HT Cable Utp Azul Leviton
HT Cable Utp Azul Leviton
HT Cable Utp Azul Leviton
Datasheet: GD102051v19
APPLICATION
Leviton Category 6 U/UTP cables exceed Category 6 performance standards. They are rated to 250MHz and are suitable for use in
all Class E structured wiring cable systems. Category 6 U/UTP cables support Gigabit Ethernet, Power over Ethernet, voice, and
broadband video transmissions at frequencies up to 250MHz.
2.3.1.1
FEATURES AND BENEFITS
• 23 AWG solid annealed copper wire
• 4 unshielded twisted pairs cabled together
• Central separator for increased internal crosstalk performance
• HFFR-LS* jacket enables the cable to meet the requirements of the
Construction Products Regulation (CPR) EuroClass Eca
2.3.1.1
• CE and UKCA marked for CPR
• Included in the Leviton Limited 25-Year System Warranties when
used in conjunction with Leviton copper connectivity. System
warranties are available for qualified projects installed by certified
contractors
• Designed and manufactured in a carbon neutral facility in the UK
• Reel and box packaging are 100% recyclable C6U
* Halogen Free Flame Retardant – Low Smoke UTP6Z
STANDARDS
• Designed and constructed to give optimum electrical performance to the following standards:
• ISO/IEC 11801 Class E, IEC 61156-5
• EN50173-1 and EN 50288-6-1
2.3.1.1
• ANSI/TIA 568.2-D
• Supports Gigabit Ethernet
• Recommended for PoE standards:
• IEEE 802.3bt PoE Type 1 (15.4 Watts) formerly 802.3af
• IEEE 802.3bt PoE Type 2 (30 Watts) formerly 802.3at
• IEEE 802.3bt PoE Type 3 (60 Watts)
• IEEE 802.3bt PoE Type 4 (90 Watts)
• Exceeds IEEE 802.3bt standard up to 0.5 amps per conductor (100 watts) continuously
• Cisco UPoE (60 Watts)
• Cisco UPoE+ (90 Watts)
• Power over HDBaseT™ PoH (95 Watts)
REACTION TO FIRE
Material Identifier HF1
Material Description Standard HFFR-LS
Flammability Rating IEC/EN 60332-1-2
Classification / EuroClass Eca
ELECTRICAL PERFORMANCE
Frequency (MHz) 1 4 10 20 100 200 250 500 550
Insertion Loss Standard 2.0 3.8 6.0 8.5 19.8 29.0 32.8 N/A N/A
(dB/100m) Typical 1.7 3.5 5.6 8.0 18.9 27.6 31.1 43.0 45.4
Standard 75.3 66.3 60.3 55.8 45.3 40.8 39.3 N/A N/A
NEXT (dB)
Typical 91.0 91.5 86.0 80.4 69.2 64.0 64.1 46.0 45.4
Standard 72.3 63.3 57.3 52.8 42.3 37.8 36.3 N/A N/A
PSNEXT (dB)
Typical 83.7 84.2 78.0 71.9 61.9 57.3 57.0 44.0 43.4
Standard 67.8 58.0 50.0 44.0 30.0 24.0 22.0 N/A N/A
ACR-F (dB)
Typical 91.2 83.7 75.8 68.2 52.3 47.8 45.0 31.0 30.2
Standard 64.8 55.0 47.0 42.0 27.0 21.0 19.0 N/A N/A
PSACR-F (dB)
Typical 84.8 76.4 68.4 61.4 46.4 42.4 39.6 28.0 27.2
Return Loss Standard 20.0 23.0 25.0 25.0 20.1 18.0 17.3 N/A N/A
(dB) Typical 34.0 36.5 39.1 41.6 37.1 31.3 30.2 20.2 19.9
• The standard values shown are the most demanding taken from across the relevant IEC, TIA and EN specifications. These standards values are
the maximum permittable for Insertion loss and the minimum permittable for other parameters.
• N/A = Not applicable
INSTALLATION
Temperature (Installation) 0°C to +50°C Min Bend Radius (Installation) 8 x Outer Diameter
Temperature (Operation) -20°C to +75°C Min Bend Radius (Operation) 4 x Outer Diameter
Max Tensile Load (Installation) 10kg per simplex cable Field Test NVP Value 0.69
COUNTRY OF ORIGIN
COO: United Kingdom