Nothing Special   »   [go: up one dir, main page]

Dpcompact Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 50

Product Data Sheet

00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Rosemount Compact Orifice
Flowmeter Series
INTEGRATED DESIGN FOR LIMITED
STRAIGHT PIPE RUN, CLOSED LOOP
CONTROL, AND GENERAL PURPOSE
MONITORING APPLICATIONS
• Reduced installation cost compared to a
traditional orifice plate
• Accurate and repeatable
• Easy-to-install direct mount assembly
• Self-centering
• Based on ASME/ISO corner tap design
• Patented technology

Content
The Rosemount 405 Compact Orifice Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Rosemount DP-Flow Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Rosemount 3051SFC Compact Orifice Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
Rosemount 3095MFC Compact Orifice Mass Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . page 20
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 20
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 28
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29
Rosemount 405 Compact Orifice Primary Element. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 32
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 32
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 36
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 38
HART Configuration Data Sheet (CDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
FOUNDATION fieldbus™ Configuration Data Sheet (CDS) . . . . . . . . . . . . . . . . . . . . . . . . . . page 43
Fluid Data Sheet (FDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 46

www.rosemount.com
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

The Rosemount 405 Compact Orifice Series


Best-in-Class Integrated DP Flowmeters Rosemount pressure transmitters
By integrating Rosemount pressure transmitters with combined with the Rosemount 405 Compact
the 405 Compact Orifice Series primary element, Orifice create Best-in-Class Flowmeters
Rosemount provides the highest performing DP
Flowmeters. This fully integrated flowmeter 3095MFC Compact
Orifice Mass Flowmeter
eliminates the need for fittings, tubing, valves,
adapters, manifolds, and mounting brackets, thereby
reducing welding and installation time. 405C

Less Expensive than an Orifice Plate Installation


Direct mounting minimizes total installed cost by
reducing engineering, procurement, labor, and
material expenditures while offering unsurpassed
utility.
Direct Mount
405P
A 3-valve isolation manifold and 1-in (25 mm) thick
wafer-style body allows direct mounting while
eliminating field connections between the process
and the differential pressure-measuring device. The 3051SFC Compact
integral configuration results in a robust, inexpensive, Orifice Flowmeter
and easy-to-install assembly.
Based on ASME/ISO Corner Tap Design
Accurate and Repeatable The incorporation of design features from proven
The 405C Conditioning Orifice is ideal for limited pipe standards results in a product that performs in a
run measurements in gas, liquid, or steam predictable manner and operates on well-known
applications (8-in. (200 mm) nominal diameter and principles.
smaller lines). The 405C Conditioning Orifice delivers
consistent and accurate measurements one would Advanced PlantWeb® Functionality
expect from traditional orifice plate technology. Rosemount orifice flowmeters power
PlantWeb through a scalable
Centering Mechanism architecture, advanced diagnostics, and
Improper centering of any orifice type device can MultiVariable capabilities. This reduces
cause an error of up to ±5% in small line sizes. A operational and maintenance
centering mechanism independent of flange rating is expenditures while improving throughput
standard with the 405 Compact Orifice Series. and utilities management.

Rosemount DP-Flow Solutions


Annubar® Flowmeter Series: Rosemount Integral Orifice Flowmeter Series: Rosemount 3051SFP
3051SFA ProBar®, 3095MFA Mass ProBar®, 485, ProPlate®, 3095MFP Mass ProPlate, and 1195
and 285 These integral orifice flowmeters eliminate the inaccuracies that
The state-of-the-art, fifth generation Rosemount 485 Annubar become more pronounced in small orifice line installations. The
combined with the 3051S or 3095 MultiVariable transmitter creates completely assembled, ready to install flowmeters reduce cost and
simplify installation.
an accurate, repeatable and dependable insertion-type flowmeter.
The Rosemount 285 provides a commercial product offering for
your general purpose applications. Orifice Plate Primary Element Systems: Rosemount
1495 and 1595 Orifice Plates, 1496 Flange Unions and
Compact Orifice Flowmeter Series: Rosemount 1497 Meter Sections
3051SFC, 3095MFC, and 405 A comprehensive offering of orifice plates, flange unions and
Compact Orifice Flowmeters can be installed between existing meter sections that is easy to specify and order. The 1595
flanges, up to a Class 600 (PN100) rating. In tight fit applications, Conditioning Orifice provides superior performance in tight fit
a conditioning orifice plate version is available, requiring only two applications.
diameters of straight run upstream.

2
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

405 Compact Orifice Series Selection Guide


Rosemount 3051SFC Compact Orifice Flowmeter
See ordering information on page 16.
• Combines the Rosemount 3051S scalable pressure
transmitter with the 405 Compact Orifice Primary
• Accuracy up to ±0.80% of volumetric rate
• Remote display and interface assembly enables direct mounting
with “at-grade” operator interface
• FOUNDATION® fieldbus protocol available
• Ideal fluid type: liquid

3051SFC Compact
Orifice Flowmeter
Rosemount 3095MFC Compact Orifice Mass Flowmeter
See ordering information on page 29.
• Combines the Rosemount 3095MV MultiVariable
mass flow transmitter with the 405 Compact Orifice Primary
• Accuracy up to ±0.70% of mass flow rate
• Measures differential pressure, static pressure,
and process temperature (remotely) all in one flowmeter assembly
• Dynamically calculates compensated mass flow
• Ideal fluid types: gas and steam

3095MFC Compact Orifice


Mass Flowmeter

Rosemount 405 Compact Orifice Primary


See ordering information on page 38.
• Integral manifold head allows direct
mounting of DP transmitters
• Ideal fluid types: liquid, gas, and steam
• Accuracy up to ±0.5% of discharge coefficient uncertainty
• Direct mounting capability to ANSI 600# rating
405C Conditioning 405P Compact
• Self-centering alignment ring Orifice Orifice

3
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Rosemount 3051SFC Compact Orifice Flowmeter


SPECIFICATIONS
Performance Functional
System Reference Accuracy Service
Percent (%) of volumetric flow rate • Liquid
TABLE 1. 3051SFC Compact Orifice Flowmeter • Gas
Ultra for • Steam
Classic Ultra Flow
(8:1 flow (8:1 flow (14:1 flow 4–20 mA/HART
Type Beta turndown) turndown) turndown) Zero and Span Adjustment
0.4 ±1.05% ±0.85% ±0.80% Zero and span values can be set anywhere within the range.
3051SFCC
0.65 ±1.35% ±1.20% ±1.15% Span must be greater than or equal to the minimum span.
0.4
3051SFCP(1) ±2.45% ±2.35% ±2.30% Output
0.65(4)
Two-wire 4–20 mA is user-selectable for linear or square root
0.4
3051SFCP(2) ±2.00% ±1.90% ±1.85% output. Digital process variable superimposed on 4–20 mA
0.65(4)
signal, available to any host that conforms to the HART
0.4
3051SFCP(3) ±1.55% ±1.45% ±1.40% protocol.
0.65(4)
Power Supply
(1) Line sizes 1/2-in. (15mm).
External power supply required.
(2) Line sizes 1-in. to 1 1/2-in. (25mm to 40mm). Standard transmitter (4–20 mA): 10.5 to 42.4 V dc with no load
(3) Line sizes 2-in. to 12-in. (50mm to 300mm). 3051S HART Diagnostics transmitter: 12 to 42 Vdc with no load

(4) For 0.65 beta and ReD< 10,000 add an additional ± 0.5% to the
Discharge Coefficient Uncertainty.

Repeatability
±0.1%

Line Sizes
• 1/2-in.(15 mm) – not available for the 3051SFCC
• 1-in. (25 mm) – not available or the 3051SFCC
• 11/2-in. (40 mm) – not available for the 3051SFCC
• 2-in. (50 mm)
• 3-in. (80 mm)
• 4-in. (100 mm)
• 5-in (125 mm)
• 6-in. (150 mm)
• 8-in. (200 mm)
• 10-in. (250 mm)
• 12-in (300 mm)

Performance Statement Assumptions


• Measured pipe I.D

Sizing
Contact an Emerson Process Management representative for
assistance. A Configuration Data Sheet is required prior to order
for application verification.

4
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Load Limitations FOUNDATION fieldbus Parameters
Maximum loop resistance is determined by the voltage level of Schedule Entries 14 (max.)
the external power supply, as described by: Links 30 (max.)
Virtual Communications Relationships (VCR) 20 (max.)
Standard Transmitter
Standard Function Blocks
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
Resource Block
1387
• Contains hardware, electronics, and diagnostic information.
Load (Ohms)

1000 Transducer Block


• Contains actual sensor measurement data including the
500 sensor diagnostics and the ability to trim the pressure
Operating
sensor or recall factory defaults.
Region
0 LCD Block
10.5 20 30 • Configures the local display.
Voltage (V dc) 42.4
2 Analog Input Blocks
The HART communicator requires a minimum • Processes the measurements for input into other function
loop resistance of 250Ω for communication. blocks. The output value is in engineering or custom units
and contains a status indicating measurement quality.
3051S HART Diagnostics Transmitter (option code DA1)
PID Block with Auto-tune
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 12.0)
• Contains all logic to perform PID control in the field including
1322 cascade and feedforward. Auto-tune capability allows for
superior tuning for optimized control performance.
Load (Ohms)

1000
Backup Link Active Scheduler (LAS)
The transmitter can function as a Link Active Scheduler if the
500 Operating current link master device fails or is removed from the
Region segment.
0 Software Upgrade in the Field
12.0 20 30
42.4 Software for the 3051S with FOUNDATION fieldbus is easy to
Voltage (V dc)
upgrade in the field using the FOUNDATION fieldbus Common
The HART communicator requires a minimum Device Software Download procedure.
loop resistance of 250Ω for communication.
PlantWeb Alerts
Enable the full power of the PlantWeb digital architecture by
ASP™ Diagnostics Suite for HART (Option Code DA1)
diagnosing instrumentation issues, communicating advisory,
The 3051S provides Abnormal Situation Prevention indication
maintenance, and failure details, and recommending a
for a breakthrough in diagnostic capability. The New 3051S solution.
ASP™ Diagnostics Suite for HART includes Statistical
Process Monitoring (SPM), variable logging with time stamp Advanced Control Function Block Suite
and advanced process alerts. The enhanced EDDL graphic (Option Code A01)
display provides an intuitive and user-friendly interface to Input Selector Block
better visualize these diagnostics. • Selects between inputs and generates an output using
The integral SPM technology calculates the mean and specific selection strategies such as minimum, maximum,
standard deviation of the process variable 22 times per midpoint, average, or first “good.”
second and makes them available to the user. The 3051S Arithmetic Block
uses these values and highly flexible configuration options for
• Provides pre-defined application-based equations including
customization to detect many user-defined or application flow with partial density compensation, electronic remote
specific abnormal situations (e.g. detecting plugged impulse seals, hydrostatic tank gauging, ratio control and others.
lines and fluid composition change). Variable logging with time
Signal Characterizer Block
stamp and advanced process alerts capture valuable process
and sensor data to enable quick troubleshooting of application • Characterizes or approximates any function that defines an
and installation issues. input/output relationship by configuring up to twenty X, Y
coordinates. The block interpolates an output value for a
FOUNDATION fieldbus given input value using the curve defined by the configured
coordinates.
Power Supply
Integrator Bock
External power supply required; transmitters operate on 9.0 to • Compares the integrated or accumulated value from one or
32.0 V dc transmitter terminal voltage. two variables to pre-trip and trip limits and generates
Current Draw discrete output signals when the limits are reached. This
17.5 mA for all configurations (including LCD display option) block is useful for calculating total flow, total mass, or
volume over time.

5
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Output Splitter Block Process Temperature Limits


• Splits the output of one PID or other control block so that the Direct Mount Transmitter
PID will control two valves or other actuators. • 450 °F (232 °C)
Control Selector Block Remote Mount Transmitter
• Selects one of up to three inputs (highest, middle, or lowest) • 850 °F (454 °C) – Stainless Steel
that are normally connected to the outputs of PID or other
control function blocks. Transmitter Temperature Limits
Ambient
Block Execution Time • –40 to 185 °F (–40 to 85 °C)
Resource - • With Integral Display(1): –40 to 175 °F (–40 to 80 °C)
Storage
Transducer -
• –50 to 230 °F (–46 to 110 °C)
LCD Block -
• With Integral Display: –40 to 185 °F (–40 to 85 °C)
Analog Input 1, 2 20 milliseconds
• With Wireless Output (Code X): –40 to 185 °F (–40 to 85 °C)
PID with Auto-tune 35 milliseconds
Input Selector 20 milliseconds Differential Pressure Limits
Arithmetic 20 milliseconds Maximum differential pressure (DP) up to 800 inH2O.
Signal Characterizer 20 milliseconds
Integrator 20 milliseconds Pressure Limits(2)
Output Splitter 20 milliseconds Direct Mount Transmitter
Control Selector 20 milliseconds • Pressure retention per ANSI B16.5 600# or DIN PN

Fully Compensated Mass Flow Block (Option Code H01)


Static Pressure Limits
Calculates fully compensated mass flow based on differential • Range 1A: Operates within specification between static line
pressure with external process pressure and temperature
pressures of 0.5 psia to 2000 psig (0.03 to 138 bar)
measurements over the fieldbus segment. Configuration for the
• Ranges 2A– 3A: Operates within specifications between
mass flow calculation is easily accomplished using the
static line pressures of 0.5 psia and 3626 psig (0.03 bar-A to
Rosemount 3095 Engineering Assistant.
250 bar-G)
ASP™ Diagnostics Suite for FOUNDATION fieldbus (Option
Code D01) Vibration Limits
The 3051S ASP™ Diagnostics Suite for FOUNDATION fieldbus Qualified per IEC61298-3 (1998) for field with high vibration level or
provides Abnormal Situation Prevention indication and enhanced pipeline with high vibration level (10-60Hz 0.21mm displacement
EDDL graphic displays for easy visual analysis. peak amplitude / 60 - 500Hz 3g).
The integral Statistical Process Monitoring (SPM) technology The weight and length of the transmitter assembly shall not exceed
calculates the mean and standard deviation of the process 5.8 lbs and 7.75-in.
variable 22 times per second and makes them available to the
user. The 3051S uses these values and highly flexible Burst Pressure Limits
configuration options for customization to detect many
Coplanar or traditional process flange
user-defined or application specific abnormal situations (e.g.
detecting plugged impulse lines and fluid composition change). • 10000 psig (689,5 bar)

Wireless Self-Organizing Networks


Output
Wireless enabled HART.
Transmit Rate
User selectable, 15 sec. to 60 min.
Power Module
Replaceable, Intrinsically Safe Lithium-thionyl chloride Power
Module with polybutadine terephthalate (PBT) enclosure.
Five-year life at one minute transmit rate: ten-year life at ten
minute transmit rate.(1)
(1) Reference conditions are 70 °F (21 °C), and routing data for three
additional network devices.
NOTE
Continuous exposure to ambient temperature limits, -40 °F (-40
°C) or 185 °F (85 °C), may reduce specified life by less than 20
percent.

(1) LCD display may not be readable and LCD updates will be
slower at temperatures below -4 °F (-20 °C).
(2) Static pressure selection may effect pressure limitations.

