nearest distributor for assistance.
Any attempt to modify or repair the power supply will void the manufacturers warranty.
41