Electric Expansion Valve


Type SEH-P
Page 2 – Bulletin 100-20-5

SEH-P ELECTRIC EXPANSION VALVE


Sporlan is pleased to introduce the SEH-P, the newest
addition to the family of large Electric Expansion Valves,
and the largest valve approved for air-cooled R-410A
applications. Featuring a straight through configuration,
this EEV provides an alternative to the existing angle 5.61”
(1.43 mm)
configuration of the SEHI-400. Contact your local Sales
Engineer for assistance with sizing a Sporlan EEV for your 0.91”
(23 mm) 1.813” (46 mm) HEX
application, or selecting a suitable controller to optimize
your system’s performance.
‘A’

FITTINGS ‘A’ FLOW

11X11 ODF 9.88”(251 mm)


11X13 ODF 9.88”(251 mm) 1.90” 2.18”
(48 mm) (55 mm)
11X17 ODF 10.25”(260 mm)
13X13 ODF 9.88”(251 mm)
13X17 ODF 10.25”(260 mm)
Dimensions in inches (mm)

SPECIFICATIONS
Motor Type Permanent magnet bipolar internal (wet) motor
Compatible Refrigerant All common HCFC and HFC refrigerants, including R-410A
Compatible Oil All common mineral, polyester and alkylbenzene oils
Supply Voltage 12 volts DC +/-10%
Cable Type Hermetic (20’ Standard)
Phase Resistance 75 ohms +/-10%
Stepping Current 160 mA/winding
Holding Current Not recommended
Number of Steps 6386 Full Steps
200/second (L/R)
Step Rate
400/second recommended (properly configured current chopper)
Full Stroke Transit Time 32/16 seconds (Voltage/Current)
Initialization 7500 steps closing
Recommend one 10% overdrive closed per day
Overdriving
(overdriving open not permitted)
MRP / MWP 620 psig (43 bar)
MOPD 450 psid (31 bar)
Max Internal Leakage 100 cc/min @ 100 psid (6.9 bar) dry air (forward flow only)
Max External Leakage .10 oz/yr at 300 psig (2.8 gram/yr @ 20 bar)
Fluid Temperature Range -50°F to 155°F (-40°C to 68°C)
Ambient Temperature Range -50°F to 140°F (-40°C to 60°C)
Installation Maximum Temperature 250°F (121°C) for 15 minutes
Relative Humidity 0-100% (Condensing)
Materials of Construction Brass, copper, stainless steel, synthetic seals
Bulletin 100-20-5 – Page 3

FULL STROKE CAPACITIES - TONS (AT EVAPORATOR TEMPERATURE °F)


Capacity is calculated at full stroke, with no reserve capacity. Valve should be selected with consideration given to entire range of potential system conditions.

R-134a
40°F 20°F 0°F
REFRIGERANT Pressure Drop Across Valve (psid)
40 60 80 100 120 140 160 180 40 60 80 100 120 140 160 180 40 60 80 100 120 140 160 180
R-134a 197 241 278 311 340 368 393 417 187 230 265 296 325 351 375 398 178 218 252 282 308 333 356 378

R-410A
40°F 20°F 0°F
REFRIGERANT Pressure Drop Across Valve (psid)
80 120 160 200 240 280 320 360 80 120 160 200 240 280 320 360 80 120 160 200 240 280 320 360
R-410A 282 345 399 446 488 528 564 598 275 337 389 435 477 515 550 584 267 327 378 423 463 500 535 567

-20°F -40°F
REFRIGERANT Pressure Drop Across Valve (psid)
80 120 160 200 240 280 320 360 80 120 160 200 240 280 320 360
R-410A 258 316 365 408 447 483 516 548 249 305 352 394 431 466 498 528