6
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Overpressure Limits Failure Mode Alarm
Transmitters withstand the following limits without damage: HART 4-20mA (output option codes A and B)
• Range 1A: 2000 psig (138 bar) If self-diagnostics detect a gross transmitter failure, the analog
• Ranges 2A–3A: 3626 psig (250 bar) signal will be driven offscale to alert the user. Rosemount
TABLE 2. Overpressure Limits(1) standard (default), NAMUR, and custom alarm levels are
Carbon Steel Stainless available (see Table 3).
Standard Type Rating Steel Rating High or low alarm signal is software-selectable or
ANSI/ASME Class 150 285 (20) 275 (19) hardware-selectable via the optional switch (option D1).
ANSI/ASME Class 300 740 (51) 720 (50) TABLE 3. Alarm Configuration
ANSI/ASME Class 600 1480 (102) 1440 (99) High Alarm Low Alarm
At 100 °F (38 °C), the rating decreases with increasing temperature.
DIN PN 10/40 580 (40) 580 (40) Default ≥ 21.75 mA ≤ 3.75 mA
DIN PN 10/16 232 (16) 232 (16) NAMUR compliant(1) ≥ 22.5 mA ≤ 3.6 mA
DIN PN 25/40 580 (40) 580 (40) Custom levels(2) 20.2 - 23.0 mA 3.6 - 3.8 mA
At 248 °F (120 °C), the rating decreases with increasing temperature.
(1) Analog output levels are compliant with NAMUR
(1) Carbon Steel and Stainless Steel Ratings are measured in recommendation NE 43, see option codes C4 or C5.
psig (bar).
(2) Low alarm must be 0.1 mA less than low saturation and high
alarm must be 0.1 mA greater than high saturation.
Humidity Limits
• 0–100% relative humidity 3051S Safety-Certified Transmitter Failure Values
Safety accuracy: 2.0%(1)
Turn-On Time Safety response time: 1.5 seconds
Performance within specifications less than 2 seconds (typical)
(1) A 2% variation of the transmitter mA output is allowed before
after power is applied to the transmitter
a safety trip. Trip values in the DCS or safety logic solver
should be derated by 2%.
Damping
Analog output response to a step input change is user-selectable
from 0 to 60 seconds for one time constant. This software damping
is in addition to sensor module response time
Dynamic Performance(1)

(1)
4 - 20 mA (HART®)(2) Fieldbus protocol(3) Typical Transmitter Response Time
(4)
Total Response Time (Td + Tc) :
3051S_C, Ranges 2A - 3A: 100 milliseconds 152 milliseconds
Range 1A: 255 milliseconds 307 milliseconds Transmitter Output vs. Time

Dead Time (Td)(5)


Pressure Released
45 milliseconds (nominal) 97 milliseconds
Td = Dead Time
Update Rate 3051S 22 times per second 22 times per second Td Tc
Tc = Time Constant
100%
Response Time = Td +Tc

63.2% of Total
36.8%
Step Change

0%
Time

(1) Does not apply to wireless output code X. See “Wireless Self-Organizing Networks” on page 6 for wireless transmit rate.

(2) Dead time and update rate apply to all models and ranges; analog output only

(3) Transmitter fieldbus output only, segment macro-cycle not included.


(4) Nominal total response time at 75 °F (24 °C) reference conditions. For option code DA1, add 45 milliseconds (nominal) to 4-20 mA (HART®) total
response time values.

(5) For option code DA1, dead time (Td) is 90 milliseconds (nominal).

7
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Physical Process-Wetted Parts


Integral Manifolds
Temperature Measurement • 316 SST
Remote RTD • Hastelloy C-276
• 100 Ohm platinum with 1/2-in. NPT nipple and union (078 Remote Manifolds
series with Rosemount 644 housing) • 316 SST
Model 0078D21N00A025T32Ex
• Hastelloy C-276
Connection Head: 00644-4410-0011
Transmitter Vent Valves and Process Flanges
• Standard RTD cable is shielded armored cable, length is 12
feet (3.66 m) • 316 SST

Thermowell with Remote RTD • Hastelloy C-276

• 1/2-in. x 1/2-in. NPT, 316 SST • Glass-filled PTFE O-rings


Process Isolating Diaphragms
NOTE • 316L SST
Remote temperature measurement is not available for 1/2-in., 1-in., • Hastelloy C-276
and 11/2-in. sizes. Integral Manifold O-Rings
• PTFE/Graphite
Electronic Connections for Remote Mount
1
/2–14 NPT, G1/2, and M20 × 1.5 (CM20) conduit. HART interface Non-Wetted Parts
connections fixed to terminal block for output code A
Sensor Module Fill Fluid
Material of Construction • Silicone oil

Body/Plate • Inert Fill optional

• 316 SST Cover O-rings

• 50 micro-inch Ra surface finish • Buna-N

Manifold Head/Valves Remote Mounting Brackets

• 316 SST • SST

Flange Studs and Nuts Electronic Housing

• Customer supplied • Low copper aluminum, NEMA 4x, IP65

• Available as a spare part • SST (optional)

Transmitter Connection Studs and Nuts Paint

• Studs– A193 Grade B8M. • Polyurethane


Bolts
• Nuts– A194 Grade 8M.
• CS
Gasket and O-rings
• Gaskets are customer supplied.
Transmitter Connections
• Durlon 8500 fiber gaskets are recommended. Consult an
Remote Mount
Emerson Process Management representative for use with
other gaskets. • Available with 1/4-in. (standard) or 1/2-in. (option code E)
connections
• Available as a spare part
Orifice Type
NOTE • Square edged, Wafer style
Gaskets and O-rings must be replaced when the 405 is Orifice Pressure Taps
disassembled. • Corner

Process Connections
Mounts between the following flange configurations:
ASME B16.5
(ANSI) DIN JIS
Class 150 PN16 (option code G) 10k (option code B)
Class 300 PN40 (option code H) 20k (option code R)
Class 600 PN100 (option code H) 40k (option code S)

ANSI alignment ring is included as standard when ordering.

8
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Typical Orifice Hole Sizes (For 3051SFCC) 3051SFC Weight
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
is equal to 2 x typical orifice hole size (dC = 2d). The table below 1
/2-in. (15 mm) 10.7 (4.58) 7.5 (3.70)
shows the diameter of each of the four typical orifice holes.
1-in. (25 mm) 11.45 (5.19) 8.25 (4.07)
TABLE 4. β = 0.4 (1)(2) 11/2-in. (40 mm) 11.95 (5.42) 8.75 (4.32)
Line Size 3051SFCC 3051SFCP 2-in. (50 mm) 12.20 (5.53) 9.00 (4.44)
1 3-in. (80 mm) 14.20 (6.44) 11.00 (5.43)
/2-in. (15 mm) Not Available 0.249 (6.325)
1-in. (25 mm) Not Available 0.420 (10.668) 4-in. (100 mm) 16.70 (7.57) 13.50 (6.67)
11/2-in. (40 mm) Not Available 0.644 (16.358) 5-in. (125 mm) 18.45 (8.37) 15.25 (7.53)
2-in. (50 mm) 0.413 (10.490) 0.827 (21.006) 6-in. (150 mm) 20.20 (9.16) 17.00 (8.40)
3-in. (80 mm) 0.614 (15.596) 1.227 (31.166) 8-in. (200 mm) 25.45 (11.54) 22.25 (10.99)
4-in. (100 mm) 0.805 (20.447) 1.610 (40.894) 10-in (250 mm) 30.70 (13.92) 27.50 (13.58)
5-in. (125 mm) 1.009 (25.629) 2.019 (51.283) 12-in (300 mm) 36.70 (16.64) 33.50 (16.54)
6-in. (150 mm) 1.213 (30.810) 2.426 (61.620) (1) Measurement in lb (kg).
8-in. (200 mm) 1.596 (40.538) 3.192 (81.077)
(2) Includes 3051S Coplanar PlantWeb housing transmitter.
10-in. (250 mm) 2.004 (50.902) 4.008 (101.80)
12-in. (300 mm) 2.400 (60.960) 4.800 (121.92) 3095MFC Weight
TABLE 5. β = 0.65(1)(2) Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
1/2-in.(15 mm) 9.50 (4.69) 6.3 (3.11)
Line Size 3051SFCC 3051SFCP
1/2-in.(15 mm) Not Available 0.404 (10.262) 1-in. (25 mm) 10.25 (5.06) 7.05 (3.48)
1-in. (25 mm) Not Available 0.682 (17.323) 11/2-in. (40 mm) 10.75 (5.31) 7.55 (3.73)
11/2-in. (40 mm) Not Available 1.047 (26.594) 2-in. (50 mm) 11.00 (5.43) 7.80 (3.85)
2-in. (50 mm) 0.620 (15.748)(3) 1.344 (34.138) 3-in. (80 mm) 13.00 (6.42) 9.80 (4.84)
3-in. (80 mm) 0.997 (25.324) 1.994 (50.648) 4-in. (100 mm) 15.50 (7.65) 12.30 (6.07)
4-in. (100 mm) 1.308 (33.223) 2.617 (66.472) 5-in. (125 mm) 17.25 (8.52) 14.05 (6.94)
5-in. (125 mm) 1.640 (40.640) 3.281 (83.34) 6-in. (150 mm) 19.00 (9.38) 15.80 (7.80)
6-in. (150 mm) 1.971 (50.063) 3.942 (100.127) 8-in. (200 mm) 24.25 (11.98) 21.05 (10.40)
8-in. (200 mm) 2.594 (65.888) 5.188 (131.775) 10-in (250 mm) 29.50 (14.57) 26.30 (12.9)
10-in. (250 mm) 3.257 (82.728) 6.513 (165.43) 12-in (300 mm) 35.50 (17.53) 32.30 (15.95)
12-in. (300 mm) 3.900 (99.060) 7.800 (198.120) (1) Measurement in lb (kg).
(1) Measurement is in inches (millimeters) (2) Includes 3095 MultiVariable transmitter.
(2) Tolerance = ±0.002-in. 405 Weight
(3) Beta (β) = 0.60-in. (15.24 mm) for 2-in. line size only. Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
1/2-in.(15 mm) 3.50 (1.73) 7.5 (3.70)
1-in. (25 mm) 4.25 (2.10) 8.25 (4.07)
11/2-in. (40 mm) 4.75 (2.34) 8.75 (4.32)
2-in. (50 mm) 5.00 (2.47) 9.00 (4.44)
3-in. (80 mm) 7.00 (3.45) 11.00 (5.43)
4-in. (100 mm) 9.50 (4.69) 13.50 (6.67)
5-in. (125 mm) 11.25 (5.55) 15.25 (7.53)
6-in. (150 mm) 13.00 (6.41) 17.00 (8.40)
8-in. (200 mm) 18.25 (9.00) 22.25 (10.99)
10-in (250 mm) 23.50 (11.59) 27.50 (13.58)
12-in (300 mm) 29.50 (14.55) 33.50 (16.54)
(1) Measurement in lb (kg).

(2) Includes 405 Direct Mount option D3.

9
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Installation Considerations Flowmeter Orientation


Flowmeter orientation for both 3051SFC Conditioning Compact
Straight Run Requirements Orifice and standard Compact Orifice.
TABLE 6. 3051SFCC Straight Pipe Requirements(1)
Beta 0.40 0.65 Gas (Horizontal)
Reducer (1 line size) 2 2
Single 90° bend or tee 2 2
Upstream (inlet)
side of primary

Two or more 90 ° bends in the same 2 2


plane
Two or more 90° bends in different 2 2
plane 120°
Up to 10° of swirl 2 2
Butterfly valve (75% to 100% open) 2 N/A 30°
Downstream (outlet) side of primary 2 2

TABLE 7. 3051SFCP Straight Pipe Requirements(1)(2)(3) 30°


Beta 0.40 0.65
Reducer (1 line size) 5 12 Liquid and Steam (Horizontal)
(2)(3)
Single 90° bend or tee 16 44
Upstream (inlet)
side of primary

Two or more 90 ° bends 10 44


in the same plane
Two or more 90° bends 50 60
in different plane 50°
Expander 12 28
Ball / Gate valve fully open 12 18
Downstream (outlet) side of primary 6 7 50°
(1) Consult an Emerson Process Management representative if 80°
disturbance is not listed.

(2) Recommended lengths represented in pipe diameters per


ISO 5167.

(3) Refer to ISO 5167 for recommended lengths when using flow
straighteners.
Gas (Vertical)

Pipe Orientation
Pipe orientation for both 3051SFCC Compact Conditioning and
FLOW

standard 3051SFCP Compact Orifice.


Process(1)
Orientation/ Flow Direction Gas Liquid Steam
Horizontal D/R D/R D/R
Vertical Up R D/R R
Vertical Down D/R NR NR 360°
(1) D = Direct mount acceptable (recommended) Liquid (Vertical)
R = Remote mount acceptable
NR = Not recommended
360°
Pipe Centering
Improper centering of any orifice type device can cause an error of
up to ±5% in small line sizes. A centering mechanism (centering
ring) independent of flange rating comes standard with the 405
Compact Orifice Series.
FLOW

3051SFCDC 3051SFCDP
Conditioning Compact
Orifice Orifice

10
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

PRODUCT CERTIFICATIONS
I5/IE Intrinsically Safe for use in Class I, Division 1, Groups A, B,
C, and D; Class II, Division 1, Groups E, F, and G; Class III,
Approved Manufacturing Locations Division 1; Class I, Zone 0 AEx ia IIC when connected in
Rosemount Inc. — Chanhassen, Minnesota USA accordance with Rosemount drawing 03151-1006;
Emerson Process Management GmbH & Co. — Wessling, Non-incendive for Class I, Division 2, Groups A, B, C, and D
Germany Enclosure Type 4X
Emerson Process Management Asia Pacific Private Limited — For entity parameters see control drawing 03151-1006.
Singapore
Beijing Rosemount Far East Instrument Co., LTD — Beijing, China Canadian Standards Association (CSA)
E6 Explosion-proof for Class I, Division 1, Groups B, C, and D;
European Directive Information Dust-Ignition-Proof for Class II and Class III, Division 1,
Groups E, F, and G; suitable for Class I, Division 2, Groups
The EC declaration of conformity for all applicable European
A, B, C, and D, when installed per Rosemount drawing
directives for this product can be found at www.rosemount.com. A
03151-1013, CSA Enclosure Type 4X; conduit seal not
hard copy may be obtained by contacting an Emerson Process
required.
Management representative.
I6/IF Intrinsically Safe for Class I, Division 1, Groups A, B, C, and
ATEX Directive (94/9/EC) D when connected in accordance with Rosemount drawings
Emerson Process Management complies with the 03151-1016;
ATEX Directive. For entity parameters see control drawing 03151-1016.
European Pressure Equipment Directive (PED) (97/23/EC)
Models 3051S_CA4; 3051S_CD2, 3, 4, 5; (also with P9 option) European Certifications
Pressure Transmitters — QS Certificate of Assessment - I1/IA ATEX Intrinsic Safety
EC No. PED-H-20, Module H Conformity Assessment Certificate No.: BAS01ATEX1303X II 1G
All other Model 3051S Pressure Transmitters EEx ia IIC T4 (Ta = -60 °C to 70 °C) -HART/Remote
— Sound Engineering Practice Display/Quick Connect/HART Diagnostics
Transmitter Attachments: Diaphragm Seal - Process Flange - EEx ia IIC T4 (Ta = -60 °C to 70 °C) -FOUNDATION fieldbus
EEx ia IIC T4 (Ta = -60 °C to 40 °C) -FISCO
Manifold — Sound Engineering Practice
IP66
Primary Elements, Flowmeter
1180
— See appropriate Primary Element QIG
TABLE 8. Input Parameters
Electro Magnetic Compatibility (EMC) (89/336/EEC) Loop / Power Groups
All Models: EN 50081-1: 1992; EN 50082-2:1995;
Ui = 30 V HART / FOUNDATION fieldbus/ Remote
EN 61326-1:1997 – Industrial
Display / Quick Connect / HART
Diagnostics
Ordinary Location Certification for FM Ui = 17.5 V FISCO
As standard, the transmitter has been examined and tested to Ii = 300 mA HART / FOUNDATION fieldbus/ Remote
determine that the design meets basic electrical, mechanical, and Display / Quick Connect / HART
fire protection requirements by FM, a nationally recognized testing Diagnostics
laboratory (NRTL) as accredited by the Federal Occupational Ii = 380 mA FISCO
Safety and Health Administration (OSHA).
Pi = 1.0 W HART / Remote Display / Quick Connect /
HART Diagnostics
Pi = 1.3 W FOUNDATION fieldbus
Hazardous Locations Certifications Pi = 5.32 W FISCO
Ci = 30 nF SuperModule Platform / Quick Connect
North American Certifications Ci = 11.4 nF HART / HART Diagnostics
FM Approvals Ci = 0 FOUNDATION fieldbus / Remote Display /
E5 Explosion-proof for Class I, Division 1, Groups B, C, and D; FISCO
dust-ignition proof for Class II and Class III, Division 1, Li = 0 HART / FOUNDATION fieldbus/ FISCO /
Groups E, F, and G; hazardous locations; enclosure Type Quick Connect / HART Diagnostics
4X, conduit seal not required when installed according to Li = 60 µH Remote Display
Rosemount drawing 03151-1003.
Special conditions for safe use (x)
1. The apparatus, excluding the Types 3051 S-T and 3051
S-C (In-line and Coplanar SuperModules respectively), is
not capable of withstanding the 500V test as defined in
Clause 6.4.12 of EN 50020. This must be considered
during installation.
2. The terminal pins of the Types 3051 S-T and 3051 S-C
must be protected to IP20 minimum.

