Technical Information
Prosonic S FMU90
Ultrasonic measuring technology
Application
• Level measurement and point level measurement of liquids or bulk solids
• Flow measurement in open channels or weirs
• Measuring range up to 45 m (148 ft)
• Pump and rake control
• Optional: advanced pump control (e.g. pump function test)
• Calculation of average, difference or total
• Backwater detection or dirt detection
• Up to 3 totalizers and 3 daily counters
• Counting and time pulses to control external units
Your benefits
• Simple, menu-guided operation with 6-line plain text display, choice of 15
languages
• Envelope curves on the display for straightforward onsite diagnostics
• Easy operation, diagnostics and measuring point documentation with the free
"FieldCare" operating program
• Temperature-dependent time-of-flight correction with integrated or external
temperature sensors
• Linearization (up to 32 points, user configurable); preprogrammed and accessible
for the most common flumes and weirs
• System integration via HART or PROFIBUS DP
• Optional aluminum field housing with ATEX II 3D approval
Prosonic S FMU90
Table of contents
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Communication-specific accessories . . . . . . . . . . . . . . . . 28
Analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . 28
Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
PROFIBUS DP interface . . . . . . . . . . . . . . . . . . . . . . . . . 15
Supplementary documentation . . . . . . . . . . . . . . . 33
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . 33
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . 33
Connection data (alternating voltage) . . . . . . . . . . . . . . . 16 Description of Device Parameters . . . . . . . . . . . . . . . . . . 33
Connection data (DC voltage) . . . . . . . . . . . . . . . . . . . . 16 Slot/Index lists (PROFIBUS DP) . . . . . . . . . . . . . . . . . . . 33
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . 17
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Performance characteristics . . . . . . . . . . . . . . . . . . 18
Reference operating conditions . . . . . . . . . . . . . . . . . . . 18
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . 18
Measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Measured value resolution . . . . . . . . . . . . . . . . . . . . . . 18
Measuring frequency . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Influence of vapor pressure . . . . . . . . . . . . . . . . . . . . . . 18
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . 19
Mechanical construction . . . . . . . . . . . . . . . . . . . . 20
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2 Endress+Hauser
Prosonic S FMU90
Electrical symbols
Direct current
Alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Reference to documentation
Reference to graphic
Result of a step
1, 2, 3, ...
Item numbers
A, B, C, ...
Views
Endress+Hauser 3
Prosonic S FMU90
BD
2
100%
D
E
F
L 0%
A0034882
1 Prosonic S sensor
2 Prosonic S transmitter
BD Blocking distance
D Distance between reference point (sensor membrane) and surface of medium
E Empty distance
F Span
L Level
The sensor transmits ultrasonic pulses in the direction of the surface of the medium. There, they are
reflected back and received by the sensor. The transmitter measures the time t between the
transmission and reception of a pulse. From this time, and using the sonic velocity c, the transmitter
calculates the distance D between the reference point (sensor membrane) and the surface of the
medium:
D = c ⋅ t/2
The level L is derived from D. With linearization, the volume V or the mass M is derived from L.
4 Endress+Hauser
Prosonic S FMU90
Q
Q
A0035219
1 Prosonic S sensor
2 Prosonic S transmitter
D Distance between sensor membrane and surface of liquid
Q Flow
The sensor transmits ultrasonic pulses in the direction of the surface of the liquid. There, they are
reflected back and received by the sensor. The transmitter measures the time t between the
transmission and reception of a pulse. From this time, and using the sonic velocity c, the transmitter
calculates the distance D between the (reference point) sensor membrane and the surface of the
liquid:
D = c x t/2
The level L is derived from D. With linearization, the flow Q is derived from L.
Blocking distance Signals within the blocking distance (BD) range cannot be measured due to the transient response of
the sensor.
A B
C
(0.23)
0.4 (1.3)
0.6 (2.0)
A0036750
Endress+Hauser 5
Prosonic S FMU90
Interference echo Ensures that interference echoes (e.g. from edges, welds or internal fixtures) are not interpreted as a
suppression (mapping) level echo.
