TP 7141
TP 7141
TP 7141
Models:
KD700-KD4000
KD1250-4, KD2500-4, KD3250-4
Controller:
APM603
TP-7141 11/22c
WARNING: This product can expose you to chemicals, including carbon monoxide and
benzene, which are known to the State of California to cause cancer and birth defects or
other reproductive harm. For more information go to www.P65warnings.ca.gov
WARNING: Breathing diesel engine exhaust exposes you to chemicals known to the
State of California to cause cancer and birth defects or other reproductive harm.
• Always start and operate the engine in a well-ventilated area.
• If in an enclosed area, vent the exhaust to the outside.
• Do not modify or tamper with the exhaust system.
• Do not idle the engine except as necessary.
For more information go to www.P65warnings.ca.gov/diesel
Product identification numbers determine service parts. Record the product identification numbers in the spaces below
immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed
kit numbers after installing the kits.
Record the product identification numbers from the generator set nameplate(s).
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice.
Controller Description________________________________________________________
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer_________________________________________________________________
Model Designation___________________________________________________________
Serial Number_______________________________________________________________
2 TP-7141 11/22
Table of Contents
TP-7141 11/22 3
4.4 Operation Records ................................................................................................................................................. 55
4.5 Load Management ................................................................................................................................................. 57
4.5.1 Metering, Load Management Overview Screen ....................................................................................... 59
4.5.2 Metering, Load Management, Status ....................................................................................................... 60
4.5.3 Load Management Setup Details ............................................................................................................. 65
Section 5. Setup Menus and Screens .................................................................................................................... 67
5.1 Setup Menus .......................................................................................................................................................... 67
5.1.1 Changing Settings .................................................................................................................................... 67
5.2 Electrical Setup ...................................................................................................................................................... 68
5.2.1 Generator Electrical Setup ....................................................................................................................... 68
5.2.2 Battery Charger Setup Screens ............................................................................................................... 69
5.2.3 Paralleling Setup ...................................................................................................................................... 69
5.3 Engine Setup.......................................................................................................................................................... 71
5.4 Setup, Communication Screen............................................................................................................................... 73
5.5 Event Configuration................................................................................................................................................ 75
5.5.1 Generator Set Information (Genset Info) .................................................................................................. 79
5.6 Data Log Screens................................................................................................................................................... 80
Section 6. Paralleling ............................................................................................................................................... 83
6.1 Introduction ............................................................................................................................................................ 83
6.2 Metering ................................................................................................................................................................. 85
6.2.1 Paralleling, Metering, Overview ............................................................................................................... 85
6.2.2 Paralleling, Metering Status ..................................................................................................................... 87
6.2.3 Paralleling, Metering, Details ................................................................................................................... 89
6.2.4 Paralleling, Metering, PGEN .................................................................................................................... 91
6.3 Setup ...................................................................................................................................................................... 92
6.3.1 Paralleling, Setup, PGEN ......................................................................................................................... 92
6.3.2 Paralleling, Setup, Protect Relay Screen ................................................................................................. 94
6.4 Generator Management ......................................................................................................................................... 95
6.4.1 Paralleling, Generator Management Status ............................................................................................. 97
6.4.2 Gen Management Modes......................................................................................................................... 98
6.4.3 Gen Management System Status, Generator .......................................................................................... 99
6.4.4
Paralleling, Gen Management, Setup Details ........................................................................................ 101
Section 7. Remote Monitoring Display, Tier 4 Only ............................................................................................ 103
7.1 Home Screen ....................................................................................................................................................... 103
7.2 Menu Screen ........................................................................................................................................................ 104
7.2.1 Overview ................................................................................................................................................ 105
7.2.2 Fuel ........................................................................................................................................................ 106
7.2.3 Temperature .......................................................................................................................................... 107
7.2.4 Pressure................................................................................................................................................. 109
7.2.5 Aftertreatment ........................................................................................................................................ 110
7.2.6 Display Settings ..................................................................................................................................... 112
Section 8. Troubleshooting ................................................................................................................................... 113
8.1 Introduction .......................................................................................................................................................... 113
8.2 Generator Set and Controller ............................................................................................................................... 113
8.3 Engine .................................................................................................................................................................. 113
8.4 Transfer Switch .................................................................................................................................................... 113
8.5 General Troubleshooting Chart ............................................................................................................................ 114
8.6 Controller Display and Voltage Regulation Troubleshooting Chart ....................................................................... 118
Section 9. Accessories .......................................................................................................................................... 119
9.1 Battery Chargers .................................................................................................................................................. 120
9.2 Input/Output (I/O) Modules ................................................................................................................................... 121
9.3 Manual Key Switch............................................................................................................................................... 124
4 TP-7141 11/22
9.4Remote Emergency Stop Kit ................................................................................................................................ 125
9.4.1 Remote emergency stop kit. .................................................................................................................. 125
9.4.2 Lockable Emergency Stop Switch .......................................................................................................... 125
9.5 Remote Serial Annunciator .................................................................................................................................. 126
9.6 Shunt Trip Line Circuit Breaker ............................................................................................................................ 128
Appendix A. Abbreviations ....................................................................................................................................... 129
Appendix B. Engine Data .......................................................................................................................................... 133
Appendix C. Alternator Protection ........................................................................................................................... 153
Appendix D. Operating Hours and Service Log ...................................................................................................... 154
TP-7141 11/22 5
6 TP-7141 11/22
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear,
and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained.
To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions.
SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and
explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or
damaged decals.
Accidental Starting
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or
equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut do wn
the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (–) lead
first. Reconnect the negative (–) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the
generator set by the remote start/stop switch.
Battery
WARNING Explosion.
Can cause severe injury or death.
Relays in the battery charger cause arcs or sparks.
Locate the battery in a well‐ventilated area. Isolate the battery charger from explosive
fumes.
TP-7141 11/22 7
Engine Backfire/Flash Fire
Servicing the fuel system. A flash fire can cause severe injury or death. Do not smoke or permit flames or sparks near the
fuel injection system, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch f uels in an
approved container when removing the fuel line or fuel system.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with the
air cleaner removed.
Combustible materials. A fire can cause severe injury or death. Generator set engine fuels and fuel vapors are flammable
and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area
with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommen ded by the
local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures .
Combustible materials. A fire can cause severe injury or death. If using generator heaters during storage, remove
combustible materials such as covers from contact with the heater or from areas where heat could potentially cause a fire.
Exhaust System
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless,
colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when
working on or near the generator set. Never operate the generator set inside a building unles s the exhaust gas is piped safely
outside. Never operate the generator set where exhaust gas could accumulate and seep back inside a potentially occupied
building.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a
poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can caus e
death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
• Light-headedness, dizziness
• Physical fatigue, weakness in joints and muscles
• Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision
• Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active.
Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the
condition of affected persons does not improve within minutes of breathing fresh air.
8 TP-7141 11/22
Fuel System
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use extreme
care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the
reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts
or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines
and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel
line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming generator set operation.
Fuel tanks. Explosive fuel vapors can cause severe injury or death. Gasoline and other volatile fuels stored in day tanks or
subbase fuel tanks can cause an explosion. Store only diesel fuel in tanks.
Hazardous Noise
Engine noise. Hazardous noise can cause hearing loss. Generator sets not equipped with sound enclosures can produce
noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss.
Wear hearing protection when near an operating generator set.
Grounding electrical equipment. Hazardous voltage will cause severe injury or death. Electrocution is possible whenever
electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, tra nsfer
switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the
equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions
increase the risk of electrocution.
TP-7141 11/22 9
Disconnecting the electrical load. Hazardous voltage will cause severe injury or death. Disconnect the generator set from
the load by turning off the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and
heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment
damage.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install a transfer switch
in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a ut ility
electrical system can cause severe injury or death to utility personnel working on power lines.
Short circuits. Hazardous voltage/current will cause severe injury or death. Short circuits can cause bodily injury and/or
equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all
jewelry before servicing the equipment.
Installing the battery charger. Hazardous voltage will cause severe injury or death. An ungrounded battery charger may
cause electrical shock. Connect the battery charger enclosure to the ground of a permanent wiring system. As an alternative,
install an equipment grounding conductor with circuit conductors and connect it to the equipment grounding terminal or the lead
on the battery charger. Install the battery charger as prescribed in the equipment manual. Install the battery charger in
compliance with local codes and ordinances.
Connecting the battery and the battery charger. Hazardous voltage will cause severe injury or death. Reconnect the
battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and
battery(ies). Have a qualified electrician install the battery(ies).
Welding on the generator set. Can cause severe electrical equipment damage. Before welding on the generator set perform
the following steps: (1) Remove the battery cables, negative (–) lead first. (2) Disconnect all engine electronic control module
(ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the
engine battery-charging alternator connections. (5) Attach the weld ground connection close to the weld location.
Hot Parts
10 TP-7141 11/22
Introduction
This manual provides operation instructions for the generator set models listed on the front cover when equipped with the
APM603 controller.
This manual contains generator set operation instructions for readers with user-level or operator-level access to the APM603
controller. Selected accessory information is also included.
Refer to the generator set maintenance manual and the engine operation manual for scheduled maintenance information.
The information (including illustrations) in this publication represents data available at the time of print. Kohler Co. reserves the
right to change this publication and the products represented without notice and without any obligation or liability whatsoev er.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid
bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this man ual
with the equipment for future reference.
The equipment service requirements are very important for safe and efficient operation. Inspect the parts often and perform
required service at the prescribed intervals. Maintenance work must be performed by appropriately skilled and suitably traine d
maintenance personnel familiar with generator set operation and service.
Separate literature contains installation and maintenance information not provided in this manual. Figure 1 lists the available
literature part numbers.
The engine electronic controls indicate engine fault codes in addition to the generator set controller. The engine operation and
service literature provide information for identifying engine fault codes.
Literature part numbers are subject to change. For the latest literature part numbers, see the generator set parts list.
Literature Description Literature Part No.
Generator Set Installation Manual, KD Models TP-7153
Generator Set Maintenance Manual, KD Models TP-7143
Generator Set/Controller Wiring Diagram Manuals Original With Updated Digital
8 I/O Module
KD700-KD750 (APM603) NA TP-7262
KD700-KD750 (APM802) NA TP-7263
KD800-KD1000 TP-7144 TP-7252
KD1250A-KD1350 (single starter) TP-7145 TP-7253
KD1250A-KD1350 (redundant starter) TP-7145 TP-7254
KD1250-4 (single starter) TP-7182 TP-7253
KD1250-4 (redundant starter) TP-7187 TP-7254
KD1500-KD1750 (single starter) TP-7146 TP-7255
KD1500-KD1750(redundant starter) TP-7146 TP-7256
KD2000-KD2500(single starter) TP-7147 TP-7257
KD2000-KD2500(redundant starter) TP-7147 TP-7258
KD2500-4 (single starter) TP-7183 TP-7257
KD2500-4 (redundant starter) TP-7188 TP-7258
KD2800-KD3250 (single starter) TP-7148 TP-7259
KD2800-KD3250 (redundant starter) TP-7148 TP-7260
KD3250-4 (single starter) TP-7184 TP-7259
KD3250-4 (redundant starter) TP-7189 TP-7260
KD3500-KD4000 TP-7170 TP-7261
Commissioning and Setup Manual, APM603 TP-7131
Communication Protocol Operation Manual, APM603 TP-7151
Service Manual, APM603 Controller TP-7149
TM
SiteTech Software Manual TP-6701
Remote Serial Annunciator III (RSA III) Instructions TT-1625
Figure 1 Related Literature
TP-7141 11/22 11
Abbreviations
This publication makes use of numerous abbreviations. Typically, the word(s) are spelled out along with the abbreviation in
parentheses when shown for the first time in a section. Appendix A, Abbreviations, also includes many abbreviation definitions.
SiteTechTM Software
A personal computer and Kohler SiteTech TM software may be required for programming the APM603 controller if the factory
default settings are not appropriate for the application. SiteTech software is also needed for assigning configurable inputs/outputs
and for updating the controller application code. Kohler SiteTech software is available only to Kohler-trained and authorized
distributors and dealers. Contact your local distributor/dealer for assistance.
Service Assistance
12 TP-7141 11/22
Section 1. Controller Specifications and Features
1.1 Introduction
The specification sheet for each generator set provides model-specific generator and engine information. The controller
specification sheet provides specifications for this controller. Refer to the respective specification sheet for data not sup plied in
this manual. Refer to the generator set service manual, installation manual, engine operation manual, and engine service manual
for additional specifications.
USB ports (one USB and one mini-B) Warning and shutdown LEDs
Touchscreen
TP-7141 11/22 13
Controller Features:
o Intuitive operation
• Fault LEDs:
o Yellow = Warning
o Red = Shutdown
• USB connector for downloading data files, uploading files, and data logging
• Mini USB connector for controller setup using a PC with SiteTechTM software
The controller features, accessories, and menu displays depend upon the engine electronic control module (ECM) setup and
features.
1.3.1 Switches and Controls
Alarm Horn. The alarm horn alerts the operator or other attendants that a warning or shutdown condition exists.
Alarm (Horn) Silence. The alarm silence button turns off the alarm horn at the operator’s discretion.
Restore alarm horn switches at all locations, including those on remote annunciators, after correcting the fault condition an d
resetting the controller. See Resetting the Controller, in this manual.
Generator Set Master Control (OFF/RESET-AUTO-RUN). These buttons reset the controller fault LEDs and start/stop the
generator set. See the Operation section for additional information.
Note:
If a manual key switch is installed, most button operations are supplanted by the key switch position. The LEDs on the controller
will continue to display the OFF, AUTO, and RUN modes. The OFF/RESET button will reset the controller. See Manual Key
Switch in the Accessories section of this manual for more information.
LED Test. Press and hold the Alarm Silence/Lamp Test button to test the controller indicator LEDs and fault LEDs.
1.3.2 Annunciator LEDs
The controller has red and yellow annunciator fault LEDs that provide visual indication that a warning or shutdown is active. In
addition, each master control button has a status-indicating LED. See Figure 3.
14 TP-7141 11/22
1.3.3 Touchscreen Display
The touchscreen display provides generator set and engine data, parameter settings, system status, and fault information. Some
values will display zero or N/A (not available) if the generator set is not running.
The main menus are listed below. Within each main menu are multiple submenus as described in the Operation Section.
• Metering
• Setup
• Data Log
• Controller Settings
• Two tabs in the upper left corner allow the viewer to toggle between two independent screens.
• The navigation menu on the left side of the screen can be expanded and contracted as shown.
• The bell icon at the upper right indicates active alerts. Touch to view active events and event history.
• The controller settings icon allows access to settings such as display brightness and date/time. This icon al so contains
the link to the logon screen for the different access levels.
• A scroll bar appears on the right side of the screen when there are multiple pages that can be viewed or accessed.
• The boxes on the bottom of the Home screens allow the viewer to move between two screens.
TP-7141 11/22 15
Touch to toggle between two independent screens.
Controller settings
Touch to expand
and contract the
menu.
Color Code:
Gray = No Active Faults
Orange = Warning
Red = Shutdown
Expanded
menu
Pencil icon for changing
the metering displays.
See Customizing the
Home Screens.
16 TP-7141 11/22
1.3.4 Access Levels
Note:
Have setup and adjustments of the controller performed only by an authorized Kohler distributor. The setup and adjustments
are password protected.
Different access levels are used to protect the controller from inadvertent changes that can adversely affect the generator s et
operation. Access levels are described in Figure 5. The current access level is shown in the upper left corner of the screen
when the navigation menu is expanded as shown in Figure 6. The User level is the default level.
Some parameter settings are displayed at the user level but require operator access or higher to change the setting. Password-
controlled access is granted to trained, qualified Kohler distributors and dealers. See the Controller Settings Section for
instructions to log on at the Operator or Distributor access level.
After a set amount of time, the access automatically returns to the User level. The default session time duration is one hour.
The session time can be changed in the Controller Settings menu.
TP-7141 11/22 17
18 TP-7141 11/22
Section 2. Inputs and Outputs
The controller is equipped with the standard, dedicated inputs and outputs shown in Figure 7 and Figure 8. These inputs and
outputs are factory set and cannot be adjusted.
Inputs Tier 2 Inputs Tier 4 Input Type
Auxillary Fault (Shutdown) Auxillary Fault (Shutdown)
Auxillary Warning Auxillary Warning
Battery Charger Fault Battery Charger Fault
Breaker Closed Breaker Closed
Breaker Tripped/Open Breaker Tripped/Open
Fuel Leak Alarm Fuel Leak Alarm
High Fuel Level Switch Warning High Fuel Level Switch Warning
Idle Switch Idle Switch Digital Input
Low Fuel Level Switch Low Fuel Level Switch
Low Oil Level Low Oil Level Switch Warning
Remote Emergency Stop Remote Emergency Stop
Remote Reset Remote Reset
Reserved Factory Use Load Bank Fault
Reserved Factory Use Power Supply 1 Fault
Reserved Factory Use Power Supply 2 Fault
Remote Engine Start Remote Engine Start Two-Wire Input
Speed Bias Speed Bias Analog Voltage Input,
Scalable up to +/- 10 VDC
Voltage Bias Voltage Bias
* Only with remote-mounted electrically operated circuit breakers.