11
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

N1 ATEX Type n Japanese Certifications


Certificate No.: BAS01ATEX3304X II 3 G
E4 TIIS Flameproof
EEx nL IIC T4 (Ta = -40 °C TO 70 °C)
Ex d IIC T6
Ui = 45 Vdc max
IP66 Certificate Description
TC15682 Coplanar with Junction Box Housing
Special conditions for safe use (x) TC15683 Coplanar with PlantWeb Housing
The apparatus is not capable of withstanding the 500V TC15684 Coplanar with PlantWeb Housing
insulation test required by Clause 9.1 of EN 50021: 1999. and LCD Display
This must be taken into account when installing the TC15685 In-Line SST with Junction Box Housing
apparatus. TC15686 In-Line Hastelloy with Junction Box Housing
ND ATEX Dust TC15687 In-Line SST with PlantWeb Housing
Certificate No.: BAS01ATEX1374X II 1 D TC15688 In-Line Hastelloy with Plantweb Housing
T105°C (-20 °C ≤ Tamb ≤ 85 °C) TC15689 In-Line SST with Plantweb Housing
Vmax = 42.4 volts max and LCD Display
A = 22 mA TC15690 In-Line Hastelloy with PlantWeb Housing
IP66 and LCD Display
1180
Special conditions for safe use (x)
1. The user must ensure that the maximum rated voltage Australian Certifications
and current (42.4 volts, 22 milliampere, DC) are not E7 SAA Flameproof and Dust Ignition-proof
exceeded. All connections to other apparatus or
Certification No.: AUS Ex 3798X
associated apparatus shall have control over this voltage Ex d IIC T6 (Ta = 60°C) IP66
and current equivalent to a category “ib” circuit according DIP A21 TA T6 (Ta = 60°C) IP66
to EN 50020.
2. Cable entries must be used which maintain the ingress Special conditions for safe use (x)
protection of the enclosure to at least IP66. 1. It is a condition of safe use that each housing shall be
3. Unused cable entries must be filled with suitable blanking connected to external circuits via suitable conduit or
plugs which maintain the ingress protection of the Standards Australia certified cable glands. Where only one
enclosure to at least IP66. entry is used for connection to external circuits, the unused
4. Cable entries and blanking plugs must be suitable for the entry shall be closed by means of the blanking plug
ambient range of the apparatus and capable of supplied by the equipment manufacturer or by a suitable
withstanding a 7J impact test. Standards Australia certified blanking plug.
5. The 3051S must be securely screwed in place to maintain 2. It is a condition of safe use that a dielectric strength test
the ingress protection of the enclosure. shall be applied whenever the terminal block is changed or
E1 ATEX Flameproof replaced in either the dual compartment or single
Certificate No.: KEMA00ATEX2143X II 1/2 G compartment housings. The breakdown current shall be
EEx d IIC T6 (-50 °C ≤ Tamb ≤ 65 °C) less than 5 mA, when 500 V, 47 to 62 Hz, is applied for one
EEx d IIC T5 (-50 °C ≤ Tamb ≤ 80 °C) minute. Note: if tested with an optional T1 transient
Vmax = 42.4V protector terminal block fitted, the protection will operate
1180 and hence there will be no current indicated.
3. It is a condition of safe use that each transmitter module
Special conditions for safe use (x)
shall be used with a Model 300S housing, in order to
This device contains a thin wall diaphragm. Installation, comply with flameproof requirements.
maintenance and use shall take into account the
4. It is a condition of safe use that each model 300S housing
environmental conditions to which the diaphragm will be
fitted with a transmitter module shall be marked with the
subjected. The manufacturer’s instructions for installation
same certification marking code information. Should the
and maintenance shall be followed in detail to assure safety
housing be replaced after initial supply to another model
during its expected lifetime. The Model 3051S pressure
300S housing, the replacement housing shall have the
transmitter must include a Series 300S housing integrally
same certification marking code information as the
mounted to a Series Model 3051S Sensor module as per
housing it replaces.
Rosemount drawing 03151-1023.

12
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
IECEx Certifications N7 IECEx Type n
I7/IG IECEx Intrinsic Safety Certificate No.: IECExBAS04.0018X
Certificate No.: IECExBAS04.0017X Ex nC IIC T4 (Ta = -40 °C to 70 °C)
Ui = 45 Vdc MAX
Ex ia IIC T4 (Ta = -60 °C to 70 °C) -HART/Remote
Display/Quick Connect/HART Diagnostics IP66
Ex ia IIC T4 (Ta = -60 °C to 70 °C) -FOUNDATION fieldbus Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500 V
Ex ia IIC T4 (Ta = -60 °C to 40 °C) -FISCO
IP66 insulation test required by Clause 8 of IEC 79-15: 1987.

TABLE 9. Input Parameters Combinations of Certifications


Loop / Power Groups Stainless steel certification tag is provided when optional approval
Ui = 30 V HART / FOUNDATION fieldbus/ is specified. Once a device labeled with multiple approval types is
Remote Display / Quick Connect installed, it should not be reinstalled using any other approval
/ HART Diagnostics types. Permanently mark the approval label to distinguish it from
Ui = 17.5 V FISCO unused approval types.
Ii = 300 mA HART / FOUNDATION fieldbus/ K1 Combination of E1, I1, N1, and ND
Remote Display / Quick Connect K5 Combination of E5 and I5
/ HART Diagnostics K6 Combination of E6 and I6
Ii = 380 mA FISCO
K7 Combination of E7, I7, and N7
Pi = 1.0 W HART / Remote Display / Quick
KA Combination of E1, I1, E6, and I6
Connect / HART Diagnostics
Pi = 1.3 W FOUNDATION fieldbus KB Combination of E5, I5, I6 and E6
Pi = 5.32 W FISCO KC Combination of E5, E1, I5 and I1
Ci = 30 nF SuperModule Platform / Quick KD Combination of E5, I5, E6, I6, E1, and I1
Connect
Ci = 11.4 nF HART / HART Diagnostics
Ci = 0 FOUNDATION fieldbus / Remote
Display / FISCO / Quick Connect
/ HART Diagnostics
Li = 0 HART / FOUNDATION fieldbus /
FISCO / Quick Connect / HART
Diagnostics
Li = 60 µH Remote Display

Special conditions for safe use (x)


1. The Models 3051S HART 4-20mA, 3051S fieldbus,
3051S Profibus and 3051S FISCO are not capable of
withstanding the 500V test as defined in clause 6.4.12 of
IEC 60079-11. This must be taken into account during
installation.
2. The terminal pins of the Types 3051S-T and 3051S-C
must be protected to IP20 minimum.

13
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

WIRELESS CERTIFICATIONS Hazardous Locations Certifications

Telecommunication Compliance North American Certifications


Factory Mutual (FM) Approvals
All wireless devices require certification to ensure that they adhere to
I5 FM Intrinsically Safe, Non-Incendive, and Dust Ignition-proof.
regulations regarding the use of the RF spectrum. Nearly every
Intrinsically Safe for Class I/II/III, Division 1,
country requires this type of product certification. Emerson is working
Groups A, B, C, D, E, F, and G.
with governmental agencies around the world to supply fully
Zone Marking: Class I, Zone 0, AEx ia llC
compliant products and remove the risk of violating country directives
Temperature Codes T4 (Tamb = -50 to 70° C)
or laws governing wireless device usage.
Non-Incendive for Class I, Division 2, Groups A, B, C, and D.
Dust Ignition-proof for Class II/III, Division 1,
FCC and IC Approvals Groups E, F, and G.
This device complies with Part 15 of the FCC Rules. Operation is Ambient temperature limits: -50 to 85° C
subject to the following conditions: This device may not cause For use with Rosemount SmartPower options
harmful interference this device must accept any interference 00753-9220-XXXX only.
received, including interference that may cause undesired operation. Enclosure Type 4X / IP66
This device must be installed to ensure a minimum antenna
separation distance of 20cm from all persons. CSA - Canadian Standards Association
I6 CSA Intrinsically Safe
Ordinary Location Certification for FM Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
Temp Code T3C
As standard, the transmitter has been examined and tested to Enclosure Type 4X / IP66
determine that the design meets basic electrical, mechanical, and fire For use with Rosemount SmartPower options
protection requirements by FM, a nationally recognized testing 00753-9220-XXXX only.
laboratory (NRTL) as accredited by the Federal Occupational Safety
and Health Administration (OSHA). European Certifications
I1 ATEX Intrinsic Safety
European Directive Information
Certificate No.: BAS01ATEX1303X II 1G
The EC declaration of conformity for all applicable European
Ex ia IIC T4 (Ta = -60 °C to 70 °C)
directives for this product can be found at www.rosemount.com. A IP66
hard copy may be obtained by contacting an Emerson Process For use with Rosemount SmartPower options
Management representative.
00753-9220-XXXX only.
ATEX Directive (94/9/EC) 1180
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC) Country Restriction
Models 3051S_CA4; 3051S_CD2, 3, 4, 5; (also with P9 option) Bulgaria General authorization required for outdoor use
and public service
Pressure Transmitters — QS Certificate of Assessment -
France Outdoor use limited to 10mW e.i.r.p.
EC No. PED-H-100, Module H Conformity Assessment
Italy If used outside of own premises, general
All other Model 3051S Pressure Transmitters authorization is required.
— Sound Engineering Practice Norway May be restricted in the geographical area within
a radius of 20 km from the center of Ny-Alesund.
Transmitter Attachments: Diaphragm Seal - Process Flange - Romania Use on a secondary basis. Individual license
Manifold — Sound Engineering Practice required.
Primary Elements, Flowmeter
— See appropriate Primary Element QIG Figure 1.
Radio Power Label (See
Electro Magnetic Compatibility (EMC) (2004/108/EC) Figure 1) indicates output
All Models: EN 50081-1: 1992; EN 50082-2:1995; power configuration of the radio.
EN 61326-1:1997 + A1, A2, and A3 – Industrial Devices with this label are Radio Power Label
configured for output power less
Radio and Telecommunications Terminal Equipment Directive
than 10 mW e.i.r.p. At time of
(R&TTE)(1999/5/EC)
purchase the customer must
Emerson Process Management complies with the R&TTE
specify ultimate country of
Directive.
installation and operation.

IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECEx BAS 04.0017X
Ex ia IIC T4 (Ta = -60 °C to 70 °C)
For use with Rosemount SmartPower options
00753-9220-XXXX only.
IP66

14
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

DIMENSIONAL DRAWINGS

Rosemount 3051SFC Compact Orifice Flowmeter


Orifice Plate Front View Orifice Plate Side View Orifice Plate Top View

D
C
(Primary Element Type code P)
Compact Orifice Plate

1.13 (28.7)
1.00 (25.4

D
Conditioning Orifice Plate
(Primary Element Type code C)

1.13 (28.7)
1.00 (25.4

TABLE 10. Dimensional Drawings(1)


Plate Type A B Transmitter Height C D
Type P and C 5.50 (140) Transmitter Height + A 7.75 (197) 7.75 (197) - closed 6.00 (152) - closed
8.25 (210) - open 6.25 (159) - open
(1) Measurement in inches (millimeters).