Linearization table
• Manual or semi-automatic entry
• Up to 32 "Level/volume" linearization points
Linearization table
• Up to 32 linearization points "upstream level - flow"
• Manual or semi-automatic entry
6 Endress+Hauser
Prosonic S FMU90
Endress+Hauser 7
Prosonic S FMU90
Application examples for Level measurement with point level detection and alarm generation
level measurement
Device version: FMU90 - *1***131**** (1 input, 3 relays, 1 output)
FDU9x
max
Prosonic S
max
min
L
min
L
A0034883
Prosonic S
L1 L2
L1 + L2
2
A0034884
Prosonic S
D2 M
D1
A0034885
8 Endress+Hauser
Prosonic S FMU90
Prosonic S
A0034886
Conveyor belt
Device version: FMU90 - *1***111**** (1 input, 1 output)
Prosonic S
A0034887
Endress+Hauser 9
Prosonic S FMU90
Application examples for Volume counter + time pulses (e.g. for sampler)
flow measurement
Device version: FMU90 - *2***131**** (1 input, 3 relays, 1 output)
Prosonic S
FDU9x
1 2 3 m³
D
Q
A0034888
Prosonic S
A0034889
Prosonic S
Q(l/s)
L (m)
Q (l/s)
123 m³
L
A0034890
10 Endress+Hauser
Prosonic S FMU90
Input
Sensor inputs Number of sensor inputs
1 or 2; defined in order code 060 (level input)
Connectable sensors
• FDU90 TI01469F
• FDU91 TI01470F
• FDU91F TI01471F
• FDU92 TI01472F
• FDU93 TI01473F
• FDU95 TI01474F
The connected sensor is recognized automatically.
Input for external point level Number of point level switch inputs
switches
4; to be selected in order code 090 (additional input)
Switching possibilities
External passive point level switch (NC or NO contact)
• 0: < 8 V
• 1: > 16 V
Possible applications
• Pump feedback
For devices with advanced pump control software (FMU90-*3******B*** or FMU90-
*4******B***)
• Pump tariff control
• Start/stop/reset daily counters for flow measurements
For devices with advanced pump control software (FMU90-*3******B*** or FMU90-
*4******B***)
• Min/max level detection e.g. using Liquiphant
Endress+Hauser 11
Prosonic S FMU90
Use
Sound time-of-flight correction for FDU90 and FDU91 with sensor heating
Connectable sensors
• Pt100 (3-wire or 4-wire connection)
• Omnigrad S TR61 from Endress+Hauser
A Pt100 with a 2-wire connection may not be used due to insufficient measuring accuracy.
12 Endress+Hauser
Prosonic S FMU90
Output
Analog outputs Number of analog outputs
1 or 2; to be selected in order code 080 (output)
Technical data
• Version: active current output
• Output damping: user-definable: 0 to 1 000 s
• Load: max. 600 Ω; influence negligible
• Max. ripple: USS = 200 mV at 47 to 125 Hz (measured at 500 Ω)
• Max. noise: Ueff = 2.2 mV at 0.5 to 10 kHz (measured at 500 Ω)
Output signal
Configurable:
• 4 to 20 mA with HART
• 0 to 20 mA without HART
The HART signal is superimposed on the first analog output. The second analog output does not
have a HART signal.
Response to errors
• For 4 to 20 mA setting, choice of:
• MIN: -10 % (3.6 mA)
• MAX: 110% (22 mA)
• HOLD (last current value is kept)
• User-specific value
• For 0 to 20 mA setting, choice of:
• MAX: 110 % (21.6 mA)
• HOLD (last current value is kept)
• User-specific value
Endress+Hauser 13
Prosonic S FMU90
Technical data
• Version: potential-free changeover contact, SPDT, can be inverted
• Switching capacity (DC voltage): 35 VDC, 100 W
• Switching capacity (alternating voltage): 4 A, 250 V, 1 000 VA for cosφ = 0.7
Assignable functions
• Limit value
• Inband
• Out of band
• Limit
• Counting pulse for flow counting
For devices with flow software: FMU90 - *2********** or FMU90 - *4**********
Max. count frequency: 2 Hz
Adjustable pulse length
• Time pulse
For devices with flow software: FMU90 - *2********** or FMU90 - *4**********
Max. frequency: 2 Hz
Adjustable pulse length
• Alarm/diagnostics to indicate:
• backwater
• dirt in flume
• echo loss
• Pump control
• Individually per pump, or alternating for multiple pumps
• Acc. to fixed limit value
• Acc. to pump rate
• Advanced pump control
For devices with advanced pump control: FMU90 - *3********** or FMU90 - * 4**********
• Control of standby pump
• Storm function to prevent unnecessary pump run times
• Pump function test
• Flush control to clean pump chambers
• Operating hours alarm
• Pump alarm
• Rake control (difference- or ratio-based control)
• Fieldbus relay (switch directly via the PROFIBUS DP bus)
Assigned LEDs
In the case of devices with a display module, a yellow LED is assigned to each relay
• The LED is lit when the relay is energized.
• The LED of an alarm relay is lit during normal, interference-free operation.
• The LED for a pulse relay flashes briefly at every pulse.
Response to errors
Configurable:
• HOLD (last value is kept)
• Energized
• De-energized
• Current value is used.
Switch-on delay after power failure configurable.