Figure 7 Standard Dedicated User Inputs
TP-7141 11/22 19
20 TP-7141 11/22
Section 3. Operation
Note:
Use the procedures in this document after the generator set has been installed according to the instructions in the generator set
Installation Manual.
Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult the battery manufacturer’s instructions regarding battery care and maintenance.
Coolant Level. Check the coolant level according to the cooling system maintenance information.
Note: Block Heater Damage.
The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block
heater. Run the engine until it is warm, and refill the radiator to purge the air from the system before energizing the block heater.
Diesel Exhaust Fluid (DEF) Tank, if equipped. Ensure that there is an adequate DEF supply; keep the DEF tank full. When filling, watch
that the DEF tank is not overfilled.
Drive Belts. Check the belt condition and tension of the radiator fan, water pump, and battery charging alternator belt(s) according to the
drive belt system maintenance information.
Enclosure Doors, if equipped. Check that the service access doors are closed and secured. Leaving the doors open can interfere with
the cooling air flow and create excessive noise. Check that the enclosure door to the load connection panel is closed and secured. Some
units have a micro switch safety feature that will trip (by shunt trip) the main line circuit breaker if the load connection panel is open.
Exhaust System. Check for exhaust leaks and blockages. Check the silencer and piping condition and check for tight exhaust system
connections.
• Inspect the exhaust system components (exhaust manifold, exhaust line, flexible exhaust, clamps, silencer, and outlet pipe) for
cracks, leaks, and corrosion.
• Check for corroded or broken metal parts and replace them as needed.
• Check for loose, corroded, or missing clamps and hangers. Tighten or replace the exhaust clamps and/or hangers as needed.
• Check that the exhaust outlet is unobstructed.
• Visually inspect for exhaust leaks (blowby). Check for carbon or soot residue on exhaust components. Carbon and soot residue
indicates an exhaust leak. Seal leaks as needed.
Fuel Level. Check the fuel level and keep the tank(s) full to ensure adequate fuel supply. (diesel models)
Lamp Test. Press and hold the lamp-test button for 1 second to verify all controller LEDs are operational.
Oil Level. Check the oil level. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or
debris on or near the generator set.
Radiator. Check that the radiator fins and air inlets/outlets are clean of leaves, insects, dirt, and other debris. Use compressed air to clear
the obstructed passages as needed.
Visual Inspection. Walk around the generator set and look for leaking fluids, loose or dangling wiring, and loose or missing hardware.
Repair as needed before starting the generator set. Repeat the visual inspection routinely while the unit is running.
TP-7141 11/22 21
3.2 Generator Set Operation
There are three primary modes of operation, selected by pressing the controller buttons.
Button Description
OFF/RESET Press the OFF/RESET button to stop the generator set immediately, with no engine cooldown.
The generator set remains off and will not respond to a remote start signal.
Press and HOLD the OFF/RESET button for 3 seconds to reset an active fault (shutdown). Be
sure to identify and correct the problem that caused the shutdown before clearing the fault.
AUTO Press AUTO to place the generator set into automatic (standby) mode. The generator set will
respond to remote start and remote stop signals.
RUN Press the RUN button to start the generator set. The generator set runs until the OFF/RESET or
AUTO button is pressed or until a fault condition causes the generator set to shut down.
Figure 9 Controller Button Operation
Notes:
• The alarm horn sounds and the Not-In-Auto Warning display appears whenever the generator set is not in the AUTO
mode.
• The transient start/stop function of the controller prevents accidental cranking of the rotating engine. The generator set
stops and recranks when the OFF/RESET button is momentarily pressed and then the RUN button is pressed.
• The controller provides up to 30 seconds of programmable cyclic cranking and up to 60 seconds rest with up to 6
cycles. The default setting is 15 seconds cranking and 15 seconds rest for 3 cycles. An authorized Kohler distributor or
dealer can make cyclic cranking adjustments using SiteTech™ software.
22 TP-7141 11/22
3.2.1.1 Starting and Stopping Functions, Parallel Operation
The modes of operation for a generator set that is part of a multi-unit paralleled system are shown below. Select the modes by
pressing the controller buttons as shown.
Button Description
OFF/RESET Press the OFF/RESET button to stop the generator set immediately, with no engine cooldown.
The generator set remains off and will not respond to a remote start signal.
Press and hold the OFF/RESET button for 3 seconds to reset an active fault (shutdown). Be sure
to identify and correct the problem that caused the shutdown before clearing the fault.
RUN Press the RUN button to start the generator set. No other generator sets in the system will start.
AUTO Press AUTO to place the generator set into automatic (standby) mode. The generator set will
respond to remote start and remote stop signals.
The generator set will start and run when a start signal is received via a remote start, local auto-
start, or communications-based start.
All generator sets in the system (connected by PGEN paralleling communications and in Standby
Mode by pressing AUTO) will start when any one of the generator sets receives a start signal.
However, any generator set in the system that is not in AUTO mode will not start.
If Generator Management is on, the generator set may shut down after a period of time.
When the start signal is removed, the generator set will shut down with the appropriate engine
cooldown.
AUTO-RUN Press AUTO and RUN together for a system start signal.
All generator sets in the system start and run, close to bus, synchronize, parallel, share load, etc.
Some generator sets may shut down after a period of time (indicated by Generator Management)
but they remain in Standby Mode ready to start and run if needed.
AUTO-OFF Press AUTO and OFF together to remove a system start signal, if AUTO-RUN is active.
All generator sets in the system open their breakers, enter engine cooldown, shut down, and enter
Standby Mode. Closing the remote start contacts has no effect. Generator sets in the system will
enter Standby Mode.
Note:
Pressing AUTO and OFF together stops the generator sets only if there are no other system start
signals present.
When the generator set is in AUTO mode, it can respond to a start signal. A start signal can include any of the following:
• A remote start signal via contacts 3 and 4 (closing a contact between 3 and 4 on terminal block TB -12), typically
received from an automatic transfer switch (ATS) or a remote panel. A closed contact across 3 and 4 takes precedence
over all other start signals. If the generator set is already running, it will keep running and the original source of that
start signal will be ignored.
• System Start (AUTO-START). Press AUTO and RUN simultaneously to send a start signal.
• Removal of start signal via contacts 3 and 4 (opening the contact between 3 and 4).
• System Stop (AUTO-OFF). Press AUTO and OFF simultaneously on any controller in the system to send a stop signal
to cancel the system start.
Note:
Pressing AUTO and OFF simultaneously has no effect if the system start is not active or if the system is receiving a
start signal from another source.
TP-7141 11/22 23
3.2.4 Engine Cooldown
The engine cooldown cycle runs the generator set with no load to allow hot engine components time to cool slowly before the
engine is stopped.
When the generator set is running in AUTO mode, an engine cooldown cycle begins when the remote start input is deactivated
or a stop signal is received.
The cooldown cycle runs until the cooldown temperature is reached or a predetermined amount of time expires. The cooldown
time and cooldown temperature are adjustable parameters. See the Engine Setup section for more information about the engine
cooldown settings.
Note:
No engine cooldown cycle occurs if the OFF button is pressed or if a fault occurs. The shutdown is immediate. If possible, ru n
the generator set without load for at least 5 minutes to ensure adequate engine cooldown.
NOTICE
Injector damage. Cutting power to the exhaust aftertreatment system can damage the injectors. Rewiring the emergency stop
voids the warranty. If power is cut to the exhaust aftertreatment system during operation or the cooling process, inspect injectors
for damage and replace if needed.
Note:
When the operator presses the OFF button or the emergency stop button, or a shutdown fault occurs, the generator set shuts
down immediately and does not enter low idle cooldown. Only the DEF injector cooldown will continue to function and protect
the injectors from damage.
Tier 4 generator sets (KD1250-4, KD2500-4, and KD3250-4) use low idle cooldown and DEF injector cooldown to prevent
damage to the DEF injectors. When running in AUTO, removal of the start/stop signal initiates a low idle cooldown. The generator
set controller automatically lowers the frequency to low idle during the low idle cooldown until exhaust temperatures reach 220˚C
(428˚F) or for 10 minutes of operation (whichever comes first). Injector cooldown occurs at the same time, and the DEF pump
continues to pump DEF through the injectors even after the engine stops.
Low idle cooldown is the preferred shutdown option for tier 4 generator sets and only occurs when the generator set is running
in AUTO. If the operator starts the generator set by pressing the RUN button, the preferred shut-down method is to switch to
AUTO to allow a low idle cooldown.
In addition to a low idle cooldown, the EATS system utilizes a DEF injector cooldown where the DEF pump continues to pump
DEF through the injectors as the engine aftertreatment system (EATS) cools. The EATS initiates a DEF injector cooldown when
the operator presses the OFF button or the emergency stop button, the generator set receives a remote stop signal, or a
shutdown fault occurs.
24 TP-7141 11/22
3.2.5 Emergency Stop
Note:
Use the emergency stop switch(es) for emergency shutdowns only. Use the generator set OFF/RESET button for normal
shutdowns.
The emergency stop switch shuts down the generator set immediately. The controller fault LED lights and the unit shuts down
without running the engine cooldown cycle.
Use the following procedure to reset the generator set after shutdown by a local or remote emergency stop switch. Refer to the
Controller Resetting procedure to restart the generator set following a fault shutdown.
3. Press and hold the generator set OFF/RESET button for 3 seconds.
4. After resetting all faults using the controller reset procedure, press the generator set RUN and/or AUTO button to restart
the generator set. The generator set will not crank until the reset procedure is completed.
NOTICE
Injector damage. Cutting power to the exhaust aftertreatment system can damage the injectors. Rewiring the emergency stop
voids the warranty. If power is cut to the exhaust aftertreatment system during operation or the cooling process, inspect injectors
for damage and replace if needed.
When the emergency stop button is pressed, a tier 4 generator set immediately shuts down and the EATS initiates a DEF injector
cooldown where DEF is pumped through the injectors.
The emergency stop switch is factory wired on tier 4 generator sets to keep the EATS powered when the emergency stop button
is pressed. The emergency stop switch will only remove power from the base generator set. Rewiring of the emergency stop
switch will affect the warranty of EATS components. If rewiring the emergency stop switch is necessary, c ontact an authorized
Kohler distributor or dealer.
Note:
Pressing the emergency stop switch cuts power to the heating components of the EATS. If power is not returned, DEF in the
DEF lines, DEF tank, and DEF components can freeze, blocking the DEF flow and causing an inducement (reduction in engine
torque).
TP-7141 11/22 25
3.2.5.2 EATS Electrical Disconnect (Tier 4)
The EATS electrical disconnect is located on the lower electrical box. The EATS electrical disconnect is a manually operated
switch that functions as a stop switch for the EATS. When the EATS electrical disconnect is turned off, power is cut to the FDS
pump and the DEF line heaters.
IMPORTANT! The EATS electrical disconnect should typically be in the ON position even when the generator set is not running.
If needed, the EATS electrical disconnect should only be turned off when the EATS active light is off or in an emergency situation.
If the EATS electrical disconnect is ever turned OFF while the EATS active light is still on, then damage to the DEF injectors is
likely. If the EATS electrical disconnect is turned off, the ECU and the controller report a fault. If power is not returned to the DEF
line heaters in cold weather conditions, DEF lines can freeze and cause blockage.
Lower
electrical box
OFF
EATS electrical
disconnect
ON
Cold weather operation should be addressed in areas where the ambient temperatures fall below freezing, 0°C (32°F). The
following items are recommended for cold weather starting and/or operation when the unit is located in an enclosure or unheated
structure. Have a licensed electrician install 120 VAC, 15 amp outlets as needed if not already in the immediate area.
Refer to the engine operation manual regarding engine oil viscosity, fuel composition, and coolant mixture recommendations.
• The engine block heater is generally recommended for most units when operated below 0°C (32°F) and required as
part of NFPA 110. Refer to the generator set specification sheet for temperature recommendations in available opti ons.
• A battery heater is generally recommended for most units when operated below 0°C (32°F). Refer to the respective
specification sheet for model availability.
• An alternator heater to prevent moisture and frost buildup is available for some generator sets.
• Heater tape is recommended when the generator set is equipped with a closed crankcase ventilation system and
operated at or below 50% of rated load. Wrap the UL/CSA compliant heater tape around the crankcase
canister/breather system hose that runs from the crankcase to the air intake and use cable ties as needed to secure
the heater tape. If the heater tape is within 152 mm (6 in.) of the exhaust system, use thermal insulation material to
protect the heater tape.
Note:
Tier 4 generator sets (KD1250-4, KD2500-4, KD3250-4) are equipped with DEF line heaters, DEF tank heaters, and DEF
component heaters. These EATS heating components are standard on tier 4 generator sets. To prevent freezing and blocking
of the DEF flow, power should always be supplied to these EATS heaters. Ensure that the EATS electrical disconnect switch is
closed (in the ON position), the emergency stop is released, and that power is provided through the AC power supplies. Refer
to the Engine Aftertreatment System installation and Application manual for electrical requirements and installation details. Refer
to the following subsection on EATS electrical disconnect in this manual for operation instructions.
26 TP-7141 11/22
3.4 Exercising the Generator Set
Operate the generator set under load periodically. Refer to the engine operation manual for the exercise intervals and load
recommendations. Perform the exercise in the presence of an operator when the generator set does not have an automatic
transfer switch with an exercise option.
The operator should perform all of the prestart checks before starting the manual exercise procedure. Start the generator set
according to the starting procedure. While the generator set is operating, listen for a smooth-running engine and visually inspect
generator set for fluid or exhaust leaks.
The generator set controller does not provide weekly scheduled exercise periods. If the system is equipped with an automatic
transfer switch (ATS), refer to the ATS literature for information about scheduled exercise periods.
Note:
Tier 4 generator sets (KD1250-4, KD2500-4, KD3250-4) require a minimum exhaust temperature to prevent hydrocarbon buildup
in the catalyst. Tier 4 generator sets use a load bank or the building design to maintain a minimum load. For operation and
requirements, refer to the previous subsection on EATS Electrical Disconnect and the Exhaust Aftertreatment System Installation
and Application Manual.
Tier 4 generator sets (KD1250-4, KD2500-4, KD3250-4) require a minimum exhaust temperature to prevent hydrocarbon buildup
on the SCR. To control exhaust temperatures, a minimum load is maintained either through a load bank or the building design.
See the Exhaust Aftertreatment System Installation and Application Manual listed under Related Literature.
• When the hydrocarbon (HC) level reaches the specified limit (default setting is 25%), the APM603 issues a high
hydrocarbon warning that the load needs to increase in order to reduce hydrocarbon buildup.
• At 50% the APM603 will report a critically high warning and command the load bank to turn on. When the APM603
commands the load bank to turn on, the load bank has 2 minutes to be connected to the generator set.
o If after 2 minutes the APM603 does not detect the load bank size as the minimum load, then the generator set will
issue a Load Bank Malfunction Warning.
o If applying the load bank exceeds 90% of the generator set the output rating, the APM603 will not command the
load bank to turn on.
• In paralleling applications, the APM603 will either bring another generator set on line and remove the generator set that
has high hydrocarbon levels off line, or apply the load bank depending on how many generator sets are currently online
and how many generator sets are offline in standby.
o In APM603 paralleling applications, the load bank must be applied to the generator set side of the motorized
breaker.
o See Paralleling section in this manual for addition information on load bank operation in paralleling applications.
• If switchgear is used to manage the hydrocarbon buildup, the switchgear system must keep the hydrocarbon below the
trip points set in the APM603.
TP-7141 11/22 27
3.6 Warnings and Faults
Yellow and red LEDs above the controller’s touchscreen indicate warnings and faults.
Inhibit time: This time delay prevents the fault from triggering immediately when the engine starts. The inhibit time allows the
engine to come up to speed and stabilize before triggering a fault. For example, the low oil pressure fault event typically has an
inhibit time of 10 seconds to allow oil pressure in the engine to build up.
Time Delay. This time delay prevents a fault from triggering immediately when a condition is first detected. This delay prevents
nuisance warnings or shutdowns caused by momentary changes in the signal, which could be false signals or electrical noise.
For example, the overvoltage fault event typically has a time delay of 30 seconds. The overvoltage condition must be detected
for 30 seconds before the fault is triggered.
3.6.1 Yellow System Warning LED and Fault Messages
The yellow WARNING LED turns on and the alarm horn sounds to indicate a warning but does not shut down the generator set.
See the following subsection, Notifications (Bell Icon), for a list of fault and warning events and messages.
Press the Alarm Silence button to silence the alarm horn at the operator’s discretion. If the controller is set up for an NFPA 110
application, press the AUTO button before silencing the alarm horn.
Warnings are automatically cleared from the controller when the condition is corrected.
When a system warning continues, it may lead to a fault and cause a system shutdown.
3.6.2 Red System Fault Shutdown LED and Fault Messages
When a fault condition is detected, the red system FAULT LED turns on, the alarm horn sounds, and the unit shuts down. See
the following subsection, Notifications (Bell Icon), for a list of fault shutdown messages.
