Nothing Special   »   [go: up one dir, main page]

IMG - 0171 PSME Code 2008 162b

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

AND AIRGONDITIONING

CHAPTER 8 - HEATING, VENTILATTNG, REFRIGERATION


discharge capacity determined by test wiEt
c. Refrigerant containing vessels which are not
the outlet open to the atmosphere and with
a pai of equipment listed by a recognized
a differential pressure across the restraining
engineering 'testing laboratory having a
member equalto twice the marked pressure
foli6w-up inspection service shall be
setting of the pressure relief valve'
constructed in accordance with the rules of
Chapter 7 (Unifled Pressure Vessel)' of
b. The rated discharge capacity rupture
members and discharge piping shall be as
d. Every systems, except as ptovided in given in Table 8.6'
Sections'10,V.d., 11.A and 11'B, shall be
protected by a pressure relief device unless
so constructed that pressure due to fire 11.7 Required CaPacitY
conditions will be relieved safely by soldered
joints, lead gaskets, fusible plugs, or their a. The minimum required rated discharge
capacity of pressure relief device for a
Parts of the sYstem. refrigerlnt containing vessels shall be
deteimined by the following formula:
Section 11.0 Pressure Relief Devices
C=fDL
11.1 Each pressure vessel containing liquid
may be shut off by valves
refrigerant and which
Where C = Minimum required rated
from all other parts of a refligerating system' discharge capacity oT the relief device in kg of
shall be protected by an approved pressure air per minute.
relief valve in parallel with a rupture member or
a second appioved pressure relief"valves if its D = Outside diameter of the vessel
gross volume exceeds 0.142 m" unless its in mm.
diameter does not exceed 152 mm'
L- Length of the vessel in mm'
11.2 Each pressure vessel having a gross volume of
0.142 mt or less, containing liquid refrigerant f - Factor dePendent uPon kind of
and which may be shut off by valves from all refrigerant as follows:
other parts of a refrigerating system, shall be
protecied by an approved pressure relief device Refrigerant Value of "f'
Kind of
or an aPProved fusible Plug.
Ammonia(NH3) 0'041
Dichlorodifluoromethane,(R-12,R'22) 0'1 63
11.3 The requirements of Section 10'Vd and 1'1
R-134a, R500
shall noi apply to-iflooded evaporators located in
a refrigerator c*a binet.
11.8 Pressure Setting Test
11.4 Each pressure vessel shall have the Design a. The pressure setting of relief devices for
Working Pressure stamped thereon if its gross refrigerant containing vessels shall be tested
volume exceeds 0.1 42 m" -
with the outlet open to the atmosphere and
the relief device shall function at a pressure
11.5 Compressors operating above 103'35 kPa not more than ten (10) percent above the
qauqe and having a displacement exceeding pressure marked thereon, if such marking is
I.gi ,t per minute shall be equipped by the- bAg tpa or more, qr at not more than 6839
manufacturer with a pressure relief device of kPa above the pressure marked thereon' if
adequate size to prevent rupture of the such marking is less than 689 kPa'
compressor, located between the compressor
and stop valve on the discharge side' The 11.9 Marking
discharge from such relief device may be vented
to the atmosphere or into the low pressure side a. All pressure relief valves for refrigerant
of the sYstems' containing vessels shall be set and sealed
by the minufacturer. The name or trade of
11.6 CaPacitY Rating the manufacturer, the pressure setting
expressed in kPa, the rated discharge
a. The rated discharge capacity of a pressure capacity expressed in kilogram of a.ir per
relief valve, expressed in points of air per minute, and the minimum equivalent length
minute shall be one-fifth (1/5) of its

164

You might also like