14 Endress+Hauser
Prosonic S FMU90
Technical data
• Profile: 3.0
• Service Access Points (SAPs): 1
• ID number: 1540 (hex) = 5440 (dec)
• GSD: EH3x1540.gsd
• Addressing: via DIP switches on the device or via software (e.g. DeviceCare/FieldCare)
• Default address: 126
• Bus termination: can be activated/deactivated by a switch in the device
• Locking: the device can be locked by hardware or software
Transmittable values
• Primary values (level or flow, depending on the device version)
• Distances
• Counters
• Temperatures
• Average / difference / total
• Relay status
• Rake control
• Pump control
Function blocks
• 10 Analog Input Blocks (AI)
• 10 Digital Input Blocks (DI)
• 10 Digital Output Blocks (DO)
Endress+Hauser 15
Prosonic S FMU90
Power supply
Connection data (alternating Device version
voltage)
Order code 050 (power supply); option A (90-253VAC)
Technical data
• Supply voltage: 90 to 253 VAC (50/60 Hz)
• Power consumption: ≤ 23 VA
• Current consumption: ≤ 100 mA at 230 VAC
Technical data
• Supply voltage: 10.5 to 32 VDC
• Power consumption: ≤ 14 W (typically 8 W)
• Current consumption: ≤ 580 mA at 24 VDC
Galvanic isolation The following terminals are galvanically isolated from one another:
• Power supply
• Sensor inputs
• Analog output 1
• Analog output 2
• Relay outputs
• Bus connection (PROFIBUS-DP)
16 Endress+Hauser
Prosonic S FMU90
Electrical connection
Cable entries Polycarbonate field housing
Precut openings on the bottom of the housing for the following cable entries:
• M20x1.5 (10 openings)
• M16x1.5 (5 openings)
• M25x1.5 (1 opening)
Endress+Hauser 17
Prosonic S FMU90
Performance characteristics
Reference operating • Temperature: +24 °C (+75 °F)±5 °C (±9 °F)
conditions • Pressure: 960 mbar (14 psi) ±100 mbar (±1.45 psi)
• Humidity: 60 % r.F. ±15 % r.F.
• Surface of medium: ideally a reflecting surface (e.g. calm, even liquid surface of 1 m2 (10.76 ft2)
• Sensor alignment: vertically to surface of medium
• No interference echoes in the signal beam
• Parameter settings:
• Tank shape = flat ceiling
• Medium property = liquid
• Measuring conditions = calm surface
Maximum measured error Determined under reference operating conditions according to EN 61298-2:
±0.2 % in relation to the maximum sensor span
Measured error Determined under reference operating conditions; includes linearity, reproducibility and hysteresis:
±2 mm (±0.08 in) + 0.17 % of the measured distance
18 Endress+Hauser
Prosonic S FMU90
Environment
Ambient temperature –40 to 60 °C (–40 to 140 °F)
• The functionality of the LCD display becomes limited at TA < –20 °C (–4 °F).
• If the device is operated outdoors in strong sunlight, use a protective cover.
Electromagnetic Electromagnetic compatibility in accordance with all of the relevant requirements outlined in the EN
compatibility (EMC) 61326 series and NAMUR Recommendation EMC (NE 21). For details, refer to the Declaration of
Conformity.
With regard to interference emission, the device meets the requirements of class A, and is only
designed for use in an "industrial environment".
Endress+Hauser 19
Prosonic S FMU90
Mechanical construction
Dimensions Dimensions of polycarbonate field housing
15 (0.59)
A B
14
15 7
13 (0.51)
ø6.5 (0.26) 1 (5.
(5 7 9)
.94
)
180 (7.09)
170 (6.69)
192 (7.56)
80 )
15
(3.
5 )
97 ) (8.
82 16
(3. 2
2)
( 4.9
1 25 C
Mount the housing bracket on a level surface so that it cannot become warped or bent.
Otherwise it may be difficult or impossible to mount the polycarbonate field housing.