Use the Alarm Silence button to silence the alarm horn at the operator’s discretion. If the controller is setup for an NFPA 110
application, press the AUTO button before silencing the alarm horn.
Refer to the subsection Resetting the Controller for information to reset a system shutdown.
3.6.3 Fault, Notice, and Status Displays
New warning or shutdown messages appear in a banner across the top of the screen. See Figure 11. Touch ACKNOWLEDGE
ALL to close the banner. Touch VIEW ACTIVE ALERTS or the Bell icon to see a list of all active faults.
Warnings and shutdowns appear on the Active Alerts screen and become part of the event log. The Event Log also includes
status messages.
• Shutdown messages are written in red and include a red symbol with an X.
• Warning messages are yellow and include a yellow triangle with an ! symbol.
28 TP-7141 11/22
3.6.4 Notifications (Bell icon)
The bell icon provides quick access to the Event Log. If the bell appears straight up and down, there are no active warnings or
faults. If the bell is “ringing,” indicated by the bell at an angle with waves, there is at least one active warning or fault . The
breadcrumb bar at the top of the page also changes color if there are active warnings or faults. If there are no active warn ings
or faults, the area is gray. If a warning is active, it is yellow. If a fault is active, it is red.
Touch the Bell icon to review active alerts and the event log. Event details lists the name, severity, and time and date for the
event. Touch View Snapshot to see data captured 7.5 seconds before and after the event. The items displayed in the Snapshot
are factory selected. For example, in Figure 13 the generator power is displayed for each warning and fault.
When a fault is indicated, be sure to identify and correct the cause of the fault before resetting the controller. Contact an
authorized Kohler distributor or dealer for service, if necessary.
When the fault condition has been corrected, press and hold the OFF/RESET button for 3 seconds to clear the fault from the
controller. If the fault occurs again, contact an authorized Kohler distributor or dealer for service. Do not start the generator set
until the condition has been corrected.
TP-7141 11/22 29
Figure 13 Event Details and Snapshot
Event Log:
This menu allows the user to review up to 10,000 entries of generator set system events including shutdowns, warnings, notices,
and status events with date and time stamp.
A message is sent each time there is a change in a monitored engine condition (i.e. fault becomes active, fault is cleared). Upon
broadcast of this message, the controller will request another message that contains the following information for each fault:
• SPN (Suspect Parameter Number) is a 3-to-5 digit code that represents an engine component. Refer to the engine Operation
Manual for a list of SPN codes.
• FMI (Failure Mode Indicator) is a two-digit code that represents the type of fault that occurred (i.e. short circuit, value is
high).
For generator events, see the Event Configuration section. For a list of engine events and FMI codes, see the Engine Data
Appendix.
3.6.5 EATS Inducement Notifications (Tier 4 Generator Sets)
For tier 4 generator sets (KD1250-4, KD2500-4, KD3250-4), engine aftertreatment system (EATS) warnings and shutdown faults,
when active, appear at the top of the page. If the icons are not visible, there are no active DEF warnings or faults. These icons
indicate low DEF fluid, poor DEF quality, poor SCR conversion, or component failure. If action is not taken, a reduction in engine
torque occurs. Orange icons indicate warnings, and red icons indicate shutdown faults. See Figure 14. For details about system
inducements, refer to the Engine Aftertreatment System Installation and Application manual listed under Related Literature.
Engine emission
system malfunction
indicator
30 TP-7141 11/22
3.7 Resetting the Controller (Following System Shutdown)
Use the following procedure to restart the generator set after a system shutdown. This procedure includes the resetting of the
optional remote annunciator.
Refer to the Emergency Stop Section to reset the generator set after an emergency stop.
1. Disconnect the generator set load using the line circuit breaker or automatic transfer switch.
2. Correct the cause of the fault shutdown or warning. See the Safety Precautions and Instructions section of this manual
before proceeding.
3. Reset the fault by pressing and holding the OFF/RESET button for 3 seconds.
5. When equipped, the remote annunciator alarm horn sounds. Press the ALARM SILENCE/LAMP TEST button to stop
the alarm horn. The alarm silenced LED turns on if the alarm is silenced.
6. Allow the generator set to run long enough to verify that the fault condition has been corrected.
7. Press the generator set OFF/RESET button to stop the generator set.
9. Silence the controller alarm horn by pressing the ALARM SILENCE button.
10. Reconnect the generator set load via the line circuit breaker or automatic transfer switch.
11. When equipped, the remote annunciator alarm horn sounds. Press the ALARM SILENCE/LAMP TEST button to stop
the alarm horn. The alarm silence LED turns on if the alarm is silenced.
• Display Brightness
Adjusts the brightness of the controller’s touchscreen display. Touch the sun icons at either end of the bar to increase
or decrease the brightness of the display.
• LED Brightness
Adjusts the brightness of the Warning and Fault LEDs above the display. Touch the sun icons at either end of the bar
to increase or decrease the brightness of the LEDs.
• Date/Time
Set the date, time, and time zone at the controller’s location. The date and time are displayed on the Home screens
and are used in the event log and for data logging.
• Language.
For future development. At this time, English is the only available option.
Controls the session time for access levels above the user level. The access level returns to the lowest (user) level
after the session timeout to prevent unauthorized access after an operator or service technician has finished working.
• Access Level
This is where an operator or technician can log into the controller using an Operator or Technician password. The
Operator and Technician level passwords allow access to view and change settings that are not available at the default
user level. See the Access Levels Section for more information.
TP-7141 11/22 31
Figure 15 Controller Settings and Access Levels
32 TP-7141 11/22
3.9 Screen Shots
It is possible to save screen shots showing the controller display. Screen shots showing the controller display can be saved to
a flash drive. The screens shots are saved as .png files, which can be viewed using a photo viewer on your PC.
Refer to the Controller Features Section for the locations of the USB port and the Alarm Silence/Lamp Test bu tton on the
controller, if necessary.
2. Check for the flash drive symbol near the top of the screen, which shows that the controller recogniz es the flash drive.
3. Navigate to the desired screen and press the Alarm Silence/Lamp Test button once.
4. Wait at least 5 seconds to allow the png file to be saved to the flash drive. If the flash drive has an LED indicator, wait
for the LED to stop flickering.
5. If multiple screen shots are needed, repeat steps 2 and 3 for each screen.
6. Remove the flash drive from the controller and insert it into a USB port on your PC. Open the files to verify that the
screen shots were saved correctly.
TP-7141 11/22 33
3.10 Menu Navigation
The APM603 controller provides menus and submenus that display controller settings, generator set status, and paralleling
information. The following list shows the locations of the menus and submenus on the controller.
• Metering
o Favorites
o Electrical
• Generator
• Inputs
• Outputs
• Battery Charger (N/A for KD models)
o Engine
o Op Records
o Load Management
• Overview
• Status
o System
o Load
• Setup Details
• Setup
o Electrical
• Generator
• Battery Charger (N/A for KD models)
• Paralleling
o Engine
o Communications
o Event Config
o Genset Info
• Data Log
• Paralleling (only appears if paralleling screens are enabled under Setup>Electrical>Paralleling)
o Metering
• Overview
• Status
• Details GEN 1-4
• Details GEN 5-8
• PGEN
o Setup
• PGEN
• Protect Relay
o Gen Management
• Overview
• Status
o System
o Generator
• Setup Details
34 TP-7141 11/22
Section 4. Metering Menu and Screens
The Favorites screen provides another way to display your choice of data. Separate favorites screens can be set up for each
access level: user, operator, and technician.
The metering screens are designed for viewing only. Settings cannot be changed through the metering screens.
• Favorites
• Engine
• Operation records
• Load Management
TP-7141 11/22 35
4.1.1 Home
At startup, the controller displays the home screen shown in Figure 18. Two home screens showing up to 16 different generator
set values can be displayed. Touch the square buttons at the bottom of the screen to move between the two home screen
displays.
36 TP-7141 11/22
The parameters shown below are displayed on the home screens by default. Follow the instructions in the next section to
change the parameters displayed. Up to 16 system parameters can be selected for display on the two Home screens.
Default Parameters
Average Voltage L to L
Frequency
Battery Voltage
Oil Pressure
Total Real Power
Speed
Coolant Temperature
Fuel Level
Voltage L1-N
Voltage L2-N
Voltage L3-N
Total Power Factor
Current L1
Current L2
Current L3
Runtime Hours
Figure 19 Default Parameters Shown on the Home Screens
To add a gauge, there must be at least one empty space available on the screen. It may be necessary to remove a gauge to
create an empty space. When any gauge is removed, the remaining gauges shift to fill the vacated space, and the new open
space will appear at the end of the second screen. To change the order of the gauges, it is necessary to remove the gauges
using the trash can icon and then replace them in the desired order.
• Electrical – Generator
• Electrical – Inputs
• Electrical – Outputs
• Electrical – Battery Charger 1 (no battery charger data is available for KD models)
• Electrical – Battery Charger 2 (no battery charger data is available for KD models)
• Engine
• Operation Records
• Load Management
• Paralleling
Full gauge, half gauge, vertical gauge, or tile (text only) styles are available.
TP-7141 11/22 37
Procedure to Remove Gauges from the Home Screens
The numbers below correspond to the numbered steps in the Procedure to Remove Gauges from the Home Screen.
1 3
2 4
38 TP-7141 11/22
Procedure to Add New Gauges to the Home Screen
The numbers below correspond to the numbered steps in the Procedure to Add New Gauges to the Home Screen.
1 4
2 5
3 6
TP-7141 11/22 39
4.1.3 Favorites
The Favorites screen allows the user, operator, and technician to view selected parameters from different categories on one
screen.
The numbers below correspond to the numbered steps in the Procedure to View Favorites.
1 3
• Electrical – Generator
• Electrical – Inputs
• Electrical – Outputs
• Electrical – Battery Charger 1 (no battery charger data is available for KD models)
• Electrical – Battery Charger 2 (no battery charger data is available for KD models)
• Engine
• Operation Records
• Load Management
• Paralleling
Note:
The parameters are listed on the Favorites screen in the order selected.
40 TP-7141 11/22
Procedure to Select Favorites
First, go to the Favorites screen as described in Figure 22.
1. Touch the Star icon in the upper right corner of the screen.
2. Touch the category.
3. Touch the stars for one or more parameters to be included in the Favorites display. The selected stars turn solid
white.
4. Touch the left arrow symbol to close the selection box. Repeat steps 2 and 3 for other categories.
5. Observe that the selected parameters are now displayed in the order they were selected.
The numbers below correspond to the numbered steps in the Procedure to Select Favorites.
1 4
2 5
TP-7141 11/22 41
4.2 Electrical
4.2.1 Metering Screens, Electrical, Generator
The Generator Metering screens display generator set electrical information such as output voltage, frequency, current, and
other electrical data listed in Figure 25. The metering screens display information only. Parameter settings cannot be changed
from the metering screens.
The numbers below correspond to the numbered steps in the Procedure to View Generator Electrical Metering Screens.
1 3
2 4
42 TP-7141 11/22
The generator metering screen displays the values shown below.
Parameter Units
Frequency Hz
Average Voltage L-L V
Average Voltage L-N V
Three Phase Average Current kA
Total Real Power kW
Total Reactive Power kVAR
Total Apparent Power kVA
Total Power Factor
Battery Voltage * V
Controller RTC Battery Voltage V
Voltage L1-L2 V
Voltage L2-L3 V
Voltage L3-L1 V
Voltage L1-N V
Voltage L2-N V
Voltage L3-N V
Current L1 A or kA
Current L2 A or kA
Current L3 A or kA
Real Power L1 kW
Real Power L2 kW
Real Power L3 kW
Reactive Power L1 kVAR
Reactive Power L2 kVAR
Reactive Power L3 kVAR
Apparent Power L1 kVA
Apparent Power L2 kVA
Apparent Power L3 kVA
Voltage Phase Angle L1-L2 Degrees
Voltage Phase Angle L1-L3 Degrees
* On units with redundant starters, battery voltage is
displayed for two batteries.
Figure 25 Generator Metering Data
TP-7141 11/22 43
4.2.2 Input Metering
Input status is displayed on the Metering, Electrical, Inputs screen.
The standard, dedicated inputs are listed in the previous section Inputs and Outputs. Optional input/output modules are avail able.
I/O Module 0 inputs and outputs are factory set. I/O Module 1 outputs are also factory set. I/O Module 1 inputs and I/O Module
2 inputs and outputs are configurable.
A personal computer and Kohler SiteTech™ software are required to assign input functions to the inputs on the I/O modules.
SiteTech is available to Kohler authorized distributors and dealers.
The numbers below correspond to the numbered steps in the Procedure to View Input and Output Status.
1 3
2 4
44 TP-7141 11/22
4.2.3 Output Metering
The Electrical Metering screen for outputs displays the status of the outputs.
The standard, dedicated outputs are listed in Section 2. Optional I/O Modules are available.
A personal computer and Kohler SiteTech™ software are required to assign output functions to the programmable outputs on
the I/O module. SiteTech is available to Kohler authorized distributors and dealers.
The numbers below correspond to the numbered steps in the Procedure to View Output Status.
1 3
2 4
Output Units/Value
Run/Generator Running On/Off
BCA Excitation On/Off
Horn On/Off
Common Failure/Fault On/Off
Common Warning On/Off
High Coolant Temperature On/Off
Close Breaker On/Off
Trip Breaker On/Off
Alternator Excitation %
I/O Module 0 Digital Outputs0-7 On/Off
I/O Module 1 Digital Outputs0-7 On/Off
I/O Module 2 Digital Outputs0-7 On/Off
TP-7141 11/22 45
4.2.4 Battery Charger
The electrical metering screens for battery chargers are not applicable for model KD generator sets.
4.3 Engine
The Engine Metering screen displays the engine data shown in Figure 31.
1. In the navigation panel on the left side of the screen, touch Metering or the gauge symbol.
The numbers below correspond to the numbered steps in the Procedure to View the Engine Metering Screen.
1 3
46 TP-7141 11/22
Tier 2 Generator Models Tier 4 Generator Models
Item Units Item Units
Engine Speed RPM Frequency Hz
Oil Pressure PSI Coolant Temp °F or °C
Oil Temperature °F or °C Oil Pressure PSI or kPa
Coolant Temperature °F or °C Engine Speed RPM
Crankcase Pressure PSI/kPa DEF Level %
Intake Manifold Pressure PSI Fuel Level %
Intake Manifold Temperature °F or °C
Intercooler Coolant Temperature
°F or °C
(K175 engines only)
Ambient Temperature °F or °C
ECU Runtime Hours Hours
Fuel Pressure PSI/kPa
Common Rail Fuel Pressure PSI/kPa
Fuel Temperature °F or °C
Fuel Consumption Rate Gallons/hour
4.3.1 Overview
The Overview Metering screen displays the overview data shown in Figure 33.
Note:
This menu is only available on Tier 4 generator sets.
1. In the navigation panel on the left side of the screen, touch Metering or the gauge symbol.
3. Touch Overview.
The numbers below correspond to the numbered steps in the Procedure to View the Engine Overview Metering Screen.
1 3
2 4
TP-7141 11/22 47
Tier 4 Generator Sets
Item Units
Engine Speed RPM
Oil Pressure PSI or kPa
Coolant Temp °F or °C
Fuel Level %
Run Time Hours Hours
SCR System State ScrSytemStates
DEF Level %
SCR HC Level %
SCR Temperature °F or °C
Coolant Level
Aftercooler Coolant Level
ECU Battery Voltage V
ECU Keyswitch Voltage V
SCR Operator Inducement
Severity Level
Engine Derate Is Active Yes/No
NOx Control Torque Limit %
Engine Operating State EngOperatingStates
48 TP-7141 11/22
4.3.2 Fuel
The Fuel Metering screen displays the fuel data shown in Figure 35.
Note:
This menu is only available on Tier 4 generator sets.
1. In the navigation panel on the left side of the screen, touch Metering or the gauge symbol.
3. Touch Fuel.
The numbers below correspond to the numbered steps in the Procedure to View the Engine Fuel Metering Screen.
1 3
2 4
TP-7141 11/22 49
4.3.3 Temperature
The Temperature Metering screen displays the Temperature data shown in Figure 37.
Note:
This menu is only available on Tier 4 generator sets.
1. In the navigation panel on the left side of the screen, touch Metering or the gauge symbol.
3. Touch Temperature.
The numbers below correspond to the numbered steps in the Procedure to View the Temperature Metering Screen.
