Dwyer MSX-W12
Dwyer MSX-W12
Dwyer MSX-W12
Unit: CFM
Range: 15000 CFM Max
Unidirectional
4-20 mA current output
7 = ON
8 = OFF
Wiring for:
2-wire 4-20 mA current
output
CALIBRATION
The transmitter security feature must be unlocked before calibration is accessible. See
Section Program Menu-Menu Access Security. There is a 3 second delay from the
time the zero or span calibration buttons are released until the time that the change
in calibration takes place. This delay is used to prevent stress related offsets on the
lower ranges.
Zero Calibration
The zero calibration can be set by applying zero pressure to both of the pressure ports
and pressing the zero button for 3 seconds. If the LCD display is present, the display
will read ZERO and then sequence back to the home display.
Span Calibration
The span calibration function allows the pressure value to be adjusted so that the
currently applied pressure is the maximum configured pressure. This will in turn set
the maximum analog output at the set pressure. It is recommended that the ZERO
function be applied before performing a span. Apply the maximum desired pressure
to the device, press and hold span for 3 seconds. If the LCD display is present, SPAN
is displayed. The span function will be processed 3 seconds after the span button is
released.
LCD DISPLAY MAINTENANCE/REPAIR
The LCD comes with a housing cover, which contains a window. The display plugs Upon final installation of the Series MSX, no routine maintenance is required. The
into the pins on top of the circuit board. The LCD is 180° rotatable so that it will read Series MSX is not field serviceable and should be returned if repair is needed. Field
properly if the device must be mounted with the connections facing up. repair should not be attempted and may void warranty.
The following error messages will appear if an LCD is present and the device is an This symbol indicates waste electrical products should not be disposed
error state. of with household waste. Please recycle where facilities exist. Check with
your Local Authority or retailer for recycling advice.
LCD Error Messages
Error Code Message
OVER The applied pressure is 3% greater than the selected output high WARRANTY/RETURN
value causing an Over Range Error. Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact
UNDR The applied pressure is 1% less than the selected output low value customer service to receive a Return Materials Authorization (RMA) number before
causing an Under Range Error. shipping the product back for repair. Be sure to include a brief description of the
FAIL When the span button is pressed, the pressure value is out of the problem plus any additional application notes.
range to allow a correct setting.
ER 1 The pressure applied to the sensor is beyond its ability to read.
ER 2 The pressure sensor is communicating but reporting an internal error.
ER 3 The pressure sensor is not communicating.
ER 4 The stored user settings are invalid.
ER 5 The stored factory settings are invalid.
ER 6 Non-volatile user memory has failed.
ER 7 Non-volatile factory memory has failed.
PROGRAM MENU
Home Menu
During normal operation, the display will be in the Home Menu and will display the
current measured pressure and the engineering units.
DISPLAY ALL
SEGMENTS
HOME
SCREEN
FIRMWARE VERSION
(MAY VARY)
HOME SCREEN
(MODE = PRESSURE) HOME
SCREEN
VELOCITY
MENU
PRESSURE MENU
(OUTPUT LOW MENU)
PRESSURE MENU
(OUTPUT HIGH MENU)
PRESSURE MENU
(ALARM LOW)
PRESSURE MENU
(ALARM HIGH)
RESET MENU
S S
HOME
SCREEN POWER ON
(RESET)
MSX VELOCITY SETTINGS FLOWCHART
MENU LEGEND
PRESS ZERO/VALUE BUTTON HOLD ZERO/VALUE BUTTON
PRESS SPAN/DIGIT BUTTON HOLD SPAN/DIGIT BUTTON
PRESS EITHER ZERO/VALUE HOLD BOTH ZERO/VALUE
OR SPAN/DIGIT BUTTON AND SPAN/DIGIT BUTTON
VELOCITY
MENU
VELOCITY MENU
(OUTPUT LOW MENU)
VELOCITY MENU
(OUTPUT HIGH MENU)
RESET MENU
HOME POWER ON
SCREEN (RESET)
FLOW
MENU
FLOW MENU
(AREA)
FLOW MENU
(OUTPUT LOW MENU)
FLOW MENU
(OUTPUT HIGH MENU)
RESET MENU
HOME POWER ON
SCREEN (RESET)