20 Endress+Hauser
Prosonic S FMU90
18 180 (7.09)
1(
7.1
3)
202 (7.95)
180 (7.09)
3 )
9.1
2( "7 (0.28)
23
"11 (0.43)
A0033258
Endress+Hauser 21
Prosonic S FMU90
Σ=0 Σ = 1...3
43 (1.69)
43 (1.69)
35 (1.38)
35 (1.38)
104 (4.09)
104 (4.09)
14 14 )
3( ) 3 (5. 5.91
EN 60715 5.6
(3.62 EN 60715 6 3) 0(
TH 35x7.5/15 3)
92 TH 35x7.5/15 15
(1.4x0.3/0.6) (1.4x0.3/0.6)
Σ=4
43 (1.69)
35 (1.38)
104 (4.09)
9)
14 8.1
EN 60715 3(
5.6 8(
TH 35x7.5/15 3) 20
(1.4x0.3/0.6)
A0035915
22 Endress+Hauser
Prosonic S FMU90
92 min 11
(3.62) (0.43)
40 7)
(1.5
10 max 6
96 9
(3.78) 0 .3 (0.24)
A0032560
5 Dimensions of remote display and operating module for cabinet door installation. Unit of
measurement mm (in)
2 5 3
6 7 4
A0034920
Endress+Hauser 23
Prosonic S FMU90
1 2 3
9 8 7 6
A0033634
24 Endress+Hauser
Prosonic S FMU90
Operability
HART operation methods
3
1
2 4
7 6 5
A0034891
Operation method,
4
PROFIBUS DP
...
2
3
5
T T
1 6
9 8 7
A0034892
Endress+Hauser 25
Prosonic S FMU90
6
5
1
4
1
2 2
3
3 4
A0034921
Locking operation
• Via the lock switch in the terminal compartment
• Via a key combination at the operating module
• By entering a locking code via the software (e.g. "FieldCare")
26 Endress+Hauser
Prosonic S FMU90
CE mark The measuring system meets the legal requirements of the applicable EU Directives. These are listed
in the corresponding EU Declaration of Conformity along with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
RoHS The measuring system is not compliant with the substance restrictions of the Restriction on
Hazardous Substances Directive 2011/65/EU (RoHS 2).
RCM-Tick marking The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.
A0029561
EAC conformity The measuring system meets the legal requirements of the applicable EAC guidelines. These are
listed in the corresponding EAC Declaration of Conformity along with the standards applied. Endress
+Hauser confirms successful testing of the device by affixing to it the EAC mark.
Ordering information
Ordering information Detailed ordering information is available for your nearest sales organization
www.addresses.endress.com or in the Product Configurator under www.endress.com :
1. Click Corporate
2. Select the country
3. Click Products
4. Select the product using the filters and search field
5. Open the product page
Endress+Hauser 27
Prosonic S FMU90
The Configuration button to the right of the product image opens the Product Configurator.
Accessories
Communication-specific Commubox FXA195 HART
accessories
• For intrinsically safe HART communication with FieldCare or DeviceCare via the USB interface
• Additional information: Technical Information TI00404F
Commubox FXA291
• Connects the CDI interface (Common Data Interface) of Endress+Hauser devices with the USB port
of a computer.
• Order number: 51516983
• Additional information: Technical Information TI00405C
.64)
194 (7 278 (1
0.9)
227 (8.94)
A0034922
10 Weather protection cover for polycarbonate field housing. Unit of measurement mm (in)
28 Endress+Hauser
Prosonic S FMU90
A0034923
3.2 (0.13)
60 (2.36)
ø33.7 (1.3)
4 (0.16)
700 (27.6)
20 (0.8)
100 (3.94)
13 (0.5)
(2.99)
76
45 (1.77)
200 (7.87)
6.5 (0.3)
(3.94)
100
55 (2.17)
25 (0.98)
75 (2.95)
109 (4.29)
100
130 (5.12) (3.94)
150 (5.91)
A0037799
Weight:
4.0 kg (8.82 lb)
Material
316L (1.4404)
Endress+Hauser 29
Prosonic S FMU90
Order number
71452327
3.2 (0.13)
60 (2.36)
ø33.7 (1.3)
1400 (55.1)
20 (0.8) 4 (0.16)
100 (3.94)
13 (0.5)
(2.99)
76
45 (1.77)
200 (7.87)
6.5 (0.3)
(3.94)
100
55 (2.17)
25 (0.98)
75 (2.95)
109 (4.29)
100
130 (5.12) (3.94)
150 (5.91)
A0037800
Weight:
6.0 kg (13.23 lb)
Material
316L (1.4404)
Order number
71452326
A0035916
30 Endress+Hauser
Prosonic S FMU90
To mount the remote display of the Prosonic S FMU9x in the housing of the larger remote display of
the FMU86x predecessor
• Dimensions: 144 x 144 mm (5.7 x 5.7 in)
• Material: 304 (1.4301)
• Order number: 52027441
Endress+Hauser 31
Prosonic S FMU90
125 (4.92)
20.5 (0.8)
115 (4.53)
28 (1.1)
78 (3.01)
E
L
!D
A0035035
32 Endress+Hauser
Prosonic S FMU90
Supplementary documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• The W@M Device Viewer: enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: enter the serial number from the nameplate or scan the
2-D matrix code (QR code) on the nameplate.
Endress+Hauser 33
*71526735*
71526735
www.addresses.endress.com