1 3
2 4
50 TP-7141 11/22
Item Unit
Coolant Temperature °F or °C
Oil Temperature °F or °C
SCR Temperature °F or °C
DEF Temperature °F or °C
Fuel Temperature °F or °C
Intake Manifold Temperature °F or °C
Ambient Temperature °F or °C
Auxiliary Coolant Temperatue °F or °C
ECU Temperature °F or °C
Turbo 1 Turbine Intake Temperature °F or °C
Turbo 2 Turbine Intake Temperature °F or °C
Turbo 1 Compressor Intake Temperature °F or °C
Exhaust Gas Port 1 Temperature °F or °C
Exhaust Gas Port 2 Temperature °F or °C
Exhaust Gas Port 3 Temperature °F or °C
Exhaust Gas Port 4 Temperature °F or °C
Exhaust Gas Port 5 Temperature °F or °C
Exhaust Gas Port 6 Temperature °F or °C
Exhaust Gas Port 7 Temperature °F or °C
Exhaust Gas Port 8 Temperature °F or °C
Exhaust Gas Port 9 Temperature °F or °C
Exhaust Gas Port 10 Temperature °F or °C
Exhaust Gas Port 11 Temperature °F or °C
Exhaust Gas Port 12 Temperature °F or °C
Exhaust Gas Port 13 Temperature °F or °C
Exhaust Gas Port 14 Temperature °F or °C
Exhaust Gas Port 15 Temperature °F or °C
Exhaust Gas Port 16 Temperature °F or °C
TP-7141 11/22 51
4.3.4 Pressure
The Pressure Metering screen displays the pressure data shown in.
Note:
This menu is only available on Tier 4 generator sets.
1. In the navigation panel on the left side of the screen, touch Metering or the gauge symbol.
3. Touch Pressure.
The numbers below correspond to the numbered steps in the Procedure to View the Pressure Metering Screen.
1 3
2 4
52 TP-7141 11/22
4.3.5 Aftertreatment
The Aftertreatment Metering screen displays the aftertreatment data shown in Figure 41.
Note:
This menu is only available on Tier 4 generator sets.
1. In the navigation panel on the left side of the screen, touch Metering or the gauge symbol.
3. Touch Aftertreatment.
The numbers below correspond to the numbered steps in the Procedure to View the Engine Aftertreatment Metering
Screen.
1 3
2 4
TP-7141 11/22 53
Item Units
SCR System State ScrSytemStates
DEF Level %
DEF Temperature °F or °C
DEF Concentration %
DEF Consumption L/Hr
SCR HC Level %
SCR Temperature °F or °C
DEF Doser Absolute Pressure PSI or kPa
DEF Doser Pump Speed RPM
DEF Doser Pump Command %
Engine Derate Is Active Yes/No
NOx Control Torque Limit %
SCR Operator Inducement Severity Level
SCR Defrost Complete Yes/No
DEF Defrost Complete Yes/No
DEF Level Inducement State AftertreatmentInducementState
System Failure Inducement State AftertreatmentInducementState
DEF Level Time To Next Inducement Min
System Failure Time To Next Inducement Min
SCR Exhaust Gas Mass Flow kg/Hr
DEF Line Heater 1 On/Off
DEF Line Heater 2 On/Off
Aftertreatment 1 Intake NOx ppm
Aftertreatment 1 Outlet NOx ppm
Aftertreatment 2 Outlet NOx ppm
Aftertreatment 3 Outlet NOx ppm
Aftertreatment 1 Outlet NH3 ppm
Aftertreatment 2 Outlet NH3 ppm
Aftertreatment 3 Outlet NH3 ppm
Figure 41 Aftertreatment Metering Data
54 TP-7141 11/22
4.4 Operation Records
The Op Records screen displays generator set operation records such as engine run time, last start date, and other information
shown in Figure 43.
To reset the maintenance records after performing scheduled oil changes and other maintenance tasks, log in as Technician.
The password is required.
The numbers below correspond to the numbered steps in the Procedure to View Operation Records.
1 3
TP-7141 11/22 55
Parameter Units
Total Run Time Hours Hours
Total Loaded Hours Hours
Total Unloaded Hours Hours
Total kW Hours kWh
Controller Hours Hours
Controller Run Time Hours Hours
ECU Run Time Hours Hours
Number of Starts
Number of Crank Attempts
Last Crank Duration Seconds
Last Start Run Time Duration Hours
Last Start Time of Day
Last Start Date (Day)
Last Start Date (Month)
Last Start Date (Year)
Last Stop Time of Day
Last Stop Date (Day)
Last Stop Date (Month)
Last Stop Date (Year)
Total Run Time Since Maintenance Hours
Loaded Hours Since Maintenance Hours
Unloaded Hours Since Maintenance Hours
kW Hours Since Maintenance kWh
Reset Maintenance Records * Yes/No *
* The Technician password is required to reset maintenance records.
56 TP-7141 11/22
4.5 Load Management
Load management allows a generator set to support load which may occasionally exceed the rated capacity of the generator
set.
Note:
Life safety and critical loads should never be connected to a device that is managed as a priority through load management.
Load management should only be used on loads that can be turned on and off as required to allo w the generator system to
operate reliably for life safety and critical loads that are always connected.
In single-generator set applications, load management may shed unimportant but highly demanding loads when the generator
set is overloaded, preventing a power outage caused by the generator set going offline.
In paralleling systems, load management permits the bus to stay at rated voltage and frequency while an additional generator
set is synchronizing to it. It ensures the total load on the bus does not exceed the total capacity of the generators online at a
given moment. Load management may shed lower priority loads in the event that a generator fails or the system is waiting for a
generator to synchronize and close to the bus.
The load management function in the generator set controller supports up to 16 load control priorities. In a single -generator set
application, the system will be limited to 16 (8 for each D8IOM) load control priorities for KD models. In paralleling systems, the
full 16 load control priorities can be used. These priorities generate internal notices for the add and shed conditions. The internal
notices are generated any time a load is add or shed, but they will only operate a load control relay if they are co nfigured to a
digital output.
• For KD models, one or two digital input/output modules (DIOMs) are required, providing up to 8 or 16 outputs (4 per
original DIOM or 8 per updated D8IOM) to be accessed and configured to control up to 16 loads (each load priority can
interrupt several devices) from a single generator.
• For non-KD Models, the optional 4 input / 15 output relay module is required, providing up to 14 RDO outputs to be
accessed and configured to control up to 14 loads (each load priority can interrupt several devices) from a single
generator.
In paralleling applications, up to 16 load priorities can be accessed and the load priorities can be divided among all of the
generator sets. For instance, Generator #1 can support Load Priorities 1 and 4, Generator #2 can support Priorities 2 and 5 and
Generator #3 can support Priorities 3 and 6. This configuration requires the optional relay module on each generator and perm its
partial load control functionality even if one controller is powered down or fails (redundancy).
Load Priority 1 is shed last and added first. The priorities are added in increasing sequence and shed in decreasing sequence.
All load priorities are immediately shed when load control is initiated. Load control is initiated when the system receives a start
signal (a system start, a remote start, or a start by communication). In a paralleling application, the controller can receiv e a start
signal from any generator set which is connected to the PGEN communication network. Pressing RUN on the controller will not
cause the loads to shed.
All loads are added immediately when load control is de-activated. Load control is de-activated when the start signal is removed.
Load management adds loads based on the capacity of the system—loads will add more quickly if the available capacity is
higher.
Load management sheds loads based on the degree of overload of the system—loads will shed more quickly as the degree of
the system overload increases.
Note:
If paralleling and using generator management, the Generator Management Start Percentage setting should be significantly
lower than the Overload Shed Threshold so that additional generator sets will come online before a load is shed. Go to the Gen
Management group in SiteTech to adjust the Generator Management Start Percentage setting. The Overload Shed Threshold
can be adjusted at Metering>Load Manage>Status>System. See the Load Management Setup Section for more information.
An under frequency event or overload event will also shed load. If a load priority is shed due to one of these events, the load
management system can be configured to leave the priorities as shed until a related event occurs to allow them to be add back .
This prevents the system from entering a shed and add cycle. For example, if the load is shed due to overload and removing
the load removes the overload condition, if the load is added back it could cause the overload condition again and shed the l oad
again.
TP-7141 11/22 57
The load control will shed subsequent loads more quickly if shedding a load did not remove the overload or underfrequency
condition.
In a single-generator set application the load management logic uses the generator metering.
In a paralleling application the load management logic uses the bus metering. The priorities are set as a system so the load
management settings are identical in each controller and each controller will shed and add a given load priority at the same time.
In a paralleling application where Generator Management is used, some generator sets may be shut down (turned Off) by the
Generator Management. Even if the generator set is Off, it will manage load priorities as part of the system, performing a lo ad
add and load shed as needed. This may seem contrary to intuition, but the generator sets are acting as a system. If voltage and
frequency of the paralleling bus are adequate, and Load Add accumulators are met, the loads will be enabled, even if a partic ular
generator set is shut down by the Generator Management.
58 TP-7141 11/22
4.5.1 Metering, Load Management Overview Screen
The overview provides a simple graphical view of the load management system.
The numbers below correspond to the numbered steps in the Procedure to View Load Management Overview.
1 3
2 4
Note:
Custom names for loads can be set up through SiteTechTM. Contact a Kohler authorized distributor or dealer.
If a load is in the process of being add or shed, the load will have an indication of % until that occurs. It is shown as a p ercentage
since the time varies based on the capacity available. When the % reached 100%, the load management will initiate the add or
shed.
The key at the bottom of the display shows the current load as well as the total online capacity and available capacity. If a
generator is offline (either due to a shutdown via Generator Management or a fault or the generator is not commun icating via
PGEN), unavailable capacity will be shown as well.
Total Load is the value of all the loads on the system. This includes loads that are not assigned a priority and are always
connected.
Online Capacity is the capability of the system with all the generators that are currently online. For a single-generator set
application, this is the total capacity of the generator. For a paralleling system, this is the sum of capacity for all online generators.
Available Capacity indicates the difference between the Online Capacity and the Total Load. It is remaining capacity available
for additional loads to be potentially added.
TP-7141 11/22 59
4.5.2 Metering, Load Management, Status
The status screens provide a listing of the load management metered values as well as key settings for reference.
4.5.2.1 Status, System
The Load Management System Status provides indication of key settings and values related to the overall operation of the load
management system.
The numbers below correspond to the numbered steps in the Procedure to View Load Management System Status.
1 3
2 4
60 TP-7141 11/22
Parameter Units
Load Management Enabled Yes/No
Total Load kW
Online Capacity kW
Available Capacity kW
Total Bus Capacity kW
Generators Online
Generators Failed
Next Priority to Shed
Time Based Load Add Enabled Yes/No
Time Based Add Time Seconds
Time Based Load Add Timer Active Yes/No
kW Capacity Add Threshold %
kW Capacity Add Accumulator %
Require Reset After kW Shed Yes/No
Overload Shed Threshold %
Overload Shed Accumulator %
Under Frequency Shed Threshold %
Under Frequency Shed Accumulator %
Require Reset After UF Shed Yes/No
Under Frequency Inhibit Enabled Yes/No
Under Frequency Inhibit Time Seconds
Under Frequency Inhibit Time Remaining Seconds
New Gen Online As Reset Yes/No
Stage Loads After Utility Return Yes/No
Figure 46 Load Management System Status Parameters
Load Management Enabled indicates a Yes if the load management system is being used on the generator or paralleling
system. If No, load management is not being used and will not drive any of the outputs.
Total Load indicates the value of all the loads on the system. This includes loads that are not assigned a priority and are always
connected.
Online Capacity indicates the capability of the system with all the generators that are currently online. For a single-generator
set application, this is the total capacity of the generator. For a paralleling system, this is the sum of capacity for all online
generators.
Available Capacity indicates the difference between the Online Capacity and the Total Load. It is remaining capacity available
for additional loads to be potentially added.
Generators Online indicates the number of generators online. For a single-generator set application, this will be 1. For
paralleling systems, it will be the total number of generators that are on the closed to the bus.
Generators Failed indicates in a paralleling system if any of the generators on PGEN are in a shutdown (fault) condition. Note
that as long as the controller is still communicating on PGEN, load management can control the outputs on the controller for a
generator this is in a shutdown condition. For a single-generator set application this will be 0.
Next Priority to Shed indicates the priority number of the next load that will be shed should the system enter a condition that
requires a load shed.
TP-7141 11/22 61
Time Based Load Add Enabled indicates if the Time Based Load Add functionality is enabled. This function will add the loads
in the priority order based on time once the system has reached an acceptable voltage and frequency. This technique does not
consider load capacity or expected kW for each priority. The loads are staged sequentially at a time interval defined by the Time
Based Load Add Time. For example, if the Time Based Load Add Time is set to 10 seconds, once the system reaches an
acceptable voltage and frequency, a 10 seconds timer will start. When that time expires, Priority 1 will be added. The 10 second
timer will start again and Priority 2 will be added when it expires. This will continue until all priorities are added.
Note:
Time Based Load Add does not consider the capacity of the generator set or generator system or the expected load of each
priority before adding and may overload the system. If an under frequency or overload shed becomes active, Time Based Load
Add will abort and not add any additional loads.
Time Based Load Add sheds all priorities at startup. It is not configurable to shed fewer loads.
Time Based Load Add Time is the amount of time between each load priority addition when using Time Based Load Add.
Time Based Load Add Timer Active indicates if a timer is currently in use and the system is preparing to add a load when the
timer expires. If this is Yes, the system will add a load when it expires. If this is No, no additional loads will be added based on
Time Based Load Add.
kW Capacity Add Threshold sets the maximum total load that the load management system will intentionally add to the
generator set or generator system. To determine whether adding the next priority load will push the system over the threshold,
the resulting total is calculated by adding the expected load to the current load. For example, if the threshold is set at 90%, the
current load is at 70% of total capacity, and adding the next priority load will add 15% of total capacity, adding the load will put
the system at 85% of total capacity, which is below the threshold. The kW Capacity Add Accumulator will start. If adding the load
would put the system at 92% capacity, the load will not be added.
The total load may exceed the kW Capacity Add Threshold value if the power required by a load is higher than the expected
kW.
kW Capacity Add Accumulator indicates progress until the next priority load will be added. The timer starts if adding the next
priority load will not exceed the kW Capacity Add Threshold for the system. Load management will add the next priority load
when the kW Capacity Add Accumulator reaches 100%.
The kW Capacity Add Accumulator is a weighted timer. The Accumulator will speed up or slow down depending upon the
available capacity and the expected kW. The time required will increase as the calculated total load increases and will decrease
as the calculated total load decreases.
Require Reset After kW Shed forces the system to lock out adding loads if an overload shed occurs. The overload shed is not
expected to operate, so an overload condition is an indication of a misconfiguration of the system (such as an incorrect expe cted
kW load level for a priority). Requiring a reset prevents load cycling due to a misconfiguration. See New Gen Online As Reset.
Overload Shed Threshold is an indication of the amount of overload a system can experience before load shed initiates. For
example, if this is set to 100%, if the total load exceeds 100% then the Overload Shed Accumulator starts. Load management
will shed the next priority load when the Overload Shed Accumulator reaches 100%.
Overload Shed Accumulator is an indication of progress until the load will be shed due to an overload situation.
The time to shed a priority will increase as the overload condition increases and will decrease as the overload condition
decreases. The Accumulator is not a fixed time but will speed up or slow down depending upon the overload.
Under Frequency Shed Threshold is the frequency droop (operation below nominal) allowed before the system will shed a
load. For example, if this is set to 90% and the frequency of the generator drops below 90% of nominal then the Under Frequency
Shed Accumulator starts. When the Under Frequency Shed Accumulator reaches 100%, load management will shed the next
priority load.
Under Frequency Shed Accumulator is an indication of progress until the load will be shed due to an under frequency situation.
The time to shed a priority will increase as the under frequency condition increases and will decrease as the under frequency
condition decreases. The Accumulator is not a fixed time but will speed up or slow down depending upon the amou nt exceeding
the under frequency threshold.
Require Reset After UF Shed forces the system to lock out adding loads if an under frequency shed occurs. The under
frequency shed is not expected to operate, so an under frequency condition is an indication of a misconfiguration of the system
(such as an incorrect expected kW load level for a priority). Requiring a reset prevents load cycling due to a misconfiguration.
See New Gen Online as Reset.
62 TP-7141 11/22
Under Frequency Inhibit Enabled indicates if the load management system will ignore any under frequency conditions for a
period of time as the generator is starting up. This allows the system to reach the rated voltage and frequency before the un der
frequency shed is detected and forces a load shed.
Note:
This setting is only necessary on applications where some of the load priorities are not shed on start up.
Under Frequency Inhibit Time is the period of time during start up when an under frequency condition is ignored. This is only
applicable if the Under Frequency Inhibit is enabled.
Under Frequency Inhibit Time Remaining indicates the amount of time left before the under frequency shed logic will begin
operating.
New Gen Online as Reset allows the load management to see an additional generator connecting the paralleling bus as a reset
condition. If a load was shed based on an overload shed or under frequency shed, the load will now be considered for addition
again if the kW Capacity threshold is met.
Stage Loads After Utility Return reduces the inrush loading to the utility when returning loads after a power failure. This is
used to reduce fluctuations in the utility voltage during a transition from the generator system to the utility when the util ity source
impedance is relatively high. The loads are added based on Time Based Add Time settings.
4.5.2.2 Load Management Status, Load
The Load Management Status Load screen provides indication of the shed status for each load priority.
1. In the navigation panel on the left side, touch Metering or the gauge symbol.
The numbers below correspond to the numbered steps in the Procedure to View Load Management Status, Load.