15
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

ORDERING INFORMATION
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
Model Product Description
3051SFC Compact Orifice Flowmeter
Code Measurement Type
D Differential Pressure
Code Primary Element Type
C Conditioning Orifice Plate
P Orifice Plate
Code Material Type
S 316 Stainless Steel (SST)
H(1) Hastelloy
Code Line Size
005(2) 1/2-in.(15 mm)
010(2) 1-in. (25 mm)
015(2) 11/2-in. (40 mm)
020 2-in. (50 mm)
030 3-in. (80 mm)
040 4-in. (100 mm)
050(1) 5-in. (125 mm)
060 6-in. (150 mm)
080 8-in. (200 mm)
100(1) 10-in (250 mm)
120(1) 12-in. (300 mm)
Code Primary Element Style
N Square Edged
Code Beta Ratio
040 0.40 Beta Ratio (β)
065(3) 0.65 Beta Ratio (β)
Code Temperature Measurement
R Remote Thermowell and RTD
T(1) Integral RTD and Thermowell
0 No Temperature Sensor
Code Transmitter Connection Platform
3 Direct-mount, 3-valve integral manifold, SST
7 Remote-mount, 1/4-in. NPT connections
Code Differential Pressure Range
1 0 to 25 in H2O (0 to 62.2 mbar)
2 0 to 250 in H2O (0 to 623 mbar)
3 0 to 1000 in H2O (0 to 2.5 bar)
Code Static Pressure Range
A None
Code Output Protocol
A 4–20 mA with digital signal based on HART protocol
F(4) FOUNDATION fieldbus protocol
X(5) Wireless (Requires wireless options and wireless housing 5A)

16
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
Code Transmitter Housing Style Material Conduit Entry Size
00 None (Customer-supplied electrical connection)
01 Assemble to Rosemount 753R Web-based Monitoring Indicator
1
1A PlantWeb Housing Aluminum /2-14 NPT
1B PlantWeb Housing Aluminum M20 x 1.5 (CM20)
1C PlantWeb Housing Aluminum G1/2
1
1J PlantWeb Housing 316L SST /2-14 NPT
1K PlantWeb Housing 316L SST M20 x 1.5 (CM20)
1L PlantWeb Housing 316L SST G1/2
2A Junction Box Housing Aluminum 1/2-14 NPT

2B Junction Box Housing Aluminum M20 x 1.5 (CM20)


2C Junction Box Housing Aluminum G1/2
2E Junction Box housing with output for remote display and interface Aluminum 1/2-14 NPT

2F Junction Box housing with output for remote display and interface Aluminum M20 x 1.5 (CM20)
2G Junction Box housing with output for remote display and interface Aluminum G1/2
2J Junction Box Housing 316L SST 1/2-14 NPT
1
2M Junction Box housing with output for remote display and interface 316L SST /2-14 NPT
5A Wireless PlantWeb housing Aluminum M20 x 1.5 (CM20)
7J(6) Quick Connect (A size Mini, 4-pin male termination)
Code Transmitter Performance Class for Flow
(7)
1 Ultra: up to ± 0.85% flow rate accuracy, 8:1 flow turndown, 10-year stability, limited 12-year warranty
2 Classic: up to ± 1.05% flow rate accuracy, 8:1 flow turndown, 5-year stability
3(7) Ultra for Flow: up to ± 0.75% flow rate accuracy, 14:1 flow turndown, 10-year stability. limited 12-year warranty
Code Options
Installation Accessories
G DIN Alignment Ring (PN 16)
H DIN Alignment Ring (PN 40, PN 100)
B JIS Alignment Ring 10K
R JIS Alignment Ring 20K
S JIS Alignment Ring 40K
Remote Adapters
E Flange adapters 316 SST (1/2-in. NPT)
High Temperature Applications
T Graphite valve packing (Tmax = 850 °F)
Flow Calibration
WC(8) Discharge coefficient verification (3 point)
WD(8) Discharge coefficient verification (10 point)
Pressure Testing
P1 Hydrostatic testing with certificate
Special Cleaning
P2 Cleaning for special processes
PA Cleaning per ASTM G93 Level D (section 11.4)
Special Inspection
QC1 Visual and dimensional inspection with certificate
QC7 Inspection and performance certificate
Transmitter Calibration Certification
Q4 Calibration Data Certificate for Transmitter
QP Calibration Data Certificate and Tamper Evident Seal
Safety Certification
QS Certificate of FMEDA data
QT(9) Safety Certified to IEC 61508 with certificate of FMEDA data
Material Traceability Certifications
Q8(10) Material Cert per ISO 10474 3.1.B and EN 10204 3.1.B

17
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information


Code Conformance
J2 ANSI B31.1
J3 ANSI B31.3
J4 ANSI B31.8
Material Conformance
J5(11) NACE MR-0175 / ISO 15156
Country Certification
J1 Canadian Registration
Product Certifications
E1 ATEX Flameproof
I1 ATEX Intrinsic Safety
IE FM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
IF CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
IA(1) ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only
N1 ATEX Type n
ND ATEX Dust
K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND)
E4 TIIS Flameproof
E5 FM Explosion-proof, Dust Ignition-proof
I5 FM Intrinsically Safe, Division 2
K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5)
E6 CSA Explosion-proof, Dust Ignition-proof, Division 2
I6 CSA Intrinsically Safe
K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and I6)
E7(1) SAA Flameproof, Dust Ignition-proof
I7 IECEx Intrinsic Safety
IG IECEx FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only
N7 IECEx Type n
K7 SAA Flameproof, Dust Ignition-proof, IECEx Intrinsic Safety, Type n (combination of E7, I7, and N7)
KA ATEX and CSA Flameproof, Intrinsically Safe, Division 2 (combination of E1, I1, E6, and I6)
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, and I6)
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
KC FM and ATEX Explosion-proof, Intrinsically Safe, Division 2 (combination of E5, E1, I5, and I1)
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
Alternative Transmitter Material of Construction
L1 Inert Sensor Fill Fluid
L2 Graphite-filled PTFE o-ring
LA Inert sensor fill fluid and graphite-filled PTFE o-ring
Display(12)
M5 PlantWeb LCD display
M7(7)(13) Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
M8(7)(13) Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
M9(7)(13) Remote mount LCD display and interface, 100 ft. (31 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / Hart output
Terminal Blocks
T1(14) Transient terminal block
T2(15) Terminal block with WAGO spring clamp terminals
T3(15) Transient terminal block with WAGO spring clamp terminals
Manifold for Remote Mount Option
F2 3-Valve Manifold, SST
F6 5-Valve Manifold, SST
PlantWeb Control Functionality
A01(16) FOUNDATION fieldbus Advanced Control Function Block Suite
PlantWeb Diagnostic Functionality
D01(16) FOUNDATION fieldbus Diagnostics Suite
DA1(17) HART Diagnostic Suite

18
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
PlantWeb Enhanced Measurement Functionality
H01(16)(18) Fully Compensated Mass Flow Block
Code Wireless Options - Select code from each wireless category (example: WA2WK1)
Wireless Transmit Rate
WA User Configurable Transmit Rate
Operating Frequency and Protocol
1 2.4 GHz DSSS, HART
2 900 MHz FHSS, HART
Antenna
WK Omnidirectional, Integral Antenna
SmartPower™
1 Long-life Power Module Adapter, Intrinsically Safe
NOTE: Long-life Power Module must be shipped separately, order Part No. 00753-9220-0001.
Code Options
Special Configuration (Software)
C4(7)(19) NAMUR alarm and saturation signal levels, high alarm
C5(7)(19) NAMUR alarm and saturation signal levels, low alarm
C6(7)(19) Custom alarm and saturation signal levels, high alarm
Note: A Configuration Data Sheet must be completed, see document number 00806-0100-4810.
C7(7)(19) Custom alarm and saturation signal levels, low alarm
Note: A Configuration Data Sheet must be completed, see document number 00806-0100-4810.
C8(7)(19) Low alarm (standard Rosemount alarm and saturation signal levels)
Special Configuration (Hardware)
D1(7)(19) Hardware Adjustment (zero, span, alarm, security).
D4 External ground screw
DA(7)(19) Hardware adjustment (zero, span, alarm, security) and external ground screw
Conduit Electrical Connector
ZE(20) M12, 4-pin, Male Connector (eurofast®)
(20)
ZM A size Mini, 4-pin, Male Connector (minifast®)
(1) Consult factory for availability.

(2) Not available for Primary Element Type code C.

(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.

(4) Requires PlantWeb housing.

(5) Available approvals are FM Intrinsically Safe, Division 2 (option code I5), CSA Intrinsically Safe (option code I6), ATEX Intrinsic Safety
(option code I1; only available with 2.4 GHz), and IECEx Intrinsic Safety (option code I7; only available with 2.4 GHz).

(6) Available with output code A only. Available approvals are FM Intrinsically Safe, Division 2 (option code I5) or ATEX Intrinsic Safety (option code I1). Contact
an Emerson Process Management representative for additional information.

(7) Not available with Output Protocol code X.

(8) Not available with Primary Element Type code P.

(9) Not available with output code F or X. Not available with housing code 01 or 7J.

(10) Instrument valves not included in Traceability Certification.

(11) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits
apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

(12) Not available with Housing code 01 or 7J.

(13) Not available with output code F, Housing code 01, option code DA1, or option code QT.

(14) Not available with Housing code 00, 01, 5A, or 7J.

(15) Available with Output Protocol code A and Plantweb housing only.

(16) Requires PlantWeb housing and output code F.

(17) Requires PlantWeb housing and output code A. Includes Hardware Adjustments as standard. Not available with option code QT.

(18) Requires Rosemount Engineering Assistant to configure.

(19) Not available for Output Protocol code F or Housing code 01.

(20) Not available with Housing code 00, 01, 5A, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Division 2
(option code I5) or FM FISCO Intrinsically Safe (option code IE), install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA
4X and IP66). 19
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Rosemount 3095MFC Compact Orifice Mass Flowmeter


SPECIFICATIONS
Performance Functional
System Reference Accuracy Service
Percent (%) of mass flow rate • Liquid
• Gas
TABLE 11. 3095MFC Compact Orifice Mass Flowmeter • Steam
Mass flow Ultra for Flow
(8:1 flow (10:1 flow Power Supply
TYPE BETA turndown) turndown) 4–20 mA option
3095MFCC 0.4 ±0.90% ±0.70% • External power supply required. Standard transmitter
0.65 ±1.30% ±1.15% (4–20 mA) operates on 11 to 55 v dc with no load
3095MFCP(1) 0.4
±2.50% ±2.45% Process Temperature Limits
0.65(4)
Direct Mount Transmitter
3095MFCP(2) 0.4
±2.10% ±2.00% • 450 °F (232 °C)
0.65(4)
Remote Mount Transmitter
3095MFCP(3) 0.4
±1.50% ±1.40% • 850 °F (454 °C) – Stainless Steel
0.65(4)
(1) Line sizes 1/2-in. (15mm) Transmitter Temperature Limits
(2) Line sizes 1-in. to 1 1/2-in. (25 mm to 40 mm) Ambient
• -40 to 185 °F (-40 to 85 °C)
(3) Line sizes 2-in. to 12-in. (50 mm to 300 mm)
• with integral display: -4 to 175 °F (-20 to 80 °C)
(4) For 0.65 beta and ReD< 10,000 add an additional ±0.5% to the Storage
Discharge Coefficient Uncertainty.
• -50 to 230 °F (-46 to 110 °C)
• with integral display: -40 to 185 °F (-40 to 85 °C)
Repeatability
±0.1%
Differential Pressure Limits
Line Sizes Maximum differential pressure (DP) up to 800 inH2O.
1
• /2-in. (15 mm) – not available for the 3095MFCC
Pressure Limits(1)
• 1-in. (25 mm) – not available for the 3095MFCC
Direct Mount Transmitter
• 11/2-in. (40 mm) – not available for the 3095MFCC
• Pressure retention per ANSI B16.5 600# or DIN PN 100
• 2-in. (50 mm)
• 3-in. (80 mm)
Overpressure Limits
• 4-in. (100 mm)
0 to 2 times the absolute pressure range with a maximum of 3626
• 5-in (125 mm)
psia (250 bar).
• 6-in. (150 mm)
• 8-in. (200 mm)
Static Pressure Limits
• 10-in. (250 mm)
Operates within specification between static pressures of 0.5 psia
• 12-in (300 mm)
(0.03 bar-A) and the URL of the static pressure sensor.

Output
Vibration Limits
Two-wire 4–20 mA, user-selectable for DP, AP, GP, PT, mass flow,
Qualified per IEC61298-3 (1998) for field with high vibration level
or totalized flow. Digital HART protocol superimposed on 4–20 mA
or pipeline with high vibration level (10-60Hz 0.21mm
signal, available to any host that conforms to the HART protocol.
displacement peak amplitude / 60 - 500Hz 3g).
The weight and length of the transmitter assembly shall not
Performance Statement Assumptions
exceed 5.8 lbs and 7.75-in.
• Measured pipe I.D
• Electronics are trimmed for optimum flow accuracy

Sizing
Contact an Emerson Process Management representative for
assistance. A Configuration Data Sheet is required prior to order
for application verification. (1) Static pressure selection may effect pressure limitations.

20
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Load Limitations Physical Properties Database
Maximum loop resistance is determined by the voltage level of • Maintained in Engineering Assistant Software Configurator
the external power supply, as described by: • Physical properties for over 110 fluids
Maximum Loop Resistance = Power Supply - 11.0 • Natural gas per AGA
0.022
• Steam and water per ASME
2000
Load (Ohms)

• Other database fluids per American Institute of Chemical


Engineers (AIChE)
• Optional custom entry
Operating
250 Region FOUNDATION fieldbus Function Blocks
0
Standard Function Blocks
11.0 16.5(2) 42.4(1) 55
Resource Block
Power Supply
• Contains hardware, electronics, and diagnostic information.
(1) For CSA approval, power supply must not exceed 42.4 V dc.
Transducer Block
(2) HART protocol communication requires a loop resistance value
between 250-1100 ohms, inclusive. • Contains actual sensor measurement data including the
sensor diagnostics and the ability to trim the pressure
FOUNDATION fieldbus (output option code V) sensor or recall factory defaults.
LCD Block
Power Supply • Configures the local display.
External power supply required; transmitters operate on 9.0 to
5 Analog Input Blocks
32.0 V dc transmitter terminal voltage.
• Processes the measurements for input into other function
Current Draw blocks. The output value is in engineering or custom units
17.5 mA for all configurations (including LCD display option) and contains a status indicating measurement quality.
PID Block with Auto-tune
Humidity Limits • Contains all logic to perform PID control in the field including
• 0–100% relative humidity cascade and feedforward. Auto-tune capability allows for
superior tuning for optimized control performance.
Turn-On Time
Advanced Control Function Block Suite
Digital and analog measured variables will be within specification (Option Code A01)
7 – 10 seconds after power is applied to the transmitter.
Input Selector Block
Digital and analog flow output will be within specifications 10 – 14
seconds after power is applied to the transmitter. • Selects between inputs and generates an output using
specific selection strategies such as minimum, maximum,
Damping midpoint, average, or first “good.”
Analog output response to a step input change is user-selectable Arithmetic Block
from 0 to 29 seconds for one time constant. This software damping • Provides pre-defined application-based equations including
is in addition to sensor module response time flow with partial density compensation, electronic remote
seals, hydrostatic tank gauging, ratio control and others.
Failure Mode Alarm Signal Characterizer Block
• Characterizes or approximates any function that defines an
Output Code A input/output relationship by configuring up to twenty X, Y
If self-diagnostics detect a non-recoverable transmitter failure, coordinates. The block interpolates an output value for a
the analog signal will be driven either below 3.75 mA or above given input value using the curve defined by the configured
21.75 mA to alert the user. High or low alarm signal is coordinates.
user-selectable by internal jumper pins. Integrator Bock
Output Code V • Compares the integrated or accumulated value from one or
two variables to pre-trip and trip limits and generates
If self-diagnostics detect a gross transmitter failure, that
discrete output signals when the limits are reached. This
information gets passed as a status along with the process
block is useful for calculating total flow, total mass, or
variable(s).
volume over time.
Configuration Output Splitter Block
HART Hand-held Communicator (Model 275 or 375) • Splits the output of one PID or other control block so that the
• Performs traditional transmitter maintenance functions PID will control two valves or other actuators.
3095 Multivariable Engineering Assistant (EA) software package Control Selector Block
• Contains built-in physical property database • Selects one of up to three inputs (highest, middle, or lowest)
that are normally connected to the outputs of PID or other
• Enables mass flow configuration, maintenance, and diagnostic
control function blocks.
functions via HART modem (output option code A)
Enables mass flow configuration via PCMCIA Interface for
FOUNDATION fieldbus (output option code V)
21
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Physical Material of Construction


Body/Plate
Temperature Measurement (1) • 316 SST
Remote RTD • 50 micro-inch Ra surface finish
• 100 Ohm platinum with 1/2-in. NPT nipple and union (078 Manifold Head/Valves
series with Rosemount 644 housing) • 316 SST
Model 0078D21N00A025T32Ex
Flange Studs and Nuts
Connection Head: 00644-4410-0011
• Customer supplied
• Standard RTD cable is shielded armored cable, length is 12
feet (3.66 m) • Available as a spare part

• Remote RTD material is SST Transmitter Connection Studs and Nuts

Thermowell • Studs– A193 Grade B8M.

