Nothing Special   »   [go: up one dir, main page]

Tap Position Display Type REG-F 'BCD B4': Technical Data

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Technical Data REG-F_BCD_version_B4_b_English

Tap Position Display


F1
Type REG-F 'BCD B4'
The tap positon display REG-F 'BCD' shows the BCD coded
output signal of a tap position interface or from the dry contact
row of a tap changer transformer with BCD output.
An external DC voltage U+ on the inputs 'EBCD1 ...EBCD80'
with reference to 'E GND' will be displayed.
REG-F ´D1 B4´
The build in power supply unit delivers the internal voltages. 96x48x122mm

 8 BCD inputs for range 0 ... 99 Code table


 2 digit display with bright red digits in 20mm size Eingang: Anzeige
BCD Code BCD
 Large auxiliary voltage range of the power supply
80 40 20 10 8 4 2 1
Technical specifications 0 0 0 0 0 0 0 0 0
Regulations and standards 0 0 0 0 0 0 0 u+ 1
IEC1010, IEC801-1 to 6, VDE0110, VDE0160 0 0 0 0 0 0 u+ 0 2
Interference immunity EN50082-2 0 0 0 0 0 0 u+ u+ 3
Emitted interference EN50081-2, EN55011
0 0 0 u+ 0 u+ u+ u+ 17
Mechanical data
0 u+ u+ u+ u+ 0 0 0 78
Construction Panel mounted housing DIN43700
0 = EGND
96x48x122 mm (WxHxD)
material UV94V-1
Safety
Connector 1 pieces; 'F1': 12poles, 0.5..1.5 mm²
Safety class / overvoltage category I/II
Degree of protection IP40
Contamination level 2
Weight inclusive 1 connector < 0.4 kg
Test voltage AC 2.3 kV
Mounting within cutout 92.5x44 mm
Auxiliary voltage inputs EBCD1 .80, EGND
Input to PE
External voltage U+ on EBCD1...80, reference to E GND
Input resistance (Ri) ~120 kΩ Power supply
Galvanically Feature H1 AC 100 … 240 V / DC 100 … 353V
EBCD 'ON' 12 .. 150V DC (feature E4) isolated Feature H2 AC 20 … 60 V / DC 20 ... 72V
EBCD 'OFF' <3 VDC Power consumption < 6 VA / 6 W H1; 1 A/T H2; 2 A/T
Ripple voltage < 2 V, 50Hz Temperature Operation 0 ... +55 °C
Storage, transport -25 ... +75 °C
EBCD 'ON' 50.. 250V DC (feature E3)
EBCD 'OFF' <10 VDC Contact assignment
connector 'F1'
EBCD 'ON' 50.. 250V AC / DC (feature E31) 12pol.
EBCD 'OFF' <10 VDC 1 L(+)
2 N (-)
3 PE
EBCD 'ON' 180.. 250V DC (feature E39)
4 E GND
EBCD 'OFF' <100 VDC
5 EBCD 80
6 EBCD 40 (sign -)
Variant with sign (-) (feature A2) 7 EBCD 20
Display from -39 … -0 … 39 8 EBCD 10
Sign (-) at pin 6 of F1 connector (EBCD 40) 9 EBCD 8
EBCD 80 is then inactive 10 EBCD 4
11 EBCD 2
12 EBCD 1

Features Code
Tap Position Display REG-F BCD B4 panel case 96 x 48 REG-F D1 B4
Auxiliary voltage AC 100..240 V / DC 100…353 V H1
galvanically isolated AC 20... 60 V / DC 20 ... 72 V H2 V-ON V-OFF
Input voltage U+ DC 12 … 150 V E4 ≥ 12 V <3V
on EBCD1 … 80 DC 50 … 250 V E3 ≥ 50 V < 10 V
AC / DC 50 … 250 V E31 ≥ 50 V < 10 V
DC 180 … 250 V E39 ≥ 180 V < 100 V
Display range 0 … 99 A4
Display range with sign (-) -39 … -0 … 39 A2

Issue 01/2019 Page 1


We take care of it.

Application REG-F ´BCD B4´ REG-F ´BCD´ BCD - display REG-D / DA

feature B4 panel case 96 x 48mm V 2b BCD 1 input HV


D1 BCD - input code V 4b 2 (50...250V)
H1 power supply AC 230V
E4 input 6xBCD V 6b 4
external voltage U+ V 8b 8
DC 12 ... 150V
V 10b 10
V 12b 20
BCD V 2z,4z GND
Trafo tap changer BCD
BCD-Code "15" tap display
cable length l
BCD1 F1/12 EBCD1 V 24b BCD 1 input LV
BCD2 F1/11 EBCD2 V 26b 2 (12 ... 50V)

BCD4 F1/10 EBCD4 V 28b 4


BCD8 F1/9 EBCD8 V 30b 8
BCD10 F1/8 EBCD10 V 24z 10
BCD20 F1/7 EBCD20 V 26z 20
GND F1/4 E GND V 32b/32z GND
U+

GND

U+

cable lenght l, AWG U+ / GND external N(-) L(+)


PE
< 100m 18AWG (0,8mm²) 12 ... 150V DC for REG-D with LV input; F1/3 F1/2 F1/1
< 40m 24AWG (0,5mm²) REG-D with HV iput (pinning not equal to LV) 19" rack
U+ external 50 ... 250V DC

A. Eberle GmbH & Co. KG Tel.: +49 (0) 911/ 62 81 08-0 http://www.a-eberle.de
Frankenstr. 160 D-90461 Nürnberg Fax.: +49 (0) 911/ 62 81 08-99 E-mail: info@a-eberle.de
Änderungen ohne Vorankündigung vorbehalten. Page 2