1 3
2 4
TP-7141 11/22 63
Parameter Units
Priority 1 Load Shed Yes/No
Priority 2 Load Shed Yes/No
Priority 3 Load Shed Yes/No
Priority 4 Load Shed Yes/No
Priority 5 Load Shed Yes/No
Priority 6 Load Shed Yes/No
Priority 7 Load Shed Yes/No
Priority 8 Load Shed Yes/No
Priority 9 Load Shed Yes/No
Priority 10 Load Shed Yes/No
Priority 11 Load Shed Yes/No
Priority 12 Load Shed Yes/No
Priority 13 Load Shed Yes/No
Priority 14 Load Shed Yes/No
Priority 15 Load Shed Yes/No
Priority 16 Load Shed Yes/No
Figure 48 Load Shed Status Parameters
A Yes indicates the load is currently shed due to load management. A No indicates that load management is not requiring the
load to be shed. If load management indicates No and the load is not powered, there are other issues in the system.
64 TP-7141 11/22
4.5.3 Load Management Setup Details
The setup details screen provides a table view of key settings for the load management configuration.
The numbers below correspond to the numbered steps in the Procedure to View Load Management Setup Details.
1 3
2 4
Note:
Custom names for loads can be set up through SiteTech. Contact a Kohler authorized distributor or dealer.
TP-7141 11/22 65
66 TP-7141 11/22
Section 5. Setup Menus and Screens
The values displayed in the Setup Menus are parameter settings. They are not actual measured values. Refer to the Metering
Displays for measured values.
The Setup Menus display the controller configuration settings as shown in the following sections. Some of the settings can be
adjusted by an operator, installer, or service technician with Operator access or higher.
• Engine
• Communication
• Event Configuration
• Genset Info
Note:
Have setup and adjustments of the generator set controller performed only by an authorized Kohler distributor. The setup and
adjustments are password protected.
General Procedure to Change Settings (for authorized Kohler distributors or service technicians)
1. Use an external flash drive or SiteTech to export the configuration data and save the file for future reference, if needed.
See the APM603 Controller Service Manual for instructions.
2. Go to Controller Settings and log in with the Operator or Technician level password. See the Controller Settings section
for instructions.
Note:
The access level login expires after 1 hour. See the Controller Settings Section for instructions to change the session
duration, if necessary.
3. In the navigation menu on the left side of the screen, touch Setup.
TP-7141 11/22 67
5. Touch the desired subcategory.
6. The settings are displayed. Settings that can be changed appear in a blue box.
7. Touch the blue box with the setting that you wish to change. A keypad window opens on the screen.
8. Use the keypad to enter the new setting and touch the green arrow.
Notes:
There may be clicking sounds coming from the controller when some settings are changed.
Some changes may require the controller to restart.
The numbers below correspond to the numbered steps in the Procedure to View Generator Setup Parameters.
1 3
2 4
68 TP-7141 11/22
Parameter Units Write Access Notes
System Voltage L-L V Technician
System Voltage L-N V Technician
System Frequency Hz N/A Factory-set to 50 or 60 Hz
Phase None Technician Single Phase, Single Phase Dogleg, Three Phase Wye, or Three Phase Delta
kW Rating kW Technician
Rated Current A Technician
Voltage Adjust V Operator
Speed Adjust RPM Operator
Operating Mode None N/A Factory-set to Standby or Prime
Maximum Power Limit kW N/A 102% of Standby Rating, 112% of Prime Rating
Maximum Current A N/A Factory configured
Note:
The Paralleling menu will appear on the Home screen if Paralleling Enabled is set to Yes in this menu.
TP-7141 11/22 69
The numbers below correspond to the numbered steps in the Procedure to View Paralleling Setup Parameters.
1 3
2 4
70 TP-7141 11/22
5.3 Engine Setup
The Engine Setup screen includes the engine settings shown below.
The numbers below correspond to the numbered steps in the Procedure to View Engine Settings.
1 3
TP-7141 11/22 71
ECU Power Override provides power to the engine’s ECU without cranking the engine. This feature may be turned on for some
troubleshooting or service procedures; otherwise, it should be off.
Engine Speed displays the target engine speed. Typically, this is 1800 RPM but may be adjusted if the system is required to
operate at a slightly modified speed.
Crank Turning Speed is the limit between engine rotating and engine stopped. When the engine speed (RPM) is above this
limit, the controller considers the engine to be turning. Until the speed falls below this limit, the controller will prevent
reengagement of the starter.
Start Aid Time displays the time programmed to allow the engine starting aid to warm up before cranking the engine.
Cranking Start Aid Time indicates the time programmed to allow operation of a preheat or ether system during the engine
crank cycle.
Crank On Time indicates the time allocated for generator set crank in seconds, from 10 to 30 seconds.
Crank Off Time indicates the time allocated for generator crank pause in seconds, from 1 to 60 seconds.
Crank Cycle Limit indicates the allowed number of crank attempts before the system indicates that crank failed, from 1 to 6
cycles.
Cooldown Time Limit indicates the amount of time allocated for the engine cooldown period.
Cooldown Temp Limit indicates the required temperature the engine must reach during cooldown before the engine will shut
off.
Note:
When the engine is signaled to stop, it will continue to run through the cooldown cycle unless the unit is OFF or a shutdown fault
occurs. In a paralleling application, if a shutdown occurs the generator will still perform a cool down for a period of time defined
by Trip to Shutdown Delay in Protective Relay functions.
The cool down will run until the engine reaches the cooldown temperature limit or the cooldown time expires, whichever happens
first. If you want to skip a cool down, set the Time Limit to 0. To force the unit to run the full Time Limit every time, set the Temp
Limit to an extremely low number that cannot possibly be achieved before the Time Limit expires.
72 TP-7141 11/22
5.4 Setup, Communication Screen
The communication setup screen provides a list of Modbus and network communication settings.
1. In the navigation panel on the left side, touch Setup or the settings symbol.
3. Touch the arrows on the right to scroll through the communication settings.
The numbers below correspond to the numbered steps in the Procedure to View Communications Setup.
1 3
The communication protocol for each port is factory set and not adjustable. Operator-level access is required to change the
other communication settings. Contact a Kohler authorized distributor or dealer for assistance.
Communication Protocol
The RS-485 ports are factory-set for the communication protocol applicable to each port.
TP-7141 11/22 73
Baud Rates
The following baud rates can be selected. All devices in the Modbus network must use the same baud rate.
• None
• 9600 bps
• 19200bps
• 38400 bps
• 57600 bps
• 115200 bps
Modbus Address
Each generator set controller in a system must have a unique Modbus ® address.
Modbus® Communications
The controller communicates using Modbus ® as a slave connection with the Modbus ® master initiating the communication.
The controller seeks the parameters and diagnostic information then responds back to the Modbus ® master. In addition, the
controller accepts information to alter controller parameters including generator set starting and stopping. Refer to the List of
Related Materials for available Modbus ® literature.
Note:
Only one Modbus® master can be connected to the controller when using Modbus RTU. Examples include the remote serial
annunciator, monitoring software, and switchgear applications.
Modbus® is a registered trademark of Schneider Electric USA, Inc.
74 TP-7141 11/22
5.5 Event Configuration
The Event Configuration (Config) screen displays the setup of fault messages (warnings and shutdowns). Time delays, warning
limits, and shutdown limits for the faults are shown.
3. Touch the up and down arrows on the right to scroll through the event settings.
The numbers below correspond to the numbered steps in the Procedure to View Event Configuration.
1 3
TP-7141 11/22 75
Tier 2 Generator Sets (KD700-KD4000) Tier 4 Generator Sets (KD1250-4, KD2500-4, KD3250-4)
Event Units Write Event Units Write
Access Access
Under Voltage Warning Delay Seconds Operator Under Voltage Warning Delay Seconds Operator
Under Voltage Warning Limit % Operator Under Voltage Warning Limit % Operator
Under Voltage Shutdown Delay Seconds Operator Under Voltage Shutdown Delay Seconds Operator
Under Voltage Shutdown Limit % Operator Under Voltage Shutdown Limit % Operator
Over Voltage Warning Delay Seconds Operator Over Voltage Warning Delay Seconds Operator
Over Voltage Warning Limit % Operator Over Voltage Warning Limit % Operator
Over Voltage Shutdown Delay Seconds Operator Over Voltage Shutdown Delay Seconds Operator
Over Voltage Shutdown Limit % Operator Over Voltage Shutdown Limit % Operator
Under Frequency Warning Delay Seconds Operator Under Frequency Warning Delay Seconds Operator
Under Frequency Warning Limit % Operator Under Frequency Warning Limit % Operator
Under Frequency Shutdown Delay Seconds Operator Under Frequency Shutdown Delay Seconds Operator
Under Frequency Shutdown Limit % Operator Under Frequency Shutdown Limit % Operator
Over Frequency Warning Delay Seconds Operator Over Frequency Warning Delay Seconds Operator
Over Frequency Warning Limit % Operator Over Frequency Warning Limit % Operator
Over Frequency Shutdown Delay Seconds Operator Over Frequency Shutdown Delay Seconds Operator
Over Frequency Shutdown Limit % Operator Over Frequency Shutdown Limit % Operator
Over Power Warning Delay Seconds Operator Over Power Warning Delay Seconds Operator
Over Power Warning Limit % Operator Over Power Warning Limit % Operator
Over Power Shutdown Delay Seconds Operator Over Power Shutdown Delay Seconds Operator
Over Power Shutdown Limit % Operator Over Power Shutdown Limit % Operator
Over Current Warning Delay Seconds Operator Over Current Warning Delay Seconds Operator
Over Current Warning Limit % Operator Over Current Warning Limit % Operator
Over Current Shutdown Delay Seconds Operator Over Current Shutdown Delay Seconds Operator
Over Current Shutdown Limit % Operator Over Current Shutdown Limit % Operator
AC Signal Recovery Time Seconds Operator AC Signal Recovery Time Seconds Operator
Over Speed Shutdown Delay Seconds Operator Over Speed Shutdown Delay Seconds Factory
Over Speed Shutdown Limit % Operator Over Speed Shutdown Limit % Factory
Low Battery Voltage Warning Delay Seconds Operator Low Battery Voltage Warning Seconds Operator
Delay
Low Battery Voltage Warning Limit % Operator Low Battery Voltage Warning Limit % Operator
High Battery Voltage Warning Delay Seconds Operator High Battery Voltage Warning Seconds Operator
Delay
High Battery Voltage Warning Limit % Operator High Battery Voltage Warning Limit % Operator
Weak Cranking Battery Delay Seconds Operator Weak Cranking Battery Delay Seconds Operator
Weak Cranking Battery Limit % Operator Weak Cranking Battery Limit % Operator
Battery Voltage Event Recovery Seconds Operator Battery Voltage Event Recovery Seconds Operator
Delay Delay
Low RTC Battery Delay Seconds Operator EPS Supplying Load Delay Seconds Operator
Low RTC Battery Limit % Operator EPS Supplying Load On Limit % Operator
EPS Supplying Load Delay Seconds Operator EPS Supplying Load Off Limit % Operator
EPS Supplying Load On Limit % Operator Low Fuel Level Warning Limit % Operator
EPS Supplying Load Off Limit % Operator Critically Low Fuel Level Warning % Operator
Limit
Low Fuel Level Warning Limit % Operator Low Fuel Level Shutdown Limit % Operator
Critically Low Fuel Level Warning % Operator High Fuel Level Warning Limit % Operator
Limit
Low Fuel Level Shutdown Limit % Operator Fuel Level Delay Seconds Operator
High Fuel Level Warning Limit % Operator Maximum Power Warning Delay Seconds Operator
Fuel Level Delay Seconds Operator Enable Fuel Level Events On/Off Operator
76 TP-7141 11/22
Tier 2 Generator Sets (KD700-KD4000) Tier 4 Generator Sets (KD1250-4, KD2500-4, KD3250-4)
Event Units Write Event Units Write
Access Access
Maximum Power Warning Delay Seconds Operator Enable Low Fuel Level Switch On/Off Operator
Shutdown
Battery Charger 1 Fault On/Off Operator Enable Low DEF Level Warning On/Off Technician
Battery Charger 2 Fault On/Off Operator Low DEF Level Warning Limit % Technician
Enable Fuel Level Events On/Off Operator Enable Low DEF Level Shutdown On/Off Technician
Low DEF Level Shutdown Limit % Technician
Load Bank Power Rating kW Technician
High HC Warning Delay Seconds Factory
High HC Warning Active Limit % Technician
High HC Warning Clear Limit % Technician
Critically High HC Warning Delay Seconds Factory
Critically High HC Warning Active % Factory
Limit
Critically High HC Warning Clear % Factory
Limit
Load Bank Malfunction Delay Seconds Factory
The delay for each event indicates how long the condition must be present to trigger the event. The limit on each event indicates
the condition that triggers the time delay to begin. If the condition corrects itself before the time delay expires, no event is
indicated and the timer resets. If the condition reappears, the timer starts over.
Under Voltage displays the percentage of the system voltage that the generator set must drop below for an undervoltage
condition to be indicated.
Over Voltage displays the percentage of the system voltage that the generator set must exceed before an overvoltage condition
be indicated.
Under Frequency displays the percentage of the system frequency that the generator set frequency must drop below for an
under frequency condition to be indicated.
Over Frequency displays the percentage of the system frequency that the generator set frequency must exceed before an over
frequency condition be indicated.
Over Power indicates the percentage of the system rated power that the generator set must exceed before an over power
condition be indicated.
Over Current indicates the percentage of the system rated current that the generator set must exceed before an over current
condition be indicated.
AC Signal Recovery Time is the amount of time allowed for AC signal to be lost before an AC Loss is indicated.
Over Speed is the engine speed that the engine must exceed for an overspeed condition to be indicated.
Low Battery Voltage displays the system battery voltage that the battery must drop below for a low battery voltage condition to
be indicated.
High Battery Voltage displays the system battery voltage that the battery must exceed for a high battery voltage condition to
be indicated.
Weak Cranking Battery displays the system battery voltage that the battery must drop below during engine crank for a weak
cranking battery condition to be indicated.
Battery Voltage Event Recovery Delay indicates the amount of time allowed for the battery voltage to recover from a fault.
The controller uses this delay to recognize the voltage as fully recovered and to prevent multiple warnings due to oscillating or
fluctuating battery voltage.
TP-7141 11/22 77
Low RTC Battery indicates the Real Time Clock battery voltage that the voltage must drop below for a low RTC battery condition
to be indicated.
EPS Supplying Load On Limit and Off Limit define the % of load the generator must be suppling to be considered supplying
load.
Low Fuel Level and Critically Low Fuel Level define the fuel level limits as a percentage that must be met before indication is
provided.
High Fuel Level indicates the fuel level limit to be exceeded before indication is provided.
Low DEF Level Warning Limit and Low DEF Level Shutdown Limit (tier 4 generator sets only) are customer configurable
parameters that define the points at which the controller issues a Low DEF Level Warning or a Low DEF Level Shutdown.
Low DEF Level Warning (tier 4 generator sets only) provides an advanced warning that DEF is low and the operation should
add DEF. Low DEF Level Shutdown shuts down the generator set to avoid an inducement.
Load Bank Power Rating (tier 4 generator sets only) specifies the amount of load in kW that the load bank will add to the
system to reduce hydrocarbon levels.
High HC Warning Active Limit (tier 4 generator sets only) initiates an advanced warning indicating that the operator needs to
increase load to avoid hydrocarbon buildup on the SCR. If the hydrocarbon levels continue to increase, the controller will apply
the load bank.
Critically High HC Warning Active Limit notifies the operator that the load bank is not effectively reducing the hydrocarbon
levels in the SCR. Failure by the operator to immediately correct the issue will result in engine torque reduction.
High HC Warning Delay and Critically High HC Warning Delay (tier 4 generator sets only) indicates the period of time from
when hydrocarbon levels exceed the warning limit to when the warning is issued. If hydrocarbon levels fall below the warning
limit during the delay period, then the warning is not issued.
Load Bank Malfunction Delay (tier 4 generator sets only) indicates the period of time from the generator set kW output level
falling below the load bank kW rating to the warning being issued. If the generator set kW output level increases a bove the load
bank kW rating, then the malfunction warning is not issued.
78 TP-7141 11/22
5.5.1 Generator Set Information (Genset Info)
The GENSET INFO screen displays information about the generator set, including the model and serial number, and engine
and alternator information. The generator set information is loaded at the factory or read from the engine ECM. The GENSET
INFO data cannot be changed in the field.
The numbers below correspond to the numbered steps in the Procedure to View Generator Set Information.
1 3
TP-7141 11/22 79
5.6 Data Log Screens
Data log files can be created and saved to a flash drive.
Before starting the data log, insert a flash drive into the USB port on the front of the controller. When the controller reco gnizes
the flash drive, the symbol appears at the top of the screen. Select one or more parameters to log over a period of time, and
select the log rate (intervals from once per second to once a day).
The data logger will collect data until STOP is selected on the screen or until the flash drive runs out of memory.
When complete, remove the flash drive from the controller and insert it into a personal computer to view the data files. The data
file name includes the date, an alpha-numeric code, and the .csv extension. The file can be opened using a spreadsheet program
like Microsoft Excel. A word-processing program or Notepad can also open the file. The data entries in the file are time- and
date-stamped.
1. Check for the flash drive symbol at the top of the screen to verify that the controller recognizes the flash drive installed
in the USB port.