• 1/2-in. x 1/2-in. NPT, 316 SST • Nuts– A194 Grade 8M.


Gasket and O-rings
• Gaskets are customer supplied.
NOTE
Remote temperature measurement is not available for 1/2-in., 1-in., • Durlon 8500 fiber gaskets are recommended. Consult an
and 11/2-in. sizes. Emerson Process Management representative for use with
other gaskets.
• Available as a spare part
Electronic Connections for Remote Mount
• 1/2–14 NPT, G1/2, and M20 × 1.5 (CM20) conduit. HART
interface connections fixed to terminal block for output code A NOTE
Process-Wetted Parts Gaskets and O-rings should be replaced when the 405 is
Integral Manifolds disassembled.
• 316 SST
• Hastelloy C-276
Transmitter Connections
Remote Manifolds
Remote Mount
• 316 SST
• Available with 1/4-in. (standard) or 1/2-in. (option code E)
• Hastelloy C-276 connections
Transmitter Vent Valves and Process Flanges Orifice Type
• 316 SST • Square edged, Wafer style
• Hastelloy C-276 Orifice Pressure Taps
• Glass-filled PTFE O-rings • Corner
Process Isolating Diaphragms
• 316L SST Process Connections
• Hastelloy C-276 Mounts between the following flange configurations
Integral Manifold O-Rings ASME B16.5
• PTFE/Graphite (ANSI) DIN JIS
Class 150 PN16 (option code G) 10k (option code B)
Non-Wetted Parts Class 300 PN40 (option code H) 20k (option code R)
Sensor Module Fill Fluid
Class 600 PN100 (option code H) 40k (option code S)
• Silicone oil
• Inert Fill optional ANSI alignment ring is included as standard when ordering
Cover O-rings
• Buna-N
Remote Mounting Brackets
• SST
Electronic Housing
• Low copper aluminum, NEMA 4x, IP65
• SST (optional)
Paint
• Polyurethane
Bolts
• CS

(1)
22
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Typical Orifice Hole Sizes (For 3095MFCC) 3051SFC Weight
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
is equal to 2 x typical orifice hole size (dC = 2d). The table below 1
/2-in. (15 mm) 10.7 (4.58) 7.5 (3.70)
shows the diameter of each of the four typical orifice holes.
1-in. (25 mm) 11.45 (5.19) 8.25 (4.07)
TABLE 12. β = 0.4 (1)(2) 11/2-in. (40 mm) 11.95 (5.42) 8.75 (4.32)
Line Size 3051SFCC 3051SFCP 2-in. (50 mm) 12.20 (5.53) 9.00 (4.44)
1 3-in. (80 mm) 14.20 (6.44) 11.00 (5.43)
/2-in. (15 mm) Not Available 0.249 (6.325)
1-in. (25 mm) Not Available 0.420 (10.668) 4-in. (100 mm) 16.70 (7.57) 13.50 (6.67)
11/2-in. (40 mm) Not Available 0.644 (16.358) 5-in. (125 mm) 18.45 (8.37) 15.25 (7.53)
2-in. (50 mm) 0.413 (10.490) 0.827 (21.006) 6-in. (150 mm) 20.20 (9.16) 17.00 (8.40)
3-in. (80 mm) 0.614 (15.596) 1.227 (31.166) 8-in. (200 mm) 25.45 (11.54) 22.25 (10.99)
4-in. (100 mm) 0.805 (20.447) 1.610 (40.894) 10-in (250 mm) 30.70 (13.92) 27.50 (13.58)
5-in. (125 mm) 1.009 (25.629) 2.019 (51.283) 12-in (300 mm) 36.70 (16.64) 33.50 (16.54)
6-in. (150 mm) 1.213 (30.810) 2.426 (61.620) (1) Measurement in lb (kg).
8-in. (200 mm) 1.596 (40.538) 3.192 (81.077)
(2) Includes 3051S Coplanar PlantWeb housing transmitter.
10-in. (250 mm) 2.004 (50.902) 4.008 (101.80)
12-in. (300 mm) 2.400 (60.960) 4.800 (121.92) 3095MFC Weight
TABLE 13. β = 0.65(1)(2) Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
1/2-in.(15 mm) 9.50 (4.69) 6.3 (3.11)
Line Size 3051SFCC 3051SFCP
1/2-in.(15 mm) Not Available 0.404 (10.262) 1-in. (25 mm) 10.25 (5.06) 7.05 (3.48)
1-in. (25 mm) Not Available 0.682 (17.323) 11/2-in. (40 mm) 10.75 (5.31) 7.55 (3.73)
11/2-in. (40 mm) Not Available 1.047 (26.594) 2-in. (50 mm) 11.00 (5.43) 7.80 (3.85)
2-in. (50 mm) 0.620 (15.748)(3) 1.344 (34.138) 3-in. (80 mm) 13.00 (6.42) 9.80 (4.84)
3-in. (80 mm) 0.997 (25.324) 1.994 (50.648) 4-in. (100 mm) 15.50 (7.65) 12.30 (6.07)
4-in. (100 mm) 1.308 (33.223) 2.617 (66.472) 5-in. (125 mm) 17.25 (8.52) 14.05 (6.94)
5-in. (125 mm) 1.640 (40.640) 3.281 (83.34) 6-in. (150 mm) 19.00 (9.38) 15.80 (7.80)
6-in. (150 mm) 1.971 (50.063) 3.942 (100.127) 8-in. (200 mm) 24.25 (11.98) 21.05 (10.40)
8-in. (200 mm) 2.594 (65.888) 5.188 (131.775) 10-in (250 mm) 29.50 (14.57) 26.30 (12.9)
10-in. (250 mm) 3.257 (82.728) 6.513 (165.43) 12-in (300 mm) 35.50 (17.53) 32.30 (15.95)
12-in. (300 mm) 3.900 (99.060) 7.800 (198.120) (1) Measurement in lb (kg).
(1) Measurement is in inches (millimeters) (2) Includes 3095 MultiVariable transmitter.
(2) Tolerance = ±0.002-in. 405 Weight
(3) Beta (β) = 0.60-in. (15.24 mm) for 2-in. line size only. Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
1/2-in.(15 mm) 3.50 (1.73) 7.5 (3.70)
1-in. (25 mm) 4.25 (2.10) 8.25 (4.07)
11/2-in. (40 mm) 4.75 (2.34) 8.75 (4.32)
2-in. (50 mm) 5.00 (2.47) 9.00 (4.44)
3-in. (80 mm) 7.00 (3.45) 11.00 (5.43)
4-in. (100 mm) 9.50 (4.69) 13.50 (6.67)
5-in. (125 mm) 11.25 (5.55) 15.25 (7.53)
6-in. (150 mm) 13.00 (6.41) 17.00 (8.40)
8-in. (200 mm) 18.25 (9.00) 22.25 (10.99)
10-in (250 mm) 23.50 (11.59) 27.50 (13.58)
12-in (300 mm) 29.50 (14.55) 33.50 (16.54)
(1) Measurement in lb (kg).

(2) Includes 405 Direct Mount option D3.

23
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Installation Considerations Pipe Centering


Improper centering of any orifice type device can cause an error of
Straight Run Requirements up to ±5% in small line sizes. A centering mechanism (centering
ring) independent of flange rating comes standard with the 405
TABLE 14. 3095MFCC Straight Pipe Requirements(1)
Compact Orifice Series.
Beta 0.40 0.65
Reducer (1 line size) 2 2
Single 90° bend or tee 2 2
Upstream (inlet)
side of primary

Two or more 90 ° bends in the same 2 2


plane
Two or more 90° bends in different 2 2
plane
Up to 10° of swirl 2 2
Butterfly valve (75% to 100% open) 2 N/A 3095MFCDC 3095MFCDP
Conditioning Orifice Compact Orifice
Downstream (outlet) side of primary 2 2

TABLE 15. 3095MFCP Straight Pipe Requirements(1)(2)(3)


Beta 0.40 0.65
Reducer 5 12
(2)(3)
Single 90° bend or tee 16 44
Upstream (inlet)
side of primary

Two or more 90 ° bends 10 44


in the same plane
Two or more 90° bends in different 50 60
plane
Expander 12 28
Ball / Gate valve fully open 12 18
Downstream (outlet) side of primary 6 7

(1) Consult an Emerson Process Management representative if


disturbance is not listed.

(2) Recommended lengths represented in pipe diameters per ISO


5167.

(3) Refer to ISO 5167 for recommended lengths when using flow
straighteners.

Pipe Orientation
Pipe orientation for both 3095MFCC Compact Conditioning Mass
Orifice and standard 3095MFCP Compact Mass Orifice.
Process(1)
Orientation/ Flow Direction Gas Liquid Steam
Horizontal D/R D/R D/R
Vertical Up R D/R R
Vertical Down D/R NR NR
(1) D = Direct mount acceptable (recommended)
R = Remote mount acceptable
NR = Not recommended

24
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Flowmeter Orientation
Flowmeter orientation for both 3095MFC Conditioning Compact
Orifice and standard Compact Orifice.

Gas (Horizontal)

120°

30°

30°

Liquid and Steam (Horizontal)

50°

50°
80°

Gas (Vertical)
FLOW

360°
Liquid (Vertical)

360°
FLOW

25
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

PRODUCT CERTIFICATIONS Canadian Standards Association (CSA)


E6 Explosion Proof for Class I, Division 1, Groups B, C, and D.
Rosemount 3095 with HART Dust-Ignition Proof for Class II/Class III, Division 1, Groups
E, F, and G. CSA enclosure Type 4X suitable for indoor and
outdoor hazardous locations. Provides nonincendive RTD
European Directive Information
connection for Class I, Division 2, Groups A, B, C, and
The EC declaration of conformity for all applicable European
D.Factory Sealed. Install in accordance with Rosemount
directives for this product can be found on the Rosemount website
Drawing 03095-1024. Approved for Class I, Division 2,
at www.rosemount.com. A hard copy may be obtained by
Groups A, B, C, and D.
contacting our local sales office.
I6 Intrinsically Safe for Class I, Division 1, Groups A, B, C, and
ATEX Directive (94/9/EC) D. when installed in accordance with Rosemount drawing
Emerson Process Management complies with the ATEX Directive. 03095-1021. Temperature Code T3C.
For input parameters and installation see control drawing
European Pressure Equipment Directive (PED) 03095-1021.
(97/23/EC)
3095M_2/3,4/D Flow Transmitters — QS Certificate of European Certifications
Assessment - EC No. PED-H-20 I1 ATEX Intrinsic Safety
Module H Conformity Assessment Certificate Number: BAS98ATEX1359X II 1 G
All other 3095_ Transmitters/Level Controller — EEx ia IIC T5 (Tamb = –45 °C to 40 °C)
Sound Engineering Practice EEx ia IIC T4 (Tamb = –45 °C to 70 °C)
Transmitter Attachments: Process Flange - Manifold — 1180
Sound Engineering Practice
TABLE 16. Connection Parameters (Power/Signal
Electro Magnetic Compatibility (EMC) Terminals)
(89/336/EEC) Ui = 30V
3095MV Flow Transmitters Ii = 200 mA
— EN 50081-1: 1992; EN 50082-2:1995; Pi = 1.0 W
EN 61326-1:1997 – Industrial Ci = 0.012 µF
Li = 0
Ordinary Location Certification for Factory TABLE 17. Temperature Sensor Connection Parameters
Mutual Uo = 30V
As standard, the transmitter has been examined and tested to Io = 19 mA
determine that the design meets basic electrical, mechanical, and Po = 140 mW
fire protection requirements by FM, a nationally recognized testing Ci = 0.002 µF
laboratory (NRTL) as accredited by the Federal Occupational Li = 0
Safety and Health Administration (OSHA).
TABLE 18. Temp Sensor Terminals Connection Parameters
Co = 0.066 ␮F Gas Group IIC
Hazardous Locations Certifications Co = 0.560 ␮F Gas Group IIB
Co = 1.82 ␮F Gas Group IIA
North American Certifications Lo = 96 mH Gas Group IIC
FM Approvals Lo = 365 mH Gas Group IIB
E5 Explosion Proof for Class I, Division 1, Groups B, C, and D. Lo = 696 mH Gas Group IIA
Dust-Ignition Proof for Class II/Class III, Division 1, Groups Lo/Ro = 247 ␮H/ohm Gas Group IIC
E, F, and G. Enclosure type NEMA 4X. Factory Sealed. Lo/Ro = 633 ␮H/ohm Gas Group IIB
Provides nonincendive RTD connections for Class I, Division Lo/Ro= 633 ␮H/ohm Gas Group IIA
2, Groups A, B, C, and D.
Special Conditions for Safe Use
I5 Intrinsically Safe for use in Class I, II and III, Division 1, The 3095, when fitted with the transient terminal block
Groups A, B, C, D, E, F, and G hazardous outdoor locations. (order code B), are not capable of withstanding the 500 volts
Non-incendive for Class I, Division 2, Groups A, B, C, and D. insulation test required by EN50 020, Clause 6.4.12 (1994).
Temperature Code T4. Factory Sealed. This condition must be accounted for during installation.
For input parameters and installation see control drawing N1 ATEX Type N
03095-1020.
Certificate Number: BAS98ATEX3360X II 3 G
EEx nL IIC T5 (Tamb = –45 °C to 40 °C)
EEx nL IIC T4 (Tamb = –45 °C to 70 °C)
Ui = 55V

The apparatus is designed for connection to a remote


temperature sensor such as a resistance temperature
detection (RTD)

26
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Special Conditions for Safe Use Electro Magnetic Compatibility (EMC) (89/336/EEC)
The 3095, when fitted with the transient terminal block 3095 Flow Transmitters
(order code B), are not capable of withstanding the 500 volts — EN 50081-1: 1992; EN 50082-2:1995; EN 61326-1:1997 –
insulation test required by EN50 021, Clause 9.1 (1995). Industrial
This condition must be accounted for during installation.
E1 ATEX Flameproof Ordinary Location Certification for Factory Mutual
Certificate Number: KEMA02ATEX2320X II 1/2 G As standard, the transmitter has been examined and tested to
EEx d IIC T5 (-50°C ≤ Tamb ≤ 80°C) determine that the design meets basic electrical, mechanical, and
T6 (-50°C ≤ Tamb ≤ 65°C)
fire protection requirements by FM, a nationally recognized testing
1180
laboratory (NRTL) as accredited by the Federal Occupational
Special Conditions for Safe Use (x): Safety and Health Administration (OSHA).
The device contains a thin wall diaphragm. Installation,
maintenance, and use shall take into account the
environmental conditions to which the diaphragm will be Rosemount 3095 Fieldbus
subjected. The manufacturer’s instructions for installation
and maintenance shall be followed in detail to assure safety
Hazardous Locations Certifications
during its expected lifetime.
ND ATEX Dust North American Certifications
Certificate Number: KEMA02ATEX2321 II 1 D
V = 55 Vdc MAX FM Approvals
I = 23 mA MAX E5 Explosion Proof for Class I, Division 1, Groups B, C, and D.
IP66 Dust-Ignition Proof for Class II/Class III, Division 1, Groups
1180 E, F, and G. Enclosure type NEMA 4X. Factory Sealed.
Provides nonincendive RTD connections for Class I,
Combinations of Certifications Division 2, Groups A, B, C, and D.
Stainless steel certification tag is provided when optional approval I5 Intrinsically Safe for use in Class I, II and III, Division 1,
is specified. Once a device labeled with multiple approval types is Groups A, B, C, D, E, F, and G hazardous outdoor locations.
installed, it should not be reinstalled using any other approval Non-incendive for Class I, Division 2, Groups A, B, C, and D.
types. Permanently mark the approval label to distinguish it from Temperature Code T4. Factory Sealed.
unused approval types.
For input parameters and installation see control drawing
K5 E5 and I5 combination
03095-1020.
K6 E6 and I6 combination IE FISCO for use in Class I, II and III, Division 1, Groups A, B,
C, D, E, F, and G hazardous outdoor locations. Temperature
K1 I1, N1, E1, and ND combination Code T4. Factory Sealed.