R-22, R-404A, R-407A, R-407C, R-422D, R-507


40°F 20°F 0°F
REFRIGERANT Pressure Drop Across Valve (psid)
75 100 125 150 175 200 225 250 75 100 125 150 175 200 225 250 75 100 125 150 175 200 225 250
R-22 288 333 372 408 440 471 499 526 281 325 363 398 429 459 487 513 273 315 353 386 417 446 473 499
R-404A 191 221 247 270 292 312 331 349 181 209 234 256 277 296 314 331 170 196 220 240 260 278 295 310
R-407A 269 311 348 381 412 440 467 492 257 297 332 364 393 420 445 470 244 282 315 346 373 399 423 446
R-407C 266 307 343 375 406 434 460 485 255 294 329 360 389 416 441 465 243 281 314 344 371 397 421 444
R-422D 196 227 253 278 300 320 340 358 185 214 239 262 283 303 321 338 174 201 225 246 266 284 301 318
R-507 187 216 241 264 286 305 324 341 177 204 228 250 270 289 307 323 167 193 215 236 255 272 289 305

-20°F -40°F
REFRIGERANT Pressure Drop Across Valve (psid)
75 100 125 150 175 200 225 250 75 100 125 150 175 200 225 250
R-22 264 305 341 374 404 432 458 483 255 294 329 360 389 416 441 465
R-404A 159 184 205 225 243 260 276 290 147 170 190 208 225 240 255 268
R-407A 231 267 299 327 353 378 401 422 – – – – – – – –
R-407C 232 267 299 328 354 378 401 423 – – – – – – – –
R-422D 163 188 210 230 249 266 282 297 – – – – – – – –
R-507 156 180 201 220 238 254 270 284 145 167 187 205 221 236 251 264

FULL STROKE CAPACITIES - kW (AT EVAPORATOR TEMPERATURE °C)


Capacity is calculated at full stroke, with no reserve capacity. Valve should be selected with consideration given to entire range of potential system conditions.

R-134a
5°C -10°C -20°C
REFRIGERANT Pressure Drop Across Valve (bar)
2.5 4 5.5 7 8.5 10 11.5 13 2.5 4 5.5 7 8.5 10 11.5 13 2.5 4 5.5 7 8.5 10 11.5 13
R-134a 657 831 975 1100 1212 1315 1410 1499 616 779 914 1031 1136 1232 1322 1405 588 743 872 983 1084 1175 1260 1340

R-410A
5°C -10°C -20°C
REFRIGERANT Pressure Drop Across Valve (bar)
5 8 11 14 17 20 23 26 5 8 11 14 17 20 23 26 5 8 11 14 17 20 23 26
R-410A 944 1194 1400 1579 1740 1888 2024 2152 912 1153 1353 1526 1681 1824 1956 2079 888 1123 1317 1486 1637 1776 1904 2024

-30°C -40°C
REFRIGERANT Pressure Drop Across Valve (bar)
5 8 11 14 17 20 23 26 5 8 11 14 17 20 23 26
R-410A 861 1089 1277 1441 1588 1722 1847 1963 832 1052 1234 1392 1534 1663 1784 1897
Page 4 – Bulletin 100-20-5

FULL STROKE CAPACITIES - kW (AT EVAPORATOR TEMPERATURE °C)


Capacity is calculated at full stroke, with no reserve capacity. Valve should be selected with consideration given to entire range of potential system conditions.

R-22, R-404A, R-407A, R-407C, R-422D, R-507


5°C -10°C -20°C
REFRIGERANT Pressure Drop Across Valve (bar)
4 6 8 10 12 14 16 18 4 6 8 10 12 14 16 18 4 6 8 10 12 14 16 18
R-22 891 1092 1261 1409 1544 1668 1783 1891 860 1053 1216 1359 1489 1608 1719 1824 836 1024 1183 1322 1449 1565 1673 1774
R-404A 589 721 833 931 1020 1102 1178 1250 547 670 774 865 948 1024 1095 1161 517 633 731 817 895 967 1034 1096
R-407A 834 1021 1179 1319 1444 1560 1668 1769 783 959 1107 1238 1356 1465 1566 1661 746 914 1055 1180 1293 1396 1493 1583
R-407C 819 1003 1158 1295 1419 1532 1638 1738 773 946 1093 1221 1338 1445 1545 1639 740 906 1046 1170 1281 1384 1479 1569
R-422D 606 742 857 958 1050 1134 1212 1286 562 688 794 888 973 1051 1124 1192 530 649 749 837 917 991 1059 1123
R-507 577 706 815 912 999 1079 1153 1223 534 655 756 845 926 1000 1069 1134 506 620 716 800 877 947 1012 1074