2. In the navigation menu on the left side of the screen, touch Data Log.
3. Confirm that USB Connected appears on the screen. Touch the Circle icon with three dots near the upper right corner
of the screen. A list of categories opens.
5. Touch each parameter that you want to log. Multiple parameters from different categories can be logged at the same
time. A check mark appears in the boxes for the selected parameters. Touch the left arrow at the bottom to close the
selection window. Repeat steps 4 and 5 for other categories and parameters as needed. The parameters to be logged
are listed on the left side of the screen.
6. Click on the blue box labeled Log Rate, located in the lower right corner of the screen. The Data Logger Sample Rate
window opens.
7. Select the desired log rate and touch the up arrow to close the window. The new log rate appears in the blue box at
the bottom of the screen.
8. Touch START LOG to begin collecting data. Data Log In Progress is displayed. The data is stored to the flash drive.
9. Touch STOP to end the data logging process. Wait at least 5 seconds to allow the data to be written to the files before
removing the flash drive from the controller.
Note:
If the flash drive memory becomes full, the controller will stop logging data.
To view the data, insert the flash drive into your PC and open the .csv file.
80 TP-7141 11/22
The numbers below correspond to the numbered steps in the Data Logging Procedure.
1 6
2 7
3 8
4 9
TP-7141 11/22 81
82 TP-7141 11/22
Section 6. Paralleling
6.1 Introduction
Note:
The Paralleling menu will appear if Paralleling Screens Enabled is set to Yes in the Setup>Electrical>Paralleling menu.
While it may be common for a facility to install a single large generator to meet its power needs, paralleling two or more
generators offers a number of practical benefits and advantages over a single-generator system.
Redundancy
The redundancy provided by the paralleling of two or more generators delivers greater reliability and flexibility than a sing le
generator can provide. In critical applications, having more than one generator connected to the bus at all times ensures
continuous generator power in the unlikely event that a generator fails.
Efficiency
Instead of one large generator that might operate inefficiently at a low power level, several small generators can be paralleled
together and turned on and off as necessary to more efficiently support the varying demands of the load.
When a loss of utility power occurs, almost every system responds with the basic sequence shown here.
1. Engine Start Delay. A timer starts when there is a loss of utility. If utility returns before the timer expires, the system
does not start. If the utility outage is long enough for the timer to expire, the system wil l commit to transferring to
generator power.
2. Start / Start-Up Load Shed. All available generators start. If the system is designed to supply power to loads as soon
as one generator is online (typical for systems serving critical and life-safety loads), low-priority loads are shed or are
inhibited from transferring. This prevents the first-on generator from being overloaded.
3. First Generator Breaker Closes. The first generator to reach the rated voltage and frequency closes to the bus. First -
on logic prevents multiple generators from simultaneously closing to the bus. The bus is now energized, and power is
available to the load. Low-priority loads may remain shed.
4. Synchronization. The incoming generator’s voltage, frequency and phase are matched to the runnin g bus. When
matched, the generator paralleling breaker closes.
5. Second Generator Breaker Closes/Load Sharing. Additional generator power is available to the load. The system’s
load-sharing controls actively control the kW and kVAR output of each generator in order to proportionally share the
load (maintain the same percent load on each generator) and maintain rated frequency and voltage.
6. Load Management. As additional generators close to the bus, more power is available for the load. The load
management system actively adds loads based on available bus capacity.
7. Generator Management. Generator management optimizes the number of online generators based on the load, starting
and stopping as required. Generators are sequenced on in order of operator-assigned priority (or based on runtime)
and taken off in reverse priority. Defined setpoints determine the percent load level and time delay at which the
generator set will be brought on or taken offline.
Synchronization
The automatic synchronizer matches the incoming generator’s output (waveform) to the running bus. When the voltage,
frequency and phase are all matched, the synchronizer will close the incoming generator’s breaker.
Voltage Match. The synchronizer adjusts the incoming generator’s voltage to match the running bus.
Frequency Match. The synchronizer adjusts the engine speed for the incoming generator to match the frequency of the running
bus.
Phase Match. The synchronizer adjusts the engine speed for the incoming generator to match the phase of the running bus.
When all three are matched, the two sine waves will be the same.
TP-7141 11/22 83
Tier 4 Load Bank Operation During Paralleling
Parallel operation for a tier 4 generator set is similar to parallel operation for tier 2 generator set with the exception of the load
bank. Tier 4 generator sets use load banks to prevent hydrocarbon buildup. To utilize the load bank properly, the APM603 makes
some additional calculations related to the load of the generator sets in parallel.
• The load bank will only be applied in parallel with the customer’s load when applying the load will result in the total kW
of the generator set being at or greater than the kW rating of the load bank and the total kW output of the generator set
with the load bank’s load will not exceed 90% of the generator set’s rated capacity.
• When the HC levels of one generator set (running in parallel with multiple generator sets) needs to be reduced, and
adding the load will not result in the total kW output of the generator set being at or greater than the kW rating of the
load bank, then the following will occur:
o The generator set will have 90 seconds to shed its load and go offline.
o Once the generator set goes offline the load bank will be activated.
• When the generator is running and the HC buildup is over 50%, the controller will do one of the following depending on
status of the paralleling breaker, availability of other generator sets, and the bus capacity and other parameter settings:
o If the paralleling breaker is open, then the controller will activate the load bank.
o If the breaker is closed then the controller will do one of the following based on the following conditions:
- If this is the only generator online, and there is enough remaining available power on the generator to power
the load bank and total power output of the generator with the load bank does not exceed 90% of the
generator’s rated power, then the load bank will be activated.
- If this is the only generator online, and there is not enough remaining available power on the generator to
power the load bank and be under 90% of the generator’s rated power, then the load bank will be inactive.
o If there are multiple generators online and the sum of the powers is more than the rating of the load bank and less
than 90% of the generator’s rated power, then the load bank will be activated. The sum of the powers is a
combination of the following:
- Current output power of the generator set without the load bank connected.
- Power rating of the load bank divided by the number of generator sets online.
o If there are multiple generators online and the sum of the powers is more than the rating of the load bank and
exceeds 90% of the generator’s rated power, then the load bank will not be activated. The sum of the powers is a
combination of the following:
- Current output power of the generator without the load bank connected.
- Power rating of the load bank divided by the number of generators online.
o If there are multiple generators online and the sum of the powers is less than the rating of the load bank, then the
generator will shed its loads and go offline and then apply the load bank. The sum of the powers is a combination
of the following:
- Current output power of the generator without the load bank connected.
- Power rating of the load bank divided by the number of generators online.
• While the generator is running and the load bank is active, and the HC Level drops at or below 0% the generator will
do the following:
o Deactivate the load bank and clear the regen active event.
• Stopping the generator while the load bank is active, will result in the following:
84 TP-7141 11/22
o High HC Level Warning shall remain in its current state until the HC drops to or below the clear threshold.
o Load Bank Control Malfunction Warning shall remain in its current state until the generator has been restarted with
appropriate amount of load to clear the event.
• Stopping the generator remotely, will cause the generator to go into Low Idle Cooldown.
• Stopping the generator using the OFF button, E-Stop, or any shutdown event, will cause the generator to immediately
shutdown and bypass the Low Idle Cooldown.
6.2 Metering
This section provides a list of paralleling metering screens that display the status of the paralleling system and generators within
that system. Metering screens are display screens only; there are no adjustable parameters in the metering screens.
1. In the navigation panel on the left side, touch Paralleling or the symbol of two generators.
The numbers below correspond to the numbered steps in the Procedure to View Paralleling Overview.
1 3
2 4
Note:
Custom names for generators can be set up through SiteTechTM. Contact a Kohler authorized distributor or dealer.
TP-7141 11/22 85
The top of the display provides a key to explain the color designation.
• A generator shown in green with lines through it is running. It may or may not be on the bus depending upon the status
of the electrically operated breaker or contactor.
• A generator in solid green is in standby and disconnected from the bus. The generator is ready to start as required.
• A generator in blue is in cool down. It is disconnected from the bus but still running.
• A generator in yellow has a warning. This generator may be running and connected to the bus or it may be in cooldown
or it could be in standby waiting for a start signal.
• A generator in red has a shutdown fault. It is not running, not connected to the bus and not available for paralleling.
Along with each color, a text description is provided to indicate the generator status.
Note:
The fact that a generator is not running does not automatically mean it has a fault. Generator Management may shut down a
generator when it is not needed.
The lines on the display indicate the status of the bus and electrically operated breaker or contactor.
Each generator has a breaker symbol to indicate if the electrically operated breaker or contactor is open or closed. When the
breaker is open, the breaker symbol does not appear connected to the bus lines and the breaker symbol is green. When the
breaker is closed, the breaker symbol will appear connected to the bus lines and the breaker symbol will be red.
As soon as one generator closes to the bus, the bus line up the center of the display will show as red. As each generator closes,
the bus line changes to red.
The bottom of the display shows the frequency, load and voltage of the bus. It does not show the information for a single
generator but each generator closed to the bus should have a matching frequency and voltage. Each generator closed to the
bus will share load so that each generator has an equal percentage loaded.
86 TP-7141 11/22
6.2.2 Paralleling, Metering Status
The status screens provide a listing of the paralleling metered values.
The Paralleling System Status provides indication of key settings and values related to the overall operation of the paralle ling
system.
1. In the navigation panel on the left side, touch Paralleling or the symbol with two generators.
4. Touch the up and down arrows on the right to view the status parameters, which are described below.
1 3
2 4
TP-7141 11/22 87
Parameter Units
Bus Voltage Average L to L V
Bus Voltage Average L to N V
Bus L1 L2 Phase Angle Degrees
Bus L1 L3 Phase Angle Degrees
Bus Frequency Hz
Bus Voltage L1 L2 V
Bus Voltage L2 L3 V
Bus Voltage L3 L1 V
Bus Voltage L1 L0 V
Bus Voltage L2 L0 V
Bus Voltage L3 L0 V
Paralleling State
Start Active Yes/No
Synch Active Yes/No
In Sync Yes/No
Frequency Matched Yes/No
Phase Matched Yes/No
Voltage Matched Yes/No
Close Breaker True/False
Trip Breaker True/False
Figure 66 Paralleling Metering Status Parameters
The electrical metering of the bus is shown. If the generator is not closed to the bus but trying to synchronize, the generator is
adjusting the speed and voltage outputs to match the voltage, frequency and phase of the bus in order to close.
Start Active indicates if the generator has a start signal. This signal could be from a transfer switch, from the control buttons on
the front of the generator or through PGEN.
In Sync indicates if the generator has successfully synced to the bus. The generator has not yet closed to the bus. All three
parameters that follow, Frequency Matched, Phase Matched and Voltage Matched must be Yes for In Sync to be Yes.
Frequency Matched indicates the difference between the generator set frequency and the bus frequency is within the
acceptable window.
Phase Matched indicates the difference between the generator set phase and the bus phase is within the acceptable window.
Voltage Matched indicates the difference between the generator set voltage and the bus voltage is within the acceptable
window.
Close Breaker indicates if the controller has commanded the electrically operated breaker or contactor to close.
Trip Breaker indicates if the controller has commanded the electrically operated breaker or contactor to trip based on a
protective function.
88 TP-7141 11/22
6.2.3 Paralleling, Metering, Details
The Paralleling System Generator Details provides details for each generator in the system. It provides the ability to view k ey
data on other generators in the system from a single generator.
1. In the navigation panel on the left side, touch Paralleling or the symbol of two generators.
3. Touch Details Gen 1-4 or Details Gen 5-8 or the list symbol for either.
5. Touch the up and down arrows on the right to view the parameters, which are described below.
The numbers in the list below correspond to the numbered steps in the Procedure to View Paralleling System Generator
Metering.
1 4
2 5
TP-7141 11/22 89
Parameter Units
Synch Status
Real Power Percentage %
Reactive Power Percentage %
Run Time Hours Hours
Fuel Level %
Rated Power kW
Engine Speed RPM
Bus Percent Voltage %
Connected Yes/No
Was Connected Yes/No
Online Yes/No
Faulted Yes/No
Bus Energized Yes/No
Start Signal Yes/No
Real Power Percentage indicates the percentage load on the generator of real power (kW). All generators paralleled together
should share load in order to have equal percentage.
Reactive Power Percentage indicates the percentage load on the generator of reactive power (kVAR). All generators paralleled
together should share load in order to have equal percentage.
Run Time Hours indicates the total run time hours on the generator.
Fuel Level indicates the percentage of fuel level for the generator.
Engine Speed indicates the current engine speed for the generator.
Bus Percent Voltage indicates the measured voltage as percent of system voltage.
Connected indicates if the generator is connected through the PGEN communication with the other generators.
Was Connected indicates at one point the generator was connected through the PGEN communication with other generators
but is not connected at this time.
Faulted indicates if the generator is faulted and not available for paralleling.
Note: If the controller is still communicating through PGEN with other generators, the load management implemented on the
generator controller is still operational.
Bus Energized indicates if the generator is sensing that the bus has voltage and frequency.
Start Signal indicates if the generator has a start signal. This signal could be from a transfer switch, from the control buttons on
the front of the generator or through PGEN.
90 TP-7141 11/22
6.2.4 Paralleling, Metering, PGEN
The PGEN metering provides details related to the paralleling system communication.
1 3
2 4
Disconnected Nodes indicates how many generators have been on the PGEN communication network before but are not
communicating at this time. In a fully functioning system this would be 0. If a unit is out of service or the controller has stopped
communicating, then there will be a value greater than 0.
Scheduler ID indicates which controller, based on PGEN ID, is the master in the system.
Note:
If a master scheduler controller stops communicating another controller takes over the as the Scheduler ID.
TP-7141 11/22 91
6.3 Setup
The screens in this section show the settings for systems using the onboard paralleling features.
Paralleling system setup and commissioning must be performed by a trained and authorized Kohler distributor or dealer. A
separate Commissioning and Setup manual provides more information and instructions for setting up a paralleling system. See
the List of Related Materials in this manual for the document part number for the Commissioning and Setup Manual for your unit.
Technician-level access is required to adjust the paralleling parameters on the controller display. Additional paralleling
parameters are only accessible using SiteTech software. A personal computer (laptop) and Kohler SiteTech software are
required to adjust these settings. SiteTech software is available only to Kohler authorized distributors and dealers.
1. In the navigation panel on the left side, touch Paralleling or symbol with two generators.
1 3
2 4
92 TP-7141 11/22
Parameter Units Write Access Level
PGEN Baud Rate BPS Factory set
PGEN Comm Protocol Factory set
PGEN Node ID Technician
PGEN Version N/A
PGEN Scheduler Yes/No Technician
Figure 72 PGEN Setup Parameters
PGEN Baud Rate is fixed from the factory. All controllers must use the same baud rate and the rate is fixed for optimal
performance.
PGEN Comm Protocol is fixed from the factory to support the same setting on all controllers in the system.
PGEN Version indicates the version of PGEN communication used in the system and is fixed from the factory.
PGEN Scheduler indicates Yes if the controller is the master scheduler in the system.
TP-7141 11/22 93
6.3.2 Paralleling, Setup, Protect Relay Screen
The Paralleling System Protective Relays provides indication of key settings related to the protective relay functions relate d to
paralleling.
1. In the navigation panel on the left side, touch Paralleling or symbol with two generators.
4. Touch the up and down arrows on the right to view the protective relay setup parameters, which are described below.
1 3
2 4
94 TP-7141 11/22
Trip to Shutdown Delay indicates the time allowed to clear the trip condition to avoid the shutdown. It also serves as a cooldown
period for the generator in a case where the protective relay function is causing the trip.
Generator management sequences the generators off in an order determined by configuration parameters and operating
conditions (load, runtime, fuel level). The highest order generator sets stop first (when load is low enough) and re-start last (when
load is too high). The order can be viewed on the front panel of the controller, but can only be adjusted under certain condi tions
(see Gen Management Order later in this section).
The time to start a generator set (if the load increases) varies with the degree of overload as a percent of online capacity (the
sum of rated power for those generators that are connected to the bus).
The time to stop a generator set (if the load is low enough) varies with the degree of load as a percent of total available capacity
(the sum of rated power for all generators in the system whether connected to the bus or not). A generator with a fault or in Off
mode is not considered available.
Note:
Receipt of a start signal will cause all generator sets to start, synchronize, and close to the bus.. If a generator set is f aulted or
manually stopped and then placed back in Auto, generator management will require the generator set to start and connect to
the bus before it is permitted to stop again—even if generator management had previously signaled the generator set to stop.
TP-7141 11/22 95
The overview provides a simple graphical view of the generator management status.
1. In the navigation panel on the left side, touch PARALLELING or the symbol of two generators.
2. Touch GEN MANAGEMENT or the three horizontal bars with a generator symbol.
1 3
2 4
The generators are listed in order of priority. If the generators were provided a custom name during the system set up, the name
will appear. If not, the name will appear as Gen X, where X is the system assigned generator number.
• Depending upon the Generator Management Mode, the priority of a generator can change over time. For example, if
the mode is Fuel Level, as the fuel level of each generator changes the order of priority for each generator will change.