Rosemount 3095 with Fieldbus For input parameters and installation see control drawing
03095-1020.
European Directive Information
Combinations of Certifications
The EC declaration of conformity for all applicable European
Stainless steel certification tag is provided when optional approval
directives for this product can be found on the Rosemount website
is specified. Once a device labeled with multiple approval types is
at www.rosemount.com. A hard copy may be obtained by
installed, it should not be reinstalled using any other approval
contacting our local sales office.
types. Permanently mark the approval label to distinguish it from
unused approval types.
ATEX Directive (94/9/EC)
K5 E5 and I5 combination
Emerson Process Management complies with the ATEX Directive.
Canadian Standards Association (CSA)
European Pressure Equipment Directive (PED)
IF CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus
(97/23/EC)
protocol only
3095F_2/3,4/D and 3095M_2/3,4/D Flow Transmitters
— QS Certificate of Assessment - EC No. PED-H-20 European Certifications
Module H Conformity Assessment
IA ATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus
All other 3095_ Transmitters/Level Controller protocol only
— Sound Engineering Practice
Transmitter Attachments: Process Flange - Manifold Australian Certifications
— Sound Engineering Practice IG IECEx FISCO Intrinsic Safety
Primary Elements, Flowmeter
— See appropriate Primary Element QIG

27
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

DIMENSIONAL DRAWINGS
Rosemount 3095MFC Compact Orifice Mass Flowmeter
Orifice Plate Front View Orifice Plate Side View Orifice Plate Top View

D
(Primary Element Type code P)
Compact Orifice Plate

B C

1.13 (28.7)
1.00 (25.4

D
Conditioning Orifice Plate
(Primary Element Type code C)

B C

1.13 (28.7)
1.00 (25.4

TABLE 19. Dimensional Drawings(1)


Plate Type A B Transmitter Height C D
Type P & C 5.50 (140) Transmitter Height + A 6.25 (159) 7.75 (197) - closed 6.0 (152) - closed
8.25 (210) - open 6.25 (159) - open
(1) Measurement is in inches (millimeters).

28
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

ORDERING INFORMATION
Rosemount 3095MFC Compact Orifice Mass Flowmeter Ordering Information
Model Product Description
3095MFC Compact Orifice Mass Flowmeter
Code Primary Element Type
C Conditioning Orifice Plate
P Orifice Plate
Code Material Type
S 316 Stainless Steel (SST)
H(1) Hastelloy
Code Line Size
005(2) 1
/2-in. (15 mm)
010(2) 1-in. (25 mm)
015(2) 11/2-in. (40 mm)
020 2-in. (50 mm)
030 3-in. (80 mm)
040 4-in. (100 mm)
050(1) 5-in. (125 mm)
060 6-in. (150 mm)
080 8-in. (200 mm)
100(1) 10-in (250 mm)
120(1) 12-in. (300 mm)
Code Primary Element Style
N Square Edged
Code Beta Ratio
040 0.40 Beta Ratio (β)
065(3) 0.65 Beta Ratio (β)
Code Temperature Measurement
R Remote Thermowell and RTD
T(1) Integral RTD and Thermowell
0 No Temperature Sensor
Code Transmitter Connection Platform
3 Direct-mount, 3-valve integral manifold, SST
7 Remote-mount, 1/4-in. NPT connections
Code Differential Pressure Range
1 0 to 25 in H2O (0 to 62.2 mbar)
2 0 to 250 in H2O (0 to 623 mbar)
3 0 to 1000 in H2O (0 to 2.5 bar)
Code Static Pressure Range
B 0 – 8 to 0 – 800 psia (0 –55.16 to 0 – 5515.8 kPa)
C 0 – 8 to 0 – 800 psig (0 –55.16 to 0 – 5515.8 kPa)
D 0 – 36.2 to 0 – 3626 psia (0 –250 to 0 – 25000 kPa)
E 0 – 36.2 to 0 – 3626 psig (0 –250 to 0 – 25000 kPa)
Code Output Protocol
A 4–20 mA with digital signal based on HART protocol
V FOUNDATION fieldbus protocol
Code Transmitter Housing Style Conduit Entry Size
1A Polyurethane-covered aluminum 1/2-14 NPT
1B Polyurethane-covered aluminum M20 x 1.5 (CM20)
1C Polyurethane-covered aluminum PG 13.5
1J SST 1/2-14 NPT

1K SST M20 x 1.5 (CM20)


1L SST PG 13.5

29
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Rosemount 3095MFC Compact Orifice Mass Flowmeter Ordering Information


Code Options
Performance Class
U3(4) Ultra for Flow: up to ±0.70% mass flow rate accuracy, up to 10:1 turndown, 10-year stability, limited 12-year warranty
PlantWeb Control Functionality
A01(5) Advanced Control Function Block Suite
Installation Accessories
G DIN Alignment Ring (PN 16)
H DIN Alignment Ring (PN 40, PN 100)
B JIS Alignment Ring 10K
R JIS Alignment Ring 20K
S JIS Alignment Ring 40K
Remote Adapters
E Flange adapters 316 SST (1/2-in. NPT)
High Temperature Applications
T Graphite valve packing (Tmax = 850 °F)
Flow Calibration
WC(6) Discharge coefficient verification (3 point)
WD(6) Discharge coefficient verification (10 point)
Pressure Testing
P1 Hydrostatic Testing with certificate
Special Cleaning
P2 Cleaning for special processes
PA Cleaning per ASTM G93 Level D (section 11.4)
Special Inspection
QC1 Visual and dimensional inspection with certificate
QC7 Inspection and performance certificate
Transmitter Calibration Certification
Q4 Calibration data certificate for transmitter
Material Traceability Certification
Q8(7) Material certification per ISO 10474 3.1.B and EN 10204 3.1.B
Code Conformance
J2 ANSI B31.1
J3 ANSI B31.3
J4 ANSI B31.8
Material Conformance
J5(8)(9) NACE MR-0175 / ISO 15156
Country Certification
J1 Canadian Registration
Product Certifications
E1 ATEX Flameproof
I1 ATEX Intrinsic Safety
N1 ATEX Type n
K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND)
ND ATEX Dust
E5 FM Explosion-proof, Dust Ignition-proof
I5 FM Intrinsically Safe, Division 2
K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5)
E6 CSA Explosion-proof, Dust Ignition-proof, Division 2
I6 CSA Intrinsically Safe, Division 2
K6 CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E6 and I6)
IE(1) FM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
IF(1) CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
IA(1) ATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
IG(1) IECEx FISCO Intrinsic Safety
I7 IECEx Intrinsic Safety
E4 TIIS Flameproof
ID TIIS FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only

30
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Rosemount 3095MFC Compact Orifice Mass Flowmeter Ordering Information
I3 China Intrinsic Safety
E3 China Flameproof
Alternative Transmitter Material of Construction
L1(9) Inert Sensor Fill Fluid
Display
M5 Integral mount LCD display
Terminal Blocks
T1 Transient Protection
Manifold for Remote Mount Option
F2 3-Valve Manifold, SST
F6 5-Valve Manifold, SST
Typical Model Number: 3051MFC C S 040 N 040 0 3 B A 1A
(1) Consult factory for availability.

(2) Not available for Primary Element Type code C.

(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.

(4) Ultra for Flow applicable for HART protocol, DP ranges 2 and 3 with SST isolator material and silicone fill fluid options only.

(5) Function Blocks include: Arithmetic, Integrator, Analog Output, Signal Characterizer, Control Selector, and Output Selector.

(6) Not available with Primary Element Type code P.

(7) Instrument valves not included in Traceability Certification.

(8) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO 15156 for sour oil field production environments. Environmental
limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

(9) Not available with DP range 1.

31
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Rosemount 405 Compact Orifice Primary Element


SPECIFICATIONS

Performance Vibration Limits


Discharge Coefficient Uncertainty Qualified per IEC61298-3 (1998) for field with high vibration level
TABLE 20. 405 Compact Orifice Primary Element or pipeline with high vibration level (10-60Hz 0.21mm
displacement peak amplitude / 60 - 500Hz 3g).
Discharge Coefficient
The weight and length of the transmitter assembly shall not
Type Beta Uncertainty
exceed 5.8 lbs and 7.75-in.
405C 0.4 ±0.50%
(Conditioning Compact) 0.65 ±1.00% Assembly to a transmitter
405P(1)(2) 0.4 ±1.75% Select option code C11 for the Rosemount 3051S transmitter (or
(Standard Compact) 0.65 ±1.75% option code S3 for the Rosemount 3051C or 3095MV transmitters)
405P(3) 0.4 ±1.25% to factory assemble the Rosemount 405 to a Rosemount pressure
(Standard Compact) 0.65 ±1.25% transmitter. If the 405 and transmitter are not factory assembled,
they may be shipped separately. For a consolidated shipment,
(1) Line sizes 1/2 to 11/2-in. (12.7 to 38.1 mm). inform the Emerson Process Management representative when
(2) Discharge Coefficient Uncertainty for 1/2-in. units with Beta = 0.65 placing the order.
is ±2.25%.

(3) Line sizes 2 to 12-in. (50 mm to 300 mm) Physical


Line Sizes Material of Construction
1
• /2-in. (15 mm) – not available for the 405C Body/Plate
• 1-in. (25 mm) – not available for the 405C • 316 SST
• 11/2-in. (40 mm) – not available for the 405C • 50 micro-inch Ra surface finish
• 2-in. (50 mm) Manifold Head/Valves
• 3-in. (80 mm) • 316 SST
• 4-in. (100 mm)
Flange Studs and Nuts
• 5-in (125 mm)
• Customer supplied
• 6-in. (150 mm)
• Available as a spare part
• 8-in. (200 mm)
• 10-in. (250 mm) Transmitter Connection Studs and Nuts
• 12-in (300 mm) • Studs– A193 Grade B8M.
• Nuts– A194 Grade 8M.
Sizing Gasket and O-rings
Contact an Emerson Process Management sales representative • Gaskets are customer supplied.
assistance. A “Configuration Data Sheet” is required prior to order • Durlon 8500 fiber gaskets are recommended. Consult an
for application verification. Emerson Process Management representative for use with
other gaskets.
Functional • Available as a spare part

Service NOTE
• Liquid Gaskets and O-rings should be replaced when the 405 is
• Gas disassembled.
• Vapor
Transmitter Connections
Operating Process Temperature Limits
Direct Mount
Standard (direct/remote mount):
• Integrally mount to 3051 and 3095 transmitters,
• –40 to 450 °F (–40 to 232 °C) range 1, 2, and 3.
Extended (remote mount only with option code T): Remote Mount
• –148 to 850 °F (–100 to 454 °C) • Available with 1/4-in. (standard) or 1/2-in. (option code E)
connections
Differential Pressure Limits
Orifice Type
Maximum differential pressure (DP) up to 800 inH2O.
• Square edged, Wafer style
Maximum Working Pressure Orifice Pressure Taps
• Corner
• Pressure retention per ANSI B16.5 600# or DIN PN100

32
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Process Connections 3051SFC Weight
Mounts between the following flange configurations: Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
ASME B16.5 1
/2-in. (15 mm) 10.7 (4.58) 7.5 (3.70)
(ANSI) DIN JIS
1-in. (25 mm) 11.45 (5.19) 8.25 (4.07)
Class 150 PN16 (option code G) 10k (option code B)
11/2-in. (40 mm) 11.95 (5.42) 8.75 (4.32)
Class 300 PN40 (option code H) 20k (option code R)
2-in. (50 mm) 12.20 (5.53) 9.00 (4.44)
Class 600 PN100 (option code H) 40k (option code S)
3-in. (80 mm) 14.20 (6.44) 11.00 (5.43)
ANSI alignment ring is included as standard when ordering. 4-in. (100 mm) 16.70 (7.57) 13.50 (6.67)
5-in. (125 mm) 18.45 (8.37) 15.25 (7.53)
Typical Orifice Hole Sizes (For 405C) 6-in. (150 mm) 20.20 (9.16) 17.00 (8.40)
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore 8-in. (200 mm) 25.45 (11.54) 22.25 (10.99)
is equal to 2 x typical orifice hole size (dC = 2d). The table below 10-in (250 mm) 30.70 (13.92) 27.50 (13.58)
shows the diameter of each of the four typical orifice holes.
12-in (300 mm) 36.70 (16.64) 33.50 (16.54)
TABLE 21. β = 0.4 (1)(2)
(1) Measurement in lb (kg).
Line Size 3051SFCC 3051SFCP
1
(2) Includes 3051S Coplanar PlantWeb housing transmitter.
/2-in. (15 mm) Not Available 0.249 (6.325)
1-in. (25 mm) Not Available 0.420 (10.668) 3095MFC Weight
11/2-in. (40 mm) Not Available 0.644 (16.358) Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
2-in. (50 mm) 0.413 (10.490) 0.827 (21.006) 1/2-in.(15 mm) 9.50 (4.69) 6.3 (3.11)
3-in. (80 mm) 0.614 (15.596) 1.227 (31.166)
1-in. (25 mm) 10.25 (5.06) 7.05 (3.48)
4-in. (100 mm) 0.805 (20.447) 1.610 (40.894)
11/2-in. (40 mm) 10.75 (5.31) 7.55 (3.73)
5-in. (125 mm) 1.009 (25.629) 2.019 (51.283)
2-in. (50 mm) 11.00 (5.43) 7.80 (3.85)
6-in. (150 mm) 1.213 (30.810) 2.426 (61.620)
3-in. (80 mm) 13.00 (6.42) 9.80 (4.84)
8-in. (200 mm) 1.596 (40.538) 3.192 (81.077)
4-in. (100 mm) 15.50 (7.65) 12.30 (6.07)
10-in. (250 mm) 2.004 (50.902) 4.008 (101.80)
5-in. (125 mm) 17.25 (8.52) 14.05 (6.94)
12-in. (300 mm) 2.400 (60.960) 4.800 (121.92)
6-in. (150 mm) 19.00 (9.38) 15.80 (7.80)
TABLE 22. β = 0.65(1)(2) 8-in. (200 mm) 24.25 (11.98) 21.05 (10.40)
Line Size 3051SFCC 3051SFCP 10-in (250 mm) 29.50 (14.57) 26.30 (12.9)
1 12-in (300 mm) 35.50 (17.53) 32.30 (15.95)
/2-in. (15 mm) Not Available 0.404 (10.262)
1-in. (25 mm) Not Available 0.682 (17.323) (1) Measurement in lb (kg).
11/2-in. (40 mm) Not Available 1.047 (26.594) (2) Includes 3095 MultiVariable transmitter.
2-in. (50 mm) 0.620 (15.748)(3) 1.344 (34.138)
3-in. (80 mm) 0.997 (25.324) 1.994 (50.648) 405 Weight
4-in. (100 mm) 1.308 (33.223) 2.617 (66.472) Line Size Direct Mount (D3)(1)(2) Remote Mount (R3)(1)
1/2-in.(15 mm) 3.50 (1.73) 7.5 (3.70)
5-in. (125 mm) 1.640 (40.640) 3.281 (83.34)
6-in. (150 mm) 1.971 (50.063) 3.942 (100.127) 1-in. (25 mm) 4.25 (2.10) 8.25 (4.07)
8-in. (200 mm) 2.594 (65.888) 5.188 (131.775) 11/2-in. (40 mm) 4.75 (2.34) 8.75 (4.32)
10-in. (250 mm) 3.257 (82.728) 6.513 (165.43) 2-in. (50 mm) 5.00 (2.47) 9.00 (4.44)
12-in. (300 mm) 3.900 (99.060) 7.800 (198.120) 3-in. (80 mm) 7.00 (3.45) 11.00 (5.43)
4-in. (100 mm) 9.50 (4.69) 13.50 (6.67)
(1) Measurement is in inches (millimeters)
5-in. (125 mm) 11.25 (5.55) 15.25 (7.53)
(2) Tolerance = ±0.002-in.
6-in. (150 mm) 13.00 (6.41) 17.00 (8.40)
(3) Beta (β) = 0.60-in. (15.24 mm) for 2-in. line size only. 8-in. (200 mm) 18.25 (9.00) 22.25 (10.99)
10-in (250 mm) 23.50 (11.59) 27.50 (13.58)
12-in (300 mm) 29.50 (14.55) 33.50 (16.54)
(1) Measurement in lb (kg).