-30°C -40°C
REFRIGERANT Pressure Drop Across Valve (bar)
4 6 8 10 12 14 16 18 4 6 8 10 12 14 16 18
R-22 814 997 1151 1287 1409 1522 1627 1726 787 963 1112 1244 1362 1471 1573 1669
R-404A 483 592 683 764 837 904 966 1025 451 553 638 713 782 844 902 957
R-407A 710 869 1004 1122 1229 1328 1420 1506 – – – – – – – –
R-407C 709 868 1002 1120 1227 1326 1417 1503 – – – – – – – –
R-422D 498 610 705 788 863 932 997 1057 – – – – – – – –
R-507 476 583 673 753 824 890 952 1010 445 545 629 703 770 832 889 943

Liquid Temperature Correction Factors


°F 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
°C -18 -12 -7 -1 4 10 16 21 27 32 38 43 49 54 60
R-22 1.56 1.51 1.45 1.40 1.34 1.29 1.23 1.17 1.12 1.06 1.00 0.94 0.88 0.82 0.76
R-134a 1.70 1.63 1.56 1.49 1.42 1.36 1.29 1.21 1.14 1.07 1.00 0.93 0.85 0.78 0.71
R-404A 2.04 1.94 1.84 1.74 1.64 1.54 1.43 1.33 1.22 1.11 1.00 0.89 0.77 0.65 0.53
R-407A 1.76 1.68 1.61 1.53 1.46 1.39 1.31 1.24 1.16 1.08 1.00 0.92 0.83 0.74 0.64
R-407C 1.69 1.62 1.55 1.49 1.42 1.35 1.28 1.21 1.14 1.07 1.00 0.93 0.85 0.77 0.69
R-410A 1.79 1.71 1.63 1.55 1.47 1.40 1.32 1.24 1.16 1.08 1.00 0.92 0.83 0.73 0.62
R-507 1.99 1.89 1.79 1.69 1.59 1.50 1.40 1.30 1.20 1.10 1.00 0.89 0.78 0.66 0.51
R-422D 1.99 1.90 1.80 1.70 1.60 1.50 1.41 1.31 1.20 1.10 1.00 0.90 0.79 0.68 0.57

⚠WARNING – USER RESPONSIBILITY


Failure or improper selection or improper use of the products described herein or related items can cause death, personal injury and property damage.
This document and other information from Parker Hannifin Corporation, its subsidiaries and authorized distributors provide product or system options for further
investigation by users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the final selection of the system and components and assuring that all performance,
endurance, maintenance, safety and warning requirements of the application are met. The user must analyze all aspects of the application, follow applicable industry
standards, and follow the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or
authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specifications provided by the user,
the user is responsible for determining that such data and specifications are suitable and sufficient for all applications and reasonably foreseeable uses of the
components or systems.
For safety information see the Safety Guide at www.parker.com/safety or call 1-800-CParker.

OFFER OF SALE
The items described in this document are hereby offered for sale by Parker Hannifin Corporation, its subsidiaries or its authorized distributors. This offer and its
acceptance are governed by the provisions stated in the detailed “Offer of Sale” available at www.parker.com.

FOR USE ON AIR CONDITIONING and REFRIGERATION SYSTEMS ONLY

© 2013 Parker Hannifin Corporation Bulletin 100-20-5 / 42013