The top of the screen provides a key to explain the symbol and color designation used on the overview. A timer face in white
indicates a timer is active to either turn a generator on or off. The timer face will appear on the line of the generator for which
the timer applies. A red circle indicates the stop kW setting for the generator. A green arrow indicates the start kW setting for the
generator. If a generator is running, it will show the stop setting. If a generator is stopped, it will show the start settin g.
The key at the bottom of the display shows the current load as well as the total online capacity (green) and available capacity
(yellow). If a generator is offline (either due to a shutdown via Generator Management or a fault, or the generator is not
communicating via PGEN), the capacity of that generator is shown as unavailable (white). A vertical blue dotted line indicates
the current load on the system.
96 TP-7141 11/22
6.4.1 Paralleling, Generator Management Status
The status screens provide a listing of the generator management metered values as well as key settings for reference.
6.4.1.1 Status, System
The Gen Management System Status provides indication of key settings and values related to the overall operation of the load
management system.
1. In the navigation panel on the left side, touch Paralleling or the symbol of two generators.
2. Touch Gen Manage or the three horizontal bars with a generator symbol.
The numbers below correspond to the numbered steps in the Procedure to View Paralleling System Status Metering.
1 3
2 4
TP-7141 11/22 97
Generator Management Enabled indicates whether generator management is turned on for the generator.
Note:
This parameter can be set individually for each generator set and will inhibit the Generator Management Configuration Mismatch
Warning for this generator set if set to OFF.
Note:
Disabling the generator management on one generator set in a paralleling system will not keep the other generator sets in the
paralleling system from alarming if the generator management configuration of any of the other nodes differs from the disabled
generator set.
Note:
Generator sets with Generator Management disabled are not taken into consideration for generator management on the other
generator sets. It is not recommended to disable any of the generator sets in a paralleling system where generator management
is intended to be used; the generator management may operate too many generator sets in these cases.
Generator Management Mode indicates which form of generator management is active. See Section 6.4.2 for descriptions of
the available modes.
Total Online Capacity indicates the capability of the system with all the generators that are currently online.
Total Available Capacity indicates the difference between the Online Capacity and the Total Load.
Stop by Gen Management indicates whether the generator set has been stopped by the gen management function.
Start by Gen Management indicates whether the generator set has been started by the gen management function.
6.4.2 Gen Management Modes
The Gen Management Mode is the method that generator management uses to determine the starting and stopping order of the
available generator sets. All of the generator sets in the system must have the same setting for this parameter for the generator
management to operate correctly. This parameter can be set to one of the following:
Manual/Fixed. The order of the generator sets is manually set. In this mode, the order is set once by the user.
Note:
The controllers require that the order be valid. If two nodes share a common order or there is a gap in the order sequence, t he
controllers will attempt to re-sort the order until it is valid. If the order is not valid (automatic re-sorting failed) generator
management will be disabled and all generator sets will run all of the time.
Run Time. The generator management start/stop order is determined by the runtime hours on the generator sets. In this mode,
the order is determined to ensure that the generator set with the fewest runtime hours is the last to stop. Each subsequent order
is assigned to generator sets with increasing runtime hours.
If a generator set is not running, the system will add the Run Time Threshold to the runtime hours for that generator set before
it considers it in the order—this allows the generator sets to avoid starting and stopping continuously. The actual runtime will
have to differ by more than the threshold to force the generator set order to switch (the stopped generator set will start,
synchronize to the paralleling bus, and begin sharing load—the running generator set will soft-unload, disconnect from the bus,
cool down and stop).
Note:
If the load on the system requires an additional generator set to start, the generator set with the most runtime hours will always
be the first one to stop if the load decreases enough to permit it (the threshold is no longer taken into consideration as so on as
the generator set is connected to the paralleling bus).
Fuel Level. The generator management start/stop order of the generator sets is determined by the level of the fuel in the tank
which supplies each generator set. In this mode, the order is determined to ensure that the generator set with the most fuel is
the last to stop. Each subsequent order is assigned to generator sets with decreasing fuel percentage.
If a generator set is running, the system will add the Fuel Level Threshold to the measured Fuel Level fo r that generator set
before it considers it in the order. This allows the generator sets to avoid starting and stopping continuously. The actual f uel level
will have to differ by more than the threshold to force the generator set order to switch. The stopped generator set will start,
98 TP-7141 11/22
synchronize to the paralleling bus, and begin sharing load. The running generator set will soft-unload, disconnect from the bus,
cool down, and stop.
Note:
Fuel Level Order Selection mode requires separate fuel tanks for the generator sets and fuel level senders connected to the
controller to operate. Operation of Fuel Level mode without sensors is not defined.
Note:
If the load on the system requires an additional generator set to start, the generator set with the lowest fuel level will always be
the one to stop (the threshold is no longer taken into consideration as soon as the generator set is connected to the paralleling
bus).
6.4.3 Gen Management System Status, Generator
The Gen Management System Generator provides details on each generator in the system. Each generator has a page of data
so as you page down you will see the information for each generator on a single screen.
1. In the navigation panel on the left side, touch Paralleling or the symbol of two generators.
2. Touch Gen Manage or the three horizontal bars with a generator symbol.
The numbers below correspond to the numbered steps in the Procedure to View Generator Management System Status,
Generator.
1 3
2 4
TP-7141 11/22 99
Parameter Units
Priority 1 Generator Name String
Priority 1 Generator Capacity kW
Priority 1 Start Power kW
Priority 1 Start Accumulator %
Priority 1 Stop Power kW
Priority 1 Stop Accumulator %
Priority 1 Generator Online Yes/No
Priority 1 Generator Fault Yes/No
Generator Name is the descriptive name of the generator. If the generators were provided a custom name during the system
set up, the name will appear. If not, the name will appear as Gen X, where X is the system assigned generator number.
Note:
Custom names for generators can be set up through SiteTechTM. Contact a Kohler authorized distributor or dealer.
Start Power indicates the kW setting that needs to be exceeded in order for the generator management to begin a timer to add
the generator back to the bus.
Start Accumulator is an indication of progress until generator management will start the generator.
Note:
The time to start will decrease as the load demand increases and will decrease as the load demand decreases. The Accumulator
is not a fixed time but will speed up or slow down depending upon the load demand.
Stop Power indicates the lower limit kW setting for gen management. When the load drops below this kW limit, generator
management starts a timer to stop the generator.
Stop Accumulator is an indication of progress until generator management will stop the generator.
Note:
The time to stop will decrease as the load demand decreases and will increase as the load demand decreases. The Accumulator
is not a fixed time but will speed up or slow down depending upon the load demand.
1. In the navigation panel on the left side, touch PARALLELING or the symbol of two generators.
2. Touch GEN MANAGEMENT or the three horizontal bars with a generator symbol.
1 3
2 4
Note:
Custom names for generators can be set up through SiteTech.
The table indicates the kW Capacity of the generator along with the Start kW and Stop kW settings and the start and stop timer
settings. Generator Start kW, Stop kW, Start Time and Stop Time can be adjusted using SiteTech. See Figure 81 for the
SiteTech Group. Start and Stop kW values are calculated from the configuration parameters and the respective capacity values.
The actual settings are made using percentages: parameters Start Percentage and Stop Percentage.
Home screen
Remote monitor
Menu Screen
Navigation buttons
Menu button
o Menu Screen
The Menu screen on the remote monitor displays a selectable list of available engine metering screens. See Figure 84.
Note:
The navigation icons correspond to the navigation buttons directly below them.
The Engine Overview screens (1–3) on the remote monitor displays the engine overview data shown in Figure 86.
Note:
The navigation icons correspond to the navigation buttons directly below them.
Press Next Menu button. Press Next Menu button. Press the Return-to-Menu button.
The Engine Fuel screen on the remote monitor displays the engine fuel data shown in Figure 88.
Note:
The navigation icons correspond to the navigation buttons directly below them.
Use the Arrow buttons to highlight the Press the Return-to-Menu button.
menu item and press Enter.
The Engine Temperature screens (1–5) on the remote monitor displays the engine temperature data shown in Figure 90.
Note:
The navigation icons correspond to the navigation buttons directly below them.
The Engine Pressure screen on the remote monitor displays the engine pressure data shown in Figure 92.
Note:
The navigation icons correspond to the navigation buttons directly below them.
Use the Arrow buttons to highlight the Press the Next Menu button. Press the Return-to-Menu button.
menu item and press Enter.
The Engine Aftertreatment screens (1–5) on the remote monitor displays the engine aftertreatment data shown in Figure 94.
Note:
The navigation icons correspond to the navigation buttons directly below them.
Press Next Menu button. Press Next Menu button. Press Next Menu button.
On the User Settings screen, use the button interface to change brightness and contrast or units of measurement.
Note:
The navigation icons correspond to the navigation buttons directly below them.
Use the Arrow buttons to highlight the Press the Return to Menu button.
menu item and press Enter.
Menu items
8.1 Introduction
This section contains generator set, controller, and general engine troubleshooting information. This section may refer to other
literature for procedures and additional information. See the list of related materials in the Introduction of this manual for literature
part numbers. The information in this section is a guideline for generator set operating technicians.
Corrective action and testing often require knowledge of electrical and electronic circuits. To avoid additional problems caused
by incorrect repairs, have an authorized service distributor/dealer perform service.
Use the following charts to diagnose and correct common problems. First check for simple causes such as a dead engine starting
battery or an open circuit breaker. The charts include a list of common problems, possible causes of the problem, recommended
corrective actions, and references to detailed information or repair procedures.
Maintain a record of repairs and adjustments performed on the equipment Use the record to help describe the problem and
repairs or adjustments made to the equipment.
8.3 Engine
Refer to the following charts for general engine troubleshooting. Refer to the engine operation manual and/or engine service
manual for all specific engine troubleshooting.
start
voltage
High fuel
Overheats
inoperative
Starts hard
Lacks power
consumption
Excessive or
Displays error
No or low output
Low oil pressure
Exercise run time
message/locks up
Publication
Power to the controller is interrupted; Check for power battery power to the controller. If W/D, Controller
X X X
no power to the controller. fuse does not auto-reset troubleshoot the controller S/M
wiring.†
TP-7141
* Sec./Section - numbered section of this manual; ATS - Automatic Transfer Switch; Eng. - Engine; Gen. - Generator Set; I/M - Installation Manual; O/M - Operation Manual;
M/M – Maintenance Manual; S/M - Service Manual; S/S - Spec Sheet; W/D - Wiring Diagram Manual
† Have an authorized service distributor/dealer perform this service.
11/22
Trouble Symptoms
TP-7141
voltage
records
not start
High fuel
Overheats
inoperative
Starts hard
and/or event
Lacks power
consumption
Excessive or
11/22
Section or
Displays error
message/locks up
Probable Causes Recommended Actions Reference*
Alternator
X AC output circuit breaker open Reset the breaker and check for AC voltage at the
generator set side of the circuit breaker.
X Transfer switch test switch in the OFF Move the transfer switch test switch to the AUTO ATS O/M
position position.
X Transfer switch fails to transfer load Move the ATS test switch to the AUTO position. ATS O/M, S/M
Troubleshoot the transfer circuit and time delays.
X Wiring, terminals, or pin in the exciter Check for continuity. Gen. S/M, W/D
field open
X Main field (rotor) inoperative (open or Test and/or replace the rotor. † Gen. S/M
grounded)
X Stator inoperative (open or grounded) Test and/or replace the stator.† Gen. S/M
X X Voltage regulator settings incorrect Check and adjust the voltage regulator.†
X X Battery connections loose, corroded, Verify that the battery connections are correct, clean, I/M or M/M
or incorrect and tight.
X X Battery weak or dead Recharge or replace the battery. The spec sheet S/S
provides recommended battery CCA rating.
X X Starter/starter solenoid inoperative Replace the starter or starter solenoid. Eng. S/M
X X Engine harness connector(s) not Disconnect the engine harness connector(s) then W/D
locked tight reconnect it to the controller.
X Fault shutdown Identify and correct the fault condition. Then reset the Operation
fault on the controller.. Section
* Sec./Section - numbered section of this manual; ATS - Automatic Transfer Switch; Eng. - Engine; Gen. - Generator Set; I/M - Installation Manual; O/M - Operation Manual;
M/M – Maintenance Manual; S/M - Service Manual; S/S - Spec Sheet; W/D - Wiring Diagram Manual
† Have an authorized service distributor/dealer perform this service.
115
116
Trouble Symptoms
up
voltage
not start
High fuel
Overheats
inoperative
Starts hard
time and/or
Exercise run
Lacks power
consumption
Excessive or
event records
Displays error
Section or Publication
message/locks
Stops suddenly
abnormal noise
X X X X Air cleaner clogged Clean or replace the filter element. Eng. O/M
X X X X X Engine overload Reduce the electrical load. See the generator set S/S
spec sheet for wattage specifications.
X Exhaust system leak Inspect the exhaust system. Replace damaged or I/M
broken exhaust system components.†
X Exhaust system not securely Inspect the exhaust system. Tighten the loose I/M
installed exhaust system components.†
X X X X Governor inoperative Adjust the governor.† Eng. S/M
X X X X X Engine ECM and/or sensors Troubleshoot the engine ECM and/or sensors.† Eng. O/M, Eng. S/M
Cooling System
X Coolant level low Restore the coolant to normal operating level. M/M or Eng. O/M
X Cooling water pump inoperative Tighten or replace the belt, if applicable. Replace Eng. O/M or S/M
the water pump.
X High temperature shutdown Allow the engine to cool down. Then troubleshoot M/M, orEng. O/M
the cooling system.
X Low coolant level shutdown, if Restore the coolant to normal operating level. M/M or Enigne O/M
equipped
X Thermostat inoperative Replace the thermostat. Eng. S/M
TP-7141
* Sec./Section - numbered section of this manual; ATS - Automatic Transfer Switch; Eng. - Engine; Gen. - Generator Set; I/M - Installation Manual; O/M - Operation Manual;
M/M – Maintenance Manual; S/M - Service Manual; S/S - Spec Sheet; W/D - Wiring Diagram Manual
† Have an authorized service distributor/dealer perform this service.
11/22
Trouble Symptoms
TP-7141
voltage
not start
High fuel
Overheats
Starts hard
and/or event
Lacks power
consumption
Excessive or
11/22
Displays error
Section or
message/locks up
records inoperative
Probable Causes Recommended Actions Reference*
Fuel System
X X Fuel tank empty or fuel valve shut off Add fuel and move the fuel valve to the ON position.
X X X Air in fuel system (diesel only) Bleed the diesel fuel system. Eng. O/M
X X X X Fuel filter restriction Clean or replace the fuel filter. M/M or Eng. O/M
X X X Fuel or fuel injectors dirty or faulty Clean, test, and/or replace the dirty or faulty fuel Eng. S/M
(diesel only) injector.†
X X X X Fuel injection timing out of adjustment Adjust the fuel injection timing.† Eng. S/M
(diesel only)
X X X Fuel feed or injection pump Rebuild or replace the injection pump.† Eng. S/M
inoperative (diesel only)
Lube System
X X X Oil level low Restore the oil level. Inspect the generator set for oil M/M or Eng. O/M
leaks.
X Low oil pressure shutdown Check the oil level. M/M or Eng. O/M
X X X X Crankcase oil type incorrect for Change the oil. Use oil with a viscosity suitable for the M/M or Eng. O/M
ambient temperature operating climate.
* Sec./Section - numbered section of this manual; ATS - Automatic Transfer Switch; Eng. - Engine; Gen. - Generator Set; I/M - Installation Manual; O/M - Operation Manual;
M/M – Maintenance Manual: S/M - Service Manual; S/S - Spec Sheet; W/D - Wiring Diagram Manual
† Have an authorized service distributor/dealer perform this service.
117
118
Section or
8.6
Publication
Trouble Symptoms Probable Causes Recommended Actions Reference*
Display is black/off Controller requires reset Disconnect and reconnect battery voltage to the
controller
Output voltage unstable Voltage regulation calibration incorrect Readjust voltage regulation. † Controller S/M
* Sec./Section - numbered section of this manual; ATS - Automatic Transfer Switch; Eng. - Engine; Gen. - Generator Set; I/M - Installation Manual; O/M - Operation Manual;
M/M – Maintenance Manual; S/M - Service Manual; S/S - Spec Sheet; W/D - Wiring Diagram Manual
† Have an authorized service distributor/dealer perform this service.
Controller Display and Voltage Regulation Troubleshooting Chart
TP-7141
11/22
Section 9. Accessories
Accessories are available to help finalize installation, add convenience to operation and service, and establish state and lo cal
code compliance. This section describes controller-related accessories available at print time of this publication. See Figure 97.
Obtain the most current accessory information from your local authorized service distributor/dealer.
Kit Description
Battery Charger
Input/ Output Modules
Manual Key Switch
Remote Emergency Stop
Remote Serial Annunciator
Shunt Trip Line Circuit Breaker
The battery charger sends a fault message to the APM603 controller in the event of a battery charger fault. See TP -7072, Battery
Charger Installation and Operation Manual, for information about fault conditions and for battery charger operation instructi ons.