(2) Includes 405 Direct Mount option D3.

33
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Installation Consideration Pipe Orientation


Process(1)
Straight Pipe Requirement Orientation/ Flow Direction Gas Liquid Steam
Use the appropriate lengths of straight pipe upstream and Horizontal D/R D/R D/R
downstream of the 405 to minimize the effects of moderate flow
Vertical Up R D/R R
disturbances in the pipe. Table 23 and Table 24 lists
recommended lengths of straight pipe per ISO 5167. Vertical Down D/R NR NR
(1) D = Direct mount acceptable (recommended)
TABLE 23. 405C Straight Pipe Requirements(1) R = Remote mount acceptable
NR = Not recommended
Beta 0.40 0.65
Reducer (1 line size) 2 2 Pipe Centering
Single 90° bend or tee 2 2
Upstream (inlet)
side of primary

Improper centering of any orifice type device can cause an error of


Two or more 90 ° bends in the same 2 2 up to ±5% in small line sizes. A centering mechanism (centering
plane ring) independent of flange rating comes standard with the 405
Two or more 90° bends in different 2 2 Compact Orifice Series.
plane
Up to 10° of swirl 2 2
Butterfly valve (75% to 100% open) 2 N/A
Downstream (outlet) side of primary 2 2

TABLE 24. 405P Straight Pipe Requirements(1)(2)(3)


Beta 0.40 0.65
Reducer 5 12 405C Conditioning
(2)(3) 405P Compact
Single 90° bend or tee 16 44
Upstream (inlet)

Orifice
side of primary

Orifice
Two or more 90 ° bends 10 44
in the same plane
Two or more 90° bends in different 50 60
plane
Expander 12 28
Ball / Gate valve fully open 12 18
Downstream (outlet) side of primary 6 7

(1) Consult an Emerson Process Management representative if


disturbance is not listed.

(2) Recommended lengths represented in pipe diameters per ISO


5167.

(3) Refer to ISO 5167 for recommended lengths when using flow
straighteners.

34
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Flowmeter Orientation
Flowmeter orientation for the Conditioning Compact Orifice and
standard Compact Orifice.

Gas (Horizontal)

120°

30°

30°

Liquid and Steam (Horizontal)

50°

50°
80°

Gas (Vertical)
FLOW

360°
Liquid (Vertical)

360°
FLOW

35
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

DIMENSIONAL DRAWINGS
Rosemount 405 Compact Orifice Plate
(Remote Mount Transmitter)
Adapter Plate (R3) Flange Adapter (R3 with option E)

2.13
(54.1)
1/2"-in NPT
1/4"-in NPT
(Primary Element Type code P)

HIGH
Compact Orifice Plate

INSTRUMENT 2.13 HIGH FLANGE


VALVE (54.1) INSTRUMENT ADAPTER
VALVE
LOW
ADAPTER INSTRUMENT LOW
PLATE VALVE ADAPTER INSTRUMENT
PLATE VALVE

EQUALIZER
VALVE EQUALIZER
VALVE
.85 (21.6)
.85 (21.6)

1.13 (28.7) 1.13 (28.7)


1.00 (25.4) 1.00 (25.4)

2.13
(54.1)
1/2"-in NPT
1/4"-in NPT
Conditioning Orifice Plate
(Primary Element Type code C)

HIGH
INSTRUMENT 2.13 HIGH
VALVE FLANGE
(54.1) INSTRUMENT ADAPTER
VALVE
LOW
ADAPTER INSTRUMENT LOW
PLATE VALVE ADAPTER INSTRUMENT
PLATE VALVE

EQUALIZER
VALVE EQUALIZER
VALVE
.85 (21.6)
.85 (21.6)

1.13 (28.7) 1.13 (28.7)


1.00 (25.4) 1.00 (25.4)

36
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

Rosemount 405 Compact Orifice Plate


(Direct Mount)
Front View (transmitter connection A3) Front View (transmitter connection D3)

1.30
(Primary Element Type code P)

HIGH (33)
Compact Orifice Plate

INSTRUMENT 2.13 2.13


VALVE (54.1) HIGH (54.1)
INSTRUMENT
VALVE
LOW
ADAPTER INSTRUMENT
PLATE LOW
VALVE INSTRUMENT
VALVE

EQUALIZER
VALVE EQUALIZER
VALVE
.70
(18)

1.13 (28.7) 1.13 (28.7)


1.00 (25.4) 1.00 (25.4)

1.30
(33)
Conditioning Orifice Plate
(Primary Element Type code C)

2.13
HIGH (54.1)
INSTRUMENT
VALVE

LOW
INSTRUMENT
VALVE

EQUALIZER
VALVE

1.13 (28.7)
1.13 (28.7) 1.00 (25.4)
1.00 (25.4)

NOTE
Transmitter connection code A3 is to be used with a traditional style transmitter (such as a Rosemount 1151). This
is a stainless steel adapter plate for allowing the direct mount of traditional style transmitters.

37
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

ORDERING INFORMATION
Rosemount 405 Compact Orifice Primary Element Ordering Information
Model Product Description
405 Compact Primary Element
Code Primary Element Type
C Conditioning Orifice Plate
P Orifice Plate
Code Material Type
S 316 Stainless Steel (SST)
H(1) Hastelloy
Code Line Size
005(2) 1
/2-in. (15 mm)
010(2) 1-in. (25 mm)
015(2) 11/2-in. (40 mm)
020 2-in. (50 mm)
030 3-in. (80 mm)
040 4-in. (100 mm)
050(1) 5-in. (125 mm)
060 6-in. (150 mm)
080 8-in. (200 mm)
100(1) 10-in. (250 mm)
120(1) 12-in. (300 mm)
Code Temperature Measurement
R Remote Thermowell and RTD
T(1) Integral RTD and Thermowell
0 No Temperature Sensor
Code Beta Ratio
040 0.40 Beta Ratio (β)
065(3) 0.65 Beta Ratio (β)
Code Transmitter Connection
D3 Coplanar, Direct mount, 3-valve integral manifold, SST
R3 Remote-mount, 1/4-in. NPT connections
A3 Traditional, Direct mount, 3-valve integral manifold with adapter plate, SST
Code Options
Installation Accessories
G DIN Alignment Ring (PN 16)
H DIN Alignment Ring (PN 40, PN 100)
B JIS Alignment Ring 10K
R JIS Alignment Ring 20K
S JIS Alignment Ring 40K
Adapters
E Flange adapters 316 SST (1/2-in. NPT)
High Temperature Applications
T Graphite valve packing (Tmax = 850 °F)
Flow Calibration
WC(4) Discharge coefficient verification (3 point)
WD(4) Discharge coefficient verification (10 point)
Pressure Testing
P1 Hydrostatic testing with certificate
Special Cleaning
P2 Cleaning for special processes
PA Cleaning per ASTM G93 Level D (section 11.4)
Continued on Next Page

38
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
Rosemount 405 Compact Orifice Primary Element Ordering Information
Special Inspection
QC1 Visual and Dimensional Inspection with certification
QC7 Inspection and performance certification
Material Traceability Certification
Q8(5) Material certification per ISO 10474 3.1.B and EN 10204 3.1.B
Code Conformance
J2 ANSI B31.1
J3 ANSI B31.3
J4 ANSI B31.8
Material Conformance
J5(6) NACE MR-0175 / 15156
Country Certification
J1 Canadian Registration
Typical Model Number: 405 C S 040 N 040 D3
(1) Consult factory for availability.

(2) Not available for Primary Element Type code C.

(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.

(4) Not available with Primary Element Type code P.

(5) Instrument valves not included in Traceability Certification.

(6) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits
apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

39
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

HART Configuration Data Sheet (CDS)


DP FLOW CDS
Complete this form to define a custom flow configuration for DP Flowmeters. Unless specified, the flowmeter will
be shipped with the default values identified by the H symbol.
For technical assistance in filling out this CDS, call a Rosemount representative.

NOTE
Any missing information will be processed with the indicated default values.

* = Required Item
★ = Default
Customer Information
Customer: Contact Name:

Customer Phone: Customer Fax:

Customer Approval Sign-Off: Customer PO:

Calculation Approval
❑ Check this box if a calculation for approval prior to manufacturing is required

Application and Configuration Data Sheet (Required with Order)


Tag:

Model No (1)

* Select fluid type ❑ Liquid ❑ Gas ❑ Steam


(2)
* Fluid name

Flowmeter Information (optional)


* Failure Mode Alarm Direction (select one) ❑ Alarm High★ ❑ Alarm Low
Software Tag: ___ ___ ___ ___ ___ ___ ___ ___ (8 characters)

Descriptor: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (16 characters)

Message: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___

___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (32 characters)

Date: Day __ __ (numeric) Month __ __ (numeric) Year __ __ (numeric)

(1) A complete model number is required before Rosemount Inc. can process the order.

(2) If the Fluid is not located in Table 25 on page 42, the “Ordering Information” on page 38 must be completed.

For Rosemount Use Only


S.O.: LI
CHAMP: DATE:
ADMIN:

40
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

* = Required Item
★ = Default
Primary Element Information
* Select Differential Producer (Select One)
Annubar Orifice
❑ 485 Annubar/ 3095MFA Mass ProBar, 3051SFA ProBar ❑ 3051SFP, 3095MFP, 1195
❑ 285 Annubar ❑ 405C, 405P, 3051SFC, 3095MFC
❑ Annubar Diamond II + / Mass Probar ❑ 1595 Conditioning Orifice
❑ Long Radius Wall Taps, ASME ❑ 21/2D & 8D Taps, ASME
❑ Long Radius Wall Taps, ISO ❑ Corner Taps, ASME
❑ ISA 1932, ISO ❑ Corner Taps, ISO
Venturi ❑ D & D/2 Taps, ASME
❑ Nozzle, ISO ❑ D & D/2 Taps, ISO
❑ Rough Cast/Fabricated Inlet, ASME ❑ D & D/2 Taps, ISO 99 Amendment 1
❑ Round Cast Inlet, ISO ❑ Flange Taps, AGA
❑ Machined Inlet, ASME ❑ Flange Taps, ASME
❑ Machined Inlet, ISO ❑ Flange Taps, ISO
❑ Welded Inlet, ISO ❑ Flange Taps, ISO 99 Amendment 1
Other (All options require a discharge coefficient value) ❑ Small Bore, Flange Taps, ASME
❑ Calibrated Orifice: Flange, Corner, or D & D/2 Taps.
Discharge coefficient: __________________
❑ Calibrated Orifice: 21/2 D & 8D Taps
Discharge coefficient: __________________
❑ Calibrating Nozzle
Discharge coefficient: __________________
❑ Calibrating Venturi
Discharge coefficient: __________________
❑ Area Averaging Meter
Discharge coefficient: __________________
❑ V-Cone®
Discharge coefficient: __________________
Diameter (d) ________________ ❑ inch★ at __________ ❑ °F ❑ °C
❑ millimeters ❑ 68 °F★
Special Annubar dimension (required if customer supplies mounting hardware). ❑ ODF _____ ❑ ODT _____
Pipe Information
* Orientation / Flow Direction: ❑ Vertical Up ❑ Vertical Down ❑ Horizontal
* Line Size / Schedule: ___________________________________ Body I.D. (D): ___________________________________

Materials of Construction
* Pipe Material ❑ Carbon Steel ❑ 304 SST ❑ 316 SST ❑ Hastelloy ❑ Other ________________
* Primary Element Material ❑ 316 SST ❑ Hastelloy ❑ Other ___________________ (Please verify material availability)
Operating Conditions
4 mA value Minimum Normal Maximum Full Scale:20 mA flow rate Design
(design to P and T)
Flow Rate 0 *(1) * *

Pressure (P) — *(1) * *(1) *(2)

Temperature (T) — *(1) * *(1) *

RTD Mode
❑ Normal Mode ★ (Requires a RTD to be connected. If the RTD is disconnected or fails, the 3095MV output goes to alarm value)

❑ Fixed Temperature Mode: Specify the fixed temperature value _____________________ ❑ °F ❑ °C


❑ Backup Mode (Uses the connected RTD for temperature measurement. If the RTD is disconnected or fails, the transmitter uses a fixed
temperature value as a backup. This will not cause the mA output to go to alarm value and can potentially cause inaccurate flow
measurement.) Fixed temperature value to be used as backup_________________ ❑ °F ❑ °C

41
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

* = Required Item
★ = Default
Base Conditions
❑ Standard Base (P=14.696 psia / 101.325 kPa abs, T= 60 °F (15.56 °C))

❑ Normal Base (P=14.696 psia / 101.325 kPa abs, T= 32 °F (0 °C))

❑ Standard Base for Natural Gas (AGA) (P=14.73 psia, T= 60°F (15.56 °C))

❑ User Defined: P= ________ Units: ________ T= ________ Units = ________

Compressibility at Base: ________________________ OR Density at Base: ________________________

(1) Operating ranges for pressure and temperature are needed for transmitter configuration.

