PDV/0538 /2022

To : PT. Sinarmonas Industries

Schedule of Technical Data

Date 31-Mar-22 Rev. 0


FOR APPROVAL
Prepared

Budi Darmawan
Engineer

Checked

Anggono
Supervisior

Approved

Praptono Hadi Prasetyo


Manager
2YSLCY IEC 60228, IEC 60502-1
Schedule of Technical Data
0.6/1 (1.2) kV IEC 60332-1

1 1. Conductor : Plain Annealed Copper wire class 5


2. Insulation : Extruded PE

2 3. Filler* : Polypropylene Yarn


4. Overall Screen ( OS ) : Helically Overlapped Polyester Tape

3 Helically overlapped single coated aluminium tape


Tinned Copper Wire Braided
4 5. Outer Sheath : Extruded PVC (Black Colour)
* For Size 16 mm² and above with Polypropylene Yarn
5
Core identification :
- 4 Cores : Brown, Black, Grey, Blue

Marking by Ink Jet Printing :


e.g. IEC 60502 JEMBO CABLE 2YSLCY 4 x 4 mm² 0.6/1 kV "Year" "Length Marking"
Length Marking by Ink Jet Printing with interval every 1 meter

CONSTRUCTION
Conductor Insulation TCWB Outer Sheath Approx. Approx.
Standard
Item Number Nominal Size No of Shape Approx. Min. Nom. Nom. Nom. OD Cable Length per
drum/coil
wire dia. Thickness Coverage Thickness of Cable Weight

sqmm - - mm mm % mm mm kg/km m

AN2YSLCY004205FI 4 x 2,5 56 f 1,98 0,53 0,7 80 1,8 13,3 294 1000

AN2YSLCY004004FI 4x4 80 f 2,37 0,53 0,7 80 1,8 14,3 356 1000

AN2YSLCY004006FI 4x6 128 f 3,04 0,53 0,7 80 1,8 16,0 470 1000

AN2YSLCY004010FI 4 x 10 80 f 3,98 0,53 0,7 80 1,8 18,2 669 1000

AN2YSLCY004016FI 4 x 16 126 f 5,29 0,53 0,7 80 1,8 21,7 889 1000

AN2YSLCY004070FI 4 x 70 360 f 11,29 0,89 1,1 80 2,0 38,99 3.329 1000

AN2YSLCY004120FI 4 x 120 608 f 14,68 0,98 1,2 80 2,3 48,30 5.325 500

AN2YSLCY004185FI 4 x 185 925 f 18,10 1,34 1,6 80 2,6 59,1 7.952 300

AN2YSLCY004240FI 4 x 240 1221 f 20,80 1,43 1,7 80 2,8 66,9 10.479 300

f : Class 5 Round Bunched


- Tolerance of overall diameter : OD ≤ 20 mm : ± 1.0 mm, OD ≤ 40 mm : ± 2 mm, OD > 40 mm : ± 5%

CHARACTERISTICS

Max. DC Short Circuit AC


Min. Insulation Current Carrying Capacity at 30ºC
Conductor
Item Number Nominal Size Resistance at Current at Voltage
Resistance at
20°C
20°C In Ground In Air 1 sec. test

sqmm Ohm/km M.Ohm.km A A kA kV / 5 min.

AN2YSLCY004205FI 4 x 2,5 7,98 2.100 28 32 0,31 3,5

AN2YSLCY004004FI 4x4 4,95 1.800 36 42 0,50 3,5

AN2YSLCY004006FI 4x6 3,3 1.500 46 54 0,75 3,5

AN2YSLCY004010FI 4 x 10 1,91 1.200 60 75 1,30 3,5

AN2YSLCY004016FI 4 x 16 1,21 1.100 78 100 2,05 3,5

AN2YSLCY004070FI 4 x 70 0,272 900 175 246 9,12 3,5

AN2YSLCY004120FI 4 x 120 0,161 800 239 346 15,40 3,5

AN2YSLCY004185FI 4 x 185 0,106 800 301 456 23,40 3,5

AN2YSLCY004240FI 4 x 240 0,0801 700 349 538 30,96 3,5


- Minimum bending radius:
- Installed : 12 x OD
- Standard packing : wooden drum