The original DIOM provides 8 digital inputs and 4 digital (relay) outputs. The updated D8IOM adds more outputs, providing 8
digital inputs and 8 digital (relay) outputs. See Figure 99 to compare the original and updated designs. Full support of the new
D8IOM requires firmware version 3.6 or later for the APM603 controller and version 1.11 or later for the APM802 controller.
Factory connections
and settings.
DO NOT CHANGE.
Factory connections
and settings.
DO NOT CHANGE
DI0 DIR0
DI1 DIR1
DI2 DIR2
DI3 DIR3
DI4 DIR4
DI5 DIR5
DI6 DIR6
Note: The locations of the input and output connections on the
DI7 DIR7
updated module are different from the original.
11609000401
Outputs
Factory Settings
Digital Inputs/Outputs Module 0 (not configurable) Module 1 Module 2
Input DI0 Power Supply 1 Fault Warning Configurable Configurable
Input DI1 Power Supply 2 Fault Warning Configurable Configurable
Input DI2 Remote Reset Configurable Configurable
Input DI3 Auxiliary Shutdown Configurable Configurable
Input DI4 High Fuel Level Switch Warning Configurable Configurable
Input DI5 Auxiliary Warning Configurable Configurable
Input DI6 Low Oil Level Switch Warning Configurable Configurable
Input DI7 Reserved Factory Use Configurable Configurable
Output DO0 System Ready Configurable Configurable
Output DO1 Low Coolant Temp Configurable Configurable
Output DO2 Not In Auto Configurable Configurable
Output DO3 EPS Supplying Load Configurable Configurable
Output DO4 NA Configurable Configurable
Output DO5 NA Configurable Configurable
Output DO6 NA Configurable Configurable
Output DO7 NA Configurable Configurable
Figure 102 Digital 8 I/O Module Default Settings (Tier 2 and Tier 4 Generator Sets)
Controller
A three-position key switch is available. The key switch allows the controller to be locked in standby mode, which may be required
by some local codes. See Figure 103 for the key switch location.
The RUN, OFF, and AUTO positions on the key switch operate as described below.
• RUN
When the key is moved to the RUN position, the generator set starts and runs. The generator will continue to run until
the key is moved to the OFF or AUTO button position or until a fault condition causes the generator set to shut down.
• OFF
When the key is placed in the OFF position, the generator set shuts down immediately, without running the engine
cooldown cycle. The generator set will not respond to remote start commands when the key is in the OFF position.
• AUTO
Moving the key to the AUTO position places the generator set in Standby mode. The generator set will start and run
when a remote start signal is received. The key can be removed only when the switch is in AUTO, locking the generator
set in standby mode. When the key is in the AUTO position, generator management may cause the generator to stop
and go to a standby state.
Controller Pushbuttons
When the controller is equipped with the optional key switch, the functions of the pushbuttons on the controller are affected.
• For normal starting and stopping, the key switch overrides the pushbuttons on the controller.
o When the key is in the RUN position, pressing OFF/RESET on the controller does not stop the generator set.
o When the key switch is in the OFF position, pressing the RUN button on the controller will not start the generator
set. Pressing AUTO + RUN simultaneously will signal the generator set to start.
• To clear a fault condition, press and hold the OFF/RESET button on the controller for 3 seconds. The key switch does
not clear faults from the controller.
• The Alarm Silence/Lamp Test button function does not change when a key switch is installed.
The Emergency Stop button overrides the key switch and the controller pushbuttons. Pressing the Emergency stop button will
shut down the generator set regardless of the key switch position. To clear the Emergency stop fault from the controller, first
reset the E-stop switch and then press the OFF/RESET button on the controller for 3 seconds. A remote reset signal can be
used, if so configured, to clear the E-Stop fault. The key switch cannot be used to clear the E-Stop fault.
The emergency stop (E-stop) kit allows immediate shutdown of the generator set from a remote location. If the emergency stop
switch is activated, the EMERGENCY STOP lamp lights and the unit shuts down immediately, bypassing the engine cooldown
cycle. Before attempting to restart the generator set, reset the emergency stop switch and reset the generator set by pressing
and holding the OFF/RESET button for 3 seconds.
Two emergency stop kits are available. See Figure 104 and the following instructions.
1. To stop the generator set, pull down on the handle, breaking the glass piece.
2. To reset the emergency stop switch, return the handle to the original position and replace the glass piece with a new
one.
Use the single glass piece located inside the switch for replacement and order additional glass pieces as service parts.
9.4.2 Lockable Emergency Stop Switch
This switch can be locked in the activated position to prevent generator set starting. Use a customer-provided locking device
inserted into the holes in the shroud to lock the switch until the generator set can be operated safely.
Operation
Press the red STOP button to shut down the generator set in an emergency.
Using the emergency stop button bypasses the engine cooldown cycle, stopping the engine immediately. The emergency stop
LED on the RSA III lights (if equipped) and the unit shuts down. The generator set cannot be restarted until the emergency stop
switch(es) is/are reset.
Lockout/Tagout
The emergency stop button can be locked in the STOP position. Insert a lock through two openings in the yellow shroud to
prevent the stop button from being pulled out. See Figure 104. Remove the lock for normal operation.
To reset the E-stop switch, remove the locking device and pull the button out. Reset the controller by pressing and holding the
OFF/RESET button for 3 seconds.
The RSA III meets NFPA 110, Level 1 (2005) applications that require remote controls and alarms be powered by a storage
battery such as the engine starting battery. AC adaptor kit GM62466-KP1 is available when NFPA is not required.
The front panel decals include areas that can be used to identify user-selected fault inputs and identify associated power system
equipment.
An RSA III annunciator can be used for a single generator set or with a combination of a generator set and automatic transfer
switch. In systems using more than a single RSA III, one must be designated as the master device to broadcast to additional
RSA III annunciators, designated as slave devices. Up to five RSA III slave devices can be used with an RSA III master device .
All RSA III annunciators are factory set as the master device, but can be changed to a slave device using a PC and SiteTech™
software that connects to the RSA III front panel via a universal serial bus (USB) connection.
The RSA II and RSA 1000 can be connected with the RSA III provided that the master remote annunciator is an RSA III.
Refer to TT-1625 Remote Serial Annunciator (RSA III) Kits for operation and installation instructions.
A personal computer with SiteTechTM software is required to make the RSA III functional. SiteTech is available to Kohler
authorized distributors and dealers. Refer to TP-6701, SiteTech Software Operation Manual, for more information.
The RSA III kits include components for surface mounting or flush mounting.
Figure 106 shows the status of the system ready LED, generator set running LED, communication status LED, common fault
LED, common fault output, and horn for each fault or status condition.
If a fault occurs, the RSA III horn activates and the corresponding LED illuminates. The following paragraphs describe specific
features of the RSA III.
If the RSA III is used with an Ethernet communication network, order Modbus ® Ethernet converter GM41143-KP2 and refer to
TT-1405 Converters, Connections, and Controller Setup for Network Communication for system installation.
RSA III with Single Generator Set RSA III with Single ATS Control RSA III with Four ATS Controls
A, amp ampere blk. htr. block heater DAC digital to analog converter
ABDC after bottom dead center BMEP brake mean effective pressure dB decibel
AC alternating current bps bits per second dB(A) decibel (A weighted)
A/D analog to digital br. Brass DC direct current
ADC advanced digital control; BTDC before top dead center DCR direct current resistance
analog to digital converter
adj. adjust, adjustment Btu British thermal unit DEF diesel exhaust fluid
ADV advertising dimensional drawing Btu/min. British thermal units per minute deg., ° degree
AGM absorbent glass mat C Celsius, centigrade dept. department
Ah amp-hour cal. Calorie dia. Diameter
AHWT anticipatory high water CAN controller area network DI/EO dual inlet/end outlet
temperature
AISI American Iron and Steel Institute CARB California Air Resources Board DIN Deutsches Institut fur Normung e.
V. (also Deutsche Industrie
Normenausschuss)
ALOP anticipatory low oil pressure CAT5 Category 5 (network cable) DIP dual inline package
alt. alternator CB circuit breaker DPDT double-pole, double-throw
Al aluminum CC crank cycle DPST double-pole, single-throw
ANSI American National Standards cc cubic centimeter DS disconnect switch
Institute (formerly American
Standards Association, ASA)
AO anticipatory only CCA cold cranking amps DVR digital voltage regulator
APDC Air Pollution Control District ccw. Counterclockwise E2PROM, electrically-erasable
EEPROM programmable read-only memory
API American Petroleum Institute CEC Canadian Electrical Code E, emer. emergency (power source)
approx. approximate, approximately cert. certificate, certification, certified EATS Exhaust Aftertreatment System
APU Auxiliary Power Unit cfh cubic feet per hour ECM electronic control module, engine
control module
AQMD Air Quality Management District cfm cubic feet per minute EDI electronic data interchange
AR as required, as requested CG center of gravity EFR emergency frequency relay
AS as supplied, as stated, as CID cubic inch displacement e.g. for example (exempli gratia)
suggested
ASE American Society of Engineers CL centerline EG electronic governor
ASME American Society of Mechanical cm centimeter EGSA Electrical Generating Systems
Engineers Association
assy. Assembly CMOS complementary metal oxide EIA Electronic Industries Association
substrate (semiconductor)
ASTM American Society for Testing com communications (port) EI/EO end inlet/end outlet
Materials
ATDC after top dead center coml commercial EMI electromagnetic interference
ATS automatic transfer switch Coml/Rec Commercial/Recreational emiss. Emission
auto. Automatic conn. Connection eng. Engine
aux. auxiliary cont. continued EPA Environmental Protection Agency
avg. average CPVC chlorinated polyvinyl chloride EPS emergency power system
AVR automatic voltage regulator crit. Critical ER emergency relay
AWG American Wire Gauge CRM Common Rail Manifold ES engineering special, engineered
special
AWM appliance wiring material CSA Canadian Standards Association
bat. Battery CT current transformer ESD electrostatic discharge
BBDC before bottom dead center Cu copper est. estimated
BC battery charger, battery charging cUL Canadian Underwriter’s E-Stop emergency stop
Laboratories
BCA battery charging alternator cu. in. cubic inch etc. et cetera (and so forth)
BCI Battery Council International cw. Clockwise exh. exhaust
BDC before dead center CWC city water-cooled ext. external
BHP brake horsepower cyl. Cylinder F Fahrenheit, female
blk. black (paint color), block (engine) D/A digital to analog FDS Fluid Dosing System
Note:
Two lists are included in the appendix, one for tier 2 generator sets (KD700-KD4000) and a second for tier 4 generator sets
(KD1250-4, KD2500-4, KD3250-4).
Controller Displays as Provided by the Engine ECM
Ambient temperature
Charge air pressure
Charge air temperature
Common rail fuel pressure
Coolant level
Coolant temperature
Crankcase pressure
Engine model number
Engine serial number
Engine speed
Fuel pressure
Fuel consumption rate
Fuel temperature
Intercooler coolant temperature (K175 engines only)
Oil pressure
Oil temperature
Run time hours
A message is sent each time there is a change in a monitored engine condition (i.e. fault becomes active, fault is cleared). Upon
broadcast of this message, the controller will request another message that contains the following information for each fault :
• SPN (Suspect Parameter Number) is a 3-to 5-digit code that represents an engine component. See the Engine
Operation Manual for SPN codes.
• FMI (Failure Mode Indicator) is a two-digit code that represents the type of fault that occurred (i.e. short circuit, value is
high).
Tier 2 Engine Fault Codes (KD700-KD4000) Tier 2 Engine Fault Codes (KD700-KD4000)
Fuel Supply Pressure Severely Low Warning 1 Water In Fuel Unknown Failure Shutdown 11
Fuel Supply Pressure Shorted High Warning 3 Water In Fuel Condition Exists Shutdown 31
Fuel Supply Pressure Shorted Low Warning 4 Oil Pressure Severely Low Shutdown 1
Fuel Supply Pressure Condition Exists Warning 31 Oil Pressure Plausibility Shutdown 2
Water In Fuel Severely High Shutdown 0 Oil Pressure Shorted High Shutdown 3
Water In Fuel Shorted High Shutdown 3 Oil Pressure Shorted Low Shutdown 4
Water In Fuel Open Circuit Shutdown 5 Oil Pressure Condition Exists Shutdown 31
Crankcase Pressure Severely High Shutdown 0 Rail 1 Pressure Condition Exists Shutdown 31
Injector 15 Shorted High Warning 3 Inlet Air Heater Grounded Circuit Warning 6
Injector 15 Shorted Low Warning 4 Inlet Air Heater Unknown Failure Warning 11
Injector 15 Open Circuit Warning 5 Inlet Air Heater 2 Shorted High Warning 3
Injector 15 Abnormal Signal Warning 8 Inlet Air Heater 2 Shorted Low Warning 4
Injector 16 Shorted High Warning 3 Inlet Air Heater 2 Grounded Circuit Warning 6
Injector 16 Shorted Low Warning 4 Inlet Air Heater 2 Unknown Failure Warning 11
Tier 4 Engine Fault Codes (KD1250-4, KD2500-4, KD3250-4) Tier 4 Engine Fault Codes (KD1250-4, KD2500-4, KD3250-4)
Fuel Supply Pressure Shorted High Warning 3 Barometric Pressure Shorted High Warning 3
Fuel Supply Pressure Shorted Low Warning 4 Barometric Pressure Grounded or Warning 30
Open Circuit
Fuel Supply Pressure Condition Exists Warning 31 Barometric Pressure Condition Exists Warning 31
Water In Fuel Severely High Shutdown 0 Coolant Temperature Severely High Shutdown 0
Water In Fuel Shorted High Shutdown 3 Coolant Temperature Shorted High Shutdown 3
Water In Fuel Shorted Low Shutdown 4 Coolant Temperature Shorted Low Shutdown 4
Water In Fuel Open Circuit Shutdown 5 Coolant Temperature Open Circuit Shutdown 5
Water In Fuel Unknown Failure Shutdown 11 Coolant Temperature High Warning 15
Water In Fuel Condition Exists Shutdown 31 Coolant Temperature Condition Exists Shutdown 31
Oil Pressure Severely Low Shutdown 1 Coolant Level Low Shutdown 1
Oil Pressure Plausibility Shutdown 2 Coolant Level Shorted High Shutdown 3
Oil Pressure Shorted High Shutdown 3 Coolant Level Shorted Low Shutdown 4
Oil Pressure Shorted Low Shutdown 4 Coolant Level Unknown Failure Shutdown 11
Oil Pressure Low Warning 17 Coolant Level Condition Exists Shutdown 31
Oil Pressure Condition Exists Shutdown 31 Rail 1 Pressure Severely High Shutdown 0
Crankcase Pressure Severely High Shutdown 0 Rail 1 Pressure Shorted High Shutdown 3
Crankcase Pressure Shorted High Shutdown 3 Rail 1 Pressure Shorted Low Shutdown 4
Crankcase Pressure Shorted Low Shutdown 4 Rail 1 Pressure Condition Exists Shutdown 31
Crankcase Pressure High Warning 15 Ambient Air Shorted High Warning 3
Temperature
Crankcase Pressure Condition Exists Shutdown 31 Ambient Air Shorted Low Warning 4
Temperature
Intake Manifold Severely High Shutdown 0
Pressure Ambient Air Open Circuit Warning 5
Temperature
Intake Manifold Shorted High Shutdown 3
Pressure Ambient Air Condition Exists Warning 31
Temperature
Intake Manifold Shorted Low Shutdown 4
Pressure Fuel Temperature Severly High Warning 0
Intake Manifold High Warning 15
Fuel Temperature Shorted High Warning 3
Pressure
Intake Manifold Condition Exists Shutdown 31 Fuel Temperature Shorted Low Warning 4
Pressure
Intake Manifold Severely High Shutdown 0 Fuel Temperature Open Circuit Warning 5
Temperature
Intake Manifold Shorted High Shutdown 3 Fuel Temperature Condition Exists Warning 31
Temperature
Intake Manifold Shorted Low Shutdown 4 Oil Temperature Severly High Shutdown 0
Temperature Oil Temperature Shorted High Warning 3
Intake Manifold Open Circuit Shutdown 5
Temperature Oil Temperature Shorted Low Warning 4
Intake Manifold High Warning 15
Temperature Oil Temperature Open Circuit Warning 5
Intake Manifold Condition Exists Shutdown 31
Temperature Oil Temperature High Warning 15
Air Filter Pressure Severely High Warning 0
Oil Temperature Condition Exists Warning 31
The controller has built-in thermal protection for the alternator. This feature functions similarly to a thermal circuit breaker. When
the output current exceeds the nominal rating for a short period of time the condition causes the fault shutdown. The amount of
time at which current is over the rating is inversely related to the amount of current above the nominal rating. In other words, the
higher the current, the shorter the acceptable time.
The current and time limits are defined by actual test data and are maintained in the personality parameter file. Alth ough the
equation for detecting a fault is proprietary, some of the important limits are shown below for informational purposes.
Rated Current Time Delay
200% 40 seconds
300% 10 seconds
425% 5 seconds
950% 1 second
Use the log below to keep a cumulative record of operating hours on your generator set and the dates required services were
performed. Enter hours to the nearest quarter hour.
Operating Hours Service Record
Total
Date Run Hours Run Hours Service Date Service