(2) Required to verify that the product selection meets design criteria.
(1)
TABLE 25. Rosemount Fluids Database
Acetic Acid Divinyl Ether Methane n-Hexane 1-Heptanol
Acetone Ethane Methanol n-Octane 1-Heptene
Acetonitrile Ethanol Methyl Acrylate n-Pentane 1-Hexene
Acetylene Ethylamine Methyl Ethyl Ketone Oxygen 1-Hexadecanol
Acrylonitrile Ethylbenzene Methyl Vinyl Ether Pentafluorothane 1-0ctanol
Air Ethylene m-Chloronitrobenzene Phenol 1-Octene
Allyl Alcohol Ethylene Glycol Neon Propadiene 1-Nonanol
Ammonia Ethylene Oxide Neopentane Pyrene 1-Pentadecanol
Argon Fluorene Nitric Acid Propylene 1-Pentanol
Benzene Furan Nitric Oxide Styrene 1-Pentene
Benzaldehyde Helium-4 Nitrobenzene Sulfer Dioxide 1-Undecanol
Benzyl Alcohol Hydrazine m-Dichlorobenzene Propane 1-Nonanal
Biphenyl Hydrogen Nitroethane Toluene 1,2,4- Trichlorobenzene
Carbon Dioxide Hydrogen Chloride Nitrogen Trichloroethylene 1,1,2- Trichloroethane
Carbon Monoxide Hydrogen Cyanide Nitromethane Vinyl Acetate 1,1,2,2- Tetrafluoroethane
Carbon Tetrachloride Hydrogen Peroxide Nitrous Oxide Vinyl Chloride 1,2-Butadiene
Chlorine Hydrogen Sulfide n-Butane Vinyl Cyclohexane 1,3-Butadiene
Chlorotrifluoroethylene Isobutane n-Butanol Water 1,3,5- Trichlorobenzene
Chloroprene Isobutene n-Butyraldehyde 1-Butene 1,4-Dioxane
Cycloheptane Isobutyl benzene n-Butyronitrile 1-Decene 1,4-Hexadiene
Cyclohexane Isopentane n-Decane 1-Decanal 2-Methyl-1-Pentene
Cyclopentane Isoprene n-Dodecane 1-Decanol 2,2-Dimethylbutane
Cyclopentene Isopropanol n-Heptadecane 1-Dodecene
Cyclopropane n-Heptane 1-Dodecanol
(1) This list is subject to change without notice. Steam per ASME Steam tables. All other fluids per AlChE.

Drawing/Notes

42
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

FOUNDATION fieldbus™ Configuration Data Sheet (CDS)


DP FLOW CDS
Complete this form to define a custom flow configuration for DP Flowmeters. Unless specified, the flowmeter will
be shipped with the default values identified by the H symbol.
For technical assistance in filling out this CDS, call a Rosemount representative.

NOTE
Any missing information will be processed with the indicated default values.

* = Required Item
★ = Default
Customer Information
Customer: Contact Name:

Customer Phone: Customer Fax:

Customer Approval Sign-Off: Customer PO:

Calculation Approval
❑ Check this box if a calculation for approval prior to manufacturing is required

Application and Configuration Data Sheet (Required with Order)


Tag:

Model No (1)

* Select fluid type ❑ Liquid ❑ Gas ❑ Steam


(2)
* Fluid name

Flowmeter Information (optional)


* Failure Mode Alarm Direction (select one) ❑ Alarm High★ ❑ Alarm Low
Software Tag: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (16 characters)

Descriptor: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___

___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (32 characters)

Message: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___

___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (32 characters)

Date: Day __ __ (numeric) Month __ __ (numeric) Year __ __ (numeric)

(1) A complete model number is required before Rosemount Inc. can process the order.

(2) If the Fluid is not located in Table 26 on page 45, the “Ordering Information” on page 38 must be completed.

For Rosemount Use Only


S.O.: LI
CHAMP: DATE:
ADMIN:

43
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

* = Required Item
★ = Default
Primary Element Information
* Select Differential Producer (Select One)
Annubar Orifice
❑ 485 Annubar/ 3095MFA Mass ProBar, 3051SFA ProBar ❑ 3051SFP, 3095MFP, 1195
❑ 285 Annubar ❑ 405C, 405P, 3051SFC, 3095MFC
❑ Annubar Diamond II + / Mass Probar ❑ 1595 Conditioning Orifice
❑ Long Radius Wall Taps, ASME ❑ 21/2D & 8D Taps, ASME
❑ Long Radius Wall Taps, ISO ❑ Corner Taps, ASME
❑ ISA 1932, ISO ❑ Corner Taps, ISO
Venturi ❑ D & D/2 Taps, ASME
❑ Nozzle, ISO ❑ D & D/2 Taps, ISO
❑ Rough Cast/Fabricated Inlet, ASME ❑ D & D/2 Taps, ISO 99 Amendment 1
❑ Round Cast Inlet, ISO ❑ Flange Taps, AGA
❑ Machined Inlet, ASME ❑ Flange Taps, ASME
❑ Machined Inlet, ISO ❑ Flange Taps, ISO
❑ Welded Inlet, ISO ❑ Flange Taps, ISO 99 Amendment 1
Other (All options require a discharge coefficient value) ❑ Small Bore, Flange Taps, ASME
❑ Calibrated Orifice: Flange, Corner, or D & D/2 Taps.
Discharge coefficient: __________________
❑ Calibrated Orifice: 21/2 D & 8D Taps
Discharge coefficient: __________________
❑ Calibrating Nozzle
Discharge coefficient: __________________
❑ Calibrating Venturi
Discharge coefficient: __________________
❑ Area Averaging Meter
Discharge coefficient: __________________
❑ V-Cone®
Discharge coefficient: __________________
Diameter (d) ________________ ❑ inch★ at __________ ❑ °F ❑ °C
❑ millimeters ❑ 68 °F★
Special Annubar dimension (required if customer supplies mounting hardware). ❑ ODF _____ ❑ ODT _____
Pipe Information
* Orientation / Flow Direction: ❑ Vertical Up ❑ Vertical Down ❑ Horizontal
* Line Size / Schedule: ___________________________________ Body I.D. (D): ___________________________________

Materials of Construction
* Pipe Material ❑ Carbon Steel ❑ 304 SST ❑ 316 SST ❑ Hastelloy ❑ Other ________________
* Primary Element Material ❑ 316 SST ❑ Hastelloy ❑ Other ___________________ (Please verify material availability)
Operating Conditions
4 mA value Minimum Normal Maximum Full Scale:20 mA flow rate Design
(design to P and T)
Flow Rate 0 *(1) * *

Pressure (P) — *(1) * *(1) *(2)

Temperature (T) — *(1) * *(1) *

RTD Mode
❑ Normal Mode ★ (Requires a RTD to be connected. If the RTD is disconnected or fails, the 3095MV output goes to alarm value)

❑ Fixed Temperature Mode: Specify the fixed temperature value _____________________ ❑ °F ❑ °C


❑ Backup Mode (Uses the connected RTD for temperature measurement. If the RTD is disconnected or fails, the transmitter uses a fixed
temperature value as a backup. This will not cause the mA output to go to alarm value and can potentially cause inaccurate flow
measurement.) Fixed temperature value to be used as backup_________________ ❑ °F ❑ °C

44
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

* = Required Item
★ = Default
Base Conditions
❑ Standard Base (P=14.696 psia / 101.325 kPa abs, T= 60 °F (15.56 °C))

❑ Normal Base (P=14.696 psia / 101.325 kPa abs, T= 32 °F (0 °C))

❑ Standard Base for Natural Gas (AGA) (P=14.73 psia, T= 60°F (15.56 °C))

❑ User Defined: P= ________ Units: ________ T= ________ Units = ________

Compressibility at Base: ________________________ OR Density at Base: ________________________

(1) Operating ranges for pressure and temperature are needed for transmitter configuration.

(2) Required to verify that the product selection meets design criteria.

TABLE 26. Rosemount Fluids Database(1)


Acetic Acid Divinyl Ether Methane n-Hexane 1-Heptanol
Acetone Ethane Methanol n-Octane 1-Heptene
Acetonitrile Ethanol Methyl Acrylate n-Pentane 1-Hexene
Acetylene Ethylamine Methyl Ethyl Ketone Oxygen 1-Hexadecanol
Acrylonitrile Ethylbenzene Methyl Vinyl Ether Pentafluorothane 1-0ctanol
Air Ethylene m-Chloronitrobenzene Phenol 1-Octene
Allyl Alcohol Ethylene Glycol Neon Propadiene 1-Nonanol
Ammonia Ethylene Oxide Neopentane Pyrene 1-Pentadecanol
Argon Fluorene Nitric Acid Propylene 1-Pentanol
Benzene Furan Nitric Oxide Styrene 1-Pentene
Benzaldehyde Helium-4 Nitrobenzene Sulfer Dioxide 1-Undecanol
Benzyl Alcohol Hydrazine m-Dichlorobenzene Propane 1-Nonanal
Biphenyl Hydrogen Nitroethane Toluene 1,2,4- Trichlorobenzene
Carbon Dioxide Hydrogen Chloride Nitrogen Trichloroethylene 1,1,2- Trichloroethane
Carbon Monoxide Hydrogen Cyanide Nitromethane Vinyl Acetate 1,1,2,2- Tetrafluoroethane
Carbon Tetrachloride Hydrogen Peroxide Nitrous Oxide Vinyl Chloride 1,2-Butadiene
Chlorine Hydrogen Sulfide n-Butane Vinyl Cyclohexane 1,3-Butadiene
Chlorotrifluoroethylene Isobutane n-Butanol Water 1,3,5- Trichlorobenzene
Chloroprene Isobutene n-Butyraldehyde 1-Butene 1,4-Dioxane
Cycloheptane Isobutyl benzene n-Butyronitrile 1-Decene 1,4-Hexadiene
Cyclohexane Isopentane n-Decane 1-Decanal 2-Methyl-1-Pentene
Cyclopentane Isoprene n-Dodecane 1-Decanol 2,2-Dimethylbutane
Cyclopentene Isopropanol n-Heptadecane 1-Dodecene
Cyclopropane n-Heptane 1-Dodecanol
(1) This list is subject to change without notice. Steam per ASME Steam tables. All other fluids per AlChE.

Block Tag Names


AI Block Name (Flow): ____________________________ (AI 1400 ★)
AI Block Name (DP): ____________________________ (AI 1500 ★)
AI Block Name (SP): ____________________________ (AI 1600 ★)
AI Block Name (PT): ____________________________ (AI 1700 ★)
INTEG Block Name (Flow Total): ____________________________ (INTEG 2100 ★)

Drawing/Notes

45
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Fluid Data Sheet (FDS)


For custom fluid not in the Rosemount Fluid Database
For technical assistance in filling out this CDS, call an Emerson Process Management representative. Complete
this form to define a custom fluid. The H symbol identifies the default value.

NOTE
This form is not required if using the Rosemount Fluid Database.

* = Required Item
★ = Default
Customer Information
Customer: Contact Name:

Customer Phone: Customer Fax:

Customer PO:

Fluid Properties
❑ Custom Liquid– Complete Table ❑ Liquid
❑ Custom Gas– Complete Table ❑ Gas
❑ Custom Natural Gas– Complete Table ❑ Natural Gas

For Rosemount Use Only


S.O.: LI
CHAMP: DATE:
ADMIN:

46
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series
TABLE 27. Custom Liquid Worksheet
* = Required Item
★ = Default
Mass Liquid Density and Viscosity Information
1. Fill in the following operating temperatures

a) _________________________ min

b) _________________________ [1/3 (max - min))] + min

c) _________________________ [2/3 (max - min))] + min

d) _________________________ max

2. Transfer the values from the above section to the numbered lines below.
3. Check one Density box, then enter the values for each temperature and the standard density.
4. Check one Viscosity box, then enter values for each temperature. (At least one viscosity value is required).
Density Viscosity
❑ Density in lbs/CuFt ❑ Viscosity in centipoise
❑ Density in kg/CuM ❑ Viscosity in lbs/ft sec
❑ Viscosity in pascal sec

Temperature Temperature
a) _____________ min a) _____________ min.

b) _____________ [1/3 (max - min))] + min b) _____________ [1/3 (max - min))] + min

c) _____________ [2/3 (max - min))] + min c) _____________ [2/3 (max - min))] + min

d) _____________ max d) _____________ max

Base density: __________________________________________________________


(at base reference conditions specified)
Volumetric Liquid Density and Viscosity Information
* Density at Flow: _________________________________________________ Units: ❑ lb/ft3 ❑ Kg/m3 ❑ Other:
OR

Specific Gravity at Flow: ____________________________________________

* Viscosity at Flow: ________________________________________________ Units: ❑ Centipoise ❑ Other:

47
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

TABLE 28. Custom Gas Worksheet


* = Required Item
★ = Default
Mass Gas Compressibility and Viscosity Information
1. Fill in the following operating pressures and operating temperatures

Operating Pressures Operating Temperatures

1) _____________ min 5) _____________ min

2) _____________ [1/3 (max - min))] + min 6) _____________ [1/2 (max - min))] + min

3) _____________ [2/3 (max - min))] + min 7) _____________ max

4) _____________ max 8) _____________ [1/3 (max - min))] + min

9) _____________ [2/3 (max - min))] + min

2. Transfer the values from the above section to the numbered lines below
3. Check one Density/Compressibility box, then enter the 12 values for each pressure/temperature range.
4. Check one Viscosity box, then enter values for each temperature. (At least one viscosity value is required).
5. Enter values for molecular weight, isentropic exponent, and standard density (or standard compressibility).
Density Viscosity
❑ Density in lbs/CuFt ❑ Viscosity in centipoise
❑ Density in kg/CuM ❑ Viscosity in lbs/ft sec
❑ Compressibility ❑ Viscosity in pascal sec
Pressure Temperature Temperature

1) ____________ 5) _____________________________ 5) ________________________________________

2) ____________ 5) _____________________________ 8) ________________________________________

3) ____________ 5) _____________________________ 9) ________________________________________

4) ____________ 5) _____________________________ 7) ________________________________________

1) ____________ 6) _____________________________

2) ____________ 6) _____________________________ Molecular Weight: _________________________

3) ____________ 6) _____________________________ Isentropic Exponent: _______________________ 1.4 ★

4) ____________ 6) _____________________________

1) ____________ 7) _____________________________

2) ____________ 7) _____________________________

3) ____________ 7) _____________________________

4) ____________ 7) _____________________________

Standard density/compressibility: __________________________________________________________

Volumetric Gas Compressibility and Viscosity Information


* Density at Flow: ______________________________ Units: ❑ lb/ft3 ❑ Kg/m3 ❑ Other:
OR

M.W. / Specific Gravity at Flow: _________________________________________________

Compressibility at Flow: _____________________________________________________

Compressibility at Base: ____________________________________________________

* Viscosity at Flow: _____________________________ Units: ❑ Centipoise ❑ Other: Isentropic Exponent (K):______ 1.4 ★

48
Product Data Sheet
00813-0100-4810, Rev HA
Rosemount Compact Orifice
March 2008 Flowmeter Series

49
Rosemount Compact Orifice Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series March 2008

Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale


The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount, the Rosemount logotype, ProPlate, Mass ProPlate, and Annubar are registered trademarks of Rosemount Inc.
All other marks are the property of their respective owners.

Emerson Process Management


Rosemount Inc. Emerson Process Management Emerson Process Management Asia
8200 Market Boulevard Heath Place Pacific Private Limited
Chanhassen, MN USA 55317 Bognor Regis 1 Pandan Crescent
T (US) (800) 999-9307 West Sussex PO22 9SH Singapore 128461
T (Intnl) (952) 906-8888 England T (65) 6777 8211
F (952) 949-7001 T 44 (0) 1243 863121 F (65) 6777 0947
F 44 (0) 1243 867554 Enquiries@AP.EmersonProcess.com
www.rosemount.com

¢00813-0100-4810;¤
© 2008 Rosemount Inc. All rights reserved.

You might also like